HALFEN CAST-IN CHANNELS

B 09 E

CONCRETE

W
NE

with design resistances


acc. DIN 1045-1 : 2008 - 08 incl.
HALFEN handrail connections
and Curtain wall systems

H A L F E N C A S T - IN CHANNE LS
Table of Contents

HALFEN cast-in channels HTA

1 HALFEN cast-in channels HTA and HZA


-

General
Application examples
Materials / Corrosion protection
Installation / Assembly
Product range Overview of channels & bolts
Available lengths and Anchor placement
Anchor configurations
Available types
Preliminary note on dimensioning / Example
Dimensioning:
- Load capacity HTA, HZA
- Dynamic loads
- Minimum spacing
- Shock resistance

2 HALFEN bolts HS, HSR and HZS


-

Product range
Bolt identification and lengths
Dimensioning

3 HALFEN handrail connection HGB


-

General
Application examples
Materials / Corrosion protection
Installation / Assembly
Product range
Principles of dimensioning
Dimensioning

4 HALFEN HTU channels for fastening of trapezoid metal plates


-

General / Materials
Installation / Assembly
Type selection, Identification
Dimensioning
Application examples

4
5
6- 7
8- 9
10 - 11
12 - 13
14
15
16 - 17
18 - 19
20 - 21
22
23 - 25
26
27
28 - 29
30
31 - 32
33
34
35
36
37
38
39
40 - 42
43
44
45
46
47
48

2009 HALFEN - B 09 - E - www.halfen.com

H A L F E N C A S T - IN CHANNE LS
Table of Contents

HALFEN cast-in channels HTA

5 For Roofs and walls


-

HALFEN timber fixing strap


HALFEN rafter shoe HSF
Brick tie anchors
Brick tie anchors, HALFEN anchor bolt systems
Firewall mounts
Restraint with turnbuckle SPV
Restraint tie HKZ
Restraint tie HKZ - GF/GU
Precast connection HVL
HALFEN corner guard HKW

6 Curtain wall HCW


-

General
Application examples
Selecting the HALFEN cast-in channel based on load
HALFEN high load channel HCW 52/34 for Curtain wall connections
HALFEN channel with ribbed steel anchors HTA-R and HZA-R
Brackets HCW-ED and HCW-EW for front mounting
Brackets HCW-B1 and HCW-B2 for top face mounting

7 Accessories/ Framing channels

49
50
51
52
53 - 54
55
56
57
58
59
60
61
62
63
64 - 65
66 - 67
68
69 - 71
72 - 73
74

Nuts, washers
Threaded rods, Hexagonal head bolts, Coupler sleeves, Ring nuts
Rail clips
Framing channels HM/HL/HZL overview of models
Framing channels HM/HL/HZL application examples

74
75
76
77
78

Index
Adresses / Contacts

79
80

Appendix

2009 HALFEN - B 09 - E - www.halfen.com

HALFEN cast-in channels HTA and HZA


The Benefits at a Glance
HTA / HZA channels

HALFEN cast-in channels save

considerable installation time. The result:


Faster completion of the construction project,

HTA HALFEN cast-in channels


COLD-FORMED

reduced cost

HALFEN bolts

part from excellent adjustability,

HGB channels

HTU channels

Safe and reliable


No damage to supporting
reinforcement
Approved for fire- resistant structural
elements
Can be installed in concrete pressure
and tensile- stress zones
Available in highly corrosion- resistant
steels
Suitable for dynamic loading
Building authority approval

Roof and Wall

Curtain Wall

Accessories

HZA HALFEN cast-in channels


COLD-FORMED, toothed

HTA HALFEN cast-in channels


HOT-ROLLED

Quick and economical


Adjustable anchoring
Bolts instead of welding
Extremely economical
for mountings in rows
Installation with basic tools,
saves money
Pre-engineered to reduce
construction time
Large selection for the
most varied requirements
Assembly with no health
hazard, no noise, no vibration

HZA HALFEN cast-in channels Dynagrip


HOT-ROLLED, toothed

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


General

Approvals
c ia

l ly

No
p.
Ap

.4
21
Z-

...

ed

ov
appr

2
HALFEN bolts

HTA
HZA 41/22
HZA Dynagrip

The channels are equipped with


hammerhead or toothed bolts with
associated nuts and washers, ready for
fixing any structural elements. The castin channel is to be set flush in concrete

HALFEN cast-in channels, consisting of


a C-profile with at least two anchors
on the back of the profile, hot-dip
galvanised or made from stainless
steel, have received building authority
approvals by the German Construction
Materials Supervisory Board (DIBt).

HTA / HZA channels

Z-21.4-...

- Approval No. Z-21.4-34


- Approval No. Z-21.4-145
- Approval No. Z-21.4-1691

3
resistance rating of F60 or F90 and the
conditions according to section 3.2.7
with appendices of the above-cited
approvals are met, the fire resistance
classification of the concrete
component remains unchanged.

4
HTU channels

HALFEN cast-in channels HTA and


HZA, in combination with HALFEN
bolts, have been certified for use in
fire-exposed structural elements. When
the anchoring channels are installed
in concrete components with a fire

HGB channels

Fire Protection

Reinforced Concrete Standard per DIN 1045-1:2001-07

5
Roof and Wall

Design rating per


DIN 1045-1:2001-07

The new DIN 1045-1 standard does


not change the required edge distance.

FRd = all. F x 1,4


FRd =

Material design resistance

perm. F =

allowable load acc. anchor


channel approval

6
Curtain Wall

Since January 2005, a design acc. DIN


1045-1:2001-07 has been mandated
for all structural elements of concrete, reinforced concrete or prestressed
concrete. The DIBt certification criteria
have been adjusted accordingly.
The design resistance FRd is calculated
as shown on the right.

Quality

Certification GmbH has verified that


our quality management system meets
the requirements of the DIN EN ISO
9001:2000 standard.

7
Accessories

Quality is the outstanding feature


of our products. HALFEN materials
and products are subjected to most
stringent quality control procedures. A
quality inspection by the German Lloyd

Cert.-No. QS-281 HH

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Application Examples: Mounting with HALFEN Anchor Channels

HTA / HZA channels

HALFEN bolts

Faade mounting Curtain wall

HGB channels

HTU channels

4
Faade mounting Curtain wall

Faade mounting Curtain wall

Roof and Wall

Before
Stadium seats: mounting in rows
After

Curtain Wall

Accessories

Fastening of escape routes

Utility pipes: Curved channels

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Application Examples: Fastening with HALFEN anchor channels with dynamic loading

HTA / HZA channels

HALFEN bolts

Tunnel construction: Fastening of catenary tension jacks

HGB channels

Mounting of technical equipment

HTU channels

4
Tunnel construction: Fastening of overhead lines

Roof and Wall

6
Curtain Wall

Adjustable machine bearing

Accessories

Elevator shaft: Fastening of guide rails

2009 HALFEN - B 09 - E - www.halfen.com

Fastening of an aerial cableway

H A L F E N C A S T- IN CHA NNE LS HTA AND H ZA


Materials / Corrosion Protection

HTA / HZA channels

Hot-dip galvanised FV:

Zinc galvanised GVs:

Dipped in a galvanizing bath at a temperature of


approx. 460C, a method used primarily for
open-profile channels.

Electrochemical process. HALFEN


bolts are available with special CrVI -free
coating.

HALFEN cast-in channels, steel, hot-dip galvanised


Steel

2
HALFEN bolts

Channel profile

Material
1.0038 ( S235JR )
1.0044 ( S275JR )
1.0976 ( S355MC )

Bolt anchor B6

Steel

Weld-on anchor

Steel

Standard
DIN EN 10 025-2
DIN EN 10 025-2
DIN EN 10 149-2
DIN EN 10263 or
DIN EN 10269
DIN EN 10 025-2

Zinc coat
FV: 50 m
FV: 50 m
FV: 50 m
FV: 50 m
FV: 50 m

HALFEN bolts, galvanised steel


Steel
Material

HGB channels

Bolt

Steel FK 4.6 or 8.8

DIN EN ISO 898-1 and


DIN EN ISO 4034

Hexagonal nut

Steel FK 5 or FK 8

DIN EN 20 898-2 and


DIN EN ISO 4034

Washer

Steel

DIN EN ISO 7089, 7093


or 7090

Stainless steel A4:

Chromium is the most important alloying element in


stainless steel. A specific chromium concentration
ensures the generation of a passive layer on the
surface of the steel that protects the base material
against corrosion. This explains the high corrosion
resistance of stainless steel.

HTU channels

Standard

Zinc coat
FV: 40 m
GVs: 12 m
FV: 40 m
GVs: 12 m
FV: 40 m
GVs: 12 m

Materials:
FV = Steel S235JR, hot-dip galvanised
A4 = Steel, stainless 1.4571/1.4404/1.4401
HCR = Steel, stainless 1.4547/1.4529
Steel acc. DIN EN 10 025-2 and HALFEN specification
Refer to building authority approval for stainless steels Z-30.3-6
Corrosion protection of mill finished anchor page 9

HALFEN cast-in channels, stainless steel

5
Roof and Wall

Stainless steel
Material
Channel profile
Bolt anchor B6

6
Curtain Wall

Weld-on anchor

1.4401, 1.4404 or 1.4571


1.4529 or 1.4547
1.4401, 1.4404, 1.4571
or 1.4578
1.4529 or 1.4547
1.4401, 1.4404 or 1.4571
Steel

Standard
DIN EN 10 088
DIN EN 10 088
DIN EN 10 088
DIN EN 10 025-2

Corrosion resistance class


III
IV
III
IV
III

HALFEN bolts, stainless steel


Stainless steel
Material

7
Accessories

Bolt

Hexagonal nut

DIN EN 3506-1 and


DIN EN 10 088

III

1.4529, HCR-50

DIN EN 3506-1

IV

1.4401, 1.4404 or 1.4571,


A4-50, A4-70
1.4401, 1.4404, 1.4571
or 1.4578
1.4529 or 1.4547

Corrosion resistance class

1.4401, 1.4404, 1.4571


or 1.4578, A4-50 or A4-70

1.4529, HCR-50
Washer

Standard

DIN EN 3506-2 and


DIN EN 10 088

DIN EN 10 088

III
IV
III
IV

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Materials / Corrosion Protection

Corrosion protection requirements per technical approval for HALFEN cast-in channels HTA and HZA

HTA / HZA channels

Component corrosion protection


Anchor

Bolt, nut, washer

mill finish

mill finish

no
corrosion protection

For use only if all components of the fixture are protected by a


minimum concrete cover as specified in DIN 1045-1:2001-07, Tab. 4,
depending on environmental conditions.

Hot-dip galvanised (zinc


plating 50 m)

Hot-dip galvanised (zinc


plating 50 m)

Galvanised
(Zinc plating 5 m)
Mechanically galvanised
(Zinc plating 10 m)

For interior use only, as in residential buildings, offices,


hotels, schools, hospitals, stores,
with the exception of wet rooms

Hot-dip galvanised
(Zinc plating 50 m)

Hot-dip galvanised
(Zinc plating 50 m)

Hot-dip galvanised
(Zinc plating 40 m)
Elec. Galv. Special coating
(Zinc plating 12 m)

Interior components as above, with higher corrosion


protection requirements according
DIN 1045-1:2001-07, Tab.3 XC1

HALFEN bolts

Areas of use
Channel

Stainless steel
1.4401/1.4404
or 1.4571

Stainless steel
A4-50
A4-70

Structures of corrosion resistance class III according


Z-30.3-6, e.g. wet rooms or outdoors

Stainless steel
1.4529 or 1.4547

Stainless steel
1.4529
HCR-50

Structures of corrosion resistance class IV according Z-30.3-6


highly exposed to corrosive action from chlorides and sulphur dioxide
(indoor swimming pools, ref. Tab. 10 of certification Z-30.3-6)

HALFEN channels with weld-on anchors mill finish


Corrosion protection of the mill finished weld-on anchor is
based on the following concrete cover c:

Channel
Concrete
cover
c [mm]

38/23-Q 52/34-Q

30

40

55/42

50

72/48
72/49

60

The minimum concrete cover depends on local conditions


and/or bid specifications

HGB channels

Stainless steel
1.4529 or 1.4547

HALFEN channels entirely of stainless steel (A4)


The HALFEN cast-in channels "entirely of stainless steel" are
not restricted to any concrete cover since no part of them can
corrode.
Range of applications:
Bridge and tunnel construction (e.g. fastening of pipelines)
Construction of sewage treatment plants (fastening of
spillover weirs
Chemical industry (mountings exposed to aggressive
substances)
Ventilated faades, e.g. masonry veneer
For all structural reinforced concrete elements requiring
larger concrete covers

The HALFEN cast-in channels consisting of a high corrosion


resistance (HCR) material are a must in cases of high
concentrations of chlorides, sulphur and nitrogen oxides.
Where used:

2009 HALFEN - B 09 - E - www.halfen.com

7
Accessories

Road tunnels
Maritime construction in saltwater
Indoor swimming pools
Areas not routinely cleaned
Poorly vented parking garages
As needed in narrow, heavily travelled city streets

Curtain Wall

HALFEN cast-in channels of stainless steel - HCR

4
HTU channels

Stainless steel
1.4401/1.4404
or 1.4571

Roof and Wall

mill finish

Glazed faades at the Paris Renaissance Hotel, fastened with HALFEN cast-in channels

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Installation

1.1

How delivered

1.2

Cut to size on site


Standard fixed lengths

HTA / HZA channels

HALFEN can supply short pieces and


standard lengths ready to be installed.

2 anchors!

HALFEN cast-in channels


can be cut to size at the
construction site

250 mm
25 mm

Non-standard fixed lengths also refer to

250 mm

250 mm

Site-mountable HALFEN end anchor

25 mm

HALFEN bolts

250 mm
25 mm

Installation, attached to formwork

MD

ANK-E
35 e 225

2.1

25 - 35 mm

p. 14

2.2

[mm]

Desired length ready to be installed

Installation on top face

Timb
Timbering

3
HGB channels

2.1.1 with nails

2.2.1

2.2.2

directly on reinforcement:
with tying wire

directly on reinforcement:
with HALFEN ChanClip
ChanClip

2.1.2 with staples

4
HTU channels

HALFEN
cast-in channel

HALFEN
cast-in channel

Steel formwork

2.1.3 aluminium pop rivets

5
Roof and Wall

2.2.3

fixing via auxiliary equipment:

2.1.4 HALFEN bolt and nut

Curtain Wall

2.1.4 Curved HALFEN cast-in channel in tubbing


segment

2.2.3

Mounting using an auxiliary equipment

Accessories

10

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Assembly

Removing the filler

-VF

HTA / HZA channels

-KF

Installing the HALFEN bolts

25 mm !

= Bolt HS,
without teeth

= Bolt HZS, HSR


toothed or nibbed

Dependable assembly with HALFEN cast-in channels

HALFEN bolts can be inserted anywhere in the channel


slot, then turned 90 and locked in place by tightening
the nut. Do not position bolts at the channel ends past
the last anchor (= 25 mm from the end of the channel).
On channels with bolt anchors, the anchor locations can
be seen through the channel slot.

HGB channels

HTA, HZA

4
HTU channels

4.1

Strip the channel interior only


in the sections which must be
accessed for use.

Combination strip filler: Pull strips by hand, assist with tool if


necessary, for instance a screwdriver.

HALFEN bolts

Haropor fu l l fo a m f i l l er: Use a suitable tool (such as a


carpenters hammer).

Test
Positional marking at the tip of the shank of the HALFEN
bolts: After the installation, verify the proper alignment of
the bolts via the marking slot at the tip of the shank. The
slot must be oriented at a right angle to the longitudinal
axis of the channel.

5
Roof and Wall

3.1

HZA profiles:
Adjustable
The toothing causes positive interlocking and ensures load
transfer in the lengthwise direction of the channel,
eliminating any risk of slippage.

2009 HALFEN - B 09 - E - www.halfen.com

Lock set
The bolt heads must sit flush on both flanks of the
anchoring channel and locked in place by tightening the
nut with the torque wrench. Observe the torque values
shown in the table on the bottom of page 31.

7
Accessories

Tinst [Nm]

Curtain Wall

3mm

11

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA

HTA / HZA channels

Load group FRd

Product Range: Overview of Channels + Bolts

37,8 kN 44,8 kN

30,8 kN

35,0 kN

C20/25

C20/25

C30/37

C30/37

HTA 72/49

14,0 kN

16,8 kN

diagonal load transverse load

HTA 54/33

HTA 49/30

152

177

90

72
54
6

HTU channels

Material:

30
7,5

Bolt:
HS 50/30

Weight:

Material:

9.73 [kg/m]

HTA 72/48

22

7,5

22

Bolt:
HS 72/48

3,25
33

49
33

49
5

10

HGB channels

Cold - formed

HALFEN bolts

HTA 55/42

Bolt:
HS 50/30

Weight:
5.43 [kg/m]
5.25 [kg/m]

HTA 52/34-Q

Material:

HTA 52/34

Weight:
3.43 [kg/m]
3.31 [kg/m]
3.06 [kg/m]

HTA 50/30

153

162

182

72
52

26

22

22

30

34

2,75

11,5

34

42
13

15,5

33

50
4

52

11,5

90

55

48

Hot - rolled

Curtain Wall

176

Roof and Wall

22

7
Accessories

Bolt:
HS 72/48
HSR 72/48
Material: Weight:
10.59 [kg/m]
10.46 [kg/m]

12

Bolt:
HS 50/30
Material: Weight:
8.48 [kg/m]

Bolt:
HS 50/30
HSR 50/30
Material: Weight:
6.48 [kg/m]
6.28 [kg/m]

Bolt:
HS 50/30
HSR 50/30
Material: Weight:
5.81 [kg/m]
5.65 [kg/m]

Material:

Weight:
3.76 [kg/m]
3.57 [kg/m]

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Product Range: Overview of Channels + Bolts

8,4 kN

all load directions

14,0 kN

diag.load transverse load

11,2 kN
all load directions

6,3 kN

7,0 kN
all load directions

HZA 41/ 22

HTA 40/25

11,2 kN

4,2 kN

4,9 kN

diag.load transverse load diag.load transverse load

HTA 38/17

HTA 28/15

1
HTA / HZA channels

16,8 kN



Bolt:
HS 40/22
Material:

HZA 38/23

Material:

HZA 29/20

Dynagrip

Weight:
2.13 [kg/m]
2.04 [kg/m]

47

15

17

12

Bolt:
HS 38/17

Bolt:
HZS 41/22

Weight:
2.36 [kg/m]
2.27 [kg/m]

HTA 40/22

18

18

 

2,5

28

Material: Weight:
1.99 [kg/m]
1.90 [kg/m]
1.88 [kg/m]

Bolt:
HS 28/15
Material: Weight:
1.22 [kg/m]
1.15 [kg/m]
1.01 [kg/m]

Product identification

Dynagrip

HGB channels

38



25


2,75

2,3

40

4
HTU channels



68

76

HALFEN bolts

HTA 38

Roof and Wall

/17

inside, channel back


on models with full foam
filler, also on channel side

2,5
14

20

23
6

18

Curtain Wall

29

2,5

23

5,5

80

40

38

18

74

96

HZA profiles, toothed

Bolt:
HS 40/22
HSR 40/22

Bolt:
HZS 38/23
Material:

Weight:
2.83 [kg/m]
2.71 [kg/m]

Material:

Weight:
2.45 [kg/m]
2.30 [kg/m]

2009 HALFEN - B 09 - E - www.halfen.com

Bolt:
HZS 29/20
Material: Weight:
1.79 [kg/m]

Accessories

suitable for dynamic loads


Material:
FV = steel S235JR, hot-dip galvanised
A4 = stainless steel 1.4571/1.4404/1.4401
HCR = stainless steel 1.4547/1.4529

13

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Available Lengths and Anchor Placement

HALFEN cast-in channels - available lengths


Number of
anchors

Anchor spacing

[mm]

[ea]

[mm]

100

50

150

100

200

150

250

200

250/3

100

300

250

300/3

125

350

150

25

400

175

25 175

175 25

550

250

250

250

800 L < 6070

4 - 25

250

HTA / HZA channels

Length

HTU channels

Illustration

Short sections

HALFEN bolts

HGB channels

Fixed
standard
lengths

Roof and Wall

5
6070

25 (31)

250 (200)

100

25

150

100

150

25

25

25

ca. 35

ca. 35

100 mm short section available only for HTA 28/15 and 38/17
for profiles 52/34 72/49 the channel projects by about 35 mm
HALFEN cast-in channels HTA 38/17K and HZA 29/20 have 31 anchors due to 200 mm anchor spacing

Fixed standard lengths

- produced on order

Fixed standard lengths

HTA 28/15, 38/17, 40/22, 40/25, 49/30,


50/30, 52/34, 52/34-Q, 54/33, 72/48
HZA 38/23, 41/22
Length [mm] / Number of anchors

- produced on order
HTA 38/17K

HZA 29/20

Length [mm] / Number of anchors


1250/ 7

1450/ 8

1650/ 9

1850/ 10

1050 / 5

1300 / 6

1550 / 7

1800/ 8

2050/ 11

2250/ 12

2450/ 13

2650/ 14
3450/ 18

2050 / 9

2300/ 10

2550/ 11

2800/ 12

2850/ 15

3030/ 16

3250/ 17

3050/ 13

3300/ 14

3550/ 15

3800/ 16

3650/ 19

3850/ 20

4050/ 21

4250/ 22

4050/ 17

4300/ 18

4550/ 19

4800/ 20

4450/ 23

4650/ 24

4850/ 25

5050/ 26

Accessories

Curtain Wall

Stock lengths

25

5050/ 21

5300/ 22

5550/ 23

5800/ 24

5250/ 27

5450/ 28

5650/ 29

5850/ 30

200

200

200

200

200

14

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA

B6 = bolt anchor with


hexagonal head

c ia

l ly

Z
No
p.
Ap

A = weld-on anchor -Q or -L,


grade S235JR, mill finish or
stainless steel A4
(for profiles 28/15 to 50/30)

1.4
-2

...

ov
appr

HTA / HZA channels

Anchors on HALFEN HTA and HZA channels configuration and dimensions

ed

Anchor Configuration

Anchor orientation
weld-on anchor:

HTA
72/49

HTA

HTA

HTA

55/42 52/34, 54/33*


A

B6

125/128 125/128 140


5

5,7

50/30, 49/30

B6

B6

HTA

HTA (- V )
40/22, 40/25, 38/17
B6

B6

HZA (- V )
41/22

28/15
A

B6

B6

119 125/128

60

62

51

33

62

32

62

51

33

62

11

10

50

50

40

40

18

12

10

12

Orientation

Q, *L

Q, L

Q, L

Q, L

Q, L

d2 or a [mm]

20

20

40

24

20

20

18

16

16

18

12

18

16

16

18

weld-on anchor A only for custom channels

reduced anchor length for thin structural elements, reduced strength not covered in certification

Type ANK-E end anchor for producing arbitrary lengths of HALFEN cast-in channels at the construction site

lly

Z
No
p.
Ap

1.4
-2

appr

34

ov

28/15 - FV
28/15 - A4
38/17 - FV
40/22 - FV
40/25 - FV
41/22 - FV
38/17 - A4
40/22 - A4
40/25 - A4
41/22 - A4

Installation Instructions for end anchor ANK - E

Thread

Tightening Torque
MD [Nm]

ANK - E1 - FV
ANK - E1 - A4

M 8
M 8

10
10

ANK - E2 - FV

M 10

20

5
ANK - E2 - A4

M 10

20

2 2
Anchors
Anker

A
Cut the HALFEN cast-in channel at the selected point. The
cut face must extend at a right angle to the longitudinal axis
of the channel. The end projection e must be not less than
35 mm and not more than 225 mm.
B
Select an ANK-E end anchor matching the HALFEN cast-in
channel profile per Table 1. Slide the clamping element all
the way over the back of the channel. If necessary, push in
the foam filler at the end of the channel.

End anchor

Roof and Wall

cia

for profile
HTA- / HZA-

6
35 e 225

Curtain Wall

ed

Clamping
element

ANK-E
bolt

Short HZA 41/22 sections


may be used with one end anchor
only. Not covered in the approval.

[mm]

ANK-E

35 e 225

7
Accessories

Table 1: End anchor selection

C
Turn the bolt applying the necessary torque per Table 1.
Desired fixed standard length

2009 HALFEN - B 09 - E - www.halfen.com

HGB channels

Length l [mm]
Dimension
d1 or t [mm]
Width b [mm]

HTA
72/48

HTU channels

HALFEN

cast-in channel
Anchor
configuration

HALFEN bolts

15

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Available Types

HTA / HZA channels

Curved HALFEN cast-in channels


Where used:
Tunnel construction
Reinforced-concrete pipes for utility shafts
Curved walls

L
Outside channel slot

Ordering Example:
HALFEN cast-in channel, curved
HTA 52/34-Q - A4, Ri = 4000 mm, L = 1050 mm
Ra

HALFEN bolts

i
Inside channel slot

HGB channels

Ri = radius of inside channel slot


Ra = radius of ouside channel slot
L = Length of bent profile

ess

Wall thickn

Curved HALFEN cast-in channels in tubbing segments

Smallest radius of curvature all materials


72/48,

72/49

52/34

54/33

50/30

49/30

40/22

40/25

HZA
41/22

HZA
29/20
38/23

38/17

28/15

Inside slot:
min. Ri

1,0 m

upon
request

0,8 m

4,0 m

0,8 m

0,8 m

0,7 m

1,0 m

1,5 m

1,5 m

0,5 m

0,5 m

Outside slot:
min. Ra

4,0 m

upon
request

4,0 m

8,0 m

4,0 m

8,0 m

2,0 m

3,0 m

4,0 m

on
request

1,5 m

1,0 m

HTU channels

HTA profile

For channel profiles 72/48 and 55/42 the minimum radiuses of curvature apply to carbon steel only (type WB, FV)

Curtain Wall

Paired HALFEN cast-in channels

HALFEN cast-in channel - Corner pieces

Material/Type:

Material/Type:

Channel:
FV = hot-dip galvanised
A4 = stainless steel

Channel and anchor:


A4 = stainless steel
l

Spacer:
Reinforcing steel BSt 500S
a

Roof and Wall

Standard model:
a/b = 125/250 mm
Other a & b leg dimensions
and different profiles
available on request

Figure: Corner piece HTA 38/17

Accessories

7
Ordering example:
Pair of HALFEN channels HTA 38/17,
l = 350 mm, a = 200 mm,
hot-dip galvanised, with filler

16

Where used:
Mounting HALFEN console anchors for supporting
masonry veneer
Other near-edge mounts

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Available Types

HALFEN anchor channels, hot-dip galvanised with stainless steel anchors


lly

Z
No
p.
Ap

1.4
-2

appr

34

ov

Anchor
chorr A4

When hot-dip galvanised channels with


stainless steel bolt anchors are used,
the prestressing wires may be in direct
contact with the stainless steel bolt
anchors.

FV profile

hot-dip galvanised

Available length: 6.07 m;


Available profiles: HTA 50/30,
49/30, 40/25, 38/17

Prestressing
strand

HALFEN bolts

2
Stainless steel A4

Example:
HTA - V 38/17 - FV (hot-dip galvanised)
hred. = 50 mm
Load capacity:
Short section: FRd = 5,6 kN
Running length: FRd = 3,3 kN

Hinweis:
Available profiles:
28/15 - V, 38/17 - V, 40/25 - V,
40/22 - V; 41/22 - V

17

50

38

HGB channels

HALFEN anchor channels HTA -V with reduced-length anchors

4
HTU channels

Hot-dip galvanised (FV) versions


available

18

Alternatively:
According to approval HTA type:
HTA 28/15
h = 47 mm
Load capacity:
Short section: FRd = 4,9 kN
Running length: FRd = 4,2 kN

Not covered in approval


Reduced load-bearing capacity
according to CC- method

5
Roof and Wall

2,3

15

47

28

12

Special HALFEN Solution for Corner Loads, Profile HTA 52/34


70

Where used: Faade mounting


Type: Stainless steel (A4)

200

0,0
0
0
2
0,2
4
0,4
6
0,6
8
0,8
,0
1,0

Additional reinforcement required

2009 HALFEN - B 09 - E - www.halfen.com

Curtain Wall

175
Wall thickness

200

45

Existing
corner
rebar

HTA / HZA channels

cia

ed

Component 1

Component 2

17

Accessories

Prestressing
strand

20

Required per
DIN 1045-1, Section 12.10
Between bonded tendons and zincgalvanised components [] a minimum
of 20 mm concrete must be provided,
otherwise there is a risk of hydrogeninduced stress corrosion cracking.
The solution:

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Preliminary note on Dimensioning

HTA / HZA channels

According to the new standards (e.g. EC2, DIN 1045-1,


EC3, DIN 18800-1) the normal loads (working loads) are
multiplied by the partial safety factor F and the normal load
capacity is divided by the partial safety factor M, yielding
the respective ratings identified by the index "d" (design).

The tables following this chapter show the design resistances


FRd.
The term "design value" represents the current standards
based on their new safety concepts and must be strictly
differentiated from the previous definition of "allowable
value".

Minimum breaking load FBr

Characteristic
load capacity FRk

3
HGB channels

Safety

Rating level
DIN 1045:1988-07
Load

act. F all. F

HTU channels

global

Loading capacity

HALFEN bolts

prev. F

(G+P)

Material
Safety

Design value
DIN 1045 -1:2008-08
(design level)

FEd FRd

Load
Safety

E = effect

R = resistance

charact.
effect
(Gk, Qk)

d = design

Fig. 1: Comparison of design calculation between DIN 1045: 1988-07 and DIN 1045-1: 2008-08

Roof and Wall

Curtain Wall

Following the adoption of DIN 1045 -1 : 2008-08, the recent


anchor channel approvals have also taken the new safety
concept into account.
As a result, the load capacity rating for channel and screw is
as follows:

To date, the verification process has not concurrently


become established in all industries. In the areas where the
"working load" is the basis, it is still the material on which the
admissible load per anchor channel certification is based. This
is the case for instance in machine and crane engineering,
which, inter alia, still go by global safety concepts. In these
cases the following conversion rule applies to the load
capacity values shown in the tables: (Exception: dynamic
loads page 22) :

FRd = allowable F 1.4

Accessories

7
FRd

Load capacity rating

all. F = FRd / 1.4

all.F = allowable load according to


anchor channel approvals

18

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Dimensioning Example

Dimensioning Example

HTA / HZA channels

1
Factors:
Working loads on the curtain wall connector
- actual dead load (gravity)
Fg = 6.00 kN
- actual wind load
Fw = 12.00 kN

2
HALFEN bolts

The calculation example is based on a design with partial safety


factors (on the load and material side).
On the load side, safety factors F are introduced.
F = 1.35 (acc. DIN 1045-1)
F = 1.50 (acc. DIN 1045-1)
Fgd = F Fg = 1.35 6.0 kN =
Fwd = F Fw = 1.5 12.0 kN =

3
8.1 kN
18.00 kN

HGB channels

For dead load:


For wind load:

- Design loads gravity


- Design loads wind loads

Design loads, bearing on the channel:

BVd

VyEd

BHd

= (Fgd 70 + Fwd 30) / 130


= (8.1 70 + 18.0 30) / 130 = 8.51 kN
= Fwd = 18.0 kN

HTU channels

NEd

= arctan (8.51 / 18.0) = 25.3 > 15 Zone 1, ref. p. 20

5
=
=

Roof and Wall

FEd

= 19.91 kN = 2 9.96 kN

HTA 50/30 - 350 - 3 anchors with 2 bolts spacing 150mm ( p. 20)

Curtain Wall

HALFEN CAST-IN CHANNEL SELECTED:


according to expert report:

required ar = 150 mm ( p. 23) = act. ar = 150 mm


FRd = 2 14.0 kN > FEd = 2 9.96 kN

7
Accessories

HALFEN BOLT SELECTED:


2 each HS 50/30 M12x60 8.8 ( p. 31)
FRd = 27.2 kN

> FEd = 9.96 kN

2009 HALFEN - B 09 - E - www.halfen.com

19

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Dimensioning

HTA Design resistance FRd


Dimensions in [mm]

Design resistance FRd


Running lengths
Single loads

Paired loads

HTA
profiles

b1

s 250

F F

FRd [kN]

FRd [kN]

L = 300

L= 250

L = 300

L = 350

p 100

p 100

p 100

p 125

p 150

FRd [kN]

FRd [kN]

FRd [kN]

FRd [kN]

FRd [kN]

FRd [kN]

FRd [kN]

37.8 (44.8)

18.9 (22.4)

37.8
(44.8)

37.8
(44.8)

18.9
(22.4)

18.9
(22.4)

37.8
(44.8)

52/34
54/33

30.8 (35.0)

15.4 (17.5)

30.8
(35.0)

30.8
(35.0)

15.4
(17.5)

15.4
(17.5)

30.8
(35.0) +

50/30
49/30

14.0

7.0

16.8

14.0

9.8

7.0

14.0

14.0

40/22
40/25

8.4

5.6

11.2

8.4

8.4

5.6

11.2

11.2

11.2

38/17

6.3

4.2

9.8

9.8

6.3

6.3

4.2

9.8

9.8

9.8

28/15

4.2

2.8

4.9

4.9

4.2

4.2

2.8

4.9

4.9

4.9

FRd under inclined load and centric load 150

Zone 1

lly
cia

ZNo
p.
Ap

.4
21

appr

34

ed

Concrete C20/25
Concrete C30/37

y
o

ov

150

NEd2 + VyEd2 < FRd

FEd =

(*) acc. expert report

to

Dimensions in [mm]

Design resistance FRd


Running lengths

Short sections
Paired loads

HTA
Profile

explained on next page

Single loads

b1

F F

L 200
F

bi 250

p 100

pi 100

FRd [kN]

FRd [kN]

72/48
72/49
55/42

37.8 (44.8)

18.9 (22.4)

52/34
54/33

30.8 (35.0)

15.4 (17.5)

FRd [kN]

FRd [kN]

FRd [kN]

37.8 (44.8)

18.9 (22.4)

30.8 (35.0)

15.4 (17.5)

50/30
49/30

16.8

9.8

16.8

9.8

40/22
40/25

14.0

8.4

14.0

8.4

38/17

11.2

6.3

11.2

11.2

6.3

28/15

4.9

4.2

4.9

4.9

4.2

FRd under inclined load and transverse load < 15

Concrete C20/25
Concrete C30/37

Zone 2

lly
cia

ZNo
p.
Ap

.4
21

appr

20

p1 b1 p2

b2

bi 250

Paired loads
L 150

L = 100

34

FEd =

NEd2 + VyEd2 < FRd

ed

HALFEN bolts
HGB channels
HTU channels
Roof and Wall
Curtain Wall
Accessories

s 250 bi 250 pi 100

bi 250

Single loads

Paired loads (*)

L=200 u.250

72/48
72/49
55/42

Paired loads
L > 250

L=150,200,250

p 1 b1 p 2

b2

FRd [kN]

Single loads
L=100

Short sections

HTA / HZA channels

ov

< 15

to

explained on next page

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Dimensioning

HZA DYNAGRIP Design resistance FRd


s = anchor spacing see page 14
Single loads
s

Concrete C20/25

b1

bi 250

FRd [kN]
pi = 50

pi = 150

38/23

16.8

9.4

12.0

29/20

11.2

6.3

9.0

lly

91
16

HZA DYNAGRIP profile

ov
appr

HZA Design resistance FRd


s = anchor spacing see page 14
Single loads

FRd with simultaneous loading in all directions

Concrete C20/25

Paired loads
s

b1

oZ
p. N
Ap

1.4
-2

5
14

HZA profile

bi 250

FRd [kN]
bi 250, pi 100

7.0

4.9

41/22

s = anchor spacing see page 14


Paired loads

FRd with transverse load


Paired loads

Concrete C20/25

p1

1.4
-2

5
14

p2
pi 50

Test criteria:
= arccos

VxEd
2

< 15

NEd + VxEd + VyEd

FRd [kN]

bi 450, pi 50

HZA profile

41/22

7,0

ed

ov
appr

Curtain Wall

< 15

lly

oZ
p. N
Ap

b1

bi 450

NEd2 + VxEd2 + VyEd2 < FRd


cia

ov
appr

Design resistance
i t
FRd

FEd =

pi 100

bi 250

FRd [kN]

lly

ed

cia

p1 b1 p2

b2

bi 250

NEd2 + VxEd2 + VyEd2 < FRd

FEd =

F F

Explanations to pages 20 - 21
Load capacity when concrete C30/37 - values in
brackets - admissible only when strain of the concrete in
the transverse direction relative to the longitudinal
channel axis is prevented by reinforcement (each one rod
BSt 500 S, ds 8 mm in the area around the HTA anchor)
or by cross pressure.
When anchored in concrete of strength class C12/15, the
admissible loads for C20/25 must be reduced by a factor

2009 HALFEN - B 09 - E - www.halfen.com

3
HGB channels

Design resistance FRd

Roof and Wall

.4 21

of 0,7; when in lightweight concrete with a closed structure


LC 25/28 (expanded clay, expanded shale or pumice), by
a factor of 0,67. Does not apply to HZA 41/22.
Profile 38/17 K with a shorter anchor spacing of 200 mm;
FRd design rating = 9,8 kN.
Intermediate values may be linearly interpolated.
Value applies to welded anchors only,
Ordering example HTA 52/34 - Q

21

7
Accessories

oZ
p. N
Ap

FRd [kN]

bi 250

ed

z
cia

F F

p1 b1 p2

bi 250

NEd2 + VxEd2 + VyEd2 < FRd

FEd =

F F

b2

HALFEN bolts

Paired loads

HTU channels

FRd with simultaneous loading in all directions

HTA / HZA channels

Design resistance FRd

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Dimensioning

HTA / HZA channels

HALFEN bolts

Dynamic loads for hot-rolled HALFEN cast-in channels

The load amplitudes shown below apply only to the anchor


channels of the respective material and anchor configurations
indicated.
Only the associated screws, shown in the table on the right,
may be used.
If load cycles are less than N = 2 10 6, the amplitude for the
HTA 40/22 and HTA 50/30 profiles can be looked up in the
bottom-right diagram.

Material:
Steel

55/42

HGB channels

Material:
A4

F
[kN]

Load amplitude for load cycles of N = 2 10 6


Material

Load amplitude
F = Fo - Fu [kN]
under tensile stress

29/20-B6, 29/20-Q

S275JR

2.0

29/20-B6, 29/20-Q

1.4401/1.4404/
1.4571

1.8

38/23-B6, 38/23-Q

S275JR

3.0

38/23-B6, 38/23-Q

1.4401/1.4404/
1.4571

2.4

Profile
anchor configuration

2.0

M16

2.4

M16. 20

7.0

M20

72/48-Q

7.0

M24, 27, 30

55/42-Q

8.0

52/34-Q

HTU channels

M24

8,0

Anchor configurations:
- B6 = with bolt anchor
- Q = with welded anchors, anchor position Q
(crosswise). Also refer to approvals Z-21.4-34 of 2
Aug.2004 and Z-21.4-1691 of 23 Nov.2005.

52/34

Available on request

29/20

38/23

3,0

50/30
40/22

2,4
2,0

38/23

1,8

29/20

Example:
HZA profile 38/23 -FV (standard, hot-dip galvanised),
channel length = 250 mm
max. load:
12 kN

16,8 kN

(adm. F =1,4

page 21
page 18

Including dynamic load:


3 kN (load amplitude F)

Fo = top load

Accessories

12,0 kN
9 kN

Fu = bottom load

Ordering example in case of dynamic loads:


HZA 38/23-FV-350
(automatically comes with B6 bolt anchors)
or:
HTA 52/34 - Q - FV - 550

Load Amplitude Chart


as a function of the number of load cycles N. Material as shown

Load amplitude kN

Roof and Wall

S235JR

F = F o - F u

Curtain Wall

M16

50/30-B6, 50/30-Q

M12

40/22-B6, 40/22-Q

7,0
72/48

Permissible
bolts

Load amplitude HTA 55/42-Q


Load amplitude HTA 72/48-Q
Load amplitude HTA 52/34-Q
Load amplitude HTA 38/23
Load
ampli
tude
HTA
50/3
0
Load
ampli
tude H
TA
40/22

1 load cycle

Load amplitude HTA 29/20


Number of load cycles N

22

Number of load cycles N

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA

Single channels

ae

Paired channels

af

ar1

a1

ae

...

ov
appr

HTA / HZA channels

The minimum spacing specified in the table applies to reinforced normal weight concrete of all strength classes
C20/25. If increasing the spacing by 30% there will be no requirements to the reinforcement.

1.4
-2

Minimum member
dimensions

ar1

b
h
d

ar
aa

paired channels

ar

ar
250

aa
500

ae
225

af
450

ar1

ae
225

a1

HTA 72/48, 72/49

500

175 + c

HTA 55/42

250

500

225

450

225

500

185 + c

HTA 52/34, 54/33

200

400

175

350

175

400

160 + c

HTA 50/30, 49/30

150

300

130 (100)

250

225

150

130 (100)

300

90 + c

HTA 40/22, 40/25

100

200

80 (70)

200

140

125

80 (70)

200

80 + c

HTA 38/17

75

150

50

100

100

100

50

150

70 (80) + c

HTA 28/15

50

100

40

80

50

100

40

100

50 (75) + c

HZA 41/22

100

150

80

200

100

100

80

200

85 + c

HZA 29/20 DYNAGRIP

100

200

80

200

140

125

80

200

80 + c

HZA 38/23 DYNAGRIP

150

300

130

250

225

150

130

300

96 + c

The parenthesized dimensions apply if act. ar 2 x adm. a r.


Minimum component width b = 2 x a r applies in single channel conf.
Determined by channel height, length of anchor and necessary
concrete cover c per DIN 1045 -1.
Parenthesized anchor lengths for HTA 38/17 and 28/15 apply only to
non-standard profiles with weld-on anchors.
Admissible only for centric tensile stress, and for HZA 41/22 also if
exposed to stress in the longitudinal direction of the channel.

In cases of transverse and inclined tensile load the distance from the
edge of the unstressed component may be reduced to ar red.= 0,5 x a r or
50 mm if, analogous to the figure on see page 24, an anchor
reinforcement is provided.
In cases of inclined tensile load 45 and transverse tensile stress per
pendicular to the edge spacings of 75 to 100 mm an anchor
reinforcement is required see page 24.

HALFEN bolts

Z
No
p.
Ap

M i n i m u m s p a c i n g a r, a e , a a , a f a n d h

All dimensions in [mm]

l ly

3
HGB channels

c ia

4
HTU channels

ed

Dimensioning

Re d u c e d e d g e d i s t a n c e a r i n c a s e s o f r e d u c e d l o a d c a p a c i t y F R d f o r s h o r t H TA e l e m e n t s
x

FRd [kN] inclined and centric tensile load


4,9
5,6
7,0
8,4
9,8 11,2 12,6

14,0

ar
< 15

z
15,4

ae

Roof and Wall

150

Zone 2
x

16,8

18,2

aa
ar

z
19,6

HTA 72/48, 72/49, 55/42

21,0

24,5

28,0

30,8

35,0

37,8

175

185

190

200

230

250

HTA 52/34, 54/33

75

100

110

125

140

150

155

165

175

185

190

200

HTA 50/30, 49/30

75

100

110

125

140

150

HTA 40/22, 40/25

50

55

60

65

75

100

50

55

60

65

75

Reduced edge distance a r in mm


Required interaxial spacing aa = 2 ar

HTA 38/17
HTA 28/15

50

Zone 2

FRd [kN] transverse and inclined tensile load


4,9
5,6
7,0
8,4
9,8 11,2 12,6

14,0

15,4

16,8

18,2

19,6

21,0

24,5

28,0

30,8

35,0

37,8

165

175

190

200

230

250

HTA 72/48, 72/49, 55/42

HTA 52/34, 54/33

75

90

100

125

150

155

160

165

175

190

200

HTA 50/30, 49/30

75

90

100

125

150

HTA 40/22, 40/25

50

55

60

65

70

75

90

100

50

55

60

65

70

75

Reduced edge distance a r in mm


Required interaxial spacing aa = 2 ar

HTA 38/17
HTA 28/15

50

2009 HALFEN - B 09 - E - www.halfen.com

23

6
Curtain Wall

Zone 1

Zone 1

7
Accessories

These data do not take into account the effect of the


various anchoring depths hv. For an exact calculation of
the necessary minimum spacings, refer to the
publication by Prof. Eligehausen in 1997 Concrete
Calendar, part 2, p. 609 &f.

HTA / HZA channels


HALFEN bolts

HTU channels

l ly

1.4
-2

...

ov
appr

Reduced edge distance a r under pure centric tensile stress


Fig. 1

Dimensions
in mm

NEd
50

HALFEN
cast-in
channel

ar

N Ed

50

U-shaped
reinforcement bar
Smallest
admissible
diameter of
mandrel acc.
DIN 1045-1

ar

N Ed

NEd

ae

50

a r 50 mm

40

20

20

20

20
30

HGB channels

c ia

Z
No
p.
Ap

Dimensioning

ed

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA

d br
ds

In cases where HTA 28/15 to 50/30,


HZA 41/22, 29/20 and 38/23
HALFEN channels are installed for instance on the front face of thin faade
panels and for structural considerations
minimum spacing cannot be

Roof and Wall

adm. As=

Rd = (1,4 S) = 11,2 kN/cm

with S = 8 kN/cm per approval.


Approval No. Z-21.4-34 (HTA),
Z-21.4-145 (HZA), Z-21.4-1691
(HZA DYNAGRIP) for this application.

FRd [kN]
FRd
=
cm
4 x Rd [kN/cm] 44.8

Required U-bar dimensions


Profiles

Steel stress

Required reinforcement cross section AS


[cm] of the leg of a U-bar:

maintained, the edge distance ar may


be reduced to 50mm, provided the
anchoring loads and splitting tensile
forces are taken up by an anchor
reinforcement, as shown in Fig.1.

U-bar dimensions [mm]


L

ds

dbr

HTA 28/15, 38/17,


40/22, 40/25
HZA 29/20, 41/22

250

24

HTA 49/30, 50/30


HZA 38/23

250

32

Additional reinforcement for HZA 41/22 when the edge distance 75 and < 100mm

Fig. 2: Arrangement of anchor reinforcement

Curtain Wall

U-bar As
FEd
75 mm
100 mm

FEd

7
Accessories

As

FEd

HZA 41/22

FEd

HZA 41/22

Cross section A - A

adm. As =
FRd [kN]

Rd [kN/cm]

24

FRd
cm,
11.2

Rd
see above.

Additional reinforcement when the


edge distance of the HZA 41/22
HALFEN cast-in channels is

75 mm ar < 100 mm and the load


vector is perpendicular to the edge
(Fig. 2).

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Dimensioning

Reduced edge distance a e with reduced load capacity F Rd


below that per table page 23, provided two stirrups (Fig.3)
are installed directly above and below the short HTA element.

When using HALFEN cast-in channels HTA 28/15, 38/17,


40/22 and 40/25 for installation in slim reinforced concrete
columns, it is permissible for the end distance ae to remain

Dimensioning FRd and load spacings 'p' for HALFEN cast-in channels in slim columns

FEd
Load spacing p [mm]

FEd

FEd

FEd

FEd

FEd

FEd

FEd

FEd

max

100

150

200

250

300

min

100

100

100

125

150

4.5

3.5

3.1 (4.3

4.2

3.2

2.8 (4.2

4.6
4.2

4.6
4.2

7.0

7.6

Profile

HALFEN bolts

HTA

FEd

3
HGB channels

Stress zone

Support width [mm] and channel length [mm]

FRd [kN]

HTA 38/17
HTA 40/22
HTA 40/25

5.7

4.7

5.0 (6.3

4.5

3.4

3.1 (4.6

4.5

4.5

5.7

4.9

5.3 (6.7

7.4

4.5

3.4

3.1 (4.5

4.5

8.1
4.5

2
2
+ Vy Ed < FRd
F Ed = N Ed

Zone 1

Concrete C30/37

150

Centric
and diagonal
tensile stress

< 15

Zone 2

HTU channels

HTA 28/15

HTA / HZA channels

Transverse
and inclined
tensile stress

5
Roof and Wall

Values apply to short elements with 3 anchors.


Stress zones 1 and 2:

Values are based on the new design method for anchor channels
CEN/TC250 draft of the Comit Europen de Normalisation

6
Fig. 3: Placement of the back-up reinforcement (dimensions in mm)
Curtain Wall

ae

y
Additional clip 6

FEd

7
Accessories

z
Additional clip 6

FEd

2009 HALFEN - B 09 - E - www.halfen.com

25

HA LF E N C A S T - IN CHA NNE LS HTA AND H ZA


Dimensioning

HTA / HZA channels

Shock resistance with partial safety factor = 1,0


The following conditions must be met:
Minimum component dimensions, axial spacing and edge
distance per official approval ( page 23) must be observed.
For practical applications (normal operating and working
loads, static loads) the load values specified in the DIBt
certifications apply. Accordingly, static load components in
the longitudinal channel axis of HTA profiles are not
admissible. Instead, HZA channels must be selected.

When used for instance in shelter construction, HALFEN


cast-in channels provide added protection for the
shock-resistant mounting of built-in components.

HALFEN bolts

2
Shock resistance Strength per bolt linear, diagonal and transverse tensile stress

HALFEN cast-in channel

Transverse
Querzug
stress

Diag.stress
Schrgzug

HGB channels

z
Shock resistance under linear,
diagonal and transverse stress for
HALFEN bolts type Typ HS and HZS

HTA

HZA (toothed)

Strength class 4.6


for HALFEN bolts type HS
(hammerhead & hooked bolts)

Strength class 8.8


for HALFEN bolts
type HZS

HALFEN bolt

M8

M10

M12

M16

M20

M12

M16

FRd,shock [kN]

5,6

13

24

40

20
(13)

30
(20)

15

25

60

120

80 (80)

120 (80)

Tensioning torque [Nm]

Values in brackets for stainless


steel A4-50, A4-70

Shock resistance Strength in longitudinal channel direction


HALFEN cast-in channel

HTU channels

Load in longitudinal
profile direction

Shock resistance per bolt connection in


longitudinal channel direction

Roof and Wall

5
Increased equivalent resistance FRd,E
per bolt connection in longitudinal
channel direction

Curtain Wall
Accessories

HTA 38/17

HTA 40/22

Hammerhead HS

HTA 50/30, HTA 52/34

HZA 41/22
HZA 38/23
HZA 29/20

Hooked head HS

HZS

HALFEN bolt

M8

M10 M10 M12 M16 M10 M12 M16 M10 M12 M16 M20 M12

M16

FRd,shock [kN]
at RK
0,63 / 6,3

2,5

20
(13)

30
(20)

FRd,E [kN]
at RK
1,0 / 10

12

12

12

12

12

12

15

20
(13)

30
(20)

FRd,E [kN]
at RK
1,6 / 16

12

20
(13)

30
(20)

Values in brackets - see above

0.63/6.3

0.63

Acceleration
amax. [m/s2]
6.3

1.0/10

1.0

10.0

16

2.5

1.6/16

1.6

16.0

25

4.0

Standard shock classification RK

HTA 28/15

Velocity
vmax. [m/s]

Excursion
smax. [cm]
10

Acceleration build-up
rmax. [g/ms]
1.6

Shock resistance Channel longitudinal and transverse resistance to linear, diagonal and transverse tensile stress

Shock resistance of the HALFEN


cast-in channels per 250 mm anchor
region,profile longitudinal and transverse resistance to linear, diagonal
and transverse tensile stress

HALFEN cast-in channel

FRd,shock [kN]

HTA 28/15 HTA 38/17 HTA 40/22 HTA 50/30

17

20

40

HTA 52/34 HZA 41/22


HZA 38/23
HTA 54/33 HZA 29/20

55

20

30

In case of a difference in the load-bearing capacity between the bolt and the HALFEN cast-in channel, use the smaller value.
applies to profile 50/30 HTA anchoring version with weld-on I-anchors.
For short elements, L = 100 - 250mm, and paired load combinations, assume three times the design resistance values specified in the
DIBt certifications (ref. tables page 20,21)

26

2009 HALFEN - B 09 - E - www.halfen.com

HALFEN bolts
The Advantages at a Glance

lly

Z
No
p.
Ap

1.4
-2

appr

Model HS

34

HTA / HZA channels

cia

ov

2
HALFEN bolts

Smooth HALFEN bolts


for all type HTA profiles
Load bearing in 2 directions
Identified at shank tip by
1 marking notch

3
HGB channels

Model HS

ed

alfen bolts with a patented,


S-shaped head for even
more reliable attachment:
The new shape of the head
ensures enhanced protection
against screw slippage in the
channel

Model HSR

c ia

Z
No
p.
Ap

Model HZS

Teeth

2009 HALFEN - B 09 - E - www.halfen.com

...

ov
appr

Toothed HALFEN bolts


Toothing ensures positive load
bearing even in the longitudinal
direction. Any risk of slippage is
eliminated.
Identified at shank tip by
2 marking notches

7
Accessories

Model HZS

1.4
-2

Roof and Wall

l ly

Curtain Wall

Nip

ed

Model HSR

For hot-rolled profiles only:


HTA 40/22, 50/30, 52/34, 72/48
For regular steel only: WB and FV
Load bearing in all directions
Load bearing in longitudinal
channel direction per expert report
Identified at shank tip by
2 marking notches

HTU channels

HALFEN bolt with nib

27

HA LF E N BOL TS
Product Range

HALFEN bolts
Fits
profile

HTA
72/48, 72/49

HTA
72/48

HTA
55/42

HTA
55/42, 52/34, 54/33, 50/30, 49/30

HTA
52/34, 50/30

HTA
40/22, 40/25

Bolt

HS 72/48

HSR 72/48

HS 50/30

HS 50/30

HSR 50/30

HS 40/22

58

58

,5

32

41

Bolt
size

41

41
l

HTA / HZA channels

HALFEN bolts

2
l [mm]
15

M 20

M 24

M 27

M 30

M20

M 24

M10

M 12

M 16

M 20

M16

M20

20

M 10

M 12

M 16

GVs4.6 GVs4.6

25
A4-50
A4-50
FV4.6
GVs4.6 GVs4.6 GVs4.6

30

3
HGB channels

35

A4-50
A4-50
FV4.6
GVs4.6 GVs4.6 GVs4.6
GVs4.6

A4-50
A4-50
FV4.6
FV4.6
GVs4.6 GVs4.6 GVs4.6
GVs8.8

40

GVs8.8
A4-50

A4-50

A4-50

HTU channels

FV4.6

GVs8.8

HCR-50
A4-50

A4-50
A4-50L
FV4.6
FV4.6
GVs4.6 GVs4.6 GVs4.6

A4-50
FV8.8
GVs4.6 GVs4.6
GVs8.8 GVs8.8 GVs8.8
GVs4.6

60

Roof and Wall

65
70
72
FV4.6
75

FV4.6
FV8.8

FV4.6

FV4.6

FV4.6

80

6
Curtain Wall

87
A4-50
FV4.6

FV4.6
FV8.8

FV4.6

GVs8.8 GVs8.8
125

7
Accessories

150

GVs8.8 GVs8.8

GVs4.6 GVs4.6 GVs4.6


GVs8.8 GVs8.8

GVs8.8
HCR-50
A4-50
A4-50L
GVs4.6 GVs4.6
GVs8.8 GVs8.8 GVs8.8
A4-70T A4-70T

FV4.6

A4-50

A4-50
GVs4.6

FV8.8

GVs8.8

100

A4-50

A4-50
FV4.6
GVs4.6

55

GVs8.8
A4-50

FV4.6
GVs4.6 GVs4.6 GVs4.6

FV8.8

A4-50

GVs4.6
GVs4.6 GVs8.8 GVs4.6

50
FV4.6

A4-50

FV8.8
A4-50
GVs4.6
GVs8.8

45

A4-50

FV4.6

FV4.6
GVs8.8

FV4.6

FV4.6

FV4.6

FV4.6

A4-50
GVs4.6

A4-50
A4-50
A4-50L A4-50L
GVs4.6 GVs4.6 GVs4.6
GVs8.8 GVs8.8

A4-50T A4-50
FV4.6
FV4.6
GVs4.6 GVs4.6
GVs8.8 GVs8.8
A4-50
GVs4.6 GVs4.6 GVs4.6

A4-50

A4-50
FV4.6
GVs4.6 GVs4.6 GVs4.6
GVs8.8

A4-50
A4-50
FV4.6
GVs4.6 GVs4.6 GVs4.6
GVs8.8

A4-50

GVs4.6 GVs4.6
A4-50

GVs4.6 GVs4.6

175
200
250
300

FV4.6

L = left-hand thread; T = partial thread

28

A4-50
GVs4.6 GVs4.6
GVs4.6
GVs4.6

GVs4.6 GVs4.6 GVs4.6


GVs4.6 GVs4.6

Notes

next page

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N BOL TS
Product Range

HTA 38/17, 38/17-K


HZA 38/23

HSR 40/22

HS 38/17

,5

32

HTA 28/15
HZA 29/20
HS 28/15

29

20

HZA
29/20

HZA
38/23

HZA
29/20

HZA
38/23

HZA
41/22

Fits
profile

HZS 29/20

HZS 38/23

HS 29/20

HS 38/23

HZS 41/22

Bolt

29

29

Bolt
size

21

5
34,

1
HTA / HZA channels

HTA
40/22

2
M 12

M 16

M6

M8

M 10

M12

GVs4.6 GVs4.6 GVs4.6


A4-70
GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6
A4-70 A4-50
A4-70
GVs4.6 GVs4.6 GVs4.6
HCR-50
A4-70 A4-70 A4-50
A4-70 A4-70
FV4.6 FV4.6 FV4.6
FV4.6
GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6

M 12

M12

M16

M12

M16

M12

20
25
30
GVs8.8

GVs8.8 GVs8.8

GVs4.6

GVs4.6
A4-50

A4-70

GVs8.8

l [mm]

15

A4-50
FV8.8
HCR-50
A4-70
A4-70 A4-50
FV4.6
FV8.8
GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6

M16

HALFEN bolts

M 10

35

HGB channels

M16

40
GVs8.8

GVs8.8 GVs8.8

GVs4.6

GVs4.6
45

HCR-50
A4-70 A4-50
A4-70
A4-50L A4-50L
A4-50L
FV4.6
FV4.6 FV4.6
GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6

A4-70

A4-50
FV8.8
GVs8.8 GVs8.8

GVs4.6

50

GVs4.6

HTU channels

GVs8.8

A4-50
FV8.8

55
HCR-50
A4-70 A4-50
A4-70
FV8.8
GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6 GVs4.6
GVs8.8 GVs8.8
GVs8.8
A4-70

60
GVs4.6

GVs8.8

GVs4.6

GVs8.8 GVs8.8

65
70
72

FV8.8
A4-70T

Roof and Wall

GVs8.8

A4-70
FV8.8

75
A4-70
A4-50L

A4-70
A4-50
A4-50L
GVs4.6 GVs4.6 GVs4.6

A4-70

A4-70

A4-50
80

GVs4.6 GVs4.6 GVs4.6

GVs4.6
GVs8.8

GVs4.6

GVs8.8 GVs8.8

A4-50
FV4.6

A4-50

GVs4.6 GVs4.6 GVs4.6

GVs4.6 GVs4.6
A4-50
GVs4.6

GVs4.6 GVs4.6
A4-50

FV8.8

A4-50

A4-50

GVs4.6 GVs4.6 GVs4.6

GVs4.6 GVs4.6

GVs8.8

GVs8.8 GVs8.8

GVs8.8

GVs8.8 GVs8.8

GVs8.8

GVs4.6

GVs4.6

GVs4.6

GVs4.6

GVs4.6

GVs4.6

100

125

150

GVs8.8 GVs8.8

Accessories

A4-50

Curtain Wall

87

175
A4-50 A4-50
GVs4.6 GVs4.6

L = left-hand thread; T = partial thread

2009 HALFEN - B 09 - E - www.halfen.com

A4-50
GVs4.6

GVs8.8
GVs8.8
GVs8.8

200

GVs8.8

250
300

GVs8.8

Notes

next page

29

HA LF E N BOL TS
Bolt Identification and Lengths

Identifying the HALFEN bolts

HTA / HZA channels

Nomenclature on bolt head

Manufacturer

H4.6
4.6

(for individual dimensions)


strength grade or material grade

HALFEN
H
4.6
4.6

2
HALFEN bolts

H 4.6
4.6

Strength grade 4.6


galvanised or hotdip galvanised

HALFEN

H 4.6
A4-50

Material grade A4 - 50
stainless steel

marking notches at shank tip:


HS all types
HZS 41/22

3
HGB channels

H 4.6

HALFEN

HALFEN
H
4.6
8.8

HSR all types


HZS 38/23
HZS 29/20

H 8.8
4.6

Strength grade 8.8


galvanised or hot-dip
galvanised

HALFEN

H 4.6
A4-70

Material grade A4 - 70
stainless steel

Official approvals

Z - 21.4 - 34: HALFEN cast-in channels HTA and associated HALFEN bolts HS
Z - 21.4 - 145: HALFEN cast-in channels HZA 41/22 and associated HALFEN bolts HZS
Z - 21.4 - 1691: HALFEN cast-in channels HZA DYNAGRIP and associated HALFEN bolts HZS

Halfen
Langenfeld

Halfen
Langenfeld

Halfen
Langenfeld

HTA, HS

HZA, HZS

HZA, HZS DYNAGRIP

HTU channels

4
Determining the bolt length l erf for HALFEN bolts
lerf

s
i tx

l erf = t fix + i + s + vmin

vMIN

5
Roof and Wall

HALFEN
bolt

l erf
t fix
i
s
vmin
m

Curtain Wall

Dimensions Vmin
Bolt diameter

vmin = m + [mm]

M6

11,0

M8

12,5

M10

14,5

M12

17,0

M16

20,5

M20

26,0

M24

29,0

M27

31,5

M30

33,5

= required bolt length


= clamping thickness of
attached part
= height of profile lip
= washer thickness page 74
=m+
= height of nut EN ISO 4034
= projection approx. 5 (7 as from M20) mm

Dimensions, profile lip i


Channel profile

28/15

29/20

38/17

38/23

40/22

40/25

41/22

49/30

50/30

52/34

54/33

55/42

72/48

72/49

i [mm]

2,3

5,0

3,0

5,5

6,0

6,0

7,2

7,5

8,0

11,5

7,5

12,9

15,5

10,0

Accessories

7
Notes re pages 28-29
M10, M12 matching profile 38/23
Can only be used when no load
component acts on channel in its
longitudinal direction.

30

M6, M8, M10 matching profile


29/20. Can only be used when no
load component acts on channel in
its longitudinal direction.

Can only be used when no load


component acts on channel in its
longitudinal direction.
Length ending

2009 HALFEN - B 09 - E - www.halfen.com

c ia

l ly

Z
No
p.
Ap

Dimensioning

1.4
-2

...

ed

HA LF E N BOL TS

ov
appr

Load capacity design ratings F Rd and M Rd


Bolt type HS - Design ratings FRd and MRd
Grade 8.8

Bending moment
per bolt

Thread

FRd [kN]

Stainless steel A4-50. HCR-50

Bending moment
per bolt

M6

3.1

MRd [Nm]
2.8

FRd [kN]

MRd [Nm]

M8

5.6

7.0

M10

9.0

14.0

18.6

M12

13.0

24.5

27.2

M16

24.2

62.2

50.5

M20

37.8

121.1

M24

54.3

M27

70.7

M30

86.4

Stainless steel A4-70

Bending moment
per bolt

FRd [kN]

MRd [Nm]

Bending moment per bolt

FRd [kN]

MRd [Nm]

5.6

6.2

7.7

13.2

34.9

9.0

12.2

12.2

26.2

61.2

13.0

21.4

17.6

45.9

155.4

24.2

54.3

33.0

79.0

37.8

106.0

116.6

209.6

113.7

54.3

183.3

310.7

148.4

419.9

HALFEN bolts

Grade 4.6

HTA / HZA channels

Changing bending stress:


For facade veneers subjected to variable flexural stress conditions (e.g.
due to temperature change), the
alternating stress amplitude must
not exceed a value of A = 50 N/
mm2 ( =1,0) by the mean value M,
relative to the stressed cross section
of the bolt.

Stainless steel A4-50, HCR-50


Bending moment
per Bolt

Bolt Type

FRd [kN]

29/20 - M12

27.2

38/23 - M12

27.2

61.2

38/23 - M16

50.5

155.4

41/22 - M12

27.2

61.2

13.0

21.4

41/22 - M16

50.5

155.4

24.2

54.3

MRd [Nm]
61.2

FRd [kN]

MRd [Nm]

33.0 *

116.6 *

FRd

* Material stainless steel A4-70


MRd = 42 Nm.
For profile HTA 38/17 with a channel
length L > 250 mm the bending moment of
the bolt must be reduced to MRd = 101 Nm
Bending moment relative to the upper edge
of the profile or concrete. In case of flexure
and additional centric or diagonal tensile
stress the strain values must be added up:

= Load capacity design rating of the


bolt
MRd = Design rating of the absorbable
bending moment
NEd = Design rating of the existing tensile
load component
MEd = Design rating of the existing
bending moment

NEd FRd (1 - MEd / MRd)

Tightening Torque for HALFEN bolts


Tightening Torque [Nm]
Bolt type
Material / Grade

HS
4.6

HS
8.8

HS A4-50
HS A4-70
HS HCR-50

M6

M8

M10

15

M12

HSR
8.8

HZS 41/22
8.8

HZS 41/22
A4-50

HZS 38/23
8.8

HZS 38/23
A4-70

HZS 29/20
8.8

48

15

25

70

25

50

50

80

80

M16

60

200

60

200

120

80

120

120

M20

120

400

120

400

M24

200

680

200

M27

300

1000

M30

400

2009 HALFEN - B 09 - E - www.halfen.com

7
Accessories

Thread

Curtain Wall

Observe load-bearing capacity of the


profile! In case of a difference in the loadbearing capacity between the bolt and the
HALFEN cast-in channel, use the smaller
value
For profile HTA 28/15 with a channel
Length L > 250 mm the bending moment of the bolt must be reduced to

Roof and Wall

Bending moment
per Bolt

HTU channels

Bolt Type HZS - Design ratings FRd and MRd


Grade 8.8

HGB channels

Available thread sizes for the various profiles page 28-29

31

HA LF E N BOL TS
Dimensioning

HALFEN bolts

Design load-carrying capacity F Rd [kN]


Bolt type HSR

galvanised
2.7 3.9 4.2 3.1 5.6 5.7 8.0 3.1 5.6 9.0 13.0 5.6 9.0 13.0 13.0 13.0 24.2 30.8
(GV)
Stainless
steel
A4

2.7 3.9 4.2 3.1 5.6 5.7 8.0

Grade 8.8
FRd in longitudinal
channel direction

72/48 - M20

72/48 - M16

72/48 - M12

50/30 - M16

50/30 - M12

50/30 - M10

50/30 - M8

40/22 - M12

40/22 - M10

40/22 - M8

40/22 - M6

38/17 - M12

38/17 - M10

38/17 - M8

38/17 - M6

28/15 - M10

28/15 - M8

Channel nut GWP


28/15 - M6

HTA / HZA channels

5.6 9.0 13.0 5.6 9.0 13.0 13.0 13.0 24.2 30.8

according to expert report


Bolt HSR

[kN]

40/22 - M16

7.0

50/30 - M16

7.0

50/30 - M20

10.5

72/48 - M20

10.5

Rec. max.Design load-carrying capacity per HALFEN bolt HS in the longitudinal channel direction [kN]

3
HGB channels

for steel profiles

for stainless steel profiles

Bolt type HS with strength class


4.6

8.8

M6

0.14

0.56

A4-50

A4-70

M8

0.28

0.98

0.28

M 10

0.42

1.54

0.42

M 12

0.70

2.24

0.70

M 16

1.26

4.20

1.26

HTU channels

Thread

M 20

1.96

6.58

1.96

M 24

2.80

9.52

2.80

M 27

3.64

12.46

M 30

4.48

15.26

Direct attachment
Surface-flush
installation

Spaced attachment
Non-flush installation
Shim
see Note

Distance

Roof and Wall

For supporting structures exposed


to stress in the longitudinal channel
direction, use hot-rolled HALFEN
cast-in channels in conjunction with
toothed HALFEN bolts type HSR, or
toothed HALFEN cast-in channels HZA
in conjunction with toothed HALFEN
bolts type HZS.
In cases of load support involving friction, the maximum design ratings are
shown in the table on the left (tigthening torque see page 31)

Curtain Wall

Square washer

Accessories

Note (non-flush installation)


If the front edge of the channel is set
back from the concrete surface, the
attached structure must be shimmed
using the washer VUS, provided for
spaced attachment ( page 74 ).

32

For spaced attachment always install a


square washer

In the case of transverse stress, add


the bolt flexure to the tensile force.
see footnote page 31

Example:
HALFEN cast-in channel: HTA 49/30
HALFEN bolt:
HS 50/30 - M16
Washer:
VUS 49/30 - M16
Bending moment MRd : page 31

2009 HALFEN - B 09 - E - www.halfen.com

Handrail Connections HGB


The Advantages at a glance

HTA / HZA channels

HALFEN handrail connections HGB

2
HALFEN bolts

Prole HGB E- 54/33 - A4

3
HALFEN handrail connections HGB
Prole HGB E- 49/30 - A4

HTU channels

Safe and dependable

HALFEN handrail connections HGB


Prole HGB E-40/25-A4

statically verified mounting


no damage to the concrete on the
visible front faces of the slab
while construction is in progress, it
can also serve to secure safety rails
(note DIN EN 795 Fall protection)
The associated high-strength HALFEN
bolts ensure secure and statically
solid attachment of the banister
structure

Roof and Wall

adjustable anchoring
can be used even on thin front
faces of d 100 mm
bolts instead of welds or dowels
pre-engineered to reduce
construction time
permits later adjustment and even
simple replacement of all attached
structures

HGB channels

Fast and cost-effective

6
Curtain Wall

onstruction specialists
consider the HALFEN
handrail connections type HGB
to be particularly well suited for
fastening banisters on the front
faces of thin deck and balcony
slabs.

HALFEN handrail connections HGB


Prole HGB E-38/17-A4

Accessories

2009 HALFEN - B 09 - E - www.halfen.com

33

HA LF E N H A N DRA IL CO NNE CTIO NS H GB


General

HTA / HZA channels

HALFEN bolts

HGB channels

Regulatory requirements
Balconies are a part of the structural
system. "They must be designed,
constructed, modified and maintained
in such fashion that public safety or
order and especially life, health or the
natural fundamentals of life are not
jeopardized". (MBO 07 and implementation directives)

A regulatory requirement as part


of regional building codes refers to
structural stability: "Every structure as a
whole and in its individual components
must be stably self-supporting". This
stability must be statically verifiable on
the basis of technical standards (here
DIN 1055 Part 3+4).

In this context, the technical rules


established by public announcement
as regulatory building codes must be
observed.
Technical rules specify load parameters, the calculation, dimensioning of
structural products, construction types,
structural layouts etc..

Another regulatory requirement


addresses traffic safety, for example:
Balconies and loggias must have
fall-preventing safety banisters when
they border on an area that lies more
than 1 meter below. Up to a drop
height of 12m the minimum banister
height is 0.90m from the top surface

of the finished floor or accessible


ledge. For drop heights greater than
12m (except as per German LBOs)
the banister must be 1.10m heigh.
Other regulations, not covered here,
address the design, dimensioning,
banister spacing, fire protection,
thermal/sound insulation, and
rainwater drainage.

Regulations, standards and directives to be observed when constructing banisters:

HTU channels

4
Regional Building Codes

VOB Part B,
4, execution:

4.2 (1) The contractor is required to perform the installation, at his own responsibility, in accordance with the contract. He has to abide by the accepted standards
of the art as well as the provisions of the law and regulatory directives. VOB Part
B, 4.3, requires the contractor to report to the customer, in writing, any obvious design flaws, which he, as the expert, must be able to recognize. He alone is
responsible for any resulting defect and consequential expenses. If he has satisfied
his reporting obligation, the responsibility for the defect (such as a frontal banister
attachment into too thin a concrete slab) passes to the customer.

BVM Directive

Directive on metal banisters / balustrades, version 10/08, publisher: BVM

Other applicable regulations and Standards


(excerpted):

Accident Prevention Regulation General Provisions (VGB 1)


Industrial Safety Regulations
ETB Directive Fall Prevention Components, version 06/85
Stainless Steels, certification No. Z-30.3-6, of December 5th, 2003
DIN 1045-1: Support structures of concrete, reinforced concrete and prestressed
concrete; design and construction
DIN 1055-3: Action on support structures - part 3; intrinsic load and
superimposed loads for above-ground structures
DIN 1055-4: Action on support structures - part 4; wind loads
DIN 18800-1: Steel structures; design and construction
DIN 18800-7: Steel structures; verification of weldability

Roof and Wall

Curtain Wall

Accessories

The individual federal states have established different building codes and regulations. In all cases the technical regulations require verification of structural safety and
functional fitness. The dimensioning of the banister mount must be backed up by a
static calculation or a regulatory certification.

34

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N H A N DRA IL CO NNE CTIO NS H GB


Application Examples

Mounting of grandstand banister, O2 World Berlin (under construction)

Copyright Anschutz-Entertainment-Group

HTA / HZA channels

HALFEN bolts

HGB channels

HTU channels

4
HALFEN handrail connections combine cost-effectiveness with aesthetic appearance

Roof and Wall

Curtain Wall

Accessories

Fall protection during the construction phase

2009 HALFEN - B 09 - E - www.halfen.com

Finished, HGB cast-in channel, residential construction

35

HA LF E N H A N DRA IL CO NNE CTIO NS H GB

Stainless Steel A4:

HTA / HZA channels

Materials / Corrosion Protection

Chromium is the most important alloying element in


stainless steel. A specific chromium concentration
ensures the generation of a passive layer on the
surface of the steel that protects the base material
against corrosion. This explains the high corrosion
resistance of stainless steel.

Anchor channels of stainless steel may be employed


outdoors even in an industrial environment and near the
ocean but may not be exposed to saltwater".
refer to BVM directive Metal banisters and balustrades.

2
HALFEN bolts

HALFEN cast-in channels, stainless steel

Materials

HGB channels

Standard

Corrosion resistance class per


Z-30.3-6
III

Channel profile

1.4401, 1.4404 or 1.4571

DIN EN 10 088

Ribbed-head
anchor

Reinforcing steel BSt 500S

DIN 488

HALFEN bolts, stainless steel

Stainless steel

Designation
Materials

HTU channels

5
Roof and Wall

Stainless steel

Designation

Standard

Corrosion resistance class per


Z-30.3-6

Bolt

1.4401, 1.4404, 1.4571


or 1.4578, A4-70

DIN EN 3506-1 and


DIN EN 10 088

III

Hexagonal nut

1.4401, 1.4404 or 1.4571,


A4-70

DIN EN 3506-2 and


DIN EN 10 088

III

Washer

1.4401, 1.4404, 1.4571


or 1.4578

DIN EN 10 088

III

A4 = Stainless steel 1.4571/1.4404/1.4401

Galvanised material for closed, dry rooms, for instance when


Galvanised:
Dipped in a galvanizing bath at a temperature of
approx. 460C, a method used primarily for openprofile channels.

mounting staircase banisters in residential buildings, schools or


retail stores.

Available on request

6
Curtain Wall

Identifying the HALFEN HGB cast-in channels

Accessories

7
Product identification
on the anchor
additionally inside the profile

36

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N H A N DRA IL CO NNE CTIO NS H GB


Installation / Assembly

1
HTA / HZA channels

Nail the HALFEN cast-in channel to the formwork


Where possible, use stainless
steel nails to avoid
extraneous corrosion.

2
HALFEN bolts

After the formwork is


removed, extract the foam
filler from the HALFEN castin channels.

3
Nail the HALFEN cast-in channel to the formwork

HGB channels

Installation and adjustment of the balusters

HTU channels

5
Roof and Wall

Remember to
also order the
washers

Turn HGB-M banister bolts


90 (up to the stop in the
HALFEN cast-in channel).

Banister bolts

Torque
[Nm]

HGB - M 50/30

M 16

60

for profiles 49/30

M 12

25

HGB - M 40/22

M 16

60

for profiles 40/25

M 12

25

HGB - M 38/17

M 16

60

for profiles 38/17

M 12

25

Curtain Wall

Stainless steel
Material grade A4-70

Tighten the nut - done

and 54/33

2009 HALFEN - B 09 - E - www.halfen.com

7
Accessories

Use torque wrench for


tightening the nuts.
Apply torque as shown in
the table on the right.

37

HA LF E N H A N DRA IL CO NNE CTIO NS H GB


Product Range

HALFEN HGB cast-in channels and bolts


Nomenclature

HTA / HZA channels

Dimensions HGB-E [mm]

hA
Weight
kg / ea

HALFEN bolts

HGB E - 54/33-A4

150

3
HGB channels

hA

HGB E - 40/25-A4

HGB E - 38/17-A4

14

200

1.348

100

0.589
12

110

0.743

200

0.897

100

0.213
10

90

0.320

200

0.427

100

0.176

150
200

l1 / l2

dA

hA

Type / FK

Size

14

250

2.363

HGB M-50/30
A4-70

M12x40

170/170

HGB M-50/30
A4-70

M12x40

HGB M-40/22
A4-70

M12x40

HGB M-38/17
A4-70

M12x40

1.105

1.591

150

Weight
kg / ea

200

150

dA

100

HGB E - 49/30-A4

HTU channels

HALFEN HGB bolts

dA

10

90

0.265

170/170

170/170

170/170

14

14

12

150

90

90

1.457

1.031

0.817

M16x50

M16x50

M16x40

M16x40

0.353

Ordering example HGB channel:

Ordering example banister bolt:

HGB-E-49/30 - 200 - A4

HGB-M-50/30 - M12x40 - A4 - 70

5
Roof and Wall

Dimensions HGB-EE [mm]

Material
Length [mm]
Nomenclature

Materials:
A4 = Stainless steel
1.4571/1.4404/1.4401
FV = Steel S235JR, hot-dip
galvanised (for interiors)

Material
Thread- x Length
Nomenclature

Available on request

Bolt placement:

Corner piece

l2

30

Accessories

45

03

25

Curtain Wall

Short element

100

Dimensions [mm]:
l1 = 170, l2 = 170, = 90
25

38

25

Available on request

45

100

25

l1

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N H A N DRA IL CO NNE CTIO NS H GB


Dimensioning Fundamentals

Rail height hb

The minimum height hb of a banister is 0.90 m from the top edge of


the finished floor or accessible ledge to the upper edge of the banister/
balustrade. In the case of drop heights of more than 12.0 m (except as
specified in the applicable regional building code (LBO)), the banister
must be 1.10 m high.

HTA / HZA channels

Banister height

2
HALFEN bolts

It would be desirable to have one uniform minimum height of 1.00m as


has already been mandated in the commercial sector and in some other
European countries..

Balcony slab

HTU channels

Clearances

5
clear distance between bottom edge of hand rail
and top edge of facing / lower structure
clear distance between the top edge of the
finished floor and the bottom edge of the facing /
lower structure
distance between posts (inter-axis)
clear distance between horizontal facings
clear distance between vertical facings

Dimensions

+M

-M

DF

Accessories

o
Fc

N
d

The forces bearing on the banister must be conducted into the


structural base. It will be necessary to verify that the forces
a) are absorbed by the banister itself and
b) can be transferred by the mounting elements into the
deck slab.

Fc
DF

2009 HALFEN - B 09 - E - www.halfen.com

6
Curtain Wall

The structural design of the banister must take all fundamental requirements
into account. As a general rule, all banisters must be built in a way that a
person cannot fall through them, for instance between rods, lattice bars or
solid infill.
They should also be designed so as not to entice but instead to discourage
anyone from climbing over them.
The specific requirements for a banister are determined by the intended use
(private, public, commercial) and the drop height involved.
Also to be observed are the building codes of the individual federal states,
the ETB Directive Fall Protection Components and DIN 18065 (Stairs in
Buildings definition,rules, key measurements).

HGB channels

b = clear distance between back of the veneer and


the front face of the balcony slab or gutter /
kick plate

Roof and Wall

The thickness of the balcony slab must be at least h = (120) mm


when the HGB is mounted on the front face. Other mounting types
and systems require a thicker slab.
All concrete-embedded mounts installed outdoors (e.g. on balconies)
must consist of stainless steel.

An attachment with anchor channels or dowel systems requires


concrete at least of grade C 20/25. If the concrete is of less than a
grade C 20/25 or it is unknown, a case-by-case decision must be
made.

39

HA LF E N H A N DRA IL CO NNE CTIO NS H GB


Dimensioning

Banister heights

HTA / HZA channels

HALFEN bolts

Drop height

Minimum height of banister

Less than 12 m

100 cm

Greater than 12 m

110 cm

Relevant local building regulations LBO and if necessary other provisions e.g., ZTV-ING for civil constructions
should be observed.

Load assumptions
1. Rail load H according to DIN 1055-3, Table 7
The actual horizontal loads per table 7 are to be assessed at full height in the drop height and at 50% in the
opposite direction (but not less than 0.5 kN/m).

HGB channels

HTU channels

Notes

2. Vertical loads V according to BVM directive


For mounting, the following assumptions as per the BVM
directive: 1998 for metal banisters / balustrades
are made.

3. Wind loads FW according to DIN 1055-4


7.1 (3) Wind and actual horizontal loads need not be
added together.
Except balcony parapets and pergolas, which serve as
escape routes. As per ETB Directive Fall Prevention
Components, wind and horizontal loads are to be added
together.

Residential buildings and common


rooms with little traffic

h= 0,5 kN/m

General

h= 1,0 kN/m

Areas with considerable gatherings,


factories, workshops

h= 2,0 kN/m

Dead weight of structure including


lining

V1 = 0,40 KN/m

From window planter

V2 = 0,35 KN/m

From support capacity

V3 = 0,15 KN/m

Velocity pressure q in kN/m2


and total wind power FW
are calculated as per DIN 1055-4
(not applicable to interior banisters).

Roof and Wall

5
Size determination
H
FW

DF
F oc
F uc
d

Balusters

V, M, H, Fw

-M

+M

Fc

20

N=
N

10

F = N2 + V2

20

30

max. M
+ H or Fw
d

H or Fw

hp

Accessories

10

Pressure area under connecting plate


Compressive force above
Compressive force below
inner lever arm, hp/2 - 10 mm,
depends on the size of the connecting plate
= Loads and stress factors per pillar

DF
30

Curtain Wall

Connecting plate

=
=
=
=

u
Fc

DF

40

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N H A N DRA IL CO NNE CTIO NS H GB


Dimensioning

Calculation example:
Impact per pillar:
1.625 m
1.00 m
9.0 m < 25.0 m
0.5 kN/m (residential building)

Wind effect:
Structure height 9.0 m < 25.0 m not susceptible to vibrations
q = 0.65 kN/m Wind zone 2, inland, h 10 m
Load bearing area:
A = 1.241.625 = 2.02 m 2.0 m

Wind load*):

Fw,Ed = 1.74 1.5 = 2.61 kN

Rail load*):

HEd = 0.5 1.625 1.5 = 1.22 kN

Vertical load:
VEd = 0.15 1.625 1.5 = 0.4 kN
+ 0.40 1.625 1.35 = 0.9 kN
+ 0.35 1.625 1.35
= 0.8 kN

2
from support load
from dead load
from window planter

Size determination:

HGB channels

NEd =

M Ed
1,75
+ Fw, Ed =
+ 2 ,61 = 37,61 kN
0,05
d

VEd = 0.4 + 0.9 + 0.8 = 2.1 kN


2

Wind effect:
Fw = cpe q A = -1.34 0.65 2.0 = -1.74 kN

FEd = N Ed + VEd =

Example:

MEd = 2.610.56+(0.4+0.9) 0.10+0.8(0.10+0.10)


= 1.75 kNm

External pressure coefficient:


h/d = 0.75
cpe,1
= - 1.4
cpe,10 = - 1.2
cpe = c pe,1 +( cpe,10 - cpe,1)lg A = -1.4+(-1.2+1.4)lg2 = -1.34

37,61 + 2,1 = 37,67 kN = 2 18,8 kN

Selected:
3

VEd = 0,4 kN

HALFEN cast-in channel: HGB-E-54/33-200, Mounting type B

Fw,Ed = 2,61

with MRd = 2.44 kNm > MEd = 1.75 kNm


FRd = 2 22.8 kN > FEd = 218.8 kN
VRd = 11.2 kN > VEd = 2.1 kN

at
hp =120 mm

Banister bolt: HGB-M-50/30, M16x50


with FRd = 33.0 kN

> FEd = 18.8 kN

VEd = 0,9 kN

100

80
160
80

50 30
50
30

NEd

7
Accessories

560

OKFF

HALFEN cast-in channel HGB-E

hp=120

Curtain Wall

*) the higher value of wind and rail load is the determining


factor.

VEd = 0,8 kN
100

page 42

100

1240

MRd, FRd, VRd

FEd

5
Roof and Wall

1000

HEd = 1,22 kN *)

4
HTU channels

Pillar spacing:
Pillar height over OKFF:
Structure heigth:
Railload:

HALFEN bolts

Size determination:

HTA / HZA channels

Banister bolt HGB-M

2009 HALFEN - B 09 - E - www.halfen.com

VEd

41

HA LF E N H A N DRA IL CO NNE CTIO NS H GB


Dimensioning

Fastening with 1 bolt

Fastening with 2 bolts

cast-in channel HGB - E

hp

cast-in channel HGB - E

HALFEN bolts
HGB channels

Banister bolt HGB - M

hp

Banister bolt HGB - M

HTA / HZA channels

25 25

25

The maximum acceptable force is comprised of a


horizontal component N and a vertical component
V. Thus the vertical load V, which acts as a transverse
load for the channels, is limited for all the profiles as
per the table presented below left.

25

NEd

Concrete C20/25

VEd
FEd

FEd = NEd2 + VEd2 FRd


VEd VRd

Design values of acceptable connection moments MR,d [kNm] and load capacity FRd [kN] per HGB - screw

100-200

150-200

150 -200

HTU channels

4
e

[mm]

[mm]

38/17

40/25

49/30

54/33

38/17

40/25

49/30

54/33

38/17

40/25

49/30

54/33

40

120

0.36

0.41

0.61

1.28

0.46

0.61

0.92

1.67

0.51

0.66

1.02

1.79

60

160

0.52

0.60

0.90

1.87

0.67

0.90

1.35

2.44

0.75

0.97

1.50

2.62

80

200

0.68

0.78

1.17

2.44

0.87

1.17

1.75

3.18

0.97

1.26

1.95

3.41

100

240

0.83

0.95

1.42

2.97

1.07

1.42

2.14

3.87

1.19

1.54

2.37

4.16

120

280

0.97

1.11

1.67

3.48

1.25

1.67

2.50

4.54

1.39

1.81

2.78

4.88

140

320

1.10

1.26

1.90

3.97

1.42

1.90

2.85

5.18

1.58

2.06

3.17

5.56

9.8

11.2

16.8

35.0

2x 6.3

2x 8.4

2x 12.6

2x 22.8

2x 7.0

2x 9.1

2x 14.0

2x 24.5

FEd

FEd

Mounting type
A

< 80

FEd

Roof and Wall


Curtain Wall

FRd [kN]

VRd
per
channel
[kN]

ar

ae

[mm]

[mm]

38/17

4.9

50

40

40/25

7.4

60

45

49/30

9.9

70

50

54/33

11.2

75

50

7
Accessories

Profile

50
ar
25

42

VEd
per channel

FEd

Mounting type
C

100

HGB-E

Design values of acceptable transverse forces V Rd and edge distancess a r , a e

ae

FEd

80

HGB-E

Mounting type

HGB-E

Design values of the load capacity FRd and MRd


Bolts
Type
HGB-M

Stainless steel A4-70

Bending moment per


screw
Thread

FRd [kN]

MRd [Nm]

M12

17,6

45,9

M16

33,0

116,6

2009 HALFEN - B 09 - E - www.halfen.com

HALFEN HTU cast-in channels


The Advantages at a Glance

HTA / HZA channels

he technically perfect
solution for attaching
trapezoidal steel sheet to concrete
with HALFEN HTU cast-in channels
and self-tapping screws has today
become a standard solution for
construction specialists.

HALFEN bolts

2
HALFEN HTU cast-in channels
Anchor design AN

HGB channels

Safe and dependable

4
HTU channels

Safe and low-slip anchoring


through the shape of the anchoring
elements
Due to the Styropor filling,
the drill and/or self-tapping
screws will not strike the concrete
officially approved

Roof and Wall

HALFEN HTU cast-in channels


Anchor design D

Fast and easy screw-attachment of


the trapezoidal sheet metal
Cost-effective assembly
Two anchor designs AN and D for
optimum adaptation to the existing
reinforcement

6
Curtain Wall

Fast and cost-effective

Accessories

2009 HALFEN - B 09 - E - www.halfen.com

43

HA LF E N H TU CAS T- IN CHANNE LS
General, Material

HALFEN bolts

General
The connecting elements
for mounting between channel and
steel trapezoidal profile are considered
IFBS-approved per general technical
approval titled Connections for use with
structures employing cold profiles made
of steel sheet.

channel

No
p.
Ap

.4
21
Z-

84

pr
ove
d

n
t-i

as

The HALFEN trapezoidal metal sheet


mounting channels
were developed in cooperation with the
industrial association for light-weight
steel construction (IFBS).They consist of
a C-shaped channel with at least two
welded-on anchors, hot-dip galvanised
or of stainless steel and have been
approved by the German Construction
Materials Supervisory Board.

H TU c

HTA / HZA channels

ocially

ap

Approval No. Z-14.1-4

Z-21.4-84

Approval No. Z - 21.4 - 84

HGB channels

HTU channels

Material / Corrosion protection


Hot-dip galvanised FV:
Dipped in a galvanising bath at temperature of
approx. 460C,
a method used primarily for open-profile channels.

HALFEN HTU cast-in channels, steel hot-dip galvanised

Steel
Material

Standard

Zinc coating

1.0038 ( S235JR )

DIN EN 10 025-2

FV: 50 m

Channel profiles

Roof and Wall

Anchor AN, D

Connecting elements: Steel galvanised as per app. no. Z-14.1-4 of the industrial association for lightweight steel construction (IFBS).

Stainless steel A4:


Chromium is the important alloying element in stainless steel. A specific chromium concentration ensures
the generation of a passive layer on the surface of the
steel that protects the base material against corrosion.
This explains the high corrosion resistance of stainless
steel.

Curtain Wall

FV = Steel S235JR, hot-dip galvanised


A4 = Stainless steel 1.4571/1.4404/1.4401

HALFEN HTU cast-in channels, steel hot-dip galvanised

Stainless steel A4

Accessories

Material

Standard

Corrosion resistance class


per Z-30.3-6

1.4401, 1.4404 o. 1.4571

DIN EN 10 088

III

Channel profiles
Anchors AN, D

Connecting elements: Stainless steel in concurrence with screw suppliers

44

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N H TU CAS T- IN CHANNE LS
Installation, Assembly

Installation
The pre-finished channel type HTU is to be embedded in the
concrete parts flush with the surface edge. It is advisable to
level the concrete surface and to apply a slight slope to the
outer edge of the concrete. This is to ensure that the trapezoidal sheet metal rests only on the HTU channel. If, on the
other hand, the manufacturer of the trapezoidal sheet metal
requires a total support width of more than
60 mm, this can be achieved through a flush channel installation and a flat concrete surface. A horizontal placement,
properly aligned, and centred in the case of trusses of prestressed concrete, is to be ensured. Maintaining a
20 mm butt joint gap between the individual channel ends is
recommended.

HTA / HZA channels

HALFEN bolts

3
HGB channels

Trapezoidal sheet metal attachment in roof area

Trapezoidal sheet metal attachment in wall area

Position of screws

20

HTU channels

sealing disc

25Channel-end to screw spacing


Channel-end to concrete edge spacing

>1/3 a

Dimensions in mm

2009 HALFEN - B 09 - E - www.halfen.com

Butt joint gap

Curtain Wall

Recommended butt joint gap between two channels

20

7
Accessories

Assembly (with self-tapping screw)


The self-tapping screw is placed on the screw driver and is
fastened in one step without predrilling a pilot hole. Even
the 4-fold overlapping at joints does not pose a problem
with the self-tapping screw.
Use power screw drivers with approx. 1500 rpm and with
a socket wrench, size 10.
Suitable tools for the respective screws can be obtained
from the screw supplier.
The trapezoidal sheet metal must be attached in the central
third of the channel back; The screw must be positioned at
a minimum distance of 25 mm from the channel ends.

Roof and Wall

>1/3 a

45

H TU c

as

channel

Z
No
p.
Ap

Model Selection, Identification

1.4
-2

ocially

Type HTU 60/22/3


Configuration D

HALFEN bolts

2,81 cm

4,94 cm

1,13 cm4 / 0,71 cm

1,84 cm4 / 1,27 cm

Profile weight with anchors


Connecting elements HTU material stainless steel
Channel thickness 3 mm
e.g. JT3-3H-5.5x25-E16 with 4.5mm pre-drilled
or JZ7-6.3x22-E16 with 5.3mm pre-drilled. .
- not certified Coordination with the screw suppliers is necessary

2,50 kg/m

Connecting elements HTU material steel Z-14.1-4:


Self-tapping screws 6.3x19
e.g. JT2-6-6.3-19-x16 with sealing disc.
Connecting element is exposed to weather: JT3-66.3x25-E16 (Wall) or JZ3-6-6.3x25-E22 (Roof)
HTU 60/22/3

= hot-dip galvanised

Example:

Type/ Profile
Anchor configuration
Material/ Finish
Length [mm]
Styropor - strip filler

4,25 kg/m

No.of
anchhors

4,26 kg/m

Connecting elements HTU material steel Z-141-4:


Self-tapping screws 6.3x22
e.g. JT2-6-6.3-x22-V16 with sealing disc
or cartridge fired pins SBR-14.
Connecting element is exposed to weather: see left
HTU 60/22/6

= hot-dip galvanised

No.of
anchhors

HTU 60/22/3 - AN2 - FV - 3000 - Sf

HTU 60/22/6 - AN2 - FV - 3000 - Sf

HTU 60/22/3 - D2 - FV - 3000 - Sf

HTU 60/22/6 - D2 - FV - 3000 - Sf

HTU 60/22/3 - AN3 - FV - 3000 - Sf

20

HTU 60/22/6 - AN3 - FV - 3000 - Sf

20

HTU 60/22/3 - D3 - FV - 3000 - Sf

20

HTU 60/22/6 - D3 - FV - 3000 - Sf

20

= Stainless steel A4
HTU 60/22/3 - AN2 - A4 - 3000 - Sf

HTU 60/22/3 - D2 - A4 - 3000 - Sf

HTU 60/22/3 - AN3 - A4 - 3000 - Sf

20

HTU 60/22/3 - D3 - A4 - 3000 - Sf

20

FV = Steel S235JR, hot-dip galvanised


A4 = Stainless steel
1.4571/1.4404/1.4401

Anchor spacing:
Type D2 and/or AN2

Type D3 and/or AN3

Dimensions in mm

Material A4 only in 3mm thickness

Identification HTU
For identification, a label is affixed to the back or each channel.
HTU 60/22/3 Type D
(Steel S235 and/or 1.4401/1.4404/1.4571, thickness 3mm)

for screw-fastening of trapezoidal sheet metal


with hexagonal sheet metal or self-tapping screws

46

n
t-i

channel

Z
No
p.
Ap

1.4
-2

ocially

84

pr
ove
d

Accessories

2,49 kg/m

as

Curtain Wall

75

22
100

75

Profile cross-section A
Moment of inertia ly / Moment of resistance wy

H TU c

HGB channels
HTU channels
Roof and Wall

63,5

63,5

HTU 60/22/3 - D2 - FV - 3000 - Sf

60

60

22
100

Configuration D

Configuration AN

60

60

HTA / HZA channels

Configuration AN

ap

Type HTU 60/22/6

84

pr
ove
d

n
t-i

HA LF E N H TU CAS T- IN CHANNE L

ap

2009 HALFEN - B 09 - E - www.halfen.com

H TU c

as

channel

Z
No
p.
Ap

Dimensioning

1.4
-2

ocially

84

pr
ove
d

n
t-i

HA LF E N H TU CAS T- IN CHANNE LS

ap

Max. design load-carrying capacity FEd

Anchor spacing s [mm]

qEd

p s

max. FEd [kN]

450

4,6

max.uniformly distributed load


qEd [kN/m]

max. FEd [kN]


3,5

15,5

3,5

46,6

3,5

15,5

3,5

46,6

HALFEN bolts

Profile HTU

p s

60 / 22 / 3
150

7,0

p=s
450

7,0

150

7,0

p = /2

60 / 22 / 6

NEd2 + FxEd2 + FyEd2 max. FEd

3
HGB channels

Concrete C20/25

Minimum distance with utilisation of maximum load as per Table 1


Profile

Minimum interaxial spacing and edge distance

60/22/3

aa

ar

ae

af

60/22/6

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

HTU

af
20

20

100 +
nom c

ae

200

ar

min. b
Type D

200

100

20

20

If the trapezoidal sheet metal mounting channels are


attached in such fashion that the anchors of adjacent
channels are offset from each other by at least 200 mm,
the interaxial spacing aa may be reduced to 80 mm.
With less than full utilisation of the maximum impart FEd
as per above table, the edge distance ar may be reduced
only in case of a sole central tensile stress NEd, to:

ar red. =

prev. NEd
x ar 50mm
max. FEd

Prev. NEd = design rating


per previous impact
max. FEd = maximum impact
as per above table

75 +
nom c

aa

ar

HTU channels

100

200

5
Roof and Wall

200

With full utilisation of the maximum impact FEd


as per above table, the last anchor must be at least
90 mm from the component edge.
With full utilisation of the maximum impact FEd
as per above table, the terminating anchors must be at
a min. distance of 150mm from one another
Determined by the geometry of the anchors and the
required concrete covering.

Minimum component width with a one-channel layout.

In cases of transverse stress (VxEd , VyEd), the edge distances


must not be reduced.

2009 HALFEN - B 09 - E - www.halfen.com

Accessories

Type AN

Curtain Wall

HTA / HZA channels

47

HA LF E N H TU CAS T- IN CHANNE LS
Application Examples

HTA / HZA channels

HALFEN bolts

2
Mounting the HTU cast-in channels in the front-face of the slab

HGB channels

HTU channels

Roof and Wall

Vertical HTU cast-in channels for the mounting of faade panels

Faade fixed with HALFEN HTU cast-in channels

Assembly of trapezoidal sheet metal with self-tapping screws

HTU cast-in channels in a prestressed concrete girder

Curtain Wall

Accessories

48

2009 HALFEN - B 09 - E - www.halfen.com

Roof and Wall


The Advantages at a Glance

he ecient and established


mounting systems for wooden
roof structures, masonry mounts
and horizontal connectors for
concrete faades have proved to be
practice-oriented and productivityincreased solutions.

HALFEN rafter shoe HSF


For taking up the horizontal forces
acting on rafter and collar beam roofs,
type-tested.

2
HALFEN bolts

HTA / HZA channels

HALFEN timber xing strap HNA

3
HGB channels

For taking up the occurring load e.g.


wind load when attaching roof structures.

HALFEN brick tie anchor systems


ML+BL

4
HTU channels

Mounting systems for connecting


masonry with concrete walls and
columns or steel structures.

HALFEN corner guard HKW


Mounting systems for connecting
concrete walls and columns or steel
structures.

Roof and Wall

HALFEN restraint tie HKZ


HALFEN restraint with turnbuckle SPV
For bearing compressive and tensile loads
from concrete wall elements.

Curtain Wall

HALFEN precast connection HVL


For bearing the horizontal loads from
concrete wall elements (load perpendicular to the bracket).

Accessories

2009 HALFEN - B 09 - E - www.halfen.com

49

R OO F & W A L L
HALFEN Timber Fixing Strap

For attaching roof structures to concrete or reinforced


concrete ring beams and/or reinforced concrete slabs,
either continuous HTA HALFEN cast-in channels or short
elements HTA HALFEN cast-in channels are embedded in
the concrete construction.The selection of the HTA HALFEN
cast-in channels as well as of the nailing straps and the nails
is based on the incident load (e.g., from wind force)
Calculation and design basics:
DIN 1055 - 4:2005 - 03
DIN 1052 : 2004 - 08
The timber fixing straps can be placed on one or on both
sides of the wooden beams. The load capacities FRd are
should be taken from the following table. With one-sided
placements, the beams are to be secured against twisting
(e.g. through nailing the upper formwork)

HTA / HZA channels

HALFEN bolts

Typical attachment of wooden beams using HNA nailing straps on HALFEN cast-in channels embedded in concrete.

Model selection
Dimensions in mm
N 120
N 95
BN 120
BN 95

WN 120
WN 185

Ordering example:
HNA - BN 120 - FV

BN 185
Type WN 120 without hole 17)

HGB channels

Assembly example:
F1,d

Roof and Wall

Curtain Wall

HALFEN
cast-in channel
HTA 38/17

Model selection, timber fixing straps

suitable for
HALFEN
cast-in channel:

Material/Finish
FV = S235, hot-dip galvanised
Identification: Length
[mm]
HNA - N 95 - FV

HTA 28/15
hot-dip galvanised
(FV)

HNA - N 120 - FV
HNA - WN120 - FV

Design rating of the load capacity FRd [kN] per


beam attachment

HTA 38/17
hot-dip galvanised
(FV)

HNA - BN120 - FV

Double-sided
for b 60 mm

b 100 mm

4.2

4.9

5.6

1.4

2.8

2.8

6.3

7.5

8.4

1.4

2.8

2.8

Wire nails

Anchor nails

According to
DIN EN 10230-1/
DIN 1151

According to the
technical approval of
the manufacturer

HNA - BN185 - FV
HNA - WN120 - FV
HNA - WN185 - FV

Example: Existing loads:


HTA - cast-in channel:
Beam dimension:

50

Attachment of the timber fixing straps to


wooden beams

Placement of the timber fixing straps


One-sided

HNA - BN 95 - FV

Accessories

F1,d

HALFEN bolt M10 with


nut,
order separately

HNA - WN185 - FV

F1,d < FRd


Timber fixing strap
HNA - BN 120

HTU channels

Finish
Length [mm]
Type

selected: Timber fixing strap double-sided Type HNA - N 120


F1,d = 4.9 kN
with FRd = 5.6 kN > F1, d
HTA 28/15, short element L = 250 mm
HALFEN cast-in channel: FRd = 2x4.2 > F1, d
b/d = 100/160 mm
Wire nails: Load bearing capacity per DIN EN 10230-1/DIN 1151

2009 HALFEN - B 09 - E - www.halfen.com

R OO F & W A L L
HALFEN Rafter Shoe HSF

2 toothed plates are included

type-tested

Example 1

rafter shoe HSF 6/12


cast-in channel HTA

Design ratings FRd


Load level
FRd

[kN/Rafter]

The distribution of the horizontal forces into the concrete


structure occurs via officially approved HALFEN cast-in channels type HTA.
During assembly, ensure that the serration of the counter plate engages in the base plate. The marking slot on the counter
plate must be oriented perpendicular to the direction of the
slot in the elongated hole.
Rafter roof system:

Required HALFEN
cast-in channel

Min.
edge
distance

Required
HALFEN bolt

Type

ar [mm]

Type Dimensions

9.00

12.6

HTA 38/17

75

HS 38/17 - M16 x 40

12.00

16.8

HTA 40/22, 40/25

100

HS 40/22 - M16 x 50

14.00

19.6

HTA 50/30, 49/30

150

HS 50/30 - M16 x 50

F1,d < F Rd

FN,

F1,d

HTA / HZA channels

The maximum normal rafter strength is limited by the dimensioning


of the individual rafter shoe parts. Load tests showed an average
breaking load of 50 kN. With normal strengths that are greater than
the recommended load capacity (= about 1/3 of the breaking load),
the rafter spacing may need to be reduced, if required.
The minimum edge distance ar of the HALFEN cast-in channels can
be reduced with lower loads, see table page 23. The distance to the
outer concrete edge must be at least 170 mm.
It must be ensured that the HALFEN cast-in channels are installed
flush with the concrete surface.

Accessories

HALFEN rafter shoes Typ HSF 6/12

2009 HALFEN - B 09 - E - www.halfen.com

Curtain Wall

Load
capacity

Minimal planning effort, simply specify the profile and


location of the HALFEN channels to be embedded in the
concrete.
Clear static conditions through flexible mounting of the
rafter shoe. Type-tested statics, Test report No. 1. P
30 - 201/82, No. II B 3 - 543 - 506 Extension report.
No need for labour-intensive support constructions.
Simple and problem-free erection of the roof structure:
a) Rotatable arrangement of the support plate,
b) Movable nailing brackets for vertical anchoring
for different rafter widths from 0 to 120 mm.
c) Adjustable in the longitudinal rafter direction 15 mm.
Adjustable in the longitudinal channel direction of HALFEN
channels, allowing for different rafter spacings without
special additional provisions.
Excellent corrosion protection through hot-dip galvanisation

HALFEN bolts

The Advantages at a Glance:

HGB channels

Material/Finish:
FV = Steel S235JR,
hot-dip galvanised

HTU channels

Dimensions
in mm

In modern wood construction, rafter shoes type HSF 6/12


are used to absorb the horizontal forces of rafter and collar
beam roofs.

Roof and Wall

HSF 6/12

51

R OO F & W A L L
Brick Tie Anchor Systems

HTA / HZA channels

HALFEN brick tie anchor systems are


efficient and proven mounting systems
for attaching brick work, infills, partitions,
facings (with and without air gap and/
or heat insulation) using HALFEN brick
tie anchors ML or BL to concrete walls

and concrete supports or to steel and


wooden structures. Due to the moveability of the brich tie anchors in the brick tie
channels, the risk of masonry settlement
cracksis reduced considerably.

Wall attachment

Facing brickwork attachment

HALFEN bolts

Embedding length e

All HTA and HMS profiles have a


Haropor foam filling for protection
against concrete infiltration. The channels
are attached to the formwork using nails.
When erecting the brick wall, the HALFEN brick tie anchors are inserted in the
brick tie channels at any desired location
or at recommended distances and after
a 90 rotation pushed into the grouting
space mortar for anchoring.

d
FZ,Ed

FZ,Ed
l

Embedding length e 50mm

FQ,Ed

air gap a - see FM Catalogue

Brick tie anchor ML in combination with HALFEN cast-in channels 25/15-D and 28/15

HGB channels

HMS cast-in channel with lug anchor

HTA cast-in channel

HMS 25/15 D

HTU channels

4
HTA 28/15
officially approved

ML

ML

Roof and Wall

HM welded to steel supports

6
Curtain Wall

HM 28/15

1. Attach to
formwork

2. Bend out lug


anchor

3. cast concrete

ML

Accessories

The lug anchors are bent out at the construction site manually
at distances of 250 for a secure reanchoring in concrete.

52

2009 HALFEN - B 09 - E - www.halfen.com

R OO F & W A L L
Brick Tie Anchor Systems, HALFEN Anchor Bolt Systems

Top view
15

a as per static requirements

25

HTA / HZA channels

HL slotted framing channels anchored in concrete or


masonry

Dowel
HALFEN Dbel

2
HALFEN bolts

HL 28/15
1

ETA-07/0249

ML
L

ETA-07/0250
A 07/0250

Wedge anchor HB-BZ-U


HALFEN
Z-21.3-1853
Zul.-Nr. . . . . .
DIBt

Institut
fr Massivbau

Anchor studs HB -VMU-A


Internally threaded sleeves HB-VMU-IGH
Perfo sleeve HB-VMU-SH

HB-BZ-U 8-15/80

A h bolt
b lt system
HALFEN Anchor
Use and assembly
see HB Catalogue

HL 28/15

HGB channels

Technische Universitt
Darmstadt

4
HTU channels

Wedge anchor HB-BZ-U 8-15/80


Galvanised or stainless steel (A4)
Approved for cracked and uncracked concrete
With large washer DIN9021/EN ISO 7093

HL 28/15

Anchor studs HB -VMU-A 8-20/110


Galvanised or stainless steel (A4)
Approved for solid brick masonry
With large washer DIN 9021/EN ISO 7093 is to be ordered separately

large washer
order separately

2009 HALFEN - B 09 - E - www.halfen.com

Curtain Wall

HL 28/15

Anchor studs HB-VMU-A 8-20/110 with


Perfo sleeve HB-VMU-SH 14x100
or
Internally threaded sleeves HB-VMU-IGH M8 with
Perfo sleeve HB-VMU-SH 16x100

7
Accessories

HB -VMU-AH + SH
HB-VMU-IGH+SH

large washer
order separately

Roof and Wall

5
HB -VMU-A

Galvanised or stainless steel (A4)


Approved for perforated brick masonry
Large washer see above

53

R OO F & W A L L
Brick Tie Anchor Systems

HTA / HZA channels

Masonry attachment
with BL

HTA 28/15
officially approved
ML 1

HTA 38/17
officially approved
BL

Masonry attachment with ML/BL

max. load F Z,Ed = 0.32 kN


per cm embedded length e,
max. F Z,Ed
3.2 kN
max. F Q,Ed 2.7 kN

ML

max. F Z,Ed
max. F Q,Ed

2.5 kN
1.4 kN

Onesided

FQ,Ed

FZ,Ed

FQ,Ed

ML 1

FQ,Ed

(can be
used as an
alternative)

25

HTU channels

Brick tie anchor


15

28

75

15

28

15

ML
Standard

ML1

MLQ - D
Double-sided

MLQ - E
One-sided

MLS
Oblique

26 x 2 [mm]

25 x 1,25 [mm]

25 x 3 [mm]

25 x 3 [mm]

22 x 3 [mm]

HTA 28/15
Type

L = 6070 mm

48

Roof and Wall

Brick tie anchor

HMS 25/15 D
L = 2500 mm

L = 1050 mm

oblique

Fz,Ed

Consider the profile load capacity!

HL 28
28/15
8/15
8/1

Length l
[mm]

Type

Length l
[mm]

Type

Length l
[mm]

Type

Length l
[mm]

Type

Length l1
[mm]

ML - 85

ML 1 - 125

MLQ-D - 85

MLQ-E - 85

MLS - 300

ML - 120

ML 1 - 185

MLQ-D - 120

MLQ-E - 120

MLS - 350

ML - 180

ML 1 - 245

MLQ-D - 180

MLQ-E - 180

MLS - 400

BL
Standard

BLQ - D
Double-sided

BLQ - E
One-sided

30 x 2 [mm]

30 x 3 [mm]

30 x 3 [mm]

L = 6070 mm

HTA 38/17

Curtain Wall

38

17

L = 1050 mm
L = 6070 mm

Type

50 (74)

Length l
[mm]

Type

Length l
[mm]

Type

Length l
[mm]

BL - 85

BLQ-D - 85

BLQ-E - 85

BL - 120

BLQ-D - 120

BLQ-E - 120

BL - 180

BLQ-D - 180

BLQ-E - 180

Material:
FFV =

Steel S235JR,
hot-dip galvanised
SSV = Steel DX51D + Z275,
Sendzimir galvanised
A4 = Stainless steel
A
1.4571/1.4404/1.4401
A2
A = Stainless steel 1.4301
Other lengths:

Available on request

Debond sleeve ML-G 150 for wall attachments, suitable for ML - anchors

Accessories

Doublesided
FZ,Ed

FZ,Ed
FQ,Ed

ML 1

b1 (150)

HGB channels

25 25 25

Standard

l1

ML, BL

(can be
used as an
alternative)

Brick tie anchors

b (300)

HALFEN bolts

Masonry attachment with


ML 1

30

ML-G 150

Permits movement in the longitudinal anchor direction e.g.,


when attaching long wall combinations or partitions to bearing concrete structures to avoid fissuring.

150

ML-G 150, Material: Soft PVC, Material thickness 1,5 mm

54

2009 HALFEN - B 09 - E - www.halfen.com

R OO F & W A L L
Firewall Mounts

Firewall mount according to DIN 4102 T4

HTA / HZA channels

Statically required attachments of load-bearing, room-enclosing


solid walls can be designed with HALFEN brick tie channels as
firewalls according to DIN 4102 T4 Chapter 4.8 as well.
Anchoring to the adjacent components (steel reinforced
concrete support, wall) fulfils the requirements for fire
conditions with regard to stability and fire resistance rating, if it
conforms to the standards of DIN 4102 T4 Para. 4.8.4

HALFEN bolts

Attachment of a load bearing solid wall as a firewall according to DIN 4102 T4 Para. 4.8.4 (Pic. 20.2)

Masonry: Bricks (gross density class) and minimum thickness d according to DIN 4102 T4, Section 4.8.3, Table 45.

4
HTU channels

Insulation layer: According to DIN 4102 T4 Line. 4.5.2.6


insulation layers in connecting joint gaps must [...] consist
of mineral fibre according to DIN 18165 T.2/07.91, Section
2.2, must be of building material class A, have a melting point
1000C according to DIN 4102 T. 17 and exhibit a gross
density of 30 kg/m [...].

HGB channels

3
Explanations, DIN regulations

Product information
for thin bed mortar

HMS 25/15

ML

ML 1

HTA 28/15

ML

ML 1

HTA 38/17

BL

Roof and Wall

for normal grout

Typ

Brick tie anchor ( see page 54)

HALFEN brick tie anchors can be used at any desired


position across the total length of the brick tie channel.
As a rule, anchor spacing is 250 mm (4 anchors per
meter).
Note:
HALFEN cast-in channels HTA and HZA Dynagrip along with
HALFEN bolts are allowed for use in fire-exposed components. The permissible loads for the HALFEN channels are
determined based on the bolt dimensions for a fire resistance
rating of 60 minutes (F60) and 90 minutes (F90) according
to technical approval. (see Certification Z-21.4-34 for
HALFEN cast-in channels HTA and Certification Z-21.4-1691
for HALFEN cast-in channels HZA Dynagrip).

2009 HALFEN - B 09 - E - www.halfen.com

55

Curtain Wall

HALFEN cast-in
channel

7
Accessories

Vertical section

R OO F & W A L L
Restraint with Turnbuckle SPV

HTA / HZA channels

SPV

F Ed = Impact
FEd

HALFEN channel Type HTA

FEd

HALFEN bolts

HGB channels

HTU channels
Roof and Wall

Ensure a sufficient screwing depth:


M 12 10 mm
M 16 13 mm

Ordering example
Designation: SPV - 7,0 - 100 - A4

The restraint with turnbuckle SPV is


suitable for taking up compressive
and tensile loads up to FEd = 14.0 kN
and for distances up to 200 mm. By
turning the clamping sleeve with a
right/ left hand thread, the distance
can be adjusted continuously within
the adjustable range. Mounting on the
components is done using HALFEN
cast-in channels (order separately).

Type
Load group
Wall distance b
Material/Finish

Turnbuckle SPH
2 HALFEN bolts (1 right-hand thread,
1 left-hand thread)
3 flat nuts
2 washers and
2 locking washers SIC

HALFEN cast-in channels, order separately

HALFEN restraint with turnbuckle Type SPV


Load group

[kN]

5,0

7,0

10,0

Load capacity. FRd [kN]

7,0

9,8

14,0

Wall distance

6
Curtain Wall

Included in shipment

Product characteristics

Type

SPV

HALFEN bolt
left-hand thread

Sleeve

HALFEN bolt
HALFEN bolt
rigth-hand thread left-hand thread

Sleeve

HALFEN bolt
HALFEN bolt
rigth-hand thread left-hand thread

Sleeve

HALFEN bolt
rigth-hand thread

M12

M12

M16

M16

M16

M16

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

10010

50

60

40

50

60

40

12015

50

75

40

50

75

40

14015

50

75

60

50

75

60

80

60

50

16015

50

95

60

50

95

60

80

75

60

18015

50

115

60

50

115

60

80

95

60

20015

50

135

60

50

135

60

80

115

60

[mm]

HALFEN cast-in channel

HTA 38/17

HTA 38/17

HTA 49/30

Short elements 150, 200 and 250


With load group 7,0 the negative tolerance is restricted

Accessories

Type HTA

Restraint with
turnbuckle SPV

HALFEN channel

For further accessories


ffor concrete faades
ssee Catalogue
C
Concrete Faade FB

56

2009 HALFEN - B 09 - E - www.halfen.com

R OO F & W A L L
Restraint Tie HKZ

HALFEN cast-in channel HTA

HTA / HZA channels

F Ed = Impact

HKZ

FEd
FEd

HALFEN bolts

2
(interaxial spacing)

a1

The serration grooves in the bracket


and in the toothed washer ensure
excellent static load distribution.
Embedding the HALFEN cast-in
channels at a right angle to each other
in the concrete ensures three-dimensional adjustability.

Hammer-head bracket
with serration
Toothed washer

Ordering example
Designation:

Please order HALFEN cast-in channels, HALFEN bolts and washers


separately

HKZ-38/17 - 100 - A4

Type
Distance a1
Material/ Finish

4
HTU channels

Included in shipment

HALFEN restraint tie Typ HKZ

Load group Load capa- Wall distance


(tensile)
city
b
kN
kN
mm
0
25
50
75
3.5
4.9
100
125
150
175
200
0
25
50
75
100
7.0
9.8
125
150
175
200
225

Type

a1

mm
HKZ 28/15 - 50 - GV
HKZ 28/15 - 75 - GV
HKZ 28/15 - 100 - GV
HKZ 28/15 - 125 - GV
HKZ 28/15 - 150 - GV
HKZ 28/15 - 175 - GV
HKZ 28/15 - 200 - GV
HKZ 28/15 - 225 - GV
HKZ 28/15 - 250 - GV
HKZ 38/17 - 75 - GV
HKZ 38/17 - 100 - GV
HKZ 38/17 - 125 - GV
HKZ 38/17 - 150 - GV
HKZ 38/17 - 175 - GV
HKZ 38/17 - 200 - GV
HKZ 38/17 - 225 - GV
HKZ 38/17 - 250 - GV
HKZ 38/17 - 275 - GV
HKZ 38/17 - 300 - GV

Type

a1

mm
HKZ 28/15 - 50
HKZ 28/15 - 75
HKZ 28/15 - 100
HKZ 28/15 - 125
HKZ 28/15 - 150
HKZ 28/15 - 175
HKZ 28/15 - 200
HKZ 28/15 - 225
HKZ 28/15 - 250
HKZ 38/17 - 75
HKZ 38/17 - 100
HKZ 38/17 - 125
HKZ 38/17 - 150
HKZ 38/17 - 175
HKZ 38/17 - 200
HKZ 38/17 - 225
HKZ 38/17 - 250
HKZ 38/17 - 275
HKZ 38/17 - 300

- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4
- A4

Dimensions
Length
l
mm
90
115
140
165
190
215
240
265
290
115
140
165
190
215
240
265
290
315
340

Spacing Tolerance
ar
mm
mm

50

a1
20

Mounting on
cast-in channel
Holes

with HALFEN
bolt

mm

LL 11x55
RL 11

HTA 28/15
HS 28/15
M10x30
Tightening
torque
MA=15Nm

75

a1
20

LL 13x55
RL

HTA 38/17
HS 38/17
M12x50
Tightening
torque
MA=25Nm

Short elements 150, 200, or 250 mm long or anchoring dowels with official technical approval.
Only limited suitability for anchoring faades !
Check edge distance ar when using anchoring dowels

2009 HALFEN - B 09 - E - www.halfen.com

6
Curtain Wall

Model selection: GV = galv. Not Model selection: A4 = Stainless


suitable for rear-ventilated faades
steel Grade 1.4571/1.4401

7
Accessories

Characteristics

Roof and Wall

Product characteristics

HGB channels

57

R OO F & W A L L
Restraint Tie HKZ - GF / GU

HKZ - GU

HTA / HZA channels

FEd

FEd

cast-in channel
HTA

HALFEN bolts

Slab

FEd
FEd

F Ed = Impact

HGB channels

HTU channels

HKZ - GF

cast-in channel
HTA

Product characteristics

Ordering example

The serration grooves in the bracket


and in the washer ensure excellent static load distribution. The double-sided
attachment using a HALFEN bolt and/
or a threaded plate ensures, positive

Roof and Wall

Load
group
(TensileCompression)
[kN]

3.5

Curtain Wall

7.0

12.0

Model selection:
GV = galvanised

Load capa- Wall distance


b
city
FRd

[kN]

4.9

9.8

7
Accessories

Designation: HKZ - GF 38/17 - 125 - gv

and slippage-free wind anchoring when


using HALFEN cast-in channels Type
HTA embedded in concrete. During
assembly, adjustments are possible in
3 directions.

Type
Interaxial spacing a1
Material/ Finish

HALFEN restraint ties type HKZ-GF and type HKZ-GU


Characteristics:

Slab

16.8

[mm]

Type

a1

[mm]

Model selection:
A4 = Stainless steel
1.4571/1.4401

Type

a1

[mm]

Dimensions:

Attachment to
cast-in channel

Length Spacing Tolerance elongal


ar
ted hole

with HALFEN
bolt

[mm]

25

HKZ - GF 28/15 - 75 - GV

HKZ - GF 28/15 - 75 - A4

115

50

HKZ - GF 28/15 - 100 - GV

HKZ - GF 28/15 - 100 - A4

140

75

HKZ - GF 28/15 - 125 - GV

HKZ - GF 28/15 - 125 - A4

165

100

HKZ - GF 28/15 - 150 - GV

HKZ - GF 28/15 - 150 - A4

190

125

HKZ - GF 28/15 - 175 - GV

HKZ - GF 28/15 - 175 - A4

215

25

HKZ - GF 38/17 - 100 - GV

HKZ - GF 38/17 - 100 - A4

143

50

HKZ - GF 38/17 - 125 - GV

HKZ - GF 38/17 - 125 - A4

168

75

HKZ - GF 38/17 - 150 - GV

HKZ - GF 38/17 - 150 - A4

193

100

HKZ - GF 38/17 - 175 - GV

HKZ - GF 38/17 - 175 - A4

218

125

HKZ - GU 38/17 - 200 - GV

HKZ - GU 38/17 - 200 - A4

243

150

HKZ - GU 38/17 - 225 - GV

HKZ - GU 38/17 - 225 - A4

268

175

HKZ - GU 38/17 - 250 - GV

HKZ - GU 38/17 - 250 - A4

293

50

HKZ - GU 50/30 - 200 - GV

HKZ - GU 50/30 - 200 - A4

240

75

HKZ - GU 50/30 - 225 - GV

HKZ - GU 50/30 - 225 - A4

265

100

HKZ - GU 50/30 - 250 - GV

HKZ - GU 50/30 - 250 - A4

290

125

HKZ - GU 50/30 - 275 - GV

HKZ - GU 50/30 - 275 - A4

315

150

HKZ - GU 50/30 - 300 - GV

HKZ - GU 50/30 - 300 - A4

340

[mm]

[mm]

[mm]

50

a1
20

11x55

75

a1
20

13x55

75

a1
20

13x60

150

a1
20

17x60

HTA 28/15
HS 28/15
M10x30
Tigthening
torque
MA=15Nm

HTA 38/17
HS 38/17
M12x50
Tigthening
torque
MA=25Nm

HTA 49/30
HS 50/30
M16x50
Tigthening
torque
MA=60Nm

Please order short elements 150, 200, or 250 mm long separately.


Check edge distance ar when using anchoring dowels.
Only limited suitability for anchoring faades!
58

2009 HALFEN - B 09 - E - www.halfen.com

R OO F & W A L L
Precast Connection HVL

Pre-assembled = fast installation !

Installation
component 1,
cast-in channel
HVL - E
Finished
concreAnzuschlieendes
te
component
Betonfertigteil to
be attached

HTA / HZA channels

2
HALFEN bolts

Assembly
part
Montageteil
Strap
HVL
Lasche HVL- M
-M

Installation
component 2,
cast-in channel
HTA 38/17 - 150

Assembly:
In the "as delivered" condition, the
connecting strap
is ready to be
installed: The screw
fastening sets and
the counter plate
are pre-assembled!

Pre-assembled
components

HGB channels

Corrosion protection

Pre-assembled, consisting of:


Hammer-head strap with toothed
plate
1 toothed counter plate
2 bolt sets (Bolt HS 38/17 - M 12
x 50 + washer + tapered
compression spring)

Consisting of HALFEN cast-in channel


HTA 38/17 - 300 with 2 bolt anchors
and one loop end anchor.

Hammer-head strap, cast-in channel:


hot-dip galvanised,
HALFEN bolts, nuts, washers, springs:
galvanised.
These parts are covered by mortar
grout when installed.

Roof and Wall

5
60

Vertical
section

Hd = 8,4 kN

6
BSt 500 S
(at construction site)

Curtain Wall

Length of recess: 350


15

Channel HTA 38/17 - 300 - UB

35

Accessories

140

10

75

65

10

Top view

4
HTU channels

Installation component 1 HVL-E

50

Assembly part HVL-M

Reinforcement at
construction site

2009 HALFEN - B 09 - E - www.halfen.com

Hd

Dimensions in mm
Design changes reserved

59

R OO F & W A L L
HALFEN Corner Guard

250

HTA / HZA channels

92

500

HALFEN corner guards


are supplied with
anchors ready to be
installed

250

HALFEN bolts

500

8mm

L [mm]

HGB channels

Example: Corner guards on wall corners and pillars in an industrial building

Pillar edge, typical cross-section

Type selection:

Corner guard
HKW

HTU channels

Link

Roof and Wall


Curtain Wall

Length No.
L of ana/t [mm] [mm] chors

Type

Main bar
Steel reinforcemnet anchor HKW

Advantages:
The 92 angle ensures a tight fit to the formwork. Thus,
connection with the concrete is achieved and leakage of
concrete slurry between the formwork and the corner
profile is avoided.
The U-shaped concrete-reinforced anchors do not interfere
with the corner reinforcement and facilitate the assembly
of the reinforcement cage.
The concrete-reinforced anchors guarantee optimal
anchoring.
Low price due to serial production.

Material/Finish:

Anchor dimensions

FV =
A2 = stainhot-dip
less steel.
galvanised

HKW 50/5 -

Corner guard HKW

HKW 80/6 -

HKW 100/8 -

500 / 2

FV

A2

750 / 2

FV

A2

1000 / 2

FV

A2

1500 / 3

FV

A2

2000 / 4

FV

A2

500 / 2

FV

A2

750 / 2

FV

A2

1000 / 2

FV

A2

1500 / 3

FV

A2

2000 / 4

FV

A2

500 / 2

FV

A2

750 / 2

FV

A2

1000 / 2

FV

A2

1500 / 3

FV

A2

2000 / 4

FV

A2

lxe
[mm]

Radius
R
[mm]

75 x 55

100 x 85

110 x 85

16

Accessories

7
Material/Finish:
FV = corner profile: Steel S235JR, hot-dip galvanised
anchor: BSt 500 S
A2 = corner profile: stainless steel 1.4301
anchor: BSt 500 NR

60

Ordering example:
HKW 50/5 - A2 - 2000/4
Length/ No.of anchors
Material/Finish
Type/ Profile

2009 HALFEN - B 09 - E - www.halfen.com

Curtain Wall HCW


The advantages at a glance
HTA / HZA channels

oday, modern buildings require


faades of the highest quality
that are safe and can be erected in
short time. The Curtain Wall System
is therefore selected by architects
and builders more and more
frequently.

HALFEN bolts

HCW B1

HGB channels

For the post and beam faade.


Anchoring on the top surface
of the storey slab.

HCW B2

HTU channels

For the modular faade.


Anchoring on the top surface
of the storey slab.

3 dimensionally adjustable
connection when used with
anchor channel
Bolts instead of welds
Fast assembly reduces installation
time

6
Curtain Wall

HCW- ED/EW

Roof and Wall

Fast and cost-effective

For the post and beam faade.


Anchoring on the face end
of the storey slab.

Accessories

2009 HALFEN - B 09 - E - www.halfen.com

61

HA LF E N C U R T A IN WALL S UPPO RT SY STEMS H CW


General

HTA / HZA channels

HALFEN bolts

HALFEN Curtain wall system

This principle of construction is


characterized by an outer wall with a
continuous outer skin (see Fig. 1)
The curtain wall faade is to protect
the interior of a building from external,
undesirable environmental influences
and yet, if desired, permit eye-contact
with the outside through structural
components that can be opened and/
or are transparent. Specifically, this

means sufficient stability against wind


loads as well as enough insulating
ability against frost in winter, the heat
in summer as well as against external
noise pollution.
In addition, certain requirements must
be met in the event of a fire and other
disaster.

Fig. 1

HGB channels

HTU channels

Roof and Wall

Curtain Wall

Accessories

The post and beam faade and the modular faade.

In principle, one distinguishes between


two construction methods of curtain
wall faades: the post and beam
faade and the modular faade.
One basic differentiating characteristic
is the way the expansions within the
faade are taken up. The first possibility, known by the term post and beam
faade (see Figure 2) is that the vertical and horizontal frame profiles are
lined up in a straight line in practical
production lengths, e.g., floor-to-ceiling
and segment--wide. They are installed
such that their longitudinal and transverse ends are kept slightly shorter,
thus leaving room for a gap corresponding to the necessary expansion. The
longitudinal and transverse connections are constructed in a moveable
fashion. The filler element (glass or
panel) installed in this post and beam
structure floats so-to-speak, and allows
for an expansion within the scope of
the installation clearance that was left
open. The glass and filler elements
are delivered separately and are not
installed until they are at the construction site, necessitating construction site
scaffolding. With the second construc-

62

Fig. 2

tion method, the modular faade, (see


Figure 3), the faade is made of elements prefabricated in the workshop,
with glass, natural stone and panels
already integrated. For taking up the
expansions, the faade profiles are individually telescoped into one another in
mazelike fashion.
This method of construction allows

Fig. 3

the faade contractor to begin with


the interior work on the respective
floor immediately after hanging a
completely prefabricated module, since
a driving-rain protection is ensured.
In general, scaffolding is not required
with this method of construction.

2009 HALFEN - B 09 - E - www.halfen.com

HA LF E N C U R T A IN WALL S UPPO RT SY STEMS H CW


Application Examples

HTA / HZA channels

Little Britain,
London

HALFEN bolts

Petronas Towers,
Kuala Lumpur

3
HGB channels

Liberty Life Project South Africa:


Mounting of a curtain wall faade using HCW-B2 brackets on
HTA channels

Post-Tower,
Bonn

Jin-Mao,
Shanghai

HTU channels

4
Peoplebuilding Hemel,
UK

Roof and Wall

5
Mounting of a curtain wall faade using HCW-ED brackets on
HTA channels

Central Plaza,
Hong Kong

Messeturm,
Frankfurt

Mercedes,
Mnchen

6
Curtain Wall

Burj
Dubai

Mandela Rhodes Project, South Africa:


Mounting of a curtain wall faade using HCW-B2 brackets on
HTA Anchor channels

2009 HALFEN - B 09 - E - www.halfen.com

Accessories

Sage Music Centre, Gateshead, UK

63

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
Selection of HALFEN Cast-in Channels depending on Load Condition

Load conditions and required HALFEN cast-in channels

Normal ceiling slab thicknesses with normal tensile and transverse tensile loads
HALFEN channels with bolt anchors and/or I-weld-on anchors

cia

lly

oZ
p. N
Ap

HALFEN bolts

Hot rolled toothed channels and bolts

.4 - 21

91
16

ed

HTA / HZA channels

ov
appr

HGB channels

3
Thin slabs with high transverse tensile
loads and a small edge distance
HALFEN curtain wall - channel
HCW 5234
(not included in the HTA-Approval)

HCW 52/34 and bolt


HS 50/30, M16, M20
grade
Gte 8.8

HTU channels

See page 12 + 13

HCW 52/34

Roof and Wall


Curtain Wall

125

61

34

52
22

See page 66 + 67
Hot rolled toothed channels with rebar
anchors and bolts

Thin slabs with high tension loads


HALFEN channels HTA-R or HZA-R
with rebar anchors
(not included in the HTA- and
HZA-Approval)

Accessories

See page 68

64

2009 HALFEN - B 09 - E - www.halfen.com

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
Selecting of HALFEN Cast-in Channel for each Load Condition

Load condition and required HALFEN channels


lly

Z
No
p.
Ap

1.4
-2

34

app

r ov

HTA / HZA channels

1
cia

ed

Plain hot rolled channels and bolts

Plain cold formed channels and bolts


HS 38/17
M12, M16

HS 40/22
M12, M16

HTA 38/17

HTA 40/25

HS 50/30
M12, M16, M20

Bolt HSR according to


expert report

2
22

22

119

60

51

HALFEN bolts

54

30

49

25

40
18

33

HTA 54/33

68

18

17

38

HTA 49/30

HGB channels

0,5 FRes.

4
HTU channels

0,5 FRes.

Roof and Wall

5
Liberty Life Project South Africa

2009 HALFEN - B 09 - E - www.halfen.com

18

54

22

22

Curtain Wall

HTA-R 54/33

49

7
Accessories

17

18

HTA-R 49/30

33

40

330

HTA-R 40/25

38

30

HTA-R 38/17

150

22

22

30

52

HS 40/22
M12, M16

220

HTA-R 52/34

50

34

HTA-R 50/30

330

150

18

22

40

220

HTA.-R 40/22

HS 50/30
M12, M16, M20

HS 38/17
M12, M16

25

HS 50/30
M12, M16, M20

HS 40/22
M12, M16

Plain cold formed channels with rebar anchors and


bolts

150

Plain hot rolled channels with rebar anchors and bolts

65

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
HALFEN Cast-in Channel HCW 52/34

Typical installation

Product describtion

HTA / HZA channels

Curtain wall mullion

Identification:
Material:

Bracket (example)

HCW 52/34
hot-dip galvanised

HALFEN Curtain Wall channel HCW 52/34

HALFEN bolt
Grade 8.8 (Order separately)

Concrete slab

HALFEN bolts

HGB channels

3
Dimensions in mm
Reinforcement requirements

Channel dimensions and positioning

HALFEN bolt Grade 8.8


HS 50/30

HTU channels

9 bars Diam. 8 mm at 100 mm - centres

Roof and Wall

Curtain Wall

Accessories

7
Dimensions in mm.
Modifications reserved.
Note: HALFEN channel HCW 52/34 is not
included in the HTA-/HZA-Approval.

66

3 bars
Diam. 8 mm
at 100 mm - centres

2009 HALFEN - B 09 - E - www.halfen.com

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
HALFEN Cast-in Channel HCW 52/34

Channel load data

FV ultimate

HTA / HZA channels

The following average ultimate loads were determined from three


tests:

FRes.

Load deformation diagram

= 142.3 kN

FN ultimate

= 47.4 kN
= 150.0 kN

Load Fres.

The adjacent load deformation diagram may be used to determine


allowable loads based on acceptable displacement and the required
safety factor according to local building codes. The diagram is based
on the following:
Tensile and transverse loads were increased at a ratio of 1:3 up to
the breaking point.
Concrete slab thickness 125 mm and reinforcement as shown on
previous slab.
Concrete strength class C 20/25 N/mm.
The load is transferred into the channel via two HALFEN bolts HS
50/30 M20 Grade 8.8. The bolt spacing is 150 mm. A sample
calculation is shown below. The safety factor is chosen arbitrarily.
However, the actual factors to be used must be analyzed based on
general project-specic conditions or building regulations in eect.

[kN]

Fres, ultimate = 150 kN

150
140

HALFEN bolts

1st crack appearing in


the concrete

130
120
110
100
90

3
HGB channels

1 = 4.12

FRes,ultimate

80

= 3 (ultimate test
70

=
=
=

60

142.3 kN
47.4 kN
150.0 kN

50

20

Perm. load with = 3 against average ultimate load from the tests:
perm. FV
=
142.3 / 3
= 47.4 kN
perm. FN
=
47.4 / 3
= 15.8 kN
perm. Fres
=
150 / 3
= 50.0 kN

10
0

= 35 kN < 47.4 kN
= 10 kN < 15.8 kN
=
= 36.4 kN < 50 kN

Displacement r [mm] in load direction Fres.

Roof and Wall

Control: Working load FV


Working load FN
Working load Fres

40
36. 4
30

Actual working loads at the bolts (specification by faade stress analyst):


Transverse tensile stress
FV = 35 kN
Tensile stress
FN = 10 kN

HTU channels

Calculation example: Assumed safety factor


load / working load)
Average ultimate load from the tests:
Transverse tensile stress
FV ultimate
Tensile stress
FN ultimate
Res. diagonal tensile load
Fres,ultimate

Displacement at working load < 1 mm (s. diagram).


Actual safety factor for average ultimate load 1 = (150 / 36.4) = 4.12

Associated HALFEN bolts HS 50/30

Model selection HALFEN bolts HS 50/30 GV Grade 8.8


Material
grade

Perm. bending
moment

[mm]

Permissible
resulting bolt
load (all directions)
perm. Fs [kN]

Available length
L

Recommended
initial torque
[Nm]

[Nm]

M 16

8.8

40, 60, 80, 100

36.1

111

200

M 20

8.8

45, 60, 80, 100

56.4

216

400

2009 HALFEN - B 09 - E - www.halfen.com

7
If the bolt is stressed in the direction of
an elongated hole, its load capacity must
be verified taking into account the bolt
flexure.
see page 31.

Accessories

Thread

6
Curtain Wall

considered equivalent to a hot-dip galvanised design. Other


bolt sizes and materials can be supplied. Please contact us for
detailed information.

Depending on the load size, we recommend the use of HALFEN bolts HS 50/30 M16 and/or M20, grade 8.8 in combination with the HALFEN cast-in channel HCW 52/34. The
bolt sizes mentioned below are manufactured in galvanised
design with a special coating. For interior use this design is

67

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S

Design dimension basics

HTA / HZA channels

HALFEN Cast-in Channels with Rebar Anchor HTA-R and HZA-R

Shear VyEd
Tension NEd
res. Tension FEd

Material resistance

Shear Material Resistance


Tension Material Resistance
Resultant Tension Material Resistance

VyRd
NRd
FRd

Design load

VyEd
NEd
FEd

H A L F E N c a s t - i n c h a n n e l s H TA - R a n d H Z A - R - M a t e r i a l d e s i g n r e s i s t a n c e v a l u e s
40

54

49

12

34

23

150

150

12

14

52

20

17

HTU channels

12

330

30

22

38

29

38

14

330

50

40

33

30

25

HGB channels

Structural analysis

220

HALFEN bolts

The minimum edge distance shown in the table apply to reinforced


concrete

Roof and Wall

5
HALFEN cast-in channel Type

Concrete strength grade


C20/25
fck,cyl. = 20 N/mm
fck,cube = 25 N/mm

Curtain Wall

Accessories

FRd [kN]
ae [mm]

HTA-R 38/17

HTA-R 40/25
HTA-R 40/22
HZA-R 29/20

HTA-R 49/30
HTA-R 50/30
HZA-R 38/23

HTA-R 54/33
HTA-R 52/34

350 mm
3 anchors

350 mm
3 anchors

350 mm
3 anchors

350 mm
3 anchors

2 7,0

2 9,1

2 14,0

2 24,5

VyRd [kN]

ar [mm]
50

40

2 2,4

60

45

2 3,7

70

50

2 4,9

75

50

2 5,6

Material:
hot-dip galvanised

channel

Steel S235JR , Steel S275JR , Steel S355MC

anchor

BSt 500S

Material:
stainless steel

channel
anchor

1.4571 / 1.4401 / 1.4404


BSt 500S

Not available for HALFEN channels HZA-R 29/20


Notes: Other channel lengths from 150 - 6070 mm available,
Note: HALFEN channels HTA-R / HZA-R are not included in the HTA- / HZA-Approval.

68

2009 HALFEN - B 09 - E - www.halfen.com

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
Edge of Slab Brackets HCW-ED

Application example
HALFEN Edge of slab brackets are connected in pairs to either side of the mullion and are available in two types:
Type HCW-ED brackets are designed to support both
vertical and horizontal loads.
Type HCW-EW brackets are designed to support
horizontal wind loads only.

bolt distance

HALFEN bolts

The brackets ensure a convenient adjustability of the attachment.


The HALFEN bolts (fastening of the bracket to the
HALFEN cast-in channel) and the regular hexagonal bolts
M12,(fastening of the bracket to the faade pillar) should be
of the strength grade 8.8.
A round auxiliary hole in the long leg of the brackets serves
the temporary attachment - e.g. by means of self-tapping
screws to the pillar- until the actual connection is established.

F hd
+
2

3
HGB channels

F hd
2
To guarantee a correct assembly, the HCW-ED brackets are
marked R for right, L for left and UP for above.

4
HTU channels

The brackets are made of high-quality aluminium material.


Special nylon discs are placed between bracket and pillar at
the "Wind load" - Bracket HCW-EW to reduce the friction.

HTA / HZA channels

Bracket dimensions [mm]

HCW-ED Brackets

HCW-EW Brackets

for taking up the dead loads


and wind loads

wind loads only

5
Roof and Wall

Curtain Wall

Toothed washers included in shipment

Size

Bracket code

small

HCW-ED 1
HCW-EW 1

108

70

114

10

57

64

25

51

36

40

57

medium

HCW-ED 2
HCW-EW 2

133

70

127

10

64

64

51

51

36

40

82

large

HCW-ED 3
HCW-EW 3

159

70

140

10

70

64

76

51

36

40

108

2009 HALFEN - B 09 - E - www.halfen.com

7
Accessories

Toothed washers included in shipment

69

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
Design Loads using two HCW-ED Brackets

HALFEN bolts

Interaction diagram Type HCW-ED1 (small)


Design value of the vertical applied load Fvd [kN]

HTA / HZA channels

Roof and Wall

Curtain Wall

Accessories

+ F hd
2

+ F hd
2

Fvd
2

Fvd
2

Denition of the loads at the


bracket / post connection

Interaction diagram Type HCW-ED2 (medium)


Design value of the vertical applied load Fvd [kN]

HTU channels

required connection bolt


M12 Grade 8.8

Design value ot the horizontal applied load Fhd [kN]

Permitted load
interaction area

required connection bolt


M12 Grade 8.8

3.5

7.0

Design value ot the horizontal applied load Fhd [kN]

Interaction diagram Type HCW-ED3 (large)


Design value of the vertical applied load [kN]

HGB channels

Calculation basis

required connection bolt


M12 Grade 8.8

Design value ot the horizontal applied load Fhd [kN]

70

2009 HALFEN - B 09 - E - www.halfen.com

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
Design Loads using two HCW-EW Brackets, Forces in the HALFEN Bolts

Calculation basis

1
HTA / HZA channels

Max. applied design load Fhd [kN]


Size
Bracket code
max. Fvd [kN]
small
0
HCW-EW 1
medium
0
HCW-EW 2
large
0
HCW-EW 3
HCW-EW Brackets are for carrying wind loads only.

Sy
max. Fhd [kN]
8.5
11.67
13.96

Sx

The components of the design reaction forces in the HALFEN bolts at the connection
location Curtain wall - bracket and HALFEN cast-in channel are calculated by multiplying the design loads Fvd and Fhd at the connection location curtain wall bracket and
faade post with the factors sx, sy and sz. The factors are dependent on the bracket
geometry, the load direction and the bolt position. (see Fig. to the right). The following
table shows the multiplication factors for determining the design -reaction forces in the
HALFEN bolts.
Lower mounting position of the HALFEN bolt (Position 3)
Dead load
Wind load
Si = (Fvd / 2) si
Si = (Fhd / 2) si

Sz

Denition of the loads at the


-bracket / post connection
-bracket / channel connection

sx

sy

sz

sx

sy

sz

sx

sy

sz

0,5

3,2

-1,0

-1,0

1,0

0,0

-0,3

3,0

-0,7

HCW-ED 2
HCW-ED 3

0,5
0,5

3,6
4,0

-1,0
-1,0

-0,5
-0,4

1,0
1,0

0,0
0,0

0,0
0,1

3,3
3,5

-0,7
-0,7

0,6
0,6

1,3
1,6

-1,0
-1,0

-1,0
-0,5

3,6
3,1

0,0
0,0

-0,3
0,0

3,4
3,4

-0,7
-0,7

HCW-ED 3

0,6

1,9

-1,0

-0,4

2,9

0,0

0,1

3,4

-0,7

Upper mounting
position of the
HALFEN bolt
(Position 1)

Upper mounting position of the HALFEN bolt (Position 1)


HCW-ED 1
HCW-ED 2

Lower mounting
position of the
HALFEN bolt
(Position 3)

Combined load 45
Si = (res. Fd / 2) si

Bracket
HCW-ED 1

HGB channels

res.Fd
2

Forces acting on the T-head bolts at the channel

F vd
2

HTU channels

F hd
+
2

HALFEN bolts

Design wind loads Type HCW-EW

Calculation example
slab thickness = 200 mm,
width of mullion = 80 mm
projection a = 80 mm p. 69
Design dead load
Design wind load (wind suction)

Fvd = + 3.5 kN
Fhd = + 7.0 kN

Upper mounting position (Position 1)


Sx = (3.5/2) 0.6 + (7/2) (-0.5) =
Sy = (3.5/2) 1.6 + (7/2) 3.1 =
Sz = (3.5/2) (-1.0) + 0 =

5
- 0.70 kN
+ 13.65 kN
- 1.75 kN

Resultant bolt load

Determination of the design reaction forces in a HALFEN bolt


Lower mounting position (Position 3)
Sx = (3.5/2) 0.5 + (7/2) (-0.5) =
- 0.88 kN
Sy = (3.5/2) 3.6 + (7/2) 1.0 =
+ 9.80 kN
Sz = (3.5/2) (-1.0) + 0 =
- 1.75 kN

per bolt

determining factor for the bolt selection


SELECTED HALFEN CHANNEL:
HTA-R 50/30 - 350 - 3 Anchor - fv

page 68

with VyRd = 2 5.6 kN > 2 Sz = 2 1.75


(ar 75 mm)
FRd = 2 14.0 kN > 2 res. Sd = 2 13.78 kN

Control: bolt spacing: P =80+236=152mm


SELECTED HALFEN BOLT:

Resultant bolt load

HS 50/30 - M12 60 gv 8.8


per bolt

Requirement as per interaction diagram page 70

2009 HALFEN - B 09 - E - www.halfen.com

6
Curtain Wall

HALFEN Bracket Type HCW-ED 2


possible projection M = 82 25 mm
Interaction diagram Type HCW-ED 2
( p. 70) shows that the given loading is within
the permitted load interaction area

Accessories

Selected:

Roof and Wall

Given:

71

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
Top of Slab Brackets HCW-B1

Support brackets for horizontal and vertical loads

HTA / HZA channels

Typical installation

Posts of the
curtain wall - faade

2
HALFEN bolts

Concrete slab

HGB channels

HTU channels

HALFEN cast-in channel

posts, the faade designer must provide a static verification


of the connection.The connection of the base bracket to the
HALFEN cast-in channel is established using HALFEN bolts
M16 Grade 8.8 (order separately). The connection between
the connecting plate and the base bracket can be made
laterally movable or as a fixed point depending on the faade
type.

HALFEN brackets HCW-B1 for the assembly on the top face


of the slab are available in two load levels and three collar
dimensions. The brackets are made of steel of the quality
grade S355 and are galvanised.
The vertical adjustability is 10 mm. In combination with
HALFEN channels HTA, three dimensional adjustability is
ensured. The lateral connecting plates are screwed to the
faade posts using M8 screws (not included). Concerning the

Roof and Wall

Design load ranges

Load
range[kN]

dead load Fvd


[kN]

wind load Fhd [kN]


(suction + compression)

4/12

12

7/24

24

Curtain Wall

Fvd , Fhd : Acceptable design loads with a partial safety factor F = 1.35 for dead load and
F = 1.5 for wind load.

Type selection
Load
range[kN]

7
Accessories

4/12

7/24

a
[mm]

Designation

L
[mm]

W
[mm]

HALFEN
channel

Rec. HALFEN
bolt

50

HCW-B1 - 4/12-50

270

150

75

HCW-B1 - 4/12-75

295

150

100

HCW-B1 - 4/12-100

320

150

HTA 40/22250
2 Anchors

HS 40/22
M1660
8.8

50

HCW-B1 - 7/24 -50

270

175

75

HCW-B1 - 7/24 -75

295

175

100

HCW-B1 - 7/24 -100

320

200

HTA 50/30300
3 Anchors

HS 50/30
M1660
8.8

Recommended HALFEN channel with full utilisation of the bracket load capacity

72

2009 HALFEN - B 09 - E - www.halfen.com

H A L F E N C U R TA I N WA L L S U P P O R T S Y S T E M S
Top of Slab Brackets HCW-B2

Brackets for horizontal and vertical loads

HTA / HZA channels

1
Typical installation
Posts of the
curtain wall - faade

2
HALFEN bolts

Concrete slab

Roof and Wall

Fvd [kN]

6
Curtain Wall

Design value of the vertical applied load

required HALFEN bolt at


channel
HS 50/30 M1660 gv 8.8

HGB channels

connection.
The connection of the base brackets to the HALFEN cast-in
channel is established using HALFEN bolts M16 Grade 8.8
(order separately). The connection between the connection
plate and the base bracket can be made laterally movable or
as a fixed point depending on the faade type.

HALFEN brackets HCW-B2 are made of steel of the quality


grade S355 and are galvanised. The vertical adjustability is
24 mm. In combination with HALFEN cast-in channels HTA,
three dimensional adjustability is ensured.
The lateral connecting plates are screwed to the faade posts
using M12 screws (not included). Concerning the posts,
the faade designer must provide a static verification of the

HTU channels

HALFEN cast-in channel

Design value ot the horizontal applied load Fhd [kN]

Allowable load
interaction area

Accessories

2009 HALFEN - B 09 - E - www.halfen.com

73

A C C E S S OR I E S
Nuts, Washers

HTA / HZA channels

MU
Hexagonal nuts
DIN EN ISO
4032/DIN 934

galvanised
F.k.8
Thread

GV

A4
Stainless
steel A4
Thread

M 6

M 6

M 8

M 8

M 10

M 10

M 12

M 12

HALFEN bolts
HGB channels
HTU channels

Roof and Wall

Curtain Wall

Accessories

VUS 40/25
for Profile
40/25;
HZA
41/22
VUS 49/30
for Profile
54/33,
49/30

VUS 52/34
for Profile
52/34,
50/30

VUS 72/49
for Profile
72/48,
72/49

VUS 41/41
for all
41er
Profiles

[mm]

[mm]

[mm]

10/5

10/6

11.5

GV

US

15.0

Washers
DIN EN ISO DIN
7093/DIN
440
9021 if so
9021
DIN 440

17/8

16/ 9.5 19.6

19/10

18/12

galvanised
for bolt
M 6

M 10

30

10.5

2.5

21.9

440

M 12

45

13.5

M 12

M 12

37

13

M 16

50

17

72

22

M 16

41.5

440

M 20

S/m
EN
[mm]

[mm]

M 8

13/6.5 13/7.5

M 10

17/08 16/ 9.5 19.6

M 12

M 12

19/10

M 16

Ordering example: US - M 12 - GV -DIN 9021

18/12

M 10

9021

DIN

[mm]

9021

34.6

[mm]

[mm]

8.4

30/16
S/m

[mm]

6.6

24/13 24/15.5 27.7

A2
Stainless
steel A2
Thread

24

M 20

36/22

22

M 16

36/19

M 8

M 20

30/19

A4
Stainless
steel A4
for bolt

M 8

M 16

Square washers

ISO

9021

FV
hot-dip
galvanised
Thread

VUS

S/m

DIN

13/6.5 13/7.5

M 24

S/m

15.0
21.9

US
Washers
DIN EN
ISO 7089/
DIN 125

24/13 24/15.5 27.7

GV

A4

galvanised for
bolt

Stainless
steel A4
for bolt

[mm]

[mm]

[mm]

M 6

M 6

12

6,4

1,6

M 8

M 8

16

8,4

1,6

M 10

M 10

21

10,5

M 12

M 12

24

13

2,5

FV

A4

axbxd

M 16

M 16

30

17

hot-dip galvanised for bolts:

Stainless steel
A4 for bolts:

[mm]

M 20

M 20

37

21

M 24

M 24

M 10

M 10

40 x 40 x 5

M 12

M 12

40 x 40 x 5

M 16

M 16

40 x 40 x 5

M 10

M 10

37 x 37 x 5

M 12

M 12

37 x 37 x 5

M 16

M 16

37 x 37 x 5

M 20

M 20

37 x 37 x 5

M 16

M 16

50 x 50 x 6

M 20

M 20

50 x 50 x 6

M 20

M 20

54 x 54 x 6

M 24

M 24

54 x 54 x 6

M 27

M 27

54 x 54 x 6

M 30

M 30

54 x 54 x 6

44

25

M 27

50

28

M 30

56

31

FV

A2
D
d
Stainless
hot-dip galvanisteel A2
[mm]
[mm]
sed for bolt
for bolt
M 8
17
8,4
M 10
M 10
21
10,5
M 12
M 12
24
13
M 16
M 16
30
17
Ordering example: US - M 12 - GV - DIN 125

SIC

Locking
washer

GV

A4

galvanised

stainless steel A4

s
[mm]
1,6
2
2,5
3

Suitable for HALFEN


bolts
Type

Dimensions

SIC - 50/30 - gv SIC - 50/30 - A4

50/30

M16, M20

SIC - 40/22 - gv SIC - 40/22 - A4

38/17
40/22

M16

SIC - 38/23 - gv SIC - 38/23 - A4

38/23

M16

SIC - 29/20 - gv SIC - 29/20 - A4

29/20

M12
M12, M10

M 6

M 6

40 x 40 x 6

SIC - 38/17 - gv SIC - 38/17 - A4

38/17
40/22

M 10

M 10

40 x 40 x 6

SIC - 28/15 - gv SIC - 28/15 - A4

28/15

M8, M10

M 12

M 12

40 x 40 x 6

SIC - 20/12 - gv SIC - 20/12 - A4

20/12

M8

Ordering example: VUS 52/34 - FV - M 20

Area of application VUS:


for shimming non-flush
installations.

Shimming

Ordering example: SIC - 38/17 - GV

Area of application SIC:


For securing HALFEN bolts
against reverse torsion
during installation.

Assembly scheme:
HALFEN
channel
HALFEN bolt
Locking
washer SIC

74

2009 HALFEN - B 09 - E - www.halfen.com

A C C E S S OR I E S
Threaded rods, Hex bolts, Coupler sleeves, Ring nuts

[kN]

[kN]

M 6

1000

3.1

2,2

M 6

Thread
M 6

M 8

M 8

1000

5.6

4,0

M 8

M 8

M 10

M 10

1000

9.0

6,4

M 10

M 12

M 12

1000

13.0

9,3

M 16

M 16

1000

24.2

17,3

M 20

M 20

1000

37.8

27,0

1000

54.3

38,8

M 24

FRd

perm.F

gv

Coupler sleeves, round

A4
stainless
steel A4

FRd

perm.F

[mm] [mm]

[kN]

[kN]

10/10

15

3.1

2.2

12/14

20

5.6

4.0

M 10

13/16

25

9.0

6.4

M 12

M 12

16/20

30

13.0

9.3

M 16

M 16

21/25

40

24.2

17.3

M 20

M 20

26/32

50

37.8

27.0

FRd

perm.F

[kN]

[kN]

galvanised
Thread

Ordering example: VBM - A4 - M 16

Ordering example: GWS - M 12 1000 - GV

HSK
Hexagonal head
bolts
DIN EN ISO 4017/
DIN 933
(without nuts)

gv 8.8
galvanised
F.K. 8.8
Dimensions
M 6 x 12

A4

Stainless steel A4

DIN

EN ISO

Dimensions

[mm]

[mm]

10

10

Hexagonal coupler sleeves with


view holes

M 6 x 25
M 8 x 25

M 8 x 25

13

M 8 x 40

FV

SKM

13

A4

M 10

stainless
steel A4
Thread
M 10

13

40

9,0

6,4

M 12

M 12

17

40

13,0

9,3

M 16

M 16

22

50

24,2

17,3

hot-dip gal.
Thread

[mm] [mm]

Ordering example: SKM - FV - M 12

M 10 x 20
M 10 x 45

17

16

M 10 x 60

SPH

M 10 x 70

Turnbuckles
with rightand left-hand
thread

M 12 x 22
M 12 x 25

M 12 x 25

M 12 x 30

M 12 x 30

M 12 x 40

M 12 x 40

19

18

M 12 x 50

Hex bolts are used


in combination with
HALFEN threaded
plates

HJV
Adjustment
coupler

A4

A4

Stainless steel A4 Stainless steel A4


Thread M 12
Thread M 16
Length L [mm] Length L [mm]

for
M12
[mm]

for
M16
[mm]

M12 60

M16 60

16

22

M12 75

M16 75

16

22

M12 95

M16 95

16

22

M 12 x 60

M 12 x 60

M12 115

M16 115

16

22

M 12 x 80

M 12 x 80

M12 135

M16 135

16

22

M 16 x 40

M 16 x 40

perm. F = 5 kN
FRd = 7 kN

perm. F = 10 kN
FRd = 14 kN

M 16 x 60

M 16 x 60

M 16 x 90

M 16 x 90

M 12 x 90

FV
hot-dip
gal.
Type

Stainl. A4

A4

2
3

Type

24

[mm] [mm] [mm]

24

max FEd per.F


[kN]

[kN]

f= min. screw
depth
M12 = 10mm
M16 = 13 mm

RM
Ring nut
DIN 582

4
HTU channels

M 10 x 30

M 10 x 45

Ordering example: SPH - A4 - M 12 x 75

gv

FRd

perm. F

C 15E, galv. hot-dip


gal.Thread

[mm]

[kN]

[kN]

40

13

2.1

1.5

M 8

20

2.0

1.4

50

17

4.6

3.3

M 10

25

3.2

2.3

10

50

17

7.0

M 12

30

4.8

3.4

M 16

35

9.8

7.0

M 20

40

16.8

12.0

6
Curtain Wall

M 10 x 30

1
HTA / HZA channels

[mm]

M 6

Length

HALFEN bolts

A4
stainless steel
A4
Thread

HGB channels

Threaded rods
DIN 976-1

VBM

gv
galvanised
FK 4.6
Thread

Roof and Wall

GWS

Ordering example: RM - GV - M 12

7
Accessories

Recommended design value of the load


capacity with a centric tensile stress
Recommended design value of the action
Cross section

2009 HALFEN - B 09 - E - www.halfen.com

75

A CC E S S OR I E S
Rail Clips

HTA / HZA channels

HALFEN bolts

KLP - S Rail clips, S235JR (St 37-2) forged


FV
hot-dip
galvanised

Heel width
n

Type
[mm]
Nr. 10
16
Nr. 26
without heel
Nr. 20
20
Nr. 30
without heel
22
Nr. 40
without heel
Nr. 50
Ordering example: KLP - S -

for HALFEN
bolts
x l [mm]
M 16 x 60
M 16 x 60
M 20 x 65
M 20 x 65
M 27 x 75
M 27 x 75
Nr. 26 - FV

all. load

Dimensions
[mm]
a
44,0
62,5
50,0
62,5
62,5
62,5

b
45
64
52
64
64
64

c
12
21
18
21
21
21

d
18
18
22
22
29
29

h
5
9
8
9
9
9

preferred for use with


Other beam,
flange thickchannels
ness channels
t [mm]
80 - 140
4-6
160 - 240
7 -9
S 24, A 45, A55
160 - 240
7-9
S24 - S49

at all.
= 125 N/mm
k
12,0
16,5
15,0
16,5
16,5
16,5

m
22,0
34,5
22,0
34,5
32,5
32,5

Normal
profile I

F [kN]
3,5
3,5
10,0
10,0
10,0
10,0

160 - 240

A - 45
A - 55
A - 65

7-9

Size being discontinued

Load diagram:
KLP - S

HGB channels

Assembly example
KLP - S

By engaging in the channel slot,


the rail clip with heel is secured
against torsion.

HALFEN channel
heel

HTU channels

FV
hot-dip galvanised
60/10
60/12
60/14
60/16
60/18
60/20

Clamping
height
h [mm]
10
12
14
16
18
20

Preferred for use with

all. load
[kN]

Normal profile I

F1 = 7,0
HALFEN bolt
M 16 x 60, Grade 4.6

120 - 160
220 - 240
240 - 280
300 - 340
360 - 380
400 - 450

F2 = 11,25
HALFEN bolt
M 16 x 60, Grade 8.8

Normal profile IPB Crane and/or running tracks


100
140
160 - 180
200 - 220
240 - 260
280 - 300

A65, S 33, S 41
A100, S 49, A75
A120, S 54
S 64

Consider load capacity of HALFEN channels (Observe the lever arm conditions when selecting the HALFEN channels and bolts)
Check flange thickness of profile!

Bolt M 16 x 80 necessary

Load diagram
KLP - 60

LL 24 x 18

60

18

Roof and Wall

KLP - 60 rail clips (formerly DIN 3568)

F2

F1

6
Curtain Wall

75
HALFEN framing
channel

HALFEN bolt
e.g. HS 50/30
Washer
e.g. US DIN 125

Assembly example
KLP - 60

HALFEN rail clip


e.g. KLP

7
Accessories

HALFEN framing channel


e.g. HL 50/40

e.g. HL 50/40

HALFEN channel nut


e.g GWP 50/40
Threaded rod with
locking nut and square
washer VUS

76

2009 HALFEN - B 09 - E - www.halfen.com

A C C E S S OR I E S
Framing Channels HM/HL/HZL Type Overview

HZ

HZ

HM

/2
38

HZ

/2
41

41

/2 2

HM 52/34

HM 50/30

HM 40/22

HZM 38/23

-D

/15

28

/6

HM
HM 72/48

HTA / HZA channels

L4
HL

HZM 29/20

63
ZL

/15

422

HALFEN bolts

HL

1/4

/1
28

40

28

HZL 63/63

HM/HL 50/40

486

18

18

14

22

26

40

63

23

23

22

22

48

29

20

33

38

40

30

34

48

50

18

22

22

50

52

22

HGB channels

63

72

for use in combination with


medium heavy profiles

HM 41/41-D

HS 40/22

HM/HL 41/83

HZS/HS
38/23

HM/HL 41/62

HZS/HS
29/20

HM 41/62-D

HS 50/30

HM/HL
HZM/HZL
41/22

* Only HM/HL 41/41

HM 41/22D
HZM 41/22D

HS 40/22

HLL 41/41

HLL 41/22

* Only HM/HL 41/22

41

41

41

41

22

22

22

22

22

* Nur

22

22

41
22

21

21

42

41

41

41

124

62

83

41

41

83

41

4
HTU channels

HM/HL
HZM/HZL
41/41

HS 50/30

Roof and Wall

HS 72/48

* Nur

HM/HL 41/41

HM/HL 41/22

22

18

12

12

30

28
12

16

Materials/Finish:

20
10

12

28

26

HM/HL
20/12

FV =

Steel S235JR
hot-dip galvanised or mill finish

SV =

Steel S235JR
sendzimir galvanised

A4 = Stainless steel
1.4571/1.4404/1.4401

Accessories

18

17

36

28
38

HM/HL
315

15

36

HM/HL
28/15

15

HM/HL
26/26

HM/HL
28/28

HM
38/17

26

HM/HL
36/36

A2 = Stainless steel 1.4301


HS 38/17

2009 HALFEN - B 09 - E - www.halfen.com

HS 28/15

GWP 28/15

HS 20/12

Curtain Wall

HS 41/41

HCR = Stainless steel


1.4547/1.4529

77

HA LF E N F R A MING CHANNE LS
Framing Channels HM/HL/HZL, Application Examples

HTA / HZA channels

HALFEN framing channels HM/HZM and HALFEN framing channels perforated HL can be attached to the substructure in
various ways:
-

HALFEN bolts

fastened to concrete or masonry with wedge anchors HB-BZ


screwed to HALFEN cast-in channels Type HTA and/or HZA
attached to threaded rods
clamped to profile steel supports
welded to steel components
screwed or nailed to wooden structures

HGB channels

3
4

HTU channels

Typical use of the HALFEN framing systems

The HALFEN framing channels are a


part of the HALFEN framing systems:
Mountings for plant construction,
technical building equipment, heavy
and light installations.

Roof and Wall

Y will find the product


You
rrange for framing system
aapplications in the
Catalogue MT.
C

Curtain Wall

Accessories

78

2009 HALFEN - B 09 - E - www.halfen.com

APPENDIX
Index

Adjustment coupler HJV


ANK-E end anchor for HALFEN channels HTA

Page:
74 - 78
75
15

BL, BLQ brick tie anchor


Brick tie anchor ML, BL
Brick tie channel HMS

54
52 - 55
52

Accessories

Cold-formed cast-in channels HTA, HZA


Corner guard HKW
Corner pieces for HALFEN cast-in channels
Corrosion protection HALFEN channels & bolts
Coupler sleeves VBM, SKM
Curved HALFEN cast-in channels HTA, HZA
Dowels

12
60
16
8-9
75
16

DYNAGRIP HALFEN cast-in channels


Dynamic Loads for HALFEN cast-in channels

53
12
22

End anchor ANK-E for HALFEN channels HTA

15

Firewall mount
Fixed standard lengths for HALFEN channels HTA,HZA
Framing channels
GWP threaded plate
HALFEN bolts
HALFEN cast-in channels
HALFEN framing channels
Handrail connections HGB
HCR stainless steel HALFEN channels, - bolts
HCW Curtain Wall System
Hexagonal coupler SKM
Hexagonal nuts, -bolts
HGB handrail connection systems
HJV adjustment coupler
HKW HALFEN corner guard
HKZ restraint tie, toothed
HL framing channels, perforated
HM framing channels
HMS brick tie channels
HNA timber fixing straps
Hot rolled profiles HTA
HS HALFEN bolts
HSF rafter shoe
HSR HALFEN bolts with nib
HTA HALFEN cast-in channels
HTU profiled metal sheets fixing channels

55
14
77 - 78
32
27 - 32
12
77 - 78
33 - 42
12
61 - 73
75
74
33 - 42
75
60
57 - 58
77 - 78
77 - 78
52
50
12
27 - 32
51
27 - 32
12
43 - 48

HZA HALFEN cast-in channel DYNAGRIP


HZA HALFEN cast-in channel, toothed
HZM HALFEN framing channels, perforated
HZS HALFEN bolts, toothed

13
13
77
27 - 32

KLP rail clip

76

Locking washer SIC

74

ML, MLQ HALFEN brick tie anchor


Nuts MU

52 - 55
74

Perforated framing channels HL


Precast connection HVL
Profiled metal sheet fixing channel HTU
Profiles HM, HL

77 - 78
59
43 - 48
77 - 78

Rafter shoe HSF


Rail clips KLP
Restraint tie HKZ
Restraint with turnbuckle SPV
Ring nuts RM

51
76
57 - 58
56
75

Shock resistance
Short lengths & cut lengths of HALFEN channels
SIC locking nut
SKM coupler sleeve
SPH turnbuckles with right- and left hand thread
SPV restraint with turnbuckle
Square washers VUS

26
14
74
75
75
56
74

Threaded plates GWP

32
75
50
13
77
75

Threaded rods
Timber fixing
Toothed profiles HZA cast-in channels
Toothed profiles HZM, HZL framing channels
Turnbuckles with right- and left hand thread SPH

VBM coupler sleeve


VUS washer

75
74

Washer US, VUS

74

79

C ON TA C T H A L F E N WO RLDWIDE

HALFEN Gesellschaft m.b.H.


Leonard-Bernstein-Str. 10
1220 Wien

Phone: +43 - 1 - 259 6770


E-Mail: office@halfen.at
Internet: www.halfen.at

Fax: +43 - 1 - 259 - 6770 99

Belgium/Luxembourg

HALFEN-FRIMEDA N.V.
Borkelstraat 131
2900 Schoten

Phone: +32 - 3 - 658 07 20


E-Mail: info@halfen.be
Internet: www.halfen.be

Fax:

+32 - 3 - 658 15 33

China

HALFEN Construction Accessories Distribution Co.Ltd.


Room 601 Tower D, Vantone Centre
No.A6 Chao Yang Men Wai Street
Chaoyang District
Beijing P.R. China 100020

Phone: +86 - 10 5907 3200


E-Mail: info@halfen.com
Internet: www.halfen.cn

Fax:

+86 - 10 5907 3218

Czech Republic

HALFEN-DEHA s.r.o.
K Vypichu 986 Komerni zna Rudn, hala 6
25219 Rudn

Phone: +420 - 311 - 690 060


E-Mail: info@halfen-deha.cz
Internet: www.halfen-deha.cz

Fax:

+420 - 311 - 671 416

France

HALFEN S.A.S.
18, rue Goubet
75019 Paris

Phone: +33 - 1 - 445231 00


E-Mail: halfen@halfen.fr
Internet: www.halfen.fr

Fax:

+33 - 1 - 445231 52

Germany

HALFEN-DEHA Vertriebsgesellschaft mbH


Katzbergstrae 3
40764 Langenfeld

Phone: +49 - 2173 - 970 0


E-Mail: info@halfen.de
Internet: www.halfen.de

Fax:

+49 - 2173 - 970 225

Italy

HALFEN-DEHA S.r.l. Soc. Unipersonale


Via F.lli Bronzetti N 28
24124 Bergamo

Phone: +39 - 035 - 0760711


E-Mail: info@halfen.it
Internet: www.halfen.it

Fax:

+39 - 035 - 0760799

Netherlands

HALFEN b.v.
Vonderweg 5
7468 DC Enter

Phone: +31 - 547 - 3830 30


E-Mail: info@halfen.nl
Internet: www.halfen.nl

Fax:

+31 - 547 - 3830 35

Norway

HALFEN-FRIMEDA AS
Postboks 2080
4095 Stavanger

Phone: +47 - 51 82 34 00
E-Mail: post@halfen.no
Internet: www.halfen.no

Fax:

+47 - 51 82 34 01

Poland

HALFEN Sp. z o.o.


Ul. Obornicka 287
60-691 Poznan

Phone: +48 - 61 - 622 14 14


E-Mail: info@halfen.pl
Internet: www.halfen.pl

Fax:

+48 - 61 - 622 14 15

Spain

HALFEN-DEHA S.L.
c/ Fuente de la Mora 2, 2 D
28050 Madrid

Phone: +34 - 91 - 632 18 40


E-Mail: info@halfen.es
Internet: www.halfen.es

Fax:

+34 - 91 - 633 42 57

Sweden

HALFEN AB
Box 150
435 23 Mlnlycke

Phone: +46 - 31 - 98 58 00
E-Mail: info@halfen.se
Internet: www.halfen.se

Fax:

+46 - 31 - 98 58 01

Switzerland

HALFEN Swiss AG
Industriestrasse 32
8108 Dllikon

Phone: +41 - 44 - 849 78 78


E-Mail: mail@halfen.ch
Internet: www.halfen.ch

Fax:

+41 - 44 - 849 78 79

United Kingdom /
Ireland

HALFEN Ltd.
Humphrys Road Woodside Estate
Dunstable LU5 4TP

Phone: +44 - 1582 - 47 03 00


E-Mail: info@halfen.co.uk
Internet: www.halfen.co.uk

Fax: +44 - 1582 - 47 03 04

5.000 03/09

Austria

2009 Halfen GmbH, Germany


applies also to copying in extracts.

HALFEN is represented with subsidiaries in the following 14 countries, please contact us:

NOTES REGARDING THIS CATALOGUE


Technical and design changes reserved. The information in this publication is based on state-of-the-art technology at the time of publication. We reserve the right to make technical and design changes at any time. Halfen GmbH shall not accept liability for the accuracy of