Professional Documents
Culture Documents
'13SRK-T-138
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
INVERTER WALL MOUNTED TYPE
RESIDENTIAL AIR-CONDITIONER
(Split system, air to air heat pump type)
DXK32ZL-S
TECHNICAL MANUAL
'10 SRK-T-105
'13 SRK-T-138
CONTENTS
1. SPECIFICATION
........................................................................................
2. EXTERIOR DIMENSIONS
.........................................................................
(1) Indoor unit
..........................................................................................
3.
4.
5.
6.
3
4
4
7. CAPACITY TABLE
...................................................................................
8. APPLICATION DATA ..................................................................................
(1) Installation of indoor unit ......................................................................
(2) Installation of outdoor unit
..................................................................
9. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ...............
(1) Operation control function by remote control ......................................
(2) Unit ON/OFF button
...........................................................................
(3) Auto restart function
.........................................................................
(4) Custom cord switching procedure .......................................................
(5) Selection of the annual cooling function ..............................................
(6) Flap and louver control ...........................................................................
19
23
30
30
31
31
31
32
32
33
34
35
35
36
43
18
19
(1) Cautions
............................................................................................. 43
(2) Items to check before troubleshooting ................................................. 43
(3)
(4)
(5)
(6)
(7)
Troubleshooting procedure (If the air conditioner does not run at all) ........
.....................
Troubleshooting procedure (If the air conditioner runs)
Self-diagnosis table .............................................................................
Service mode (Trouble mode access function) ...................................
Inspection procedures corresponding to detail of trouble ....................
-
1-
-
43
44
45
46
54
'10 SRK-T-105
'13 SRK-T-138
......................................................................................... 63
2-
-
'13 SRK-T-138
1. SPECIFICATION
Model
Item
Power source
Nominal cooling capacity (range)
Nominal heating capacity (range)
Cooling
Powe
consumption
Heating
Max power consumption
Cooling
Running
current
Heating
Inrush current, max current
Operation
Cooling
data
Power factor
Heating
EER
Cooling
COP
Heating
Cooling
Sound power level
Heating
Cooling
Sound pressure level
Heating
Silent mode sound pressure level
Exterior dimensions (Height x Width x Depth)
kW
kW
kW
A
%
dB(A)
mm
Exterior appearance
( Munsell colour )
Fine snow
( 8.0Y 9.3/0.1 ) near equivalent
Net weight
Compressor type & Q'ty
Compressor motor (Starting method)
Refrigerant oil (amount, type)
Refrigerant (Type, amount, pre-charge length)
Heat exchanger
Refrigerant control
Fan type & Q'ty
Fan motor (Starting method)
Cooling
Air flow
Heating
Available external static pressure
Outside air intake
Air filter, Quality / Quantity
Shock & vibration absorber
Electric heater
Remote control
Operation
Room temperature control
control
Operation display
kg
kW
kg
W
3
m /min
Pa
Stucco white
( 4.2Y 7.5/1.1 ) near equivalent
15
91
Wireless-Remote control
Microcomputer thermostat
RUN: Green , TIMER: Yellow , HI POWER: Green ,ECONO: Orange
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
Safety equipments
Refrigerant piping size ( O.D )
Connecting method
Attached length of piping
Installation
Insulation for piping
data
Refrigerant line (one way) length
Vertical height diff. between O.U. and I.U.
Drain hose
Drain pump, max lift height
Recommended breaker size
L.R.A. (Locked rotor ampere)
Connection wiring
Size x Core number
IP number
Standard accessories
Option parts
mm
m
m
m
mm
A
A
20
13.3 / 12.7 / 12.2 (220/ 230/ 240 V)
1.5mm2 x 4 cores ( Including earth cable ) / Terminal block ( Screw fixing type )
IPX0
IPX4
Mounting kit, Clean filter ( Allergen clear filter x 1, Photocatalytic washable deodorizing filter x 1 )
Interface kit ( SC-BIKN-E )
DB
WB
DB
WB
Cooling
27C
19C
35C
24C
Heating
20C
7C
6C
Operation
Standards
ISO5151-T1
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z235
-
-
49.5
412X18Slot hole
106
244
349
Installation plate
6-5X17.5Slot hole
53.5
Service space 50
46
225
221.5
25
Unit
A
633.5
703.5
792
25
50
Space for installation and service when viewing from the front
50
886
610
450
1098
244
299
77
106
Service space
64
55
100
318
248
55
Symbol
A
B
C
D
E
F
G
60
9
4
43.5
15.8858"
Flare
6.3514"
Flare
65
65
VP16
17.3
19
Unit:mm
120
Option
60
Content
Gas piping
Liquid piping
Hole on wall for right rear piping
Hole on wall for left rear piping
Drain hose
Outlet for wiring
Outlet for pipingon both side
150
1090
8.5
301.8
55
44.5
65 Service space
43
44.5
7.7
15Service space
4
19
'13 SRK-T-138
2. EXTERIOR DIMENSIONS
(1) Indoor unit
Model DXK32ZL-S
RKW000Z402 A
1300
20
40
20
40
10
410
370
55
60
262
190
76
580
970
325
41
60
200
50
55
103
40
15
15
574
626
Intake
L2
50
50
Outlet
L3
Service
space
Intake
L1
L4
30front
45side
50back
27
195
B
C
D
E
110
70
A
51
195
Content
Service valve connection of the
15.8858"Flare
attached connecting pipegas side
Service valve connectionliquid side 6.3514"Flare
Pipecable draw-out hole
203places
Drain discharge hole
Anchor bolt hole
M104places
150
15
103
Terminal block
38
110
50
50
50
Symbol
41
67
L1
L2
L3
L4
Dimensions
Examples of
installation
Open
300
100
250
Open
250
150
250
Unit:mm
250
500
Open
100
Notes
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
(3) Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly
to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the rear panel.
'13 SRK-T-138
RCR000Z006
'13 SRK-T-138
150
Unit: mm
60
17.3
-
'13 SRK-T-138
Exposed mounting
48
0.3mm22 cores.
Upper part
Lower case
LCD
Lower part
TEMP
ON/OFF
Upper
Sheath
Sheath
Upper
Upper cace
Upper cace
Board
X
120
Exterior appearance
(Munsell color)
Board
X
Lower
Wiring
In case of pulling out from
upper left
X, Y Terminal block
Attach M3 screw
with washer
Lower Wiring
In case of pulling out from center
Pearl White
(N8.5) near equivalent
Embedded mounting
X wiring : 170mm
Y wiring : 190mm
Wall surface
120
Remote
control
outline
46
23
45
42
44
11.5
Wiring oulet
Electrical box
Not included
120
83.5
Wiring
11
Installation hole
9.55 Slot hole 4places
19
Unit:mm
Wiring specifications
(1) If the prolongation is over 100m, change to the size below.
But, wiring in the remote control case should be under 0.5mm2. Change the wire size outside of
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.
Length
Wiring thickness
100 to 200m
Under 300m
Under 400m
Under 600m
0.5mm22 cores
0.75mm22 cores
1.25mm22 cores
2.0mm22 cores
PJZ000Z274
-
-
Th21
Th22
-
HEAT
EXCHANGER
SC-BIKN-E
INTERFACE KIT
Th3
Th1
CNS
CNF
CNG
CNE
BK L
RD
WH SN
YG G
DISPLAY
8
WIRELESS RECEIVER
BACK-UP SW
F
250V
3.15A
Va
DS
PRINTED
CIRCUIT
BOARD
2N
RD
BK
WH
Y
BL
HEAT
EXCHANGER
CNU
1
3
4
5
6
CNX2
CNX1
FMI
SM1
LM2
LM1
SIGNAL WIRE
POWER WIRES
TO OUTDOOR UNIT
Power source
220230240V 50Hz
2N
Item
Fuse
Terminal block
F
T
Yellow
YG YellowGreen
White
WH
Red
Blue
BL
RD
Black
BK
Color Marks
Mark
Color
Varistor
Diode stack
DS
Va
Humidity sensor
Th3
LM1,2
Th21,2
Flap motor
Louver motor
SM1
Th1
Fan motor
Description
FMI
CNE-CNX2 Connector
'13 SRK-T-138
3. ELECTRICAL WIRING
(1) Indoor unit
Model DXK32ZL-S
RWA000Z402 A
POWER WIRES
SIGNAL WIRE
TO INDOOR UNIT
-
YG
RD
WH
BK
SIN
RIN
RD
M
FMo2
M
FMo1
20S
17.5
32
2.5
30
TH4
1.5
TH3
EEV
CNEEV WH
F3 250V 3.15A
ACTIVE
FILTER
UNIT
1.5mm2 x 4
TH2
CNTH BK
SWITCHING
POWER
CIRCUIT
250V 20A
F8
PWB ASSYMAINPWB1
F1
indoor-outdoor
wire size x number
CNFAN
WH
250V 3.15A
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit.
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen
along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
C-2
CNSUB
WH
WH
WH
WH
CNFAN2
CNFAN0
WH
C-1 RD
S-2
S-1 WH
CNMAIN
WH
S0 WH
CN20V
WH
R
R0 BK
CN20V
WH
Model
F1
RD WH
CN20S CNFAN1
CNA
WH
YG G1
YG G3
WH
FUSE BK
250V 20A
YG
BK
250V 1A
YE
T1
TB2
TERMINAL
BLOCK
TB1
PWB ASSYSUBPWB2
F2
TERMINAL
BLOCK
250V 1A
OR
T2
POWER
220230240V 50Hz
250V 20A
F2
POWER
TRANSISTOR
WH
BK
RD
CM
Red
White
Yellow
YellowGreen
WH
Y
YG
Orange
OR
RD
Brown
BR
Color
Black
BK
Mark
TH4
20S
TH3
Terminal block
TH2
TB1,2
Reactor
Fan motor 2
Fan motor 1
FMo2
EEV
FMo1
Connector
CN20S
CNTH
CNEEV
CNFAN1,2
Description
Compressor motor
Item
CM
'13 SRK-T-138
RWC000Z260
'13 SRK-T-138
4. NOISE LEVEL
Condition
Mike
(Indoor Unit)
Model
DXK32ZL-S
Cooling
51 dB(A)
Noise
Level
Heating
48 dB(A)
ISO-T1,JIS C9612
position as below
1m
Unit
0.8m
Mike position
(Center & Low points)
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
UVCPFCTF
2C2C
0
Mike
0
0
0
Mike
Unit
0
0
0
0.8m
Mike position
(Center & Low points)
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
(Outdoor Unit)
Model
DXC32ZL-S
Cooling
53 dB(A)
Noise
Level
Heating
54 dB(A)
0
position as below
1m
Mike
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
UVCPFCTF
2C2C
0
0
0
0
0
0
0
0
0
0
0
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
-
10 -
ISC12092
'13 SRK-T-138
Condition
Mike
(Indoor Unit)
Model
DXK32ZL-S
Cooling
51 dB(A)
Noise
Level
Heating
49 dB(A)
ISO-T1,JIS C9612
position as below
1m
Unit
0.8m
Mike position
(Center & Low points)
...... Cooling
Heating
0
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF 2C
0
Mike
0
0
Mike
position as below
0
1m
Unit
0.8m
Mike position
(Center & Low points)
0
/KF1EVCXG$CPFHTGSWGPE[
*\
(Outdoor Unit)
Model
DXC32ZL-S
Cooling
58 dB(A)
Noise
Level
Heating
60 dB(A)
Mike
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
2C
UVCPFCTF
2C
0
0
0
0
0
0
0
0
0
0
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
-
11 -
ISC12092
'13 SRK-T-138
Condition
Mike
(Indoor Unit)
Model
DXK32ZL-S
Cooling
47 dB(A)
Noise
Level
Heating
46 dB(A)
ISO-T1,JIS C9612
position as below
1m
Unit
0.8m
Mike position
(Center & Low points)
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
2C
UVCPFCTF
2C
0
Mike
0
0
0
0
0
0
0
Mike
position as below
1m
Unit
0.8m
Mike position
(Center & Low points)
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
(Outdoor Unit)
Model
DXC32ZL-S
Cooling
52 dB(A)
Noise
Level
Heating
60 dB(A)
Mike
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
2C
UVCPFCTF
2C
0
0
0
0
0
0
0
0
0
0
0
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
-
12 -
ISC12092
'13 SRK-T-138
Condition
Mike
(Indoor Unit)
Model
DXK32ZL-S
Cooling
41 dB(A)
Noise
Level
Heating
42 dB(A)
ISO-T1,JIS C9612
position as below
1m
Unit
0.8m
Mike position
(Center & Low points)
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
2C
UVCPFCTF
2C
0
Mike
0
0
0
0
0
0
0
Mike
position as below
1m
Unit
0.8m
Mike position
(Center & Low points)
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
(Outdoor Unit)
Model
DXC32ZL-S
Cooling
50 dB(A)
Noise
Level
Heating
54 dB(A)
Mike
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
2C
UVCPFCTF
2C
0
0
0
0
0
0
0
0
0
0
0
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
-
13 -
ISC12092
'13 SRK-T-138
Condition
Mike
(Indoor Unit)
Model
DXK32ZL-S
Cooling
26 dB(A)
Noise
Level
Heating
38 dB(A)
ISO-T1,JIS C9612
position as below
1m
Unit
0.8m
Mike position
(Center & Low points)
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
UVCPFCTF
2C
2C
0
Mike
0
0
0
0
0
0
0
Mike
position as below
1m
Unit
0.8m
Mike position
(Center & Low points)
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
(Outdoor Unit)
Model
DXC32ZL-S
Cooling
42 dB(A)
Noise
Level
Heating
51 dB(A)
Mike
...... Cooling
Heating
0
0
5QWPF2TGUUWTG.GXGN
F$
5QWPF2TGUUWTG.GXGN
F$
UVCPFCTF
UVCPFCTF
2C
2C
0
0
0
0
0
0
0
0
0
0
0
/KF1EVCXG$CPFHTGSWGPE[
*\
/KF1EVCXG$CPFHTGSWGPE[
*\
-
14 -
ISC12092
'13 SRK-T-138
5. PIPING SYSTEM
ModelSRK92ZL-S
DXK32ZL-S
Model
Cooling cycle
Indoor unit
Room temp.
sensor
(Th1)
Flare
connection
Heat
exchanger
sensor
(Th22)
Gas pipie
Service valve
(Gas)
Check joint
4way valve
Humidity
sensor
(Th3)
Heating cycle
Outdoor unit
Discharge pipe
temp. sensor
(TH4)
Flare connection
Accumlator
Muffler
Accumlator
Heat
exchanger
Heat
exchanger
sensor
(Th21)
Compressor
Receiver
Liquid
pipe
Outdoor air
temp. sensor
(TH3)
Electronic
expansion valve
(EEV)
Capillary tube
Service valve
(Liquid)
Strainer
Capillary tube
Strainer
15 -
Heat
exchanger
Heat
exchanger
sensor
(TH2)
'13 SRK-T-138
6. RANGE
RANGE OF
USAGE
& LIMITATIONS
6.
OF
USAGE
& LIMITATION
Model
SRK25ZJP-S1, 35ZJP-S1
SRK50ZJP-S1
DXK32ZL-S
Item
Indoor return air temperature
(Upper, lower limits)
Max. 30m
Rating 10%
Voltage at starting
Max. 6 times/h
(Inching prevention 6 minutes)
Min. 3 minutes
Selection chart
Correct
cooling and
heating capacity
accordance
with the Correction
conditions as factors
follows. as
Thefollows.
net cooling and heating capacity can be
Netthe
capacity
= Capacity
showninon
specification
obtained in the following way.
(1) Coefficient of cooling and heating capacity in relation to temperatures
Net capacity = Capacity shown on specification Correction factors as follows.
(1) Coefficient of cooling and heating capacity in relation to temperatures
1.3
1.3
1.2
1.2
Cooling
Cooling
1.1
1.1
1.0
1.0
Heating
Heating
0.9
0.9
0.8
0.8
0.7
0.7
0.6
0.6
Cooling operation
Cooling operation
Outdoor air D.B.
Outdoor
air D.B.
temperature
temperature
C D. B.
C D. B.
Applicable
Applicablerange
range
46
46
40
40
35
35
30
30
25
25
20
20
26
26
24
24
Heating operation
Heating operation
Indoor air D.B.
Indoor
air D.B.
temperature
Ctemperature
D. B.
C D. B.
00
-5-5
-10
-10
-15
-15
27
25
30
20
25
15
20
10
15
Depends
Dependson
oninstalled
installedsituation
situation
14
16
18
20
22
14
16
18
20
22
Indoor
. . ISO-T1
Indoorair
airW.B.
W.B.temperature
temperatureC
CW.B
W.B
ISO-T1Standard
StandardCondition
Condition
-15
-10
-10
-5
0
5
10
15
0
5
10
15
ISO-T1 Standard Condition
ISO-T1 Standard Condition
Outdoor air W.B. temperature C W.B.
Outdoor air W.B. temperature C W.B.
-5
16 -
'09SRK-DB-087D
'13 SRK-T-138
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
10
15
20
25
30
Cooling
1.0
0.99
0.975
0.965
0.95
0.935
Heating
1.0
1.0
1.0
1.0
1.0
1.0
-15
-10
-9
-7
-5
-3
-1
5 or more
Adjustment coefficient
0.95
0.95
0.94
0.93
0.91
0.88
0.86
0.87
0.92
1.00
8970
DXK32ZL-S
9200
DXK32ZL-S
17 -
'13 SRK-T-138
7. CAPACITY TABLE
Model
DXK32ZL-S
Cool Mode
(kW)
Air flow
Hi
21.0
3
(m /min)
Outdoor 21DB
air temp. 14WB
23DB
26DB
27DB
28DB
31DB
33DB
16WB
18WB
19WB
20WB
22WB
24WB
(kW)
Heat Mode(HC)
Outdoor
air temp.
-15WB 6.15
6.02
5.88
5.76
5.63
10 10.37 7.61 10.85 7.48 11.25 7.67 11.44 7.56 11.64 7.44 11.98 7.58 12.30 7.31
-10WB 6.96
6.84
6.75
6.58
6.44
12 10.18 7.51 10.67 7.38 11.09 7.59 11.29 7.48 11.49 7.38 11.85 7.52 12.18 7.27
-5WB
7.54
7.43
7.28
7.20
7.08
0WB
Hi
23.5
5WB
(m3/min) 6WB
7.91
7.79
7.65
7.56
7.45
10.07 9.95
9.90
9.70
9.57
9.75
14
9.99 7.40 10.48 7.28 10.93 7.51 11.13 7.41 11.34 7.31 11.72 7.47 12.06 7.23
16
9.79 7.28 10.29 7.19 10.76 7.43 10.98 7.34 11.18 7.25 11.58 7.41 11.93 7.18
18
9.59 7.18 10.09 7.07 10.58 7.34 10.81 7.26 11.02 7.17 11.43 7.36 11.79 7.13
20
9.38 7.06 9.88 6.98 10.40 7.26 10.64 7.19 10.85 7.09 11.28 7.29 11.65 7.07
22
9.16 6.96 9.67 6.87 10.21 7.17 10.47 7.11 10.68 7.00 11.13 7.24 11.50 7.02
24
8.94 6.84 9.45 6.77 10.02 7.07 10.29 7.01 10.50 6.93 10.97 7.17 11.35 6.97
26
8.72 6.72 9.22 6.65 9.82 6.98 10.10 6.94 10.32 6.86 10.80 7.11 11.19 6.89
28
8.49 6.59 8.99 6.54 9.62 6.90 9.91 6.86 10.13 6.78 10.63 7.01 11.03 6.83
30
8.25 6.48 8.76 6.42 9.41 6.80 9.71 6.78 9.93 6.71 10.45 6.95 10.86 6.78
32
8.01 6.35 8.51 6.31 9.20 6.71 9.51 6.69 9.73 6.62 10.27 6.88 10.68 6.72
34
7.77 6.23 8.27 6.19 8.98 6.61 9.31 6.59 9.52 6.53 10.08 6.82 10.50 6.66
35
7.64 6.17 8.14 6.13 8.86 6.56 9.20 6.55 9.42 6.49 9.99 6.78 10.41 6.63
36
7.51 6.11 8.01 6.07 8.75 6.50 9.09 6.51 9.31 6.45 9.89 6.75 10.32 6.60
38
7.26 5.97 7.75 5.94 8.52 6.41 8.88 6.41 9.09 6.35 9.69 6.68 10.12 6.53
39
7.12 5.91 7.62 5.88 8.40 6.35 8.77 6.37 8.98 6.31 9.59 6.63 10.03 6.50
18 -
ISC12091
RKW012A400
19 -
Before installation check that the power supply matches the air conditioner.
CAUTION
Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed.
5 cm minimum
from the wall
Installation board
For installation work, be careful not to get injured with the heat
exchanger, piping flare portion or screws etc.
Be sure to insulate the refrigerant pipes so as not to condense the
ambient air moisture on them.
Insufficient insulation can cause condensation, which can lead to moisture
damage on the ceiling, floor, furniture and any other valuables.
When perform the air conditioner operation (cooling or drying
operation) in which ventilator is installed in the room. In this case,
using the air conditioner in parallel with the ventilator, there is the
possibility that drain water may backflow in accordance with the
room lapse into the negative pressure status. Therefore, set up the
opening port such as incorporate the air into the room that may
appropriate to ventilation (For example; Open the door a little). In
addition, just as above, so set up the opening port if the room lapse
into negative pressure status due to register of the wind for the high
rise apartment etc.
Be sure to perform air tightness test by pressurizing with nitrogen
gas after completed refrigerant piping work.
If the density of refrigerant exceeds the limit in the event of refrigerant
leakage in the small room, lack of oxygen can occur, which can cause
serious accidents.
Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone lines ground lead. Incorrect grounding can cause unit faults
such as electric shocks due to short-circuiting.
(Install at location that meets the following conditions, after getting approval from the customer)
Indoor unit
WARNING
Do not run the unit with removed panels or protections.
Do not perform any change of protective device itself or its setup
Touching rotating equipments, hot surfaces or high voltage parts can cause condition.
personal injury due to entrapment, burn or electric shocks.
The forced operation by short-circuiting protective device of pressure
switch and temperature controller or the use of non specified component
can cause fire or burst.
Do not put the drainage pipe directly into drainage channels where
poisonous gases such as sulphide gas can occur.
Poisonous gases will flow into the room through drainage pipe and
seriously affect the users health and safety. This can also cause the
corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
Ensure that no air enters in the refrigerant circuit when the unit is
installed and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit
becomes too high, which can cause burst and personal injury.
BEFORE INSTALLATION
Keep the installation manual together with owners manual at a place where
any user can read at any time. Moreover if necessary, ask to hand them to a
new user.
For installing qualified personnel, take precautions in respect to themselves by
using suitable protective clothing, groves, etc., and then perform the
installation works.
Please pay attention not to fall down the tools, etc. when installing the unit at
the high position.
If unusual noise can be heard during operation, consult the dealer.
The meanings of Marks used here are as shown on the right:
WARNING
Read the SAFETY PRECAUTIONS carefully first of all and strictly follow it
during the installation work in order to protect yourself.
The precautionary items mentioned below are distinguished into two levels,
WARNING and
CAUTION .
WARNING : Wrong installation would cause serious consequences such
as injuries or death.
CAUTION : Wrong installation might cause serious consequences
depending on circumstances.
Both mentions the important items to protect your health and safety so strictly
follow them by any means.
Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the maintenance
methods of this equipment to the user according to the owners manual.
SAFETY PRECAUTIONS
INSTALLATION
MANUAL FOR INDOOR UNIT
Model DXK32ZL-S
'13 SRK-T-138
Air-cleaning filters
Filter holders
(Attached to the front panel of indoor unit)
Piping cover
(for insulation of connection piping)
Knife
Saw
Tape measure
Hammer
Spanner wrench
Torque wrench
Pipe bender
10
11
12
13
Designed specifically
for R410A
(
)
specifically
( Designed
)
for R410A
~ 82.0Nm
( 14.0
(1.4 ~ 8.2kgfm) )
Inclination plate
Sleeve
Putty
Qty
Sealing plate
Option parts
Wood screws
(for remote control switch holder 3.5 X 16mm)
10
Tapping screws
(for installation board 4 X 25mm)
Qty
Installation board
(Attached to the rear of the indoor unit)
Before installation check that the power supply matches the air conditioner.
BEFORE INSTALLATION
Mounting
board
Bolt
(M6 12)
Mounting
board
Max.10
Nut
(M6)
Outdoor side
Drain hose
Pipings
Indoor side
Turn to
tighten
Outdoor side
Installed state
106
53.5
Piping hole (65)
For bolt anchor
and nut anchor
349
50
Space
50 for service
25
Right-hand-side piping
Left
Left downward
Left
Downward rear
Rear
Right
Piping is possible in the rear, left, left rear, left downward, right or downward direction.
Left-hand-side piping
106
(Unit : mm)
Insert the drain cap which was removed Insert the drain hose securely, making
at procedure 2 securely using a
rotate. And install the screw.
hexagonal wrench etc.
Note: Be careful that If it is not Inserted
Note: Be careful that If it is not Inserted
securely, water leakage may
securely, water leakage may occur.
occur.
50
299
Space
for service 100
77
Piping for Gas 633.5
Piping for Liquid 703.5
Drain hose 772 (16)
886
450
Indoor unit
Installation board
Wood screws
Matters of special notice when piping from left or central/rear of the unit.
[Top view]
[Drain hose changing procedures]
Indoor side
65
b Top
putty
Outdoor side
putty
Indoor side
Installation board
10 cm m
inim
from the um
wall
CAUTION
5 cm minimum
from the wall
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
A place where the air conditioner can be received the signal surely during operating the wireless remote control.
Places where there is no affected by the TV and radio etc.
Do not place where exposed to direct sunlight or near heat devices such as a stove.
Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed.
A solid place where the unit or the wall will not vibrate.
A place where there will be enough space for servicing. (Where space mentioned below can be secured)
Where wiring and the piping work will be easy to conduct.
The place where receiving part is not exposed to the direct rays of the sun or the strong rays of the street lighting.
A place where it can be easily drained.
A place separated at least 1m away from the television or the radio. (To prevent interference to images and sounds.)
Places where this unit is not affected by the high frequency equipment or electric equipment.
Avoid installing this unit in place where there is much oil mist.
Places where there is no electric equipment or household under the installing unit.
Indoor unit
(Install at location that meets the following conditions, after getting approval from the customer)
65 Space
for service
8.5
49.5
221.5
44.5
20 -
44.5
301.8
15 Space
for service 7.7
corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
Ensure that no air enters in the refrigerant circuit when the unit is
installed and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit
becomes too high, which can cause burst and personal injury.
'13 SRK-T-138
Wall
Installation board
Indoor unit
Installation Steps
Press
Remove
21 -
0.0 - 0.5
0.0 - 0.5
0.0 - 0.5
9.52
12.7
15.88
1.0 - 1.5
1.0 - 1.5
1.0 - 1.5
2.0 - 2.5
2.0 - 2.5
1.5 - 2.0
CAUTION
To remove / To install
Approx. 80
Terminal block
Installing
Remove the air filter.
Cover the unit with the front panel.
Tighten the screw (A) 2pcs / screw
(B) 3pcs to fix the front panel.
Install the air filter.
Install the air inlet panel.
Screw (B)
Drain hose
When it is exposed indoor.
Vinyl tape
Screw (A)
Screw (B)
Air filter
Front panel
1. Open the air inlet panel and remove the air filters.
2. Install the filter holders, with the air-cleaning filters installed in the holders.
In the air conditioner.
Each air-cleaning filter can be installed in the left or right filter holder.
3. Install the air filters and close the inlet panel.
Latch
Screw (B)
Screw (A)
Connection wiring,
Earth wiring
Outer tape
Drain hose
Wood screw
Clamp
Refrigerant piping
Cover the indoor unit s flare-connected joints, after they are checked for a gas leak,
with an indoor unit heat insulating material and then wrap them with a tape with an
attached insulation pad placed over the heat insulating materials slit area.
CAUTION
Cover the coupling with insulator and then cover it with tapes.
Removing
Remove the air inlet panel.
Remove the screw (A) 2pcs / screw
(B) 3pcs fixing to the front panel.
Remove the 3 latches in the upper
section of the front panel and then
remove the front panel from the unit.
0.0 - 0.5
6.35
Liquid side
Gas side
Indoor
Wavy
Copper pipe
Measurement B (mm)
Connection
Odor from
the gutter
Wall
Gutter
Pour water to the drain pan located under the heat exchanger, and ensure that the water is discharged outdoor.
When the extended drain hose is indoor, always use a shield pipe (to be arranged by the user) and ensure it is
thermally insulated.
Shield pipe
Drainage
Since this air conditioner has been designed to collect dew drops on the rear
surface to the drain pan, do not attach the power cord above the gutter.
Flaring
block
Measurement B
Flaring work
Dimension A
Liquid side 6.35 : 9.1 (mm)
Gas side 9.52 : 13.2 (mm)
12.7 : 16.6 (mm)
15.88 : 19.7 (mm)
CAUTION
1 Push up at the marked portion of the indoor unit base lower latch, and slightly
pull it toward you. (both right and left hand sides) (The indoor unit base lower
latch can be removed from the installation board)
2 Push up the indoor unit upward. So the indoor unit will be removed from the
installation board.
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them.
Remove the flared nuts. (on both liquid and gas sides)
Indoor
Preparation
Installation board
Latch (2 locations)
90 0.5
RKW012A400
'13 SRK-T-138
CAUTION
To remove / To install
22 -
6 Battery
Cover
Approx. 80
5 Wood screws
3.5 X 16
Wiring Clamp
1 2N 3
Terminal block
CAUTION
1
2
3
4
Lid
Screw (B)
Screw (A)
Screw (B)
Front panel
Air-cleaning
filter
In connecting an interface, connect to the respective terminal securely with the connection harness
supplied with an optional Interface connection kit SC-BIKN-E and fasten the connection harness
onto the indoor control box with the clamp supplied with the kit.
For more details, please refer to the users manual of your Interface connection kit SC-BIKN-E.
Screw
Control cover
CNS terminal
Test run
After installation
Check the following points again after completion of the installation, and before turning on the power. Conduct a test run again and ensure that the unit operates properly.
At the same time, explain to the customer how to use the unit and how to take care of the unit following the users manual.
Filter holder
1. Open the air inlet panel and remove the air filters.
2. Install the filter holders, with the air-cleaning filters installed in the holders.
In the air conditioner.
Each air-cleaning filter can be installed in the left or right filter holder.
3. Install the air filters and close the inlet panel.
Screw (B)
Screw (A)
Installing
Remove the air filter.
Cover the unit with the front panel.
Tighten the screw (A) 2pcs / screw
(B) 3pcs to fix the front panel.
Install the air filter.
Install the air inlet panel.
'13 SRK-T-138
23 -
RCR012A101
Ventilate the working area well in the event of refrigerant leakage during
installation.
If the refrigerant comes into contact with naked flames, poisonous gas is produced.
Use the prescribed pipes, flare nuts and tools for R410A.
Using existing parts (for R22 or R407C) can cause the unit failure and serious
accidents due to burst of the refrigerant circuit.
Tighten the flare nut by torque wrench with specified method.
If the flare nut were tightened with excess torque, this may cause burst and
refrigerant leakage after a long period.
Do not open the operation valves for liquid line and gas line until
completed refrigerant piping work, air tightness test and evacuation.
If the compressor is operated in state of opening operation valves before
completed connection of refrigerant piping work, air can be sucked into refrigerant
circuit, which can cause bust or personal injury due to anomalously high pressure
in the refrigerant.
The electrical installation must be carried out by the qualified electrician
in accordance with the norm for electrical work and national wiring
regulation, and the system must be connected to the dedicated circuit.
Power supply with insufficient capacity and incorrect function done by improper
work can cause electric shocks and fire.
Be sure to shut off the power before starting electrical work.
Failure to shut off the power can cause electric shocks, unit failure or incorrect
function of equipment.
Be sure to use the cables conformed to safety standard and cable
ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production or fire.
This appliance must be connected to main power supply by means of a
Use the circuit breaker for all pole correct capacity. Circuit breaker
Take care when carrying the unit by hand.
If the unit weights more than 20kg, it must be carried by two or more persons. Do
should be the one that disconnect all poles under over current.
Using the incorrect circuit breaker, it can cause the unit malfunction and fire.
not carry by the plastic straps, always use the carry handle when carrying the unit
Install isolator or disconnect switch on the power supply wiring in
by hand. Use gloves to minimize the risk of cuts by the aluminum fins.
Dispose of any packing materials correctly.
accordance with the local codes and regulations.
The isolator should be locked in OFF state in accordance with EN60204-1.
Any remaining packing materials can cause personal injury as it contains nails and
After maintenance, all wiring, wiring ties and the like, should be returned
wood. And to avoid danger of suffocation, be sure to keep the plastic wrapper
to their original state and wiring route, and the necessary clearance from
away from children and to dispose after tear it up.
Be sure to insulate the refrigerant pipes so as not to condense the
all metal parts should be secured.
Secure a space for installation, inspection and maintenance specified in
ambient air moisture on them.
Insufficient insulation can cause condensation, which can lead to moisture
the manual.
Insufficient space can result in accident such as personal injury due to falling from
damage on the ceiling, floor, furniture and any other valuables.
Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone lines ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.
CAUTION
Ensure that no air enters in the refrigerant circuit when the unit is
Do not bundling, winding or processing for the power cord. Or, do not
installed and removed.
deforming the power plug due to tread it.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit
This may cause fire or heating.
Do not run the unit with removed panels or protections.
becomes too high, which can cause burst and personal injury.
Do not processing, splice the power cord, or share a socket with other power plugs.
Touching rotating equipments, hot surfaces or high voltage parts can cause
This may cause fire or electric shock due to defecting contact, defecting insulation
personal injury due to entrapment, burn or electric shocks.
and over-current etc.
Keep the installation manual together with owners manual at a place where any user can read at any time.
Moreover if necessary, ask to hand them to a new user.
For installing qualified personnel, take precautions in respect to themselves by using suitable protective
clothing, groves, etc., and then perform the installation works.
Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
If unusual noise can be heard during operation, consult the dealer.
The meanings of Marks used here are shown as follows:
WARNING
Read the SAFETY PRECAUTIONS carefully first of all and strictly follow it during the installation work in order
to protect yourself.
The precautionary items mentioned below are distinguished into two levels,
WARNING and
CAUTION .
WARNING : Wrong installation would cause serious consequences such as injuries or death.
CAUTION : Wrong installation might cause serious consequences depending on circumstances.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the
operating methods as well as the maintenance methods of this equipment to the user according to the owners
manual.
SAFETY PRECAUTIONS
This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to the respective installation manuals supplied with the units.
When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power
supply voltage and etc.) and installation spaces.
Model DXC32ZL-S
The right hand side of the unit as viewed from the fro
A person carrying the right hand side must take heed
carrying the left hand side must hold with his right han
the front panel of the unit and with his left hand the c
2) Portage
1) Delivery
CAUTION
(1) If the unit is installed in the area where the snow will a
The bottom plate of unit and intake, outlet may be bloc
'13 SRK-T-138
n.
protective
ad at any time.
or units, power
ANT USED
012A101
24 -
2
1
1
Option parts
Sealing plate
Sleeve
Inclination plate
Putty
Drain hose (extension hose)
Piping cover
f
(for insulation of connection piping)
a
b
c
d
e
1
1
1
1
1
1
Qty
1
2
3
4
5
6
7
8
CAUTION
(Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)
When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity center position.
If not properly balanced, the unit can be thrown off-balance and fall.
Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant.
A cylinder containing R410A has a pink indication mark on the top.
A unit designed for R410A has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.
The processed dimension of the flared part of a refrigerant pipe and a flare nuts parallel side measurement have also been altered to raise strength against pressure.
Accordingly, you are required to arrange dedicated R410A tools listed in the table on the left before installing or servicing this unit.
Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to change, which results in performance degradation.
In charging refrigerant, always take it out from a cylinder in the liquid phase.
All indoor units must be models designed exclusively for R410A. Check connectable indoor unit models in a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)
Qty
Do not install the outdoor unit in a location where insects and small
animals can inhabit.
Insects and small animals can enter the electric parts and cause damage or fire.
Instruct the user to keep the surroundings clean.
Do not use the base flame for outdoor unit which is corroded or damaged
due to long periods of operation.
Using an old and damage base flame can cause the unit falling down and cause
personal injury.
Do not use any materials other than a fuse with the correct rating in the
location where fuses are to be used.
Connecting the circuit with copper wire or other metal thread can cause unit
failure and fire.
Do not touch any buttons with wet hands.
It can cause electric shocks.
Do not touch any refrigerant pipes with your hands when the system is in
operation.
During operation the refrigerant pipes become extremely hot or extremely cold
depending the operating condition, and it can cause burn injury or frost injury.
Do not touch the suction or aluminum fin on the outdoor unit.
This may cause injury.
Do not put anything on the outdoor unit and operating unit.
This may cause damage the objects or injury due to falling to the object.
Do not use the unit for special purposes such as storing foods, cooling
precision instruments and preservation of animals, plants or art.
Do not clean up the unit with water.
Use the circuit breaker for all pole correct capacity. Circuit breaker
Take care when carrying the unit by hand.
If the unit weights more than 20kg, it must be carried by two or more persons. Do
should be the one that disconnect all poles under over current.
Using the incorrect circuit breaker, it can cause the unit malfunction and fire.
not carry by the plastic straps, always use the carry handle when carrying the unit
Install isolator or disconnect switch on the power supply wiring in
by hand. Use gloves to minimize the risk of cuts by the aluminum fins.
Dispose of any packing materials correctly.
accordance with the local codes and regulations.
The isolator should be locked in OFF state in accordance with EN60204-1.
Any remaining packing materials can cause personal injury as it contains nails and
After maintenance, all wiring, wiring ties and the like, should be returned
wood. And to avoid danger of suffocation, be sure to keep the plastic wrapper
to their original state and wiring route, and the necessary clearance from
away from children and to dispose after tear it up.
Be sure to insulate the refrigerant pipes so as not to condense the
all metal parts should be secured.
Secure a space for installation, inspection and maintenance specified in
ambient air moisture on them.
Insufficient insulation can cause condensation, which can lead to moisture
the manual.
Insufficient space can result in accident such as personal injury due to falling from
damage on the ceiling, floor, furniture and any other valuables.
the installation place.
Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone lines ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.
CAUTION
Ensure that no air enters in the refrigerant circuit when the unit is
Do not bundling, winding or processing for the power cord. Or, do not
installed and removed.
deforming the power plug due to tread it.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit
This may cause fire or heating.
Do not run the unit with removed panels or protections.
becomes too high, which can cause burst and personal injury.
Do not processing, splice the power cord, or share a socket with other power plugs.
Touching rotating equipments, hot surfaces or high voltage parts can cause
This may cause fire or electric shock due to defecting contact, defecting insulation
personal injury due to entrapment, burn or electric shocks.
and over-current etc.
2 I
o
15.88
Flare
15.88
15.88
Gas pipe
6.35
6.35
6.35
Flare
Liquid pipe
CAUTION
Restrictions
(1) If the unit is installed in the area where the snow will accumula
The bottom plate of unit and intake, outlet may be blocked by s
'13 SRK-T-138
25 -
rroded or damaged
e damage or fire.
r drying operation)
e, using the air
possibility that
lapse into the
g port such as
to ventilation (For
bove, so set up the
status due to
or its setup
c shocks.
at work.
le such as water
hutting the
on of dust or water.
installation,
t be pushed up
y.
paration of at least
instruction.
n.
protective
ad at any time.
Wooden pallet
Heavy
580
Outlet
200
Size
Wind
direction
Open
300
100
250
I
Open
250
150
250
II
Intake
L2
Outlet
Intake
(service
space )
L3
L1
L4
L1
L2
L3
L4
Example installation
(mm)
500
Open
100
250
III
Wind
direction
In installing the unit, fix the units legs with bolts specified on the above.
The protrusion of an anchor bolt on the front side must be kept within 15mm.
Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.
Refer to the above illustrations for information regarding concrete foundations.
Install the unit in a level area. (With a gradient of 5mm or less.) Improper installation can result in a
compressor failure, broken piping within the unit and abnormal noise generation.
190
Intake
6) Installation
5) Installation space
Over 500mm
(2) If the unit can be affected by strong wind, following measures are required.
Strong wind can cause damage of fan (fan motor), or can cause performance degradation, or can trigger
anomalous stop of the unit due to rising of high pressure.
Check the following points in light of the indoor unit specifications and the installation site.
Observe the following restrictions on unit installation and use. Improper installation can result in a compressor failure or performance degradation.
Since drain water generated by defrost control may freeze, following measures are required.
Do not execute drain piping work by using a drain elbow and drain grommets (optional parts).
[Refer to Drain piping work.]
(1) If the unit is installed in the area where the snow will accumulate, following measures are required.
The bottom plate of unit and intake, outlet may be blocked by snow.
The right hand side of the unit as viewed from the front (diffuser side) is heavier.
A person carrying the right hand side must take heed of this fact. A person
carrying the left hand side must hold with his right hand the handle provided on
the front panel of the unit and with his left hand the corner column section.
2) Portage
Pad
When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity center position.
If not properly balanced, the unit can be thrown off-balance and fall.
(Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)
Deliver the unit as close as possible to the installation site before removing it from
the packaging.
When you have to unpack the unit for a compelling reason before you haul it to
the installation point, hoist the unit with nylon slings or ropes and protection pads
so that you may not damage the unit.
1) Delivery
CAUTION
20
or units, power
410
20
ANT USED
'13 SRK-T-138
erating unit.
lling to the object.
as storing foods, cooling
mals, plants or art.
ch is corroded or damaged
6.35
Flare
15.88
Flare
15.88
15.88
0.8
O-type pipe
Pipe material*
Copper
pipe outer
diameter
6.35
15.88
45 ~ 60
15~ 20
14 ~ 18
68~ 82
6.35 (1/4")
15.88 (5/8")
150
300
Outdoor unit
Copper
pipe outer
diameter
6.35
15.88
Outdoor unit
Indoor unit
1.0 ~ 1.5
Gas side
operation valve
Check joint
0 ~ 0.5
(mm)
Edging
(For knock-out hole protection)
Nitrogen
gas
Hand
0.5MPa
Secondary side
Relief valve
Primary side
Station valve
Brazing
Catch
<N2>
Taping
1 Although outdoor and indoor units themselves have been tested for air tightness at the factory, check the connecting pipes after the installation work for air tightness
from the operation valves check joint equipped on the outdoor unit side. While conducting a test, keep the operation valve shut all the time.
a) Raise the pressure to 0.5MPa, and then stop. Leave it for five minutes to see if the pressure drops.
b) Then raise the pressure to 1.5MPa, and stop. Leave it for five more minutes to see if the pressure drops.
Tightening angle ( )
0
04
9.1
19.7
Fix both liquid and gas operation valves at the valve main bodies as illustrated on the right, and then fasten them,
applying appropriate fastening torque.
Do not apply force beyond proper fastening torque in tightening the flare nut.
First remove the five screws ( mark) of the service panel and push it down into
the direction of the arrow mark and then remove it by pulling it toward you.
The pipe can be laid in any of the following directions: side right, front, rear and downward.
Remove a knock-out plate provided on the pipe penetration to open a minimum necessary area and attach an
edging material supplied as an accessory by cutting it to an appropriate length before laying a pipe.
Carry out the on site piping work with the operation valve fully closed.
Give sufficient protection to a pipe end (compressed and blazed, or with an adhesive tape) so that water or
foreign matters may not enter the piping.
Bend a pipe to a radius as large as practical.(R100~R150) Do not bend a pipe repeatedly to correct its form.
Flare connection is used between the unit and refrigerant pipe. Flare a pipe after engaging a flare nut onto it.
Flare dimensions for R410A are different from those for conventional R407C. Although we recommend the
use of flaring tools designed specifically for R410A, conventional flaring tools can also be used by adjusting
the measurement of protrusion B with a protrusion control gauge.
The pipe should be anchored every 1.5m or less to isolate the vibration.
Tighten a flare joint securely with a double spanner.
CAUTION
O-type pipe
1.0
15.88
6.35
About brazing
Take care so that installed pipes may not touch components within a unit.
If touching with an internal component, it will generate abnormal sounds and/or vibrations.
IMPORTANT
Select refrigerant pipes of the table shown on the right wall thickness and
material as specified for each pipe size.
6.35
6.35
Liquid pipe
Gas pipe
NOTE
The use restrictions appearing in the table above are applicable to the standard pipe size combinations shown in the table below.
20m or less
20m or less
30m or less
CAUTION
Dimensional restrictions
Restrictions
Indoor unit
In installing the unit, fix the units legs with bolts specified on the above.
The protrusion of an anchor bolt on the front side must be kept within 15mm.
Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.
Refer to the above illustrations for information regarding concrete foundations.
Install the unit in a level area. (With a gradient of 5mm or less.) Improper installation can result in a
compressor failure, broken piping within the unit and abnormal noise generation.
Check the following points in light of the indoor unit specifications and the installation site.
Observe the following restrictions on unit installation and use. Improper installation can result in a compressor failure or performance degradation.
Do not execute drain piping work by using a drain elbow and drain grommets (optional parts).
[Refer to Drain piping work.]
Nitrogen
26 B
4. ELECTRICAL WIRING WO
'13 SRK-T-138
27 -
Copper
pipe outer
diameter
6.35
15.88
Tightening angle ( )
45 ~ 60
15~ 20
14 ~ 18
68~ 82
6.35 (1/4")
15.88 (5/8")
<Work flow>
Fill refrigerant
Confirm that the vacuum gauge indicator does not rise even if
the system is left for one hour or more.
Vacuuming completed
Run the vacuum pump for at least one hour after the vacuum
gauge shows 0.1MPa or lower. (76cmHg or lower)
Vacuuming begins
3.15
0.025
15
Charge hose
(Designed specifically for R410A)
Operation valve
(three-way valve)
Handle Lo
-0.1MPa
(-76cmHg)
Gauge manifold
(Designed specifically for R410A)
Handle Hi
Charge hose
(Designed specifically for R410A)
Vacuum pump adapter
(Anti-reverse flow type)
(Designed specifically for R410A)
Vacuum pump
Pressure gauge
rize
ssu
Pre
10 ~ 12
All gas pipes must be securely heat insulated in order to prevent damage from dripping water that comes from the condensation formed on them during a cooling
operation or personal injury from burns because their surface can reach quite a high temperature due to discharged gas flowing inside during a heating operation.
(2) Use a heat insulating material that can withstand 120 C or a higher temperature. Poor heat insulating capacity can cause heat insulation problems or cable
deterioration.
Improper heat insulation/anti-dew dressing can result in a water leak or dripping causing damage to household effects, etc.
Band (accessory)
Exterior tape
NOTE Put down the refrigerant volume calculated from the pipe length onto the caution label attached
on the service panel.
Since R410A refrigerant must be charged in the liquid phase, you should charge it, keeping the container
cylinder upside down or using a refrigerant cylinder equipped with a siphon tube.
Charge refrigerant always from the liquid side service port with the operation valve shut. When you find it
difficult to charge a required amount, fully open the outdoor unit valves on both liquid and gas sides and
charge refrigerant from the gas (suction) side service port, while running the unit in the cooling mode. In
doing so, care must be taken so that refrigerant may be discharged from the cylinder in the liquid phase
all the time. When the cylinder valve is throttled down or a dedicated conversion tool to change liquid
phase refrigerant into mist is used to protect the compressor, however, adjust charge conditions so that
refrigerant will gasify upon entering the unit.
In charging refrigerant, always charge a calculated volume by using a scale to measure the charge
volume.
When refrigerant is charged with the unit being run, complete a charge operation within 30minutes.
Running the unit with an insufficient quantity of refrigerant for a long time can cause a compressor failure.
Indoor unit
1.0 ~ 1.5
Gas side
operation valve
Check joint
0 ~ 0.5
(mm)
Securely tighten the operation valve cap and the check joint blind nut after adjustment.
Operation valve
(two-way valve)
Check joint
Outdoor unit
(1) Dress refrigerant pipes (both gas and liquid pipes) for heat insulation and prevention of dew condensation.
* When an additional charge volume calculation result is negative, it is not necessary to charge refrigerant
additionally.
For an installation measuring 15m or shorter in pipe length, please charge the refrigerant volume charged
for shipment at the factory, when you recharge refrigerant after servicing etc.
Additional charge volume (kg) = { Main length (m) Factory charged volume 15 (m) } x 0.025 (kg/m)
This unit contains factory charged refrigerant covering 15m of refrigerant piping and additional refrigerant
charge on the installation site is not required for an installation with up to 15m refrigerant piping.
When refrigerant piping exceeds 15m, additionally charge an amount calculated from the pipe length and
the above table for the portion in excess of 15m.
(1) Calculate a required refrigerant charge volume from the following table.
To prevent a different oil from entering, assign dedicated tools, etc. to each refrigerant type. Under no circumstances must a
gauge manifold and a charge hose in particular be shared with other refrigerant types (R22, R407C, etc.).
Use a counterflow prevention adapter to prevent vacuum pump oil from entering the refrigerant system.
Pay attention to the following points in addition to the above for the R410A and compatible machines.
6) Evacuation
Copper
pipe outer
diameter
6.35
15.88
1 Although outdoor and indoor units themselves have been tested for air tightness at the factory, check the connecting pipes after the installation work for air tightness
from the operation valves check joint equipped on the outdoor unit side. While conducting a test, keep the operation valve shut all the time.
a) Raise the pressure to 0.5MPa, and then stop. Leave it for five minutes to see if the pressure drops.
b) Then raise the pressure to 1.5MPa, and stop. Leave it for five more minutes to see if the pressure drops.
c) Then raise the pressure to the specified level (4.15MPa), and record the ambient temperature and the pressure.
d) If no pressure drop is observed with an installation pressurized to the specified level and left for about one day, it is acceptable. When the ambient temperature fall
1 C, the pressure also fall approximately 0.01MPa. The pressure, if changed, should be compensated for.
e) If a pressure drop is observed in checking e) and a) d), a leak exists somewhere. Find a leak by applying bubble test liquid to welded parts and flare joints and
repair it. After repair, conduct an air tightness test again.
2 In conducting an air tightness test, use nitrogen gas and pressurize the system with nitrogen gas from the gas side. Do not use a medium other than nitrogen gas
under any circumstances.
150
300
0
04
9.1
19.7
Fix both liquid and gas operation valves at the valve main bodies as illustrated on the right, and then fasten them,
applying appropriate fastening torque.
Do not apply force beyond proper fastening torque in tightening the flare nut.
CAUTION
A
B
Close
Carry out the on site piping work with the operation valve fully closed.
Give sufficient protection to a pipe end (compressed and blazed, or with an adhesive tape) so that water or
foreign matters may not enter the piping.
Bend a pipe to a radius as large as practical.(R100~R150) Do not bend a pipe repeatedly to correct its form.
Flare connection is used between the unit and refrigerant pipe. Flare a pipe after engaging a flare nut onto it.
Flare dimensions for R410A are different from those for conventional R407C. Although we recommend the
use of flaring tools designed specifically for R410A, conventional flaring tools can also be used by adjusting
the measurement of protrusion B with a protrusion control gauge.
The pipe should be anchored every 1.5m or less to isolate the vibration.
Tighten a flare joint securely with a double spanner.
Power cable
After installation
Indoor - Outdoor
connecting wire
Grounding terminal
Wiring diagram
It has stuck on the lid of a
Cable clamp
4. ELECTRICAL WIRING WO
'13 SRK-T-138
28 -
(mm)
Indoor unit
1.0 ~ 1.5
a conventional tool
clutch) type
Grommet
Drain hose
(To be procured on the installers part)
Cable clamp
Electrical installation work must be performed by an electrical installation service provider qualified by a power provider of the country.
Electrical installation work must be executed according to the technical standards and other regulations applicable to electrical installations in the country.
Do not use any supply cord lighter than one specified in parentheses for each type below.
braided cord (code designation 60245 IEC 51)
ordinary tough rubber sheathed cord (code designation 60245 IEC 53)
flat twin tinsel cord (code designation 60227 IEC 41)
Use polychloroprene sheathed flexible cord (code designation 60245 IEC57) for supply cords of parts of appliances for outdoor use.
Ground the unit. Do not connect the grounding wire to a gas pipe, water pipe, lightning rod or telephone grounding wire.
If improperly grounded, an electric shock or malfunction may result.
A grounding wire must be connected before connecting the power cable. Provide a grounding wire longer than the power cable.
The installation of an impulse withstanding type earth leakage breaker is necessary. A failure to install an earth leakage breaker can result in an accident
such as an electric shock or a fire.
Do not turn on the power until the electrical work is completed.
Do not use a condensive capacitor for power factor improvement under any circumstances. (It dose not improve power factor, while it can cause an
abnormal overheat accident)
For power supply cables, use conduits.
Do not lay electronic control cables (remote control and signaling wires) and other cables together outside the unit. Laying them together can result in
the malfunctioning or a failure of the unit due to electric noises.
Fasten cables so that may not touch the piping, etc.
When cables are connected, make sure that all electrical components within the electrical component box are free of loose connector coupling or
terminal connection and then attach the cover securely. (Improper cover attachment can result in malfunctioning or a failure of the unit, if water
penetrates into the box.)
Never use a shield cable.
1 2/N 3
Earth
Outdoor unit
L
Earth
leakage
Safety
breaker
20A
CAUTION
Clearance
RCR012A101
Insulation
Gas piping
Exterior tape
Phase
Switch breaker
Always use an earth leakage circuit breaker designed for inverter circuits to
prevent a faulty operation.
Earth leakage breaker
CAUTION
Always perform grounding system installation work with the power cord unplugged.
Connect a pair bearing a common terminal number with an indoor-outdoor connecting wire.
In cabling, fasten cables securely with cable clamps so that no external force may work on terminal connections.
Grounding terminals are provided in the control box.
Liquid piping
For details of electrical cabling, refer to the indoor unit installation manual.
Drain elbow
Grommet
All gas pipes must be securely heat insulated in order to prevent damage from dripping water that comes from the condensation formed on them during a cooling
operation or personal injury from burns because their surface can reach quite a high temperature due to discharged gas flowing inside during a heating operation.
Wrap indoor units flare joints with heat insulating parts (pipe cover) for heat insulation (both gas and liquid pipes).
Give heat insulation to both gas and liquid side pipes. Bundle a heat insulating material and a pipe tightly together so that no gaps may be left between them and
wrap them together with a connecting cable by a dressing tape.
Both gas and liquid pipes need to be dressed with 20mm or thicker heat insulation materials above the ceiling where relative humidity exceeds 70%.
(2) Use a heat insulating material that can withstand 120 C or a higher temperature. Poor heat insulating capacity can cause heat insulation problems or cable
deterioration.
Band (accessory)
NOTE Put down the refrigerant volume calculated from the pipe length onto the caution label attached
on the service panel.
In charging refrigerant, always charge a calculated volume by using a scale to measure the charge
volume.
When refrigerant is charged with the unit being run, complete a charge operation within 30minutes.
Running the unit with an insufficient quantity of refrigerant for a long time can cause a compressor failure.
Improper heat insulation/anti-dew dressing can result in a water leak or dripping causing damage to household effects, etc.
(1) Dress refrigerant pipes (both gas and liquid pipes) for heat insulation and prevention of dew condensation.
* When an additional charge volume calculation result is negative, it is not necessary to charge refrigerant
additionally.
For an installation measuring 15m or shorter in pipe length, please charge the refrigerant volume charged
for shipment at the factory, when you recharge refrigerant after servicing etc.
Additional charge volume (kg) = { Main length (m) Factory charged volume 15 (m) } x 0.025 (kg/m)
Power cables and connecting wires are securely fixed to the ter
After installation
connecting wire
'13 SRK-T-138
minutes.
pressor failure.
29 -
sulation
Gas piping
Exterior tape
r (accessory)
label attached
charge
the container
Indoor unit
Power cable
Power
supply
Earth
leakage
circuit
breaker
Safety
breaker
20A
EARTHING WORK
Single-phase
Phase
20A, 30mA,
0.1sec or less
30A
Switch breaker
2.5mm2
The pipe joints for indoor and outdoor pipes have been insulated.
The reverse flow check cap is attached.
The cover of the pipe cover (A) faces downward to prevent rain from entering.
Gaps are properly sealed between the pipe covers (A) (B) and the wall surface / pipes.
The screw of the side cover is tightened securely.
Screw x11
When change the Printed circuit board, please take off the top panel.
Power cables and connecting wires are securely fixed to the terminal block.
After installation
20A
1.5mm2 X 4
Always use an earth leakage circuit breaker designed for inverter circuits to
prevent a faulty operation.
CAUTION
Always perform grounding system installation work with the power cord unplugged.
Connect a pair bearing a common terminal number with an indoor-outdoor connecting wire.
In cabling, fasten cables securely with cable clamps so that no external force may work on terminal connections.
Grounding terminals are provided in the control box.
The specifications shown in the above table are for units without heaters. For units with heaters, refer to the
installation instructions or the construction instructions of the indoor unit.
Switchgear or Circuit breaker capacity which is calculated from MAX. over current should be chosen along the
regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than
three cables contained in a conduit and a voltage drop is 2%. For an installation falling outside of these
conditions, please follow the internal cabling regulations. Adapt it to the regulation in effect in each country.
1.5
R
N
R
4or5
G
Check the following points again after completion of the installation, and before turning on the power. Conduct a test run again and ensure that the unit operates properly.
Explain to the customer how to use the unit and how to take care of the unit following the installation manual.
Indoor - Outdoor
connecting wire
Earth
Outdoor unit
Indoor unit
1 2/N 3
CAUTION
Grounding terminal
Wiring diagram
It has stuck on the lid of a control box.
Cable clamp
'13 SRK-T-138
'13 SRK-T-138
HI POWER/ECONO button
TEMPERATURE button
These button set the room temperature.
(These buttons are used for setting the
current time and timer function as
well.)
CANCEL button
This button cancels the ON timer, OFF
timer, and SLEEP operation.
SLEEP button
CLEAN switch
ACL switch
ON TIMER button
This button selects ON TIMER operation.
RUN
TIMER
HI POWER
ON
1.5 sec.
OFF
CLEAN operation
ON
ON/OFF
HOT KEEP
ECONO
0.5 sec.
3 sec.
OFF
1 sec.
30 -
'09SRK-DB-087D
'13 SRK-T-138
(a) Operation
(b) Details of operation
Heating
(i)
(ii)
(J170)
Cut
(i)
(ii)
31 -
'13 SRK-T-138
Interface kit
(SC-BIKN-E)
SW2-4
Function
Shorted
ON
Enabled
Shorted
OFF
Disabled
Open
ON
Disabled
Open
OFF
Disabled
Note: (1) Default states of the jumper wire (J172) and the interface kit at the shipping from factory On the
PCB, the dip switch (SW2-4) is set to enable the annual cooling function.
OFF
(i) If the outdoor air temperature sensor (TH3) detects below 5C, the indoor unit
speed is switched to 9th step. (It is not possible to change.)
'09SRK-DB-087D
(ii) If the outdoor air temperature sensor (TH3) detects higher than 7C, the indoor
unit speed is changed to the normal control speed.
(Flap stopped)
(Swing)
Approx. 5
Approx. 25
Approx. 35
Approx. 55
Approx. 80
HEAT
Approx. 25
Approx. 40
Approx. 50
Approx. 60
Approx. 80
(b) Louver
(Louver stopped)
(Swing)
Angle of Louver
Remote control
display
Center installation
Center
(c) Swing
(i)
32 (ii)
display
Center installation
Center
'13 SRK-T-138
(c) Swing
(i)
(ii)
In HEAT operation
Approx.
5
Approx. 35
Approx. 60
Approx. 80
( f ) Multi-directional Air Flow (up/down air scroll and left/right air scroll)
Activating both up/down air swing and left/right air swing at the same time results in a multi-directional air flow.
Left louver
Thick line
Thin line
Right louver
: moves quickly
: moves slowly
(7)Timer operation
(a) Comfortable timer setting (ON timer)
33
Thermostat ON
Thermostat
-OFF
Failure
Compressor
ON
OFF
OFF
ON
ON(HOT KEEP)
OFF
ON
OFF
(few minutes ON)
OFF
In HEAT operation
'13 SRK-T-138
Thermostat OFF
Failure
Compressor
ON
OFF
OFF
ON
ON(HOT KEEP)
OFF
ON
OFF
(few minutes ON)
OFF
4-way valve
ON
ON
OFF
(3 minutes ON)
Model
DXK32ZL-S
Fan speed
15~82rps
Auto
HI
15~82rps
MED
15~82rps
LO
15~68rps
ULO
15~50rps
4)
2 1.5
3.5
7.5
-5
-10
-15
D
-20
-20
-15
s
ro
ef
pe
to
n
tio
ra
-10
rt
sta
m
te
re
tu
ra
pe
Defrost operation
start
-5
10
5)
1) 2) 3)
-
0.5
34 -
(ii)
1)
21
5)
2
1.5
'13 SRK-T-138
5)
1) 2) 3)
5)
2
1.5
0.5
(ii)
2
1)
21
16 minutes and 50 seconds.
2)
Defrast operation
Heating operation
Max. 16 minutes and 50 seconds
2~7 minutes
Hot keep operation
'09SRK-DB-087D
'09SRK-DB-087D
Compressor
Compressor
Indoor fan motor
Indoor fan motor
Outdoor fan motor
Outdoor fan motor
4-way valve
4-way valve
Cooling
Cooling
Thermostat OFF
Thermostat OFF
OFF
OFF
ON
ON
OFF
(few minutes
OFF ON)
(few minutes ON)
OFF
OFF
Failure
Failure
OFF
OFF
OFF
OFF
OFF
(few minutes
OFF ON)
(few minutes ON)
OFF
OFF
Fan speed
Fan speedAuto
Auto
HI
HI
MED
MED
LO
LO
ULO
ULO
Model
Model
DXK32ZL-S
DXK32ZL-S
15~77rps
15~77rps
15~77rps
15~77rps
15~62rps
15~62rps
15~46rps
15~46rps
15~30rps
15~30rps
27.5
27.5
25.5
25.5
Cooling
Cooling
A
A
Dehumidifying
Dehumidifying
18.0
Heating
Heating
18
(b)
(b)
18 temperature (C)
Outdoor air
Outdoor air temperature (C)
30
30
(i)
- 35 (i)
(ii) When both the indoor and the outdoor air temperatures are in the range A, cooling or heating is switched depending on
(ii) When both the indoor and the outdoor air temperatures are in the range A, cooling or heating is switched depending on
the difference between the setting temperature and the indoor air temperature.
the difference between the setting temperature and the indoor air temperature.
Dehumidifying
18.0
Heating
'13 SRK-T-138
30
18
(b)
(i)
(ii)
When both the indoor and the outdoor air temperatures are in the range A, cooling or heating is switched depending on
the difference between the setting temperature and the indoor air temperature.
(iii)
When the operation mode has been judged following the change of setting temperature with the remote control, the hourly
judgment of operation mode is cancelled.
(c)
(d)
+1
+2
+3
+4
+5
+6
Cooling
Setting
Dehumidifying
temperature
Heating
(e) W
hen the unit is operated automatically with the wired remote control connected, the cooling operation is controlled according to the display temperatures while the setting temperature is compensated by +1C during dehumidifying or by +2C during
heating.
2)
Item
ULo
Hi, Me, Lo
DXK32ZL-S
Indoor fan
4th speed
Indoor fan
Range B
Range A
Cancel
63
68
Humidity (%)
78
36 -
'13 SRK-T-138
2)
When this control has continued for more than 30 minutes continuously, the following wind direction control is performed.
a) When the vertical wind direction is set at other than the vertical swing, the flaps change to the horizontal position.
b) When the horizontal wind direction is set at other than the horizontal swing, the louver changes to the vertical position.
'09SRK-DB-087D
2)
Operating conditions
1)
compressor
command
speed
2)
(ii)
5C or lower
Lower
limit
speed
2.5C or lower
16
0 rps
Indoor fan
2.5
Outdoor fan
4-way valve
Operating conditions:
more, or 47C or more with the compressor running, the lower limit
Model
DXK32ZL-S
Item
Outdoor air temperature
20
(ii)
25
Detail of operation
The lower limit of compressor command speed is set to 20 or 25 rps and even if the calculated result becomes lower than
that after fuzzy calculation, the speed is kept to 20 or 25 rps. However, when the thermo becomes OFF, the speed is
reduced to 0 rps.
(iii) Reset conditions:
1)
2)
(d) Cooling high pressure control
(i) Purpose:
(ii)
(iii)
Detector:
Detail of operation:
(Example) Fuzzy
8rps
(3)
(1)
8rps
(3)
(3)
53
(1)
lower limit
speed 20 rps
0rps
37 58
60
reduced to 0 rps.
(iii) Reset conditions:
1)
'13 SRK-T-138
2)
(d) Cooling high pressure control
(i) Purpose:
(ii)
(iii)
Detector:
Detail of operation:
(Example) Fuzzy
8rps
(3)
(1)
8rps
(3)
(1)
lower limit
speed 20 rps
(3)
0rps
60
58
53
60
20
'09SRK-DB-087D
Detail of operation:
1)
50
<20>
than 50 (30) <20> rps, the speed is kept to 50 (30) <20>rps. However, when the thermo becomes OFF,the speed is
2)
50 52 <120>
50 52 <120>
(2)
27
< >
30
(iii)
First time
25
27
30
Since the
seconds times
25
27
30
Reset conditions:
1)
30
2)
38 -
'13 SRK-T-138
(f)
Purpose:
(ii)
Detector:
(iii)
Detail of operation:
(Example) Fuzzy
4rps(1)
8rps(2)
4rps(1)
8rps(2)
lower limit
speed 20 rps
0rps
C
B
Indoor heat exchanger temperature(C)
'09SRK-DB-087D
Model 50
Temperature list
RPSmin < 40
40 <
= RPSmin < 80
RPSmin < 90
80 <
= RPSmin < 90
90 < RPSmin < 108
90 <
= RPSmin < 102
108 <
= RPSmin
102 <
= RPSmin
49
A
53
45
53 ~ 47
45 ~ 43
47 ~ 41
45 ~ 43
41
53
B
57
52
57 ~ 51
52 ~ 45
51 ~ 45
52 ~ 45
45
55
C
59
57
59 ~ 53
57 ~ 48
53 ~ 47
57 ~ 48
47
58
D
62
58
56.5
51
51.5
51
(ii)
Operating conditions :
2)
Detail of operation :
3)
Reset conditions :
3
10
3
Operating conditions : When the outdoor air temperature (TH3) is 13C or 17C or higher continues for 30 seconds
while the compressor command speed other than 0 rps.
2)
Detail of operation
a) Taking the upper limit of compressor command speed range at 65 rps or 35 rps, if the output speed obtained with
the fuzzy calculation exceeds the upper limit, the upper limit value is maintained.
b) The lower limit of compressor command speed is set to 20 rps or 25 rps and even if the calculated result becomes
lower than that after fuzzy calculation, the speed is kept to 20 rps or 25 rps. However, when thethermo becomes
OFF, the speed is reduced to 0 prs.
c)
20 rps or 25 rps.
3)
Reset conditions:
Upper 35 rps
Lower 25 rps
Upper 65 rps
Lower 20 rps
OFF
11
13
16
17
a)
Operating conditions : When the outdoor air temperature (TH2) is 11C or higher continues for 30 seconds while
b)
Detail of operation
Taking the upper limit of compressor command speed range at 78 rps, if the output speed obtained with the fuzzy
calculation exceeds the upper limit, the upper limit value is maintained.
ii)
39
that after fuzzy calculation, the speed is kept to 30 rps. However, when thethermo becomes OFF, the speed is
reduced to 0 prs.
iii)
Normal operation
10
11
19
20
'13 SRK-T-138
c)
Reset conditions:
11
'09SRK-DB-087D
Normal operation
-8
-6
3)Reset
conditions:
Reset conditions:
(iii)
a)The outdoor air temperature (TH2)
1)
3 becomes 66C.
b)The compressor command speed is 0 rps.
2)
(i)
Detail of operation
1)
(Example) Fuzzy
180
180
180
95
105
Discharge pipe temperature (C)
115
105 115
95 105
Item
Model
Lower limit speed
2)
(j)
(l)
Cooling
Heating
20 rps
25 rps
115
Current safe
(i) Purpose:
(ii)
(k)
180
180
95 105
Detail of operation:
Current cut
(i)
Purpose:
(ii)
Detail of operation:
40 -
item (i), (ii) is satisfied. Once the unit is stopped by this function, ti is not
(ii)
Detail of operation:
'13 SRK-T-138
(k)
(l)
Current cut
(i)
Purpose:
(ii)
Detail of operation:
'09SRK-DB-087D
(n)
(o)
Rotor lock
(p)
(q)
Cooling
1)
Operating conditions:
2)
Detail of operation:
Outdoor fan
Outdoor temperature > 10C
3rd
(FMo1,2)
2nd
(FMo1,2)
(FMo1)
2nd
OFF (FMo2)
a)
2
2nd
2
b)
40
40
c)
40
40
3)
4th
Reset conditions:
a)
b)
24
41 -
40
c)
40
'13 SRK-T-138
40
3)
4th
Reset conditions:
a)
24
b)
(ii) Heating
1)
Operating conditions:
2)
Detail of operation:
3)
Reset conditions:
3
1
a)
3
9th
b)
(q)
(ii)
(iii)
Starting conditions
1)
When 5 minutes have elapsed after the compressor ON or the completion of the defrost control
2)
3)
Cooling
30 <
=N
10 <
= Th1<
= 40
Th14<Th2
Heating
30 <
=N
0<
= Th1<
= 40
Th2<Th1+6
Contents of control
1)
When the conditions of (i) above are met, the compressor stops.
2)
Error stop occurs when the compressor has stopped 3 times within 60 minutes.
Resetting condition
When the compressor has been turned OFF
42 -
'09SRK-DB-087D
'13 SRK-T-138
Reference
10.
MAINTENANCE DATA
2 TROUBLESHOOTING
PROCEDURES FOR ELECTRICAL EQUIPMENT
(1)
Cautions
(2)
(3)
Troubleshooting procedure (If the air conditioner does not run at all)
Important
NO
YES
NO
YES
NO
YES
NO
YES
43 -
'09SRK-DB-087D
'13 SRK-T-138
(4)
NO
YES
45
NO
46 ~ 52.
YES
YES
NO
46 ~ 52.
YES
NO
44 -
'09SRK-DB-087D
'13 SRK-T-138
(5)
Self-diagnosis table
Wired (2)
remote Description
control of trouble
display
Cause
1 time
flash
ON
Heat exchanger
sensor 1 error
2 time
flash
ON
Room
temperature
sensor error
3 time
flash
ON
Heat exchanger
sensor 2 error
6 time
flash
ON
E 16
Indoor fan
motor error
E 38
Outdoor air
temperature
sensor error
E 37
Outdoor heat
exchanger
sensor error
Broken heat exchanger sensor 55C or lower is detected for 5 seconds continuously 3 times within
40 minutes after initial detection of this anomalous temperature.
wire, poor connector
connection
Or 55C or higher is detected for within 20 seconds after power ON.
Outdoor PCB is faulty
(The compressor is stopped.)
E 39
Discharge pipe
sensor error
ON
1 time 1 time
flash flash
E 42
Current cut
Compressor locking, open phase The compressor output current exceeds the set value during compressor
on compressor output, short
start.
circuit on power transistor,
(The air conditioner stops.)
service valve is closed
ON
2 time 2 time
flash flash
E 59
Trouble of
outdoor unit
ON
3 time 3 time
flash flash
E 58
Current safe
stop
Overload operation
Overcharge
Compressor locking
When the compressor command speed is lower than the set value and
the current safe has operated. (the compressor stops)
ON
4 time 1 time
flash flash
E 51
Power
transistor
error
ON
5 time 5 time
flash flash
E 36
Over heat of
compressor
ON
6 time 6 time
flash flash
E5
Error of signal
transmission
When there is no signal between the indoor PCB and outdoor PCB for
Defective power supply,
10 seconds or longer (when the power is turned on), or when there is no
Broken signal wire, defective signal for 7 minute 35 seconds or longer (during operation)(the
indoor/outdoor PCB
compressor is stopped).
ON
7 time
flash
E 48
Outdoor fan
motor error
ON
Keeps 2 time
flashing flash
E 35
Cooling high
pressure
protecton
E 60
Rotor lock
Defective compressor
Open phase on compressor
Defective outdoor PCB
ON
When conditions for turning the indoor units fan motor on exist during air
aoperation, an indoor unit fan motor speed of 300 rpm or lower is measured
for 30 seconds or longer. (The air conditioner stops.)
55C or lower is detected for 5 seconds continuously 3 times within
40 minutes after initial detection of this anomalous temperature.
Or 55C or higher is detected for within 20 seconds after power ON.
(The compressor is stopped.)
When the outdoor units fan motor speed continues for 30 seconds or
longer at 75 rpm or lower. (3 times) (The air conditioner stops.)
5 time
flash
ON
2 time
flash
E 47
Active filter
voltage error
7 time
flash
ON
2 time
flash
E 57
Refrigeration
cycle system
protective
control
E1
Error of wired
remote control
wiring
The wired remote control wire Y is open. The wired remote control
wires X and Y are reversely connected. Noise is penetrating the wired
remote control lines. The wired remote control or indoor PCB is faulty.
(The communications circuit is faulty.)
45 -
'09SRK-DB-087D
'13 SRK-T-138
(6)
Term
Explanation
Service mode
The service mode is the mode where service data are displayed by flashing of the display lights
when the operations in item (b) below are performed with the indoor control.
Service data
These are the contents of error displays and protective stops which occurred in the past in the air
conditioner system. Error display contents and protective stop data from past anomalous
operations of the air conditioner system are saved in the indoor unit controls non-volatile memory
(memory which is not erased when the power goes of f). There are two types of data, self-diagnosis
data and stop data, described below.
Self-diagnosis data
These are the data which display the reason why a stop occurred when an error display(selfdiagnosis display) occurred in an indoor unit. Data are recorded for up to 5 previous occurrences.
Data which are older than the 5th previous occurrence are erased.
In addition, data on the temperature of each sensor (room temperature, indoor heat exchanger,
outdoor heat exchanger, outdoor air temperature, discharge pipe), remote control information
(operation switching, fan speed switching) are recorded when trouble occurs, so more detailed
information can be checked.
Stop data
These are the data which display the reason by a stop occurred when the air conditioning system
performed protective stops, etc. in the past. Even if stop data alone are generated, the system
restarts automatically. (After executing the stop mode while the display is normal, the system
restarts automatically.) Data for up to 10 previous occasions are stored. Data older than the 10th
previous occasion are erased.
( Important) In cases where transient stop data only are generated, the air conditioner system
may still be normal. However, if the same protective stop occurs frequently (3 or
more times), it could lead to customer complaints.
49.)
47.)
46 -
'13 SRK-T-138
Temperature setting
21C
22C
2 times previous
23C
3 times previous
24C
4 times previous
25C
5 times previous
Temperature setting
26C
27C
2 times previous
28C
3 times previous
29C
4 times previous
30C
5 times previous
47 -
'13 SRK-T-138
(Example)
Cooling
Displayed data
MED
21C
Displays the reason for the stop (error code) the previous time an error was displayed.
22C
Displays the reason for the stop (error code) 2 times previous when an error was displayed.
23C
Displays the reason for the stop (error code) 3 times previous when an error was displayed.
24C
Displays the reason for the stop (error code) 4 times previous when an error was displayed.
25C
Displays the reason for the stop (error code) 5 times previous when an error was displayed.
Cooling
Displayed data
LO
21C
Displays the reason for the stop (stop code) the previous time when the air conditioner was stopped by protective stop control.
22C
Displays the reason for the stop (stop code) 2 times previous when the air conditioner was stopped by protective stop control.
23C
Displays the reason for the stop (stop code) 3 times previous when the air conditioner was stopped by protective stop control.
24C
Displays the reason for the stop (stop code) 4 times previous when the air conditioner was stopped by protective stop control.
25C
Displays the reason for the stop (stop code) 5 times previous when the air conditioner was stopped by protective stop control.
26C
Displays the reason for the stop (stop code) 6 times previous when the air conditioner was stopped by protective stop control.
27C
Displays the reason for the stop (stop code) 7 times previous when the air conditioner was stopped by protective stop control.
28C
Displays the reason for the stop (stop code) 8 times previous when the air conditioner was stopped by protective stop control.
29C
Displays the reason for the stop (stop code) 9 times previous when the air conditioner was stopped by protective stop control.
30C
Displays the reason for the stop (stop code) 10 times previous when the air conditioner was stopped by protective stop control.
48 -
'13 SRK-T-138
3 time
flash
5 time
flash
8 time
flash
Normal
5 time
flash
05
5 time
flash
35
(5 times)
6 time
flash
36
Refrigerant is insufficient.
Discharge pipe sensor is faulty.
Service valve is closed.
(2 times)
7 time
flash
37
8 time
flash
38
39
2 time
flash
42
Current cut
Compressor lock.
Compressor wiring short circuit.
Compressor output is open phase.
Outdoor PCB is faulty.
Service valve is closed.
Electronic expansion valve is faulty.
Compressor is faulty.
7 time
flash
47
.
Defective active filter
8 time
flash
48
1 time
flash
51
7 time
flash
57
58
Current safe
Refrigerant is overcharge.
Compressor lock.
Overload operation.
59
8 time
flash
9 time
flash
6 time
flash
Occurrence conditions
9 time
flash
4 time
flash
Cause
OFF
OFF
Error content
OFF
60
Rotor lock
1 time
flash
61
2 time
flash
62
OFF
80
2 time
flash
82
4 time
flash
84
Anti-condensation control
5 time
flash
85
Anti-frost control
6 time
flash
86
49 -
(3 times)
(3 times)
Compressor is faulty.
Compressor output is open phase.
Electronic expansion valve is faulty.
Overload operation.
Outdoor PCB is faulty.
(2 times)
(2 times)
'13 SRK-T-138
(i)
TIMER light
(Fan speed switching)
Fan speed
switching when
there is an
abnormal stop
AUTO
AUTO
DRY
HI
COOL
MED
FAN
LO
HEAT
HI POWER
ECONO
RUN light
(10s digit)
ON
1.5 sec.
OFF
0.5 sec.
TIMER light
(1s digit)
0.5 sec.
ON
OFF
11-second interval
50 -
'09SRK-DB-087D
'13 SRK-T-138
(e) Room temperature sensor, indoor heat exchanger sensor, outdoor air temperature sensor, outdoor heat
exchanger sensor table
Units: C
TIMER light
(1s digit)
RUN light
(10s digit)
-60
-61
-62
-63
-64
-50
-51
-52
-53
-54
-55
-56
-57
-58
-59
-40
-41
-42
-30
-31
-32
-43
-44
-45
-46
-47
-48
-49
-33
-34
-35
-36
-37
-38
-39
-20
-21
-10
-11
-22
-23
-24
-25
-26
-27
-28
-29
-12
-13
-14
-15
-16
-17
-18
-19
-1
-2
-3
-4
-5
-6
-7
-8
-9
Buzzer sound
Yes
(sounds for 0.1 second)
No
(does not sound)
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
Sensor name
Room temperature sensor
-64C
-64C
-64C
-64C
0.1 sec.
ON
Buzzer sound
OFF
RUN light
(10s digit)
ON
1.5 sec.
OFF
0.5 sec.
TIMER light
(1s digit)
0.5 sec.
ON
OFF
11-second interval
51 -
'13 SRK-T-138
(f)
Units: C
TIMER light
(1s digit)
RUN light
(10s digit)
-60
-62
-64
-40
-42
-20
-22
-44
-46
-48
-50
-52
-54
-56
-58
-24
-26
-28
-30
-32
-34
-36
-38
Buzzer sound
Yes
(sounds for 0.1 second)
No
(does not sound)
-2
-4
-6
-8
-10
-12
-14
-16
-18
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
126
128
130
132
134
136
138
140
142
144
146
148
150
0.1 sec.
ON
Buzzer sound
OFF
RUN light
(10s digit)
ON
1.5 sec.
OFF
0.5 sec.
TIMER light
(1s digit)
0.5 sec.
ON
OFF
11-second interval
52 -
'13 SRK-T-138
47)
53 -
'09SRK-DB-087D
'13 SRK-T-138
Sensor error
30
180
25
140
Resistance (k )
Resistance (k )
160
120
100
80
60
40
15
10
5
20
0
20
20
40
60
80
100
120
135
Temperature (C)
-10
10
20
30
40
50
60
Temperature (C)
Is it normalized?
54 -
70
'13 SRK-T-138
Current cut
Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
62
60
55 -
'09SRK-DB-087D
'13 SRK-T-138
54)
56 -
'09SRK-DB-087D
'13 SRK-T-138
(1)
(2)
(1)
(3)
62
Notes (1)
(2)
60
ourdoor PCB
See pages 62 for the fan motor and outdoor PCB check prooutdoor
After making sure the fan motor and outdoor PCB are nor-
Is it normalized?
57 -
'13 SRK-T-138
Rotor lock
Operation
Operation
mode
mode
Cooling
Cooling
Heating
Heating
Cooling
Cooling
Heating
Heating
Cooling
Cooling
Heating
Heating
Phenomenon
Phenomenon
Shortcircuit
Shortcircuit
Disconnected wire
Disconnected wire
'09SRK-DB-087D
Operation
mode
Sensor
Heat exchanger
sensor
Cooling
Ourdoor air
temperature sensor
Cooling
Discharge pipe
sensor
Shortcircuit
Disconnected wire
Defrosting is performed for 10 minutes at approx. 35 minutes.
Heating
Heating
All modes
NO
YES
NO
Replace fuse.
YES
NO
YES
Indoor electrical components
are normal.
58 -
Shortcircuit
Heat exchanger
sensor
Cooling
Ourdoor air
temperature sensor
Cooling
Disconnected wire
Defrosting is performed for 10 minutes at approx. 35 minutes.
Heating
Discharge pipe
sensor
'13 SRK-T-138
Heating
All modes
NO
YES
NO
Replace fuse.
YES
NO
YES
Indoor electrical components
are normal.
DC several V
(4~6 V)
CNU
DC15V
()
GND
DC 308~336V
Indoor PCB
Measuring
point
Yellow
White
Black
Red
Blue
FMI
(ii) Fan motor resistance check
Measuring point
59 -
Resistance when
normal
'13 SRK-T-138
Output voltage
(ACV)
8~10 sec.
Operation SW ON
1 sec.
3 min.
1 sec.
60 -
3 min.
1 sec.
Brown
Orange
Red
White
Yellow
YellowGreen
BR
OR
RD
WH
YG
Indoor
uint
Power source
220230240V
50Hz
TB2
TB1
Black
Color
BK
Mark
3
YG
RD
WH
2
N
YG
WH
SIN
BK RIN
61 2
CNFAN
WH
250V 3.15A
F1
53.
F8
TH3
250V 20A
WH
BK
RD
CM
Inspection of electronic
expansion valve
61.
See page 62.
EEV
CNEEVWH
F3 250V 3.15A
POWER
TRANSISTOR
Inspection
of resistance valve of sensor
61.
Remove the connector and check the resistance valve.
See the section of sensor characteristics on page 54.
TH4
SWITCHING
POWER
CIRCUIT
ACTIVE
FILTER
UNIT
F2
250V 20A
CNTHBK
TH2
FMo2
WH
CNFAN0
WH
C-2
CNSUB
WH
FMo1
WH
C-1 RD
CNMAIN
WH
S-1 WH S-2
S0 WH S
CN20V
WH
20S
RD
RD WH
CN20S CNFAN1
R0 BK
CN20V
WH
WH
CNFAN2
PWB ASSYSUBPWB2
CNA
WH
YG G1
YG G3
250V 20A
BK FUSE
BK
Outdoor unit
F1
Color symbol
250V 1A
F2
YE
T1
250V 1A
OR
T2
'09SRK-DB-087D
'13 SRK-T-138
'13 SRK-T-138
Red
Blue
4
Orange
White
white
Yellow
(i)
(ii)
(iii)
(iv)
Inspection of electronic expansion valve as a separate unit
Measuring point
(i)
1)
2)
3)
sub
CNFAN1 or CNFAN2
sub
sub
FM01
or
FM02
Measuring
point
Brown
Orange
White
Red
Blue
CNFAN1
or
CNFAN2
GND
(
DC15V
DC several (4~7V)
DC308~336V
Blue
Blue
62 -
Resistance when
normal
'13 SRK-T-138
Installation
manual
for wired remote controller PJA012D730
(1) Wired
remote control
(RC-E5)
Read together with indoor unit's installation manual.
WARNING
Fasten the wiring to the terminal securely and hold the cable securely so as not to apply unexpected stress on the
terminal.
Loose connection or hold will cause abnormal heat generation or fire.
Make sure the power supply is turned off when electric wiring work.
Otherwise, electric shock, malfunction and improper running may occur.
CAUTION
DO NOT install the remote control at the following places in order to avoid malfunction.
(1) Places exposed to direct sunlight
(2) Places near heat devices
(3) High humidity places
Accessories
Prepare on site
Installation procedure
Open the cover of remote control, and remove the screw under the
buttons without fail.
Remove the upper case of remote control.
Insert a flat-blade screwdriver into the dented part of the upper part
of the remote control, and wrench slightly.
Screw
Indoor units
Remote control
Control cord
Erectrical box
(Prepare on site)
Remote control
SW1 "Master"
Prepare two M4 screws (recommended length is 12-16mm) on site, and install the lower case to erectrical box.
Choose either of the following two positions in fixing it with screws.
Upper part
Upper part
Lower case
Wiring oulet
Lower case
M4 screw
2 (Prepare on site)
Lower
Upper
Lower case
Lower
63 -
Lower case
Install the lower case to the flat wall with attached two wooden screws.
Lower part
Wiring oulet
Lower part
Remote control
SW1 "Slave"
'13 SRK-T-138
mote controller
Sheath
Upper
Upper case
Board
Lower
Wiring
Sheath
Upper
Board
Lower
Wiring
The wiring inside the remote control case should be within 0.3mm (recommended) to 0.5mm2.
The sheath should be peeled off inside the remote control case.
The peeling-off length of each wire is as below.
nction.
Pulling out from upper left Pulling out from upper center
X wiring : 215mm
X wiring : 170mm
Y wiring : 195mm
Y wiring : 190mm
Install the upper case as before so as not to catch up the remote control cord, and tighten with
the screws.
In case of exposing cord, fix the cord on the wall with cord clamp so as not to slack.
Installation and wiring of remote control
Wiring of remote control should use 0.3mm2 s 2 core wires or cables. (on-site configuration)
Maximum prolongation of remote control wiring is 600 m.
If the prolongation is over 100m, change to the size below.
But, wiring in the remote control case should be under 0.5mm2 . Change the wire size outside of
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.
100 - 200m.........................0.5mm2 s 2 cores
Under 300m .......................0.75mm2 s 2 cores
Under 400m .......................1.25mm2 s 2 cores
Under 500m .......................2.0mm2 s 2 cores
Master/ slave setting when more than one remote controls are used
Screw
A maximum of two remote controls can be connected to one indoor unit (or one group of indoor units.)
Switch
Indoor units
SW1
Setting
Contents
M
Master remote control
S
Slave remote control
Control cord
Upper
Erectrical box
(Prepare on site)
Master
Remote control
SW1 "Master"
Remote control
SW1 "Slave"
Slave
Board
Lower
Set SW1 to "Slave" for the slave remote control. It was factory set to "Master" for shipment.
Note: The setting "Remote control thermistor enabled" is only selectable with the master remote control in
the position where you want to check room temperature.
The air conditioner operation follows the last operation of the remote control regardless of the
master/ slave setting of it.
M4 screw
2 (Prepare on site)
ol cord,
upper part.
r knife,
Lower case
Lower
Upper
Lower case
When remote control cannot communicate with the indoor unit for half an hour, the below indication will
appear.
Check wiring of the indoor unit and the outdoor unit etc.
.
Lower
64 -
'13 SRK-T-138
PJA012D730
Sheath
Upper case
Board
Lower
om
Sheath
Upper
Wiring
(recommended) to 0.5mm2.
so as not to slack.
Contents
emote control
mote control
Upper
Board
Lower
When shipped, the range of set temperature differs depending on the operation mode as below.
Heating : 16~30C (55~86F)
Except heating (cooling, fan, dry, automatic) : 18~30C (62~86F)
Upper limit and lower limit of set temperature can be changed with remote control.
Upper limit setting: valid during heating operation. Possible to set in the range of 20 to 30C (68 to 86F).
Lower limit setting: valid except heating (automatic, cooling, fan, dry) Possible to set in the range of 18 to 26C (62 to
79F).
When you set upper and lower limit by this function, control as below.
1. When TEMP RANGE SET, remote control function of function setting mode is "INDN CHANGE" (factory setting),
If upper limit value is set
During heating, you cannot set the value exceeding the upper limit.
If lower limit value is set
During operation mode except heating, you cannot set the value below the lower limit.
2. When TEMP RANGE SET, remote control function of function setting mode is "NO INDN CHANGE"
If upper limit value is set
During heating, even if the value exceeding the upper limit is set, upper limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
If lower limit value is set
During except heating, even if the value lower than the lower limit is set, lower limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
How to set upper and lower limit value
1. Stop the air-conditioner, and press
(SET) and
(MODE) button at the same time for over three
seconds .
The indication changes to "FUNCTION SET ".
2. Press
button once, and change to the "TEMP RANGE " indication.
3. Press
(SET) button, and enter the temperature range setting mode.
4. Select "UPPER LIMIT " or "LOWER LIMIT " by using
button.
5. Press
(SET) button to fix.
6. When "UPPER LIMIT " is selected (valid during heating)
Indication: "
SET UP"
"UPPER 30C "
Select the upper limit value with temperature setting button
. Indication example: "UPPER 26C
"
(blinking)
Press
(SET) button to fix. Indication example: "UPPER 26C" (Displayed for two seconds)
After the fixed upper limit value displayed for two seconds, the indication will return to "UPPER LIMIT ".
7. When "LOWER LIMIT " is selected (valid during cooling, dry, fan, automatic)
Indication: "
SET UP"
"LOWER 18C "
Select the lower limit value with temperature setting button
. Indication example: "LOWER 24C
"
(blinking)
Press
(SET) button to fix. Indication for example: "LOWER 24C" (Displayed for two seconds)
After the fixed lower limit value displayed for two seconds, the indication will return to "LOWER LIMIT
".
8. Press ON/OFF button to finish.
s first.
an error cord.
Previous button
65 -
'13 SRK-T-138
To next page
(Remote control function)
Function
01
setting
02
03
04
05
06
07
08
* 09
10
* 11
12
13
14
15
",
" accordingly.
16
17
18
If you input signal into CNT of the indoor printed circuit board from external, the
indoor unit will be operated independently according to the input from external.
If you input into CNT of the indoor printed circuit board from external, all units which
connect to the same remote control are operated according to the input from external.
In normal working indication, indoor unit temperature is indicated instead of airflow.
(Only the master remote control can be indicated.)
Heating preparation indication should not be indicated.
19
To next page
ON/OFF button
(finished)
66 -
'13 SRK-T-138
is decided by connected indoor and outdoor unit, and is automatically defined as following table.
Default
Model
"Auto-RUN" mode selectable indoor unit.
Indoor unit without "Auto-RUN" mode
Indoor unit with two or three step of air flow setting
Indoor unit with only one of air flow setting
Indoor unit with automatically swing louver
Indoor unit without automatically swing louver
Indoor unit with three step of air flow setting
Indoor unit with two step of air flow setting
Indoor unit with only one of air flow setting
Heat pump unit
Exclusive cooling unit
Remote control
function15
Note 3: As for plural indoor unit, set indoor functions to each master and slave indoor unit.
But only master indoor unit is received the setting change of indoor unit function 05 EXTERNAL INPUT and 06 PERMISSION /
PROHIBISHION.
From previous page
(Indoor unit function)
Fan tap
STANDARD
FAN
SPEED
HIGH
SET
SPEED1, 2
UH - Hi - Me - Lo
Hi - Me - Lo
Hi - Lo
Hi - Me
UH - UH - Hi - Me
UH - Hi - Me
UH - Me
UH - Hi
* 03
05
",
" accordingly.
06
Permission/prohibition control of operation will be valid.
* 07
With the VRF series, it is used to stop all indoor units connected with the same outdoor unit immediately.
When stop signal is inputed from remote on-off terminal "CNT-6", all indoor units are stopped immediately.
* 08
* 09
* 10
* 11
* 12
* 13
* 14
After cooling is stopped, the fan does not perform extra operation.
After cooling is stopped, the fan perform extra operation for half an hour.
After cooling is stopped, the fan perform extra operation for an hour.
After cooling is stopped, the fan perform extra operation for six hours.
* 15
After heating is stopped or heating thermostat is OFF, the fan does not perform extra operation.
After heating is stopped or heating thermostat is OFF,the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is OFF,the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for six hours.
* 16
During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes
with low fan speed after twenty minutes' OFF.
During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes
with low fan speed after five minutes' OFF.
* 17
67 -
'13 SRK-T-138
PJA012D730
(SET)
(MODE)
1. Stop air-conditioner and press
buttons at the same time for over three seconds, and the
"FUNCTION SET " will be displayed.
2. Press
(SET) button.
4. Press
or
button.
Selecct " FUNCTION " (remote control function) or "I/U
FUNCTION " (indoor unit function).
5. Press
- Me
UH - Hi - Me
Hi - Lo
UH - Me
Finishing button
Starting button
(SET) button.
Hi - Me
UH - Hi
"HIGH SPEED".
hours.
hours.
0 hours.
0 hours, then the indoor unit will be stopped by
",
n "14
our.
1
6
Lo
Function No.
Fixing button
6.
Function No.
[Note]
(1) If plural indoor units are connected to a remote control, the
indication is "I/U 000" (blinking)
The lowest number of the
indoor unit connected is indicated.
Function
Press
(SET) button.
The current setting of selected function is indicated.
(for example) "AUTO RUN ON"
If "02 AUTO RUN SET" is
selected
".
Press
or
button.
"No. and function"are indicated by turns on the remote control
function table, then you can select from them.
(For example)
" accordingly.
be valid.
Setting
or
button.
(2) Press
Select the number of the indoor unit you are to set
If you select "ALL UNIT ", you can set the same setting with
all unites.
(3) Press
(SET) button.
Press
or
button.
"No. and function" are indicated by turns on the indoor unit function
table, then you can select from them.
(For example)
Press
or
button.
Select the setting.
Function No.
low speed.
set speed.
operated intermittently.
pped.
OFF" is set automatically.
hermistor is working.
Function
Press
(SET) button.
The current setting of selected function is indicated.
(For example) "STANDARD"
If "02 FAN SPEED SET" is
selected.
Press
(SET)
"SET COMPLETE" will be indicated, and the setting will be
completed.
Then after "No. and function" indication returns, Set as the
same procedure if you want to set continuously ,and if to
finish, go to 7.
Setting
Press
or
button.
Select the setting.
Press
(SET) button.
"SET COMPLETE" will be indicated, and the setting will be
completed.
Then after "No. and function" indication returns, set as the same
procedure if you want to set continuously , and if to finish, go to 7.
s raised.
ing.
and fan.
It is possible to finish by pressing ON/OFF button on the way, but unfinished change of setting is
unavailable.
During setting, if you press
(RESET) button, you return to the previous screen.
Setting is memorized in the control and it is saved independently of power failure.
How to check the current setting
When you select from "No. and funcion" and press set button by the previous operation, the "Setting" displayed first is the current
setting.
(But, if you select "ALL UNIT ", the setting of the lowest number indoor unit is displayed.)
nd is automatically defined.
68 -
'13 SRK-T-138
Safety precautions
All the cautionary items mentioned below are important safety related items to be taken
into consideration, so be sure to observe them at all times.
No.
Part name
Quantity
Tapping screws (for the cable clump and the interface mounting bracket)
Warning
Warnings
Installation must be carried out by a qualified installer.
If you install it by yourself, it may cause an electric shock, fire and personal injury , as a result of a system malfunction.
Install it in full accordance with the instruction manual.
Incorrect installation may cause an electric shock, fire and personal injury.
Electrical work must be carried out by a qualified electrician in accordance with the technical standard for electrical equipment, the
indoor wiring standard and this instruction manual.
Incorrect installation may cause an electric shock, fire and personal injury.
Use the specific cables for wiring. And connect all the cables to terminals or connectors securely and clamp them with cable clamps in
order for external forces not to be transmitted to the terminals directly.
Incomplete connection may cause malfunction, and lead to heat generation and fire.
If the parts other than those prescribed by us are used, it may cause an electric shock, fire and sersonal injury.
Remove 2 screws from the interface casing before removal of upper casing.
Wiring inlet
(top or back)
Fix the indoor unit's connection cable with the cable clamp.
Connect the indoor unit's connection cable to the indoor control PCB.
Connect the indoor unit's connection cable to the indoor control PCB securely.
Remove
Clamp the connection cable to the indoor control box securely with the cable clamp
the upper
case
provided as an accessory.
Regarding the cable connection to the indoor unit, refer to the instruction manual for
indoor unit.
Interface board
Terminal for indoor unit's
connection cable
CNT terminal
*Either the connection cables of super link E board (SC-ADNA-E) or of wired remote control is connectable.
Switch
Setting
ON**
SW2-1
OFF
ON**
SW2-2
OFF
** Factory setting
Function
CNT level input
CNT Pulse input
Wired remote control : Enable
Wired remote control : Disable
Function
Setting
ON** External input (CNT input)
SW2-3
OFF
Operation permission/prohibition (CNT input)
ON** Annual cooling : Enable***
SW2-4
Annual cooling : Disable***
OFF
*** Indoor fan control at low outdoor air temperature in cooling
Switch
69 -
'13 SRK-T-138
Mount the lower casing of the interface on a flat surface with wood
Mount the
upper casing
70 -
'13 SRK-T-138
+12 1
CNT
(Blue 6P)
0.75mm22m
Indoor units
control box
Butt splice
White
Red
Black
XR1
Yellow
XR2
Blue
XR3
Brown
XR4
Orange
XR1
Black
XR2
Yellow
XR3
Blue
XR4
Brown
XR5
XR5
Orange
(Application coverage
0.751.25mm2)
Common
Output 1
Output 2
Output 3
Output 4
Input
power
Orange
Input/
Output
Function
Output 1
Output 2
Output 3
Output 4
Operation output
Heating output
Compressor operation output
Malfunction output
Output signal
Relay ON/OFF
XR1
ON
XR2
ON
ON
XR3
ON
XR4
Content
During air-conditioner operation
During heating operation
During compressor running
During anomalous stop
SW2-1
Connector
Terminals
SW2-3
AirInput signal
Conditioner
Setting
Setting
Content
Level/Pulse XR5
OFFON
ON
External input
ON*
ONOFF
OFF
ON* Level input
Level
OFFON Operation permission
OFF
OFF
Input External
Operation
prohibition
ONOFF
OFF
control
input
OFFON
ON*
Pulse OFFON External input
ONOFF
OFF Pulse input
OFFON Operation permission
ON
OFF
Level
ONOFF Operation prohibition
OFF
* Factory setting
Input/
Function
Output
Molex
Molex
Operation by
Remote Control
5264-06
5263T
DIP switch
(SW2-3)
Allowed
Not allowed
DIP switch
(SW2-1)
Allowed
Not allowed
DIP switch
(SW2-2)
Wiring connection between the interface and the super link E board.
Interface side
Terminal
block for
Super link
E board
Y
X
Y
X
Terminal
block for
iterface
No.
1
2
3
4
Within 200 m
Within 300 m
Within 400 m
Within 600 m
71 -
0.5 mm2
0.75 mm2
1.25 mm2
2.0 mm2
s 2 cores
s 2 cores
s 2 cores
s 2 cores
'13 SRK-T-138
DIP suitch
(SW2-2)
Caution:Wireless remote control attached to the indoor unit can be used in parallel, after connecting the wired remote control. However,
some of functions other than the basic functions such as RUN/STOP, Temperature Setting, etc. may not work properly and may have
a mismatch between the display and the actual behavior.
Wiring connection between the interface and the wired remote control.
Installation and wiring of wired remote control
A Install the wired remote control with reference to the attached instruction manual of wired remote control.
B 0.3mm2 x 2-core cable should be used for the wiring of wired remote control.
C Maximum length of wiring is 600m.
If the length of wiring exceeds 100m, change the size of cable as mentioned below.
100m-200m: 0.5mm2 x 2-core, 300m or less: 0.75mm2 x 2-core, 400m or less: 1.25mm2 x 2-core, 600m or less: 2.0mm2 x 2-core
However, cable size connecting to the terminal of wired remote control should not exceed 0.5mm2. Accordingly if the size of connection
cable exceeds 0.5mm2, be sure to downsize it to 0.5mm2 at the nearest section of the wired remote control and waterproof treatment should
be done at the connecting section in order to avoid contact failure.
D Don't use the multi-core cable to avoid malfunction.
E Keep the wiring of wired remote control away from grounding (Don't touch it to any metal frame of building, etc.).
F Connect the connection cables to the terminal blocks of the wired remote control and the interface securely (no polarity).
Rotary
switch
Interface kit(2)
Adress"1"
Interface kit(1)
Adress"0"
Interface kit(16)
Adress"F"
Remote control
Interface kit
Switch
setting
Wired remote
control: SW1
M
S
contents
Master
remote control
Slave
remote control
Remote
control
"Slave"
When using the wireless remote control in parallel with the wired remote control;
Since temperature setting range of wired remote control is different from that of wireless remote control, please adjust the setting range of wired
remote control to be the same setting range of wireless remote control by following procedure. (The set temperature may not be displayed correctly
on the wireless remote control, unless change of temperature setting range is done.)
Changing procedure of temperature setting range is as follows.
72 -
6-
7-
TEMP RANGE
TEMP
ON/OFF
TIEMR
GRILL
CHECK
SET
FAN SPEED
MODE
RESET
LOUVER
VENTI
TEST
8
356-
7-
1
Previous button
It
During
setting, if pressing
(RESET) button, it returns to the
previous screen.
'13 SRK-T-138
73 -
'13 SRK-T-138
74 -
'13 SRK-T-138
PARTS LIST
INDOOR UNIT
DKK32ZL-S
OUTDOOR UNIT
DXC32ZL-S
75 -
'13 SRK-T-138
32
35
1
34
39
40
46
4 46
4
45
33
44
6
42
43
36
46
4
45
29
28
31
12
13
37
30
12
20
21
10
16
18
19
15
27
26
14
14
14
76 -
11
23
22
17
24
14
10
25
CRAE0240
'13 SRK-T-138
DXK32ZL-S
END ITEM NO. :
No.
1
RWA002F070C
Part No.
Part Name
RE.Q
15
22
100
500
1000
1 RKW122A400F
PANEL,FRONT
FILTER,AIR
4 RKW129A214A CAP
12
50
3 RKW437A400
10
30
Note
8 W458.5H345.3(t2)
5 RKW133A401
PLATE,ORNAMENT
6 RKW011G400
LABEL,WIRING
8 RKW436A200A FLAP(A)
2 UPPER
9 RKW436A201A FLAP(B)
2 LOWER
10 RKW436A203A LOUVER
11 RKW129A209A PLATE,CONNECTING
12 RKW436A203A LOUVER
13 RKW129A209A PLATE,CONNECTING
14 RKW935C200
COLLAR
15 RKW129A208A JOINT(L)
16 RKW129A210
BRACKET,MOTOR(A)
17 RKW144A201
LINK
18 RKW144A202
CRANK(A)
19 RKW144A203
CRANK(B)
20 RKW144A204
CRANK(C)
21 SSA512T049
MOTOR,STEPPING
22 RKW129A207A JOINT(R)
23 RKW129A211
BRACKET,MOTOR(B)
24 RKW144A204
CRANK(C)
FOR LOUVER(LEFT),FLAP
25 SSA512T049
MOTOR,STEPPING
26 RKW504A401
HARNESS ASSY
27 RKW504A402
HARNESS ASSY
28 SSA423A102A
HOSE,DRAIN
1
1
FOR LOUVER(RIGHT)
29 SSA326A043
PLUG
30 RKW116A400
BRACKET,PANEL(R)
31 RKW116A401
BRACKET,PANEL(L)
33 SSA512T099
MOTOR,DC
2 FOR IMPELLER
34 SSA431G043A
IMPELLER
35 SSA923C114
BEARING,PLANE
36 RKW129A201
BRACKET,MOTOR(U)
37 RKW129A202
BRACKET,MOTOR(L)
38 RKW032A200A PLATE,INSTALLATION
39 PHA129A302A
COVER ASSY(PIPE)
77 -
'13 SRK-T-138
DXK32ZL-S
END ITEM NO. :
No.
Part No.
40 RKW132A400
42
RWA002F070C
Part Name
RE.Q
30
50
100
500
LID(R)
41 RKW132A401
LID(L)
43 RKW132A403
LID ASSY(TERMINAL)
43 RSA011H027
LABEL,NOTICE
44 RKW129A405
COVER,PIPE
45 RKW129A213
HOLDER,FILTER
46 SSA913A007A
SCREW,TAP
78 -
Note
1000
414
'13 SRK-T-138
MEMO
79 -
'13 SRK-T-138
11 10
25
16
25
12
17
18
22
21
19
2
15
26
30
20
29
14
13
28
27
31
24
6
4
23
7
CRAE0258
80 -
'13 SRK-T-138
DXK32ZL-S
END ITEM NO. :
No.
1
Part No.
12 RMA301A003B
2 RMA315D004A
3 RKW129A410
4 7 RMA315A004
4 RSA315A006
RWA002F070C
Part Name
RE.Q
HEADER ASSY
BRACKET ASSY(L)
DISTRIBUTOR ASSY
DISTRIBUTOR
HEADER
5 RSA315D019
6 SSA315B143BA CAPILLARY
8
7 P210V28X100
11 RMA321A030A
20
29
30
50
100
500
1000
Note
1
2
CAPILLARY
PIPE ASSY
8 RMA321A031
9 RMA321A024
PIPE ASSY(GAS)
PIPE ASSY(LIQUID)
10 SSA323F012F
11 SSA323F088A
UNION,SOLDER
UNION(SLD)
HOLDER ASSY,FILTER
BOX ASSY,CONTROL(R)
BOX,CONTROL(R)
14 RKW132A404
15 RKW142A401
COVER,CONTROL(R)
BOX ASSY,CONTROL(L)
16 RKW129A407
17 SSA551A223G
HOLDER,SENSOR
SENSOR ASSY
18 SSA551B017C
19 SSA561B702B
SENSOR(HUMIDITY)
BLOCK,TERMINAL
12 RKW129A411
13 14 RKW142A400
13 RKW142A402
FOR GAS
FOR LIQ.
1
22 SSA564A132
23 RKW503A400
FUSE(CURRENT)
2Z
2 F 3.15A
DISPLAY ASSY
24 RKW505A400
25 RKJ941F001A
PWB ASSY(DISPLAY)
SPRING,LEAF
2
2
10
26 RKW008A400N PARTS,STANDARD
CONTROL ASSY,REMOTE
27 RKW502A200
28 RKW012A410A MANUAL,INSTRUCTION
FILTER ASSY,CLEAN
30 RKW437A201
29 RKT437A005D
30 RKT437A801B
FILTER,LIGHT CLEAN
FILTER,CLEAN(BIO)
1
1
31 RKN032A002C HOLDER(REMO-CON)
(32) RKW011F400AB LABEL,MODEL NAME
1
1
81 -
2 RKN032A002B
'13 SRK-T-138
PANEL ASSY
15
14
2
12
7
16
13
3
5
15
4
8
13
15
15
9
1
11
10 15
CRBE0347
82 -
'13 SRK-T-138
DXC32ZL-S
END ITEM NO. :
No.
2
4
7
9
RWC003F089A
Part No.
Part Name
RE.Q
30
50
100
500
1 RCR111A102
BASE ASSY
3 PCA122A062
PANEL ASSY,FRONT
3 SSA944B031A
HANDLE
5 RCR122A101
PANEL ASSY,SERVICE
5 SSA944B031A
HANDLE
6 RCR124A102
PANEL ASSY,TOP
8 RCR125A101
PANEL ASSY,REAR
8 SSA944B031A
HANDLE
Note
1000
10 PCA142A065F
COVER,FRONT
10 S751W25X
GROMMET
2 30
11 PCA142A184B
COVER,SIDE
12 PCA131A032B
GUARD,FIN
13 PCA131A039
GUARD,FAN
14 PCA941G004
CUSHION,RUBBER
15 SSA913D020
41
M510
16 SSA913D020A
M514
83 -
'13 SRK-T-138
9
19
TO COMP.
10
16
5
4
18
14
A
15
11
(LIQ.)
13
12
(GAS)
CRBE0348
84 -
'13 SRK-T-138
DXC32ZL-S
END ITEM NO. :
No.
1
3
10
Part No.
RWC003F089A
Part Name
RE.Q
6 RCR301A103
2 RCR315D102
HEADER ASSY,GAS
6 RCR315A101
DISTRIBUTOR ASSY
30
50
100
1
500
1
Note
1000
2
3 RSA315A004A
DISTRIBUTOR
4 RCR315B101
CAPILLARY
2.64.0 L300
5 RCR315B102
CAPILLARY
2.64.0 L300
6 RCR315B105
CAPILLARY
2.64.0 L300
7 AHT351A001
ACCUMULATOR ASSY
8 PCA381A062C
VALVE,SERVICE(5/8")
9 S S A 3 8 2 C 0 68
VALVE,S(4WAY)
2 GAS
20 S
15 RCR304A109A
PIPING ASSY(EXPAN)
10 SSA387F065
VALVE,BODY(EXP)
2 EEV
11 SSA357A005
STRAINER
12 SSA357A005A
STRAINER
13 RCT315B002
CAPILLARY
14 RCR325A103
PIPE ASSY,SHELL
15 RCR381A100
VALVE,SERVICE(1/4")
16 RCR116A116
BRACKET ASSY(VALVE)
17 PCA141A110
PLATE ASSY,BAFFLE
18 RCM382F001J
COIL,SOLENOID
19 RPC382F900
COIL ASSY,SOLENOID
2.64.0 L300
1
2 LIQ.
4 FOR EEV
4 FOR 20S
85 -
'13 SRK-T-138
13
7 8
4
12
10
11
11
7 8
17
19
18
5 6
20
22
14
16
23
21
15
CRBE0349
86 -
'13 SRK-T-138
DXC32ZL-S
END ITEM NO. :
No.
Part No.
RWC003F089A
Part Name
RE.Q
30
50
100
500
1 RCR116A115
BASE,MOTOR
2 SSA431B228
FAN,PROPELLER
3 SSA512T076S
MOTOR,DC
4 SSA512T076R
MOTOR,DC
5 SSA914H014A
NUT,CAP
6 SSA915F002D
WASHER(TH-INT)
7 SSA913C021A
SCREW,TAP
8 W200H06
WASHER
9 S751W30X
GROMMET
PLATE,BAFFLE
10 PCA141A096B
Note
1000
11 SSA913D020
12 RCR141A104
PLATE ASSY,BAFFLE
10
1
13 RCR141A107
PLATE ASSY,BAFFLE(U)
14 AHT201C264C
COMPRESSOR ASSY
15 SSA941C246
CUSHION,RUBBER
16 SSA914C013
NUT,FLANGE
17 SSA947K026
COVER,TERMINAL
18 SSA932C009A
GASKET,COVER
19 SSA914C016
NUT,FLANGE
20 RCR154D104A
INSULATION,COMP
21 RCR154D105
INSULATION,COMP
22 RCR154D106
INSULATION,COMP
23 RCR504A037
WIRING ASSY
87 -
35
M510
4 RMT5126MCE1
'13 SRK-T-138
17
16
15
8
56
18
9
4
720
719
10
11
14
12
13
88 -
CRBE0350
'13 SRK-T-138
DXC32ZL-S
END ITEM NO. :
No.
1
15
Part No.
17 RCR501A103
RWC003F089A
Part Name
RE.Q
30
50
100
500
Note
1000
CONTROL UNIT
1 RCT505A302A
PWB ASSY(MAIN)
8 PWB1
2 RCT505A303
PWB ASSY(SUB)
8 PWB2
3 SSA561B665
BLOCK,TERMINAL
TB1
4 SSA561B702B
BLOCK,TERMINAL
TB2
5 SSA564A136A
FUSE(CURRENT)
6 SSA564B088
HOLDER,FUSE
7 SSA551A233C
SENSOR ASSY
4 20A
4 TH2,3,4
8 SSA554D173
CORE,FERRITE
9 RCR504A040
WIRING ASSY
10 RPC504A917A
HARNESS ASSY
11 RCT504A001A
HARNESS ASSY
12 RCR504A036A
HARNESS ASSY
13 RCR504A039A
HARNESS ASSY
PWB2 CNFAN1,PWB2
CNFAN2- FM01,FM02
14 RCT504A012
HARNESS ASSY
17 RCR142A103
LID ASSY,CONTROL
16 RCN011H500
LABEL,NOTICE
17 RCR011G101
LABEL,WIRING
18 SSA554B089
REACTOR
1 9 R K J9 4 1F 0 01 A
S P R IN G , L E A F
20 R C J941F001
(21) RCR011F100C
4
F O R TH 4
S P R IN G ,L E A F
F OR TH2
LABEL,MODEL NAME
89 -
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
C Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.