Professional Documents
Culture Documents
TECHNICAL CORRIGENDUM
QP Performance Standard for Flammable and Toxic Gas Detectors Technical Corrigendum 1
DOC. No. QP-STD-S-036
b.
Rev. 1 Corr.
Detector location shall be based on typical leakage scenarios taking into account
plant and equipment layout, prevailing wind speed and direction, atmospheric
conditions, etc.
Detectors shall be located close to potential sources of leakage as at pump or
compressor seals, at 2 or 4 m to detect build up of gas, detectors shall be located
at level lower than the expected leak source.
c.
The following table summarises exposure limits for the more common toxic gases:
COSHH (UK)
Toxic gas
STEL (ppm)
OSHA (USA)
TWA (ppm)
STEL (ppm)
TWA (ppm)
CO
200
30
400
35
CO2
15 000
5 000
30 000
10 000
H2S
15
10
15
10
SO2
Note:
STEL Short-term exposure limit.
TWA Time-weighted average.
COSHH- Control Of Substances Hazardous to Health
OSHA- Occupational Safety and Health Administration.
9.4.2
b.
The detector shall be suitable for installation in windy location subjected to high air
Velocities without loss of performance.
c.
1c
A
pp
ro
ve
d
In high potential H2S hazard area, where H2S concentration in vapor phase
exceeds 1000 ppm.
At HVAC air intakes of buildings.
Inside air-lock of buildings with HVAC system.
Inside analyzer houses where sample with high amount of H2S are analyzed.
Page 14 of 19
QP Performance Standard for Flammable and Toxic Gas Detectors Technical Corrigendum 1
DOC. No. QP-STD-S-036
Rev. 1 Corr.
Revision Number: 1 c
Item Revised:
Date: 20/3/2011
Note:
The revision history log shall be updated with each revision of the document. It shall contain a
written audit trail of the reason why the changes/amendments have occurred, what the
changes/amendments were, and the date at which the changes/amendments were made.
Page 19 of 19
STANDARDS PUBLICATION
Rev. 1
TABLE OF CONTENTS
Page No.
FOREWORD
1.0 OBJECTIVE.......................................................................................
2.0 SCOPE..............................................................................................
3.0 APPLICATION...................................................................................
4.0 TERMINOLOGY.................................................................................
4.1 DEFINITIONS....................................................................................
4.2 ABBREVIATIONS..............................................................................
5.1
5.2
QP RELATED DOCUMENTS..........................................................................
6.0 APPROVALS.....................................................................................
9.1 GENERAL...........................................................................................
9.2
10
11
9.3
12
9.4
13
9.4.1 GENERAL..........................................................................................................
13
14
9.5
15
10.0 FAT......................................................................................................
16
11.0 SAT......................................................................................................
17
12.0 DOCUMENTATIONS.............................................................................
17
Page 2 of 19
Rev. 1
12.1 GENERAL..............................................................................................
17
17
18
19
Page 3 of 19
Rev. 1
FOREWORD
This document has been developed by Corporate HSE Support Department (ST), reviewed
and edited by Corporate Quality and Management Systems Department and circulated for
user departments review before endorsed by Corporate Management for use as Corporate
Performance Standard for Flammable and Toxic Gas Detection System.
This document is published for QP Departments/Contractors/Consultants utilisation. It should
be emphasised that the document is to be used for QP operations wherever applicable and
appropriate.
This document in its present form reflects as far as possible the current QP requirements
taking into account the known available industry practices and the applicable latest national
and international codes and standards.
This document is subjected to periodical review to re-affirm its adequacy or to conform to any
changes in the corporate requirements or to include new developments on its subject.
It is recognized that there will be cases where addenda, data sheets, or other clarifications
need to be attached to the standard to suit a specific application or service environment. As
such, the content of the document shall not be changed or re-edited by any user (QP or its
contractors, suppliers, agents, etc.), but any addenda or clarifications entailing major changes
shall be brought to the attention of the Custodian Department.
The custodian of this document is Corporate HSE Support Department (ST). Therefore, all
technical comments, views, recommendations, etc on this document shall be forwarded to the
same and copied to Manager, Corporate Quality & Management Systems Department (QA).
Page 4 of 19
1.0
Rev. 1
OBJECTIVE
This standard identifies the minimum corporate performance requirements for the
flammable and toxic gas detectors.
The purposes of these systems are to detect a gas release and initiate alarms and
executive actions, where applicable, to achieve maximum safeguarding of personnel,
capital investment and the environment.
2.0
SCOPE
This standard defines the minimum requirements for design, Selection inspection &
Testing, Supply, Installation, Operation and Maintenance for fixed flammable and toxic
Gas Detection for QP projects.
It also defines the functional requirements of the Flammable and Toxic gas detection
system, which shall:
a. Detect at an early stage the presence of flammable and toxic gas.
b. Initiate audible and visible alarm signal as required to warn the detected hazard.
c. Initiate shutdown signal.
3.0
APPLICATION
This standard is applicable for the process areas, shelters and buildings where
flammable and toxic gases may be present in the event of a leak, in Onshore and
Offshore Facilities.
4.0
TERMINOLOGY
4.1
DEFINITIONS
For the purposes of this specification, the following definitions shall apply:
Contractor
Supplier/Vendor
Shall
Should
May
Page 5 of 19
Rev. 1
ABBREVIATIONS
For the purpose of this Document, the following symbols and abbreviations apply:
CO2
ESD
FAT
FEED
F&G
F&G system
HVAC
HART
H2S
HSE
I/O
IP
IR
LED
LEL
LoS
LCD
MAC
NFPA
PPM
PLC
RH
SAT
SO2
UEL
UPS
VDC
Carbon dioxide
Emergency Shutdown
Factory Acceptance Test
Front End Engineering Design
Fire &Gas
Fire and Gas Control System
Heating, Ventilation and Air Conditioning
Highway Addressable Remote Transducer Protocol
Hydrogen Sulphide
Health Safety and Environment
Input /Output
Institute of Petroleum
Infrared
Light Emitting Diode
Lower Explosive Limit
Line of Sight
Liquid Crystal Display
Manual Alarm Call point
National Fire Protection Association
Parts Per Million
Programmable Logic Controller
Relative Humidity
Site Acceptance Test
Sulphur Dioxide
Upper Explosive limit
Uninterruptible Power Supply
Volts Direct current
5.0
5.1
BS EN 50073
BS EN 60079-29-1
Page 6 of 19
5.2
Rev. 1
QP RELATED DOCUMENTS
QP-PHL-S-001
5.3
In the event of conflict between this standard and the standards / codes referenced
herein or other purchase or contractual requirements, the most stringent requirement
shall apply.
6.0
APPROVALS
The Flammable and Toxic Gas Detection Systems shall be of a type submitted to,
tested, approved, and/or listed by a certifying authority equivalent to:
7.0
7.1
All necessary health, safety and environmental procedures shall be employed to protect
personnel and the surrounding environment during on-site field works.
7.2
All relevant safety requirements of QP Safety and Fire Regulations and the Corporations
HSE policy shall be adhered to while performing works within QP operation areas.
8.0
GENERAL REQUIREMENTS
Each fire zone / sub zone shall be evaluated to determine the predominant risk
and local environment conditions. Based on this, appropriate fire and/or gas
detection devices, fire extinguishing and control measures shall be selected.
A complete set of special tools, and any devices necessary for the installation,
operation, testing, calibration and maintenance of the unit shall be provided.
All type of sensors/detectors shall have "LED "status indication (fault, alarm, etc).
9.0
9.1
GENERAL
9.1.1
Each area shall be evaluated to determine the predominant risk and based on this,
appropriate gas detection devices, and control measures shall be selected. The
likelihood and consequences of any leak scenario shall be considered when
establishing the requirement for the gas detection system in any area of the plant.
Doc. File No.: STD.S.036.R1
Page 7 of 19
Rev. 1
The selection of detectors type, principle of operation, quantity and location shall
consider the predominant combustible/flammable materials present, the type of fire
which may occur and the possible presence of flammable gases, together with the
following:
a.
The ambient conditions and likely causes of impaired performance e.g. Wind
direction and velocity, Obscuration by mists, dusts and other causes of poor
visibility, Excessive rain and presence of pollutants.
b.
Possible gas ingress into enclosed areas and identified areas where there may be
insufficient air changes.
c.
d.
e.
Possible failure modes (e.g. instrument and mechanical failures), including risk of
accidental damage, consequences of failure and the likelihood of false alarms.
f.
g.
h.
i.
Explosion hazards
Electromagnetic influences
9.1.3
Detector selection should be based on the Lower Explosive Limit (LEL) of the
predominant stream components to provide the earliest detector response. However
different types (i.e. point type gas detector and open path type) of gas detector may
be appropriate in the same area, for example at low and high elevation.
9.2
9.2.1
b.
Gas detection shall be required for an area if any of the following apply:
Areas that are non-hazardous into which gas could feasible be transported
either by mechanical ventilation systems, differential pressures, or air
movement require gas detection. The penetrations through which gas can be
leaked through air supply ducts and single-door access ways coming from
classified hazardous areas.
Area in which large volumes of gas could be released and transported to other
areas.
Gas detectors shall primarily be installed to monitor areas of the plant where
flammable gas may escape and/or accumulate. Two types of gas detector shall
be considered for use in open and sheltered process areas:
Infra-red point.
Page 8 of 19
Rev. 1
Infrared gas detectors are suitable for detection of a large range of gases,
Be aware that any plastic obstructions in the beam path are seen by infrared
detectors as hydrocarbons.
Infra-red point gas detectors shall also be located in selected areas where
essential equipment is required to remain operational when a gas alert exists.
Equipment within these zones will remain energised until gas is detected in the
area.
d.
Open path Gas Detector, The main role of such instruments is to monitor the level
of gas hazard in an area. Their integrating method of measurement makes them
more suited to indicate the presence of explosion hazards than point devices that
only measure local flammability.
e.
f.
Number of leakage sources within the areas (and hence the likelihood of a
leak);
Page 9 of 19
Rev. 1
The exhaust gases from aspirator units monitoring safe areas shall be piped back
to the external area.
g.
To allow a level of redundancy, the minimum number of detectors in any one fire
zone shall be Three, wired on separate circuits. This will allow for a single
detector failure or fault.
h. All flammable gas detectors shall have two adjustable alarm levels.
Low level gas alarms
High level gas alarms
Note:
For Executive Action Please refer to QP Corporate Fire & Safety Philosophy
No.: QP-PHL-S-001; Clause No.: 7.11.
IR Point Detectors:
II.
Detectors shall operate 100N at low level to raise an alarm in the control room;
200N detectors at high level shall be required for executive actions (i.e. shutdown)
to occur. Where point detectors protect manned buildings or other safe areas,
detection levels (low, high) shall be 15% LEL and 25% LEL.
i.
9.2.2
IR point gas detectors are generally unsuitable for use where the ambient
temperature is very high; this will be the case within the enclosures of gas
turbines. In this application, the use of catalytic gas detectors shall be considered
(this might be vendor standard), or the enclosure exhaust duct shall be monitored.
Page 10 of 19
Rev. 1
e. The detector is activated by gas that enters the measuring chamber of the
detector.
f. Main characteristics of this device are:
9.2.3
Page 11 of 19
Rev. 1
Open path gas detectors have a (recommended) minimum alarm level setting of
0.5 LELm (50 % LEL extended for one meter). That is, it can be set to give an
alarm if there is a flammable gas cloud of 5 % LEL over a distance of 10 m or, 0.5
% LEL over a distance of 100 m. Recommended alarm thresholds for open path
(line-of-sight) gas detectors are:
1 LELm & 2.5 LELm respectively for Low/High level alarm;
b. The main characteristics of this device are:
9.3
9.3.1
The Hydrogen gas detector will be installed to detect Hydrogen leaks, they will be
used in battery rooms and near process equipment handling gas rich in Hydrogen.
9.3.2
Electro-chemical point detectors for hydrogen detection shall be considered for rooms
that contain batteries where, during a recharge condition, high levels of hydrogen
might accumulate. In battery rooms where potential for significant hydrogen evolution
exists when natural ventilation is not feasible and for units handling hydrogen the
minimum number of detectors in the respective fire zone shall generally be two.
Page 12 of 19
Rev. 1
Activation of any two detectors at 10% LEL shall be required to initiate a confirmed
gas alarm and subsequent executive actions. Operation of a single detector at 10%
LEL, shall initiate an alarm only. Detection of hydrogen shall result in stopping of any
battery charging operations.
9.3.3
Electrical protection suitable for Zone 1, group IIC, Temperature class T3.
Detector output signal include outputs over HART and RS-485 Modbus protocol
for smart and addressable detectors as applicable in addition to Analogue signal
0-22 mA to include normal operation 420 mA, fault and alarm levels.
Equipped with automatic self testing features (electronic test, calibration, etc.).
Special accessories (brackets, sun shade, etc.) for detector installation shall be
provided.
Equipment for calibration (gas cylinder, pressure reducer, caps, ), testing and
maintenance shall be provided.
The VENDOR shall give the following information:
Maximum length between transmitter and F&G system panel according to cable
core section.
9.4
9.4.1
General
a.
Release of toxic gases into the atmosphere will generally create a health hazard
rather than an explosion hazard. The concentrations at which toxic gases need to
be detected are far lower level than their flammable level .Detectors for toxic
gases shall be specific for the type of the gas involved.
Page 13 of 19
Rev. 1
Detector location shall be based on typical leakage scenarios taking into account
plant and equipment layout, prevailing wind speed and direction, atmospheric
conditions, etc.
Detectors shall be located close to potential sources of leakage as at pump or
compressor seals, at 2 or 4 m to detect build up of gas, detectors shall be located
at level lower than the expected leak source.
c.
The following table summarises exposure limits for the more common toxic gases:
COSHH (UK)
Toxic gas
STEL (ppm)
OSHA (USA)
TWA (ppm)
STEL (ppm)
TWA (ppm)
CO
200
30
400
35
CO2
15 000
5 000
30 000
10 000
H2S
15
10
15
10
SO2
Note:
STEL Short-term exposure limit.
TWA Time-weighted average.
COSHH- Control Of Substances Hazardous to Health
OSHA- Occupational Safety and Health Administration.
9.4.2
In high potential H2S hazard area, where H2S concentration in vapor phase
exceeds 1000 ppm.
At HVAC air intakes of buildings.
Inside air-lock of buildings with HVAC system.
Inside analyzer houses where sample with high amount of H2S are analyzed.
b.
The detector shall be suitable for installation in windy location subjected to high air
Velocities without loss of performance.
c.
Page 14 of 19
Rev. 1
9.5
9.5.1
Ultrasonic gas leak detectors detect outdoor hydrocarbon gas leaks by sensing the
distinct high frequency acoustic ultrasound emitted by all high-pressure gas leaks.
Based on robust microphone gas sensing technology, the Ultrasonic gas detector only
needs to detect the sound of the leaking gas in order to operate.
9.5.2
Ultrasonic gas leak detectors instantly detect gas leaks as small as 0.1kg/sec at
distances up to 20m from the leak source, regardless of ambient conditions, changing
wind direction or fast dilution of the gas cloud.
9.5.3
With ultrasonic gas leak detection an accurate detection coverage range for the
individual detector can be determined and verified prior to installation. For detection of
industry standard small leaks at 0.1kg/s (ref: methane) the detection coverage will be
up to 20m. The exact coverage and positioning of the detectors can be based on an
ultrasonic background noise mapping onsite.
9.5.4
Ultrasonic gas leak detectors respond to the ultrasonic noise generated by escaping
gas at pressures of minimum 150 psi for maximum coverage of 5-20 m in radius.
9.5.5
Page 15 of 19
Rev. 1
10.0
10.1
At an early stage of the project and before the FAT, Vendor shall demonstrate that
each type of devices provided shall be compatible with the F&G SYSTEM and work
Doc. File No.: STD.S.036.R1
Page 16 of 19
Rev. 1
satisfactorily. These tests will be performed at the F&G SYSTEM factory, with one
detector of each type, to validate all links to the F&G systems and to determinate the
appropriate end of line resistors for monitoring.
10.2
During the FAT all instruments shall be inspected for any physical defect or damage,
and shall meet the corporate requirement.
10.3
11.0
10% random test for: calibration / accuracy, linearity, response time, repeatability,
electrical isolation, power supply variation, output zero, output full scale, output
50% range.
The Vendor, before delivery, shall calibrate all devices and calibration sheet shall
be delivered with the instrument.
12.0
DOCUMENTATIONS
12.1
GENERAL
All correspondence, drawings, instructions, data sheets, design calculations, or any
other written information shall be in the English language. In the case of dual
languages, one language shall be English and the other Arabic.
All dimensions, units of measurements, physical constant, etc. should be in SI units,
unless otherwise specified.
The additional documents should be furnished as appropriate.
In addition, all documents (texts, specifications, data sheets, drawings etc.) should be
provided with electronic files in the approved software (ms word, excel, auto cad, etc.).
Design calculations should be submitted in the approved and widely used software
agreed by QP.
12.2
SPECIFIC
The design shall include the submission of product data including all necessary
drawings such as detectors layout, detectors loop diagram, performance criteria, etc.
The supply shall provide two copies of the manufacturers installation, operation,
commissioning and maintenance manuals upon equipment delivery.
Completed system commissioning data and witnessed test sheets of fire simulation in
according with BS EN 50073 shall be issued upon project completion.
Page 17 of 19
13.0
Rev. 1
QUALITY REQUIREMENTS
The manufacturer/contractor shall operate a quality management system based on the
latest ISO 9000 series of standards to satisfy the requirements of this document.
The manufacturer/contractor shall demonstrate compliance by providing a copy of the
accredited certificate or the manufacturer's/contractor's quality manual. Verification of
the manufacturer's/ contractor quality system is normally part of the pre-qualification
procedure, and is therefore not detailed in the core text of this document.
Page 18 of 19
Rev. 1
Revision Number: 1
Item Revised:
Date: 26/12/2010
Note:
The revision history log shall be updated with each revision of the document. It shall contain a
written audit trail of the reason why the changes/amendments have occurred, what the
changes/amendments were, and the date at which the changes/amendments were made.
Page 19 of 19