FireandSmokeDamperControl
Theinnerworkingsofcontrolsandactuatorsinthreetypesoffireandsmoke
dampersareexplained
ByLARRYFELKER,BelimoAmericas,Sparks,Nev.
SHARE

Tweet

Recommend

Jan1,2008
1

COMMENTS 1

TheNo.1questionaboutfireandsmokedampersthatmechanicalengineersand
contractorsaskis,Howdothecontrolsworkwiththeactuators?Thisarticleexplains
that.
DAMPERTYPES

Wemustclearlydistinguishamongthreetypesofdampers.
http://hpac.com/firesmoke/fire_smokedamper_control

1/12

12/14/2015

FireandSmokeDamperControl

Firedampers

Firedampers,whichrarelyareactuated,closewhenariseintemperatureoccursandstay
shuttostopfirefrompassingthroughabarrier.About90percentoffiredampersare
curtaintypedampersthatclosewhenamechanicalfusiblelinkmelts,releasingaclosing
mechanism.Adampermustbeintheplaneofafirewall,althoughsomejurisdictions
makeexceptionsifductsareheavyduty.Outofpartitiondampersareavailablefrom
mostmanufacturers.

LatestWhitePapers
WHITE

OCT30,2015

PAPER

DiamondControls
SolutionsEmpowering
InnovativeBuilding
Management
WHITE

MAR19,2014

PAPER

EvolvingEnergy
Efficiency
Regulationsfor
HVACR

PHOTOA.Curtainfiredampers.

Inafewcases,auxiliarycontactsareneededtoproveopeningandclosinginperiodic
testing.Damperswithbladeswitchesoractuatorswithinternalauxiliaryswitchesprovide
proofofclosure.
Firedampersnormallyclosewhenthetemperatureofthefusiblelinkreaches165F,
althoughsomelocalvariationsexist.Forexample,ifsteamcoilsarepresentinducts,use
ofa212Fhighlimitmaybeused.Thefiredampertemperaturethenmayriseacouple
thousanddegrees,butthedamperwillholdforthetimeratingforwhichitwasdesigned.
Eachyear,severalmillionfiredampersareinstalledinbarriersdesignedtoslowthe
spreadoffire(PhotoA).

Webinars

Smokedampers
SEP15,2015
http://hpac.com/firesmoke/fire_smokedamper_control

2/12

12/14/2015

FireandSmokeDamperControl

Smokedampers,whichareactuated,mustopenandclosewhenrequiredtoprovidefresh
airortostopsmokepassage.Theydonothavetohavehighlimitsensorsorfusiblelinks
tocloseautomatically.Smokedampersoftenprovidesignalingforindicatorlights,as
discussedlaterinthisarticle.

WEBINAR

ANewEraof
Efficiency:Advances
inWaterSourceVRF
Technology
AUG11,2015
WEBINAR

ImprovingHVAC
EnergyEfficiency
ThroughAccurate
Humidity
Measurement
JUL22,2015
WEBINAR

HowtoGettheMost
OutofYourBuilding
AutomationSystem
withService

PHOTOB.Asmokedamper.

Practicesvarybygeographicalregionandbytypeofsmokecontrolmandatedbycodes.
Mostcommonly,asmokedetector(ortwo)insideofductswillshutdownfansandclose
dampersifsmokeisdetected.Areasmokedetectorssometimesarewiredtoacentralfire
alarmpanel,whileapanelcontactorremoterelayinitiatesclosing.
Smokedampersdonotneedtobewithinawallprovidingasmokebarriertheymerely
needtobewithin24in.ofthewall.Asaresult,theactuatorsmaybeaxleshaftmounted.
However,mostarejackshaftmountedwithlinkagetothedamperblades(PhotoB).
Combinationfireandsmokedampers

Becausecombinationfireandsmokedampers,whicharemorecommonthansimple
smokedampers,arefirerated,theirbladesmustbeinabarrierwall.Theactuatorcannot
beinthewall,soajackshaftandlinkageareemployedwiththeactuatorconnectedtothe
jackshaftextensionoutsideofthedampersleeve.(Thereareothermethods.However,this
http://hpac.com/firesmoke/fire_smokedamper_control

ViewAll

Blogs&Opinions
Blogs

Columns

FundingHVACREnergyEfficiency
ResearchandDevelopment
byLawrence(Larry)Clark,
QCxP,GGP,LEEDAP+
Posted6daysago
inClark'sRemarks

GivingThanks
3/12

12/14/2015

FireandSmokeDamperControl

isstandardintheUnitedStates.)Almostallcurrentactuatorsaredirectcoupled.

byLawrence(Larry)Clark,
QCxP,GGP,LEEDAP+

Page2of3

Posted2weeksago
inClark'sRemarks

AcceleratingEnergyProductivity
byLawrence(Larry)Clark,
QCxP,GGP,LEEDAP+
Posted4weeksago
inClark'sRemarks

FIGURE1.Acombinationfireandsmokedamperopen.

BASICCONTROL

Thereareseveralacceptedmethodsoftemperaturesensingandactuatorcontrol.A
fusiblelinkthatrestrainsashaftspringcanperformthefiredamperfunctionwhilean
actuatorprovidesthesmokecontrolfunction.Thefusiblelinkdisconnectsthedamper
bladesfromtheactuatorandensuresitsclosure.Theactuatorcanopenandclosefor
smokemanagementonlyuntilthefusiblelinkmelts.Alternately,anelectricbimetalsensor
witharesetbuttoncanbeusedforthesingleprimarysensor.
http://hpac.com/firesmoke/fire_smokedamper_control

4/12

12/14/2015

FireandSmokeDamperControl

ThesysteminFigure1isfoundinabout80percentofthecombinationfireandsmoke
dampersonthemarkettoday.Asmokedetectorwithalocalthermalsensorisusedas
showninFigure1,whichisacontainmentdamperapplication.
REOPENABLEDAMPERS

Anengineeredsmokecontrolsystemwithreopenabledampersislesscommon.These
haveprovisionsforafirefightertocontrolthedampersmoreprecisely.
Combinationfireandsmokedampersinsmokecontrolsystemshavetwosensors
primaryandsecondary.Theprimarycanbeoverriddenbyfirefighters'controlthe
secondaryismanuallyresetatthedamperonly.
Whenadualsensorisused,thefirstsensoralwaysiselectric.Itopens,removespower,
andletstheactuatorspringthedamperclosed.Thesecondsensormaybeafusiblelinkor
ahighertemperatureelectricsensor.Typically,aprimarysensorwillregister165Fbefore
closingadamper,whilethesecondarysensorwillregister250F.Inabout15percentof
cases,thesecondarysensorwillregister350F.

Signuptoreceiveourfreenewsletters
HPACEngineeringFastrack
(BiWeekly)ViewSample
HPACEngineeringGreenBuildings
(Monthly)ViewSample
FireProtectionEngineeringEmerging
Trends(Monthly)ViewSample
ProductSpotlight(Monthly)View
Sample
EMAIL*
COUNTRY*

UnitedStates

Enteryouremailabovetoreceivemessagesabout
offeringsbyPenton,itsbrands,affiliatesand/orthird
partypartners,consistentwithPentonsPrivacyPolicy.

ConnectWithUs

FIGURE2.dualsensorreopenabledamperwiring.

http://hpac.com/firesmoke/fire_smokedamper_control

TwitterFacebook
LinkedIn
RSS

5/12

12/14/2015

FireandSmokeDamperControl

ThewiringofadualsensorcombinationfireandsmokedampercanbeseeninFigure2.
Ifafireweretobreakoutandducttemperatureweretoincreaseto165F,thedamper
wouldspringclosedtokeepthefirefromspreading.However,firefighterscouldchooseto
reopenthedamperforsmokecontrolpurposes.Ifthetemperaturereachedthe250F
(sometimes350F)limit,poweragainwouldbecutoffandtheactuatorwouldspring
closed.Itcouldnotbeopenedagainuntilaresetbuttonwerepressed.Firefightersalso
couldcloseanopendampertopreventoxygenfromfeedingafireorairpressurefrom
pushingsmokeintootherareas.
Originaldampershadreleasemechanismsthatonlyincludedexternalsprings.Actuators
didnothaveaninternalspring.Later,afusiblelinkanddualspringswerestandard.One
firespringwasusedtoclosethedamperuntilthefusiblelinkcouldbereplaced,whilea
separateactuatorspringwasusedtoclosethedamperiftheactuatorlostpower,
althoughtheactuatorcouldreopenagainstthespring.Now,mostmanufacturersuse
electronicmethodsofsensingandcontrol.Theactuatorspringistheonlyspringinmost
recentdesigns.
Page3of3
INDICATORLIGHTS

Afirefighters'smokecontrolsystem(FSCS)hasstatusindicationlightsinadditionto
manualhandoffautoswitches.Thelightsallowforverificationofdamperpositionand
overridestatus.Theycanbeinitiatedfromauxiliaryswitchesonanactuator,damper
bladeswitches,orproximityswitches.
Actuatorswitchesoftenarepreferred,astheyareasreliableasbladeswitchindication.
Thelinkagebetweenactuatorjackshaftanddamperismorerobustthanthetypicalcoat
hangerconnectionfromdamperbladetoswitchpackage.
Fullyengineeredsmokecontrolsystemsexistinaboutonly10percentofapplications.
Firefightershavecontrolofdampersinthesesystems.Indicatorlightsshowthesystems'
http://hpac.com/firesmoke/fire_smokedamper_control

6/12

12/14/2015

FireandSmokeDamperControl

status.
Figure3showsasimplemethodofindicatorlightwiring.Thelightscouldbeinapanel
orlocaljunctionbox,whichcouldbelocatedintheceiling.AnFSCSpanelalsowould
haveanamberlightindicatingfault.Ifthedamperwereclosed,theredlightwouldbe
on.Ifthedamperwereopen,thegreenlightwouldbeon.Avarietyofwiringmethodsare
possible.

FIGURE3.Indicationlightwiringforasingledamper.

Insomejurisdictions,theredlightmeansfireorproblem,whilethegreenlightmeans
OK.Inotherareas,greenmeanson,andredmeansoff,particularlyforfans.
Althoughrare,somedampersnormallyareopenwhennotpowered,andtheredand
greenlightscouldbeswitched.Thiscanconfuseafirefighterduringthecommotionofa
fire.Indicationlightsshouldbediscussedwithalocalfiredepartmenttoensurecorrect
operation.
http://hpac.com/firesmoke/fire_smokedamper_control

7/12

12/14/2015

FireandSmokeDamperControl

PROPORTIONALDAMPERCONTROL

Figure4showstwoproportionalapplications.Thepressureinastairwellorductmay
needtobecontrolledatacertainsetpoint.Asmokedamperisrequiredifawallalsois
partofasmokebarrier.Giventypicalspaceconstraints,onedamperandactuatorare
technicallyandeconomicallysuperiortotwo(orthree,ifawallalsoisafirebarrier).

FIGURE4.Proportionalapplications.

Therearetwowaystoprovideproportionaldampercontrol:
NoproportionalelectricactuatormeetsUniformBuildingCode(UBC)criteriafor
15secofoperation.TheseactuatorscannotbeinstalledinUBCregions(which
currentlyareCaliforniaandafewoutsidecities).Inthesecases,twodampersare
http://hpac.com/firesmoke/fire_smokedamper_control

8/12

12/14/2015

FireandSmokeDamperControl

required.Atwopositionfireandsmokedampersitsintheratedwall.Astandard
proportionaldamperandactuatorareinstalledinseries.
InInternationalBuildingCoderegions,aproportionalfireandsmokedamperand
actuatorcanbeinstalledbecausethecode(basedonUnderwritersLaboratories
555S,StandardforSmokeDampers)requiresa75secmaximumforoperation.
Actuatorsthatmeetthe75secrequirement(20sectospringclosed,75sectodrive
open)areavailable.
CONCLUSION

Thetypeofdamperuseddependsontheapplication.Actuationisprovidedforsmoke
controldampersandcombinationfireandsmokedampers.Containmentsystemsarethe
mostcommon,whilereopenabledampersprovidefiredepartmentswithmoreoptions.
Byfollowingthewiringdiagramsinthisarticleandcomparingthemwiththesequenceof
operation,onecangainanunderstandingoftheoperationrequirementsforinterfaces
betweenmechanicalandcontrolsystems.
Codesandpracticesdiffergeographically.Oneshouldconsultlocalinspectors,
contractors,andrepresentativeswithspecificquestions.Themethodsshowninthisarticle
aretypical,althoughpracticesmayvary.

LarryFelkerisaproductmanagerforBelimoAmericas.Heisamemberofthe
InternationalCodeCouncil,theNationalFireProtectionAssociation,andtheAmerican
SocietyofHeating,RefrigeratingandAirConditioningEngineers(ASHRAE).Heserves
onASHRAETechnicalCommittee(TC)1.4:ControlTheoryandApplicationandisa
correspondingmemberofASHRAETC5.6:ControlofFireandSmoke.

http://hpac.com/firesmoke/fire_smokedamper_control

9/12

12/14/2015

FireandSmokeDamperControl

SHARE
PRINT

REPRINTS

Tweet

Recommend

FAVORITE EMAIL

DiscussthisArticle

Anonymous(notverified)

onJan20,2013

veryhelpful.thankyousomuch!
reply

POSTINGAS:

abco

(SignOut)
YOURCOMMENT:*

SUBMITCOMMENT

http://hpac.com/firesmoke/fire_smokedamper_control

10/12

12/14/2015

FireandSmokeDamperControl

Newsletter Signup
Signuptoreceiveourfreenewsletters
HPACEngineeringFastrack(BiWeekly)ViewSample
EMAIL*
COUNTRY*

UnitedStates

EnteryouremailabovetoreceivemessagesaboutofferingsbyPenton,itsbrands,affiliatesand/orthirdpartypartners,
consistentwithPentonsPrivacyPolicy.

Related Articles
MotorizedFireandSmokeDampers
PracticalApplicationsofSmokeControlSystems
SmokeControlinaNonductedReturnairSystem
ASHRAELaunchesOnlineDiscussionForum
ASHRAESeekingPapersfor2015WinterConferenceinChicago

HPAC.com
AirConditioning BuildingControls Fire/Smoke Heating HumidityControl IAQ&Ventilation Motors/Drives Piping/Pumping
http://hpac.com/firesmoke/fire_smokedamper_control

11/12

12/14/2015

FireandSmokeDamperControl

Site Features

HPAC Engineering Corporate

MediaCenter

PrivacyPolicy

RSS

TermsofService

Sitemap

Contact

SiteArchive

Follow Us

Newsletters

Search HPAC.com

ViewMobileSite

Mechanical Systems Sites


ContractingBusiness Contractor HVACTalk Comfortech2013Show HVACRDistributionBusiness RadiantLiving
FireProtectionEngineering

Copyright2015Penton

http://hpac.com/firesmoke/fire_smokedamper_control

12/12

You might also like