Profis Anchor 2.6.

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Fastening Point:
Date:

1
Heybridge - Cylinder S
18/01/2016

Specifier's comments:

1 Input data
Anchor type and size:

HIT-RE 500-SD + Rebar 25mm

Seismic/Filling set or any suitable annular gap filling solution


Effective embedment depth:

hef,act = 500 mm (hef,limit = - mm)

Material:

B500B

Approval No.:

ETA 07/0260

Issued I Valid:

26/06/2013 | 16/05/2018

Proof:

Design method Engineering judgement SOFA BOND - based on ETAG BOND testing

Stand-off installation:

eb = 0 mm (no stand-off); t = 12 mm

Baseplate:

lx x ly x t = 700 mm x 2286 mm x 12 mm; (Recommended plate thickness: not calculated

Profile:

Double flat bar; (L x W x T) = 700 mm x 550 mm x 30 mm

Base material:

cracked concrete, C20/25, fc = 25.00 N/mm2; h = 4000 mm, Temp. short/long: 0/0 C

Installation:

hammer drilled hole, Installation condition: Dry

Reinforcement:

No reinforcement or Reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
with longitudinal edge reinforcement d >= 12 + close mesh (stirrups, hangers) s <=

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.6.2

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

2
Heybridge - Cylinder S

Page:
Project:
Fastening Point:
Date:

18/01/2016

2 Load case/Resulting anchor forces

Load case: Design loads

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Tension force
Shear force
Shear force x
Anchor
1
0.000
71.655
71.655
2
0.000
69.159
69.159
3
0.000
60.841
60.841
4
0.000
58.345
58.345
5
0.000
56.265
56.265
6
0.000
73.735
73.735
max. concrete compressive strain:
- []
max. concrete compressive stress:
- [N/mm2]
resulting tension force in (x/y)=(0/0):
0.000 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]

2
Shear force y
0.000
0.000
0.000
0.000
0.000
0.000

3
4
5

3 Tension load (EOTA TR 029, Section 5.2.2)


Load [kN]
N/A

Capacity [kN]
N/A

Utilisation bN [%]
N/A

Status
N/A

Combined pullout-concrete cone failure**

N/A

N/A

N/A

N/A

Concrete cone failure**

N/A

N/A

N/A

N/A

Splitting failure**

N/A

N/A

N/A

N/A

Steel failure*

* most unfavourable anchor

**anchor group (anchors in tension)

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.6.2

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

3
Heybridge - Cylinder S

Page:
Project:
Fastening Point:
Date:

18/01/2016

4 Shear load (EOTA TR 029, Section 5.2.3)


Load [kN]
73.735

Steel failure (without lever arm)*


Steel failure (with lever arm)*

Capacity [kN]
90.000

Utilisation bV [%]
82

Status
OK
N/A

N/A

N/A

N/A

Pryout failure**

390.000

996.831

40

OK

Concrete edge failure in direction x+**

390.000

340.477

115

not recommended

* most unfavourable anchor

**anchor group (relevant anchors)

4.1 Steel failure (without lever arm)


VRk,s [kN]
135.000

gM,s
1.500

VRd,s [kN]
90.000

VSd [kN]
73.735

4.2 Pryout failure (concrete cone relevant)


Ac,N [mm2]
4950000

A0c,N [mm2]
2250000

ccr,N [mm]
750

scr,N [mm]
1500

k-factor
2.000

ec1,V [mm]
0

yec1,N
1.000

ec2,V [mm]
85

yec2,N
0.898

ys,N
0.940

N0Rk,c [kN]
402.492

gM,c,p
1.500

VRd,c1 [kN]
996.831

VSd [kN]
390.000

a
0.082

b
0.051

yec,V
0.930

yre,N
1.000

4.3 Concrete edge failure in direction x+


lf [mm]
500

dnom [mm]
25.0

k1
1.700

c1 [mm]
750

Ac,V [mm2]
3712500

A0c,V [mm2]
2531250

ys,V
0.860

yh,V
1.000

ya,V
1.000

ec,V [mm]
85

V0Rk,c [kN]
311.067

gM,c
1.500

VRd,c [kN]
340.477

VSd [kN]
390.000

yre,V
1.400

5 Displacements (highest loaded anchor)


Short term loading:
NSk

0.000 [kN]

dN

0.000 [mm]

VSk

54.618 [kN]

dV

1.639 [mm]

dNV

1.639 [mm]

Long term loading:


NSk

0.000 [kN]

dN

0.000 [mm]

VSk

54.618 [kN]

dV

2.731 [mm]

dNV

2.731 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.6.2

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Fastening Point:
Date:

4
Heybridge - Cylinder S
18/01/2016

6 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
Characteristic bond resistances depend on short- and long-term temperatures.
The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
The compliance with current standards (e.g. EC3) is the responsibility of the user
An SLS-check is not performed for SOFA and has to be provided by the user!

Fastening does not meet the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.6.2

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

5
Heybridge - Cylinder S

Page:
Project:
Fastening Point:
Date:

18/01/2016

7 Installation data
Baseplate, steel: Profile: Double flat bar; 700 x 550 x 30 mm
Hole diameter in the fixture: df = 25 mm
Plate thickness (input): 12 mm
Recommended plate thickness: not calculated
Cleaning: Premium cleaning of the drilled hole is required

Anchor type and size: HIT-RE 500-SD + Rebar 25mm


Installation torque: Hole diameter in the base material: 32 mm
Hole depth in the base material: 500 mm
Minimum thickness of the base material: 564 mm

7.1 Recommended accessories


Drilling
Suitable Rotary Hammer
Properly sized drill bit

Cleaning
Compressed air with required
accessories to blow from the bottom of
the hole
Proper diameter wire brush
y

Setting
Dispenser including cassette and mixer
For deep installations, a piston plug is
necessary
Seismic/Filling set
Torque wrench

50
350

93

350

250

1143

300

1000

85

1143

300

250

130

93

5
570

Coordinates Anchor [mm]


Anchor
1
2
3

x
-220
-220
-220

y
800
500
-500

c-x
1400
1400
1400

c+x
750
750
750

c-y
2450
2150
1150

c+y
850
1150
2150

Anchor
4
5
6

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

x
-220
-220
-220

y
-800
-1050
1050

c-x
1400
1400
1400

c+x
750
750
750

c-y
850
600
2700

c+y
2450
2700
600

Profis Anchor 2.6.2

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Fastening Point:
Date:

6
Heybridge - Cylinder S
18/01/2016

8 Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan