Siemens Energy, Inc.
siemens.com/energy
VS
i1
X1
i2
X2
VL
VL
i2
i1
V
Restricted Siemens Energy 2013 All rights reserved.
VS
V2
VL
VPST
V2
VL
VS
i1+i
VPST V2
Restricted Siemens Energy 2013 All rights reserved.
V1
i2- i
Node 2
Voltage V2
PST
V = I2 . j(XPST + XLine)
VPST
I1
jXPST
V1 = V S
IPST
VL0
I2
jXLine
VL
V2
VL0
VL
VPST
V2
I2
Restricted Siemens Energy 2013 All rights reserved.
V1 = VS
S3
Phasor Diagram:
L2
S1
L1
L3
S1
S3
L2
L3
S2
S2
S1
L2
Phasor Diagram: L1
S2
L3
S1
S3
L2
L3
S2
S3
S1 L2
S2 L3
S3
Additional
Impedance
RW
EW
Phasor Diagram:
L1
S1
S3
L2
L3
S2
Classic solution:
S1
L1 S2
L2 S3
L3
Phasor Diagram:
L1
S1
S3
L2
c
Primary circuit
S2
Operational considerations
Phase shifting transformers in Operation:
Variation of load voltage due to load current,
ohmic components neglected
jXPST*iL
VPST
jXPST*iL
XPST
iL
VL0
VPST
VS
VL
VS
VL0
VL
iL
Operational considerations
Effect of load on effective phase angle
Operational considerations
For a given phase shift under load, design
optimization is necessary:
Impedance as low as possible, minimum value determined
by short circuit requirements
With lower impedance, no load phase angle can be reduced
Lower no load phase angle means lower design rating, lower
weight, lower cost.
8
6
4
2
Single core, with hexagonal winding connection
0
0
10
20
30
40
Maximum phase angle (deg)
50
60
Operational considerations
Special considerations for reverse load flow
The effective phase angle is increased, as is the voltage across the
PST. This can cause over-excitation in the core of the PST!
VPST
~
VS
jXPST*iL
XPST
jXPST*iL
iL
VPST
VL
VS
VL0
VL0
VL
iL
Advance
jXPST*iL
VL
jXPST*iL
VL0
VPST
VL
VS
VPST
VS
VL0
iL
Restricted Siemens Energy 2013 All rights reserved.
iL
Operational considerations
Power transformer
Flux distribution at rated load, cos 1
S
1
2
S
2
1
1
Operational considerations
PST
Single phase scheme and phasor diagram
PST
U
1
3-phase
connectio
n
UZ
U
2
Operational considerations
S
2
1
1
Iexc
IL
Phasor diagram
ATL
longitudinal transversal
ATS
IS
ATexc
components
Testing
Testing phase shifting transformers :
Specific requirements:
Heat run
PST fully assembled
minimized deviation of loss distribution during short circuit
condition
access to all windings for resistance measurement
Induced voltage test
PST fully assembled
tests at zero and maximum phase shift
Testing
Heat run test:
Series Transformer
Auxiliary
Bushings
Temporary bushings inserted at all connections between series and exciting unit
For resistance measurement, all these connections can be opened
Restricted Siemens Energy 2013 All rights reserved.
=0
0
100
=0
400
0
=0
400
100
=
maximum
100
70
=
maximum
400
400
=
maximum
500
470
Testing
Induced voltage test:
Series Transformer
S1
L1
S2
L2
L3
S3
Exciting Transformer
Auxiliary bushings
Operational considerations
Bypass breaker considerations
Due to the PSTs impedance, inserting the PST with
phase angle zero normally reduces the load flow
A minimum advance phase angle is necessary to restore
the original load flow condition
Therefore, by-passing the PST might be advantageous in
certain conditions
On the other hand, lightning strikes can also appear with
the PST by-passed
Internal stresses have to be investigated carefully for this
condition
Restricted Siemens Energy 2013 All rights reserved.
Testing
Lightning impulse test:
Standard LI test:
S2
L2
Special LI test:
S2
L2
Source- and
load- terminal
connected
Testing
Lightning impulse stresses in the series winding
V(%)
150
100
50
40
80
T( s)
120
-50
Applied voltage and typical wave shape of voltage at crossover during lightning
impulse test with source and load side terminals connected
Restricted Siemens Energy 2013 All rights reserved.
S1
S2
S3
87-1
primary
L1
L2
L3
87-2
secondary
Restricted Siemens Energy 2013 All rights reserved.
LEAPS
Transmission
One-Line
To SCE Serrano
32
Sub
miles
To SCE Valley
30
Sub
miles
Lee Lake
Substation
12.7
miles
16.5
miles
Lake Elsionre
Power
Pump
House
Camp Pendleton
Substation
To SDG&E Talega
10
Sub
miles
To SG&E Escondido
Sub
37
miles
500 kV
230 kV
115 kV
13.8 to 20 kV
Existing
New Additions
Further
Additions
25 no load ( 16 taps)
Conclusion
Conclusion
Conclusion
Thank you!
Questions?