EDHK011026

- Cooling Only J-Series

EDHK011026

Split-System
Room Air Conditioners
J-Series
Cooling Only
1.
2.
3.
4.

FTN50JV18
FTN60JV18

RN50JV1
RN60JV1

Power Supply ..........................................................................................2


Functions.................................................................................................3
Specifications ..........................................................................................4
Dimensions .............................................................................................5
4.1 Indoor Unit................................................................................................5
4.2 Outdoor Unit .............................................................................................6

5. Wiring Diagrams......................................................................................7
5.1 Indoor Unit................................................................................................7
5.2 Outdoor Unit .............................................................................................8

6. Piping Diagrams......................................................................................9
6.1 Indoor Unit................................................................................................9
6.2 Outdoor Unit .............................................................................................9

7. Capacity Tables ....................................................................................10


7.1 Cooling Only...........................................................................................10
7.2 Capacity Correction Factor by the Length of Refrigerant Piping
(Reference) ............................................................................................11

8. Operation Limit......................................................................................12
9. Sound Level ..........................................................................................13
9.1 Measuring Location ................................................................................13
9.2 Octave Band Level .................................................................................14

10.Electric Characteristics..........................................................................15
11.Installation Manual ................................................................................16
11.1 Safety Precautions .................................................................................16
11.2 50 Class .................................................................................................17
11.3 60 Class .................................................................................................26

12.Operation Manual..................................................................................35
13.Optional Accessories ............................................................................56
13.1 Option List ..............................................................................................56
13.2 Installation Manual .................................................................................57

Room Air Conditioners J-Series

Power Supply

EDHK011026

1. Power Supply

Note:

Indoor Units

Outdoor Units

FTN50JV18

RN50JV1

FTN60JV18

RN60JV1

Power Supply
1 , 220 - 230 - 240 V, 50 Hz

Power Supply Intake ; Outdoor Unit

Room Air Conditioners J-Series

EDHK011026

Functions

Basic Function

Compressor

Comfortable
Airflow

Functions

Inverter
(with Inverter Power Control)

Lifestyle
Convenience

Health & Clean

Functions

Air-Purifying Filter

Photocatalytic Deodorizing Filter

Operation Limit for Cooling (CDB)

19.4
~46

Operation Limit for Heating (CWB)

Air-Purifying Filter with Photocatalytic


Deodorizing Function

PAM Control

Titanium Apatite Photocatalytic


Air-Purifying Filter

Oval Scroll Compressor

Air Filter (Prefilter)

Swing Compressor

Wipe-Clean Flat Panel

Rotary Compressor

Washable Grille

Reluctance DC Motor

MOLD PROOF Operation

Power-Airflow Flap

Heating Dry Operation

Power-Airflow Dual Flaps

Good-Sleep Cooling Operation

24-Hour ON/OFF TIMER

Power-Airflow Diffuser

NIGHT SET Mode

Wide-Angle Louvers

Auto-Restart (after Power Failure)

Vertical Auto-Swing (Up and Down)

Horizontal Auto-Swing (Right and Left)

Timer
Worry Free
Reliability &
Durability

Self-Diagnosis (Digital, LED) Display

Wiring Error Check Function

3-D Airflow

COMFORT AIRFLOW Operation

Anti-Corrosion Treatment of Outdoor Heat


Exchanger

Comfort Control Auto Fan Speed

Operation

Category

FTN50/60JV18
RN50/60JV1

Category

FTN50/60JV18
RN50/60JV1

2. Functions

Flexibility

Indoor Unit Quiet Operation

Multi-Split / Split Type Compatible Indoor


Unit

NIGHT QUIET Mode (Automatic)

Flexible Voltage Correspondence

Outdoor Unit Quiet Operation (Manual)

Chargeless

INTELLIGENT EYE Operation

Either Side Drain (Right or Left)

Quick Warming Function (Preheating


Operation)

Power Selection

Hot-Start Function

Automatic Defrosting

Automatic Operation

Program Dry Operation

Fan Only

New POWERFUL Operation (Non-Inverter)

Inverter POWERFUL Operation

Priority-Room Setting

COOL/HEAT Mode Lock

HOME LEAVE Operation

ECONO Operation

Indoor Unit ON/OFF Button

Signal Receiving Sign

Temperature Display

Remote Control 5-Rooms Centralized Controller (Option)

Remote
Controller

10 m

Remote Control Adaptor


(Normal Open-Pulse Contact)
(Option)

Remote Control Adaptor


(Normal Open Contact) (Option)

DIII-NET Compatible (Adaptor) (Option)

Wireless

Wired (Option)

Note: { : Holding Functions


: No Functions

Room Air Conditioners J-Series

Specifications

EDHK011026

3. Specifications
50 Hz, 220 V
Models

Indoor Units
Outdoor Units

Capacity (Rated)
Moisture Removal
Running Current (Rated)
Power Consumption (Rated)
Power Factor
COP (Rated)
Liquid
Piping
Connections Gas
Drain
Heat Insulation
Max. Interunit Piping Length
Max. Interunit Height Difference
Chargeless
Amount of Additional Charge of
Refrigerant
Indoor Units
Front Panel Color
H
Airflow Rate M
L
Type
Fan
Motor Output
Speed
Air Direction Control
Air Filter
Running Current
Power Consumption
Power Factor
Temperature Control
Dimensions (H W D)
Packaged Dimensions (H W D)
Weight
Gross Weight
Operation
H/M/L
Sound
Outdoor Units
Casing Color
Type
Compressor Model
Motor Output
Type
Refrigerant
Oil
Charge
Type
Refrigerant
Charge
Airflow Rate

Type
Fan
Motor Output
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Starting Current
Dimensions (H W D)
Packaged Dimensions (H W D)
Weight
Gross Weight
Operation
H
Sound
Drawing No.

Note:

FTN50JV18
RN50JV1
5.3
18,090
4,560
2.9
7.5
1,640
98
3.23
6.4
12.7
18.0
Both Liquid and Gas Pipes
30
20
10

kW
Btu/h
kcal/h
L/h
A
W
%
W/W
mm
mm
mm
m
m
m
g/m

FTN60JV18
RN60JV1
6.7
22,860
5,760
3.9
10.2
2,210
98
3.03
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
20
10

20

20

mm
mm
kg
kg

FTN50JV18
White
17.5 (618)
14.7 (519)
11.9 (420)
Cross Flow Fan
43
5 Steps, Auto
Right, Left, Horizontal, Downward
Removable / Washable / Mildew Proof
0.2
43
98
Microcomputer Control
290 1,050 238
337 1,147 366
12
17

FTN60JV18
White
18.5 (653)
15.1 (533)
11.9 (420)
Cross Flow Fan
43
5 Steps, Auto
Right, Left, Horizontal, Downward
Removable / Washable / Mildew Proof
0.2
43
98
Microcomputer Control
290 1,050 238
337 1,147 366
12
17

dBA

45 / 40 / 35

47 / 41 / 36

RN50JV1
Ivory White
Hermetically Sealed Rotary Type
RN196VHSMT
1,300
FV50S
0.52
R-410A
1.6
52.1
1,840
Propeller
50
7.3
1,597
98
33
735 825 300
784 960 390
48
55

RN60JV1
Ivory White
Hermetically Sealed Rotary Type
PN25VAAMT
1,700
FV50S
0.90
R-410A
2.0
53.0
1,872
Propeller
65
10.0
2,167
98
54
770 900 320
900 925 390
63
76

m/min
(cfm)
W
Steps

A
W
%

W
L
kg
m/min
cfm
W
A
W
%
A
mm
mm
kg
kg
dBA

50

52

C:3D067874B

C:3D067875A

The data are based on the conditions shown in the table below.

Cooling

Piping Length

Conversion Formulae

Indoor ; 27CDB / 19CWB


Outdoor ; 35CDB / 24CWB

7.5 m

kcal/h = kW 860
Btu/h = kW 3412
cfm = m/min 35.3

Room Air Conditioners J-Series

EDHK011026

Dimensions

4. Dimensions
4.1

Indoor Unit

FTN50JV18

REAR

1050

RIGHT

(SPACE FOR
MAINTENANCE)
MIN.50

OPERATION LAMP

DRAIN HOSE FOR VP13


(CONNECTING PART
I.D.14.0,O.D.18.0)
(THE HOSE LENGTH OF
LIQUID PIPE 6.4 CuT
OUTSIDE THE UNIT:
(THE LENGTH OF PIPE OUTSIDE
ABOUT 530)
THE UNIT: ABOUT 480)

GAS PIPE 12.7 CuT


(THE LENGTH OF PIPE OUTSIDE
THE UNIT: ABOUT 430)

TIMER LAMP
HOME LEAVE LAMP

FRONT GRILLE FIXING SCREWS


(INSIDE)

BLADE ANGLES

10

5
10

40

35

FAN

60

VERTICAL BLADE(MANUAL)

5
50

5
55

99.5

WALL HOLE
80 HOLE

WALL HOLE FOR EMBEDDED PIPING


80 HOLE
STANDARD LOCATIONS OF WALL HOLES

CONTROLLER
(ARC433A26)

52.5

35

40

WIRELESS REMOTE

893.5

DRY

52

163

HORIZONTAL BLADE
(AUTOMATIC)
COOLING

155.5
290

18

1050

14.5

SIGNAL
TRANSMITTER
58

TERMINAL BLOCK WITH


EARTH TERMINAL
(INSIDE)

52

FLAPS

MODEL NAME
PLATE
290

SIGNAL RECEIVER
INDOOR UNIT ON/OFF
SWITCH
ROOM TEMP. THERMISTOR
(INSIDE)

MIN.50
(SPACE FOR
MAINTENANCE)

REQUIRED SPACE

INCLUDING
INSTALLATION PLATE
240
238

30

REAR

LEFT

MIN.30
(SPACE FOR
PERFORMANCE)

AIR FLOW (INDOOR)


(FOR PERFORMANCE AND MAINTENANCE)

THE MARK () SHOWS PIPING DIRECTION

50

3D065874B

55

AIR FLOW (INDOOR)


(FOR PERFORMANCE AND MAINTENANCE)

REAR
RIGHT
(SPACE FOR
MAINTENANCE)
MIN.50

OPERATION LAMP
SIGNAL RECEIVER
INDOOR UNIT ON/OFF
SWITCH

TERMINAL BLOCK WITH


EARTH TERMINAL
(INSIDE)

ROOM TEMP. THERMISTOR


(INSIDE)

DRAIN HOSE FOR VP13


(CONNECTING PART
I. D. 14.0, O. D. 18.0)
(THE HOSE LENGTH OF
LIQUID PIPE 6.4 CuT
OUTSIDE THE UNIT :
(THE LENGTH OF PIPE OUTSIDE
ABOUT 530)
THE UNIT : ABOUT 480)

GAS PIPE 15.9 CuT


(THE LENGTH OF PIPE OUTSIDE
THE UNIT : ABOUT 430)

TIMER LAMP
FRONT GRILLE FIXING SCREWS
(INSIDE)

58

BLADE ANGLES

DRY

40 10
40

35

5
35

FAN

VERTICAL BLADE (AUTOMATIC)

WIRELESS REMOTE
CONTROLLER

5
50

(ARC433A26)
55

Room Air Conditioners J-Series

52.5

893.5

52

163

HORIZONTAL BLADE
(AUTOMATIC)
COOLING

10

1050

14.5

SIGNAL
TRANSMITTER
18

155.5
290

FLAPS

MIN.50
(SPACE FOR
MAINTENANCE)

REQUIRED SPACE

MODEL NAME
PLATE
290

INCLUDING
INSTALLATION PLATE
240
238

30

1050

55

50

60

99.5

52

REAR
LEFT

MIN.30

THE MARK () SHOWS PIPING DIRECTION

(SPACE FOR
PERFORMANCE)

FTN60JV18

WALL HOLE
80 HOLE

WALL HOLE FOR EMBEDDED PIPING


80 HOLE
STANDARD LOCATIONS OF WALL HOLES

3D059038E

Dimensions

4.2

EDHK011026

Outdoor Unit

DRAIN OUTLET
(I.D.15.9 HOSE FOR CONNECTION)

MINIMUM SPACE FOR AIR PASSAGE

WALL HEIGHT ON AIR OUTLET SIDE


=LESS THAN 1200

100

RN50JV1

78

825

50

350

50
50

350

100

300

36
330

25

350

10

580

350

124

100

325

4-HOLES FOR ANCHOR BOLTS


(M8 OR M10)
NAME PLATE
WIRING INLET

EARTH TERMINAL
IN SWITCH BOX

89 64

735

BRAND NAME LABEL

155
LIQUID STOP VALVE
(6.4CuT)

18

160

30
GAS STOP VALVE
(12.7CuT)

SERVICE PORT

3D065853D

RN60JV1

30

48
55

320

350
(345~355)

30

Hole for anchor


bolt 4 - M12

40
140

96
140

620

30

900

3
2
1
6

6
5

770

5
4

28

89

89

19

71

376

223
53 95
80
145

52
13

67

16

16

7
6
5
4
3
4
2
1
NOTE) 1.ATTACHED PIPING MAY NOT BE ATTACHED WITH A MODEL. NO.
58

70 102 117
45

54 95
84 55
19

142

352

329
143

54 95

60

55

191

Drain pipe connection


Control wiring intake
Power supply wiring intake
Refrigerant piping intake
Grounding terminal
Liquid pipe connection
Gas pipe connection
Parts name

Outside Diameter 26 3points


27 knock hole
34 knock hole
M5(in switch box)
6.4 Flare
15.9 Flare
Remarks

3D055315H

Room Air Conditioners J-Series

EDHK011026

Wiring Diagrams

5. Wiring Diagrams
5.1

Indoor Unit

FTN50/60JV18

FIELD WIRING.
PCB3

S27

S26

PCB1

H1

X1M

RED

WHT

BLK

R1T

GRN/
YLW

RECTIFIER

~
Fu
3.15A

V1

H2
MR2
H3

S38
SA1

V2

CAUTION
NOTE THAT OPERATION WILL
RESTART AUTOMATICALLY IF
THE MAIN POWER SUPPLY IS
TURNED OFF AND THEN BACK
ON AGAIN.

FG

PCB4
S37

S21

OUTDOOR

S1
RED

LED1 LED2
H1P

BLU
BRN
ORG
WHT

H2P
1

SIGNAL
RECEIVER
WIRELESS
REMOTE
CONTROLLER

t
S29

S1W

Room Air Conditioners J-Series

S6

S8

M1F

BRN
RED
ORG
YLW
PNK
BLU

PCB2

S32

RED
ORG
YLW
PNK
BLU

S28

INDOOR

R2T
M
M1S

M
M2S

FG
Fu
H1~H3
H1P, H2P
M1F
M1S, M2S
MR2
PCB1~PCB4
R1T, R2T
S1~S38
S1W
SA1
V1, V2
X1M

: FRAME GROUND
: FUSE
: HARNESS
: PILOT LAMP
: FAN MOTOR
: SWING MOTOR
: MAGNETIC RELAY
: PRINTED CIRCUIT BOARD
: THERMISTOR
: CONNECTOR
: OPERATION SWITCH
: SURGE ARRESTER
: VARISTOR
: TERMINAL STRIP
: PROTECTIVE EARTH

3D058895D

Wiring Diagrams

5.2

EDHK011026

Outdoor Unit

RN50JV1

FIELD WIRING
indoor
TO INDOOR UNIT

X1M
outdoor
1

RED

BLU

RED

BLK

RED

BLK

V1R

M1C

S1T

A2

K1M

C
4

X2M
GRN/YLW

BLK

A1

F1U

WHT

POWER SUPPLY
~ 50Hz
220V-240V

RED

L
RED

M
1~
S

A1

A2

BLK

3.15A
L
L

RED

YLW

C11R

BLK

WHT

RED
3

GRN/YLW

B1

B2

F1S

1 WHT

C12R

BLK

C11R, C12R : RUNNING CAPACITOR

M1F

: FAN MOTOR

S1T : THERMOSTAT

F1S

: SURGE ARRESTER

M1C

: COMPRESSOR MOTOR

: LIVE

F1U

: FUSE

X11A

: CONNECTOR

: NEUTRAL

K1M

: MAGNETIC CONTACTOR

X1M, X2M : TERMINAL STRIP

V1R

: RECTIFIER

BLK
L ORG
H
3 RED

BLK
M
1~

ORG
RED
WHT

M1F

X11A

: PROTECTIVE EARTH

3D066609A

RN60JV1

FIELD WIRING
indoor

TO INDOOR UNIT

X1M
outdoor
1

2
B2

B1

A2

V1R
2

K1M

BLK

BLK

RED

A1

BLK

ORG

H
2

RED

WHT

X2M
GRN/YLW

M1C

H
t

1
POWER SUPPLY
~ 50Hz
220V-240V

RED

S1T

F1U

WHT

A2

L
RED

M
1~

YLW

C11R

WHT

RED
BLK

A1
RED

BLK
3.15A

WHT

RED
3

GRN/YLW

BLU

RED

RED

F1S

C11R, C12R : RUNNING CAPACITOR

M1F

: FAN MOTOR

S1T : THERMOSTAT

F1S

: SURGE ARRESTER

M1C

: COMPRESSOR MOTOR

: LIVE

F1U

: FUSE

X11A

: CONNECTOR

: NEUTRAL

K1M

: MAGNETIC CONTACTOR

X1M, X2M : TERMINAL STRIP

V1R

: RECTIFIER

C12R

BLK
ORG

M
1~

RED
WHT

M1F

X11A

: PROTECTIVE EARTH

3D066807B

Room Air Conditioners J-Series

EDHK011026

Piping Diagrams

6. Piping Diagrams
6.1

Indoor Unit

FTN50JV18

FTN60JV18

INDOOR UNIT

INDOOR UNIT

(7.9CuT)

(7.9CuT)

HEAT EXCHANGER

HEAT EXCHANGER

THERMISTOR
ON HEAT EXCH.

THERMISTOR
ON HEAT EXCH.
CROSS FLOW FAN

CROSS FLOW FAN

FIELD PIPING

FIELD PIPING
(6.4CuT)

(6.4CuT)

M
FAN MOTOR

FIELD PIPING
(12.7CuT)

M
FAN MOTOR

FIELD PIPING

(12.7CuT)

(15.9CuT)

(12.7CuT)

REFRIGERANT FLOW
COOLING

REFRIGERANT FLOW
COOLING

4D051016M

4D051010F

6.2

Outdoor Unit

RN50JV1

RN60JV1

OUTDOOR UNIT
OUTDOOR UNIT

6.4CuT FILTER

9.5CuT

6.4CuT

LIQUID STOP
VALVE
FIELD PIPING
(6.4CuT)
6.4CuT

CAPILLARY TUBE
PROPELLER FAN
12.7CuT
12.7CuT

PROPELLER FAN

6.4CuT

HEAT EXCHANGER

OUTDOOR TEMPERATURE
THERMISTER

FILTER MUFFLER

HEAT EXCHANGER

LIQUID STOP
FIELD PIPING
VALVE
(6.4CuT)
6.4CuT
CAPILLARY TUBE

FIELD PIPING
(12.7CuT)

MUFFLER

MUFFLER 15.9CuT

9.5CuT

GAS STOP VALVE


WITH SERVICE PORT

ACCUMULATOR
COMPRESSOR

FIELD PIPING
(15.9CuT)

12.7CuT 12.7CuT
GAS STOP VALVE
WITH SERVICE PORT
ACCUMULATOR

REFRIGERANT FLOW
COOLING

COMPRESSOR
REFRIGERANT FLOW
COOLING

4D065584B

Room Air Conditioners J-Series

4D065585B

Capacity Tables

EDHK011026

7. Capacity Tables
7.1

Cooling Only

FTN50JV18 + RN50JV1 (50 Hz, 220 V)


AFR

17.5

BF

0.280

INDOOR

OUTDOOR TEMPERATURE (CDB)

EWB EDB

20

25

30

32

35

40

TC

SHC

PI

TC

SHC

PI

TC

SHC

PI

TC

SHC

PI

TC

SHC

PI

TC

SHC

PI

14.0

20

5.43

3.95

1.26

5.18

3.82

1.38

4.94

3.70

1.50

4.84

3.65

1.55

4.69

3.58

1.62

4.44

3.46

1.74

16.0

22

5.67

3.88

1.27

5.43

3.76

1.39

5.18

3.65

1.51

5.08

3.60

1.56

4.93

3.53

1.63

4.69

3.42

1.75

18.0

25

5.92

4.05

1.27

5.67

3.94

1.39

5.42

3.83

1.52

5.33

3.79

1.56

5.18

3.73

1.64

4.93

3.62

1.76

19.0

27

6.04

4.26

1.28

5.79

4.16

1.40

5.55

4.05

1.52

5.45

4.01

1.57

5.30

3.95

1.64

5.05

3.85

1.76

22.0

30

6.41

4.11

1.29

6.16

4.01

1.41

5.91

3.92

1.53

5.81

3.88

1.58

5.67

3.83

1.65

5.42

3.74

1.77

24.0

32

6.65

3.99

1.29

6.40

3.91

1.42

6.16

3.82

1.54

6.06

3.79

1.59

5.91

3.74

1.66

5.66

3.66

1.78

Symbols

NOTE:

AFR

: Airflow rate

(m/min.)

BF

: Bypass factor

EWB

: Entering wet bulb temp.

(C)

EDB

: Entering dry bulb temp.

(C)

TC

: Total capacity

(kW)

SHC

: Sensible heat capacity

(kW)

PI

: Power input

(kW)

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat.
2.
shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the
figures in the above tables.
(Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table,
please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
Level difference : 0 m
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above
table.
3D068368

FTN60JV18 + RN60JV1 (50 Hz, 220 V)


AFR

18.5

BF

0.285

INDOOR

OUTDOOR TEMPERATURE (CDB)

EWB EDB

20

25

30

32

35

40

TC

SHC

PI

TC

SHC

PI

TC

SHC

PI

TC

SHC

PI

TC

SHC

PI

TC

SHC

PI

14.0

20

6.44

4.54

1.65

6.44

4.54

1.85

6.24

4.43

2.02

6.12

4.36

2.09

5.93

4.27

2.19

5.62

4.10

2.35

16.0

22

7.17

4.68

1.71

6.86

4.52

1.87

6.55

4.36

2.03

6.42

4.30

2.10

6.24

4.21

2.20

5.93

4.06

2.36

18.0

25

7.48

4.85

1.72

7.17

4.70

1.88

6.86

4.55

2.04

6.73

4.49

2.11

6.55

4.41

2.21

6.23

4.26

2.37

19.0

27

7.64

5.06

1.72

7.32

4.91

1.88

7.01

4.77

2.05

6.89

4.71

2.11

6.70

4.63

2.21

6.39

4.49

2.37

22.0

30

8.10

4.86

1.73

7.79

4.73

1.90

7.47

4.60

2.06

7.35

4.55

2.13

7.16

4.48

2.22

6.85

4.36

2.39

24.0

32

8.41

4.71

1.74

8.10

4.59

1.91

7.78

4.48

2.07

7.66

4.43

2.14

7.47

4.37

2.23

7.16

4.25

2.40

Symbols
AFR

: Airflow rate

BF

: Bypass factor

NOTE:
(m/min.)

EWB

: Entering wet bulb temp.

(C)

EDB

: Entering dry bulb temp.

(C)

TC

: Total capacity

(kW)

SHC

: Sensible heat capacity

(kW)

PI

: Power input

(kW)

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat.
2.
shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the
figures in the above tables.
(Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table,
please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
Level difference : 0 m
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above
table.
3D068369

10

Room Air Conditioners J-Series

EDHK011026

7.2

Capacity Tables

Capacity Correction Factor by the Length of Refrigerant Piping (Reference)


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping.
(The distance between the indoor unit and the outdoor unit)

7.2.1

50 Class
R-410A (50 class)

Capacity correction factor

0.9

0.8
Range of the Refrigerant Additional Charge

10

15

20

25

30

Piping length (m)


(R12428)

7.2.2

60 Class
R-410A (60 class)

Capacity correction factor

0.9

0.8
Range of the Refrigerant Additional Charge

10

15

20

25

30

Piping length (m)


(R12429)

Note:

1. The graphs show the factor when additional refrigerant of the proper quantity is charged.

Room Air Conditioners J-Series

11

Operation Limit

EDHK011026

8. Operation Limit
RN50/60JV1

50
46

Pull-down period

30

Continuous operation

Outdoor temp. (CDB)

40

20
19.4
0

10
14
20 23
28 30
Notes:
Indoor temp. (CWB)
The graph is based
on the following conditions.
Equivalent piping length 7.5m
Level difference
0m
Air flow rate
High
4D063906C

12

Room Air Conditioners J-Series

EDHK011026

Sound Level

9. Sound Level
9.1

Measuring Location
Indoor Unit

Outdoor Unit

1m

0.8 m

1m

(R1759)

Note:

(R1003)

1. Operation sound is measured in an anechoic chamber.


2. The data are based on the conditions shown in the table below.
Cooling
Indoor ; 27CDB / 19CWB
Outdoor ; 35CDB / 24CWB

Room Air Conditioners J-Series

Piping Length
5m

13

Sound Level

EDHK011026

9.2

Octave Band Level

9.2.1

Indoor Unit
FTN60JV18

70

OVER ALL ( dB )

60

SCALE

50Hz
220V~240V
(H)

50Hz
220V~240V
(L)

45

35

NC-50

( B.G.N IS ALREADY RECTIFIED )

50

OPERATING CONDITIONS
NC-40

POWER SOURCE

40

220V~240V 50Hz

JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE
50Hz 220V~240V(H)

NC-30
30

50Hz 220V~240V(L)
NC-20
20

APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

9.2.2

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

OCTAVE BAND SOUND PRESSURE LEVEL


dB(0dB=0.0002 bar)

SCALE

50Hz
220V~240V
(H)

50Hz
220V~240V
(L)

47

36

NC-60

NC-50

( B.G.N IS ALREADY RECTIFIED )

50

OPERATING CONDITIONS

NC-40

POWER SOURCE

40

220V~240V 50Hz

JIS STANDARD
50Hz 220v~240V(H)
50Hz 220v~240V(L)

NC-30

30
NC-20

20

APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

4D066673B

8000

Outdoor Unit
RN60JV1

70

70

OVER ALL ( dB )
NC-60

60
NC-50

SCALE

50Hz
220V

50

( B.G.N IS ALREADY RECTIFIED )

50

OPERATING CONDITIONS
NC-40

POWER SOURCE

40

220V 50Hz

JIS STANDARD
50Hz 220V

NC-30

30
NC-20

APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

14

OVER ALL ( dB )

60

4D058780C

8000

RN50JV1

20

OCTAVE BAND SOUND PRESSURE LEVEL


dB(0dB=0.0002 bar)

NC-60

70

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D068090

OCTAVE BAND SOUND PRESSURE LEVEL


dB(0dB=0.0002 bar)

OCTAVE BAND SOUND PRESSURE LEVEL


dB(0dB=0.0002 bar)

FTN50JV18

OVER ALL ( dB )
NC-60

60
NC-50

SCALE

50Hz
220V

52

( B.G.N IS ALREADY RECTIFIED )

50

OPERATING CONDITIONS
NC-40

POWER SOURCE

40

220V 50Hz

JIS STANDARD
50Hz 220V

NC-30

30
NC-20

20

APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D068091

Room Air Conditioners J-Series

EDHK011026

Electric Characteristics

10. Electric Characteristics


Unit combination

Power supply

Compressor

OFM

IFM

Indoor

Outdoor

Hz - Volts

Voltage range

MCA

MFA

LRA

RLA

FLA

FLA

FTN50JV18

RN50JV1

50 - 220

MIN. 198 V
MAX. 242 V

9.2

15

33

6.8

50

0.5

43

0.2

FTN60JV18

RN60JV1

50 - 220

MIN. 198 V
MAX. 242 V

12.5

25

54

9.4

65

0.6

43

0.2

SYMBOLS:

NOTE:

MCA

: Min. circuit amps (A)

MFA

: Max. fuse amps (A)

LRA

: Locked rotor amps (A)

1. RLA is based on the following conditions.


Indoor temp. 27CDB / 19CWB
Outdoor temp. 35CDB.
2. Maximum allowable voltage unbalance between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.

RLA

: Rated load amps (A)

OFM

: Outdoor fan motor

IFM

: Indoor fan motor

FLA

: Full load amps (A)

: Fan motor rated output (W)


3D067567B

Room Air Conditioners J-Series

15

Installation Manual

EDHK011026

11. Installation Manual


11.1 Safety Precautions

16

Room Air Conditioners J-Series

EDHK011026

Installation Manual

11.2 50 Class

Room Air Conditioners J-Series

17

Installation Manual

18

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Installation Manual

Indoor/outdoor Unit Installation Drawings

Room Air Conditioners J-Series

19

Installation Manual

20

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Installation Manual

21

Installation Manual

22

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Installation Manual

23

Installation Manual

24

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Installation Manual

3PN10898-2G

Room Air Conditioners J-Series

25

Installation Manual

EDHK011026

11.3 60 Class

26

Room Air Conditioners J-Series

EDHK011026

Installation Manual

Indoor/outdoor Unit Installation Drawings

Room Air Conditioners J-Series

27

Installation Manual

EDHK011026

Indoor/outdoor Unit Installation Drawings

28

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Installation Manual

29

Installation Manual

30

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Installation Manual

31

Installation Manual

32

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Installation Manual

33

Installation Manual

EDHK011026

3PN10898-4G

34

Room Air Conditioners J-Series

EDHK011026

Operation Manual

12. Operation Manual

Room Air Conditioners J-Series

35

Operation Manual

36

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Operation Manual

37

Operation Manual

38

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Operation Manual

39

Operation Manual

40

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Operation Manual

41

Operation Manual

42

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Operation Manual

43

Operation Manual

44

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Operation Manual

45

Operation Manual

46

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Operation Manual

47

Operation Manual

48

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Operation Manual

49

Operation Manual

50

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Room Air Conditioners J-Series

Operation Manual

51

Operation Manual

52

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Operation Manual

Trouble Shooting
These cases are not troubles.
The following cases are not air conditioner troubles but have some reasons. You may just continue using it.

Case
Operation does not start soon.
When ON/OFF button was
pressed soon after
operation was stopped.
When the mode was
reselected.

Explanation
This is to protect the air conditioner.
You should wait for about 3 minutes.

The outdoor unit emits water or


steam.

In COOL or DRY mode


Moisture in the air condenses into water on the cool
surface of outdoor unit piping and drips.

Mists come out of the indoor


unit.

This happens when the air in the room is cooled into mist by
the cold airflow during cooling operation.

The indoor unit gives out odour.

This happens when smells of the room, furniture, or


cigarettes are absorbed into the unit and discharged with the
airflow.
(If this happens, we recommend you to have the indoor unit
washed by a technician. Consult the service shop where you
bought the air conditioner.)

The outdoor fan rotates while


the air conditioner is not in
operation.

After operation is stopped:


The outdoor fan continues rotating for another 60
seconds for system protection.
While the air conditioner is not in operation:
When the outdoor temperature is very high, the outdoor
fan starts rotating for system protection.

The operation stopped


suddenly.
(OPERATION lamp is on.)

For system protection, the air conditioner may stop


operating on a sudden large voltage fluctuation.
It automatically resumes operation in about 3 minutes.

No remote controller signals are


The batteries are dying and the remote controller is
displayed.
malfunctioning. Replace all the batteries with new size AAA
The remote controller sensitivity
alkaline batteries. For details, refer to To set the batteries
is low.
of this manual. (page 7.)
The display is low in contrast or * If the reset button is provided, press the reset button after the
blacked out.
batteries are replaced.
The display runs out of control.
A PISHI-PISHI squeaking
Expansion and contraction of plastic parts caused by
sound is heard when the system
temperature change makes this noise.
is in operation or after the stop
of operation

20

Room Air Conditioners J-Series

53

Operation Manual

54

EDHK011026

Room Air Conditioners J-Series

EDHK011026

Operation Manual

3PN10897-5D

Room Air Conditioners J-Series

55

Optional Accessories

EDHK011026

13. Optional Accessories


13.1 Option List
13.1.1 Indoor Unit
Option Name

50/60 Class

Air-Purifying Filter with Photocatalytic Deodorizing Function


without Frame

KAF952B42 (KAF952A42)

Remote Controller Loss Prevention with Chain

Drain Plug

Air Direction Adjustment Grille

KKF917A4

13.1.2 Outdoor Unit


Option Name

56

50 Class

60 Class

KKP937A4

KKP945A4

KPW945A4

Room Air Conditioners J-Series

EDHK011026

Optional Accessories

13.2 Installation Manual


13.2.1 KKP945A4

3P089958-1B

Room Air Conditioners J-Series

57

Optional Accessories

EDHK011026

13.2.2 KPW945A4

Before installation
Check the following parts

Name

Louver

Truss tapping screw

Installation manual

1piece

M4x4screws(max.7.5kW class)
M5x4screws(8.0/9.0kW class)

1piece

Shape

Quantity

Installation Procedure
Selection of Installation Location
Use when installing in a location that meets the following conditions.
When installing near the border to a neighbor's house
If exhaust blows directly on passers-by because outdoor unit is installed facing a road.
If exhaust blows directly on vegetation

Space Needed for Installation


A minimum of 100mm is needed
between the back of the outdoor
unit and any obstructions
(walls, etc.)
m

t
ore

han

100

Installation of Louvers
Caution
Attach the louvers overlapping the standard grill.
Installing the louvers without the grill would allow hands to enter the fan area,
which is dangerous, so be sure to install the standard grill.
When pointing up

When pointing down

(1) Remove the 4 attachment screws from


the standard grill.

(1) Remove the 4 attachment screws from


the standard grill.

(2) Install the louver pointed up.

(2) Install the louver pointed down.

Overlap the standard grill and


screw both in together.

Overlap the standard grill and


screw both in together.

The attachment screws


are in the louvers.

The attachment screws


are in the louvers.

(3) Installation complete

(3) Installation complete

3P089958-2C

58

Room Air Conditioners J-Series

Warning

Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorised importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
Organization:
DAIKIN INDUSTRIES, LTD.
AIR CONDITIONING MANUFACTURING DIVISION

JMI-0107

Scope of Registration:
THE DESIGN/DEVELOPMENT AND MANUFACTURE OF
COMMERCIAL AIR CONDITIONING, HEATING, COOLING,
REFRIGERATING EQUIPMENT, COMMERCIAL HEATING
EQUIPMENT, RESIDENTIAL AIR CONDITIONING
EQUIPMENT, HEAT RECLAIM VENTILATION, AIR
CLEANING EQUIPMENT, MARINE TYPE CONTAINER
REFRIGERATION UNITS, COMPRESSORS AND VALVES.

Organization:
DAIKIN INDUSTRIES
(THAILAND) LTD.

JQA-1452

Scope of Registration:
THE DESIGN/DEVELOPMENT
AND MANUFACTURE OF AIR
CONDITIONERS AND THE
COMPONENTS INCLUDING
COMPRESSORS USED FOR THEM

All of the Daikin Groups business


facilities and subsidiaries in Japan
are certified under the ISO 14001
international standard for
environment management.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/
c All rights reserved

Specifications, designs and other content appearing in this brochure are current as of June 2010 but subject to change without notice.

EDHK011026
Printed in Japan 06/10/0007 FS.AK.B