Table of contents
Table of contents
1
Introduction ......................................................................................................................... 8
1.1
Manufacturer ....................................................................................................................................... 8
1.2
1.3
Completeness...................................................................................................................................... 8
1.4
Safekeeping......................................................................................................................................... 8
1.5
1.5.1
1.5.2
1.5.3
1.5.4
Safety ................................................................................................................................. 12
2.1
2.2
2.3
Inappropriate use............................................................................................................................... 12
2.4
2.5
3.1
3.2
3.3
3.4
3.5
Hardware ........................................................................................................................................... 19
3.5.1
3.5.2
3.5.3
3.5.4
3.5.5
Modules ............................................................................................................................................................... 24
4.1
Packaging .......................................................................................................................................... 27
4.1.1
Purpose ............................................................................................................................................................... 27
4.1.2
4.1.3
Markings .............................................................................................................................................................. 27
3550953/00 EN
Table of contents
4.2
4.3
Storage of shipments......................................................................................................................... 28
Mounting ............................................................................................................................ 30
5.1
Preparation ........................................................................................................................................ 30
5.2
5.2.1
5.2.2
5.2.3
5.2.4
Wall mounting...................................................................................................................................................... 35
5.2.5
5.3
5.3.1
5.3.2
5.3.3
5.3.4
5.3.5
5.3.6
5.3.7
Commissioning ................................................................................................................. 47
6.1
6.2
6.2.1
6.2.2
6.3
6.3.1
6.3.2
6.3.3
7.1
7.2
General .............................................................................................................................................. 59
7.2.1
7.2.2
7.2.3
7.2.4
7.2.5
3550953/00 EN
Table of contents
7.2.6
7.2.7
7.2.8
7.2.9
7.2.10
Activating Local/Remote...................................................................................................................................... 67
7.3
NORMset ........................................................................................................................................... 68
7.4
7.4.1
7.4.2
7.4.3
Bandwidth............................................................................................................................................................ 73
7.4.4
7.4.5
7.4.6
7.5
Limit values........................................................................................................................................ 77
7.5.1
7.5.2
7.5.3
7.5.4
7.5.5
7.5.6
7.6
Compensation ................................................................................................................................... 86
7.6.1
7.6.2
Z compensation ................................................................................................................................................... 89
7.7
7.7.1
7.7.2
7.7.3
7.7.4
7.7.5
7.8
Parallel operation............................................................................................................................... 98
7.8.1
7.8.2
7.8.3
7.8.4
7.8.5
Setting delay time for parallel operation error messages .................................................................................. 104
7.8.6
7.8.7
3550953/00 EN
Table of contents
7.8.8
7.9
7.9.1
7.9.2
7.10
7.10.1
7.10.2
Setting lower limit value for the desired value ................................................................................................... 110
7.10.3
Setting upper limit value for the desired value .................................................................................................. 111
7.11
7.11.1
7.11.2
7.12
7.13
7.13.1
7.13.2
7.13.3
7.13.4
7.13.5
7.13.6
7.13.7
7.13.8
7.13.9
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
3550953/00 EN
Table of contents
10
11
12
12.1
12.2
12.3
12.4
12.5
12.6
12.7
12.8
Glossary........................................................................................................................... 143
List of key words............................................................................................................. 144
3550953/00 EN
1 Introduction
1 Introduction
This technical file contains detailed descriptions on the safe and proper installation, connection, commissioning and monitoring of the product.
It also includes safety instructions and general information about the product.
This technical file is intended solely for specially trained and authorized personnel.
1.1 Manufacturer
The product is manufactured by:
Maschinenfabrik Reinhausen GmbH
Falkensteinstrae 8
93059 Regensburg, Germany
Tel.: (+49) 9 41/40 90-0
Fax: (+49) 9 41/40 90-7001
E-mail: sales@reinhausen.com
Further information on the product and copies of this technical file are available from this address if required.
1.3 Completeness
This technical file is incomplete without the supporting documentation.
1.4 Safekeeping
This technical file and all supporting documents must be kept ready at hand
and accessible for future use at all times.
3550953/00 EN
1 Introduction
WARNING
Meaning
DANGER
WARNING
CAUTION
NOTICE
Meaning
Warning of a danger point
3550953/00 EN
1 Introduction
Pictogram
Meaning
Warning of dangerous electrical voltage
Requirements (optional).
Step 1 of 1.
Multi-step instructions
Instructions which consist of several process steps are structured as follows:
Aim of action
10
Requirements (optional).
3550953/00 EN
1 Introduction
1.
Step 1.
2.
Step 2.
Purpose
Example
UPPERCASE
Operating controls,
switches
PC keyboard
Software operating controls
Menu paths
ON/OFF
[Brackets]
Bold
>>
Italics
[ Number of
pages].
[Ctrl] + [Alt]
Press Continue button
Parameter > Control parameter
Function monitoring alarm
triggered
[ 41].
3550953/00 EN
11
2 Safety
2 Safety
2.1 General safety information
The technical file contains detailed descriptions on the safe and proper installation, connection, commissioning and monitoring of the product.
Read this technical file through carefully to familiarize yourself with the
product.
The product must be operated in accordance with this technical file and
the agreed delivery conditions and technical data
The equipment and special tools supplied must be used solely for the intended purpose and in accordance with the specifications of this technical file
12
3550953/00 EN
2 Safety
Only replacement parts, lubricants and auxiliary materials which are authorized by the manufacturer are used.
All necessary devices and personal protective equipment for the specific
activity are made available.
3550953/00 EN
13
3 Product description
3 Product description
This chapter contains an overview of the design and function of the product.
Door key
Optional:
14
3550953/00 EN
3 Product description
Check the shipment for completeness on the basis of the shipping documents.
3550953/00 EN
15
3 Product description
Summer
Winter
Regulation section
Regulating transformer
Measurement
transformer
Inputs
digital and analog
16
3550953/00 EN
3 Product description
Additional indicators using LEDs outside the display for freely selectable
functions
Master/Follower
3550953/00 EN
and
keys is disa-
17
3 Product description
+ LOCAL
Automatic regulation
Tap-change operation using operating controls
Tap-change operation using inputs
+ REMOTE
+ LOCAL
+ REMOTE
Yes
No
Yes
No
No
Yes
No
No
No
No
No
Yes
18
3550953/00 EN
3 Product description
3.5 Hardware
Figure 6: Hardware
1
2
3550953/00 EN
Door
19
3 Product description
20
3550953/00 EN
3 Product description
3550953/00 EN
21
3 Product description
10
11
15
16
4
5
6
7
8
22
3550953/00 EN
12
13
14
3 Product description
Display
Status line
2
3
7
8
or
to switch between
them)
Tap position n-1; n; n+1
10
Other measured values In auto mode and manual mode the measured value display
using the
played:
or
can be set
Unit
Measured value
dU
I
S
P
Q
Phase
Control deviation
Current
Apparent power
Active power
Reactive power
Phase angle
3550953/00 EN
23
3 Product description
Unit
Measured value
Cos
Status line Current messages and events are displayed in the status line . You can
find more information about messages and events in the Messages chapter.
3.5.5 Modules
The device has integrated modules:
MIO card
PIO card
Carry out wiring in accordance with the supplied connection diagram. The
relevant cards are described in the following sections.
24
3550953/00 EN
3 Product description
3550953/00 EN
25
3 Product description
2
3
26
3550953/00 EN
4.1.3 Markings
The packaging bears a signature with instructions for safe transport and correct storage. The following symbols apply to the shipment of non-hazardous
goods. Adherence to these symbols is mandatory.
Protect
against
moisture
Top
Fragile
Attach lifting
gear here
Center of
mass
3550953/00 EN
27
If a crate tips over, falls from a certain height (e.g. when slings tear) or experiences an unbroken fall, damage must be expected regardless of the
weight.
Every delivered shipment must be checked for the following by the recipient
before acceptance (acknowledgment of receipt):
The checks must take place after unloading when the crate or transport container can be accessed from all sides.
Visible damage If external transport damage is detected on receipt of the shipment, proceed
as follows:
Immediately record the transport damage found in the shipping documents and have this countersigned by the carrier.
In the event of severe damage, total loss or high damage costs, immediately notify the sales department at Maschinenfabrik Reinhausen and
the relevant insurance company.
Record the details of the damage immediately onsite together with the
carrier involved. This is essential for any claim for damages!
Hidden damage When damages are not determined until unpacking after receipt of the shipment (hidden damage), proceed as follows:
Make the party responsible for the damage liable as soon as possible by
telephone and in writing, and prepare a damage report.
With hidden damage, it is very hard to make the transportation company (or
other responsible party) liable. Any insurance claims for such damages can
only be successful if relevant provisions are expressly included in the insurance terms and conditions.
28
3550953/00 EN
Store the crates on timber beams and planks as a protection against rising damp and for better ventilation.
Check stored goods at regular intervals. Also take appropriate action after storms, heavy rain or snow and so on.
3550953/00 EN
29
5 Mounting
5 Mounting
This chapter describes how to correctly mount and connect the device. Note
the connection diagrams provided.
WARNING
Electric shock
Risk of fatal injury due to electrical voltage.
De-energize the device and system peripherals and lock them to prevent them from being switched back on.
Do so by short-circuiting the current transformer; do not idle the current
transformer.
NOTICE
Electrostatic discharge
Damage to the device due to electrostatic discharge.
Take precautionary measures to prevent the build-up of electrostatic
charges on work surfaces and personnel.
5.1 Preparation
The following tools are needed for mounting:
Small screwdriver for connecting the signal lines and supply lines
30
Wall mounting
3550953/00 EN
5 Mounting
Loosen the 4 Allen screws with attached Allen key to remove the mounting brackets.
2.
Loosen the 4 Allen screws with attached Allen key to remove the cable
gland plate.
The mounting brackets and the cable gland plate are removed.
3550953/00 EN
31
5 Mounting
A wall thickness of 2...5 mm (0.08...0.2 in) is needed for secure device fixing.
To mount the device in the control panel or control cabinet, proceed as follows:
32
1.
2.
Insert the device through the cutout in the control panel or control cabinet .
3.
Screw both fixing brackets to the rear of the device with 2 hexagon
socket screws each .
3550953/00 EN
5 Mounting
1.
2.
Screw the mounting brackets supplied to the back of the device using
the hexagon socket screws .
3.
Fix the device on the wall using 4 screws (maximum diameter of 5 mm/
0.22 in) .
3550953/00 EN
33
5 Mounting
The screws for fixing to the wall are not included in the scope of supply. The
screw length required depends on the wall thickness.
34
1.
2.
Screw the cap rail clip into the two top holes on the rear with the M5
hexagon socket countersunk head screws provided .
3.
Suspend the cap rail clip in the cap rail and push the underside carefully
towards the wall until the clip can be heard to click into place .
3550953/00 EN
5 Mounting
Fix the device on the wall from behind using 4 screws (M5)
The screws for wall mounting are not included in the scope of supply. The
screw length required depends on the wall thickness.
3550953/00 EN
35
5 Mounting
36
3550953/00 EN
5 Mounting
2.
3.
The door is removed and the exposed attachment points for the door
are covered.
WARNING
Electric shock
Danger of death due to connection mistakes
Ground device using the grounding screw on the housing.
Pay attention to the phase difference of the secondary terminals for the
current transformer and voltage transformer.
Connect the output relays correctly to the motor-drive unit.
3550953/00 EN
37
5 Mounting
Terminal
Cable type
Wire crosssection
Max. length
Analog input
X7
1.5 mm
400 m
Signal inputs
RS232 SUB-D
RS485
X4
-
1.5 mm
0.25 mm
0.75 mm
25 m
1000 m
0.6 Nm
-
Ethernet RJ45
Relay outputs*
Relay outputs*
optional
Current measurement
Relay outputs
Signal inputs
Digital tap position inputs
Auxiliary voltage
Power supply
CAN bus
X3
X4
shielded
(< 25 /km)
Shielded
Shielded
shielded
(< 50 /km)
min. CAT5
Unshielded
Unshielded
1.5 mm
1.5 mm
0.6 Nm
0.6 Nm
X1:5/6/9
Unshielded
4 mm
1.5 Nm
X5
X6
X6
Unshielded
Unshielded
Shielded
1.5 mm
1.5 mm
1.5 mm
0.6 Nm
0.6 Nm
0.6 Nm
X6
X2:3/4
-
Unshielded
Unshielded
Shielded
1.5 mm
1.5 mm
1.0 mm
2000 m
0.6 Nm
0.6 Nm
-
38
3550953/00 EN
5 Mounting
Radii must not fall below the minimum permissible bend radii (do not
bend fiber-optic cable).
The system's ground connection must comply with all technical regulations.
The device and its wiring must be at least 10 m away from circuit-breakers, load disconnectors and busbars.
The connection cables must be laid in metallic cable ducts with a ground
connection.
Do not route lines which cause interference (for example power lines)
and lines susceptible to interference (for example signal lines) in the
same cable duct.
3550953/00 EN
39
5 Mounting
1
2
3
4
Using "pigtails" may limit the effectiveness of the shielding. Connect closefitting shield to cover all areas.
40
3550953/00 EN
5 Mounting
The control cabinet for fitting the device must be prepared in accordance with EMC requirements:
The device's connection cables must be laid in close contact with the
grounded metal housing or in metallic cable ducts with a ground connection.
Signal lines and power lines/switching lines must be laid in separate cable ducts.
3550953/00 EN
41
5 Mounting
42
3550953/00 EN
5 Mounting
NOTICE
2.
3550953/00 EN
43
5 Mounting
Use only the specified cables for wiring. Note the cable recommendation
[ 38].
2.
3.
Connect the auxiliary voltage using the following terminals: X2:3 and
X2:4.
44
3550953/00 EN
5 Mounting
Use only the specified cables for wiring. Note the cable recommendation
[ 38].
1.
Remove 4 hexagon socket screws from cover plate and take off cover
plate.
2.
3.
Remove 4 hexagon socket screws from the cable gland plate and take
off the cable gland plate.
4.
Remove dummy plug from required cable glands in order to guide cables through.
5.
6.
7.
8.
9.
10. Guide the cable gland plate into the device opening provided for this
purpose.
11. Plug connectors into the correct slots.
12. Secure cable gland plate to device housing with 4 hexagon socket
screws.
NOTICE
3550953/00 EN
45
5 Mounting
Once you have connected the device to the grid, the screen displays the
MR logo and then the operating screen.
The green Operating display LED top left on the device's front panel
lights up.
The device is fully mounted and can be configured. The actions required for
this are described in the following chapter.
46
3550953/00 EN
6 Commissioning
6 Commissioning
You need to set several parameters and perform function tests before commissioning the device. These are described in the following sections.
NOTICE
An incorrectly connected device can lead to damages in the device and system periphery.
Check the entire configuration before commissioning.
Prior to commissioning, be sure to check the actual voltage and operating voltage.
We recommend using a device for industrial instrumentation to record the
actual transformer voltage value in order to evaluate how the device is functioning.
3550953/00 EN
47
6 Commissioning
Italian
Portuguese
Russian
>
Configuration >
General.
Language
2.
Press
or
3.
Press
2.
3.
4.
5.
Setting NORMset
If you want to quickly start up voltage regulation, you can activate NORMset
mode. If you want to set the parameters yourself, continue with the sections
below.
Activate NORMset and set the relevant parameters [ 68].
Setting control parameters
Set the following control parameters:
48
1.
2.
3.
3550953/00 EN
6 Commissioning
2.
3.
2.
3.
4.
You must ensure that the REMOTE mode is disabled before you can
control the on-load tap-changer manually in manual mode.
and
3550953/00 EN
keys.
49
6 Commissioning
During the function test, you must set the most important parameters.
Details on the parameters listed can be found in the Functions and settings [ 59] chapter.
1.
Press
2.
3.
Measure actual voltage and compare with the measured value displayed on the device's main screen.
4.
Press
key several times to display the operating values for current,
power and phase angle and compare them with values of the operating
measuring instruments.
5.
6.
7.
8.
9.
10. Press
11. Press
12. Press
13. Press
14. Press
15. Press
50
3550953/00 EN
6 Commissioning
19. Press
20. Press
21. Set delay time T1 [ 75] and delay time T2 [ 76] to the desired
value.
We recommend a temporary setting of 100 seconds for delay time T1 when
commissioning the transformer. Depending on the operating conditions, you
can also specify the delay time following a longer observation period. In this
regard, it is useful to register how the actual voltage progresses and the
number of tap-change operations per day.
Undervoltage blocking
Overvoltage blocking
Z compensation
Proceed as follows:
Checking undervoltage blocking U<
1.
Press
2.
3.
4.
Set desired value 1 such that the measured voltage Uactual is below the
undervoltage U< [%] limit value.
5.
Press
6.
The device blocks and does not issue any control commands.
Press
3550953/00 EN
51
6 Commissioning
7.
Reset the operating values for desired value 1 and undervoltage U<
[%] to the desired operating values.
Press
2.
3.
4.
Set desired value 1 such that the measured voltage Uactual is above
the overvoltage U> [%] limit value.
5.
Press
The LOWER output relay emits a control command every 1.5 seconds.
6.
Press
7.
Reset the operating values for desired value 1 and overvoltage U>
[%] to the desired operating values.
Press
2.
3.
4.
Press
6.
7.
Press
5.
52
The function test for desired value 2 and desired value 3 is complete.
3550953/00 EN
6 Commissioning
Press
2.
3.
Press
4.
If necessary, press
5.
6.
7.
Press
8.
If necessary, press
If the control deviation appears in the opposite direction, change the polarity
of the current transformer.
9.
Checking Z compensation
If you want to use Z compensation, you need to run this function test. A load
current of 10 % of the nominal transformer current is needed for the following function test .
1.
Press
2.
3.
4.
Press
5.
If necessary, press
6.
7.
Press
3550953/00 EN
53
6 Commissioning
8.
If necessary, press
If the control deviation appears in the opposite direction, change the polarity
of the current transformer.
9.
All devices are set to the same operating parameters for desired value,
circulating reactive current sensitivity and delay time T1.
2.
3.
On one of the two transformers, raise the tap position of the on-load tapchanger by one setting; on the second transformer, lower the tap position of the on-load tap-changer by one setting.
54
3550953/00 EN
6 Commissioning
4.
Adjust the circulating reactive current sensitivity until the result displayed exceeds the set value for the bandwidth by approx. 0.2 % to
0.3 %.
The value for the result changes in the help text in the last line of
the display.
5.
Set the value given in the previous step for all devices in parallel operation.
6.
Press
The devices return the on-load tap-changer units to the original tap
positions.
If the earlier tap positions are not reached, increase the value of the circulating reactive current sensitivity [ 100] parameter.
If one of the two on-load tap-changer units switches one or more tap positions higher and the other switches the same amount lower, you need to reduce the value of the circulating reactive current sensitivity [ 100] parameter.
After you have set the circulating reactive current sensitivity parameter,
continue with the circulating reactive current blocking function test described
in the next section.
6.3.3.2 Checking circulating reactive current blocking
This section describes how to run the function test for circulating reactive
current blocking.
1.
Press
2.
When setting the circulating reactive current blocking in the following process step, wait approx. 2 - 3 seconds between the individual steps.
3.
4.
The circulating reactive current blocking parameter should be reduced [ 100] from the set value of 20 % in steps of 1 % until the Parallel operation error: circulating reactive current limit exceeded is displayed.
3550953/00 EN
55
6 Commissioning
5.
After the set delay time for the parallel operation error message (time
can be adjusted [ 104]), the signaling relay X5:12 (default setting) is
activated.
6.
7.
Press
8.
Set the value determined for the circulating reactive current blocking
on the devices in parallel operation as well.
If one or all devices indicate Parallel operation error: circulating reactive current limit exceeded although the control inputs are correctly connected for
all the devices, then all the devices block.
This could be due to various causes. Further information is given in the
chapter Troubleshooting [ 126].
NOTICE
56
1.
2.
3550953/00 EN
6 Commissioning
3.
1
2
Master
Follower
Press
2.
3.
Press
4.
Press
or
5.
Press
6.
Press
7.
Press
8.
Press
or
After expiry of the set delay time for parallel operation errors
[ 104], the Tap difference to follower error message is displayed
in the main screen on the master.
3550953/00 EN
57
6 Commissioning
9.
Press
several times on the follower to manually increase the tap
position by the number of permitted steps (maximum permitted tap difference) and then one more step.
After expiry of the set delay time for parallel operation errors, the
following error messages are displayed on the master: Parallel operation error: tap difference to follower
After expiry of the set delay time for parallel operation errors, the
following error messages are displayed on the follower: Parallel operation error: permitted tap difference to master exceeded.
10. Press
11. Press
12. Press
or
sired step.
Because in parallel operation the tap positions of the transformers which are
running in parallel are compared following the Automatic tap synchronization method, it is absolutely essential that these transformers have the
same position designation and that the Raise and Lower signals produce
the same voltage change in all transformers.
The function tests for the tap synchronization method are complete.
58
3550953/00 EN
and
A confirmation appears in the display for a brief period. The key lock is
activated. Parameters can no longer be entered.
and
7.2 General
You can undertake general settings on the device in the General menu item.
You can set the following general parameters:
Language [ 48]
Regulator ID
Operations counter
Display dimming
Key lock
Function monitoring
Motor runtime
Local/Remote
3550953/00 EN
59
1.
>
Configuration >
parameter is displayed.
2.
3.
Press
4.
If necessary, press
Regulator ID.
Press
5.
Press
or
6.
7.
Press
9.6 kilobaud
19.2 kilobaud
38.4 kilobaud
57.6 kilobaud
>
Configuration >
parameter is displayed.
Baud rate.
2.
Press
or
3.
Press
60
3550953/00 EN
Switching pulse in normal If you set the switching pulse time to 1.5 seconds for example, after the set
mode delay time T1 or delay time T2
there will be a switching pulse of 1.5 seconds .
The waiting time between 2 consecutive switching pulses corresponds to the
set delay time T1 or delay time T2 .
If the motor-drive unit does not start with the factory setting (1.5 seconds),
you need to extend the raise switching pulse time / lower switching pulse
time.
Switching pulse for rapid If you set the raise switching pulse time or lower switching pulse time to
return control 1.5 seconds, for example , the next earliest switching pulse occurs in rapid
return control mode
1.5 seconds after the previous switching pulse
ended.
3550953/00 EN
61
>
Configuration >
parameter is displayed.
2.
Press
or
3.
Press
62
3550953/00 EN
1.
>
Configuration >
parameter is displayed.
2.
Operations counter.
Press
to highlight a digit.
3.
Press
4.
Press
to reduce it.
On: The display is automatically dimmed if no key is pressed for 15 minutes. The display returns to full brightness by pressing any key.
Press
>
Configuration >
parameter is displayed.
General >
Display off.
2.
Press
or
3.
Press
3550953/00 EN
63
1.
>
Configuration >
parameter is displayed.
Key lock
2.
Press
or
to select On or Off.
3.
Press
Function
On
Off
Table 8: Settings
>
Configuration >
parameter is displayed.
Function monitoring
2.
Press
or
to select On or Off.
3.
Press
The Function monitoring message for is activated/deactivated for measured voltages <30 V.
Setting delay time You can configure the delay time after which the Function monitoring message is to be issued. If you select 0, function monitoring is deactivated.
To set the delay time for the Function monitoring message, proceed as follows:
64
3550953/00 EN
1.
>
Configuration >
parameter is displayed.
2.
Press
to reduce it.
3.
Press
2.
3.
Pulse signal via Trigger motor protective switch output relay (optional)
Parameterizing control To use runtime monitoring, you need to correctly wire the corresponding
input control input and parameterize to Motor running. The motor runtime must also be set.
Wiring control input/output If you want to monitor the motor runtime, the device and motor-drive unit
relay must be connected and parameterized as shown below.
3550953/00 EN
65
If you want to use the output relay, the feedback from the motor-drive unit
Motor protective switch triggered must be wired to a control input and parameterized. This message resets the Motor runtime exceeded output relay
when the motor protective switch is switched back on and activates the Motor protective switch triggered message.
If the runtime monitoring is set to "0.0 s", this equates to it being switched
off.
66
3550953/00 EN
1.
>
Configuration >
parameter is displayed.
2.
Motor runtime.
Press
3.
Press
4.
Press
to reduce it.
and
keys.
Parameter
Function
Manual
Auto
>
Configuration >
parameter is displayed.
Manual/Automatic
2.
Press
or
3.
Press
3550953/00 EN
keys.
67
Parameter
Function
Local
Remote
>
Configuration >
parameter is displayed.
2.
Local/Remote
3.
Press
or
4.
Press
7.3 NORMset
NORMset mode is used for quickly starting voltage regulation. In NORMset
mode, the bandwidth and delay time parameters are automatically adapted
to the requirements of the grid.
To start NORMset mode, you must set the following parameters:
Normset activation
Desired value 1
Primary voltage
Secondary voltage
68
3550953/00 EN
1.
>
NORMset
NORMset activation.
2.
Press
or
to activate NORMset by selecting On or to deactivate
NORMset by selecting Off.
3.
Press
NORMset is activated/deactivated.
>
played.
Primary voltage.
2.
Press
3.
Press
to reduce it.
>
played.
Secondary voltage.
2.
Press
3.
Press
to reduce it.
3550953/00 EN
69
>
played.
Desired value 1.
2.
Press
3.
Press
to reduce it.
Desired values 13
Bandwidth
Delay time T1
Control response T1
Delay time T2
For voltage regulation, you can set delay time T1 and also delay time T2.
The following sections describe how the regulation function responds in both
cases:
Response only to delay time T1
If the measured voltage Vactual
is within the set bandwidth , no control
commands are issued to the motor-drive unit for the tap-change operation.
Control commands will also not be issued to the motor-drive unit if within the
set delay time T1
the measured voltage returns to the tolerance bandwidth . However, if the measured voltage deviates from the set bandwidth
for a long period , a tap-change command
occurs after the set delay
time T1. The on-load tap-changer carries out a tap-change in a positive or
negative direction to return to the tolerance bandwidth.
70
3550953/00 EN
1
2
3
A
+ B %: Upper limit
Vdesired: Desired value
- B %: Lower limit
Vactual is outside the bandwidth. Delay time T1 starts.
4
5
6
B
3550953/00 EN
71
Figure 40: Response of the regulation function with delay times T1 and T2
1
2
3
A
C
+ B %: Upper limit
Vdesired: Desired value
- B %: Lower limit
Vactual is outside the bandwidth. Delay time T1 starts.
Delay time T2 complete. Tap
change triggered.
4
5
6
B
The following sections describe how to set the relevant control parameters.
72
Using the control parameters menu item via the operating screen
3550953/00 EN
Reference of kV and V for Desired values set in kV refer to the primary voltage of the voltage transvoltage transformer former. Desired values set in V refer to the secondary voltage of the voltage
transformer. The transformer data must be entered correctly for this display.
To set the desired value, proceed as follows:
1.
>
Control parameter >
voltage regulator > Press
the desired parameter is displayed.
2.
3.
Press
until
to select
4.
Press
5.
Press
to reduce it.
>
Control parameter >
Voltage regulation > Press
until the desired parameter is displayed.
2.
Press
or
3.
Press
7.4.3 Bandwidth
You can use this parameter to set the maximum permissible deviation in
measured voltage UAct. The deviation relates to the activated desired value.
The following sections describe how you determine and set the bandwidth
required.
7.4.3.1 Determining bandwidth
In order to set the correct value, the transformer's step voltage and nominal
voltage must be known.
3550953/00 EN
73
Too small/large a You have to set the bandwidth in such a way that the output voltage of the
bandwidth transformer (VAct) returns to within the specified tolerance bandwidth after the
tap change. If too small a bandwidth is defined, the output voltage exceeds
the bandwidth selected and the device immediately issues a tap-change
command in the opposite direction. If a very large bandwidth is selected, this
results in a major control deviation.
The following value is recommended for the bandwidth setting:
Un-1
Un
Unom
The following section describes how you can set the bandwidth.
7.4.3.2 Setting the bandwidth
To enter the determined bandwidth, proceed as follows:
1.
>
Parameter >
Control parameter > Press
desired parameter is displayed.
2.
Press
3.
74
until the
Press
3550953/00 EN
to reduce it.
4.
Press
2
3
>
Parameter >
Control parameter > Press
desired parameter is displayed.
2.
Press
until the
3.
Press
4.
Press
3550953/00 EN
to reduce it.
75
V/B
1
>
Parameter >
Control parameter > Press
desired parameter is displayed.
2.
Press
or
3.
Press
until the
76
3550953/00 EN
The delay time T2 only takes effect if more than one tap-change operation is
required to return the voltage to within the set bandwidth. The first output
pulse occurs after the set delay time T1. After the set tap-change delay time
T2 has elapsed, additional pulses occur in order to correct the existing control deviation.
The following requirements must be noted to set delay time T2:
The delay time T2 must be greater than the switching pulse time.
The delay time T2 must be greater than the maximum operating time of
the motor-drive unit.
The delay time T2 must be less than the value set for delay time T1.
>
Parameter >
Control parameter > Press until the desired parameter is displayed.
2.
Press
3.
Press
to reduce it.
>
Parameter >
Control parameter > Press
desired parameter is displayed.
until the
T2 activation.
2.
Press
or
to activate/deactivate T2.
3.
Press
Undervoltage V<
Overvoltage V>
Overcurrent I>
3550953/00 EN
77
1
2
3
+ B %: Upper limit
Udesired: Desired value
- B %: Lower limit
7
A
B
5
6
78
3550953/00 EN
>
Control parameter >
desired parameter is displayed.
until the
2.
Press
to reduce it.
3.
Press
>
Control parameter >
desired parameter is displayed.
2.
until the
U< Delay
Press
3.
Press
to reduce it.
4.
Press
Function
On
Off
3550953/00 EN
79
1.
>
Control parameter >
desired parameter is displayed.
until the
U< blocking.
2.
Press
for On setting or
3.
Press
Function
On
Off
>
Control parameter >
desired parameter is displayed.
until the
2.
Press
for On setting or
3.
Press
80
3550953/00 EN
1
2
3
4
A
B
C
Response to overvoltage If you activated the overvoltage blocking, all switching pulses to the motorblocking drive unit are blocked when a limit value is exceeded. At the same time, the
red LED U> lights up and the Overvoltage U> message is displayed. As
soon as the measured voltage Uactual has again fallen below the limit value,
blocking and the message are reset.
The following sections describe how you can set the parameters for the
overvoltage U> limit value.
Setting overvoltage U> as %
The limit value is entered as a relative value (%) of the set desired value. To
set the limit value, proceed as follows:
3550953/00 EN
81
1.
>
Control parameter >
desired parameter is displayed.
until the
2.
Press
3.
Press
to reduce it.
Behavior
On
Off
>
Control parameter >
desired parameter is displayed.
until the
2.
Press
or
3.
Press
82
3550953/00 EN
1.
>
Control parameter >
desired parameter is displayed.
until the
I> Overcurrent
2.
Press
3.
Press
to reduce it.
>
Control parameter >
desired parameter is displayed.
until the
2.
Press
ing.
or
3.
Press
>
Control parameter >
desired parameter is displayed.
until the
2.
Press
3.
Press
to reduce it.
3550953/00 EN
83
1.
>
Control parameter >
desired parameter is displayed.
until the
2.
Press
ing.
or
3.
Press
>
control parameter >
Compensation > Press
the desired parameter is displayed.
until
2.
Press
or
3.
Press
84
3550953/00 EN
1.
>
Configuration >
2.
Continue >
Tap
Press
Continue >
to highlight a digit.
3.
Press
to reduce it.
4.
Press
>
Configuration >
2.
Continue >
Tap
Press
Continue >
to highlight a digit.
3.
Press
4.
Press
to reduce it.
Setting
Behavior
Off
Directional
3550953/00 EN
85
Setting
Behavior
Non-directional
Press
Press
1.
>
Configuration >
Continue >
Continue >
Tap
2.
Press
or
3.
Press
7.6 Compensation
You can use the compensation function to compensate for the load-dependent voltage drop between the transformer and consumer. The device provides 2 methods of compensation for this purpose:
Z compensation
Line drop compensation
Z compensation
Is simple to set
Can be used with meshed networks
86
3550953/00 EN
To set line drop compensation correctly, you need to calculate the ohmic
and inductive voltage drop in V with reference to the secondary side of the
voltage transformer. You also need to correctly set the transformer circuit
used.
You can calculate the ohmic and inductive voltage drop using the following
formulas. This voltage drop calculation relates to the relativized voltage on
the secondary side of the voltage transformer.
Formula for calculating the ohmic voltage drop:
Ur
Ux
3550953/00 EN
87
IN
kCT
kVT
r
x
L
K
>
Compensation method.
Compensation method.
Press
or
1.
Press
2.
The following sections describe how you can set the parameters for the
ohmic and inductive voltage drop.
7.6.1.1 Setting the ohmic voltage drop Ur
You can use this parameter to set the ohmic voltage drop.
If you do not want to use line drop compensation, you have to set the value
0.0 V.
1.
>
Parameter >
Compensation > Press
sired parameter is displayed.
2.
88
Press
3.
Press
4.
Press
3550953/00 EN
to reduce it.
1.
>
Parameter >
Compensation > Press
sired parameter is displayed.
2.
Press
3.
Press
4.
Press
to reduce it.
7.6.2 Z compensation
To keep the voltage constant for the consumer, you can use Z compensation
to activate a current-dependent increase in voltage. Z compensation is not
dependent on the phase angle and should only be used for small changes
in phase angle.
You can also define a limit value to avoid excess voltage on the transformer.
3550953/00 EN
89
U
UTr
ULoad
Voltage increase
Transformer voltage with
current I
Voltage on line end with
current I and on-load tapchanger in same operating
position
I
IN
kCT
Load current in A
Nominal current of current
transformer connection in A
(1 A; 5 A )
Current transformer ratio
>
Compensation method.
Compensation method.
Press
or
1.
Press
2.
The following sections describe how you can set the required parameters for
Z compensation.
7.6.2.1 Setting Z compensation
This parameter sets the voltage increase V previously calculated.
If you do not want to use Z compensation, you have to set the value 0.0 %.
90
3550953/00 EN
Select Z compensation.
1.
>
Parameter >
Compensation > Press
sired parameter is displayed.
Z compensation.
2.
Press
to reduce it.
3.
Press
To set the limit value for the current-dependent voltage increase, proceed as
follows:
Select Z compensation.
1.
>
Parameter >
Compensation > Press
sired parameter is displayed.
2.
Press
3.
Press
to reduce it.
Primary voltage
Secondary voltage
Primary current
Transformer circuit
3550953/00 EN
91
The measured values displayed for the device are influenced by the settings
for the above parameters. Note the table below.
Parameter set
Primary
voltage
Secondary
voltage
Primary
current
Transformer
connection
Voltage (main
screen)
Current
(main screen)
Current (info
screen)
Yes
Yes
Yes
Primary voltage
[kV]
Yes
Yes
Yes
Primary voltage
[kV]
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Primary voltage
[kV]
Primary voltage
[kV]
>
2.
3.
92
Press
Transformer data.
Primary voltage.
Press
Configuration >
4.
Press
5.
Press
3550953/00 EN
to reduce it.
>
Configuration >
Transformer data > Press
desired parameter is displayed.
2.
Secondary voltage.
Press
until the
3.
Press
to reduce it.
4.
Press
When you are setting the primary transformer current, the measured
value is displayed in the main screen.
Setting parameter
Primary current
Current feed
Secondary current
Display
Power connection
Info screen
Main screen
Primary/secondary current
No parameterization
No parameterization
50 A
Unknown
1A
100 %
0A
1A
1A
1A
0A
Unknown
1A
50 A
1A
1A
50 A (of primary
current)
50 A (of primary
current)
3550953/00 EN
93
1.
>
Configuration >
Transformer data > Press
desired parameter is displayed.
2.
Primary current.
Press
until the
3.
Press
4.
Press
to reduce it.
1A
5A
>
Configuration >
Transformer data > Press
desired parameter is displayed.
until the
2.
Press
or
3.
Press
94
Setting
Measurement method
Phase difference
0 1PH
0 3PHN
0 3PH
90 3PH
30 3PH
1 phase
3 phase
3 phase
3 phase
3 phase
0
0
0
90
30
3550953/00 EN
Setting
Measurement method
Phase difference
-30 3PH
3 phase
-30
Note the following sample circuits to select the correct transformer circuit.
Circuit A: 1-phase measurement in 1-phase grid
TAPCON 230
TAPCON 230
3550953/00 EN
95
Circuit C:
TAPCON 230
The current transformer CT1 is looped into the outer conductor L1 and
CT2 into the outer conductor L2.
The current transformers CT1 and CT2 are connected crosswise in parallel (total current = IL1 + IL2).
The total current IL1 + IL2 and voltage VL1-VL2 are in phase.
Circuit D
TAPCON 230
96
3550953/00 EN
Circuit E
TAPCON 230
Circuit F
TAPCON 230
The current IL1 lags behind VL1-VL2 by 30. This corresponds to a phase
shift of -30.
To set the phase difference for the transformer circuit, proceed as follows:
3550953/00 EN
97
1.
>
Configuration >
Transformer data > Press
desired parameter is displayed.
until the
Transformer circuit.
2.
Press
or
3.
Press
Maximum deviation of short-circuit voltages (UK) for transformers connected in parallel < 10 %
The following sections describe how you can set the parameters. When activating parallel operation, make sure you have configured the following parameters:
98
3550953/00 EN
1.
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
until the
CAN address.
2.
Press
3.
Press
to reduce it.
You must select the same parallel operation method for all voltage regulators operating in parallel.
The following sections describe how you can set the parameters for a parallel operation method.
7.8.2.1 Setting circulating reactive current method
When the circulating reactive current parallel operation method is selected, then parallel operation is carried out using the circulating reactive current
minimization method. The circulating reactive current is calculated from the
transformer currents and their phase angles. A voltage proportional to the
circulating reactive current is added to the independently operating voltage
regulators as a correction for the measurement voltage. This voltage correction can be reduced or increased using the circulating reactive current sensitivity setting.
The circulating reactive current method is suited to transformers connected
in parallel with a similar nominal output and short-circuit voltage VK and to
vector groups with the same and different step voltages. This does not require any information about the tap position.
To set the circulating reactive current parallel operation method, proceed
as follows:
3550953/00 EN
99
1.
>
Configuration >
Parallel operation.
2.
Press
play.
or
3.
Press
When using the circulating reactive current parallel operation method, you
have to set the parameters for the circulating reactive current sensitivity
and circulating reactive current blocking.
Setting circulating reactive current sensitivity
The circulating reactive current sensitivity is a measure of its effect on the
behavior of the voltage regulator. At a setting of 0 % no effect is present.
With circulating reactive current relating to the rated current of the current
transformer, if you set the value to 10 % for example, this would cause the
voltage in the voltage regulator to be corrected by 10 %. This correction to
the voltage can be increased or decreased with this setting to attain the optimum value.
As soon as you change the circulating reactive current sensitivity value, the
value for the result changes in the help text in the display.
To set the circulating reactive current sensitivity, proceed as follows:
1.
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
2.
Press
3.
If necessary, press
until the
to reduce it.
4.
Press
All devices operating in parallel are blocked. Depending on the set delay
time for the parallel operation error message, the signaling relay Parallel operation error is activated.
100
3550953/00 EN
To set the blocking limit for the maximum permitted circulating reactive current, proceed as follows:
1.
2.
Press
to reduce it.
3.
Press
The blocking limit for the maximum permitted circulating reactive current
is set.
Description
Master
Follower
Sync.auto
In order to use the sync.auto option, an individual CAN bus address must
be assigned to each voltage regulator. Up to 16 CAN participants are supported.
To set the tap synchronization method, proceed as follows:
1.
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
until the
2.
Press
or
3.
Press
3550953/00 EN
101
Description
Standard
Swapped
dV>0 = tapping direction toward
position n
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
102
until the
2.
Press
or
3.
Press
3550953/00 EN
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
until the
2.
Press
or
to activate blocking by selecting Blocking or to deactivate blocking by selecting Off.
3.
Press
Function
None
Group 1
Group 2
Group 1 and group 2
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
until the
2.
Press
or
3.
Press
3550953/00 EN
103
1.
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
until the
2.
Press
or
to activate blocking by selecting On or to deactivate
blocking by selecting Off.
3.
Press
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
until the
Error message.
2.
Press
to reduce it.
3.
Press
The delay time for the parallel operation error message is set.
104
3550953/00 EN
the master. If the tap difference is greater than the maximum tap position deviation, the follower and master block regulation immediately. After the set
delay time for parallel operation error messages, the follower triggers the
Parallel operation error message.
To set the maximum permitted tap difference, proceed as follows:
1.
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
until the
2.
Press
to reduce it.
3.
Press
Function
On
Off
>
Configuration >
Parallel operation > Press
desired parameter is displayed.
until the
2.
Press
or
to activate the function by selecting On or to deactivate the function by selecting Off.
3.
Press
3550953/00 EN
105
1.
>
Configuration >
Parallel operation.
2.
Press
or
to activate parallel operation by selecting On or deactivate parallel operation by selecting Off.
3.
Press
Digital signal
BCD
DUAL
GRAY
Analog signal
The following sections describe how you can set the required parameters for
tap position capture. Additional parameters for the tap position limit values
can be found in the section titled "Permitted tap positions" [ 84].
BCD
Binary code
Gray code
>
position
Configuration >
Continue >
Continue >
Tap
2.
Press
or
3.
Press
106
3550953/00 EN
200...2,000 ohms
0/4...20 mA
Adjustment to the existing tap position transmitter must be carried out during
commissioning.
To select an analog position capture, proceed as follows:
1.
>
position
Configuration >
Continue >
Continue >
Tap
2.
Press
or
3.
Press
3550953/00 EN
107
Analog signal
Setting
0 % (= 0 mA)
20 % (= 4 mA)
always 20 %
To assign the minimum tap position to the analog value, proceed as follows:
1.
>
Configuration >
2.
Continue >
Tap
Press
Continue >
to highlight a digit.
3.
Press
to reduce it.
4.
Press
>
Configuration >
Continue >
Continue >
Tap
2.
Press
3.
Press
to reduce it.
108
3550953/00 EN
Setting
100 % (= 20 mA)
always 100 %
To assign the maximum tap position to the analog value, proceed as follows:
1.
>
Configuration >
2.
Continue >
Tap
Press
Continue >
to highlight a digit.
3.
Press
to reduce it.
4.
Press
>
Configuration >
Continue >
Continue >
Tap
2.
Press
3.
Press
to reduce it.
3550953/00 EN
109
The following options are available for setting the desired voltage level remotely:
Analog setting of desired voltage level remotely
>
Configuration >
Continue >
Continue >
Set desired
2.
Press
or
to activate setting the desired voltage level remotely
(On) or deactivate it by pressing (Off).
3.
Press
Current
Value
0 mA
4 mA
Table 26: Examples of configuration for the analog input (desired value transmitter
with injected current)
To set the analog value for the minimum desired value, proceed as follows:
110
3550953/00 EN
1.
>
Configuration >
2.
Continue >
Remote
Press
Continue >
to highlight a digit.
3.
Press
to reduce it.
4.
Press
To configure the analog input, the minimum desired value must be assigned
to the minimum analog value.
To set the minimum desired value, proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Remote
2.
Press
3.
Press
to reduce it.
Current
Value
20 mA
Table 27: Example of configuration for the analog input (desired value transmitter
with injected current)
To set the analog value for the maximum desired value, proceed as follows:
3550953/00 EN
111
1.
>
Configuration >
2.
Continue >
Remote
Press
Continue >
to highlight a digit.
3.
Press
to reduce it.
4.
Press
To configure the analog input, the maximum desired value must be assigned
to the maximum analog value.
To set the maximum desired value, proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Remote
2.
Press
3.
Press
to reduce it.
112
3550953/00 EN
You can recognize pulsed inputs from the preceding "P:". The note "Warning: P = pulsed inputs" is displayed on the screen.
You can assign one of the following functions to each of the digital inputs
(GPI 1...8):
Function
Off
Master/Follower
Description
No function selected
Define master/follower mode.
Signal on: Master mode active
Remote/Loc.
Blocking
Quick Tap
MPS triggered
Motor running
Desired value 2
Desired value 3
Remote VL
P: Master
P: Follower
ParGroup1
ParGroup2
Blk U raise
Blk U lower
P: Par. on
P: S. mode
P: Syn. auto.
P: Cir. curr.
P: DV 1
3550953/00 EN
113
P: DV 2
P: DV 3
If you assign the same functionality to two inputs, the device produces an
event message [ 131]. This also applies if you assign the same functionality via a static input and via a pulsed input.
Other examples of double assignment of functions are (n, m = 1...8):
>
Configuration >
Continue >
GPI
2.
Press
or
3.
Press
Functions can be assigned to all other GPIs as described above. You can
select the GPIs as follows:
GPI
Press
GPI1 X4:13
GPI2 X4:14
GPI3 X4:15
GPI4 X4:16
GPI5 X4:17
GPI6 X4:18
GPI7 X6:1
GPI8 X6:2
1x
2x
3x
4x
5x
6x
7x
Also refer to
2 Messages [ 131]
114
3550953/00 EN
Function
Off
Master
Follower
ParState
ParError
Local/Rem.
Undervoltage
Overvoltage
Undercurrent
Overcurrent
Desired value 1
Desired value 2
Desired value 3
MPS triggered
Motor runtime >
Motor running
Bandwidth <
Bandwidth >
GPI 1
GPI 2
GPI 3
GPI 4
GPI 5
GPI 6
GPI 7
GPI 8
Event
BCD +/-
BCD 1
BCD 2
BCD 4
BCD 8
Description
No function selected
Assign master
Assign follower
Assign parallel operation status
Assign parallel operation error
Message: Local control/remote
control
Message: Undervoltage blocking
Message: Overvoltage blocking
Message: Undercurrent blocking
Message: Overcurrent blocking
Message: Desired value 1
Message: Desired value 2
Message: Desired value 3
Message: Motor protective switch
was triggered
Message: Motor runtime exceeded
Message: Motor running"
Message: Value fallen below bandwidth
Message: Bandwidth exceeded
Message: GPI 1 active
Message: GPI 2 active
Message: GPI 3 active
Message: GPI 4 active
Message: GPI 5 active
Message: GPI 6 active
Message: GPI 7 active
Message: GPI 8 active
Message : Event active
Tap position in BCD code, prefix.
3550953/00 EN
115
BCD 10
BCD 20
BCD 40
Simplex mode
If the device cannot determine the tap position, ? is displayed in the tap position display. The relays of all outputs with BCD functionality (NC) are
switched off.
To assign a function to a digital output or to deactivate it, proceed as follows:
1.
>
Configuration >
Continue >
GPO.
2.
Press
or
3.
Press
Functions can be assigned to all other GPOs as described above. You can
select the GPOs as follows:
GPO
Press
GPO1 X4:9
GPO2 X4:12
GPO3 X5:9
GPO4 X5:12
GPO5 X5:18
GPO6 X5:21
GPO7 X5:24
8x
9x
10x
11x
12x
13x
14x
116
3550953/00 EN
Function description
Off
GPI x
GPO x
LED deactivated
There is a signal at control input GPI x (e.g. GPI 1)
The signaling relay at the GPO x (e.g. GPO 1) output
has activated
Undercurrent present
Parallel operation error present
Motor protective switch triggered
Regulation is blocked
Circulating reactive current parallel operation method is
activated
Device in parallel operation activated as master
Device in parallel operation activated as follower
Value is below bandwidth
Value is above bandwidth
Desired value 1 activated
Undercurrent
Par. error
MPS triggered
Blocking
Circ. reactive
current
Master
Follower
Bandwidth <
Bandwidth >
Desired value 1
Desired value 2
Desired value 3
Function monitoring
Remote
Local
Auto
Manual
Event
Assigning function
To assign a function to an LED, proceed as follows:
3550953/00 EN
117
1.
>
Continue >
parameter is displayed.
2.
Press
or
3.
Press
Characteristics
LED 1
LED 2
LED 3 yellow
LED 3 green
LED 4 rot
LED 4 yellow
Single-colored
Single-colored
Two-colored
Two-colored
Two-colored
Two-colored
Press
1x
2x
3x
4x
5x
Measured values
Calculated values
Parallel operation
Peak memory
Default parameter
Memory overview
Event overview
118
3550953/00 EN
1
2
3
Type designation
Software version
Serial number
4
5
Additional cards
RAM memory
>
Info.
Info.
Voltage U in V or kV
2
3
Current I in % or A
Phase angle from U to I in degrees
3550953/00 EN
Measurement performance
PMeas in % or MW
Frequency f in Hz
119
>
Measured values.
1
2
4
5
The values in the rows on the right are only displayed if the transformer data
has been entered previously.
To display the calculated values, proceed as follows:
>
Calculated values
LED no.
LED 1...LED 5
...
+
120
...
3550953/00 EN
LED 6...LED 9
Key
LED no.
All LEDs
This function will only test the functional reliability of the respective LED.
The function of the device linked to the LED is not tested.
>
2.
LED test.
To carry out the function test, press the function key for the LED you
want to test.
>
Digital outputs
The status of the relays is shown in the "MIO card digital outputs" display As
soon as a relay has activated, status 1 is displayed. If status 0 is displayed,
the relay has not activated.
Proceed as follows to display the status:
>
3550953/00 EN
121
>
Digital outputs
The statuses of the relays are shown in this display. As soon as a relay has
activated, status 1 is displayed. If status 0 is displayed, the relay hasn't activated.
To display the "PIO card digital outputs" screen, proceed as follows:
>
Analog input
Information relating to the analog input is shown in this display.
If Not yet calibrated! is displayed, you need to calibrate the analog input in
order to use it to capture the tap position or set the desired voltage level remotely.
To display information about the analog input, proceed as follows:
>
122
3550953/00 EN
>
Parallel operation.
1
2
3
4
5
Reactive current in %
Tap position
>
3550953/00 EN
123
1
2
3
4
>
Peak memory.
1.
>
Peak memory.
2.
Press
and
124
3550953/00 EN
1.
>
2.
Default parameter
Press
and
Parameter file
Flash file
Events
>
Memory overview
2.
Press
or
to select an entry.
A list with all events can be found in the Messages [ 131] section.
To view the event overview, proceed as follows:
>
Event overview.
3550953/00 EN
125
8 Fault elimination
8 Fault elimination
This chapter describes how to eliminate simple operating faults.
Cause
Remedy
LOCAL/REMOTE switch in
motor-drive unit switched to
LOCAL.
No connection
Check parameters.
with
or
keys.
Check parameters.
Blocking
Correct if necessary.
Check parameters.
Correct if necessary.
Check parameters.
Correct if necessary.
Check parameters.
Correct if necessary.
Determine the recommended bandwidth
Cause
Remedy
Compensation activated
Setting:
Check parameters.
Correct if necessary.
Z compensation
126
3550953/00 EN
8 Fault elimination
Cause
Keys
LEDs in keys
Remedy
Press
il-
Parameter error
and
not illuminated.
Display
No display.
LEDs
LED flashing
COM1
Cannot be connected to
PC using TAPCONtrol.
Cause
Remedy
Measured voltage
No measured value.
Measured voltage
Measured current
No measured value.
Tap-change operations.
3550953/00 EN
Check fuse.
Check measured voltage at plug terminal
X2:1/X2:2.
127
8 Fault elimination
Characteristics/detail
Cause
Remedy
Measured current
Correct parameterization.
V/I.
Cause
Remedy
Cause
Remedy
Incorrect wiring.
Check wiring.
128
3550953/00 EN
8 Fault elimination
Characteristics/detail
Cause
Remedy
Interference.
Display fluctuates.
No step display.
No measurement signal.
"-" is displayed.
No step display.
"?" is displayed.
Cause
Remedy
No signal
Cause
Remedy
No function
No power supply
Fuse tripped
3550953/00 EN
129
8 Fault elimination
Characteristics/detail
Cause
Remedy
Serial number
Name plate (Outer right side when viewed from the front [ 20])
Info screen (
>
Info)
130
3550953/00 EN
9 Messages
9 Messages
No.
Event (yellow/red)
Event message
Remark
Red
Undervoltage
Red
Overvoltage
Red
Overcurrent
Red
7
9
Yellow
Yellow
11
Red
12
Yellow
13
Yellow
14
Red
15
Yellow
16
Red
17
Yellow
18
Yellow
19
Red
3550953/00 EN
131
9 Messages
No.
Event (yellow/red)
Event message
Remark
20
Red
21
Red
22
Red
23
Red
24
Red
25
Red
26
Red
27
Red
28
Red
30
Red
31
Red
32
Red
33
Red
34
Red
35
Red
132
3550953/00 EN
9 Messages
No.
Event (yellow/red)
Event message
Remark
36
Yellow
37
Yellow
38
Yellow
3550953/00 EN
133
10 Disposal
10 Disposal
The device was produced in accordance with European Community Directive 2011/65/EC (RoHS) and must be disposed of accordingly. If the device
is not operated within the European Union, the national disposal requirements applicable in the country of use should be observed.
134
3550953/00 EN
11 Overview of parameters
11 Overview of parameters
This section contains an overview of the relevant menus and parameters.
Parameter
Setting range
NORMset
Normset activation
On/Off
Desired value 1
49...140 V
Primary voltage
0...9999 kV
Secondary voltage
57...123 V
Control parameters > Voltage regulation
Desired value 1
49...140 V
Desired value 2
49...140 V
Desired value 3
49...140 V
Desired value selection
Desired value 1; Desired value 2; Desired
value 3
Bandwidth
0.5...9%
Delay time T1
0...600 s
Control response T1
T1 linear/T1 integral
Activation T2
T2 on/T2 off
Delay time T2
1...10 s
Control parameters > Limit values
Undervoltage U< [%]
60...100%
Delay time U<
0...20 s
Undervolt. blocking U<
On/Off
U< below 30 V
On/Off
Overvoltage U> [%]
100...140%
Overvolt. blocking U>
On/Off
Overcurrent I> [%]
50...210%
Overcurr. blocking I>.
On/Off
Undercurrent I< [%]
0...210%
Undercurr. blocking I<
On/Off
Neg. active power block.
On/Off
Control parameters > Compensation
Compensation method
LDC/Z
Line drop compensation Ur
-25...25 V
Line drop compensation Ux
-25...25 V
Z compensation
0...15%
Z comp. limit value
0...15%
Configuration > Transformer data
Primary voltage
0...9999 kV
Secondary voltage
57...123 V
3550953/00 EN
Factory setting
Current setting
Off
100 V
0 kV
100 V
100.0 V
100.0 V
100.0%
Desired value 1
2.00%
40 s
T1 linear
T2 off
10.0 s
90%
10.0 s
On
Off
110%
Off
110%
On
0%
Off
Off
LDC
0.0 V
0.0 V
0.0%
0.0%
0 kV
100.0 V
135
11 Overview of parameters
Parameter
Setting range
Factory setting
Primary current
Current transformer connection
Transformer circuit
Display kV / V
Display %/A
Configuration > General
Language
Regulator ID
Baud rate
0...10000 A
Unknown; 1 A; 5 A
0a
Unknown
See [ 94]
kV/V
%/A
0 1PH
V
%
See [ 48]
9.6 kilobaud; 19.2 kilobaud; 38.4 kilobaud;
57.6 kilobaud
R/L pulse duration
0...10 s
Operations counter
0...99999999
Display dimming
On/Off
Key lock
On/Off
Function monitoring
On/Off
Delay function monitoring
0...120 min
Motor runtime
0...30 s
Manual/Automatic
Manual/Auto
Local/Remote
Local/Remote
Configuration > Parallel operation
Parallel operation activation
On/Off
Parallel operation method
Circulating reactive
current; Master; Follower; Auto synchronization
Parallel operation group
None; Group 1;
Group 2; Group 1 and
Group 2
CAN address
0...16
Simplex mode blocking.
On/Off
Circulating reactive current
0...100%
sensitivity
Circulating reactive current
0.5...40%
blocking
Master/follower current
Blocking/Off
blocking
Parallel error delay
1...999 s
Follower tapping direction
Standard/Swapped
Max. tap difference
1...4
Follower tapping without
On/Off
Umeas
136
Current setting
German
0000
57.6 kilobaud
1.5 s
0
On
On
Off
15 min
0.0 s
Manual
Local
On
Circulating reactive
current
None
0
On
0.0%
20.0%
Blocking
10 s
Standard
1
Off
3550953/00 EN
11 Overview of parameters
Parameter
Setting range
3550953/00 EN
Factory setting
Current setting
Off
Off
Off
Quick Tap
Desired value 2
Desired value 3
ParGroup1
ParGroup2
Off
Off
ParState
ParError
Undervoltage
Overvoltage
Overcurrent
GPI 1
GPI 2
Off
Off
Off
Off
Off
0.0%
100.0%
0
19
0
40
Off
Off
0.0 5
100.0%
137
11 Overview of parameters
Parameter
Setting range
Factory setting
0...140 V
0...140 V
80.0 V
140.0 V
Current setting
138
3550953/00 EN
12 Technical data
12 Technical data
12.1 Display elements
Display
LEDs
Power consumption
88...265 VAC
12.5 VA
3550953/00 EN
139
12 Technical data
140
3550953/00 EN
12 Technical data
-25C...+70C
-40C...+85C
IEC 61131-2
IEC 60255
VDE 0435
100 x ln/1 s
2 x In/ continuous
3550953/00 EN
141
12 Technical data
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-6-2
IEC 61000-6-4
Table 51: Electromagnetic compatibility
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-3
IEC 60068-2-30
142
3550953/00 EN
Glossary
Glossary
EMC
Electromagnetic compatibility
GPI
General Purpose Input
GPO
General Purpose Output
LDC
Line drop compensation
LED
LED (Light Emitting Diode)
MR
Abbreviation for "Maschinenfabrik Reinhausen
GmbH"
R/L
Raise/lower
3550953/00 EN
143
Electromagnetic compatibility 39
Analog value [%] Tap pos. max
108
Analog value [%] Tap pos. min
F
107
124, 135
Auxiliary supply
44 Factory setting
Fiber-optic cable
Information about laying
38
B
flush panel mounting
32
Bandwidth
73 Follower
Calculation
74
without measured voltage 105
102
Visual display
75 Follower tapping direction
Baud rate
60 Follower tapping without Umeas
105
Function monitoring
C
Delay time
64
Cable recommendation
38
Suppress message
64
Calculated values
120 Function test
CAN bus
98
Additional functions
51
Data
123
Circulating reactive current
Cap rail clip
34
blocking
55
Circulating reactive current
99
Circulating reactive current
Blocking
100
sensitivity
54
Master/Follower current blockControl functions
50
ing
103
Desired value 2
52
Sensitivity
100
Desired value 3
52
COM1 setting
60
Line drop compensation
53
Compensation
86
Overvoltage U>
52
Z compensation
89
Parallel operation
54
Connection
37
Tap synchronization
56
Contrast
47
Undervoltage U<
51
Control parameter
Z compensation
53
Desired value
72 Function tests
49
control parameters
70
LDC
53
Control response T1
76
Delay time T1
Delay time T2
Activating
Deactivating
Delivery
Desired value
Desired value
Device ID
Display contrast
Display dimming
144
22
22
118
118
K
Key lock
automatic
59
63
L
Language
48
LED selection
116
Limit value
Limit value monitoring
77
Overvoltage V>
80
Undervoltage U<
78
Line drop compensation
Inductive voltage drop
89
Ohmic voltage drop
88
Line drop compensation
86
Lowest tap position
107
lowest tap position blocking limit
84
M
Measured values
Memory overview
Motor runtime
Output relay
119
125
65
65
Indicator elements
Indicator elements
LED
Info
Information
GPI
112 Neg. active power flow
NORMset
75
76
77 H
108
77 Highest tap position
14 highest tap position blocking limit
85
69
80, 82
72 High-speed return
59
47
63
3550953/00 EN
84
68
20 Tap difference
follower
104
master
104
17
85
17 Tap pos. blocking mode
85
17 Tap position blocking mode
17 tap position blocking unit
highest
85
lowest
84
67
67 tap position capture
analog
107
67
Digital
106
62
102
82 Tapping direction
98
82 Throughput capacity
82 Transformer
Primary current
93
135
Transformer data
91
Current transformer connection
81
94
80
Primary voltage
92
Secondary voltage
93
P
Transformer circuit
94
Parallel operation
98
Activate
105
CAN bus
98 U
83
Circulating reactive current 99 Undercurrent I<
79
Deactivate
105 undervoltage
Undervoltage monitoring
Parallel operation error mesrelative
79
sage
104
parallel operation group
103
Parallel operation method
99
V
tap difference
104
V< also below 30 V
80
Parameter
79
Bandwidth
73 V< blocking
79
High-speed return
82 V< delay
Overcurrent blocking
82
Peak memory
123
W
Phase difference
94
33, 35
Primary voltage
69 Wall mounting
Wiring
45
Operating controls
Operating mode
Auto mode
Local mode
Manual mode
Remote mode
operation mode
Local
Manual
Remote
Operations counter
Overcurrent blocking
overcurrent I>
relative
Overview of parameters
Overvoltage U>
Relative
Overvoltage V>
R
Raise/Lower pulse duration
Regulator ID
Reset parameters
60
59 Z compensation
Activate
124
Limit value
89
90
91
S
Secondary voltage
Short-circuit capacity
Simplex mode blocking
69
98
104
3550953/00 EN
145
MR worldwide
Australia
Reinhausen Australia Pty. Ltd.
17/20-22 St Albans Road
Kingsgrove NSW 2208
Phone: +61 2 9502 2202
Fax: +61 2 9502 2224
E-Mail: sales@au.reinhausen.com
Brazil
MR do Brasil Indstria Mecnica Ltda.
Av. Elias Yazbek, 465
CEP: 06803-000
Embu - So Paulo
Phone: +55 11 4785 2150
Fax: +55 11 4785 2185
E-Mail: vendas@reinhausen.com.br
Canada
Reinhausen Canada Inc.
3755, rue Java, Suite 180
Brossard, Qubec J4Y 0E4
Phone: +1 514 370 5377
Fax: +1 450 659 3092
E-Mail: m.foata@ca.reinhausen.com
India
Easun-MR Tap Changers Ltd.
612, CTH Road
Tiruninravur, Chennai 602 024
Phone: +91 44 26300883
Fax: +91 44 26390881
E-Mail: easunmr@vsnl.com
Indonesia
Pt. Reinhausen Indonesia
German Center, Suite 6310,
Jl. Kapt. Subijanto Dj.
BSD City, Tangerang
Phone: +62 21 5315-3183
Fax: +62 21 5315-3184
E-Mail: c.haering@id.reinhausen.com
Iran
Iran Transfo After Sales Services Co.
Zanjan, Industrial Township No. 1 (Aliabad)
Corner of Morad Str.
Postal Code 4533144551
E-Mail: itass@iran-transfo.com
Italy
Reinhausen Italia S.r.l.
Via Alserio, 16
20159 Milano
Phone: +39 02 6943471
Fax: +39 02 69434766
E-Mail: sales@it.reinhausen.com
Japan
MR Japan Corporation
German Industry Park
1-18-2 Hakusan, Midori-ku
Yokohama 226-0006
Phone: +81 45 929 5728
Fax: +81 45 929 5741
Malaysia
Reinhausen Asia-Pacific Sdn. Bhd
Level 11 Chulan Tower
No. 3 Jalan Conlay
50450 Kuala Lumpur
Phone: +60 3 2142 6481
Fax: +60 3 2142 6422
E-Mail: mr_rap@my.reinhausen.com
P.R.C. (China)
MR China Ltd. (MRT)
360
4 E
200120
86 21 61634588
86 21 61634582
mr-sales@cn.reinhausen.com
mr-service@cn.reinhausen.com
Russian Federation
OOO MR
Naberezhnaya Akademika Tupoleva
15, Bld. 2 ("Tupolev Plaza")
105005 Moscow
Phone: +7 495 980 89 67
Fax: +7 495 980 89 67
E-Mail: mrr@reinhausen.ru
South Africa
Reinhausen South Africa (Pty) Ltd.
No. 15, Third Street, Booysens Reserve
Johannesburg
Phone: +27 11 8352077
Fax: +27 11 8353806
E-Mail: support@za.reinhausen.com
South Korea
Reinhausen Korea Ltd.
21st floor, Standard Chartered Bank Bldg.,
47, Chongro, Chongro-gu,
Seoul 110-702
Phone: +82 2 767 4909
Fax: +82 2 736 0049
E-Mail: you-mi.jang@kr.reinhausen.com
U.S.A.
Reinhausen Manufacturing Inc.
2549 North 9th Avenue
Humboldt, TN 38343
Phone: +1 731 784 7681
Fax: +1 731 784 7682
E-Mail: sales@reinhausen.com
United Arab Emirates
Reinhausen Middle East FZE
Dubai Airport Freezone, Building Phase 6
3rd floor, Office No. 6EB, 341 Dubai
Phone: +971 4 2368 451
Fax: +971 4 2368 225
Email: service@ae.reinhausen.com
Luxembourg
Reinhausen Luxembourg S.A.
72, Rue de Prs
L-7333 Steinsel
Phone: +352 27 3347 1
Fax: +352 27 3347 99
E-Mail: sales@lu.reinhausen.com
www.reinhausen.com