You are on page 1of 3

Converter CRS-50

Data Sheet - N00396

Signal converter RS-232/RS-485 and RS-485/RS-232

Page 1/3
November 2004

Characteristics

Signal converter RS-232 to RS-485 and RS-485 to RS232


Internal Power (AC/DC)
Indication for communication activity
Protection RS-485 up to 2kV
Galvanic isolation between RS-485 and power supply
Optical isolation between RS-232/RS-485
Automatic flux control
Reduced size
Mounting on top hat rails

Application
The converter CRS-50 is used to link an instrument net RS-485 to an
interface RS-232 of the PC.

Electrical test

Test voltage:
UAX = 2060Vca/Vcc = 1,5kV/1 min. 60Hz
between auxiliary power supply and others
Test voltage:
UAX = 85265Vca/90300Vcc = 2,5kV/1 min. 60Hz
Between auxiliary power supply and others

Construction and mounting


* The maximum length is 1200 meters and it is possible to use up to
31 devices at the network.
*In case of shielded cable, connect one side of it to ground.

Technical data
Communication
- Baud Rate:
- Flux control:

Power supply
Power consumption:

Influence magnitude

Environment temperature:
External magnetic
Interference
Radio frequency
Interference

Type
Housing

Case

Fastening
Electrical connection
Protection class
Weight

4.8 kbps 19.2 kbps


Automatic

85 265Vca e 90 300Vcc
2060Vca/Vcc
approx 1W.

25C 2K
0,5% for field intensity of
0,4 kA/m
0,5% between 27460MHz
at a distance 1m; power 1 W

Polyamide UL94 VO
Surface mounting using DIN rail
Terminals for pin shaped cable shoes.
IP 40 no housing
IP 20 at the connection terminals
0,1 kg

Climatic conditions

Operation temperature
Functioning temperature
Transport and storage temp.
Relative humidity

Mechanical test
Impact
Vibration

-20...+60C
-25...+70C
-40...+80C
75% of annual average with
light condensation
(others on consult)

acceleration 30g, during 11ms


acceleration 2g, frequency
5..150Hz

Converter CRS-50

Data Sheet - N00396

Signal converter RS-232/RS-485 and RS-485/RS-232

Electric connection

Page 2/3
November 2004

Additional Information

The following items contain tips and cautions to be observed


by the user for a good functional performance, as well as the
maintenance of the instrument and the safety of the
installations.

Cautions
Uax=Power supply
Connector DB9 connected to PC

Be sure that the voltage and current to be connected to the


instrument, are compatible.
Loosen all connections from the instrument before removing
it from the installation.

Mounting Instructions

Dimensional
Dimensions in mm

Observe the ambient temperature range. At the place of


installation, values for vibration, dust, dirt and humidity,
which must remain between the limits, established by the
protection class of the housing and the climatic group,
specified in this data sheet, have to be observed.

For mounting on DIN rail, use the snap-in device on the rear of the
instrument.
The connections can be made with pin for shaped cable shoes.

Instructions for Use

When connections have been made, switch on the power


supply and check at the output the functioning of the
transducer

Converter CRS-50

Data Sheet - N00396

Signal converter RS-232/RS-485 and RS-485/RS-232

Page 3/3
November 2004

Code structure
Catalog n
CONVERTER RS232/485 CRS-50

Power Supply
2060Vca/Vcc
85265Vca e 90300Vcc

12
13

Additional information
Normal
Complement

1
C

Example of specification
Converter RS232/RS485 CRS-50

Power supply : 85265Vca e 90300Vcc


Code N00396131

ABB Ltda - ATLV/IE Instrumentation Electrical


Avenue Autonomistas, 1496 - 06020-902 - Osasco - SP
Phone: (11) 3688-8320 / 8323 / 8347 - Fax: (11) 3688-8322
instrumentacao@br.abb.com