General Wall Mounted

(60Hz/R410A)
6RMG0-01C

General Wall Mounted


Publication history
Test condition of international standard
General Description
1. Models line up .....................................................................................6
2. Nomenclature ......................................................................................7
3. Specifications .....................................................................................8
4. Dimensional Drawings .....................................................................10
5. Wiring diagrams................................................................................15
6. Refrigerant cycle diagram................................................................18
7. Capacity tables..................................................................................19
8. Capacity coefficient factor ...............................................................21
9. Operation range ................................................................................23
10. Air velocity and temperature distribution(reference data)..........24
11. Controller ........................................................................................26
12. Installation .......................................................................................27
13. Installation Guide at the Seaside...................................................42

General Wall Mounted

6RMG0-01C

Publication history

Publication history
Plb.No

Outdoor Units

Notes

Publication in

6RMG0-01A

All models

Added N.A models

May. 2010

6RMG0-01B

All models

Change operation range

Sep. 2010

6RMG0-01C

All models

Change motor spec

Oct. 2010

General Wall Mounted

Test condition of international standard

6RMG0-01C

Test condition of international standard


CLASSIFICATION

Indoor
Cooling
Capacity

Outdoor

Indoor
Heating
Capacity

Maximum

Outdoor

Indoor

Cooling
Operating

Outdoor

Maximum

Indoor

Heating
Operating
Enclosure

Outdoor

Indoor

Sweat /
Condensate

Outdoor

Disposal
Freeze-up/

Indoor

Low
Temperature Outdoor

KSC
9306

ISO
5151

ARI
210/240

AHAM

AS
1861.1

SSA
385

DBC(F)

27.0

27.0

26.7(80)

26.7(80)

27.0

29.0

WBC(F)

19.5

19.0

19.4(67)

19.4(67)

19.0

19.0

DBC(F)

35.0

35.0

35.0(95)

35.0(95)

35.0

46.0

WBC(F)

24.0

24.0

23.9(75)

23.9(75)

24.0

24.0

DBC(F)

20.0

20.0

21.1(70)

21.1(70)

21.0

21.0

WBC(F)

15.0

15.0

15.6(60)

15.6(60)

15.0

15.5

DBC(F)

7.0

7.0

8.3(47)

8.3(47)

7.0

7.0

WBC(F)

6.0

6.0

6.1(43)

6.1(43)

6.0

6.0

DBC(F)

32.0

32.0

26.7(80)

32.2(90)

32.0

29.0

WBC(F)

23.0

23.0

19.4(67)

22.8(73)

23.0

19.0

DBC(F)

43.0

43.0

46.1(115)

43.3(110)

43.0

54.0

WBC(F)

26.0

26.0

23.9(75)

25.6(78)

26.0

24.0

DBC(F)

27.0

27.0

26.7(80)

26.7(80)

WBC(F)

19.0

19.0

19.4(67)

22.8(73)

DBC(F)

21.0

24.0

23.9(75)

23.9(75)

WBC(F)

15.0

18.0

18.3(65)

18.3(65)

DBC(F)

27.0

27.0

26.7(80)

26.7(80)

27.0

27.0

WBC(F)

24.0

24.0

23.9(75)

23.9(75)

24.0

24.0

DBC(F)

27.0

27.0

26.7(80)

26.7(80)

27.0

27.0

WBC(F)

24.0

24.0

23.9(75)

23.9(75)

24.0

24.0

DBC(F)

21.0

21.0

19.4(67)

21.1(70)

21.0

21.0

WBC(F)

15.0

15.0

13.9(57)

15.6(60)

16.0

16.0

DBC(F)

21.0

21.0

19.4(67)

21.1(70)

21.0

21.0

WBC(F)

15.0

15.0

13.9(57)

15.6(60)

16.0

16.0

KS : Korea Standard
ISO : International Standard Organization
ARI : Airconditioning and Refrigeration Institute
AHAM : Association of Home Appliance Manufacturers

AS : Australia Standard
SSA : Saudi Arabian Standard

General Wall Mounted

6RMG0-01C

General Description

General Description
Split type of Air conditioners are known by the category name of Wall Mounted Type of units.These units can be
easily installed in a small space and have exceptional Cooling capacity.Designed for Low-noise operation,it
ensures a pleasant air conditioned environment.
LG Offers various types of units to its customers to suit for the best application and requirement.The following are
the important categories offered by LG :
1) General Wall Mounted Type Units : Units with Simplicity in design.
2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning.
3) Inverter Units : These units are capable of minimising the Power consumption with the unique inverter technology.
Some of the Important Features of these units are listed below :
1) Providing Health to the Customers : By having Filters such as Plasma Filter which is capable of removing the
Micro Organisms up to 0.1 microns.
2) Long Term Money Saving : By providing the Features such as Gold Fin, Auto Clean etc. to maintain the same
performance for years.
3) Best Comfort : With Features such as Sleep Mode,Timer,Auto Restart etc.
The Units are available with many standard and optional features which give our Customers the choice to select
the unit of their own desire.For details refer to the detailed specification followed after this description.

LG Electronics Inc.
Air Conditioning Company

General Wall Mounted

1. Models line up

6RMG0-01C

1. Models line up
General Wall Mounted
1.1 Indoor Unit
Indoor Unit

Type

C/O

H/P

Capacity
[kW (kBTU/h)]

Model Name

2.63(9)

ASNC0914DH1(LSN093CE)

3.51(12)

ASNC121E1H0(LSN122CE)

5.27(18)

ASNC1835SM1(LSN186CE)

2.63(9)

ASNH091E1H1(LSN093HE)

3.51(12)

ASNH121E1H0(LSN122HE)

5.27(18)

ASNH1835SM1(LSN186HE)

1.2 Outdoor Unit

Outdoor Unit

Type

Capacity
[kW(kBTU/h)]

Model Name

2.63(9)

ASUC0914DH1(LSU093CE)

3.51(12)

ASUC121E1H0(LSU122CE)

5.27(18)

ASUC1835SM1(LSU186CE)

2.63(9)

ASUH091E1H1(LSU093HE)

3.51(12)

ASUH121E1H0(LSU122HE)

5.27(18)

ASUH1835SM1(LSU186HE)

C/O

H/P

General Wall Mounted

6RMG0-01C

2. Nomenclature

2. Nomenclature
Identification Rule :

Code

10

Type

Code of Model

Meaning

Production Center,
Refrigerant

A~Z

L: Chang-won R22
A: Chang-won R410A

Product Type

A~Z

S: Split Type Air Conditioner

Cooling/Heating/Inverter

A~Z

C: Cooling Only
H: Heat Pump

4, 5

Capacity

0~9

Capacity
Ex. "09" 9,000 Btu/h Class

Electric Range

1~9

1: 115V/60Hz
2: 220V/60Hz
3: 208-230V/60Hz
5: 200-220V/50Hz
6: 220-240V/50Hz
7: 110V, 50/60Hz

Chassis

A~Z

Name of Chassis

Look

A~Z

Looks : D Look (Panel Type)


G Look (Grille Type)

9, 10

Function

A~Z

H : Plasma + (A/chageove) + A/Clean + 4Way + Low A


M : Plasma + (A/chageove) + A/Clean + 4Way

11

Serial No.

1~9

LG Model Development Serial No.

General Wall Mounted

3.Specifications

6RMG0-01C

3.Specifications
General Wall Mounted
Sales Model
Models
Cooling Capacity
Heating Capacity
Power Input
Running Current
EER
SEER
HSPF
Power Supply
Power Factor
Air Flow Rate

Cooling/Heating
Cooling/Heating

Indoor,Max
Outdoor,Max

Dehumidification
Sound Level

Indoor,H/M/L
Outdoor,Max
Refrigerant & Charge (at 7.5 m)
Additional Refrigerant charge
Compressor
Type
Model
Motor Type
Oil Type
Oil Charge
O.L.P. name
Fan(Indoor)
Type
Motor Output
Fan(Outdoor)
Type
Motor Type
Motor Output
Circuit Breaker*
Power Supply Cable
Power and Transmission Cable No.*mm2
Piping Connections
Liquid Side
Gas Side
Drain Hose(O.D / I.D.)
Dimensions
Indoor (W*H*D)
Outdoor (W*H*D)
Net Weight
Gross Weight
Operation Range

Indoor
Outdoor
Indoor
Outdoor
Cooling(Outdoor)
Heating(Outdoor)

Unit
kW
Btu/h.
kW
Btu/h.
W
A
W/W
Btu/h.W
/ V / Hz
%
m3/min(CFM)
m3/min(CFM)
pts/h
dB(A)3
dB(A)3
g(oz)
g/m(oz/ft)

cc
W
W
A
No.*mm2
No.*mm2
mm(in)
mm(in)
mm(in)
mm
inch
mm
inch
kg(lbs)
kg(lbs)
kg(lbs)
kg(lbs)
C(F)
C(F)
m(ft)
m(ft)

Piping Length (Min/Max)


Max. Elevation Difference
Tool Code(Chassis)
Indoor + Outdoor
Features
Temperature Control
Air Deflection
Steps, Fan/Cool
Air Deflection Control(up&down)
Air Deflection Control(left&right)
Remocon Type
Setting Temperature Range, Cooling Mode
Heating Mode
Temperature Increment
Auto Operation(electronic control)
Self Diagnosis
Timer
Sleep Operation
Healthy Dehumidification Mode
Restart Delay
Defrost Control
Hot Start

LS093CE
AS-C0914DH1
2.64
8900
810
7
3.22
11.0
13.0
1/115/60
93
7.1(250)
24(847)
2.6
36/31/28
48
R410A, 600(21.1)
20(0.22)
Rotary
GK086CAA
PSC
FVC68D
330
MRA12061-12026
Cross Flow Fan
21.5
Propeller
BLDC
64.5
15
14:3*2.5
18:4*0.75
6.35(1/4)
9.52(3/8)
21.5 / 16.0(0.85 / 0.63)
840*270*153
33-1/16*10-5/8*6-1/32
770*541*244
30-5/16*21-5/16*9-5/18
7.0(15.4)
30(66.1)
8.2(18.0)
33.3(73.4)
21~46(70~115)
4(13.2) / 15(49.2)
7.0(23)
S4+UL
Thermistor
4-way
3/4/3
Auto
Auto
Wireless LCD
64~86F
2F(1C)
Yes
Yes
24hr , On/Off
Yes
Yes
3
-

Note : : applied
- : not applicable
Filters are optional in some specific areas.
For Circuit Breaker Rating, please conform to local standards whenever necessary.

General Wall Mounted

LS122CE
AS-C121E1H0
3.37
11,500
1,150
10.5
3
10.0
13.0
1/115/60
93
9.3(330)
24(847)
3.0
41/36/34
48
R410A, 930(32.8)
20(0.22)
Rotary
GK113CAA
PSC
FVC68D
330
MRA12053-12027
Cross Flow Fan
21.5
Propeller
BLDC
64.5
20
14:3*2.5
18:4*0.75
6.35(1/4)
12.7(1/2)
21.5 / 16.0(0.85 / 0.63)
895*282*165
35-1/4*11-1/8*6-1/2
770*541*244
30-5/16*21-5/16*9-5/8
9.3(20.5)
33(72.8)
10.5(23.1)
33.3(73.4)
21~46(70~115)
4(13.2) / 15(49.2)
7.0(23)
SE+UL
themistor
4-way
3/4/3
Auto
Auto
Wireless LCD
64~86F
2F(1C)
Yes
Yes
24hr , on/off
Yes
Yes
3
-

LS186CE
AS-C1835SM1
5.2/5.1
17800/17500
2000
C/O:10.4/9.4
2.6
8.9
13.0
1, 230/208, 60
93
15.8(560)
33(1164)
5.3
46/43/41
53
R410A, 1300(45.9)
20(0.22)
Rotary
GKS113KAE, GKS086KAD,
PSC
FVC68D
330
MRA98996-12026 ,MRA12130-12026
Cross Flow Fan
21.5
Propeller
AC Induction
74.5
20
14:3*2.5
18:4*0.75
6.35(1/4)
12.7(1/2)
21.5 / 16.0(0.85 / 0.63)
1090*300*178
42-15/16*11-13/16*7-1/32
871*655*320
34-5/16*25-13/16*12-5/8
13.0(28.6)
56.4(124.3)
16.0(35.3)
60.8(134)
21~46(70~115)
4(13.2) / 20(65.6)
7.0(23)
S5+UE
thermistor
4-Way
3/4/3
Auto
Auto
Wireless LCD
64~86F
2F(1C)
Yes
Yes
24Hr, On/Off
Yes
Yes
3
-

6RMG0-01C

3.Specifications

Sales Model
Models
Cooling Capacity
Heating Capacity
Power Input

Cooling/Heating

Running Current

Cooling/Heating

EER
SEER
HSPF
Power Supply
Power Factor
Air Flow Rate

Indoor,Max
Outdoor,Max

Dehumidification
Sound Level

Indoor,H/M/L
Outdoor,Max
Refrigerant & Charge (at 7.5 m)
Additional Refrigerant charge
Compressor
Type
Model
Motor Type
Oil Type
Oil Charge
O.L.P. name
Fan(Indoor)
Type
Motor Output
Fan(Outdoor)
Type
Motor Type
Motor Output
Circuit Breaker*
Power Supply Cable
Power and Transmission Cable No.*mm2
Piping Connections
Liquid Side
Gas Side
Drain Hose(O.D / I.D.)
Dimensions
Indoor (W*H*D)
Outdoor (W*H*D)
Net Weight
Gross Weight
Operation Range

Indoor
Outdoor
Indoor
Outdoor
Cooling(Outdoor)
Heating(Outdoor)

Unit
kW
Btu/h.
kW
Btu/h.
W

LS093HE
AS-H091E1H1
3.08
10,500
3.08
10,500
1100/1100

LS122HE
AS-H121E1H0
3.37
11,500
3.37
11,500
1150/1150

9.5/9.5

10.5/10.5

W/W
Btu/h.W

2.80
9.5
13.0
7.8
1/115/60
93
9.3(330)
24(847)
3.0
41/36/34
48
R410A, 930(32.8)
20(0.22)
Rotary
GK113CAA
PSC
FVC68D
330
MRA12053-12027
Cross Flow Fan
21.5
Propeller
BLDC
64.5
20
14:3*2.5
18:4*0.75
6.35(1/4)
12.7(1/2)
21.5 / 16.0(0.85 / 0.63)
895*282*165
35-1/4*11-1/8*6-1/2
770*541*244
30-5/16*21-5/16*9-5/8
9.3(20.5)
33(72.8)
10.5(23.1)
33.3(73.4)
21~46(70~115)
1~24(34~75)
4(13.2) / 15(49.2)
7.0(23)
SE+UL
themistor
4-way
3/4/3
Auto
Auto
Wireless LCD
64~86F
60~86F
2F(1C)
Yes
Yes
24hr , on/off
Yes
Yes
3
Yes
Yes

2.6
10
13.0
7.8
1/115/60
93
9.3(330)
24(847)
3.0
41/36/34
48
R410A, 930(32.8)
20(0.22)
Rotary
GK113CAA
PSC
FVC68D
330
MRA12053-12027
Cross Flow Fan
21.5
Propeller
BLDC
64.5
20
14:3*2.5
18:4*0.75
6.35(1/4)
12.7(1/2)
21.5 / 16.0(0.85 / 0.63)
895*282*165
35-1/4*11-1/8*6-1/2
770*541*244
30-5/16*21-5/16*9-5/8
9.3(20.5)
33(72.8)
10.5(23.1)
33.3(73.4)
21~46(70~115)
1~24(34~75)
4(13.2) / 15(49.2)
7.0(23)
SE+UL
themistor
4-way
3/4/3
Auto
Auto
Wireless LCD
64~86F
60~86F
2F(1C)
Yes
Yes
24hr , on/off
Yes
Yes
3
Yes
Yes

/ V / Hz
%
m3/min(CFM)
m3/min(CFM)
pts/h
dB(A)3
dB(A)3
g(oz)
g/m(oz/ft)

cc
W
W
A
No.*mm2
No.*mm2
mm(in)
mm(in)
mm(in)
mm
inch
mm
inch
kg(lbs)
kg(lbs)
kg(lbs)
kg(lbs)
C(F)
C(F)
m(ft)
m(ft)

Piping Length (Min/Max)


Max. Elevation Difference
Tool Code(Chassis)
Indoor + Outdoor
Features
Temperature Control
Air Deflection
Steps, Fan/Cool
Air Deflection Control(up&down)
Air Deflection Control(left&right)
Remocon Type
Setting Temperature Range, Cooling Mode
Heating Mode
Temperature Increment
Auto Operation(electronic control)
Self Diagnosis
Timer
Sleep Operation
Healthy Dehumidification Mode
Restart Delay
Defrost Control
Hot Start

LS186HE
AS-H1835SM1
5.2/5.1
17800/17500
5.2/5.1
17800/17500
2000/2000
C/O:10.4/9.4
H/P:10.4/9.4
2.6
8.9
13.0
7.7
1, 230/208, 60
93
15.8(560)
33(1164)
5.3
46/43/41
53
R410A, 1300(45.9)
20(0.22)
Rotary
GKS113KAE, GKS086KAD,
PSC
FVC68D
330
MRA98996-12026 ,MRA12130-12026
Cross Flow Fan
21.5
Propeller
AC Induction
74.5
20
14:3*2.5
18:4*0.75
6.35(1/4)
12.7(1/2)
21.5 / 16.0(0.85 / 0.63)
1090*300*178
42-15/16*11-13/16*7-1/32
871*655*320
34-5/16*25-13/16*12-5/8
13.0(28.6)
56.4(124.3)
16.0(35.3)
60.8(134)
21~46(70~115)
1~24(34~75)
4(13.2) / 20(65.6)
7.0(23)
S5+UE
themistor
4-way
3/4/3
Auto
Auto
Wireless LCD
64~86F
60~86F
2F(1C)
Yes
Yes
24hr , on/off
Yes
Yes
3
Yes
Yes

Note : : applied
- : not applicable
Filters are optional in some specific areas.
For Circuit Breaker Rating, please conform to local standards whenever necessary.

General Wall Mounted

(Unit : mm)
76, Seongsan-dong, Changwon City, Gyeongnam,
641-713, Korea
www.lge.com/airconditioner

CHASSIS CODE : S4

4. Dimensional Drawings

10

6RMG0-01C

4. Dimensional Drawings

4.1 Indoor Units

General Wall Mounted

1
2

(Unit : mm)

Part name

Air suction grille

Display & signal receiver


Knockout hole

Front Panel

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea
www.lge.com/airconditioner

Item No.

CHASSIS CODE : SE

Remark

General Wall Mounted

6RMG0-01C
4. Dimensional Drawings

General Wall Mounted

11

178

(Unit : mm)
76, Seongsan-dong, Changwon City, Gyeongnam,
641-713, Korea
www.lge.com/airconditioner

CHASSIS CODE : S5

4. Dimensional Drawings

12

6RMG0-01C

General Wall Mounted

(Unit : mm)
76, Seongsan-dong, Changwon City, Gyeongnam,
641-713, Korea
www.lge.com/airconditioner

CHASSIS CODE : UL

6RMG0-01C
4. Dimensional Drawings

4.2 Outdoor Units

General Wall Mounted

13

(Unit : mm)
76, Seongsan-dong, Changwon City, Gyeongnam,
641-713, Korea
www.lge.com/airconditioner

CHASSIS CODE : UE

4. Dimensional Drawings

14

6RMG0-01C

General Wall Mounted

6RMG0-01C

5. Wiring diagrams

5. Wiring diagrams
5.1 Indoor Units
Models : ASNC0914DH1(LSN093CE), ASNH091E1H1(LSN093HE)
ASNC121E1H0(LSN122CE), ASNH121E1H0(LSN122HE)

Models : ASNC1835SM1(LSN186CE), ASNH1835SM1(LSN186HE)

General Wall Mounted

15

5. Wiring diagrams

6RMG0-01C

5.2 Outdoor Unit


Models : ASUC0914DH1(LSU093CE)

Models : ASUC121E1H0(LSU122CE)

16

General Wall Mounted

6RMG0-01C

5. Wiring diagrams

Models : ASUH091E1H1(LSU093HE), ASUH121E1H0(LSU122HE)

Models : ASUC1835SM1(LSU186CE), ASUH1835SM1(LSU186HE)

General Wall Mounted

17

6. Refrigerant cycle diagram

6RMG0-01C

6. Refrigerant cycle diagram


For Cooling only models,
INDOOR UNIT

OUTDOOR UNIT
LIQUID SIDE
CAPILLARY TUBE

HEAT
EXCHANGE
(CONDENSER)

HEAT
EXCHANGE
(EVAPORATOR)

GAS SIDE

COMPRESSOR

For Heat Pump models,


INDOOR UNIT

OUTDOOR UNIT

LIQUID SIDE

CHECK VALVE
(Heating Model only)

3-WAY VALVE
CAPILLARY TUBE
HEAT
EXCHANGE
(CONDENSER)

HEAT
EXCHANGE
(EVAPORATOR)

GAS SIDE
3-WAY VALVE

REVERSING
VALVE
(Heating Model Only)

ACCUMU
LATOR
COMPRESSOR

18

General Wall Mounted

COOLING
HEATING

6RMG0-01C

7. Capacity tables

7. Capacity tables
7.1 Cooling Capacity

AS-C0914DH1(LS093CE)
Indoor Air
Temperature
WBC()
14(57.2)
16(60.8)
18(64.4)
19(66.2)
22(71.6)
24(75.2)

DBC()
20(68)
22(71.6)
25(77)
27(80.6)
30(86)
32(89.6)

20(68)
TC
2.59
2.75
2.91
2.99
3.23
3.39

SHC
1.75
1.72
1.68
1.68
1.58
1.54

Outdoor Air Temperature : DBC()


32(89.6)
35(95)

25(77)
PI
0.45
0.61
0.66
0.66
0.66
0.66

TC
2.48
2.63
2.79
2.87
3.11
3.27

SHC
1.77
1.74
1.70
1.69
1.60
1.55

PI
0.47
0.61
0.66
0.67
0.68
0.69

TC
2.32
2.48
2.64
2.72
2.96
3.11

SHC
1.81
1.77
1.74
1.73
1.63
1.59

PI
0.63
0.74
0.78
0.79
0.80
0.82

TC
2.25
2.41
2.57
2.64
2.88
3.04

SHC
1.84
1.80
1.76
1.76
1.66
1.61

PI
0.70
0.79
0.82
0.81
0.85
0.87

40(104)
TC
2.16
2.31
2.47
2.55
2.78
2.94

SHC
1.83
1.79
1.75
1.75
1.65
1.60

43(109.4)
PI
0.77
0.83
0.84
0.84
0.86
0.87

TC
2.10
2.25
2.41
2.49
2.72
2.88

SHC
1.85
1.82
1.78
1.78
1.68
1.63

PI
1.04
1.13
1.14
1.14
1.16
1.19

TC
2.45
2.63
2.81
2.90
3.18
3.36

PI
1.09
1.18
1.19
1.20
1.21
1.24

TC
2.68
2.88
3.08
3.18
3.48
3.68

SHC
2.63
2.60
2.54
2.54
2.40
2.33

PI
1.90
2.05
2.07
2.08
2.11
2.16

TC
4.13
4.44
4.75
4.90
5.37
5.67

SHC
4.10
4.05
3.96
3.95
3.73
3.62

PI
0.75
0.79
0.79
0.79
0.79
0.81

AS-H091E1H1(LS093HE)
Indoor Air
Temperature
WBC()
14(57.2)
16(60.8)
18(64.4)
19(66.2)
22(71.6)
24(75.2)

DBC()
20(68)
22(71.6)
25(77)
27(80.6)
30(86)
32(89.6)

20(68)
TC
3.02
3.21
3.39
3.48
3.76
3.95

SHC
2.47
2.43
2.38
2.37
2.24
2.17

Outdoor Air Temperature : DBC()


32(89.6)
35(95)

25(77)
PI
0.61
0.82
0.89
0.90
0.90
0.90

TC
2.89
3.07
3.26
3.35
3.63
3.81

SHC
2.50
2.46
2.40
2.40
2.26
2.20

PI
0.63
0.83
0.90
0.91
0.92
0.93

TC
2.71
2.90
3.08
3.17
3.45
3.63

SHC
2.56
2.51
2.46
2.45
2.31
2.25

PI
0.85
1.01
1.06
1.07
1.09
1.11

TC
2.63
2.81
3.00
3.08
3.36
3.55

SHC
2.60
2.55
2.50
2.49
2.35
2.28

PI
0.95
1.08
1.12
1.10
1.15
1.18

40(104)
TC
2.51
2.70
2.88
2.97
3.25
3.43

SHC
2.58
2.54
2.48
2.48
2.34
2.27

43(109.4)
SHC
2.61
2.58
2.52
2.52
2.38
2.31

PI
1.02
1.07
1.07
1.07
1.08
1.10

AS-C121E1H0(LS122CE)/AS-H121E1H0(LS122HE)
Indoor Air
Temperature
WBC()
14(57.2)
16(60.8)
18(64.4)
19(66.2)
22(71.6)
24(75.2)

DBC()
20(68)
22(71.6)
25(77)
27(80.6)
30(86)
32(89.6)

20(68)
TC
3.30
3.51
3.71
3.81
4.12
4.32

SHC
2.49
2.45
2.40
2.39
2.26
2.19

Outdoor Air Temperature : DBC()


32(89.6)
35(95)

25(77)
PI
0.64
0.86
0.93
0.94
0.94
0.94

TC
3.16
3.36
3.57
3.67
3.97
4.17

SHC
2.52
2.48
2.42
2.42
2.28
2.22

PI
0.66
0.87
0.94
0.95
0.97
0.97

TC
2.97
3.17
3.37
3.47
3.77
3.97

SHC
2.58
2.53
2.48
2.47
2.33
2.26

PI
0.89
1.05
1.10
1.12
1.14
1.16

TC
2.88
3.08
3.28
3.37
3.68
3.88

SHC
2.62
2.57
2.52
2.51
2.37
2.30

PI
0.99
1.13
1.17
1.15
1.21
1.23

40(104)
TC
2.75
2.95
3.15
3.25
3.55
3.75

SHC
2.60
2.56
2.50
2.50
2.36
2.29

TC
4.24
4.55
4.86
5.02
5.48
5.79

SHC
4.06
3.98
3.90
3.89
3.67
3.56

43(109.4)
PI
1.07
1.12
1.12
1.12
1.13
1.15

AS-C1835SM1(LS186CE)/AS-H1835SM1(LS186HE)
Indoor Air
Temperature
WBC()
14(57.2)
16(60.8)
18(64.4)
19(66.2)
22(71.6)
24(75.2)

DBC()
20(68)
22(71.6)
25(77)
27(80.6)
30(86)
32(89.6)

20
TC
5.10
5.41
5.73
5.88
6.35
6.67

SHC
3.88
3.81
3.73
3.72
3.52
3.41

Outdoor Air Temperature : DBC()


32
35

25
PI
1.10
1.50
1.62
1.64
1.64
1.63

TC
4.88
5.19
5.50
5.66
6.13
6.44

SHC
3.93
3.86
3.77
3.76
3.56
3.45

PI
1.15
1.51
1.63
1.65
1.68
1.70

TC
4.58
4.89
5.20
5.36
5.82
6.13

SHC
4.01
3.94
3.86
3.85
3.63
3.53

PI
1.55
1.83
1.92
1.94
1.99
2.02

TC
4.44
4.75
5.06
5.20
5.68
5.99

SHC
4.08
4.01
3.92
3.91
3.69
3.58

PI
1.73
1.96
2.03
2.00
2.10
2.14

40

43

n Symbol

n Notes :

AFR: Air flow rate...........................................................[m3/min]


DB: Dry bulb temperature ......................................................[C]
WB: Wet bulb temperature ....................................................[C]
TC: Total capacity.................................................................[kW]
SHC: Sensible capacity ........................................................[kW]
PI: Power Input .....................................................................[kW]
(Comp.+ indoor fan motor+outdoor fan motor)

1. All capacities are net, evaporator fan motor heat is deducted.


2.
Indicates nominal capacity.
3. Direct interpolation is permissible. Do not extrapolate
4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.

General Wall Mounted

PI
1.86
1.95
1.94
1.94
1.96
2.00

19

7. Capacity tables

6RMG0-01C

7.2 Heating Capacity

AS-H091E1H1(LS093HE)
Outdoor Air Temperature : DBC()

Indoor Air
Temperature
DBC()
16(60.8)
18(64.4)
20(68)
21(69.8)
22(71.6)
24(75.2)

-10(14)
TC
2.44
2.43
2.43
2.43
2.43
2.41

PI
0.88
0.90
0.92
0.93
0.95
0.97

-5(23)
TC
2.64
2.64
2.65
2.65
2.64
2.61

0(32)
PI
0.92
0.94
0.97
0.98
1.00
1.02

TC
2.82
2.82
2.81
2.81
2.80
2.78

6(42.8)
PI
0.98
1.01
1.04
1.05
1.06
1.09

TC
3.13
3.11
3.08
3.06
3.04
3.01

10(50)

PI
1.05
1.08
1.10
1.11
1.12
1.14

TC
3.31
3.27
3.25
3.25
3.24
3.19

15(59)
PI
1.10
1.12
1.13
1.14
1.15
1.16

TC
3.59
3.58
3.59
3.56
3.53
3.49

PI
1.15
1.17
1.19
1.19
1.20
1.21

TC
3.93
3.92
3.92
3.90
3.86
3.82

PI
1.99
2.03
2.06
2.07
2.09
2.10

TC
6.06
6.04
6.05
6.01
5.96
5.90

PI
1.17
1.18
1.19
1.19
1.19
1.20

AS-H121E1H0(LS122HE)
Outdoor Air Temperature : DBC()

Indoor Air
Temperature
DBC()
16(60.8)
18(64.4)
20(68)
21(69.8)
22(71.6)
24(75.2)

-10(14)
TC
2.67
2.66
2.66
2.66
2.66
2.64

PI
0.91
0.94
0.96
0.97
0.99
1.02

-5(23)
TC
2.89
2.89
2.89
2.89
2.89
2.86

0(32)
PI
0.96
0.99
1.01
1.03
1.04
1.07

TC
3.09
3.08
3.08
3.07
3.06
3.04

6(42.8)
PI
1.03
1.06
1.09
1.10
1.11
1.14

TC
3.43
3.40
3.37
3.35
3.32
3.30

10(50)

PI
1.10
1.13
1.15
1.16
1.17
1.19

TC
3.62
3.57
3.55
3.55
3.55
3.49

15(59)
PI
1.22
1.23
1.24
1.24
1.24
1.25

AS-H1835SM1(LS186HE)
Outdoor Air Temperature : DBC()

Indoor Air
Temperature
DBC()
16(60.8)
18(64.4)
20(68)
21(69.8)
22(71.6)
24(75.2)

-10(14)
TC
4.11
4.11
4.11
4.11
4.11
4.07

PI
1.59
1.63
1.67
1.70
1.72
1.77

-5(23)
TC
4.46
4.46
4.47
4.47
4.46
4.41

0(32)
PI
1.66
1.71
1.76
1.79
1.81
1.86

TC
4.76
4.76
4.75
4.74
4.72
4.69

6(42.8)
PI
1.79
1.84
1.89
1.91
1.94
1.98

TC
5.29
5.25
5.20
5.17
5.13
5.09

10(50)

PI
1.91
1.96
2.00
2.02
2.04
2.07

TC
5.59
5.52
5.48
5.48
5.47
5.38

15(59)

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.
Correction Factor
Outdoor Air Temperature( CWB, RH=85%)

-10

-6

-4

-2

Correction Factor

0.95

0.95

0.89

0.87

0.87

0.89

0.91

n Notes :
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7CDB/6CWB
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input (Comp.+indoor fan motor+outdoor fan motor) (kW)

20

General Wall Mounted

PI
2.12
2.15
2.16
2.16
2.16
2.18

6RMG0-01C

8. Capacity coefficient factor

8. Capacity coefficient factor


Model: 5k~24kBtu/h Cooling Only
Capacity coefficient factor
Classification

Height

Total Pipe Length(m)

(A)

Outdoor

7.5

10

12.5

15

10

(0.94)

(0.93)

0.97

0.96

(0.95)

(0.94)

0.99

0.98

0.97

(0.96)

(0.95)

1.0

0.99

0.98

(0.97)

(0.96)

1.0

0.99

0.98

(0.97)

(0.96)

0.99

0.98

0.97

(0.96)

(0.95)

0.97

0.96

(0.95)

(0.94)

10

(0.94)

(0.93)

(A)
Indoor
Indoor
(A)
Outdoor

The values in parentheses ( ) are valid only for 18 ~ 24 kBtu models.

Model: 5k~12kBtu/h Heat Pump


Capacity coefficient factor
Classification

Height

Total Pipe Length(m)

(A)

Outdoor
(A)
Indoor
Indoor
(A)
Outdoor

7.5

10

12.5

15

10

0.97

0.97

0.99

0.98

0.97

1.0

0.99

0.98

1.0

0.99

0.98

0.99

0.98

0.97

0.97

0.97

10

General Wall Mounted

21

8. Capacity coefficient factor

6RMG0-01C

Model: 18k~24kBtu/h Heat Pump


Capacity coefficient factor
Height

Classification

Total Pipe Length(m)

(A)
5

7.5

10

12.5

15

10

0.94

0.93

0.97

0.96

0.95

0.94

0.99

0.98

0.97

0.96

0.95

1.0

0.99

0.98

0.97

0.96

Indoor

1.0

0.99

0.98

0.97

0.96

(A)

0.99

0.98

0.97

0.96

0.95

0.97

0.96

0.95

0.94

10

0.94

0.93

Outdoor
(A)
Indoor

Outdoor

Piping Length And Elevation


Pipe Size [mm(in)]

Capacity
[BTU/h]

Liquid side

9K(C/O)

6.35(1/4)

9K(H/P), 12K

6.35(1/4)

12.7(1/2)

7.5(25)

7.0(23)

15(49.2)

20(0.22)

18K

6.35(1/4)

12.7(1/2)

7.5(25)

7.0(23)

20(65.6)

20(0.22)

Gas side

Standard
Length [m(ft)]

Max. Elevation
[m(ft)]

Max. length
[m(ft)]

Additional Refrigerant
[g/m(oz/ft)]

9.52(3/8)

7.5(25)

7.0(23)

15(49.2)

20(0.22)

Outdoor unit

Indoor unit

Oil trap

A
Outdoor unit

Indoor unit

Outdoor unit

Indoor unit

In case more than 5m(16.4ft)

Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7meters (16.4~23.0ft).

22

General Wall Mounted

6RMG0-01C

9. Operation range

9. Operation range
Applied Model : LS093CE, LS122CE, LA096HNP,
LS093HE, LS122HE, LA126HNP
Cooling

Heating

21
(70F)

Low Ambient
Operation

-10
(14F)
18(64F)

24
(75F)

Warming up
Operation

Continuous
operation

Outdoor Unit [C DB]

Outdoor Unit [C DB]

46
(115F)

Continuous
operation

1
(34F)
16(61F)

32(90F)

Indoor Unit [C DB]

30(86F)

Indoor Unit [C DB]

Operative: Intermittent operation due to the operational conditions (indoor/outdoor temperature, humidity, load etc.) can cause the
heating capacity to decrease

Applied Model : LS186CE, LS186HE


Cooling

Heating

Outdoor Unit [C DB]

Continuous
operation

21
(70F)
18(64F)

24
(75F)

Warming up
Operation

Outdoor Unit [C DB]

46
(115F)

Continuous
operation

1
(34F)

32(90F)

Indoor Unit [C DB]

16(61F)

30(86F)

Indoor Unit [C DB]

General Wall Mounted

23

10. Air velocity and temperature distribution(reference data)

6RMG0-01C

10. Air velocity and temperature distribution(reference data)


General Wall Mouted 9kBtu/h
Cooling

Heating

Discharge angle:45

Discharge angle:50

Air velocity [m/s]

2.7m

Air velocity [m/s]

2.7m

2m

2m
1.2
1.0

1.0
1m

1m

0.75
0.75
0.5
5m

4m

3m

2m

0m
0m

1m

Temperature [C]

2.7m

0.5
5m

4m

3m

2m

0m
0m

1m

Temperature [C]

2.7m

2m

23

5m

4m

25
3m

2m

1m

1m

28
29

24
2m

0m
0m

1m

5m

4m

3m

30
2m

0m
0m

1m

General Wall Mouted 12kBtu/h


Cooling

Heating

Discharge angle:45

Discharge angle:50
Air velocity [m/s]

Air velocity [m/s]

1.5
1.25

2.7m

2.7m

2m

2m
1.5
1.25

1m

1.0
0.5
5m

4m

3m

2m

0.75

0.5

1m

23
25
5m

24

4m

0m
0m

5m

4m

3m

0.75

2m

0m
0m

1m

Temperature [C]

Temperature [C]

3m

2m

2.7m

2.7m

2m

2m

1m

30

1m

0m
0m

5m

General Wall Mounted

4m

3m

1m

29

28

24

1m

1.0

2m

1m

0m
0m

6RMG0-01C

10. Air velocity and temperature distribution(reference data)

General Wall Mouted 18kBtu/h


Cooling

Heating

Discharge angle:45

Discharge angle:50

Air velocity [m/s]

Air velocity [m/s]

1.5

8m

7m

6m

5m

4m

0.5
3m

2.7m

2.7m

2m

2m

1.25
0.75 1.0
2m

0.5

1m

0m

Temperature [C]

7m

6m

8m

7m

6m

5m

4m

3m

0.75
2m

1m

1.25
1.0
1m

0m

Temperature [C]

23

8m

1.5

1m

5m

25
4m

2.7m

2.7m

2m

2m
31

1m

24
3m

2m

29

28
1m

0m

8m

7m

General Wall Mounted

6m

5m

4m

3m

2m

1m

30
1m

0m

25

11. Controller

6RMG0-01C

11. Controller
Remote Control Operations
Controls
Signal transmitter

6
3
4
2
7
11
8
13

10
CANCEL
ON

OFF

9
12

SET
AUTO CLEAN

17
18
14
16

15

Flip-up door
(opened)

Operation Mode
Cooling Operation
Auto Operation or Auto Changeover

Healthy Dehumidification Operation


Heating Operation

Cooling Model(

26

), Heat Pump Model(

1. START/STOP BUTTON
Operation starts when this button is pressed
and stops when the button is pressed again.
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps
low, medium, high and CHAOS.
5. JET COOL
Used to start or stop the speed cooling.(speed
cooling operates super high fan speed in cooling
mode.)
6. CHAOS SWING BUTTON
Used to stop or start louver movement and set
the desired up/down airflow direction.
7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping
operation. (See page 22)
8. TIME SETTING BUTTONS
Used to adjust the time. (See page 22)
9. TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is
obtained and to cancel the Timer operation.
(See page 22)
10. SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
(See page 22)
11. AIR CIRCULATION BUTTON
Used to circulate the room air without cooling
or heating. (See page 23)
12. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
13. NEO PLASMA(OPTIONAL)
Used to start or stop the plasma-purification
function. (See page 20)
14. HORIZONTAL AIRFLOW DIRECTION
CONTROL BUTTON (OPTIONAL)
Used to set the desired horizontal airflow
direction.
15. RESET BUTTON
Used prior to resetting time.
16. 2nd F Button
Used prior to using modes printed in blue at
the bottom of buttons. (See page 21)
17. AUTO CLEAN (OPTIONAL)
Used to set Auto Clean mode.
18. C TO F SWITCHING BUTTON
Used to switch temperature reading from
Centigrade to Fahrenheit.

General Wall Mounted

6RMG0-01C

12. Installation

12. Installation
Installation Map
NOTICE
Installation parts you should purchase.

Installation Plate
Sleeve
Bushing-Sleeve
Putty(Gum Type Sealer)
Bend the pipe as closely
on the wall as possible,
but be careful that it
doesn't break.

Air Discarge
Vertical Air deflector
Operation Indication Lamps/
Signal Receptor
Forced Operation Button
Saddle

Vinyl tape(Wide)
Apply after carrying out a
drainage test.
To carry out the drainage
test, remove the air filters
and pour water into the heat
exchanger.

Gas side piping


Liquid side piping

Air Inlet Vents

Additional drain pipe

Air Outlet Vents

Drain Hose
Connecting cable
Base Plate

NOTE: refrigerant line wall thickness must be at least 0.8 mm (0.031 inch)

General Wall Mounted

27

12. Installation

6RMG0-01C

Select The Best Location


Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front
of the unit.
3. Make sure that condensation drainage can be conveniently routed away.
4. Do not install near a doorway.

More than
30cm(11.8in)

5. Ensure that the space around the left and right of the
unit is more than 30cm(11.8in). The unit should be
installed as high on the wall as possible, allowing a
minimum of 20cm(7.9in) from ceiling.

More than
20cm(7.9in)
More than
30cm(11.8in)

More than 2.4m(8ft)

6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.

Install the indoor unit on the wall where the height from the floors more than 1.5meters(4.9ft).
A minimum pipe run of 7.5meters(24.6ft) is required to minimize vibration and excessive noise.

Outdoor unit
1. If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure that the space around the back and sides is
more than 30cm(11.8in). The front of the unit should
have more than 70cm(27.6in) of space.
3. Do not place animals and plants in the path of the
warm air.
4. Take the air conditioner weight into account and
select a place where noise and vibration are minimum.

More than
60cm(23.6in)
More than
30cm(11.8in)

More than
70cm(27.6in)

More than
30cm(11.8in)

More than
60cm(23.6in)

5. Select a place so that the warm air and noise from


the air conditioner do not disturb neighbors.

Rooftop Installations
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring
method are adequate for the unit location. Consult local codes regarding rooftop mounting.
If the outdoor unit is installed on roof structures or walls, this may result in excessive noise and vibration, and may
be also classed as non serviceable installation.

28

General Wall Mounted

6RMG0-01C

12. Installation

How To Mount Installation Plate


The wall you select should be strong and solid enough to
prevent vibration

Installation Plate

1. Mount the installation plate on the wall with


type "A" screws. If mounting the unit on a concrete wall,
use anchor bolts.
Mount the installation plate horizontally by aligning the
centerline using a level.

Chassis
Hook
Type A

<Type 1>
Installation Plate

2. Measure the wall and mark the centerline. It is also


important to use caution concerning the location of the
installation plate-routing of the wiring to power outlets is
through the walls typically. Drilling the hole through the
wall for piping connections must be done safely.

Chassis
Hook

Type A

<Type 2>

CHASSIS
(Grade)
S4
SE
S5/S8

Distance (mm)(in)
A
55(2.17)

B
105(4.13)

C
65(2.56)

D
105(4.13)

70(2.76) 110(4.33) 90(3.54) 110(4.33)


100(3.94) 122(4.80) 240(9.45) 122(4.80)

Installation plate

D
70mm C
(2.76in) Left rear piping

<Type 1>

B
A

<Type 1>

70mm

Right rear piping (2.76in)

Installation plate
70mm

70mm

(2.76in)

(2.76in)

133mm
(5.24in)

100mm

<Type 2>

Left rear piping

(3.94in)
Right rear piping

Drill a Hole In The Wall


WALL
Outdoor

General Wall Mounted

(0.2~0.3")

Indoor

5-7mm

Drill the piping hole with a 70mm(2.76in) hole core drill.


Drill the piping hole at either the right or the left with the
hole slightly slanted to the outdoor side.

29

12. Installation

6RMG0-01C

Flaring Work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.

Cut the pipes and the cable.


1. Use the piping kit accessory or the pipes purchased locally.
2. Measure the distance between the indoor and the outdoor
unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5m(59.1in) longer than the pipe length.

Copper
pipe

Slanted Uneven Rough

90

Pipe

Burrs removal

Reamer

1. Completely remove all burrs from the cut cross section of


pipe/tube.
2. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs
into the tubing.

Point down

Putting nut on

Flare nut

Remove flare nuts attached to indoor and outdoor unit, then


put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)

Copper tube

Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.

Outside diameter
mm
inch
6.35
1/4
9.52
3/8
12.7
1/2
15.88
5/8

A
mm
1.1~1.3
1.5~1.7
1.6~1.8
1.6~1.8

Bar

Handle

"A"

Carry out flaring work using flaring tool as shown below.

Bar
Yoke
Cone

Copper pipe
Clamp handle

30

General Wall Mounted

Red arrow mark

6RMG0-01C

12. Installation

Connecting The Piping


Indoor
1. Prepare the indoor unit's piping and drain hose for
installation through the wall.
2. Remove the plastic tubing retainer(see the illustration
by) and pull the tubing and drain hose away from
chassis.
3. Replace only the plastic tubing holder 1, not the holder 2 in the original position.

For left rear piping


Route the indoor tubing and the drain hose in the direction of rear left.

2
Connecting
cable

Insert the connecting cable into the indoor unit from the
outdoor unit through the piping hole.

Drain pipe

Do not connect the cable to the indoor unit.


Make a small loop with the cable for easy connection
later.
Tape the tubing, drain hose and the connecting cable. Be
sure that the drain hose is located at the lowest side of the
bundle. Locating at the upper side can cause drain pan to
overflow inside the unit.
NOTE: If the drain hose is routed inside the room, insulate
the hose with an insulation material* so that dripping from
"sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.

Indoor unit installation

Hook the indoor unit onto the upper portion of the


installation plate.(Engage the three hooks of the rear
top and rear lower of the indoor unit with the upper
edge and lower edge of the installation plate.) Ensure
that the hooks are properly seated on the installation
plate by moving it left and right.

Indoor unit
Spacer
Installation plate
8cm

General Wall Mounted

31

12. Installation

6RMG0-01C

Connecting the pipings to the indoor unit and drain


hose to drain pipe.

Wrap the insulation material around the connecting portion.

Put a couple drops of refrigerant oil on the face of the flare


before assembling taking care not to add any contaminants.
Align the center of the pipings and sufficiently tighten the
flare nut by hand.

Overlap the connection pipe insulation material and the


indoor unit pipe insulation material. Bind them together with
vinyl tape so that there is no gap.
Plastic bands Insulation material

Indoor unit tubing

Flare nut

Pipings

Tighten the flare nut with a wrench.


Indoor unit tubing

Wrap the area which accommodates the rear piping housing section with vinyl tape.

Torque wrench

Connection pipe

Indoor
unit pipe

Connection
pipe

Flare nut

Vinyl tape
(wide)

Wrap with vinyl tape

Spanner (fixed)
Connecting cable

Outside diameter
mm
inch

6.35
9.52
12.7
15.88

1/4
3/8
1/2
5/8

Torque
kgfm
1.8~2.5
3.4~4.2
5.5~6.6
6.3~8.2

Pipe
Vinyl tape(narrow)

Bundle the piping and drain hose together by wrapping


them with vinyl tape over the range within which they fit into
the rear piping housing section.

Mount the clamp on the boss with a type "B"


screw.(SE-H/P: 9k, 12k C/O: 12k)

Wrap with vinyl tape


Type "B" screw

Drain hose

Clamp

Pipe

Boss

Vinyl tape(wide)

When extending the drain hose at the indoor unit, install the
drain pipe.

Drain hose

For right rear piping


Drain pipe

Route the indoor tubing and the drain hose to the


required piping hole position.
Indoor unit drain hose
Adhesive

Vinyl tape(narrow)

Drain hose

32

General Wall Mounted

6RMG0-01C

12. Installation

Insert the connecting cable into the indoor unit.


Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.

Spanner (fixed)
Flare nut

Tape the drain hose and the connecting cable.

Connection pipe

Torque wrench

Connecting cable

Indoor unit tubing

Outside diameter
mm
inch

6.35
9.52
12.7
15.88

Tape
Connecting
pipe
Drain hose

Connecting cable

Torque
kgfm
1.8~2.5
3.4~4.2
5.5~6.6
6.3~8.2

1/4
3/8
1/2
5/8

Mount the clamp on the boss with a type "B"


screw.(SE-H/P: 9k, 12k C/O: 12k)
Type "B" screw

Indoor unit installation

Drain hose

Clamp
Boss

Hook the indoor unit onto the upper portion of the installation plate.(Engage the three hooks of the rear top and rear
lower of the indoor unit with the upper edge and lower edge
of the installation plate.) Ensure that the hooks are properly
seated on the installation plate by moving it left and right.

When extending the drain hose at the indoor unit,


install the drain pipe.

Drain hose

Connecting
cable

Indoor unit drain hose

Drain hose

Adhesive

Vinyl tape (narrow)

Wrap the insulation material around the connecting portion.


Connecting the pipings to the indoor unit and the drain
hose to drain pipe.
Put a couple drops of refrigerant oil on the face of the flare
before assembling taking care not to add any contaminants
Align the center of the pipings and sufficiently tighten the
flare nut by hand.

Indoor unit tubing

Flare nut

Overlap the connection pipe heat insulation and the indoor unit
pipe heat insulation material. Bind them together with vinyl
tape so that there is no gap.
Plastic bands Insulation material

Pipings

Tighten the flare nut with a wrench.

General Wall Mounted

33

12. Installation

6RMG0-01C

Wrap the area which accommodates the rear piping housing section with vinyl tape.
Indoor
unit piping

Connection
pipe
Vinyl tape
(wide)

Reroute the pipings and the drain hose across the


back of the chassis.

Wrap with vinyl tape

Piping for
passage through
piping hole

Pipe
Vinyl tape(narrow)
Connecting cable

Reroute the pipings and the drain hose across the


back of the chassis.

Bundle the piping and drain hose together by wrapping


them with cloth tape over the range within which they fit into
the rear piping housing section.

Drain hose

Pipe
Drain hose
Vinyl tape(narrow)

Wrap with
vinyl tape(wide)

34

Connecting
cable

General Wall Mounted

6RMG0-01C

12. Installation

Installation Information. For left piping. Follow the instruction below.

Correct case
Press on the upper side of clamp and unfold the tubing to downward slowly.

Incorrect case
Following bending type from right to left may cause damage to the tubing.

General Wall Mounted

35

12. Installation

6RMG0-01C

Connection Of The Drain Hose


The drain hose can be connected at two different positions. Use the
most convenient position and, if necessary, exchange the position
of the drain pan, rubber cap and the drain hose.
Drain pan
Rubber cap
Drain hose
Exchange if necessary
Remove the drain hose.
Securely insert both the rubber plug and drain hose into the drain
outlets.
Be sure the rubber the cap is securely fastened so that there is no
leakage.

2
4
3

Connection Of Piping -Outdoor


Put a couple drops of refrigerant oil on the face of the flare
before assembling taking care not to add any contaminants.
Align the center of the pipings and sufficiently tighten the
flare nut by hand.

Outdoor unit
Suction Line piping
(Bigger diameter)

Evaporator Line
piping
(Smaller
diameter)

Finally, tighten the flare nut with torque wrench until the
wrench clicks.
When tightening the flare nut with torque wrench, ensure the
direction for tightening follows the arrow on the wrench.
Outside diameter
mm
inch

6.35
9.52
12.7
15.88

36

1/4
3/8
1/2
5/8

Torque
kgfm
1.8~2.5
3.4~4.2
5.5~6.6
6.3~8.2

General Wall Mounted

Torque wrench

6RMG0-01C

12. Installation

Connection Of The Cable


1. Remove the cover control from the unit by loosening
the 3 screws.
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on the conduit
panel.

Wiring Diagram
Indoor Unit
Terminal
(4P)

4. Properly connect both the power supply and low


voltage lines to the corresponding terminals on the
terminal block.

Connecting cable(Low voltage) b

Outdoor Unit
Terminal
(6P)
1

Power supply a

L1* 5
L2 6

5. Ground the unit in accordance with local codes.

6. Be sure to size each wire allowing several inches


longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.

To
branch
circuit
Ground

* L1 is neutral for 115V models.


NOTE
Connector trade size for this unit is 1/2"
for instructions on connecting depending on the
wire type you are using.

WARNING
Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant
tubing, the compressor or any moving parts.

NOTE

1.
shows field wiring.
2. Separately wire the high and low voltage line.
3. Use heat-proof electrical wiring capable of withstanding
temperatures up to 167F.
4. Use outdoor and waterproof connection cable rated more
than 300V for the connection between indoor and outdoor
unit.
(For example, Type STOW)

Outdoor unit
Terminal block

Over 5mm
(0.2")

Power Supply
Model

Power source

9k(C/O)
9K(H/P),12k
18k
24k

1,115V
1,115V
1,230/208V
1,230/208V

AWG(MIN.) Fuse or breaker

Capacity
14
14
14
12

18
18
18
18

Conduit panel
Connecting
cable

15A
20A
20A
30A

Power supply
cord
Cover control

General Wall Mounted

37

12. Installation

6RMG0-01C

Checking The Drainage


Pour a glass of water on the drain pan.
Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

Connecting area
drain hose

Leakage
checking
Drain pan

Drain
hose
Leakage
checking

Drain piping
The drain hose should point downward for easy drain flow.
Downward slope

Avoid these situations.

Accumulated
drain water
Air

Do not raise

Water
leakage

38

Water
leakage

Waving

Tip of drain hose


dipped in water
Water
leakage

General Wall Mounted

Ditch

Less than
50mm gap

6RMG0-01C

12. Installation

Forming The Piping


Form the piping by wrapping the connecting portion of
the indoor unit with insulation material and secure it
with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of
the drain outlet should be routed above the ground. Secure
the drain hose appropriately.

In cases where the Outdoor unit is installed above the


Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap
to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.

In cases where the outdoor unit is installed below the


indoor unit perform the following.
Tape the piping, drain hose and connecting cable from
down to up.
Secure the tapped piping along the exterior wall using
saddle or equivalent.

Seal small openings


around pipings with a
gum type sealer.

Seal a small opening


around the pipings
with gum type sealer.
Trap

Trap

Taping
Drain
hose

Pipings
Connecting
cable

Trap is required to prevent water


from entering into electrical parts.

General Wall Mounted

39

12. Installation

6RMG0-01C

Air Purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any
noncondensables and moisture from the system.

Air purging With Vacuum Pump


Preparation
Check that each tubing(both liquid and gas side tubes)
between the indoor and outdoor units have been properly connected and all wiring for the test run has been
completed. Remove the service valve caps from both
the gas and the liquid side on the outdoor unit. Note
that both the liquid and the gas side service valves on
the outdoor unit are kept closed at this stage.

Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off the soap with a
clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the
nitrogen cylinder. When the system pressure is reduced to
normal, disconnect the hose from the cylinder.

Leak test
Connect the manifold valve(with pressure gauges) and
dry nitrogen gas cylinder to this service port with
charge hoses.

Indoor unit

Manifold valve
Pressure
gauge
Lo
Hi

CAUTION

Be sure to use a manifold valve for air


purging. If it is not available, use a stop
valve for this purpose. The "Hi" knob of
the manifold valve must always be kept
close.

Outdoor unit

Nitrogen gas
cylinder(in vertical
standing position)

Pressurize the system to no more than 150 P.S.I.G. with


dry nitrogen gas and close the cylinder valve when the
gauge reading reached 150 P.S.I.G. Next, test for leaks
with liquid soap.
CAUTION

To avoid nitrogen entering the refrigerant system in


a liquid state, the top of the cylinder must be higher
than its bottom when you pressurize the system.
Usually, the cylinder is used in a vertical standing
position.

40

Charge hose

General Wall Mounted

6RMG0-01C

12. Installation

Soap water method


(1) Remove the caps from the gas side and liquid side
valves.
(2) Remove the service-port cap from the gas side
valve.
(3) To open the gas side valve turn the valve stem
counterclockwise approximately 90, wait for about
2~3 seconds, and close it.
(4) Apply a soap water or a liquid neutral detergent on
the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the
connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.

Suction Line

Evaporator Line
3-way valve
(Close)
3-way valve
(Open)

Cap
Hexagonal wrench

Evacuation
Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing
and indoor unit.
Confirm the "Lo" knob of the manifold valve is open.
Then, run the vacuum pump.
The operation time for evacuation varies with tubing
length and capacity of the pump. The following table
shows the time required for evacuation.

Indoor unit

Required time for evacuation when 30 gal/h vacuum pump is used


If tubing length is less
than 10m (33 ft)
10 min. or more

if tubing length is longer


than 10m (33 ft)

Outdoor unit

15 min. or more

When the desired vacuum is reached, close the "Lo"


knob of the manifold valve and stop the vacuum pump.

Finishing the job


With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter-clockwise to
fully open the valve.
Loosen the charge hose connected to the gas side service
port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service
port and fasten the flare nut securely with an adjustable
wrench. This process is very important to prevent leakage
from the system.
Replace the valve caps at both gas and liquid side service
valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.

Manifold valve
Pressure
gauge

Lo

Hi

Open

Close

Vacuum pump

General Wall Mounted

41

13. Installation Guide at the Seaside

6RMG0-01C

13. Installation Guide at the Seaside


CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.

Selecting the location(Outdoor Unit)


1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.

Sea wind

Sea wind

2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

Windbreak

It should be strong enough like concrete to prevent


the sea wind from the sea.
The height and width should be more than 150% of
the outdoor unit.

Sea wind

It should be keep more than 70 cm of space


between outdoor unit and the windbreak for easy
air flow.

3) Select a well-drained place.


1. If you cant meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water

42

General Wall Mounted

P/No.: 3828A20801X

Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com

All rights reserved


Printed in Korea Oct/2010
The specifications, designs, and
information in this brochure are subject to
change without notice.