Professional Documents
Culture Documents
METSiS
Mechanical Division
Description
Zone Peak Time
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
12.10.045 MRI
5pm December
44
3
131
-602
0
0.00
9,694
880
20.10
1,286
0
0
None
0
0
None
0
0
44
3
131
-602
0
0.00
9,694
880
20.10
1,286
0
0
0
0
0
0
5pm in December.
Clg: 33 DB, 30 WB, 26.54 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-602
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-602 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
11,773 Watts
880 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
455 Watts
12,228 Watts
1,286 Watts
13,514 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
880 L/s
0 L/s
44
20.0991
3.2411
0.3085
-13.75
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.60 kW
13.51 kW
11.4 Sq.m/Ton
0.0877 Tons/Sq.m
3.84 Tons
Description
Zone Peak Time
12.10.059
Preparation Area
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
15
3
46
-91
0
0.00
2,317
188
12.39
569
0
0
None
0
0
None
0
0
15
3
46
-91
0
0.00
2,317
188
12.39
569
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-91
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-91 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,762 Watts
188 L/s
0 L/s
0 L/s
97 Watts
2,859 Watts
198 Watts
371 Watts
0 Watts
569 Watts
3,428 Watts
Check Figures
Total Air Handler Supply Air (based on a 12 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
188 L/s
0 L/s
15
12.3838
4.4346
0.2255
-5.97
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.09 kW
3.43 kW
15.6 Sq.m/Ton
0.0641 Tons/Sq.m
0.97 Tons
Description
Zone Peak Time
12.10.047 MRI
Control Room
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
20
3
59
0
0
0.00
1,693
113
5.77
673
0
0
None
0
0
None
0
0
20
3
59
0
0
0.00
1,693
113
5.77
673
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
1,959 Watts
113 L/s
0 L/s
0 L/s
58 Watts
2,017 Watts
198 Watts
475 Watts
0 Watts
673 Watts
2,690 Watts
Check Figures
Total Air Handler Supply Air (based on a 14 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
113 L/s
0 L/s
20
5.7725
7.2483
0.1380
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
2.69 kW
25.5 Sq.m/Ton
0.0392 Tons/Sq.m
0.76 Tons
Description
Zone Peak Time
12.10.046 MRI
Technical
5pm February
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
14
3
41
-136
0
0.00
15,104
1,488
110.20
533
0
0
None
0
0
None
0
0
14
3
41
-136
0
0.00
15,104
1,488
110.20
533
0
0
0
0
0
0
5pm in February.
Clg: 33 DB, 30 WB, 26.54 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-136
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-136 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
18,617 Watts
1,488 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
768 Watts
19,385 Watts
198 Watts
335 Watts
0 Watts
533 Watts
19,919 Watts
Check Figures
Total Air Handler Supply Air (based on a 10 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
1,488 L/s
0 L/s
14
110.1958
0.6778
1.4755
-10.08
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.14 kW
19.92 kW
2.4 Sq.m/Ton
0.4195 Tons/Sq.m
5.66 Tons
Description
Zone Peak Time
12.10.0043
Mammogram
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
17
3
50
0
0
0.00
1,560
106
6.37
603
0
0
None
0
0
None
0
0
17
3
50
0
0
0.00
1,560
106
6.37
603
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
1,809 Watts
106 L/s
0 L/s
0 L/s
55 Watts
1,864 Watts
198 Watts
405 Watts
0 Watts
603 Watts
2,467 Watts
Check Figures
Total Air Handler Supply Air (based on a 14 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
106 L/s
0 L/s
17
6.3655
6.7300
0.1486
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
2.47 kW
23.7 Sq.m/Ton
0.0423 Tons/Sq.m
0.70 Tons
Description
Zone Peak Time
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
12.10.078 USG
3pm December
17
3
50
0
0
0.00
3,760
333
20.07
603
0
0
None
0
0
None
0
0
17
3
50
0
0
0.00
3,760
333
20.07
603
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
4,546 Watts
333 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
172 Watts
4,718 Watts
198 Watts
405 Watts
0 Watts
603 Watts
5,321 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
333 L/s
0 L/s
17
20.0646
3.1197
0.3205
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
5.32 kW
11.0 Sq.m/Ton
0.0911 Tons/Sq.m
1.51 Tons
Description
Zone Peak Time
12.10.014 DEXA
Room
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
20
3
61
0
0
0.00
1,954
139
6.80
695
0
0
None
0
0
None
0
0
20
3
61
0
0
0.00
1,954
139
6.80
695
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,282 Watts
139 L/s
0 L/s
0 L/s
72 Watts
2,353 Watts
198 Watts
497 Watts
0 Watts
695 Watts
3,048 Watts
Check Figures
Total Air Handler Supply Air (based on a 13 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
139 L/s
0 L/s
20
6.7940
6.6919
0.1494
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
3.05 kW
23.5 Sq.m/Ton
0.0425 Tons/Sq.m
0.87 Tons
Description
Zone Peak Time
12.25.030 Stress
Room
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
10
3
30
0
0
0.00
1,811
147
14.57
444
0
0
None
0
0
None
0
0
10
3
30
0
0
0.00
1,811
147
14.57
444
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,159 Watts
147 L/s
0 L/s
0 L/s
76 Watts
2,235 Watts
198 Watts
246 Watts
0 Watts
444 Watts
2,679 Watts
Check Figures
Total Air Handler Supply Air (based on a 12 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
147 L/s
0 L/s
10
14.5685
3.7701
0.2652
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
2.68 kW
13.3 Sq.m/Ton
0.0754 Tons/Sq.m
0.76 Tons
Description
Zone Peak Time
12.10.070 Stress
Room
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
10
3
30
0
0
0.00
1,802
147
14.84
439
0
0
None
0
0
None
0
0
10
3
30
0
0
0.00
1,802
147
14.84
439
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,149 Watts
147 L/s
0 L/s
0 L/s
76 Watts
2,225 Watts
198 Watts
241 Watts
0 Watts
439 Watts
2,664 Watts
Check Figures
Total Air Handler Supply Air (based on a 12 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
147 L/s
0 L/s
10
14.8332
3.7162
0.2691
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
2.66 kW
13.1 Sq.m/Ton
0.0765 Tons/Sq.m
0.76 Tons
Description
Zone Peak Time
10
12.10.082 Stress
Treadmill
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
21
3
62
0
0
0.00
2,298
174
8.41
703
0
0
None
0
0
None
0
0
21
3
62
0
0
0.00
2,298
174
8.41
703
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,709 Watts
174 L/s
0 L/s
0 L/s
90 Watts
2,799 Watts
198 Watts
505 Watts
0 Watts
703 Watts
3,502 Watts
Check Figures
Total Air Handler Supply Air (based on a 13 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
174 L/s
0 L/s
21
8.4087
5.9116
0.1692
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
3.50 kW
20.8 Sq.m/Ton
0.0481 Tons/Sq.m
1.00 Tons
Description
Zone Peak Time
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
13
12.10.081 X-Ray
3pm December
32
3
96
0
0
0.00
6,887
620
19.38
978
0
0
None
0
0
None
0
0
32
3
96
0
0
0.00
6,887
620
19.38
978
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
8,352 Watts
620 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
320 Watts
8,672 Watts
198 Watts
780 Watts
0 Watts
978 Watts
9,650 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
620 L/s
0 L/s
32
19.3827
3.3161
0.3016
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
9.65 kW
11.7 Sq.m/Ton
0.0857 Tons/Sq.m
2.74 Tons
Description
Zone Peak Time
12
12.10.012 Recovery
Injection
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
18
3
54
-91
0
0.00
2,781
230
12.70
639
0
0
None
0
0
None
0
0
18
3
54
-91
0
0.00
2,781
230
12.70
639
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-91
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-91 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
3,323 Watts
230 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
119 Watts
3,442 Watts
198 Watts
441 Watts
0 Watts
639 Watts
4,081 Watts
Check Figures
Total Air Handler Supply Air (based on a 12 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
230 L/s
0 L/s
18
12.7013
4.4348
0.2255
-5.01
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.09 kW
4.08 kW
15.6 Sq.m/Ton
0.0641 Tons/Sq.m
1.16 Tons
Description
Zone Peak Time
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
11
12.10.009 CT
10am December
38
3
114
-547
0
0.00
13,470
1,280
33.60
984
0
0
None
0
0
None
0
0
38
3
114
-547
0
0.00
13,470
1,280
33.60
984
0
0
0
0
0
0
11am in December.
Clg: 30 DB, 29 WB, 25.47 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 10am is
different from the total system peak time, hence the air system L/s was computed using a zone sensible load of 13,470.
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-547
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-547 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
16,474 Watts
1,280 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
661 Watts
17,135 Watts
198 Watts
891 Watts
0 Watts
1,089 Watts
18,224 Watts
Check Figures
Total Air Handler Supply Air (based on a 10 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
1,280 L/s
0 L/s
38
33.5957
2.0906
0.4783
-14.37
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.55 kW
18.22 kW
7.4 Sq.m/Ton
0.1360 Tons/Sq.m
5.18 Tons
Description
Zone Peak Time
14
12.10.053 Operator
Room
10am February
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
17
3
51
-285
0
0.00
9,241
893
52.86
547
0
0
None
0
0
None
0
0
17
3
51
-285
0
0.00
9,241
893
52.86
547
0
0
0
0
0
0
10am in February.
Clg: 29 DB, 28 WB, 23.43 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-285
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-285 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
11,350 Watts
893 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
461 Watts
11,811 Watts
198 Watts
349 Watts
0 Watts
547 Watts
12,358 Watts
Check Figures
Total Air Handler Supply Air (based on a 10 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
893 L/s
0 L/s
17
52.8583
1.3676
0.7312
-16.88
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.29 kW
12.36 kW
4.8 Sq.m/Ton
0.2079 Tons/Sq.m
3.51 Tons
Description
Zone Peak Time
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
15
12.25.002 Sub-Wait
3pm December
32
3
97
0
0
0.00
2,065
117
3.61
988
0
0
None
0
0
None
0
0
32
3
97
0
0
0.00
2,065
117
3.61
988
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,342 Watts
117 L/s
0 L/s
0 L/s
60 Watts
2,402 Watts
198 Watts
790 Watts
0 Watts
988 Watts
3,390 Watts
Check Figures
Total Air Handler Supply Air (based on a 16 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
117 L/s
0 L/s
32
3.6098
9.5581
0.1046
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
3.39 kW
33.6 Sq.m/Ton
0.0297 Tons/Sq.m
0.96 Tons
Description
Zone Peak Time
16
12.10.058 PET-CT
Room
10am February
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
36
3
108
-263
0
0.00
13,040
1,248
34.76
938
0
0
None
0
0
None
0
0
36
3
108
-263
0
0.00
13,040
1,248
34.76
938
0
0
0
0
0
0
10am in February.
Clg: 29 DB, 28 WB, 23.43 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-263
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-263 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
15,987 Watts
1,248 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
645 Watts
16,632 Watts
198 Watts
740 Watts
0 Watts
938 Watts
17,570 Watts
Check Figures
Total Air Handler Supply Air (based on a 10 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
1,248 L/s
0 L/s
36
34.7615
2.0433
0.4894
-7.32
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.26 kW
17.57 kW
7.2 Sq.m/Ton
0.1392 Tons/Sq.m
5.00 Tons
Description
Zone Peak Time
17
12.10.011 Recovery
Injection
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
16
3
48
0
0
0.00
1,638
116
7.29
586
0
0
None
0
0
None
0
0
16
3
48
0
0
0.00
1,638
116
7.29
586
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
1,911 Watts
116 L/s
0 L/s
0 L/s
60 Watts
1,971 Watts
198 Watts
388 Watts
0 Watts
586 Watts
2,557 Watts
Check Figures
Total Air Handler Supply Air (based on a 13 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
116 L/s
0 L/s
16
7.2863
6.2190
0.1608
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
2.56 kW
21.9 Sq.m/Ton
0.0457 Tons/Sq.m
0.73 Tons
Description
Zone Peak Time
18
12.10.057 Post
Endoscopy
10am February
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
34
3
101
-182
0
0.00
8,761
818
24.29
893
0
0
None
0
0
None
0
0
34
3
101
-182
0
0.00
8,761
818
24.29
893
0
0
0
0
0
0
10am in February.
Clg: 29 DB, 28 WB, 23.43 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-182
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-182 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
10,693 Watts
818 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
423 Watts
11,116 Watts
198 Watts
695 Watts
0 Watts
893 Watts
12,009 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
818 L/s
0 L/s
34
24.2852
2.8062
0.3563
-5.40
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.18 kW
12.01 kW
9.9 Sq.m/Ton
0.1013 Tons/Sq.m
3.41 Tons
Description
Zone Peak Time
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
19
12.10.018 Endoscopy
3pm December
25
3
75
0
0
0.00
6,561
601
24.14
805
0
0
None
0
0
None
0
0
25
3
75
0
0
0.00
6,561
601
24.14
805
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
7,980 Watts
601 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
310 Watts
8,290 Watts
198 Watts
607 Watts
0 Watts
805 Watts
9,095 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
601 L/s
0 L/s
25
24.1354
2.7376
0.3653
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
9.10 kW
9.6 Sq.m/Ton
0.1039 Tons/Sq.m
2.59 Tons
Description
Zone Peak Time
20
12.10.054
Opthalmology
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
21
3
62
0
0
0.00
3,948
344
16.63
703
0
0
None
0
0
None
0
0
21
3
62
0
0
0.00
3,948
344
16.63
703
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
4,761 Watts
344 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
178 Watts
4,939 Watts
198 Watts
505 Watts
0 Watts
703 Watts
5,641 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
344 L/s
0 L/s
21
16.6253
3.6695
0.2725
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
5.64 kW
12.9 Sq.m/Ton
0.0775 Tons/Sq.m
1.60 Tons
Description
Zone Peak Time
21
12.10.051 NonInvasive
2pm June
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
16
3
48
-142
0
0.00
5,093
469
29.14
593
0
0
None
0
0
None
0
0
16
3
48
-142
0
0.00
5,093
469
29.14
593
0
0
0
0
0
0
2pm in June.
Clg: 33 DB, 30 WB, 26.30 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-142
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-142 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
6,201 Watts
469 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
242 Watts
6,443 Watts
198 Watts
395 Watts
0 Watts
593 Watts
7,036 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
469 L/s
0 L/s
16
29.1339
2.2884
0.4370
-8.83
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.14 kW
7.04 kW
8.0 Sq.m/Ton
0.1243 Tons/Sq.m
2.00 Tons
Description
Zone Peak Time
22
12.10.049 NonInvasive
7pm June
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
13
3
39
-172
0
0.00
4,225
387
29.56
516
0
0
None
0
0
None
0
0
13
3
39
-172
0
0.00
4,225
387
29.56
516
0
0
0
0
0
0
7pm in June.
Clg: 31 DB, 30 WB, 26.10 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
-172
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
-172 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
5,139 Watts
387 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
200 Watts
5,339 Watts
198 Watts
318 Watts
0 Watts
516 Watts
5,854 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
387 L/s
0 L/s
13
29.5549
2.2377
0.4469
-13.16
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
-0.17 kW
5.85 kW
7.9 Sq.m/Ton
0.1271 Tons/Sq.m
1.66 Tons
Description
Zone Peak Time
23
12.10.023 Generic
Screening
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
14
3
43
0
0
0.00
3,659
327
22.72
549
0
0
None
0
0
None
0
0
14
3
43
0
0
0.00
3,659
327
22.72
549
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
4,431 Watts
327 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
169 Watts
4,600 Watts
198 Watts
351 Watts
0 Watts
549 Watts
5,149 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
327 L/s
0 L/s
14
22.7177
2.7965
0.3576
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
5.15 kW
9.8 Sq.m/Ton
0.1017 Tons/Sq.m
1.46 Tons
Description
Zone Peak Time
24
12.10.024 Generic
Screening
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1
Area
People
Volume
Htg.Loss
Htg.L/s
L/s/Sqm
Sen.Gain
Clg.L/s
L/s/Sqm
Lat.Gain
S.Exh
W.Exh
Htg.O.A.
Req.L/s
Act.L/s
Clg.O.A.
Req.L/s
Act.L/s
14
3
42
0
0
0.00
3,640
326
23.29
539
0
0
None
0
0
None
0
0
14
3
42
0
0
0.00
3,640
326
23.29
539
0
0
0
0
0
0
3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:
0
0
0
0
0
0
Watts
Watts
Watts
Watts
Watts
Watts
0 L/s
0 L/s
0 Watts
0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
4,410 Watts
326 L/s
0 L/s
Watts
Watts
Watts
Watts
0 L/s
168 Watts
4,579 Watts
198 Watts
341 Watts
0 Watts
539 Watts
5,118 Watts
Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:
326 L/s
0 L/s
14
23.2895
2.7354
0.3656
0.00
Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m
0.00 kW
5.12 kW
9.6 Sq.m/Ton
0.1039 Tons/Sq.m
1.46 Tons
7
10
43.8
20.1
20.1
5.8
5.8
876
2,000
3.0
18
0
0.83
0.83
1.000
0.320
1.000
0.320
1.000
1.000
1.000
11.5
13.8
6/0
10
733
10
410
2.660
2.660
2.660
2.100
0.640
2.100
0.790
Sub-total
Safety factors:
211
381
699
439
3,017
127
601
876
2,000
225
236
8,813
+10%
--------9,694
-15.960
-15.960
0.000
-12.600
-110
-166
0
-253
-12.600
-73
0.000
0
180
989
1,169
+10%
--------1,286
-602
+0%
---------602
Zone 2-12.10.059 Preparation Area peaks (sensible) in December at 3pm, Air Handler 2 (FCU12.10.059), Group 1, 1.0 x 15.2, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-S-C-M
Partition-1-5
Gls-S-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
0
15.2
7.2
7.2
304
300
3.0
6
0
0.83
1.000
0.320
1.000
1.000
1.000
13.0
6/0
11
410
2.660
2.660
2.100
0.820
Sub-total
Safety factors:
0
243
173
775
304
300
225
88
2,107
+10%
--------2,317
0.000
0.000
-12.600
0
0
-91
0.000
0
180
337
517
+10%
--------569
-91
+0%
---------91
Zone 3-12.10.047 MRI Control Room peaks (sensible) in December at 3pm, Air Handler 3 (FCU12.10.047), Group 1, 1.0 x 19.5, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
19.5
390
500
3.0
8
0
6/0
1.000
1.000
1.000
Sub-total
Safety factors:
Total w/ safety factors:
2.660
311
390
500
225
113
1,539
+10%
--------1,693
0.000
0.000
0
180
432
612
+10%
--------673
0
+0%
--------0
0
13.5
10.8
10.8
270
11,000
3.0
6
0
0.83
1.000
0.320
1.000
1.000
1.000
12.3
6/0
10
774
2.660
2.660
2.100
0.640
Sub-total
Safety factors:
0
215
236
1,712
270
11,000
225
73
13,731
+10%
--------15,104
0.000
0.000
-12.600
0
0
-136
0.000
0
180
305
485
+10%
--------533
-136
+0%
---------136
Zone 5-12.10.0043 Mammogram peaks (sensible) in December at 3pm, Air Handler 5 (FCU-12.10.043),
Group 1, 1.0 x 16.6, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
16.6
332
500
3.0
7
0
6/0
2.660
1.000
1.000
1.000
Sub-total
Safety factors:
265
332
500
225
96
1,418
+10%
--------1,560
0.000
0.000
0
180
368
548
+10%
--------603
0
+0%
--------0
Zone 6-12.10.078 USG peaks (sensible) in December at 3pm, Air Handler 6 (FCU-12.10.078), Group 1,
1.0 x 16.6, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
16.6
332
2,500
3.0
7
0
6/0
2.660
1.000
1.000
1.000
Sub-total
Safety factors:
265
332
2,500
225
96
3,418
+10%
--------3,760
0.000
0.000
0
180
368
548
+10%
--------603
0
+0%
--------0
Zone 7-12.10.014 DEXA Room peaks (sensible) in December at 3pm, Air Handler 7 (FCU-12.10.014),
Group 1, 1.0 x 20.4, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
20.4
408
700
3.0
6/0
1.000
1.000
1.000
2.660
326
408
700
225
0.000
0
180
Sunday, July 05, 2015, 07:05 PM
Unit
Quan
-SCCFAC
CLTD
SHGF
U.Fac
-CLF-
9
0
Sub-total
Safety factors:
Sen.
Gain
Lat.
Gain
118
452
1,777
+10%
--------1,954
Htg.
Mult.
Htg.
Loss
0.000
632
+10%
--------695
0
+0%
--------0
Zone 8-12.25.030 Stress Room peaks (sensible) in December at 3pm, Air Handler 8 (FCU-12.10.030),
Group 1, 1.0 x 10.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
10.1
202
1,000
3.0
4
0
6/0
2.660
1.000
1.000
1.000
Sub-total
Safety factors:
161
202
1,000
225
58
1,647
+10%
--------1,811
0.000
0.000
0
180
224
404
+10%
--------444
0
+0%
--------0
Zone 9-12.10.070 Stress Room peaks (sensible) in December at 3pm, Air Handler 9 (FCU-12.10.070),
Group 1, 1.0 x 9.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
9.9
198
1,000
3.0
4
0
6/0
2.660
1.000
1.000
1.000
Sub-total
Safety factors:
158
198
1,000
225
57
1,638
+10%
--------1,802
0.000
0.000
0
180
219
399
+10%
--------439
0
+0%
--------0
Zone 10-12.10.082 Stress Treadmill peaks (sensible) in December at 3pm, Air Handler 10 (FCU12.10.082), Group 1, 1.0 x 20.7, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
20.7
414
1,000
3.0
9
0
6/0
1.000
1.000
1.000
Sub-total
Safety factors:
Total w/ safety factors:
2.660
330
414
1,000
225
120
2,089
+10%
--------2,298
0.000
0.000
0
180
459
639
+10%
--------703
0
+0%
--------0
7
8
38.1
16.5
16.5
8.7
8.7
762
6,900
3.0
16
0
0.83
0.83
1.000
0.320
1.000
0.320
1.000
1.000
1.000
9.8
11.3
6/0
5
733
5
410
2.660
2.660
2.660
2.100
0.570
2.100
0.630
Sub-total
Safety factors:
181
225
608
187
2,206
99
719
762
6,900
225
133
12,246
+10%
--------13,470
-15.960
-15.960
0.000
-12.600
-110
-120
0
-208
-12.600
-110
0.000
0
180
714
894
+10%
--------984
-547
+0%
---------547
Zone 12-12.10.012 Recovery Injection peaks (sensible) in December at 3pm, Air Handler 12 (FCU12.10.012), Group 1, 1.0 x 18.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-S-C-M
Partition-1-5
Gls-S-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
0
18.1
7.2
7.2
362
600
3.0
8
0
0.83
1.000
0.320
1.000
1.000
1.000
13.0
6/0
11
410
2.660
2.660
2.100
0.820
Sub-total
Safety factors:
0
289
173
775
362
600
225
105
2,528
+10%
--------2,781
0.000
0.000
-12.600
0
0
-91
0.000
0
180
401
581
+10%
--------639
-91
+0%
---------91
Zone 13-12.10.081 X-Ray peaks (sensible) in December at 3pm, Air Handler 11 (FCU-12.10.081), Group
1, 1.0 x 32.0, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
32
640
4,700
3.0
13
0
6/0
1.000
1.000
1.000
Sub-total
Safety factors:
Total w/ safety factors:
2.660
511
640
4,700
225
185
6,261
+10%
--------6,887
0.000
0.000
0
180
709
889
+10%
--------978
0
+0%
--------0
4
16.9
17.7
17.7
338
4,698
3.0
7
0
0.83
1.000
0.320
1.000
1.000
1.000
10.7
6/0
5
774
2.660
2.660
2.100
0.570
Sub-total
Safety factors:
111
270
201
2,499
338
4,698
225
59
8,400
+10%
--------9,241
Htg.
Loss
-15.960
0.000
-12.600
-62
0
-223
0.000
0
180
317
497
+10%
--------547
-285
+0%
---------285
Zone 15-12.25.002 Sub-Wait peaks (sensible) in December at 3pm, Air Handler 15 (FCU-12.25.002),
Group 1, 1.0 x 32.4, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
32.4
648
300
3.0
14
0
6/0
2.660
1.000
1.000
1.000
Sub-total
Safety factors:
517
648
300
225
188
1,878
+10%
--------2,065
0.000
0.000
0
180
718
898
+10%
--------988
0
+0%
--------0
Zone 16-12.10.058 PET-CT Room peaks (sensible) in February at 10am, Air Handler 16 (FCU12.10.058), Group 1, 1.0 x 35.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-E-C-M
Partition-1-5
Gls-E-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
0
35.9
20.9
20.9
718
7,033
3.0
15
0
0.83
1.000
0.320
1.000
1.000
1.000
10.7
6/0
5
774
2.660
2.660
2.100
0.570
Sub-total
Safety factors:
0
573
237
2,944
718
7,033
225
125
11,855
+10%
--------13,040
0.000
0.000
-12.600
0
0
-263
0.000
0
180
673
853
+10%
--------938
-263
+0%
---------263
Zone 17-12.10.011 Recovery Injection peaks (sensible) in December at 3pm, Air Handler 17 (FCU12.10.011), Group 1, 1.0 x 15.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
15.9
6/0
2.660
254
0.000
Unit
Quan
-SCCFAC
318
600
3.0
7
0
1.000
1.000
1.000
CLTD
SHGF
U.Fac
-CLF-
Sub-total
Safety factors:
Sen.
Gain
Lat.
Gain
318
600
225
92
0
180
352
1,489
+10%
--------1,638
Htg.
Mult.
Htg.
Loss
0.000
532
+10%
--------586
0
+0%
--------0
Zone 18-12.10.057 Post Endoscopy peaks (sensible) in February at 10am, Air Handler 18 (FCU12.10.057), Group 1, 1.0 x 33.7, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-E-C-M
Partition-1-5
Gls-E-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
3
33.7
10.7
10.7
674
4,700
3.0
14
0
0.83
1.000
0.320
1.000
1.000
1.000
10.7
6/0
5
774
2.660
2.660
2.100
0.570
Sub-total
Safety factors:
85
538
121
1,504
674
4,700
225
118
7,964
+10%
--------8,761
-15.960
0.000
-12.600
-48
0
-134
0.000
0
180
632
812
+10%
--------893
-182
+0%
---------182
Zone 19-12.10.018 Endoscopy peaks (sensible) in December at 3pm, Air Handler 19 (FCU-12.10.018),
Group 1, 1.0 x 24.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
24.9
498
4,700
3.0
10
0
6/0
2.660
1.000
1.000
1.000
Sub-total
Safety factors:
397
498
4,700
225
144
5,965
+10%
--------6,561
0.000
0.000
0
180
552
732
+10%
--------805
0
+0%
--------0
Zone 20-12.10.054 Opthalmology peaks (sensible) in December at 3pm, Air Handler 20 (FCU-12.10.054),
Group 1, 1.0 x 20.7, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
20.7
414
2,500
3.0
9
0
6/0
1.000
1.000
1.000
Sub-total
E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV
2.660
330
414
2,500
225
120
3,589
0.000
0.000
0
180
459
639
Unit
Quan
-SCCFAC
CLTD
SHGF
U.Fac
-CLF-
Safety factors:
Total w/ safety factors:
Sen.
Gain
Lat.
Gain
+10%
--------3,948
+10%
--------703
Htg.
Mult.
Htg.
Loss
+0%
--------0
Zone 21-12.10.051 Non-Invasive peaks (sensible) in June at 2pm, Air Handler 21 (FCU-12.10.051),
Group 1, 1.0 x 16.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-N-C-M
Partition-1-5
Gls-N-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
2
16.1
9.0
9.0
322
2,500
3.0
7
0
0.83
1.000
0.320
1.000
1.000
1.000
15.4
6/0
10
515
2.660
2.660
2.100
0.650
Sub-total
Safety factors:
74
257
197
964
322
2,500
225
91
4,630
+10%
--------5,093
-15.960
0.000
-12.600
-29
0
-113
0.000
0
180
359
539
+10%
--------593
-142
+0%
---------142
Zone 22-12.10.049 Non-Invasive peaks (sensible) in June at 7pm, Air Handler 22 (FCU-12.10.049),
Group 1, 1.0 x 13.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-N-C-M
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
11
13.1
262
2,500
3.0
5
0
0.83
20.4
6/0
2.660
2.660
1.000
1.000
1.000
Sub-total
Safety factors:
587
209
262
2,500
225
58
3,840
+10%
--------4,225
-15.960
0.000
-172
0
0.000
0
180
289
469
+10%
--------516
-172
+0%
---------172
Zone 23-12.10.023 Generic Screening peaks (sensible) in December at 3pm, Air Handler 23 (FCU12.10.023), Group 1, 1.0 x 14.4, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr
14.4
288
2,500
3.0
6
0
6/0
1.000
1.000
1.000
Sub-total
Safety factors:
Total w/ safety factors:
2.660
230
288
2,500
225
83
3,326
+10%
--------3,659
0.000
0.000
0
180
319
499
+10%
--------549
0
+0%
--------0
14
280
2,500
3.0
6
0
6/0
1.000
1.000
1.000
Sub-total
Safety factors:
Total w/ safety factors:
2.660
223
280
2,500
225
81
3,310
+10%
--------3,640
Htg.
Loss
0.000
0.000
0
180
310
490
+10%
--------539
0
+0%
--------0
Latent
Grams
Sensible
Temp
L/s
877
0
1,202
9,694
0
11.126
0.810
0.000
1.110
8.954
0.000
66
0
90
725
0
11,773
455
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
880
12,228
22.420
880
7.756
1,286
0.494
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
1,286
8.249
0.000
1,286
8.249
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
880
880
x(
x(
22.420
8.249
11.126
7.756
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
880
x(
43.593
30.826
)=
=
12,227
1,286
---------13,514
13,485
13,514
Watts
Watts
Watts
Watts
Watts
=
=
=
13,485 / (
-602 / (
-602 /
5.60
0.00
970
x
x
)
)
=
=
=
0.6 L/s
0.0 L/s
-0.62 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
187
0
257
2,317
0
10.072
0.810
0.000
1.110
10.010
0.000
13
0
18
158
0
2,762
97
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
188
2,859
22.420
188
7.223
569
1.020
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
569
8.244
0.000
569
8.244
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
188
188
x(
x(
22.420
8.244
10.072
7.223
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
188
x(
43.578
28.410
)=
=
2,858
569
---------3,427
3,426
3,428
Watts
Watts
Watts
Watts
Watts
=
=
=
3,426 / (
-91 / (
-91 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
-0.09 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
112
0
154
1,693
0
7.852
0.810
0.000
1.110
12.230
0.000
6
0
9
97
0
1,959
58
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
113
2,017
22.420
113
6.207
673
2.021
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
673
8.228
0.000
673
8.228
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
113
113
x(
x(
22.420
8.228
7.852
6.207
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
113
x(
43.539
23.593
)=
=
2,017
673
---------2,690
2,694
2,690
Watts
Watts
Watts
Watts
Watts
=
=
=
2,694 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
1,482
0
2,031
15,104
0
11.825
0.810
0.000
1.110
8.256
0.000
118
0
162
1,207
0
18,617
768
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
1,488
19,385
22.420
1,488
8.127
533
0.121
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
533
8.249
0.000
533
8.249
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
1,488
1,488
x(
x(
22.420
8.249
11.825
8.127
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
1,488
x(
43.591
32.477
)=
=
19,385
533
---------19,918
19,839
19,919
Watts
Watts
Watts
Watts
Watts
=
=
=
19,839 / (
-136 / (
-136 /
5.60
0.00
970
x
x
)
)
=
=
=
0.8 L/s
0.0 L/s
-0.14 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
105
0
144
1,560
0
8.079
0.810
0.000
1.110
12.003
0.000
6
0
8
91
0
1,809
55
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
106
1,864
22.420
106
6.305
603
1.927
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
603
8.232
0.000
603
8.232
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
106
106
x(
x(
22.420
8.232
8.079
6.305
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
106
x(
43.548
24.069
)=
=
1,864
603
---------2,466
2,470
2,467
Watts
Watts
Watts
Watts
Watts
=
=
=
2,470 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
332
0
455
3,760
0
10.902
0.810
0.000
1.110
9.179
0.000
24
0
33
275
0
4,546
172
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
333
4,718
22.420
333
7.640
603
0.611
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
603
8.251
0.000
603
8.251
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
333
333
x(
x(
22.420
8.251
10.902
7.640
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
333
x(
43.597
30.305
)=
=
4,718
603
---------5,321
5,312
5,321
Watts
Watts
Watts
Watts
Watts
=
=
=
5,312 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.2 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
138
0
189
1,954
0
8.617
0.810
0.000
1.110
11.466
0.000
8
0
11
119
0
2,282
72
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
139
2,353
22.420
139
6.541
695
1.695
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
695
8.236
0.000
695
8.236
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
139
139
x(
x(
22.420
8.236
8.617
6.541
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
139
x(
43.560
25.212
)=
=
2,353
695
---------3,048
3,051
3,048
Watts
Watts
Watts
Watts
Watts
=
=
=
3,051 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
147
0
201
1,811
0
10.073
0.810
0.000
1.110
10.010
0.000
10
0
14
123
0
2,159
76
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
147
2,235
22.420
147
7.224
444
1.020
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
444
8.244
0.000
444
8.244
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
147
147
x(
x(
22.420
8.244
10.073
7.224
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
147
x(
43.578
28.412
)=
=
2,234
444
---------2,678
2,678
2,679
Watts
Watts
Watts
Watts
Watts
=
=
=
2,678 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
146
0
200
1,802
0
10.104
0.810
0.000
1.110
9.979
0.000
10
0
14
123
0
2,149
76
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
147
2,225
22.420
147
7.239
439
1.011
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
439
8.250
0.000
439
8.250
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
147
147
x(
x(
22.420
8.250
10.104
7.239
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
147
x(
43.594
28.482
)=
=
2,224
439
---------2,664
2,663
2,664
Watts
Watts
Watts
Watts
Watts
=
=
=
2,663 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
173
0
238
2,298
0
9.347
0.810
0.000
1.110
10.736
0.000
11
0
15
148
0
2,709
90
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
174
2,799
22.420
174
6.876
703
1.364
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
703
8.240
0.000
703
8.240
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
174
174
x(
x(
22.420
8.240
9.347
6.876
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
174
x(
43.568
26.797
)=
=
2,799
703
---------3,501
3,503
3,502
Watts
Watts
Watts
Watts
Watts
=
=
=
3,503 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
618
0
847
6,887
0
11.052
0.810
0.000
1.110
9.029
0.000
46
0
63
512
0
8,352
320
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
620
8,672
22.420
620
7.717
978
0.533
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
978
8.250
0.000
978
8.250
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
620
620
x(
x(
22.420
8.250
11.052
7.717
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
620
x(
43.594
30.654
)=
=
8,671
978
---------9,649
9,630
9,650
Watts
Watts
Watts
Watts
Watts
=
=
=
9,630 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.4 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
229
0
314
2,781
0
10.246
0.810
0.000
1.110
9.835
0.000
16
0
22
192
0
3,323
119
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
230
3,442
22.420
230
7.309
639
0.939
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
639
8.248
0.000
639
8.248
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
230
230
x(
x(
22.420
8.248
10.246
7.309
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
230
x(
43.590
28.803
)=
=
3,442
639
---------4,081
4,079
4,081
Watts
Watts
Watts
Watts
Watts
=
=
=
4,079 / (
-91 / (
-91 /
5.60
0.00
970
x
x
)
)
=
=
=
0.2 L/s
0.0 L/s
-0.09 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
1,275
0
1,747
13,470
0
11.523
0.810
0.000
1.110
8.557
0.000
99
0
136
1,045
0
16,493
661
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
1,280
17,154
22.420
1,280
7.965
1,089
0.287
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
1,089
8.253
0.000
1,089
8.253
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
1,280
1,280
x(
x(
22.420
8.253
11.523
7.965
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
1,280
x(
43.601
31.760
)=
=
17,153
1,089
---------18,243
18,187
18,224
Watts
Watts
Watts
Watts
Watts
=
=
=
18,187 / (
-547 / (
-547 /
5.60
0.00
970
x
x
)
)
=
=
=
0.8 L/s
0.0 L/s
-0.56 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
890
0
1,219
9,241
0
11.669
0.810
0.000
1.110
8.411
0.000
70
0
96
727
0
11,350
461
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
893
11,811
22.420
893
8.043
547
0.207
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
547
8.250
0.000
547
8.250
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
893
893
x(
x(
22.420
8.250
11.669
8.043
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
893
x(
43.595
32.106
)=
=
11,811
547
---------12,357
12,314
12,358
Watts
Watts
Watts
Watts
Watts
=
=
=
12,314 / (
-285 / (
-285 /
5.60
0.00
970
x
x
)
)
=
=
=
0.5 L/s
0.0 L/s
-0.29 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
116
0
160
2,065
0
5.727
0.810
0.000
1.110
14.360
0.000
6
0
8
103
0
2,342
60
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
117
2,402
22.420
117
5.356
988
2.854
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
988
8.210
0.000
988
8.210
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
117
117
x(
x(
22.420
8.210
5.727
5.356
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
117
x(
43.492
19.295
)=
=
2,401
988
---------3,389
3,396
3,390
Watts
Watts
Watts
Watts
Watts
=
=
=
3,396 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
1,243
0
1,704
13,040
0
11.584
0.810
0.000
1.110
8.497
0.000
97
0
133
1,018
0
15,987
645
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
1,248
16,632
22.420
1,248
7.997
938
0.254
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
938
8.251
0.000
938
8.251
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
1,248
1,248
x(
x(
22.420
8.251
11.584
7.997
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
1,248
x(
43.598
31.902
)=
=
16,631
938
---------17,570
17,513
17,570
Watts
Watts
Watts
Watts
Watts
=
=
=
17,513 / (
-263 / (
-263 /
5.60
0.00
970
x
x
)
)
=
=
=
0.7 L/s
0.0 L/s
-0.27 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
115
0
158
1,638
0
8.588
0.810
0.000
1.110
11.494
0.000
7
0
10
99
0
1,911
60
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
116
1,971
22.420
116
6.529
586
1.708
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
586
8.236
0.000
586
8.236
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
116
116
x(
x(
22.420
8.236
8.588
6.529
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
116
x(
43.560
25.150
)=
=
1,971
586
---------2,556
2,559
2,557
Watts
Watts
Watts
Watts
Watts
=
=
=
2,559 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.1 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
815
0
1,117
8,761
0
11.376
0.810
0.000
1.110
8.704
0.000
62
0
86
671
0
10,693
423
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
818
11,116
22.420
818
7.887
893
0.369
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
893
8.256
0.000
893
8.256
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
818
818
x(
x(
22.420
8.256
11.376
7.887
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
818
x(
43.609
31.412
)=
=
11,116
893
---------12,009
11,977
12,009
Watts
Watts
Watts
Watts
Watts
=
=
=
11,977 / (
-182 / (
-182 /
5.60
0.00
970
x
x
)
)
=
=
=
0.5 L/s
0.0 L/s
-0.19 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
599
0
820
6,561
0
11.204
0.810
0.000
1.110
8.877
0.000
45
0
62
494
0
7,980
310
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
601
8,290
22.420
601
7.796
805
0.453
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
805
8.249
0.000
805
8.249
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
601
601
x(
x(
22.420
8.249
11.204
7.796
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
601
x(
43.591
31.008
)=
=
8,290
805
---------9,095
9,074
9,095
Watts
Watts
Watts
Watts
Watts
=
=
=
9,074 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.4 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
343
0
470
3,948
0
10.753
0.810
0.000
1.110
9.328
0.000
25
0
34
285
0
4,761
178
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
344
4,939
22.420
344
7.563
703
0.690
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
703
8.253
0.000
703
8.253
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
344
344
x(
x(
22.420
8.253
10.753
7.563
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
344
x(
43.601
29.960
)=
=
4,938
703
---------5,641
5,633
5,641
Watts
Watts
Watts
Watts
Watts
=
=
=
5,633 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.2 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
467
0
640
5,093
0
11.252
0.810
0.000
1.110
8.829
0.000
35
0
48
385
0
6,201
242
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
469
6,443
22.420
469
7.821
593
0.427
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
593
8.248
0.000
593
8.248
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
469
469
x(
x(
22.420
8.248
11.252
7.821
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
469
x(
43.591
31.121
)=
=
6,442
593
---------7,035
7,018
7,036
Watts
Watts
Watts
Watts
Watts
=
=
=
7,018 / (
-142 / (
-142 /
5.60
0.00
970
x
x
)
)
=
=
=
0.3 L/s
0.0 L/s
-0.15 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
386
0
529
4,225
0
11.209
0.810
0.000
1.110
8.872
0.000
29
0
40
318
0
5,139
200
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
387
5,339
22.420
387
7.799
516
0.450
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
516
8.249
0.000
516
8.249
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
387
387
x(
x(
22.420
8.249
11.209
7.799
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
387
x(
43.591
31.019
)=
=
5,338
516
---------5,854
5,840
5,854
Watts
Watts
Watts
Watts
Watts
=
=
=
5,840 / (
-172 / (
-172 /
5.60
0.00
970
x
x
)
)
=
=
=
0.2 L/s
0.0 L/s
-0.18 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
326
0
447
3,659
0
10.987
0.810
0.000
1.110
9.094
0.000
24
0
33
270
0
4,431
169
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
327
4,600
22.420
327
7.683
549
0.567
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
549
8.250
0.000
549
8.250
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
327
327
x(
x(
22.420
8.250
10.987
7.683
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
327
x(
43.595
30.501
)=
=
4,600
549
---------5,149
5,139
5,149
Watts
Watts
Watts
Watts
Watts
=
=
=
5,139 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.2 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00
Latent
Grams
Sensible
Temp
L/s
325
0
445
3,640
0
11.002
0.810
0.000
1.110
9.079
0.000
24
0
33
269
0
4,410
168
0
0
0
0
22.000
0.420
0.000
0.000
0.000
0.000
326
4,579
22.420
326
7.691
539
0.559
Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan
539
8.250
0.000
539
8.250
=
=
=
=
TSH
TLH
=
=
x
x
1.23
2.96
x
x
326
326
x(
x(
22.420
8.250
11.002
7.691
)=
)=
SUM
=
GTH
=
1.000
Total System Load
1.20
326
x(
43.595
30.538
)=
=
4,578
539
---------5,118
5,108
5,118
Watts
Watts
Watts
Watts
Watts
=
=
=
5,108 / (
0 /(
0 /
5.60
0.00
970
x
x
)
)
=
=
=
0.2 L/s
0.0 L/s
0.00 kg./hr
4,179
4,179
22.00
22.00