Ceiling-suspended unit
MMC-AP0151H, AP0181H, AP0241H,
MMC-AP0271H, AP0361H, AP0481H
High-wall unit
MMK-AP0071H, AP0091H, AP0121H,
MMK-AP0151H, AP0181H, AP0241H
MMK-AP0072H, AP0092H, AP0122H
Design Manual
HFC R-410A
Ref.-No. SMMS01-AE-01-05
Indoor unit
Outdoor unit
Inverter unit
MMY-MAP0501T8, MAP0601T8
MMY-MAP0801T8, MAP1001T8
MMY-MAP1201T8
HEAT PUMP MODEL
Inverter unit
MMY-MAP0501HT8, MAP0601HT8
MMY-MAP0801HT8, MAP1001HT8
MMY-MAP1201HT8
Contents
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
4
7
13
19
29
34
39
45
46
69
75
This manual is used for both cooling only and heat pump models.
1.
Line branching
Outdoor unit
Branching joint
8F
Indoor unit
Header branching
Outdoor unit
7F
Branching
header
Indoor unit
Header
Outdoor unit
Branching joint
Indoor
unit
1F
Outdoor unit
Header
Branching joint
Super MMS
only
Indoor unit
Header
Super MMS
only
Header
Indoor unit
2F
Indoor unit
8F
Piping
A
system
Wiring
Indoor unit
B
system
Outdoor unit
7F
Allowable pipe length:
175 m equivalent length
1st branching
section
Height difference between
indoor units: 30 m
2F
Outdoor unit
1F
Compact
The design of the modular Toshiba Super MMS outdoor unit allows for easy unit manoeuvring into
any standard lift. Its compactness also allows it to be easily installed in limited spaces.
Toshiba Super MMS can be combined up to 48 hp (135 kW) as one refrigerant system.
The units have the best energy efciency ratio of any VRF unit. Compared with a conventional chiller
fan coil system, a large energy saving can be realized.
Self-diagnostic system
An equivalent pipe length of 175 m and vertical lift of 50 m are possible with the Toshiba Super
MMS.
The vertical lift between indoor units of 30 m is the highest in the industry.
This allows for greater exibility in the location of the system.
Indoor units with different capacities and congurations can be combined up to 135% of the
outdoor unit capacity.
A maximum of 48 indoor units can be combined with the 30-48 hp outdoor units.
Intelligent control
Toshiba Super MMS intelligent controls and modulating valves deliver the required capacity, in
accordance with the load variation from 50% to 100%.
The intelligent controls and modulating valves limit or increase the cooling capacity dynamically so
humidity and temperature are kept in the comfort zone.
2.
5
0501T8
0501HT8
14.0
16.0
6
0601T8
0601HT8
16.0
18.0
8
0801T8
0801HT8
22.4
25.0
10
1001T8
1001HT8
28.0
31.5
12
1201T8
1201HT8
33.5
37.5
hp
kW
kW
hp
hp
kW
kW
hp
hp
kW
kW
hp
hp
kW
kW
hp
5
0501T8
0501HT8
14.0
16.0
5
8
6
0601T8
0601HT8
16.0
18.0
6
10
8
0801T8
0801HT8
22.4
25.0
8
13
10
1001T8
1001HT8
28.0
31.5
10
16
12
1201T8
1201HT8
33.5
37.5
12
20
14
1401T8
1401HT8
38.4
43.0
8
6
23
16
1601T8
1601HT8
45.0
50.0
8
8
27
18
1801T8
1801HT8
50.4
56.5
10
8
30
20
2001T8
2001HT8
56.0
63.0
10
10
33
22
2201T8
2201HT8
61.5
69.0
8
8
6
37
22
2211T8
2211HT8
61.5
69.0
12
10
37
24
2401T8
2401HT8
68.0
76.5
8
8
8
40
24
2411T8
2411HT8
68.0
76.5
12
12
40
26
2601T8
2601HT8
73.0
81.5
10
8
8
43
28
2801T8
2801HT8
78.5
88.0
10
10
8
47
30
3001T8
3001HT8
84.0
95.0
10
10
10
48
32
3201T8
3201HT8
90.0
100.0
8
8
8
8
48
32
3211T8
3211HT8
90.0
100.0
12
10
10
48
34
3401T8
3401HT8
96.0
108.0
10
8
8
8
48
34
3411T8
3411HT8
96.0
108.0
12
12
10
48
36
3601T8
3601HT8
101.0
113.0
10
10
8
8
48
36
3611T8
3611HT8
101.0
113.0
12
12
12
48
38
3801T8
3801HT8
106.5
119.5
10
10
10
8
48
40
4001T8
4001HT8
112.0
126.5
10
10
10
10
48
42
4201T8
4201HT8
118.0
132.0
12
10
10
10
48
44
4401T8
4401HT8
123.5
138.0
12
12
10
10
48
46
4601T8
4601HT8
130.0
145.0
12
12
12
10
48
48
4801T8
4801HT8
135.0
150.0
12
12
12
12
48
Model
RBM-BY53E
RBM-BY103E
RBM-BY203E
RBM-BY303E
RBM-HY1043E
RBM-HY2043E
RBM-HY1083E
RBM-HY2083E
RBM-BT13E
Usage
Indoor unit capacity code (*1) : Total below 6.4
Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
Indoor unit capacity code (*1) : Total 25.2 or more
Indoor unit capacity code (*1) : Total below 14.2
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
Indoor unit capacity code (*1) : Total below 14.2
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
1 set of 3 types of T-shape joint pipes as described below:
The required quantity is arranged and they are combined at the site.
Connection piping
Balance pipe
Liquid side piping
Gas side piping
*1
*2
*3
*4
*5
*6
Appearance
(*2)
(*2)
(*2)
Max.4
branches
Max.8
branches
Qty
1
1
1
The capacity code can be obtained from page 10 (capacity code is not actual capacity).
If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.
When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.
Max. 6.0 capacity code in total can be connected.
If capacity code of outdoor unit is 26 and more, it is not used for 1st branching.
Model names for outdoor and indoor units described in this guide are shortened because of the space constraints.
Model
MMYMAP0501T8
MAP0601T8
MAP0801T8
MAP1001T8
MAP1201T8
AP1401T8
AP1601T8
AP1801T8
AP2001T8
AP2201T8
AP2211T8
AP2401T8
AP2411T8
AP2601T8
AP2801T8
AP3001T8
AP3201T8
AP3211T8
AP3401T8
AP3411T8
AP3601T8
AP3611T8
AP3801T8
AP4001T8
AP4201T8
AP4401T8
AP4601T8
AP4801T8
No. of
combined
units
1
1
1
1
1
2
2
2
2
3
2
3
2
3
3
3
4
3
4
3
4
3
4
4
4
4
4
4
Inverter
5 hp
MMYMAP0501T8
Qty
used
Inverter
6 hp
MMY-
Qty
used
MAP0601T8
Inverter
8 hp
MMY-
Qty
used
Inverter
10 hp
MMY-
Qty
used
MAP1001T8
Inverter
12 hp
MMY-
Qty
used
MAP1201T8
MAP1201T8
MAP1201T8
MAP1201T8
MAP1201T8
MAP1201T8
MAP1201T8
MAP1201T8
MAP1201T8
MAP1201T8
1
2
3
4
1
MAP0801T8
MAP0601T8
MAP0601T8
MAP0801T8
MAP0801T8
MAP0801T8
2
1
MAP0801T8
MAP0801T8
MAP0801T8
MAP0801T8
2
1
MAP0801T8
MAP0801T8
MAP0801T8
MAP0801T8
MAP1001T8
MAP1001T8
1
2
MAP1001T8
MAP1001T8
MAP1001T8
MAP1001T8
1
2
3
MAP1001T8
MAP1001T8
MAP1001T8
MAP1001T8
2
1
1
2
MAP1001T8
MAP1001T8
MAP1001T8
MAP1001T8
MAP1001T8
3
4
3
2
1
1. Product designation
MMY-
AP
000
8
8: Power supply, 3 ph, 380-415 V, 50 Hz
T: Inverter unit
Development series number
Model size hp x 10
New refrigerant R-410A
M: Single module unit. No mark: Combined model name
Super Modular Multi
1 to 4 units
14 hp (140 type) to 48 hp (480 type)
3. Rated conditions
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db.
Model
MMYMAP0501HT8
MAP0601HT8
MAP0801HT8
MAP1001HT8
MAP1201HT8
AP1401HT8
AP1601HT8
AP1801HT8
AP2001HT8
AP2201HT8
AP2211HT8
AP2401HT8
AP2411HT8
AP2601HT8
AP2801HT8
AP3001HT8
AP3201HT8
AP3211HT8
AP3401HT8
AP3411HT8
AP3601HT8
AP3611HT8
AP3801HT8
AP4001HT8
AP4201HT8
AP4401HT8
AP4601HT8
AP4801HT8
No. of
combined
units
1
1
1
1
1
2
2
2
2
3
2
3
2
3
3
3
4
3
4
3
4
3
4
4
4
4
4
4
Inverter
Qty
5 hp
used
MMYMAP0501HT8 1
Inverter
6 hp
MMY-
Qty
used
Inverter
8 hp
MMY-
Qty
used
Inverter
10 hp
MMY-
Qty
used
Inverter
12 hp
MMY-
Qty
used
MAP0601HT8 1
MAP0801HT8 1
MAP1001HT8 1
MAP1201HT8 1
MAP0601HT8 1
MAP0601HT8 1
MAP0801HT8 1
MAP0801HT8 2
MAP0801HT8 1
MAP1001HT8 1
MAP1001HT8 2
MAP0801HT8 2
MAP1001HT8 1
MAP1201HT8 1
MAP0801HT8 3
MAP1201HT8 2
MAP0801HT8 2
MAP0801HT8 1
MAP1001HT8 1
MAP1001HT8 2
MAP1001HT8 3
MAP0801HT8 4
MAP0801HT8 3
MAP0801HT8 2
MAP1001HT8
MAP1001HT8
MAP1001HT8
MAP1001HT8
2
1
1
2
MAP1001HT8
MAP1001HT8
MAP1001HT8
MAP1001HT8
MAP1001HT8
3
4
3
2
1
MAP1201HT8 1
MAP1201HT8 2
MAP1201HT8 3
MAP0801HT8 1
MAP1201HT8
MAP1201HT8
MAP1201HT8
MAP1201HT8
1
2
3
4
1. Product designation
MMY-
AP
000
8
8: Power supply, 3 ph, 380-415 V, 50 Hz
T: Inverter unit
H: Heat pump
Development series number
Model size hp x 10
New refrigerant R-410A
M: Single module unit. No mark: Combined model name
Super Modular Multi
1 to 4 units
14 hp (140 type) to 48 hp (480 type)
3. Rated conditions
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db.
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Model
name
Capacity
code
MMU-AP0091H
MMU-AP0121H
MMU-AP0151H
MMU-AP0181H
MMU-AP0241H
MMU-AP0271H
MMU-AP0301H
MMU-AP0361H
MMU-AP0481H
MMU-AP0561H
MMU-AP0071WH
MMU-AP0091WH
MMU-AP0121WH
MMU-AP0151WH
MMU-AP0181WH
MMU-AP0241WH
MMU-AP0271WH
MMU-AP0301WH
MMU-AP0481WH
MMU-AP0071YH
MMU-AP0091YH
MMU-AP0121YH
MMU-AP0151SH
MMU-AP0181SH
MMU-AP0241SH
MMD-AP0071BH
MMD-AP0091BH
MMD-AP0121BH
MMD-AP0151BH
MMD-AP0181BH
MMD-AP0241BH
MMD-AP0271BH
MMD-AP0301BH
MMD-AP0361BH
MMD-AP0481BH
MMD-AP0561BH
MMD-AP0181H
MMD-AP0241H
MMD-AP0271H
MMD-AP0361H
MMD-AP0481H
MMD-AP0721H
MMD-AP0961H
MMD-AP0071SPH
MMD-AP0091SPH
MMD-AP0121SPH
MMD-AP0151SPH
MMD-AP0181SPH
MMC-AP0151H
MMC-AP0181H
MMC-AP0241H
MMC-AP0271H
MMC-AP0361H
MMC-AP0481H
MMK-AP0071H
MMK-AP0091H
MMK-AP0121H
MMK-AP0151H
MMK-AP0181H
MMK-AP0241H
MMK-AP0072H
MMK-AP0092H
MMK-AP0122H
MML-AP0071H
MML-AP0091H
MML-AP0121H
MML-AP0151H
MML-AP0181H
MML-AP0241H
MML-AP0071BH
MML-AP0091BH
MML-AP0121BH
MML-AP0151BH
MML-AP0181BH
MML-AP0241BH
MMF-AP0151H
MMF-AP0181H
MMF-AP0241H
MMF-AP0271H
MMF-AP0361H
MMF-AP0481H
MMF-AP0561H
Ceiling-suspended unit
High-wall unit
10
1
1.25
1.7
2
2.5
3
3.2
4
5
6
0.8
1
1.25
1.7
2
2.5
3
3.2
5
0.8
1
1.25
1.7
2
2.5
0.8
1
1.25
1.7
2
2.5
3
3.2
4
5
6
2
2.5
3
4
5
8
10
0.8
1
1.25
1.7
2
1.7
2
2.5
3
4
5
0.8
1
1.25
1.7
2
2.5
0.8
1.0
1.25
Cooling
capacity
kW
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
16.0
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
14.0
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
16.0
5.6
7.1
8.0
11.2
14.0
22.4
28.0
2.2
2.8
3.6
4.5
5.6
4.5
5.6
7.1
8.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
Heating
capacity
kW
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
16.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
6.3
8.0
9.0
12.5
16.0
25.0
31.5
2.5
3.2
4.0
5.0
6.3
5.0
6.3
8.0
9.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
0.8
1
1.25
1.7
2
2.5
0.8
1
1.25
1.7
2
2.5
1.7
2
2.5
3
4
5
6
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
4.5
5.6
7.1
8.0
11.2
14.0
16.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
9.0
12.5
16.0
18.0
Height
mm
Width
mm
Depth
mm
Weight
kg
256
840
840
20
256
840
840
22
256
840
840
23
319
840
840
28
398
830
550
33
398
1350
550
44
398
1350
550
48
406
235
1650
850
620
400
52
22
198
1100
655
27
198
320
1200
550
655
800
31
27
320
700
800
30
320
1000
800
39
320
1350
800
51
380
380
850
850
660
660
50
52
380
380
470
850
1200
1380
660
660
1250
56
67
155
210
845
645
210
910
680
22
22
22
23
23
21
210
1180
680
25
210
1595
680
33
368
895
210
18
368
1055
210
19
368
275
1430
790
210
208
25
11
630
950
230
37
630
600
950
745
230
220
40
21
600
1045
220
29
1750
600
210
48
1750
600
210
49
1750
600
390
65
5. Remote controller
Appearance
Wired remote controller
Application
Function
RBC-AMT31E
Wired remote
controller
RBC-AS21E
Start/stop
Mode change
Temperature adjustment
Air ow adjustment
Timer function
Three options are available:
On after selected time (one cycle)
Off after selected time (one cycle)
Off after selected time (re-occurring)
To use, choose one of these options and
the time delay before it occurs (minimum
period is 0.5 hours).
Combined with the weekly timer a
weekly operating schedule can be set.
Filter maintenance time
Automatically displays the maintenance
time of the indoor lter.
Filter LED ashes.
Self-diagnosis function
Pressing the CHECK button displays the
problem cause using a check code.
Two controlling positions are available.
Two remote controllers can be connected
to one indoor unit. The indoor unit can then
be operated from two separate locations.
Start/stop
Temperature adjustment
Air ow adjustment
Check code display
Start/stop
Mode change
Temperature adjustment
Air ow adjustment
Timer function
Three options are available:
On after selected time (one cycle)
Off after selected time (one cycle)
Off after selected time (re-occurring)
To use, choose one of these options and
the time delay before it occurs (minimum
period is 0.5 hours).
Two controlling positions are available.
Two wireless remote controllers can be
connected to one indoor unit. The indoor
unit can then be operated from two
separate locations.
Check code display.
TCB-AX21U (W)-E
(For 4-way ceiling cassette)
RBC-AX22CE
(For ceiling-suspended unit)
TCB-AX21E
(For all units except high-pressure ducted units)
11
Appearance
Infrared remote controller
Application
Function
WH-H2UE
Weekly timer
RBC-EXW21E
Start/stop
Mode change
Temperature adjustment
Air ow adjustment (5 steps)
Clock
Timer function
- ON/OFF timer (10 min. steps)
- Daily timer
High power mode
ECO mode (sleep timer with ECO-logic)
One-touch pre-set memory
Weekly
timer
Wired remote
controller
Outdoor unit
Central remote
controller
Weekly
timer
Slave
Outdoor unit
Central remote
controller
Central
remote
controller
Indoor remote controller
12
3.
13 units
Min. 4
Max. 10.8
Outdoor unit
8HP
Capacity code
over the branch
(0.8 + 0.8 = 1.6)
Indoor unit
designation
Capacity
code
Indoor unit
Remote
controller
13
10 hp system
Outdoor unit
10HP
Indoor unit
Remote
controller
14
16 units
Min. 5
Max. 13.5
20 hp system
33 units
Min. 10
Max. 27
Outdoor unit
10HP 10HP
Indoor unit
Remote
controller
15
30 hp system
48 units
Min. 15
Max. 40.5
Indoor unit
Remote
controller
16
40 hp system
48 units
Min. 20
Max. 54
Indoor unit
Remote
controller
17
48 hp system
Indoor unit
Remote
controller
18
48 units
Min. 24
Max. 64.8
4.
1. Selection ow chart
1. Determination of indoor air conditioning load
4. Capacity correction for piping length/height between indoor and outdoor units
No
End
027
8.0
3
030
9.0
3.2
036
11.2
4
048
14.0
5
056
16.0
6
072
22.4
8
096
28.0
10
For outdoor unit, maximum number of connectable indoor units and total capacity code of indoor units are decided.
Outdoor unit
(cooling only)
MMY-MAP0501T8
MMY-MAP0601T8
MMY-MAP0801T8
MMY-MAP1001T8
MMY-MAP1201T8
MMY-AP1401T8
MMY-AP1601T8
MMY-AP1801T8
MMY-AP2001T8
MMY-AP2201T8
MMY-AP2211T8
MMY-AP2401T8
MMY-AP2411T8
MMY-AP2601T8
MMY-AP2801T8
MMY-AP3001T8
MMY-AP3201T8
MMY-AP3211T8
MMY-AP3401T8
MMY-AP3411T8
MMY-AP3601T8
MMY-AP3611T8
MMY-AP3801T8
MMY-AP4001T8
MMY-AP4201T8
MMY-AP4401T8
MMY-AP4601T8
MMY-AP4801T8
Outdoor unit
(heat pump)
MMY-MAP0501HT8
MMY-MAP0601HT8
MMY-MAP0801HT8
MMY-MAP1001HT8
MMY-MAP1201HT8
MMY-AP1401HT8
MMY-AP1601HT8
MMY-AP1801HT8
MMY-AP2001HT8
MMY-AP2201HT8
MMY-AP2211HT8
MMY-AP2401HT8
MMY-AP2411HT8
MMY-AP2601HT8
MMY-AP2801HT8
MMY-AP3001HT8
MMY-AP3201HT8
MMY-AP3211HT8
MMY-AP3401HT8
MMY-AP3411HT8
MMY-AP3601HT8
MMY-AP3611HT8
MMY-AP3801HT8
MMY-AP4001HT8
MMY-AP4201HT8
MMY-AP4401HT8
MMY-AP4601HT8
MMY-AP4801HT8
Capacity code
of outdoor unit
5
6
8
10
12
14
16
18
20
22
22
24
24
26
28
30
32
32
34
34
36
36
38
40
42
44
46
48
Max. No. of
indoor units
8
10
13
16
20
23
27
30
33
37
37
40
40
43
47
48
48
48
48
48
48
48
48
48
48
48
48
48
19
Air ow variation ratio of indoor unit vs. capacity correction (for ducted units only)
20
Outdoor unit capacity correction factor when total capacity of the indoor units is not equal to the outdoor unit capacity.
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
ho
lo
H = ho + (longest dimension of
ha, hb and hc)
ha
hc
hb
la
lb
Indoor unit
lc
Correction (%)
21
Air ow variation ratio of indoor unit vs. capacity correction (for ducted units only)
*1
*2
22
Outdoor unit capacity correction factor when total capacity of the indoor units is not equal to the outdoor unit capacity.
Refer to the capacity correction for frosting on the outdoor heat exchanger section on page 24.
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
Outdoor unit
L is the longest dimension of
(lo + la, lo + lb, lo + lc)
ho
lo
H = ho + (longest dimension of
ha, hb and hc)
ha
hb
la
hc
lb
Indoor unit
lc
Correction (%)
23
Capacity correction for frosting on the outdoor heat exchanger (heating mode)
Correct the heating capacity when frost was found on the outdoor heat exchanger.
Heating capacity =
Capacity after correction of outdoor unit correction value of capacity resulting from frost
(Capacity after correction of outdoor unit: Heating capacity calculated in the previous
section.)
Capacity correction for frosting on the outdoor heat exchanger
Rated conditions
Cooling: Indoor air temperature 27C db/19C wb.
Outdoor air temperature 35C db.
Heating: Indoor air temperature 20C db.
Outdoor air temperature 7C db/6C wb.
24
Usable range
(in warming-up mode)
Continuous
operating
range
In heating mode
Usable range
(in pull-down mode)
In cooling mode
Continuous
operating
range
Floor conguration
Ofce rooms
(Entire oor)
Ofce rooms
Stores
25
2.
4-1
4-2
4-3
4-4
4-5
3F
3-1
2F
2-1
2-2
2-3
1F
1-1
1-2
1-3
1-4
Note: ( ): Peak occurrence time
Piping distance
Floor
Room No.
4F
3F
2F
1F
26
4-1
4-2
4-3
4-4
4-5
3-1
2-1
2-2
2-3
1-1
1-2
1-3
1-4
6.5
6.5
7.2
5.1
Heating
5.4
4.2
4.2
2.7
5.4
12.0
4.5
4.8
6.0
6.3
7.0
4.5
Equivalent
length (m)
Height
difference (m)
43
12
Equipment selection
Indoor unit
Model
Capacity (kW)
MMUCooling
Heating
AP0241H
7.1
8.0
AP0181H
5.6
6.3
AP0181H
5.6
6.3
AP0121H
3.6
4.0
AP0241H
7.1
8.0
AP0481H
14.0
16.0
AP0181H
5.6
6.3
AP0181H
5.6
6.3
AP0241H
7.1
8.0
AP0241H
7.1
8.0
AP0301H
9.0
10.0
AP0181H
5.6
6.3
Capacity correction
Pipe correction x
temp. correction
Cooling
Heating
0.920
0.957
x
x
1.0
1.0
x
x
1.0
0.95
=
x
0.920
0.95
=
0.864
Outdoor unit
Model
MMY
AP2801HT8
Capacity (kW)
Cooling
Heating
78.5
88.0
6.5
6.5
8.3
5.2
Heating
6.9
5.4
5.4
3.5
6.9
13.8
5.4
5.4
6.9
6.9
8.6
5.4
Result
Good
Load (kW)
4-1
Time
Load (kW)
4-2
Time
4-3
Load (kW)
Time
1.
2.
Time
Load (kW)
4-4
Time
Load (kW)
4-5
Time
27
Schematic diagram
MMY-AP2801T8
MMY-AP2801HT8
Outdoor unit
4th branching
joint
3rd branching
joint
1st branching
joint
5th branching
joint
2nd branching
joint
Indoor unit
MMU-AP0241H
2nd branching
joint
Indoor unit
MMU-AP0181H
4-1
4-2
Indoor unit
MMU-AP0121H
Indoor unit
MMU-AP0181H
4-3
4-4
Indoor unit
MMU-AP0241H
4-5
3-5
Indoor unit
MMD-AP0481H
3rd branching
joint
4th branching
joint
Indoor unit
MMU-AP0181H
Indoor unit
MMU-AP0181H
No air conditioner
2-1
2-2
2-3
Branching header
28
Indoor unit
MMU-AP0241H
Indoor unit
MMU-AP0241H
1-1
1-2
Indoor unit
MMU-AP0181H
Indoor unit
MMU-AP0301H
1-3
1-4
5.
Outdoor unit
e.g. charged
amount (10 kg)
Room A
Room B
Room C
Room D
Room E
Room F
Indoor unit
Outdoor unit
Refrigerant piping
Indoor unit
Refrigerant piping
Outdoor unit
Very
small
room
Indoor unit
Small
room
Medium room
Large room
29
m2
kg
Total refrigerant amount
The above ve branching systems are available to increase signicantly the exibility of refrigerant piping design.
Outdoor unit
Branching joint
Line
branching
system
Indoor unit
Remote
controller
Outdoor unit
Header
branching
system
Branching header
Indoor unit
Remote controller
Outdoor unit
Branching joint
Branching header
Header
branching
after line
branching
Indoor unit
Remote
controller
Line
branching
after header
branching
Header
branching
after header
branching
30
Outdoor unit
Branching header
Branching
joint
Indoor unit
Remote
controller
Height difference
between outdoor
units H3 5 m
A master
unit
B slave
unit 1
Slave
unit 1
Example 2
Slave
unit 2
Master
unit
Slave
unit 1
Slave
unit 2
Connecting
piping of
outdoor unit
T-shape branching La
LA
joint
Lb
LB
Lc
Ld
L1
Height difference
betweeen outdoor
units H1 50 m
Master
unit
C slave
unit 2
Outdoor unit
Main
piping
Example 1
Branching piping L2
Connecting piping of indoor unit
1st branching
section
L3
Indoor unit
Equivalent length corresponding to farthest piping L 175 m
Equivalent length corresponding to farthest piping after 1st branching Li 65 m
Y-joint
L4
L5
L6
Height difference
between indoor
units H2 30 m
Indoor unit
System restrictions
Note 1:
Note 2:
4 units
48 hp
48 units
135%
105%
Note 3:
Note 4:
*
(D) is outdoor unit farthest from 1st branching, and ( j ) is indoor unit farthest from 1st branching.
**
If the height difference (H2) between indoor units exceeds 3 m, set below 30 m.
***
If the maximum combination capacity of the outdoor units is 46 hp or more, the maximum equivalent length is restricted up to 70 m.
Piping length
31
Slave
unit 2
Slave
unit 1
Master
unit
Outdoor unit
connection
piping
Main piping
Main connection
piping between
outdoor units
1st branching
section
Indoor unit
Y-shape
branching
joint
Indoor unit
connection piping
Indoor unit
Model name
MAP0501T8
MAP0601T8
MAP0801T8
MAP1001T8
MAP1201T8
MMYMAP0501HT8
MAP0601HT8
MAP0801HT8
MAP1001HT8
MAP1201HT8
Gas side
5/8
3/4
7/8
7/8
1-1/8
Liquid side
3/8
3/8
1/2
1/2
1/2
Gas side
1-1/8
1-3/8
1-3/8
1-5/8
Liquid side
5/8
5/8
3/4
7/8
3/8
3/8
3/8
3/8
*1
*2
*3
*4
*5
32
Balance pipe
Soft
OK
OK
OK
OK
NG
NG
NG
NG
NG
Liquid side
1/4
1/4
1/4
3/8
1/2
Model
RBM-BY53E
RBM-BY103E
RBM-BY203E
RBM-BY303E
RBM-HY1043E
RBM-HY2043E
RBM-HY1083E
RBM-HY2083E
RBM-BT13E
OD (Inch)
1/4
3/8
1/2
5/8
3/4
7/8
1-1/8
1-3/8
1-5/8
Code is determined according to the unit size. For details, refer to pages 7-9.
When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.
For one line after header branching, indoor units with a maximum of 6.0 capacity code in total can be connected.
If the pipe size is 3/4 or more, use a hard type or half hard type for material of the pipe.
The maximum equivalent length of the main pipe should be 70 m or shorter.
5 hp
8.5 kg
8.0 kg
Heat pump
Cooling only
6 hp
8.5 kg
8.0 kg
8 hp
12.5 kg
11.0 kg
10 hp
12.5 kg
11.0 kg
12 hp
12.5 kg
11.0 kg
When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes at the site
is not included. Calculate the additional amount needed, and add that amount to the system.
Calculation
Additional refrigerant charge amount is calculated from the size of the liquid pipe at the site and its actual length.
Additional refrigerant charge amount at the site =
Actual length of liquid pipe
(L1 x 0.025 kg/m) + (L2 x 0.055 kg/m) + (L3 x 0.105 kg/m) + (3.0 kg)
L1: Actual total length of liquid pipe 1/4 (m)
L2: Actual total length of liquid pipe 3/8 (m)
L3: Actual total length of liquid pipe 1/2 (m)
Table 7-1
Liquid side pipe diameter
Additional refrigerant amount/1 m
1/4
0.025 kg
3/8
0.055 kg
1/2
0.105 kg
5/8
0.160 kg
3/4
0.250 kg
7/8
0.350 kg
Table 7-2
Combined
horse power
(hp)
5
6
8
10
12
14
16
18
20
22
24
26
6
8
8
10
10
8
12
8
8
6
8
8
Compensation
by system hp
(kg)
0.0
0.0
1.5
2.5
3.5
0.0
0.0
0.0
3.0
5.0
0.0
7.0
-4.0
-4.0
Combined
horse power
(hp)
28
30
32
34
36
38
40
42
44
46
48
10
10
10
8
12
8
12
10
10
10
10
12
12
12
8
10
10
8
10
8
12
8
10
10
10
10
12
12
8
8
8
8
10
10
10
10
12
Compensation
by system hp
(kg)
-2.0
0.0
1.0
-6.0
3.0
-6.0
4.0
-6.0
-6.0
-5.0
-4.0
-2.0
0.0
2.0
33
6.
Wiring design
1. General
(1) Perform wiring of the power supply in conformance with the regulations of the local electric company.
(2) For the control wires connecting indoor units, outdoor units, and between indoor and outdoor units, use of
double-core shielded wires is recommended to prevent noise disturbance.
(3) Be sure to set the earth leakage breaker and the switches to the power supply section of the indoor unit.
(4) Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for each outdoor unit.
(5) Never connect the 220240 V power to the terminal block (U1, U2, U3, U4, U5, U6) for control cables, as this
will cause problems.
(6) The control wiring system and refrigerant piping system should be in the same line.
(7) Arrange the cables so that the power cables do not come into contact with the high-temperature part of the
pipe; otherwise the coating may melt and cause an accident.
(8) Do not turn on the power to the indoor unit until the refrigerant pipes have been completely evacuated.
Select the power supply cabling and fuse of each outdoor unit from the following specications:
5-core cable, in accordance with 60245 IEC 66.
Connect the outdoor units via the incorporated terminal block (L1, L2, L3, N).
3-phase
50 Hz, 380-415 V
Earth leakage breaker
manual switch
Earth
Outdoor unit
power source
Junction box
Indoor unit
power source
Single-phase
50 Hz, 220-240 V
Earth leakage breaker
power switch
Model
MMY-AP***T8, HT8
34
MAP0501HT8
MAP0601HT8
MAP0801HT8
MAP1001HT8
MAP1201HT8
Determine the wire size for the indoor unit according to the number of connected indoor units downstream.
Observe local regulations regarding wire size selection and installation.
Field-supplied fuse
20 A
20 A
30 A
30 A
30 A
4. Indoor unit power supply (must be independent from outdoor unit power)
Model
All models of indoor units
Field-supplied fuse
15 A
Note: The connecting length indicated in the table represents the length from the junction box to the outdoor unit when the indoor units are connected in parallel for
power, as shown in the illustration on the previous page. A voltage drop of no more than 2% is assumed. If the connecting length exceeds the length indicated
in the table, select the wire thickness in accordance with local wiring standards.
CAUTIONS
(1) Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems
together.
(2) When running power wires and control wires parallel to each other, either run them through separate
conduits, or maintain a suitable distance between them.
(Current capacity of power wires: 10 A or less for 300 m, 50 A or less for 500 m)
Power supply
Single-phase
220-240 V, 50 Hz
(Open)
Earth
[Central remote controller] (option)
TCB-SC642TLE (for line 64)
Standard
remote controller
Wire specication, quantity, size of interconnecting wiring and remote controller wiring
Name
Quantity
Interconnecting wiring
(indoor-indoor/indoor-outdoor/outdoor-outdoor
control wiring, central control wiring)
Remote controller wiring
(1)
(2)
Up to 1000 m
2 cores
Size
Up to 500 m
1.25 mm
Specication
2 cores
0.5 to 2.0 mm
1000 to 2000 m
2.0 mm
Shielded wire
The interconnecting wiring and central control wiring use 2-core non-polarity interconnecting wires. Use 2-core shielded wires to prevent noise disturbance. In
this case, close (connect) the end of shielded wires, and perform the functional grounding for the end of the shielded wires which are connected to both indoor
and outdoor units. For the shielded wires which are connected between the central remote controller and the outdoor unit, perform the functional grounding at
only one end of the central control wiring.
Use 2-core non-polarity wire for remote controller (A, B terminals).
Use 2-core non-polarity wire for wiring of group control (A, B terminals).
35
Central control
device
Master
unit
Slave
unit
Slave
unit
Master
unit
Slave
unit
Outdoor unit
Table 1
Indoor unit
Table 3
Remote
controller
Table 1
Wiring
Type
Size
Length
(*1):
Control wiring between indoor and outdoor units (L1, L2, L3)
Central control wiring (L4)
2-core, non-polarity
Shielded wire
1.25 mm: Up to 1000 m
2.0 mm: Up to 2000 m (*1)
Table 2
Wiring
Type
Size
Length
Table 3
Wire
Size
Length
36
Remote controller
Up to 500 m ( L6 + L7 ).
Remote controller
Table 2
Slave
unit
7. Design
Type
4-way ceiling cassette
Ceiling-suspended unit
High-wall unit
Model
MMU-AP0091H
MMU-AP0121H
MMU-AP0151H
MMU-AP0181H
MMU-AP0241H
MMU-AP0271H
MMU-AP0301H
MMU-AP0361H
MMU-AP0481H
MMU-AP0561H
MMU-AP0071WH
MMU-AP0091WH
MMU-AP0121WH
MMU-AP0151WH
MMU-AP0181WH
MMU-AP0241WH
MMU-AP0271WH
MMU-AP0301WH
MMU-AP0481WH
MMU-AP0071YH
MMU-AP0091YH
MMU-AP0121YH
MMU-AP0151SH
MMU-AP0181SH
MMU-AP0241SH
MMD-AP0071BH
MMD-AP0091BH
MMD-AP0121BH
MMD-AP0151BH
MMD-AP0181BH
MMD-AP0241BH
MMD-AP0271BH
MMD-AP0301BH
MMD-AP0361BH
MMD-AP0481BH
MMD-AP0561BH
MMD-AP0181H
MMD-AP0241H
MMD-AP0271H
MMD-AP0361H
MMD-AP0481H
MMD-AP0721H
MMD-AP0961H
MMD-AP0071SPH
MMD-AP0091SPH
MMD-AP0121SPH
MMD-AP0151SPH
MMD-AP0181SPH
MMC-AP0151H
MMC-AP0181H
MMC-AP0241H
MMC-AP0271H
MMC-AP0361H
MMC-AP0481H
MMK-AP0071H
MMK-AP0091H
MMK-AP0121H
MMK-AP0151H
MMK-AP0181H
MMK-AP0241H
MMK-AP0072H
MMK-AP0092H
MMK-AP0122H
MML-AP0071H
MML-AP0091H
MML-AP0121H
MML-AP0151H
MML-AP0181H
MML-AP0241H
MML-AP0071BH
MML-AP0091BH
MML-AP0121BH
MML-AP0151BH
MML-AP0181BH
MML-AP0241BH
MMF-AP0151H
MMF-AP0181H
MMF-AP0241H
MMF-AP0271H
MMF-AP0361H
MMF-AP0481H
MMF-AP0561H
Nominal voltage
(V-ph-Hz)
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
Voltage range
Min.
Max.
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
Fan motor
kW
0.060
0.060
0.060
0.060
0.060
0.060
0.060
0.090
0.090
0.090
0.053
0.053
0.053
0.039
0.039
0.053
0.053
0.053
0.092
0.022
0.022
0.022
0.034
0.034
0.034
0.120
0.120
0.120
0.120
0.120
0.120
0.120
0.120
0.120
0.120
0.120
0.160
0.160
0.160
0.260
0.260
0.370 3
0.370 3
0.060
0.060
0.060
0.060
0.060
0.030
0.030
0.040
0.040
0.080
0.080
0.030
0.030
0.030
0.030
0.030
0.030
0,030
0,030
0,030
0.045
0.045
0.045
0.045
0.070
0.070
0.019
0.019
0.019
0.070
0.070
0.070
0.037
0.037
0.063
0.063
0.110
0.160
0.160
FLA
0.20
0.20
0.22
0.24
0.28
0.28
0.40
0.68
0.93
0.95
0.36
0.36
0.36
0.37
0.37
0.53
0.53
0.54
1.33
0.28
0.28
0.28
0.55
0.55
0.63
0.33
0.33
0.39
0.39
0.50
0.60
0.60
0.70
0.96
1.13
1.13
0.93
1.55
1.55
1.87
2.12
6.04
6.35
0.35
0.35
0.37
0.38
0.47
0.33
0.37
0.48
0.48
0.90
0.96
0.35
0.35
0.35
0.37
0.37
0.40
0,20
0,21
0,22
0.30
0.30
0.49
0.49
0.54
0.54
0.29
0.29
0.29
0.52
0.52
0.53
0.77
0.77
1.01
1.01
1.48
1.84
1.84
Power supply
MCA
MOCP
0.25
15
0.25
15
0.28
15
0.30
15
0.35
15
0.35
15
0.50
15
0.85
15
1.16
15
1.19
15
0.45
15
0.45
15
0.45
15
0.46
15
0.46
15
0.66
15
0.66
15
0.68
15
1.67
15
0.35
15
0.35
15
0.35
15
0.69
15
0.69
15
0.79
15
0.41
15
0.41
15
0.49
15
0.49
15
0.62
15
0.75
15
0.75
15
0.88
15
1.20
15
1.41
15
1.41
15
1.16
15
1.94
15
1.94
15
2.34
15
2.65
15
7.55
15
7.94
15
0.44
15
0.44
15
0.47
15
0.48
15
0.59
15
0.41
15
0.46
15
0.60
15
0.60
15
1.13
15
1.20
15
0.44
15
0.44
15
0.44
15
0.46
15
0.46
15
0.50
15
0,24
15
0,26
15
0,27
15
0.37
15
0.37
15
0.62
15
0.62
15
0.68
15
0.68
15
0.36
15
0.36
15
0.36
15
0.65
15
0.65
15
0.66
15
0.96
15
0.96
15
1.27
15
1.27
15
1.85
15
2.30
15
2.30
15
Legend
MCA
Minimum circuit current, A
FLA
Full load current, A
MOCP Maximum overcurrent protection current, A
37
Voltage
range
Min.
Max.
342
457
342
457
342
457
342
457
342
457
Compressor
Fan motor
Power supply
RLA
4.0 + 4.0
4.6 + 4.6
5.2 + 5.2
6.5 + 6.5
9.5 + 9.5
kW
0.60
0.60
0.60
0.60
0.60
MCA
16.5
16.5
20.0
22.5
24.5
Voltage
range
Min.
Max.
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
342
457
Compressor
Unit No. 1 Unit No. 2
RLA
RLA
5.2 + 5.2
4.6 + 4.6
5.2 + 5.2
5.2 + 5.2
6.5 + 6.5
5.2 + 5.2
6.5 + 6.5
6.5 + 6.5
5.2 + 5.2
5.2 + 5.2
9.5 + 9.5
6.5 + 6.5
5.2 + 5.2
5.2 + 5.2
9.5 + 9.5
9.5 + 9.5
6.5 + 6.5
5.2 + 5.2
6.5 + 6.5
6.5 + 6.5
6.5 + 6.5
6.5 + 6.5
5.2 + 5.2
5.2 + 5.2
9.5 + 9.5
6.5 + 6.5
6.5 + 6.5
5.2 + 5.2
9.5 + 9.5
9.5 + 9.5
6.5 + 6.5
6.5 + 6.5
9.5 + 9.5
9.5 + 9.5
6.5 + 6.5
6.5 + 9.5
6.5 + 6.5
6.5 + 6.5
9.5 + 9.5
6.5 + 6.5
9.5 + 9.5
9.5 + 9.5
9.5 + 9.5
9.5 + 9.5
9.5 + 9.5
9.5 + 9.5
FLA
0.8
0.8
1.0
1.1
1.1
MOCP
20
20
30
30
30
AP1401HT8
AP1601HT8
AP1801HT8
AP2001HT8
AP2201HT8
AP2211HT8
AP2401HT8
AP2411HT8
AP2601HT8
AP2801HT8
AP3001HT8
AP3201HT8
AP3211HT8
AP3401HT8
AP3411HT8
AP3601HT8
AP3611HT8
AP3801HT8
AP4001HT8
AP4201HT8
AP4401HT8
AP4601HT8
AP4801HT8
Legend
MCA
Minimum circuit current, A
FLA
Full load current, A
MOCP Maximum overcurrent protection current, A
kW
Rated fan motor output, kW
RLA
Rated load current, A
Note: RLA is based on the following conditions:
Indoor temperature: 27C db/19C wb
Outdoor temperature: 35C db
38
Unit No. 3
RLA
4.6 + 4.6
5.2 + 5.2
5.2 + 5.2
5.2 + 5.2
6.5 + 6.5
5.2 + 5.2
6.5 + 6.5
5.2 + 5.2
6.5 + 6.5
5.2 + 5.2
9.5 + 9.5
6.5 + 6.5
6.5 + 6.5
6.5 + 6.5
6.5 + 6.5
9.5 + 9.5
9.5 + 9.5
Unit No. 4
RLA
5.2 + 5.2
5.2 + 5.2
5.2 + 5.2
5.2 + 5.2
6.5 + 6.5
6.5 + 6.5
6.5 + 6.5
6.5 + 6.5
9.5 + 9.5
Fan motor
Power supply
kW
0.6 2
0.6 2
0.6 2
0.6 2
0.6 3
0.6 2
0.6 3
0.6 2
0.6 3
0.6 3
0.6 3
0.6 4
0.6 3
0.6 4
0.6 3
0.6 4
0.6 3
0.6 4
0.6 4
0.6 4
0.6 4
0.6 4
0.6 4
MCA
36.5
40.0
42.5
45.0
56.5
47.0
60.0
49.0
62.5
65.0
67.5
80.0
69.5
82.5
71.5
85.0
73.5
87.5
90.0
92.0
94.0
96.0
98.0
FLA
1.0 + 0.8
1.0 + 1.0
1.0 + 1.1
1.1 + 1.1
1.0 + 1.0 + 0.8
1.1 + 1.1
1.0 + 1.0 + 1.0
1.1 + 1.1
1.1 + 1.1 + 1.0
1.1 + 1.1 + 1.0
1.1 + 1.1 + 1.1
1.0 + 1.0 + 1.0 + 1.0
1.1 + 1.1 + 1.1
1.1 + 1.0 + 1.0 + 1.0
1.1 + 1.1 + 1.1
1.1 + 1.1 + 1.0 + 1.0
1.1 + 1.1 + 1.1
1.1 + 1.1 + 1.1 + 1.0
1.1 + 1.1 + 1.1 + 1.1
1.1 + 1.1 + 1.1 + 1.1
1.1 + 1.1 + 1.1 + 1.1
1.1 + 1.1 + 1.1 + 1.1
1.1 + 1.1 + 1.1 + 1.1
MOCP
40
50
50
60
70
60
70
60
70
80
80
90
80
100
80
100
90
100
100
110
110
110
110
7.
Controls
3. Network control
The Super MMS control system can offer exible centralized network control according to various customer
requirements, for both open network building control in combination with other building apparatus such as
elevator, re alarm, lighting, etc., and also for stand-alone central air conditioning control.
These central control systems are mainly established by advanced local server platforms.
3-1. Open network control
Super MMS open network control is applicable for major global building management standards.
3-1-1. LONWORKS
The LONWORKS interface manages the Super MMS air conditioning system as a LON device to
command a building computer message and to monitor the operating status.
3-1-2. BACnet
The local server serves air conditioning sub-system in a building control BACnet system.
3-2. Stand-alone central control
Simple exclusive air conditioning central control with less system integration work.
3-2-1. Touch-screen controller
A combination of touch-screen and local server enables easy operation and user-friendly display.
3-2-2. Windows-based plug-in central controller
The local server provides the central control function only by plug-in into a customers computer.
39
Basic function
Individual control
Air conditioner is individually
operated at a distance.
System diagram
Main remote controller
Indoor
unit
Indoor
unit
Possible up to max.
total length 500 m
Receiver unit
Wireless
remote
controller
Remote
controller
1-2
GROUP control
One remote controller can
control a group of max. 8
indoor units. Operating on
the same setting.
Indoor
unit
Indoor
unit
Remote
controller
1-3
Model
Indoor
unit
Indoor
unit
Wired system
Wireless system
Indoor
unit
Indoor
unit
Remote
controller
Remote
controller
Wireless
remote
controller 1
Wireless
remote
controller 2
Master
Sub-controller
Master
Sub-controller
Possible up to max.
total length 500 m
Indoor
unit
Wired and wireless
combination control
(either controller
should be set as
sub-controller)
1-4
Wireless
remote
controller
Indoor
unit
Remote
controller
40
Remote
controller
Weekly
timer
Basic function
Central management
controller for 64 units
System diagram
U3, U4
Zone 4
Model
Master
unit
Outdoor unit
Line 3
U5, U6
Indoor unit
U1, U2
Master
unit
U3, U4
U5, U6
Zone 3
Outdoor unit
Line 2
Indoor unit
U1, U2
Zone 2
Master
unit
U3, U4
Zone 1
Outdoor unit
Line 1
Indoor unit
U1, U2
Power
supply
Individual control for max. 64 indoor units divided into 1 to 4 zones (up to
16 indoor units for each zone).
Usable with other central control devices (up to 10 central control devices
in one control circuit).
2-2
U3, U4
Outdoor unit
Indoor unit
U1, U2
Single-phase
220/240 V
Power
supply
Weekly timer
Central
remote controller
41
2-3
Basic function
Remote central control
without indoor remote
controller
System diagram
U3, U4
Power
supply
Outdoor unit
Model
U1, U2
Indoor unit
Central remote controller
Single-phase,
220-240 V
Even when grouping operation is performed
by connecting multiple indoor units to 1 line,
the indoor remote controller is required.
Example of grouping operation
U3, U4
Outdoor unit
U1, U2
Power
supply
(Group)
Indoor remote controller is required
Single-phase,
220-240 V
Available
U3, U4
Outdoor unit
U1, U2
Power
supply
(Group)
Available
Single-phase,
220-240 V
2-4
Power
supply
U3, U4
Master
unit
U1, U2
Indoor unit
1:1 model
connection
interface
*1
42
Basic function
LONWORKS
System diagram
Model
LON Gateway
TCB-1FLN****
LON Centre
LON Talk
LON
interfaces
Remote controller
*1
1:1 model
connection interface
3-1-2
BACnet
BACnet Centre
Local server
TCS-Net
relay interface
Remote controller
*1
1:1 model
connection interface
The local server can be connected within the BACnet network, and can be
connected to the Super MMS air conditioning system through the interface.
43
3-2-1
Basic function
Touch screen controller
System diagram
Model
Intelligent server
BMS-LSV2E
BMS-STC01E
Local server
Relay interface
Remote controller
1:1 model
connection interface
3-2-2
Windows-based central
controller
Local server
Relay interface
Remote controller
1:1 model
connection interface
44
8.
Accessories
Model
RBC-AMT31E
TCB-SC642TLE
RBC-EXW21E
RBC-AS21E
TCB-AX21U(W)-E
Applicable model
Common parts for
all model types
RBC-AX22CE
Ceiling-suspended unit
TCB-AX21E
Universal type
(except high-pressure ducted units)
Panels
Indoor unit type
4-way ceiling cassette
Accessory name
Required accessory Ceiling panel
Optional
Super long life lter
High efciency lter 65
High efciency lter 90
Filter frame
Fresh air and lter chamber
Fresh air inlet box
Auxiliary fresh air ange
Spacer for height adjustment
Model
Application model
RBC-U21PG(W)-E
TCB-UF1601UE
TCB-UFM1601UE
TCB-UFH1601UE
TCB-DF21UKE
TCB-GFC1601UE
TCB-GB1601UE
TCB-FF101URE
TCB-SP1601UE
TCB-SP1601U-KW50E
Air discharge direction kit
TCB-BC1601UE
2-way ceiling cassette
Required accessory Ceiling panel
RBC-UW136PG
AP0071-0121
RBC-UW266PG
AP0151-0301
RBC-UW466PG
AP0361-0561
1-way ceiling cassette
Required accessory Ceiling panel
RBC-US165PG
AP0151-0181
RBC-US265PG
AP0241
RBC-UY135PG
AP0071-0121
Standard ducted unit
Optional
High efciency lter 65
TCB-UFM11BFCE
AP0071-0121/AP0241-0301
TCB-UFM21BFCE
AP0151-0181/AP0361-0561
TCB-UFM11BE
AP0071-0121
TCB-UFM21BE
AP0151-0181
TCB-UFM31BE
AP0241-0301
TCB-UFM41BE
AP0361-0561
High efciency lter 90
TCB-UFH51BFCE
AP0071-0121/AP0241-0301
TCB-UFH61BFCE
AP0151-0181/AP0361-0561
TCB-UFH51BE
AP0071-0121
TCB-UFH61BE
AP0151-0181
TCB-UFH71BE
AP0241-0301
TCB-UFH81BE
AP0361-0561
Ceiling panel
RBC-UD281PE(W)
AP0071-0121
RBC-UD501PE(W)
AP0151-0181
RBC-UD801PE(W)
AP0241-0301
RBC-UD1401PE(W)
AP0361-0561
Suction canvas
TCB-CA281BE
AP0071-0121
TCB-CA501BE
AP0151-0181
TCB-CA801BE
AP0241-0301
TCB-CA1401BE
AP0361-0561
Filter chamber
TCB-FC281BPE
AP0071-0121
TCB-FC501BPE
AP0151-0181
TCB-FC801BPE
AP0241-0301
TCB-FC1401BPE
AP0361-0561
Bottom lter kit
TCB-FK281BE
AP0071-0121
TCB-FK501BE
AP0151-0181
TCB-FK801BE
AP0241-0301
TCB-FK1401BE
AP0361-0561
High-pressure ducted unit Optional
High efciency lter 65
TCB-UFM1D-1E
AP0181-0481
TCB-UFM2D-1E
AP0241-0361
TCB-UFM3DE
AP0721-0961
High efciency lter 90
TCB-UFH5D-1E
AP0181-0481
TCB-UFH6D-1E
AP0241-0361
TCB-UFH7DE
AP0721-0961
Long life pre lter
TCB-PF1D-1E
AP0181-0481
TCB-PF2D-1E
AP0241-0361
TCB-PF3DE
AP0721-0961
Filter chamber
TCB-FCY21DE
AP0181
TCB-FCY31DE
AP0241-0361
TCB-FCY51DE
AP0481
TCB-FCY100DE
AP0721-0961
Drain pump kit
TCB-DP21DE
AP0181-0481
TCB-DP22DE
AP0721-0961
Ceiling-suspended unit
Optional
Drain pump kit
TCB-DP22CE
AP0151-0481
TCB-KP12CE
AP0151-0181
TCB-KP22CE
AP0241-0481
Note: For availability of the wireless remote controller kit and other optional equipment not in this table, consult your dealer.
Remarks
Three-piece kit
45
9.
Technical specications
Indoor units
4-way ceiling cassettes
Model MMU-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Ceiling panel model number
Panel colour
Panel dimensions
Height
Width
Depth
Panel weight
Rated conditions:
*
**
46
kW
kW
0091H
2.8
3.2
0121H
3.6
4.0
0151H
4.5
5.0
0181H
5.6
6.3
0241H
7.1
8.0
0271H
8.0
9.0
0301H
9.0
10.0
0361H
11.2
12.5
0481H
14.0
16.0
0561H
16.0
18.0
0.59
0.070
0.87
0.81
0.110
1.23
0.83
0.112
1.26
V-ph-Hz
A
kW
A
mm
mm
mm
kg
256
840
840
22
256
840
840
23
256
840
840
23
256
840
840
23
319
840
840
28
319
840
840
28
319
840
840
28
256
256
256
840
840
840
840
840
840
20
20
22
Finned tube
Non-ammable insulation
Turbo fan
60
60
60
60
60
60
60
90
90
90
l/s
l/s
l/s
222
203
189
292
256
222
333
256
228
333
256
228
367
308
236
467
361
297
567
397
314
581
422
342
m3/h
m3/h
m3/h
dB(A)
dB(A)
800
800
930
1050
730
730
830
920
680
680
790
800
43/42/40 43/42/40 44/42/40 45/42/41
30/29/27 30/29/27 31/29/27 32/29/28
Standard long-life lter supplied
Remote controller
1200
920
820
47/44/41
34/31/28
1200
920
820
47/44/41
34/31/28
1320
1110
850
50/46/43
37/33/30
1680
1300
1070
53/49/46
40/36/33
2040
1430
1130
57/51/47
44/38/34
2090
1520
1230
58/53/47
45/40/34
in
in
in
3/8
3/8
1/2
1/2
1/4
1/4
1/4
1/4
1
1
1
1
RBC-U21PG (W)-E
Moon white (Munsell/2.5GY 9.0/0.5)
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
mm
mm
mm
kg
35
950
950
4.5
35
950
950
4.5
35
950
950
4.5
35
950
950
4.5
35
950
950
4.5
35
950
950
4.5
35
950
950
4.5
222
203
189
35
950
950
4.5
258
231
219
35
950
950
4.5
35
950
950
4.5
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
Indoor units
2-way ceiling cassettes
Model MMU-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Power factor
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Ceiling panel model number
Panel colour
Panel dimensions
Height
Width
Depth
Panel weight
Rated conditions:
*
**
kW
kW
0071WH
2.2
2.5
0091WH
2.8
3.2
0121WH
3.6
4.0
0151WH
4.5
5.0
0181WH
5.6
6.3
0241WH
7.1
8.0
0271WH
8.0
9.0
0301WH
9.0
10.0
0.46
0.105
99
0.89
0.47
0.106
98
0.98
V-ph-Hz
A
kW
%
A
mm
mm
mm
kg
398
830
550
33
398
1350
550
44
398
1350
550
44
398
1350
550
48
398
1350
550
48
398
1350
550
48
398
398
830
830
550
550
33
33
Finned tube
Non-ammable insulation
Centrifugal fan
53
53
53
39
39
53
53
53
l/s
l/s
l/s
158
142
125
158
142
125
217
195
167
217
195
167
317
267
200
317
267
200
350
317
267
m3/h
m3/h
m3/h
dB(A)
dB(A)
570
570
570
510
510
510
450
450
450
47/45/43
47/45/43
47/45/43
34/32/30
34/32/30
34/32/30
Standard long-life lter supplied
Remote controller
780
700
600
48/46/43
35/33/30
780
700
600
48/46/43
35/33/30
1140
960
720
51/48/46
38/35/33
1140
960
720
51/48/46
38/35/33
1260
1140
960
53/50/47
40/37/34
in
in
in
3/8
3/8
3/8
1/4
1/4
1/4
1
1
1
RBC-UW136PG
Light ivory (Munsell 10Y 9/0.5)
1/2
1/2
1/4
1/4
1
1
RBC-UW266PG
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
mm
mm
mm
kg
8
1000
650
8
8
1520
650
11
8
1520
650
11
8
1520
650
11
8
1520
650
11
158
142
125
8
1000
650
8
8
1000
650
8
8
1520
650
11
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
47
Indoor units
1-way ceiling cassettes
Model MMU-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Power factor
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Room thermostat
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Ceiling panel model number
Panel colour
Panel dimensions
Height
Width
Depth
Panel weight
Rated conditions:
*
**
48
kW
kW
0071YH
2.2
2.5
0091YH
2.8
3.2
0121YH
3.6
4.0
0151SH
4.5
5.0
0181SH
5.6
6.3
0241SH
7.1
8.0
0.48
0.103
93
0.80
0.55
0.115
91
1.10
V-ph-Hz
A
kW
%
A
mm
mm
mm
kg
235
850
400
22
198
1000
655
27
198
1000
655
27
198
1200
655
31
235
235
850
850
400
400
22
22
Finned tube
Non-ammable insulation
Centrifugal fan
22
22
22
34
34
34
l/s
l/s
l/s
150
133
117
150
133
117
217
200
183
217
200
183
333
317
283
m3/h
m3/h
m3/h
dB(A)
dB(A)
540
540
480
480
420
420
55/52/47
55/52/47
42/39/34
42/39/34
Standard long-life lter supplied
Remote controller
Supplied
540
480
420
55/52/47
42/39/34
780
720
660
55/52/48
42/39/35
780
720
660
55/52/48
42/39/35
1200
1140
1020
56/54/50
43/41/37
in
in
in
3/8
3/8
1/4
1/4
1
1
RBC-UY135PG
W: Silky shade (1Y8.5/0.5)
3/8
1/4
1
1/2
1/4
1
RBC-US165PG
1/2
1/4
1
5/8
3/8
1
RBC-US265PG
mm
mm
mm
kg
18
1050
470
3.5
18
1050
470
3.5
10
1220
755
8.0
10
1220
755
8.0
10
1420
755
9.0
150
133
117
18
1050
470
3.5
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
Indoor units
Standard ducted units
Model MMD-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Static pressure (factory setting)
Static pressure (max.)
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Panel dimensions
Height
Width
Depth
Panel weight
Rated conditions:
*
**
V-ph-Hz
A
kW
A
0.83
0.107
1.44
0.98
0.128
1.70
0.98
0.128
1.70
mm
mm
mm
kg
320
700
800
32
320
700
800
32
320
1000
800
43
320
1000
800
43
320
1000
800
43
320
1350
800
55
320
1350
800
55
320
1350
800
55
320
320
320
550
550
550
800
800
800
28
28
28
Finned tube
Non-ammable insulation
Centrifugal fan
120
120
120
120
120
120
120
120
120
120
120
l/s
l/s
l/s
133
117
95
181
150
133
217
183
150
317
275
242
317
275
242
350
300
242
450
392
333
550
475
414
550
475
414
m3/h
m3/h
m3/h
Pa
Pa
dB(A)
dB(A)
480
480
570
650
420
420
490
540
340
340
400
480
40
40
40
40
100
100
100
100
43/41/39 43/41/39 44/42/40 44/42/40
30/28/26 30/28/26 31/29/27 31/29/27
Standard long-life lter supplied
Remote controller
780
660
540
40
100
45/43/41
32/30/28
1140
990
870
40
100
46/44/42
33/31/29
1140
990
870
40
100
46/44/42
33/31/29
1260
1080
870
40
100
47/45/42
34/32/29
1620
1410
1200
40
100
49/47/45
36/34/32
1980
1710
1490
40
100
51/49/45
38/36/32
1980
1710
1490
40
100
51/49/45
38/36/32
in
in
in
3/8
1/4
1
3/8
1/4
1
3/8
1/4
1
1/2
1/4
1
1/2
1/4
1
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
mm
mm
mm
kg
9
630
500
3.5
9
630
500
3.5
9
630
500
3.5
9
780
500
4.0
9
780
500
4.0
9
1080
500
6.0
9
1080
500
6.0
9
1080
500
6.0
9
1430
500
7.0
9
1430
500
7.0
9
1430
500
7.0
kW
kW
133
117
95
158
136
111
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
49
Indoor units
High-pressure ducted units
Model MMD-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Power factor
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Static pressure (factory setting)
Static pressure (low/medium/high)
Sound power level (high)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia***
Rated conditions:
*
**
***
50
kW
kW
0181H
5.6
6.3
0241H
7.1
8.0
0271H
8.0
9.0
0361H
11.2
12.5
0481H
14.0
16.0
0721H
22.4
25.0
0961H
28.0
31.5
5.25
1.200
99
13.6
5.52
1.260
99
14.8
V-ph-Hz
A
kW
%
A
mm
mm
mm
kg
380
850
660
52
380
850
660
56
380
1200
660
67
470
1380
1250
150
470
1380
1250
150
380
380
850
850
660
660
50
52
Finned tube
Non-ammable insulation
Centrifugal fan
160
160
160
260
260
370 x 3
370 x 3
l/s
l/s
l/s
300
250
200
439
367
295
533
445
356
700
583
467
1200
1000
800
1400
1167
933
m3/h
m3/h
m3/h
Pa
Pa
dB(A)
dB(A)
1080
1580
900
1320
720
1060
137
137
68.6/137/196 68.6/137/196
50
53
37/35/33
40/38/36
Optional or eld-supplied
Remote controller
1580
1320
1060
137
68.6/137/196
53
40/38/36
1920
1600
1280
137
68.6/137/196
53
40/38/36
2520
2100
1680
137
68.6/137/196
53
40/38/36
4320
3600
2880
137
68.6/137/196
62
49/47/45
5040
4200
3360
137
68.6/137/196
63
50/48/46
in
in
in
1/2
1/4
1
5/8
3/8
1
5/8
3/8
1
5/8
3/8
1
7/8
1/2
1
7/8
1/2
1
439
367
295
5/8
3/8
1
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
Male screw connection one side
Indoor units
Slim duct units
Model MMD-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Static pressure (factory setting)
Static pressure (max.)
Air lter pressure loss
Lower air inlet
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Rear air inlet
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Rated conditions:
*
**
kW
kW
0071SPH
2.2
2.5
0091SPH
2.8
3.2
0121SPH
3.6
4.0
0151SPH
4.5
5.0
0181SPH
5.6
6.3
V-ph-Hz
A
kW
A
mm
mm
mm
kg
210
845
645
22
210
845
645
23
210
845
645
23
210
210
845
845
645
645
22
22
Finned tube
Polyethylene foam and polyurethane foam
Centrifugal fan
60
60
60
60
60
l/s
l/s
l/s
150
131
111
150
131
111
167
145
125
192
167
145
217
189
161
m3/h
m3/h
m3/h
Pa
Pa
Pa
540
470
400
6
-16/-31/-46
4
540
470
400
6
-16/-31/-46
4
600
520
450
5
-15/-30/-45
5
690
600
520
5
-15/-30/-45
5
780
680
580
4
-14/-29/-44
6
dB(A)
dB(A)
49/46/43
36/33/30
49/46/43
36/33/30
51/48/45
38/35/32
52/49/46
39/36/33
53/51/49
40/38/36
dB(A)
dB(A)
41/39/37
41/39/37
28/26/24
28/26/24
Standard long-life lter supplied
Remote controller
42/40/38
29/27/25
45/43/41
32/30/28
46/44/42
33/31/29
in
in
in
3/8
1/4
1
3/8
1/4
1
1/2
1/4
1
1/2
1/4
1
3/8
1/4
1
0.39
0.054
0.68
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
51
Indoor units
Ceiling-suspended units
Model MMC-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Room thermostat
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Rated conditions:
*
**
52
kW
kW
0151H
4.5
5.0
0181H
5.6
6.3
0241H
7.1
8.0
0271H
8.0
9.0
0361H
11.2
12.5
0481H
14.0
16.0
V-ph-Hz
A
kW
A
mm
mm
mm
kg
210
1180
680
26
210
1180
680
26
210
1595
680
34
210
1595
680
34
210
210
910
910
680
680
22
22
Finned tube
Non-ammable insulation
Centrifugal fan
30
30
40
40
80
80
l/s
l/s
l/s
200
167
150
308
250
233
308
250
233
458
383
333
500
433
367
m3/h
m3/h
m3/h
dB(A)
dB(A)
720
780
600
660
540
540
48/45/43
49/46/43
35/32/30
36/33/30
Standard long-life lter supplied
Remote controller
Supplied
1110
900
840
51/49/46
38/36/33
1110
900
840
51/49/46
38/36/33
1650
1380
1200
54/51/48
41/38/35
1800
1560
1320
56/53/50
43/40/37
in
in
in
1/2
1/4
3/4
5/8
3/8
3/4
5/8
3/8
3/4
5/8
3/8
3/4
5/8
3/8
3/4
217
183
150
1/2
1/4
3/4
0.84
0.110
1.25
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
Indoor units
High-wall units (1 Series)
Model MMK-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Starting current
Unit appearance
Suction grille and side panel
Discharge grille
Bottom surface
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Rated conditions:
*
**
kW
kW
0071H
2.2
2.5
0091H
2.8
3.2
0121H
3.6
4.0
0151H
4.5
5.0
V-ph-Hz
A
kW
A
0181H
5.6
6.3
0241H
7.1
8.0
0.32
0.037
0.42
0.35
0.040
0.47
368
895
210
18
368
1055
210
19
368
1055
210
19
368
1430
210
25
368
368
895
895
210
210
18
18
Finned tube
Non-ammable insulation
Tangential fan
30
30
30
30
30
30
l/s
l/s
l/s
167
150
133
167
150
133
217
183
167
217
183
167
333
283
250
m3/h
m3/h
m3/h
dB(A)
dB(A)
600
600
540
540
480
480
52/47/44
52/47/44
39/34/31
39/34/31
Standard single lter supplied
Remote controller
600
540
480
52/47/44
39/34/31
780
660
600
55/51/48
42/38/35
780
660
600
55/51/48
42/38/35
1200
1020
900
55/51/48
42/38/35
in
in
in
3/8
1/4
3/4
3/8
1/4
3/4
1/2
1/4
3/4
1/2
1/4
3/4
5/8
3/8
3/4
167
150
133
3/8
1/4
3/4
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
53
Indoor units
High-wall units (2 Series)
Model MMK-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Starting current
Unit appearance
Suction grille and side panel
Discharge grille
Bottom surface
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Rated conditions:
*
**
54
kW
kW
0072H
2,2
2,5
0092H
2,8
3,2
V-ph-Hz
A
kW
A
0122H
3,6
4,0
0,19
0,019
0,24
Moon white
Moon white
Moon white
mm
mm
mm
kg
275
790
208
11
275
790
208
11
275
790
208
11
Finned tube
Non-ammable insulation
Tangential fan
30
30
30
l/s
l/s
l/s
133
117
100
142
125
100
150
125
100
m3/h
m3/h
m3/h
dB(A)
dB(A)
480
420
360
48/45/42
35/32/29
Standard single lter supplied
Remote controller
510
450
360
49/46/42
36/33/29
540
450
360
50/46/42
37/33/29
in
in
mm
3/8
1/4
16
3/8
1/4
16
3/8
1/4
16
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
Indoor units
Floor-mounted console units
Model MML-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Power factor
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia (polyvinyl tube)
Rated conditions:
*
**
kW
kW
0071H
2.2
2.5
0091H
2.8
3.2
0121H
3.6
4.0
0151H
4.5
5.0
0181H
5.6
6.3
0241H
7.1
8.0
0.47
0.102
94
1.10
0.47
0.102
94
1.10
V-ph-Hz
A
kW
%
A
mm
mm
mm
kg
630
950
230
37
630
950
230
37
630
950
230
40
630
950
230
40
630
630
950
950
230
230
37
37
Finned tube
Non-ammable insulation
Centrifugal fan
45
45
45
45
70
70
l/s
l/s
l/s
133
117
100
250
217
181
250
217
181
300
258
217
300
258
217
m3/h
m3/h
m3/h
dB(A)
dB(A)
480
480
420
420
360
360
52/50/48
52/50/48
39/37/35
39/37/35
Standard single lter supplied
Remote controller
900
780
650
58/54/51
45/41/38
900
780
650
58/54/51
45/41/38
1080
930
780
62/57/52
49/44/39
1080
930
780
62/57/52
49/44/39
in
in
in
3/8
1/4
3/4
3/8
1/4
3/4
1/2
1/4
3/4
1/2
1/4
3/4
5/8
3/8
3/4
133
117
100
3/8
1/4
3/4
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
55
Indoor units
Concealed chassis units
Model MML-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Power factor
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Static pressure
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia.***
Rated conditions:
*
**
***
56
kW
kW
0071BH
2.2
2.5
0091BH
2.8
3.2
0121BH
3.6
4.0
0151BH
4.5
5.0
0181BH
5.6
6.3
0241BH
7.1
8.0
0.45
0.090
87
0.80
0.46
0.095
90
1.00
V-ph-Hz
A
kW
%
A
mm
mm
mm
kg
600
745
220
21
600
1045
220
29
600
1045
220
29
600
1045
220
29
600
600
745
745
220
220
21
21
Finned tube
Non-ammable insulation
Centrifugal fan
19
19
19
70
70
70
l/s
l/s
l/s
128
111
83
128
111
83
206
167
136
206
167
136
264
220
178
m3/h
m3/h
m3/h
kPa
dB(A)
dB(A)
460
460
400
400
300
300
0
0
49/47/45
49/47/45
36/34/32
36/34/32
Standard single lter supplied
Remote controller
460
400
300
0
49/47/45
36/34/32
740
600
490
0
49/47/45
36/34/32
740
600
490
0
49/47/45
36/34/32
950
790
640
0
55/50/46
42/37/33
in
in
in
3/8
1/4
3/4
3/8
1/4
3/4
1/2
1/4
3/4
1/2
1/4
3/4
5/8
3/8
3/4
128
111
83
3/8
1/4
3/4
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
Male screw connection one side.
Indoor units
Floor-mounted cabinet units
Model MMF-AP
Cooling capacity*
Heating capacity
Electrical data
Power supply
Operating current
Power input
Power factor
Starting current
Unit appearance
Unit dimensions
Height
Width
Depth
Unit weight
Heat exchanger
Sound proong/heat insulating material
Fan type
Fan motor power input
Air ow
High
Medium
Low
Air ow
High
Medium
Low
Sound power level (high/medium/low)
Sound pressure level (high/medium/low)**
Air lter
Controller
Connection pipes
Gas connection diameter
Liquid connection diameter
Drain connection, nom. dia***
Rated conditions:
*
**
***
kW
kW
0151H
4.5
5.0
0181H
5.6
6.3
0241H
7.1
8.0
0271H
8.0
9.0
0361H
11.2
12.5
0481H
14.0
16.0
0561H
16.0
18.0
1.60
0.350
95
2.10
1.60
0.350
95
2.10
V-ph-Hz
A
kW
%
A
mm
mm
mm
kg
1750
600
210
49
1750
600
210
49
1750
600
390
65
1750
600
390
65
1750
600
390
65
1750
1750
600
600
210
210
48
48
Finned tube
Non-ammable insulation
Centrifugal fan
37
37
63
63
110
160
160
l/s
l/s
l/s
250
217
183
333
283
233
333
283
233
533
467
383
600
517
433
600
517
433
m3/h
m3/h
m3/h
dB(A)
dB(A)
900
900
1200
780
780
1020
660
660
840
59/56/51
59/56/51
62/58/53
46/43/38
46/43/38
49/45/40
Standard single lter supplied
Remote controller
1200
1020
840
62/58/53
49/45/40
1920
1680
1380
64/61/57
51/48/44
2160
1860
1560
67/63/59
54/50/46
2160
1860
1560
67/63/59
54/50/46
in
in
in
1/2
1/4
3/4
5/8
3/8
3/4
5/8
3/8
3/4
5/8
3/8
3/4
5/8
3/8
3/4
250
217
183
1/2
1/4
3/4
5/8
3/8
3/4
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
Cooling capacities and electrical data are measured at the conditions specied by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
Male screw connection one side
57
Outdoor units
Rating
Cooling only model MMY
Heat pump model MMY
Outdoor unit type
Cooling capacity
Heating capacity
Power supply
Voltage range
Power input, cooling
Power factor, cooling
Operating current, cooling
EER, cooling
Starting current
Power input, heating
Power factor, heating
Operating current, heating
COP, heating
Starting current
Unit appearance
Dimensions
Height
Width
Depth
Total weight - cooling only unit
Total weight - heat pump unit
Heat exchanger
Sound power level
Sound pressure level
Fan type
Motor power input
Air ow
Compressor type
Motor power input
Refrigerant charge R-410A*
Cooling
Heating
Pipework**
Suction line type - diameter
Liquid line type - diameter
Balance pipe type - diameter
Maximum equivalent length separation
Maximum actual piping length
Maximum total piping length
Maximum lift - indoor unit above/below***
Control wiring
Central remote controller
Max. number of connectable indoor units
High-pressure switch
Protection devices
Operating range, cooling
Operating range, heating
Rated conditions:
*
**
***
58
hp
5
6
MAP0501T8
MAP0601T8
MAP0501HT8
MAP0601HT8
Inverter
Inverter
14.0
16.0
16.0
18.0
400-3-50 10%
400-3-50 10%
380-415
380-415
3.65
4.64
90
92
5.85
7.28
3.84
3.45
1.0
1.0
3.84
4.56
91
93
6.09
7.08
4.17
3.95
1.0
1.0
Silky shade (Munsell 1Y8.5/0.5)
8
MAP0801T8
MAP0801HT8
Inverter
22.4
25.0
400-3-50 10%
380-415
5.67
95
8.62
3.95
1.0
5.88
95
8.93
4.25
1.0
10
MAP1001T8
MAP1001HT8
Inverter
28.0
31.5
400-3-50 10%
380-415
7.68
96
11.55
3.65
1.0
7.97
96
11.98
3.95
1.0
12
MAP1201T8
MAP1201HT8
Inverter
33.5
37.5
400-3-50 10%
380-415
11.92
94
18.30
2.81
1.0
10.19
94
15.65
3.68
1.0
1800
990
750
227
228
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
kW
1800
990
750
227
228
Finned type
68
55
Propeller
0.6
2500 - 9000
Hermetic
1.1 x 2
69
56
Propeller
0.6
2500 - 9000
Hermetic
1.4 x 2
70
57
Propeller
0.6
2750 - 9900
Hermetic
2.3 x 2
71
58
Propeller
0.6
2917 - 10500
Hermetic
3.1 x 2
72
59
Propeller
0.6
2917 - 10500
Hermetic
4.2 x 2
kg
kg
8.0
8.5
8.0
8.5
11.0
12.5
11.0
12.5
11.0
12.5
in
in
in
m
m
m
m
Flare - 5/8
Brazed - 3/4
Brazed - 7/8
Brazed - 7/8
Brazed - 1-1/8
Flare - 3/8
Flare - 3/8
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
Shielded wire 1.25 mm2 x 2 cores up to 2000 m
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m
8
10
13
16
20
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
mm
mm
mm
kg
kg
dB(A)
dB(A) at 1 m
kW
l/s - m3/h
MPa
C
C
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
14
AP1401T8
AP1401HT8
Inverter
Inverter
16
AP1601T8
AP1601HT8
Inverter
Inverter
18
AP1801T8
AP1801HT8
Inverter
Inverter
20
AP2001T8
AP2001HT8
Inverter
Inverter
0801T8
0801T8
1001T8
1001T8
0601T8
0801T8
0801HT8
0601HT8
0801HT8
0801HT8
38.4
45.0
43.0
50.0
400-3-50 10%
400-3-50 10%
380-415
380-415
11.12
12.20
94
95
17.08
18.54
3.45
3.69
1.0
1.0
10.96
12.28
94
95
16.83
18.65
3.92
4.07
1.0
1.0
Silky shade (Munsell 1Y8.5/0.5)
mm
mm
mm
kg
kg
0801T8
1001HT8
0801HT8
50.4
56.5
400-3-50 10%
380-415
14.16
96
21.29
3.56
1.0
14.37
96
21.61
3.93
1.0
1001HT8
1001HT8
56.0
63.0
400-3-50 10%
380-415
16.17
96
24.31
3.46
1.0
16.46
96
24.75
3.83
1.0
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
74
61
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
11.0
12.5
11.0
12.5
11.0
12.5
1800
990
750
256
258
Finned type
dB(A)
72.5
dB(A) at 1 m 59.5
Propeller
kW
0.6
l/s
2750
m3/h
9900
Hermetic
kW
2.3 x 2
1800
990
750
227
228
1800
990
750
256
258
Propeller
0.6
2500
9000
Hermetic
1.4 x 2
73
60
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
73.5
60.5
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
kg
kg
11.0
12.5
8.0
8.5
11.0
12.5
11.0
12.5
11.0
12.5
in
in
in
m
m
m
m
Brazed - 7/8 Brazed - 3/4 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8
Flare - 1/2 Flare - 3/8
Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2
Flare - 3/8 Flare - 3/8
Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8
175
175
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
2
2
Shielded wire 1.25 mm x 2 pieces up to 1000 m, 2.0 mm x 2 pieces up to 2000 m
23
27
30
33
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
MPa
C
C
1001T8
Brazed - 7/8
Flare - 1/2
Flare - 3/8
175
300
40/50
Rated conditions:
*
**
***
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
59
60
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
22
AP2201T8
AP2201HT8
Inverter
Inverter
0801T8
0801T8
0801HT8
0801HT8
61.5
69.0
400-3-50 10%
400-3-50 10%
380-415
380-415
17.39
95
26.42
3.54
1.0
17.35
95
26.36
3.98
1.0
Silky shade (Munsell 1Y8.5/0.5)
mm
mm
mm
kg
kg
Inverter
22
AP2211T8
AP2211HT8
Inverter
Inverter
0601T8
1201T8
1001T8
0601HT8
1201HT8
61.5
69.0
400-3-50 10%
380-415
20.41
95
31.01
3.01
1.0
18.68
95
28.38
3.69
1.0
1001HT8
400-3-50 10%
380-415
400-3-50 10%
380-415
1800
990
750
256
258
Finned type
dB(A)
74.5
dB(A) at 1 m 61.5
Propeller
kW
0.6
l/s
2750
m3/h
9900
Hermetic
kW
2.3 x 2
1800
990
750
256
258
kg
kg
11.0
12.5
in
in
in
m
m
m
m
Brazed - 7/8
Brazed - 7/8
Brazed - 3/4
Brazed - 1-1/8
Brazed - 7/8
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m
37
37
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
MPa
C
C
1800
990
750
227
228
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
Propeller
0.6
2500
9000
Hermetic
1.4 x 2
74.5
61.5
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
11.0
12.5
8.0
8.5
11.0
12.5
11.0
12.5
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
24
AP2401T8
AP2401HT8
Inverter
Inverter
0801T8
0801T8
0801HT8
0801HT8
68.0
76.5
400-3-50 10%
400-3-50 10%
380-415
380-415
18.44
96
27.73
3.69
1.0
18.79
97
27.96
4.07
1.0
Silky shade (Munsell 1Y8.5/0.5)
mm
mm
mm
kg
kg
Inverter
0801T8
1201T8
1201T8
0801HT8
1201HT8
68.0
76.5
400-3-50 10%
380-415
25.02
95
38.02
2.72
1.0
21.32
96
32.06
3.59
1.0
1201HT8
400-3-50 10%
380-415
400-3-50 10%
380-415
1800
990
750
256
258
Finned type
dB(A)
75.0
dB(A) at 1 m 62.0
Propeller
kW
0.6
l/s
2750
m3/h
9900
Hermetic
kW
2.3 x 2
kg
kg
11.0
12.5
in
in
in
m
m
m
m
Brazed - 7/8
Brazed - 7/8
Brazed - 7/8
Brazed - 1-1/8
Brazed -1-1/8
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
2
2
Shielded wire 1.25 mm x 2 pieces up to 1000 m, 2.0 mm x 2 pieces up to 2000 m
40
40
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
MPa
C
C
1800
990
750
256
258
Inverter
24
AP2411T8
AP2411HT8
Inverter
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
75.0
62.0
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
Rated conditions:
*
**
***
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
61
62
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
26
AP2601T8
AP2601HT8
Inverter Inverter
1001T8
0801T8
Inverter
28
AP2801T8
AP2801HT8
Inverter
Inverter
0801T8
1001T8
mm
mm
mm
kg
kg
Inverter
30
AP3001T8
AP3001HT8
Inverter
Inverter
Inverter
1001T8
0801T8
1001T8
1001T8
1001T8
1001HT8
78.5
88.0
400-3-50
380-415
22.27
96
33.48
3.52
1.0
22.60
96
33.98
3.89
1.0
1001HT8
0801HT8
1001HT8
1001HT8
400-3-50
380-415
400-3-50
380-415
1001HT8
84.0
95.0
400-3-50
380-415
24.26
96
36.48
3.46
1.0
24.82
97
36.93
3.83
1.0
400-3-50
380-415
400-3-50
380-415
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
11.0
12.5
11.0
12.5
1800
1800
990
990
750
750
256
256
258
258
Finned type
dB(A)
75.0
dB(A) at 1 m 62.0
Propeller Propeller
kW
0.6
0.6
l/s
2917
2750
m3/h
10500
9900
Hermetic Hermetic
kW
3.1 x 2
2.3 x 2
1800
990
750
256
258
75.5
62.5
Propeller Propeller
0.6
0.6
2750
2917
9900
10500
Hermetic Hermetic
2.3 x 2
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
76.0
63.0
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
kg
kg
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
in
in
in
m
m
m
m
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8
Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
MPa
C
C
11.0
12.5
11.0
12.5
175
175
175
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
2
2
Shielded wire 1.25 mm x 2 pieces up to 1000 m, 2.0 mm x 2 pieces up to 2000 m
43
47
48
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db
-5 to 43 db
-20 to 16 wb
-20 to 16 wb
-20 to 16 wb
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
175
300
40/50
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
32
AP3201T8
AP3201HT8
Inverter
Inverter
Inverter
0801T8
0801T8
0801T8
0801HT8
0801HT8
0801HT8
90.0
100.0
400-3-50
400-3-50
400-3-50
380-415
380-415
380-415
24.41
95
37.09
3.69
1.0
24.56
95
37.32
4.07
1.0
Silky shade (Munsell 1Y8.5/0.5)
mm
mm
mm
kg
kg
Inverter
0801T8
1201T8
1001T8
1001T8
0801HT8
1201HT8
90.0
100.0
400-3-50
380-415
28.65
96
43.08
3.14
1.0
26.78
95
40.69
3.73
1.0
1001HT8
1001HT8
400-3-50
380-415
400-3-50
380-415
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
11.0
12.5
11.0
12.5
400-3-50
380-415
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
76.0
63.0
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
kg
kg
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
in
in
in
m
m
m
m
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8 Brazed - 7/8
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
175
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m
48
48
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb
C
C
1800
990
750
256
258
Inverter
1800
990
750
258
258
Finned type
dB(A)
76.0
dB(A) at 1 m 63.0
Propeller
kW
0.6
l/s
2750
m3/h
9900
Hermetic
kW
2.3 x 2
MPa
1800
990
750
256
258
Inverter
32
AP3211T8
AP3211HT8
Inverter
Brazed - 7/8
Flare - 1/2
Flare - 3/8
175
300
40/50
-5 to 43 db
-20 to 16 wb
Rated conditions:
*
**
***
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
63
64
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
mm
mm
mm
kg
kg
34
AP3401T8
AP3401HT8
Inverter
Inverter
Inverter
1001T8
0801T8
0801T8
1001HT8
0801HT8
0801HT8
96.0
108.0
400-3-50
400-3-50
400-3-50
380-415
380-415
380-415
26.53
96
39.89
3.62
1.0
27.03
97
40.22
4.00
1.0
Silky shade (Munsell 1Y8.5/0.5)
Inverter
0801T8
1201T8
1201T8
1001T8
0801HT8
1201HT8
96.0
108.0
400-3-50
380-415
33.08
95
50.26
2.90
1.0
29.54
96
44.42
3.66
1.0
1201HT8
1001HT8
400-3-50
380-415
400-3-50
380-415
400-3-50
380-415
kW
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
kg
kg
11.0
12.5
11.0
12.5
in
in
in
m
m
m
m
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8 Brazed - 1-1/8
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
175
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m
48
48
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb
-20 to 16 wb
kW
l/s
m3/h
MPa
C
C
1800
990
750
256
258
Inverter
1800
990
750
256
258
Finned type
76.5
63.5
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
dB(A)
dB(A) at 1 m
1800
990
750
256
258
Inverter
34
AP3411T8
AP3411HT8
Inverter
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
76.5
63.5
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
Brazed - 7/8
Flare - 1/2
Flare - 3/8
175
300
40/50
-5 to 43 db
-20 to 16 wb
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
36
AP3601T8
AP3601HT8
Inverter
Inverter
Inverter
1001T8
1001T8
0801T8
1001HT8
1001HT8
0801HT8
101.0
113.0
400-3-50
400-3-50
400-3-50
380-415
380-415
380-415
28.38
96
42.67
3.56
1.0
28.74
96
43.21
3.93
1.0
Silky shade (Munsell 1Y8.5/0.5)
mm
mm
mm
kg
kg
Inverter
0801T8
1201T8
1201T8
1201T8
0801HT8
1201HT8
101.0
113.0
400-3-50
380-415
37.16
94
57.06
2.72
1.0
31.49
94
48.36
3.59
1.0
1201HT8
1201HT8
400-3-50
380-415
400-3-50
380-415
400-3-50
380-415
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
kg
kg
11.0
12.5
11.0
12.5
in
in
in
m
m
m
m
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8 Brazed - 1-1/8
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
175
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m
48
48
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db
-5 to 43 db
-5 to 43 db -5 to 43 db
-5 to 43 db
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb
-20 to 16 wb
C
C
1800
990
750
256
258
Inverter
1800
990
750
256
258
Finned type
dB(A)
76.5
dB(A) at 1 m 63.5
Propeller
kW
0.6
l/s
2917
m3/h
10500
Hermetic
kW
3.1 x 2
MPa
1800
990
750
256
258
Inverter
36
AP3611T8
AP3611HT8
Inverter
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
77.0
64.0
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
Brazed - 1-1/8
Flare - 1/2
Flare - 3/8
175
300
40/50
-5 to 43 db
-20 to 16 wb
Rated conditions:
*
**
***
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
65
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
Rated conditions:
*
**
***
66
Inverter
1001T8
1001T8
1800
990
750
256
258
Finned type
dB(A)
77.0
dB(A) at 1 m 64.0
Propeller
kW
0.6
l/s
2917
m3/h
10500
Hermetic
kW
3.1 x 2
C
C
1001T8
1001HT8
1001HT8
1001HT8
106.5
119.5
400-3-50
400-3-50
400-3-50
380-415
380-415
380-415
30.36
96
45.65
3.51
1.0
30.83
96
46.36
3.88
1.0
Silky shade (Munsell 1Y8.5/0.5)
mm
mm
mm
kg
kg
Compressor type
Motor power input
Refrigerant charge R-410A*
Cooling
kg
Heating
kg
Pipework**
Suction line type - diameter
in
Liquid line type - diameter
in
Balance pipe type - diameter
in
Maximum equivalent length separation
m
Maximum actual piping length
m
Maximum total piping length
m
Maximum lift - indoor unit above/below*** m
Control wiring
Central remote controller
Max. number of connectable indoor units
High-pressure switch
MPa
Protection devices
Operating range, cooling
Operating range, heating
38
AP3801T8
AP3801HT8
Inverter
Inverter
11.0
12.5
1800
990
750
256
258
1800
990
750
256
258
Inverter
40
AP4001T8
AP4001HT8
Inverter
Inverter
Inverter
Inverter
0801T8
1001T8
1001T8
1001T8
1001T8
0801HT8
1001HT8
112.0
126.5
400-3-50
380-415
32.34
96
48.63
3.46
1.0
33.05
96
49.69
3.83
1.0
1001HT8
1001HT8
1001HT8
400-3-50
380-415
400-3-50
380-415
400-3-50
380-415
400-3-50
380-415
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
11.0
12.5
11.0
12.5
11.0
12.5
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2750
9900
Hermetic
2.3 x 2
77.0
64.0
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2 Flare - 1/2 Flare - 1/2
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8 Flare - 3/8 Flare - 3/8
175
175
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
2
2
Shielded wire 1.25 mm x 2 pieces up to 1000 m, 2.0 mm x 2 pieces up to 2000 m
48
48
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db -5 to 43 db -5 to 43 db 5 to 43 db
-5 to 43 db -5 to 43 db 5 to 43 db
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
Brazed - 7/8
Flare - 1/2
Flare - 3/8
175
300
40/50
-5 to 43 db
-20 to 16 wb
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
Inverter
Inverter
1201T8
1001T8
1001T8
1201HT8
1001HT8
1001HT8
118.0
132.0
400-3-50
400-3-50
400-3-50
380-415
380-415
380-415
36.74
96
55.24
3.21
1.0
35.14
95
53.39
3.76
1.0
Silky shade (Munsell 1Y8.5/0.5)
mm
mm
mm
kg
kg
1800
990
750
256
258
Finned type
dB(A)
77.5
dB(A) at 1 m 64.5
Propeller
kW
0.6
l/s
2917
m3/h
10500
Hermetic
kW
4.2 x 2
Compressor type
Motor power input
Refrigerant charge R-410A*
Cooling
kg
Heating
kg
Pipework**
Suction line type - diameter
in
Liquid line type - diameter
in
Balance pipe type - diameter
in
Maximum equivalent length separation
m
Maximum actual piping length
m
Maximum total piping length
m
Maximum lift - indoor unit above/below*** m
Control wiring
Central remote controller
Max. number of connectable indoor units
High-pressure switch
MPa
Protection devices
Operating range, cooling
Operating range, heating
42
AP4201T8
AP4201HT8
Inverter
C
C
11.0
12.5
1800
990
750
256
258
1800
990
750
256
258
Inverter
44
AP4401T8
AP4401HT8
Inverter
Inverter
Inverter
Inverter
1001T8
1201T8
1201T8
1001T8
1001T8
1001HT8
1201HT8
123.5
138.5
400-3-50
380-415
40.99
95
62.28
3.01
1.0
37.36
95
56.76
3.69
1.0
1201HT8
1001HT8
1001HT8
400-3-50
380-415
400-3-50
380-415
400-3-50
380-415
400-3-50
380-415
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
11.0
12.5
11.0
12.5
11.0
12.5
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
77.5
64.5
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
Brazed - 1-1/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8 Brazed - 1-1/8 Brazed - 7/8 Brazed - 7/8
Flare - 1/2
Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2
Flare - 1/2
Flare - 1/2 Flare - 1/2
Flare - 3/8
Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8
Flare - 3/8
Flare - 3/8 Flare - 3/8
175
175
175
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m
48
48
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db
-5 to 43 db -5 to 43 db 5 to 43 db -5 to 43 db
-5 to 43 db
5 to 43 db -5 to 43 db
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb
Rated conditions:
*
**
***
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
67
hp
kW
kW
V-ph-Hz
V
kW
%
A
kW/kW
A
kW
%
A
kW/kW
A
Rated conditions:
*
**
***
68
Inverter
1201T8
1201T8
1800
990
750
256
258
Finned type
dB(A)
78.0
dB(A) at 1 m 65.0
Propeller
kW
0.6
l/s
2917
m3/h
10500
Hermetic
kW
4.2 x 2
C
C
1201T8
1201HT8
1201HT8
1201HT8
130.0
145.0
400-3-50
400-3-50
400-3-50
380-415
380-415
380-415
45.59
95
69.27
2.85
1.0
39.85
95
60.55
3.64
1.0
Silky shade (Munsell 1Y8.5/0.5)
mm
mm
mm
kg
kg
Compressor type
Motor power input
Refrigerant charge R-410A*
Cooling
kg
Heating
kg
Pipework**
Suction line type - diameter
Liquid line type - diameter
in
Balance pipe type - diameter
in
Maximum equivalent length separation m
Maximum actual piping length
m
Maximum total piping length
m
Maximum lift - indoor unit above/below*** m
Control wiring
Central remote controller
Max. number of connectable indoor units
High-pressure switch
MPa
Protection devices
Operating range, cooling
Operating range, heating
46
AP4601T8
AP4601HT8
Inverter
Inverter
11.0
12.5
1800
990
750
256
258
1800
990
750
256
258
Inverter
48
AP4801T8
AP4801HT8
Inverter
Inverter
Inverter
Inverter
1001T8
1201T8
1201T8
1201T8
1201T8
1001HT8
1201HT8
135.0
150.0
400-3-50
380-415
49.67
95
75.47
2.72
1.0
41.80
94
64.19
3.59
1.0
1201HT8
1201HT8
1201HT8
400-3-50
380-415
400-3-50
380-415
400-3-50
380-415
400-3-50
380-415
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
1800
990
750
256
258
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
11.0
12.5
11.0
12.5
11.0
12.5
Brazed - 1-1/8
Brazed - 1-1/8
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
Propeller
0.6
2917
10500
Hermetic
3.1 x 2
78.0
65.0
Propeller
0.6
2917
10500
Hermetic
4.2 x 2
11.0
12.5
11.0
12.5
11.0
12.5
11.0
12.5
Flare - 1/2
Flare - 1/2 Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 1/2
Flare - 3/8
Flare - 3/8 Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
175
175
175
175
175
175
175
150 (if equivalent bend length is longer, equivalent length is standard)
300
300
300
300
300
300
300
40/50
40/50
40/50
40/50
40/50
40/50
40/50
2
Shielded wire 1.25 mm x 2 cores up to 2000 m
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m
48
48
Off: 2.90/On: 3.73
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,
overcurrent relay
-5 to 43 db -5 to 43 db -5 to 43 db 5 to 43 db
-5 to 43 db -5 to 43 db 5 to 43 db
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb
Cooling: Indoor air temperature 27C db/19C wb, outdoor air temperature 35C db
Heating: Indoor air temperature 20C db, outdoor air temperature 7C db/6C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
Please refer to page 24.
Flare - 1/2
Flare - 3/8
175
300
40/50
-5 to 43 db
-20 to 16 wb
MMD-AP0071BH, AP0091BH
Standard air ow 133 l/s (480 m3/h)
Legend
1.
High static pressure 2H tap
2.
High static pressure 1H tap
3.
Standard H tap
4.
Low static pressure H tap
5.
Standard L tap
MMD-AP0181BH
MMD-AP0151BH
6.
7.
8.
9.
Application limit
Lower air ow limit
Upper air ow limit
Long life lter
69
MMD-AP0301BH
MMD-AP0241BH, AP0271BH
MMD-AP0361BH
MMD-AP0481BH, AP0561BH
Legend
1.
High static pressure 2H tap
2.
High static pressure 1H tap
3.
Standard H tap
4.
Low static pressure H tap
5.
Standard L tap
6.
Application limit
7.
Lower air ow limit
8.
Upper air ow limit
9.
Long life lter
70
MMD-AP0181H
MMD-AP0481H
MMD-AP0361H
Legend
1.
High static pressure tap
2.
Medium static pressure tap
3.
Low static pressure tap
4.
Lower air ow limit
5.
Upper air ow limit
71
MMD-AP0961H
MMD-AP0721H
1.
2.
3.
Add an air ow damper to the air supply duct, and adjust the air ow in the range from 80% to 120% of the
standard air ow rate.
72
MMD-AP0071SPH, AP0091SPH
60
60
50
50
3
40
30
5
8
20
30
9
!
!
0
10
20
4
40
10
$
%
0
300
400
500
600
0
300
700
400
500
83
139
167
194
MMD-AP0151SPH
60
600
700
83
194
MMD-AP0181SPH
60
167
139
50
50
4
3
30
40
8
9
20
7
30
20
500
600
9
#
10
10
6
5
0
400
40
139
167
700
800
0
400
500
600
194
222
111
139
167
700
800
900
194
222
250
73
MMD-AP0121SPH
Standard air ow 167 l/s (600 m3/h)
60
2
2
1
50
30
40
50
5
8
20
3
!
6
30
5
9
20
10
40
10
%
^
0
300
400
500
600
700
0
300
400
500
600
700
83
111
139
167
194
83
139
167
194
MMD-AP0151SPH
MMD-AP0181SPH
60
60
50
50
30
3
40
8
9
20
40
20
$
@
10
#
%
0
400
500
111
139
600
700
800
0
400
500
600
700
800
900
167
194
222
111
139
167
194
222
250
Legend
1.
Upper limit of external static pressure (50 Pa)
2.
High (50 Pa)
3.
Upper limit of external static pressure (35 Pa)
4.
High (35 Pa)
5.
Upper limit of external static pressure (20 Pa)
6.
Low (50 Pa)
7.
Lower limit of external static pressure (50 Pa)
74
10
6
5
30
8.
9.
10.
11.
12.
13.
14.
15.
16.
Model
AP0091H-AP0301H
AP0361H-AP0561H
Z view
A
250
319
B
120
183
Legend
1.
Control box
2.
Hanging bolt pitch
3.
Overall panel dimension
4.
Air inlet
5.
Air outlet (4-way)
6.
Ceiling opening
7.
Hanging bolt M10 or W3/8 eld-supplied
8.
Bottom ceiling surface
9.
10.
11.
12.
13.
14.
15.
16.
75
Legend
1.
Centre of main unit
2.
Centre of panel
3.
Control box
4.
Hanging bolt pitch
5.
Unit dimension
6.
Ceiling opening
7.
Overall panel dimension
8.
Air outlet (2-way)
9.
Air inlet (2-way)
10. Ceiling
All dimensions are given in mm.
76
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
Obstruction
Hanging bolt 4-M10 eld-supplied
Ceiling panel eld-supplied
Branch duct knockout hole (also on the reverse side)
Bottom ceiling surface
Indoor unit
Refrigerant pipe connection (liquid 1/4)
Refrigerant pipe connection (gas 3/8)
Drain pipe connection (inner 32, nominal 25) for vinyl chloride pipe
Drain test point
Knockout hole for air intake (only on reverse side)
Power supply connection
Model
MMU-AP0151WH to AP0181WH
MMU-AP0241WH to AP0301WH
Legend
1.
Centre of main unit
2.
Centre of panel
3.
Control box
4.
Hanging bolt pitch
5.
Unit dimension
6.
Ceiling opening
7.
Overall panel dimension
8.
Air outlet (2-way)
9.
Air inlet (2-way)
10. Ceiling
11. Obstruction
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
A
1/4
3/8
B
1/2
5/8
77
Legend
1.
Centre of main unit
2.
Centre of panel
3.
Control box
4.
Hanging bolt pitch
5.
Unit dimension
6.
Ceiling opening
7.
Overall panel dimension
8.
Air outlet (2-way)
9.
Air inlet (2-way)
10. Ceiling
11. Obstruction
All dimensions are given in mm.
78
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
A
235
B
245
C
200
Legend
1.
Overall panel dimension
2.
Ceiling opening
3.
Centre of panel
4.
Power supply connection
5.
Drain pipe connection (VP25)
6.
Refrigerant pipe connection (gas 3/8)
7.
Refrigerant pipe connection (liquid 1/4)
8.
9.
10.
11.
12.
13.
14.
15.
79
Z view
A
1220
1420
B
1160
1360
C
545
645
D
485
585
E
530
630
F
470
570
G
254
460
H
800
1000
I
1/4
3/8
J
1/2
5/8
Legend
1.
150 knockout hole (for air intake)
2.
Overall panel dimension
3.
Ceiling opening
4.
Centre of panel
5.
Air inlet
6.
Air outlet
7.
Pitch 200 x N
80
8.
9.
10.
11.
12.
13.
14.
N
4
5
A
616
766
1066
1416
B
550
700
1000
1350
C
350
500
800
1150
D
600
750
1050
1400
E
470
620
920
1270
F
3/8
1/2
5/8
5/8
G
1/4
3/8
3/8
3/8
Legend
1.
125 knockout hole (for air intake)
2.
10-4 tapping screw 160
3.
When attaching directly
4.
Hanging bolt pitch
5.
Hanging bolt 4-M10 (eld-supplied)
6.
Ceiling opening
7.
Drain pipe connection (inner 32 vinyl chloride pipe VP25 connection)
8.
Unit dimension
9.
Hanging bolt pitch
10. Air inlet
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
Panel CL
Ceiling opening
26 power supply, remote controller cable conduit
Refrigerant pipe connection (liquid G)
Air outlet
Refrigerant pipe connection (gas F)
Inspection hole A
For air lter maintenance
Air lter
Inspection hole B
81
MMD-AP0481H
Z view
Z view
Z view
Models AP0181H-AP0271H
Model MMDAP0181H
AP0241H, AP0271H, AP0361H, AP0481H
Model AP0361H
A
1/4
3/8
B
1/2
5/8
MMD-AP0271H, AP0961H
*1
Legend
1.
Power supply/communication piping (26) (under control box)
2.
Hanging bolt slot (4-2 x 72)
3.
Hanging bolt mounting pitch
4.
Control box
5.
Refrigerant pipe connection (gas B)
6.
Refrigerant pipe connection (liquid A)
7.
Air inlet
8.
Screw hole for duct mounting (6-M6)
9.
Drain pipe connection (VP25)
10. Screw hole for duct mounting (4-M6)
All dimensions are given in mm.
82
11.
12.
13.
14.
15.
16.
17.
18.
19.
Air outlet
Refrigerant pipe connection (gas 5/8)
Refrigerant pipe connection (liquid 3/8)
Screw hole for duct mounting (8-M6)
Inspection area
Service space
Refrigerant pipe connection (gas 7/8)
Refrigerant pipe connection (liquid 1/2)
Screw hole for duct mounting (10-M6)
210
21
803
21
103
511
645
19
4-4
67
20 21
168
57
21
845
359
372
422
502
168
40
67
120
80
31
805
80
59
910
33
163
4
5
Bottom view excluding lter
21
803
21
103
511
645
19
359
372
422
502
40
168
67
80
146
31
120
9
2
4-4
67
20 21
168
210
57
21
845
805
80
59
910
33
163
4
5
Legend
1.
Inside dimension
2.
Air lter
3.
Refrigerant pipe connection
4.
Drain pipe connection
5.
Hanging plate
6.
Fresh air inlet (knockout hole)
7.
Drain pipe
All dimensions are given in mm.
83
Model MMCA
AP0151H, AP0181H 910
AP0241H to AP0271H 1180
AP0361H, AP0481H 1595
B
855
1125
1540
C
1/2
5/8
5/8
Legend
1.
Hanging position
2.
Remote controller cable conduit (knockout hole)
3.
Power supply cable inlet (knockout hole)
4.
Upper cable conduit (knockout hole)
5.
Drain pipe connection
6.
Refrigerant pipe connection (gas C)
7.
Refrigerant pipe connection (liquid D)
8.
Left side drain
9.
Cable conduit (knockout hole)
84
10.
11.
12.
13.
14.
15.
16.
17.
18.
D
1/4
3/8
3/8
30 min.
Legend
1.
(Installation board)
2.
Top of installation board
3.
Wood screw slot 15-6 x 30
4.
Anchor bolt slot 10-10 x 20
5.
Air outlet
Air ow direction adjustable (up/down/left/right)
6.
Air inlet
7.
Gas pipe
8.
Liquid pipe
9.
10.
11.
12.
13.
14.
15.
16.
17.
Drain pipe
Supplied with pipe outlet left
Including installation board
Including installation board (accessory)
Earth screw (M4) (inside control box)
Refrigerant pipe connection (gas 3/8)
Refrigerant pipe connection (liquid 1/4)
Drain pipe connection
Pipe outlet left/right side (knockout hole)
85
Legend
1.
(Installation board)
2.
Top of installation board
3.
Wood screw slot 15-6 x 30
4.
Anchor bolt slot 10-10 x 20
5.
Air outlet
Air ow direction adjustable (up/down/left/right)
6.
Air inlet
7.
Gas pipe
8.
Liquid pipe
All dimensions are given in mm.
86
9.
10.
11.
12.
13.
14.
15.
16.
17.
Drain pipe
Supplied with pipe outlet left
Including installation board
Including installation board (accessory)
Earth screw (M4) (inside control box)
Refrigerant pipe connection (gas 1/2)
Refrigerant pipe connection (liquid 1/4)
Drain pipe connection
Pipe outlet left/right side (knockout hole)
Legend
1.
(Installation board)
2.
Top of installation board
3.
Wood screw slot 21-6 x 30
4.
Anchor bolt slot 16-10 x 20
5.
Air outlet
Air ow direction adjustable (up/down/left/right)
6.
Air inlet
7.
Gas pipe
8.
Liquid pipe
9.
10.
11.
12.
13.
14.
15.
16.
17.
Drain pipe
Supplied with pipe outlet left
Including installation board
Including installation board (accessory)
Earth screw (M4) (inside control box)
Refrigerant pipe connection (gas 5/8)
Refrigerant pipe connection (liquid 3/8)
Drain pipe connection
Pipe outlet left/right side (knockout hole)
87
max. 100 mm
max. 170 mm
Legend
1.
Air inlet
2.
Air outlet
3.
Knockout hole
4.
Hook for insulation plate
5.
Refrigerant pipe connection (gas 3/8)
6.
Drain pipe connection
7.
Refrigerant pipe connection (liquid 1/4)
All dimensions are given in mm.
88
max. 170 mm
(left side)
A
3/8
1/2
5/8
B
1/4
1/4
3/8
Legend
1.
Hole for oor xing (2-10)
2.
Lower refrigerant pipe connection (50 x 100 knockout hole)
3.
Switch section (switch sold separately)
4.
Air outlet
5.
Air inlet
6.
Refrigerant pipe connection (50 x 100 knockout hole) (both sides)
7.
Power supply cord (26 knockout) (both sides)
8.
9.
10.
11.
12.
13.
14.
15.
16.
Earth screw M6
Hole for wall xing (10-20 knockout x 2)
Hole for wall xing (2-10 x 24 slot)
Refrigerant pipe connection (130 knockout hole)
Drain pipe connection (20)
Refrigerant pipe connection (gas A)
Refrigerant pipe connection (liquid B)
Wall
Front
89
No.
0
!
@
#
$
Name
Pipe connection (liquid side E)
Pipe connection (gas side F
Drain pipe connection (20A)
Control box (earth terminal provided inside)
Air lter
A
610
910
910
B
580
880
880
Legend
1.
Hole for oor xing
2.
Service space
3.
Air outlet
4.
Ceiling board
90
5.
6.
7.
8.
9.
C
550
850
850
D
4
7
7
E
1/4
1/4
3/8
F
3/8
1/2
5/8
G
5
8
8
Front
Front
Model
MMF-AP0151H, AP0181H
MMF-AP0241H, AP0271H
A
1/2
5/8
B
1/4
3/8
Legend
1.
Wall
2.
With 50 mm wall clearance
3.
Lower refrigerant pipe connection (50 x 120 knockout hole)
4.
Installation plate
5.
Air outlet
6.
Air inlet
7.
Refrigerant pipe connection (rear) (130 knockout hole)
8.
Drain hose
9.
Refrigerant pipe connection (bottom) (50 x 120 knockout hole)
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
Earth screw M4
Refrigerant pipe connection (both sides) (80 knockout hole)
Control panel
Panel cover
2-lower hole (for M8 screw or M8 anchor bolt)
130 knockout hole (for rear piping)
Refrigerant pipe connection (gas A)
Refrigerant pipe connection (liquid B)
4-lower hole (for M8 screw or M8 anchor bolt)
15 x 120 square hole (for bottom piping)
Floor
91
Front
Front
Legend
1.
Wall
2.
With 50 mm wall clearance
3.
Lower refrigerant pipe connection (50 x 120 knockout hole)
4.
Installation plate
5.
Air outlet
6.
Air inlet
7.
Refrigerant pipe connection (rear) (130 knockout hole)
8.
Drain hose
9.
Refrigerant pipe connection (bottom) (50 x 120 knockout hole)
10. Earth screw M4
All dimensions are given in mm.
92
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
Remote controller
Wired remote controller
RBC-AMT31E
93
94
Weekly timer
RBC-EXW21E
95
LON Gateway
TCB-IFLN**
200
66
22
22
78
78
22
96
170
78
147
78
150
64
22
Touch-screen controller
BMS-TP5120ACE
97
Intelligent server
BMS-LSV2E
98
(2.4)
6 5.5
63.6
170
144.9
146.9
78
78
22
18
18
22
12.55
63.5
93.5
156
93.5
63.5
18
18
234
12.55
(2.4)
63.6
200
63.6
220
246
99
Outdoor module
MMY-MAP0501T8, MAP0601T8, MAP0801T8, MAP1001T8, MAP1201T8,
MMY-MAP0501HT8, MAP0601HT8, MAP0801HT8, MAP1001HT8, MAP1201HT8,
Notes:
1.
If there is an obstacle at the top of the outdoor unit, ensure that
the top of the outdoor unit clears the obstacle by 2000 mm.
2.
Ensure that the height of obstacles around the outdoor unit
does not exced 800 mm from the bottom of the outdoor unit.
3.
Draw out the eld-supplied pipe to the front of the outdoor unit
horizontally, and keep 500 mm or more between the outdoor
unit and pipe if placing the pipe transversely.
Model
A
B
C
MMY-MAP0501T8, MAP0501HT8
5/8
3/8
280
MMY-MAP0601T8, MAP0601HT8
3/4
3/8
280
MMY-MAP0801T8, MAP0801HT8
7/8
1/2
(205)
MMY-MAP1001T8, MAP1001HT8
7/8
1/2
(205)
MMY-MAP1201T8, MAP1201HT8
1-1/8
1/2
(205)
*1
Cutting position of L-shape pipe when pipe is connected at the gas side.
(Recommended pipe connection position)
Space required for service
Front
Note 3
Note 3
MMY-MAP0501T8
MMY-MAP0601T8
MMY-MAP0501HT8
MMY-MAP0601HT8
Front
Details of front pipe/cabling holes
Details of hole for bottom piping (plane view)
Legend
1.
Anchor bolt pitch
2.
(including feet)
3.
4-15 x 20 (slot)
4.
2-60 x 150 square hole (for forklift truck)
5.
Balance pipe connection 3/8
6.
Refrigerant pipe connection (liquid B)
100
7.
8.
9.
10.
11.
12.
Front
Unit combination
Slave unit
MMY-MAP0601T8, MAP0601HT8
MMY-MAP0801T8, MAP0801HT8
MMY-MAP0801T8, MAP0801HT8
MMY-MAP1001T8, MAP1001HT8
MMY-MAP1001T8, MAP1001HT8
MMY-MAP1201T8, MAP1201HT8
Note 4 Note 3
Front
Front
Front
Note 4
Note 3
Note 4
MMY-AP1401T8, AP1401HT8
MMY-AP1601T8, AP1601HT8
MMY-AP1801T8, AP1801HT8
MMY-AP2001T8, AP2001HT8
MMY-AP2211T8, AP2211HT8
MMY-AP2411T8, AP2411HT8
Front
Front
Front
Legend
1.
Anchor bolt pitch
2.
(including feet)
3.
8-15 x 20 (slot)
101
Notes:
1.
If there is an obstacle at the top of the outdoor unit, ensure that
the top of the outdoor unit clears the obstacle by 2000 mm.
2.
Ensure that the height of obstacles around the outdoor unit
does not exced 800 mm from the bottom of the outdoor unit.
3.
Draw out the eld-supplied pipe to the front of the outdoor unit
horizontally, and keep 500 mm or more between the outdoor
unit and pipe if placing the pipe transversely.
4.
Arrange each outdoor unitin order of its capacity
(Master unit slave unit slave unit)
Slave unit
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1201T8, HT8
MMY-MAP1201T8, HT8
Front Front
Front Front
Legend
1.
Anchor bolt pitch
2.
(including feet)
3.
16-15 x 20 (slot)
All dimensions are given in mm.
102
Front
Slave unit
MMY-MAP0601T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1201T8, HT8
Note 4
Note 3
Front Front
Front
Front
Note 4
Note 3
Note 4
Note 4
MMY-AP2201T8, HT8
MMY-AP2401T8, HT8
MMY-AP2601T8, HT8
MMY-AP2801T8, HT8
MMY-AP3001T8, HT8
MMY-AP3221T8, HT8
MMY-AP3411T8, HT8
MMY-AP3611T8, HT8
Rear
Unit combination
Unit combination
Slave unit
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1201T8, HT8
MMY-MAP1201T8, HT8
MMY-MAP1201T8, HT8
Slave unit
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1201T8, HT8
MMY-MAP1201T8, HT8
Slave unit
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP0801T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1001T8, HT8
MMY-MAP1201T8, HT8
Note 4
MMY-AP3201T8, HT8
MMY-AP3401T8, HT8
MMY-AP3601T8, HT8
MMY-AP3801T8, HT8
MMY-AP4001T8, HT8
MMY-AP4201T8, HT8
MMY-AP4401T8, HT8
MMY-AP4601T8, HT8
MMY-AP4801T8, HT8
Note 3
Note 4
Note 3
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Note 4
Note 4
Notes:
1.
If there is an obstacle at the top of the
outdoor unit, ensure that the top of
the outdoor unit clears the obstacle by
2000 mm.
2.
Ensure that the height of obstacles
around the outdoor unit does not exced
800 mm from the bottom of the outdoor
unit.
3.
Draw out the eld-supplied pipe to the
front of the outdoor unit horizontally,
and keep 500 mm or more between the
outdoor unit and pipe if placing the pipe
transversely.
4.
Arrange each outdoor unitin order of its
capacity
(Master unit slave unit slave unit
slave unit)
Legend
1.
Anchor bolt pitch
2.
(including feet)
3.
16-15 x 20 (slot)
All dimensions are given in mm.
103
Gas side
Insulation
Liquid side
Insulation
Model
RBM-HY1043E
RBM-HY1083E
RBM-HY2043E
RBM-HY2083E
Gas side
380
90
83,6
7/8
5/8
Liquid side
360
60
5/8
3/8
6 x 4, 9 x 4, $ x 1, * x 1, ; x 1
1 x 4, 6 x 1, 9 x 1
6 x 8, 9 x 8, $ x 1, * x 1, ; x 1
1 x 8, 6 x 1, 9 x 1
6 x 2, 9 x 2, u x 1, O x 1
1x2
6 x 7, 9 x 7, u x 1, O x 1
1x7
Gas side
700
90
83,6
7/8
5/8
Liquid side
680
60
5/8
3/8
Gas side
385,5
95,5
89,3
1-1/4
5/8
Liquid side
360
60
5/8
3/8
Gas side
705,5
95,5
89,3
1-1/4
5/8
Liquid side
680
60
5/8
3/8
Liquid side
Balance pipe
104
a x 1, s x 1, A x 2, D x 2, F x 1
$ x 2, * x 1, b x 2, n x 1
Gas side
Insulation
Insulation
RBM-BY203E, BY303E
Liquid side
Gas side
Insulation
Insulation
Model
RBM-BY53E
RBM-BY103E
RBM-BY203E
RBM-BY303E
Gas side
250
80
5/8
1/2
Liquid side
200
70
1/2
3/8
Gas side
350
80
7/8
3/4
Liquid side
250
80
5/8
1/2
Gas side
350
80
1-1/4
1-1/8
Liquid side
250
80
5/8
5/8
Gas side
400
110
1-1/2
1-1/2
Liquid side
350
80
7/8
3/4
5 x 2, R x 2, 9 x 1, Q x 1
1 x 2, 5 x 1
7 x 1, 0 x 1, # x 2, * x 1, W x 2, ; x 1, . x 1
2 x 1, 5 x 2, 6 x 1, 9 x 1, R x 1
^ x 1, ) x 1, u x 1, e x 2, i x 1, o x 1, I x 1, O x 1
3 x 1, 6 x 1, 9 x 2
a x 3, s x 2, A x 2, D x 1, F x 1, G x 1, H x 1, J x 1
4 x 1, 7 x 1, 0 x 1, # x 2, $ x 1, * x 1, W x 1
105
Accessory socket
Outside diameter
Outside diameter
Outside diameter
Outside diameter
Outside diameter
Outside diameter
Outside diameter
106
Outside diameter