SECTION 8

CONDUITS AND ACCESSORIES, CABLE TRUNKING, CABLE TRAYS


MC 8
NG IN V PH KIN, MNG CP, KHAY CP

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

8.1 GENERAL

8.1 TNG QUT

8.1.1 DESCRIPTION

8.1.1 M T

The Sub-Contractor shall install conduits, cable

Nh thu s lp t cc ng dn, mng in, v

trunking,

ph tng cn thit khc nh c thhin trong bn

cable

trays

and

all

necessary

accessories as specified on the Sub-Contract


Drawings and this Section.
8.1.2 STANDARDS

v v trong phn ny.

8.1.2 CC TIU CHUN

All equipment, materials and workmanship

Tt c cc trang thit b, vt t v nhn cng phi

shall comply with the appropriate Singapore or

tun

British Standards or an acceptable equivalent


international standard as well as all local

Standards hay mt tiu chun quc t tng


ng cng nh tt c cc quy nh php l v

statutory obligations and regulations.

php lut ca nc s ti.

theo

tiu

chun

Singapore

or

British

8.2 EQUIPMENT

8.2 THIT B

8.2.1 STEEL CONDUITS, BOXES AND

8.2.1 NG DN, HP NI BNG THP V CC PH

ACCESSORIES

TNG.

All metal conduits shall be galvanized welded

Tt c cc ng dn kim loi phi l loi thp m

steel complying with BS 4568 - Specification for


steel conduit and fittings with metric threads of

km theo tiu chun BS 4568 - Specification for


steel conduit and fittings with metric threads of ISO

ISO form for electrical installations. No conduit

form for electrical installations.

shall be of less than 20mm.

c nh hn 20mm.

All conduit outlet boxes and junction boxes shall

Tt c cc hp ni v hp chia s l loi st mng,

be malleable iron and of standard circular

v l kiu c l trn theo tiu chun BS 4568 nh

pattern with spout to BS 4568 as specified.

qui nh.

ng dn khng

Standard circular pattern boxes shall be used

Nhng hp trn mu tiu chun phi s dng ng

with conduits up to and including 25mm.

dn 25mm hoc nh hn. Nhng hp hnh ch

Rectangular pattern adaptable boxes shall be


used for conduits of 32mm and larger.

nht s c dng vi ng 32mm v ln hn.

All conduit boxes shall be provided with lids.


Adaptable boxes shall be of mild steel of not

Tt c cc hp ni ng s c np y. Nhng hp
m tng s l loi thp mm khng nh hn

less than 2.5mm with hot dip galvanized finish.

2.5mm c trng m km. Hp s c su ln

Boxes shall be not less than 47mm deep and of

hn hoc bng 47mm v vi kch thc nh vy s

such dimensions as will enable the largest size


cable, for which the conduit run is suitable, to

cho php dy c kch ln, loi ph hp i ng


dn, ko dy m khng lm chng b un cong

be drawn in without excessive bending of the

qu mc. Np y s s dng loi cng kiu v c

cables. Lids of the same gauge with brass fixing


screws, shall be provided.

vt bt bng ng thau.

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/1

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

Spacer bar saddles shall be malleable cast iron

Kp gi ng s l loi gang mng c v c

with bases and shall be hot dip galvanised to

trng lp m km theo BS 729: 1994 - Specification

BS 729: 1994 - Specification for hot dip

for hot dip galvanized coatings on iron and steel

galvanized coatings on iron and steel articles.

articles.

Socket outlet boxes shall be constructed of

Nhng hp cm s c lm bng thp tm, m

sheet steel, galvanized finish and shall comply


with BS 4662: 1989 - Specification for boxes for

km v theo tiu chun BS 4662: 1989 Specification for boxes for the enclosure of electrical

the enclosure of electrical accessories. Flush or

accessories. Hp cm loi m hay loi gn ni s

surface mounting type outlet boxes shall be

c s dng theo nhng ni thch hp.

used where applicable.


An earthing terminal with brass screw shall be

Mi n v hp ni cm s c mt cc ni t vi

provided in each lighting and power outlet box.

vt bt bng ng thau.

All conduit entries to adaptable boxes, outlet

Tt c cc ng dn i vo hp ni, hp cm v

boxes and switchgear shall be made with

my ct s c ni bng khp ni v ci ni rng

coupling and hexagon male brass bush with


serrated steel washer.

c bng ng thau c long n rng ca bng


thp.

Accessories which have not obtained


Authoritys Certification will not be considered

Cc ph tng khng t c chng nhn ca c


quan c thm quyn s khng c xem xt, chp

or

nhn.

accepted.

8.2.2 NG THP L XO

8.2.2 FLEXIBLE STEEL CONDUIT


Flexible steel conduit and solid type adapters

ng dn mm bng thp, ng cng v khp ni

shall comply with BS 731: Part 1: 1993 Flexible steel conduit & adaptors for the

phi theo tiu chun BS 731: Part 1: 1993 - Flexible


steel conduit & adaptors for the protection of electric

protection of electric cable and shall be of the

cable v l loi kn nc bng kim loi, hay c

metallic watertight pattern, PVC oversheathed.

bc nha PVC.

8.2.3 PVC CONDUIT

8.2.3 NG NHA PVC

All rigid PVC conduits shall comply with the


requirements of BS 6099 - Conduits for

Tt c cc ng dn cng bng PVC phi tun theo


yu cu ca BS 6099 - Conduits for electrical

electrical installations. All conduits shall be of

installations. Tt c ng dn phi l loi c bn

the high impact heavy mechanical strength


type. Unless otherwise specified, all conduits

c kh cao. Tr nhng qui nh khc, tt c ng dn


s c sn mu en.

shall be coloured black.


All conduit fittings shall comply with the
requirements of BS 4607 - Non-metallic

Tt c cc ni ng s phi tun theo yu cu ca


BS 4607 - Non-metallic conduits and fittings for

conduits and fittings for electrical installations.

electrical installations. ng dn, khp ni, v cc

Conduit, fittings and accessories shall be from


the same manufacturer.

ph tng khc phi cng mt hng sn xut.

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/2

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

No conduit smaller than 20 mm meter shall be

ng nh hn 20 mm s khng c s dng.

used.
8.2.4 CABLE TRUNKING

8.2.4 MNG CP (TRUNKING)

Metal cable trunking shall be manufactured

Hp cha cp bng kim loi s c sn xut theo

complying with Singapore Standard SS 249:

tiu chun Singapore Standard SS 249: 1981 -

1981 - Steel surface cable trunking and


accessories and shall carry batch-approved

Steel surface cable trunking and accessories v mi


trunking s c mang chng nhn t c quan c

certificate on each trunking from Authority.

thm quyn. Khi c qui nh khc, h thng hp

When specified otherwise, the cable trunking

cha cp s l loi c trng m km hay thp

system shall be of the hot-dipped galvanised or


electro-galvanised sheet steel both internal and

tm m tnh in ton b t trong ra ngoi v c


ph lp bt epoxy mng vi dy 45 micron.

external

throughout

and

coated

with

electrostatic epoxy powder with a minimum film


thickness of 45 micron.
The trunking system shall comprise of purpose

H thng mng cp bao gm ch un, chia ba T,

factory made bends, tees, reducers etc., and


shall be electrically continuous grounded by

ch gim, v.v, v c ni t lin tc bng cch


lin kt mi phn trunking v nhng ch ni vi

linking each sections and joints with purpose

nhau bng ci ni bng ng. Tt c c v b long

factory made copper link. All screws bolts and


nuts shall be of zone plated or cadmium plated.

s c m km.

Covers shall be of the quick-fix pattern with


centre captive screw or spring-on type. Fixing

Np s l loi gn nhanh, loi c vt bt gi hay c


rnh ci. S lp t s dng lai vt t ci s khng

arrangement employing self-tapping screws

c chp nhn.

shall not be accepted.


Cable trunking shall have the dimensions and

Hp ni cp s c kch thc v dy nh trong

thickness as specified in the following table:-

bng sau:

METAL CABLE TRUNKING SIZE AND THICKNESS

Size (mm)

Material Thickness
(mm)

KCH THC MNG CP & DY

Kch thc (mm)

dy vt liu
(mm)

Width
(max)

Height
(max)

Body

Cover

rng
(max)

Cao
(max)

Mng cp

Np

50
100

50
50

1.0
1.2

1.0
1.2

50
100

50
50

1.0
1.2

1.0
1.2

175

50

1.5

1.2

175

50

1.5

1.2

350
100

50
75

1.6
1.2

1.5
1.2

350
100

50
75

1.6
1.2

1.5
1.2

150

75

1.5

1.2

150

75

1.5

1.2

175

50

1.6

1.2

175

50

1.6

1.2

300
150

75
100

1.6
1.5

1.5
1.2

300
150

75
100

1.6
1.5

1.5
1.2

300

100

1.6

1.5

300

100

1.6

1.5

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/3

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

150

150

1.5

1.2

150

150

1.5

1.2

200

150

1.6

1.5

200

150

1.6

1.5

8.2.5 PVC TRUNKING

8.2.5 MNG CP NHA

PVC trunking, when specified shall comply with

Trunking nha phi tun theo yu cu ca BS 4678

the requirements of BS 4678 Part 4


Specification for cable trunking made of

Part 4 Specification for cable trunking made of


insulation material. Tt c trunking phi l loi c

insulation material. All trunking shall be of the

bn c kh cao.

high impact heavy mechanical strength type.


The trunking system shall comprise of purpose

H thng trunking bao gm cc ch un, ch chia

factory made bends, tees corners, reducers,

ba T, ch gim, v.v, v mu s l mu trng ca

etc. and colour shall be to manufacturers white


unless specified otherwise.

nh sn xut, tr khi c nhng ch nh khc.

8.2.6 CABLE TRAYS

8.2.6 KHAY CP

Metal cable tray shall be perforated with return

Khay cp kim loi l loi c l , g cao t nht l

edges of minimum 20mm high.

When

20mm. Khi c nhng ch nh khc, mng in s l

specified otherwise, the cable tray shall be


fabricated from hot-dipped galvanised or

loi c lm t thp tm m km hay m tnh in


c bc lp bt epoxy vi dy ti thiu l 45

electro-galvanised steel sheet with electrostatic

micron hay lp m km ASTM A386 .

epoxy powder coating to minimum thickness of


45 micron or hot dipped galvanised to ASTM
A386 finishes.
The tray system shall comprises of purpose
factory made bends, tees, reducers etc. and

H thng mng bao gm nhng ch un khc, chia


ba T, ch gim, v.v, v c tip t lin tc bng

shall be electrically continuous grounded by

cch lin kt tng phn vi nhng ch ni vi nhau

linking each sections and joints with purpose


factory made copper link.

bng ci ni bng ng.

Metal cable tray shall have the dimensions as

Mng in kim loi s c kch thc quy nh nh

specified in the following table:-

sau:

CABLE TRAY SIZES AND THICKNESS

KCH THC KHAY CP & DY

Cable tray sizes and thickness

Khch thc khay cp v dy

Width

Thickness

rng

dy

50mm

1.0mm

50mm

1.0mm

100mm

1.0mm

100mm

1.0mm

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/4

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

150mm

1.2mm

150mm

1.2mm

200mm

1.2mm

200mm

1.2mm

250mm
300mm

1.6mm
1.6mm

250mm
300mm

1.6mm
1.6mm

450mm

1.6mm

450mm

1.6mm

600mm
750mm

1.6mm
1.6mm

600mm
750mm

1.6mm
1.6mm

1000mm

2.0mm

1000mm

2.0mm

8.2.7 CABLE LADDER

8.2.7 THANG CP

All cable ladder and accessories materials shall

Tt c thang treo cp v ph kin khc s l loi

be hot-dipped galvanised.

c trng m km.

The cable ladder shall consist of side rail and

Thang treo cp bao gm cnh bn l tay vn v

horizontal rungs. These should have rigid

nhng nc thang song song. Chng phi l loi

welded type construction and fabricated with a

c hn lin kt chc chn li vi nhau v c

minimum of 2.0mm (14 SWG) sheet steel.


Dimension of side rail should be 32mm x 32mm

sn xut t thp tm c dy ti thiu l 2.0mm


(14 SWG). Kch thc ca tay vn phi l 32mm x

channel type with flange facing outside. Rungs

32mm, loi rnh c mp cnh quay mt ra ngoi.

should be 50mm x 30mm slotted channel type


and spaced 300mm apart or to manufacturers

Nhng bc thang l 50mm x 30mm loi c s


rnh v t cch khong nhau 300mm hay nh hn

standard whichever is smaller.

theo tiu chun ca nh sn xut.

The side rail and all fittings shall have 4 nos. of


the square holes on each end for fixing splice

Cnh bn v nhng khp ni ca thang s c 4 l


vung hai u lp tm ni. Tt c c vt phi l

plates. All the bolting hardware shall be

loi ng thau v c nhng m km ngoi tr

"carriage" type and finishing with hot dipped


galvanized except that electrically continuous

ch ni dy tip t s l loi bng ng, kch


thc l di 150mm x rng 20mm. Tt c cc ph

grounding jumpers shall be copper, size shall

kin phi l loi ph hp.

be of 150mm length x 20mm width. All


accessories shall be proprietary type.
Cable ladder shall be supplied in clear width of

Thang treo cp c cung cp c rng c

150mm, 300mm, 450mm, 600mm, 750mm or


900mm as specified.

quy nh l 150mm, 300mm, 450mm, 600mm,


750mm or 900mm.
8.2.8 H THNG MNG CP T SN

8.2.8 FLUSH FLOOR TRUNKING SYSTEM


All cables in the office area are to be laid in 2, 3

Tt c cp trong khu vc vn phng s c i

or 4-way flushfloor trunking system as per the

trong h thng mng cp t sn 2, 3 hay 4 ngn

layout drawings. The flushfloor trunking system


shall be constructed from pre-galvanized steel

nh c th hin trn bng v b tr. H thng


mng cp t sn s c sn xut t thp m

sheet in accordance with BS EN10142: 1991

km tun theo tiu chun BS EN10142: 1991

(Z275NAC) or JIS G3302: 1994 (Z27). The


Flushfloor trunking system chosen must be the

(Z275NAC) hay JIS G3302: 1994 (Z27). H thng


mng cp t sn c chn phi l loi mng cp

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/5

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

type which allows the trunking top cover to be

c np c m ra khi chnh sa cc b ni bn

opened whenever the readjustment of floor

trong cc hp ng ra c yu cu hay trong trong

termination in the service outlet box is required

trng hp i thm cp hay thm cc cm cho

or in cases where new cables are to be laid in


the future or for the repositioning of service

hp ng ra phc v. Mng cp t sn cng cho


php lp t li cc vch ngn v np y hin hu

outlet box. The flushfloor trunking shall allow

cho vic tng thm cc cm cho hp ng ra dch

the reinstatement of the existing trunking


dividers and cover for the repositioning of the

v. Cc hp ni s c cc np y kim loi. Cc
np y c sn xut t thp m km tun theo

service outlet box. The junction box shall come

tiu chun BS EN10142: 1991 (Z275NAC) hay JIS

with metal flyover.

G3302: 1994 (Z27). Khng cho php s dng cc

The flyover is constructed from pre-galvanized


steel sheet in compliance with BS EN10142:

np y bng nha v c s nhiu t. iu ny tun


theo cc qui nh v i dy mi nht ca I.E.E.

1991 (Z275NAC) or JIS G3302: 1994 (Z27).


Due to Electromagnetic interferences, use of
plastic flyover is not allowed. This is to comply
with the latest I.E.E. wiring regulations.
8.3 INSTALLATION

8.3 S LP T

8.3.1 GENERAL

8.3.1TNG QUT

The complete installation shall comply with

Ton b s kp t phi tun theo tiu chun

Singapore Standard Code of Practice CP 5:

Singapore Standard Code of Practice CP 5: 1998 -

1998 - Electrical Installation.

Electrical Installation.

Different conduit and trunking systems shall be

H thng ng v hp in khc nhau s c lp

provided for each of the following systems as

t cho tng h thng sau nh c yu cu trong

called for in this Specification.

phn ny.

a)

a)

Normal lighting and general purpose


outlets (e.g. 13A
socket-outlets).

or

15A

switch

Chiu sng bnh thng v nhng cm


thng dng (nh cm cng tc 13A hay
15A)

b)

Three phase power supply.

b)

Ngun cung cp ba pha.

c)

Single and 3 phase motors.

c)

ng c ba v mt pha.

d)

E.L.V. circuits.

d)

Mch E.L.V.

e)

Telephone services.

e)

Cc cm in thoi.

f)

Protective relay circuits.

f)

Mch rle bo v.

g)

D.C. circuits.

g)

Cc mch in D.C.

h)

Security System

h)

H thng an ninh.

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/6

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

i)

Fire Alarm and Detection System

i)

H thng d v bo chy.

j)

Emergency lighting and power outlets

j)

Cc cm ngun v n chiu sng khn


cp.

circuits
k)

Public Address and Background Music

k)

H thng thng bo chy a ch v nhc nn.

l)

System
MATV/ CATV System

l)

H thng MATV/CATV.

The Sub-Contractor's attention is especially

Nh thu c bit ch l bt buc ko ton b ng

drawn to the necessity for keeping all conduit


and trunking entirely separate from other piping

v trunking, tt c phi ring bit vi nhng ng


khc v khng cho php ni gia cc ng, trunking

services and no circuit connections will be

v nhng ng nh th.

permitted between the conduits and trunking


and such pipes.
8.3.2 STEEL CONDUIT SYSTEM

8.3.2 H THNG IN BNG THP

The Sub-Contractor shall run all sub-circuit in

Nh thu s chy tt c cc mch ph vi cp bc

PVC cables in G.I. conduit (except for cast-in

PVC trong ng G.I. (ngoi tr cc cng kn) tr khi

areas, in PVC conduit) unless otherwise


specified herein or shown on the Sub-Contract

c quy nh khc y hay c th hin trong


bn v.

Drawings.
G.I. conduit for indoor installation shall comply

ng G.I. lp t trong nh phi tun theo BS

to BS 4568 Class 3 and G.I. conduit for outdor

4568 Class 3 and G.I. ng lp t ngoi tri th theo

installation shall comply to BS 4568 Class 4.

BS 4568 Class 4.

All conduit systems in plant rooms, lift motor

Tt c h thng ng trong phng my, phng mt

rooms, false ceiling voids, bulkheads and

thang my, trn trn gi, vvh ngn, phng in s

switchrooms shall be surface mounted on walls


and soffit. Conduit systems in all other areas

lp loi ni trn tng v di bao ln. Trong tt c


cc khu vc khc, h thng ng s c chn m.

shall be carried out in concealed conduit.

Tr phi c nhng s ng c bit ca Qun l

Unless special permission has been obtained

K thut, ng dn khng c php lp t di

from the Engineer, no conduit shall be installed


underneath cable trays or along steel

mng in hay dc theo nhng cu trc kim loi.

structures.
Conduit systems shall be electrically and

Sau khi lp t, h thng ng v in v c kh phi

mechanically continuous and watertight after

c tnh lin tc v kn nuc. Khi h thng c lp

installation. The system when installed, and

t, v trc khi ko dy, chng phi c bt u

before wiring, shall be kept plugged with


wooden plugs. Immediately before wiring, all

bng nhng nt bt bng g.Ngay trc khi ko


dy, tt c h thng ng phi c lau chi bn

conduit systems shall be thoroughly swabbed

trong cho n khi hon ton kh ro v sch s.

out until dry and clean.


All sets of bends in conduit runs shall be formed
The English language version prevails
SECTION 8/VISTA VERDE SPECS/ELECT

Tt c nhng ch un ng phi c lm ti ch
u tin s dng ting Anh khi c tranh chp

8/7

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

on site in bending machines. Inspection bends

trn my un ng. Nhng ch r kim tra c th

may be permitted at column, where large bends

c chp nhn ti ct nh, nn trnh nhng ch

shall be avoided. Junction box shall be installed

c cong ln. Hp ni s c lp t nhng

wherever the connections exist.

ni c s ni.

Runs between draw-in boxes shall not have

ng dn chy gia hai hp ko dy khng c c

more than two right angle bends or their


equivalent and the length of such areas shall be

nhiu hn hai gc vung 90 hay tng ng


nh vy v chiu di ca nhng khu vc nh vys

limited to 12 m to permit easy draw-in of cables.

c gii hn 12m d dng trong vic ko dy.

The Sub-Contractor shall make good any


damage to the finishes of all conduits (including

Nh thu s phi lm hon thin trnh gy h hng


h thng ng dn sau khi hon tt (k c nhng

threads cut at site) by painting two coats of

ch ren rng) bng cch sn hai lp sn c cht

good quality lead paint.

lng tt nht.
a

Nh thu s sp xp cho mt h thng ng tp

telescopic conduit system to be employed

The

Sub-Contractor

shall

arrange

for

trung c s dng nhng ch ni bng ngang

where expansion joints are crossed. However,


where conduit is surface mounted on walls or

qua. Tuy nhin, ch ng c lp ni trn tng


hay trn, ng dn mm bng kim loi c dy dn

ceilings, a normal flexible metal conduit with

bo v bn ngoi s c s dng theo tiu chun

external circuit protective continuity conductor


shall be used. The size of the circuit protective

CP 5: 1998.

conductor shall be in accordance with CP 5:


1998.
All conduit systems shall be installed so as to

Tt c h thng ng dn phi c lp t sao cho

enable wiring to be carried out on the "loop-in"

dy dn to thnh h thng vng mch vng.

system.
All conduits shall be swabbed through before

Tt c ng dn phi c lau chi sch s nhu bi

installation so as to clean out all dirt, burrs and


moisture.

bm, cnh sc, m t trc khi lp t.

Conduits shall be fixed with full spacer bar

ng dn phi c gi c nh bng nhng kp

saddles at intervals not exceeding 1.2m.

ng vi khong cch khng qu 1.2m.


8.3.3 NG NHA PVC

8.3.3 PVC CONDUIT


All conduit joints shall be made using a solvent

Tt c ch ni ng phi s dng loi keo kt dnh

adhesive recommended by the manufacturer of

lp t c ngh bi nh sn xut ng. Tt

the conduit, to methods laid down by the

c ch ni nh vy phi kn nc. Ap dng tng

manufacturer. All such joints shall be watertight.


The same conditions apply to joints between

t i vi ch ni gi ng, khp ni v cc ph kin


khc. Cm khng c nhng ng hay ni ng vo

conduit, fittings and accessories. Dipping of

keo kt dnh. Trc khi ni, u ng phi c ct

conduit or conduit fittings into solvent adhesives


is forbidden. Before joints are made, conduit

ngang v phi lm snh cc g cnh sc bn. Ch


l phi lm sch du m, m t, bi xi mng

ends shall be cut square and all burrs and

bn trong, ngoi ng v cc ph tng khc trc

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/8

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

sharp edges shall be removed. Care shall be

khi ni. ng phi c a su vo trong ni ng

taken to remove all damp, grease, cement dust

v ng u vo trong khp ni.

and

oil

from

all

faces

of

conduit

and

accessories prior to jointing. Conduits shall be


entered fully into box spouts and butted into
couplers, other than expansion couplers, for
jointing purposes.
Screwed PVC conduit shall not be used unless

Khng c bt vt ng nha PVC tr phi thc s

specifically called for or when the PVC conduit

cn thit hay khi ng nha c ni vi cc thit b

is to be connected to metal equipment, conduit


and fittings with screwed entries. Where such

kim loi, ng v khp ni c l bt vt. Nhng l vt


nh vy th khng c sn, m s s dng ci ni

entries are not available, non-screwed male

c khng c rng vi cc khp ni.

bushes and couplers shall be used.


Expansion couplers shall be used where

Ni ng ko di s s dng nhng ni ng thng

straight runs of conduit exceed 8m. Within such

di hn 8m. Bn trong khp ni nh vy cho php

couplers a space of not less than 10mm shall


be allowed between the ends of the conduit.

c h khng qu 10mm gia nhng im cui


ca ng. Keo dn cho nhng ch ni nh vy s

The solvent adhesive used in such joints shall

cho php trong trng hp c s bin ng s

allow for movement caused by expansion


without affecting the water-tightness of the joint.

khng lm thm nc qua nhng ch ni ny. Mt


h thng thng thng s c chp thun khi ng

A similar system shall be employed when

in i qua mi ni m rng trong bt c trng thi

conduits cross building expansion joints in any


situation and the couplers shall span the joints.

no v b ni s m rng mi ni ny.

All bends shall be made using the correct size

Cc ch un cong phi c lm ng cong.

spring. Conduit sizes of 25 mm and below may


be set cold but all larger sizes shall be set hot.

ng phi 25mm v nh hn c th l lnh nhng


cc ng ln hn s l nng. Kp ng s khng

A pipe vice shall not be used during this or any

c s dng trong trng hp ny hay bt k

other operation. The radius of any conduit bend


shall not be used directly to heat conduit for

trng hp no khc. Khng c dng nhit t


trc tip ln ng un v phi theo hng dn

bending purposes and the manufacturers

ca nh sn xut.

recommendation should be followed.


Full spacer bar saddles shall be PVC with

Cc kp gi ng phi l loi PVC c . Vic c

bases. The fixings shall be such that the

nh cc ng in c th lm t cc ph kin m

conduits may be taken into accessories without


sets or bends.

khng cn b cong ng.

8.3.4 NG THP MM NI VI CC TRANG THIT

8.3.4 FLEXIBLE STEEL CONDUITS


CONNECTIONS TO FIXED EQUIPMENT

Connections to electric fixed equipment shall be

Cc trang thit b s c ni bng dy cp bc

by means of PVC cables in conduits, with the


final connection being made by flexible metal

PVC t trong cc ng dn, c im cui c bc


bng ng l xo kim loi v u ni thch hp. Mt

conduit and suitable adapters. A separate

cp dn bo v ring bng ng bn ngoi theo tiu

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/9

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

external circuit protective conductor copper

chun CP 5: 1988 and BS 6004: 1995 -

cable in accordance with CP 5: 1988 and BS

Specification

for

PVC-insulated

cables

(non-

6004: 1995 - Specification for PVC-insulated

armoured) for electric power and lighting ln hn

cables (non-armoured) for electric power and


lighting of not less than 2.5mm2 run outside the

2.5mm i ra ngoi ng l xo mm v c u ni
chc chn ti mi im cui ca ng.

flexible tube and solidly connected at each tube


termination shall be provided.
Flexible conduits installed in water pump rooms

ng l xo dc lp t trong cc phng bm nc

and the like shall be of the metallic watertight

v cc phng tng t s l loi bng kim loi

pattern, PVC oversheathed and with a separate


solidly connected external circuit protective

khng thm nc, c bc nha PVC v c mt


dy dn bo v ring bn ngoi c ni mt cch

conductor.

chc chn.

8.3.5 CABLE TRUNKING

8.3.5 MNG CP

Trunking shall be terminated with end flanges

im cui ca Trunking c g ni ci m s c

which shall be bolted direct to distribution


boards or apparatus.

bt c trc tip vo t din phn phi hay cc thit


b.

Connecting pieces shall be used and bolted


with cadmium plated mushroom head steel

S dng nhng tm ni v vt c u thp hnh


nm c m cadmium, b long v long n chng

screws, nuts and vibration resistant locking

rung ng. Mi im ni s c mt ci ni bng

washers. Each joint shall have a tinned copper


link bolted to each adjacent trunking to ensure

ng c bt c n mi ci trunking k m
bo tnh lin tc v in. Nhng cnh g sc bn

electrical continuity. All frayed and sharp edges

cn phi c lm sch trc khi lp t trunking.

shall

be

removed

from

trunking

before

installation.
Conduit entry to trunking shall be by galvanized

ng dn ni vo trunking bng nhng khp ni m

coupling and brass male bush with serrated


steel washer. Knockouts shall not be provided.

km vi ni c bng ng thau c long n thp


rng ca. Nhng loi khc th khng c s

Trunking shall be drilled on site.

dng. Trunking s c khoan nh v.

Where trunking crosses expansion joints, a


trunking system shall be used which will allow

Ni trunking i ngang qua nhng ch ni, mt h


thng trunking s c lm cho php m rng

for expansion and maintain earth continuity.

v duy tr s ni t c lin tc. H thng

The system used shall be checked by the


Engineer prior to it being used.

trunking nh vy s c Qun l K thut kim tra


trc khi a vo s dng.

Trunking installed in a vertical plane shall

Trunking lp t trong mt mt phng thng ng

contain sufficient supporting devices within the


trunking to prevent strain on the cables due to

phi c cc vt gi c nh bn trong gi
cho dy dn khng b cng qu mc do trng lng

the weight of the cables, and to prevent vertical

ca cp, v trnh s chuyn ng thng ca cp.

movement of the cables.


All hangers and support for cable trunking shall
The English language version prevails
SECTION 8/VISTA VERDE SPECS/ELECT

Cc thanh treo v gi cho mng cp s l loi


u tin s dng ting Anh khi c tranh chp

8/10

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

be hot-dipped galvanized.

c nhng m km.

8.3.6 CABLE TRAYS/ LADDERS

8.3.6 KHAY CP V THANG CP

Cable trays/ ladders shall be supported from

Mng v thang s c treo t mt di nhng

the soffit of structural slab, beams, etc., by

cu trc sn, , ct v.v, bng nhng gi bng

heavy-duty
brackets.

thp chu lc c trng m km.

Tray/

hot-dipped

ladder

supports

galvanized

shall

be

steel

spaced

Cc thanh treo mng/thang s c t cch

according to the number and size of cables


being carried on the tray/ ladder, but nowhere

khong tu theo s lung v kch c ca cp trong


mng/thang, nhng khng c qu 1.5m m

shall they exceed 1.5m intervals to ensure that

bo vng ca mng khng qu 1:500 vi tt c

tray sag does not exceed 1:500 with all cables.

cp bn trong.

Cables installed on cable trays/ ladders shall be

Cp lp t trn mng/ thang phi c sp xp

neatly arranged and secured to the cable trays/

gn gng v c buc cht vo mng/thang bng

ladder by cable ties at intervals of not exceeding


1m.

cable ties vi khong cch khng qu 1m.

8.3.7 FLUSH FLOOR TRUNKING SYSTEM

8.3.7 H THNG MNG CP T SN

During the construction stage, the contractor

Trong sut qu trnh thi cng, nh thu phi lun

shall take into consideration a maximum space


of 35 to 45% to allow for future expansion. The

lun ch n khong trng ln nht cho php l


35% n 45% cho vic m rng trong tng lai.

contractor must also take note that upon

Nh thu phi cng ch rng khong trn xuyn

passing through a junction box, the trunking

qua hp ni, khong trng mng cp c cho

space is deemed reduced by at least 50%.

rng gim xung t nht 50%.

The layout design of the flushfloor trunking

Mt bng b tr ca h thng mng cp t sn s

system is either of fish, comb or grid design


configuration. The recommended spacing of

bao gm cc dng nh xng c, hnh ci lc


hay hnh li. Khong khng c ngh l

the fish, comb or grid is between 2000-

2000-3500mm. Khong khng ti a ny cng p

3500mm. This maximum spacing also applies

dng cho t hp ni n hp ni, mng cp n

to junction box-to-junction box, trunking-totrunking and service outlet box to service outlet

mng cp v t hp ng ra phc v n cc hp
ng ra phc v. Thit k h thng mng cp t

box. The design shall include flushfloor trunking

sn cng bao gm mng cp t sn chy dc treo

running along the wall perimeter of the office


area, connecting to the fish or comb or grid

chu vi tng ca khu vc vn phng, kt ni n h


thng mng cp dng hnh xng c, hnh ci

trunking

lc hay hnh li. Khong cc ngh gia h

configuration.

The

recommended

distance between the said flushfloor trunking

thng mng cp t sn v chu v tng ca khu

and the perimeter wall of the office area shall be


1000mm. Junction boxes shall be used for all

vc vn phng s l 1000mm. Hp ni s s dng


cho tt c cc gc/ cc ch giao nhau ca h thng

the bends/ intersections of the flushfloor

mng cp t sn.

trunking system.
It is recommended that all wiring terminations at
The English language version prevails
SECTION 8/VISTA VERDE SPECS/ELECT

Tt c cc dy dn u ni ti trm lm vic s d
u tin s dng ting Anh khi c tranh chp

8/11

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

workstations be flexible to enable relocation of

dng di chuyn cc hp ng ra phc v trong vng

the floor service outlet boxes within 4 meters

4m theo chiu di cng mng cp. Sau khi lp hon

along the trunking run. Cables laid complete

chnh cp vi cc b ni, phi tin hnh kim tra

with termination shall


requirements specified.

nh c yu cu.

be

tested

to

the

8.3.8 APPLICATION

8.3.8 NG DNG

Cable ladders, trays and trunking for indoor

Thang, mng v trunking lp t trong nh s l loi

installation shall be electro-galvanised steel with

thp m km bng in c ph lp bt epoxy tnh

electrostatic epoxy power coating of 45 micron


and for outdoor application shall be hot-dipped

in dy 45 micro v lp ngoi tri s l loi thp


nhng m km theo ASTM A386.

galvanised steel to ASTM A386 finish.


8.3.9 PAINTING

8.3.9 CNG TC SN

All brackets shall be painted with two coats of

Cc gi s c sn hai lp lt v ti thiu mt

primer and minimum one coat of final finish to


match the building finish.

lp cui ph hp vi mu sn cui ca to nh.

All electro-galvanised conduits, trunkings, cable


trays and ladder shall also be painted with two

Tt c cc ng dn, trunking, mng v thang m


km bng in cng s c sn bng hai lp lt

coats of primer and minimum one coat of final

v ti thiu mt lp cui nh sau:

finish be as follows:Electrical

ORANGE

CAM

in

Public Address/ Emergency


Voice Communication
GREY

H thng thng bo/ thng bo khn

Telephone

WHITE

in thoi

TRNG

Security

As background colour

H thng an ninh

Mu nn

Data

BLUE

D liu

XANH DNG

MATV/CATV

GREEN

H thng MATV/CATV

XANH L

XM

or any other colour as specified by the

Hay nhng mu khc c Qun l K thut ph

Engineer.

duyt.

All hot-dipped galvanised conduits, trunking,


cable trays and ladders shall be colour banded

Tt c cc ng dn, trunking, mng, thang c


nhng m km s c nh du mu vi khong

at intervals not exceeding 5m and wherever

cch khng qu 5m v nhng ni cn thit, ch

necessary, at bends, tees, etc. and where they


pass from one room or zone to another.

cong, ch chia, v.v v nhng ni chng i t phng


hay khu vc ny qua mt khu vc khc .

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/12

J. Roger Preston Vietnam Co., Ltd


SECTION 8 CONDUITS&ACCESSORIES, CABLE TRUNKING, CABLE TRAYS MC 8 - NG IN V PH KIN, MNG CP, KHAY CP

All metal and PVC trunking/ conduits installed in

Cc ng dn/ trunking bng nha v kim loi lp

general view of the public shall be painted with

t trong tng th chung s c sn mt lp ph

one coat of final finish to match the wall/ ceiling

hp vi tng/ trn hay cc mu khc c Qun

colour or any other colour as specified by the


Engineer.

l K thut ph duyt.

The English language version prevails


SECTION 8/VISTA VERDE SPECS/ELECT

u tin s dng ting Anh khi c tranh chp


8/13