You are on page 1of 11

Howtoestimatethecostofinstallingan

ElectricalDistributionCenter(EDC)
CandidateNumber0112233
June2012

TableofContents

1)
2)
3)
4)

Introduction

TypesandMethodsofMeasurement
SpecificFactorsinTakeoffandPricing
OverviewofLabor,Material,Equipment,
IndirectCosts,andApproachtoMarkups
5) SpecialRiskConsiderations

6) RatiosandAnalysis

7) Misc.PertinentInformation

8) SampleSketch

9) SampleTakeOffandPricing

10) Glossary

3
35
56
68
8
8
8
9
10
11

3
1. Introduction
Thepurposeofthefollowingtechnicalpaperistoprovidethereadersomegeneralinformationonhow
toproperlyestimatetheinstallationofanElectricalDistributionCenterorEDCasitisoftenreferredin
theconstructionindustry.
MainCSIDivision

Division16000
SpecificSubDivision:CodeandName

Division16050BasicElectricalMaterialsandMethods

Division16100WiringMethods

Division16405ElectricalDistributionCenter

TheElectricalDistributionCenterorEDCwasintroducedtotheconstructionindustryasatime
saver,andtimeismoney.TheseEDChousesareconstructedasasingleunitcontaining
switchboards,panelboards,drytype,stepdowntransformers,groundingconductorsfromeach
transformertogroundchasethroughtheflooroftheEDC,plywoodmountingboardsforthelowvoltage
systems,generaldutyservicereceptacles,lightfixtures,andswitches.Nearlyallswitchgear
manufacturershaveEDCunitsavailable,rangingfromlarge4,000Aunitstosmaller400Aunits.Each
unitisULlistedandispreassembledandeachEDCisspecificallydesignedatanoffsitemanufacturing
facility,accordingtothespecificneedsandrequestsoftheowner.ThelargerEDChousesarealso
constructedwithdetachableliftconnectionsforeasierinstallations.Theotherkeyaspectofthedesign
oftheEDChouseisthateachoneismanufacturedanddeliveredasweatherproofunits.Itisimportant
tomaintaintheseunitsintheirweatherproofconditionuntilthebuildingisfullyenclosed.Thisallows
theswitchgeartobeheatedupearlyandusedasthemaintemporarypowersource.
Intodayscommercialconstructionmarket,timeistrulyoftheessence.Ownersareexpecting
theirprojectscompletedfaster,andatthesametimeexpectingtheirprojectstobebuiltforlessmoney.
Historically,thetypicallargeboxretailstoreswereconstructedwiththescheduleinmindandthecost
forconstructionwaslessimportant.Thatisnottosaythatmoneywasnoobject,notatall,butthe
ownerwantedtosellhismerchandiseasquicklyaspossible.Therefore,manyovertimehourshadtobe
figuredinordermeetcriticalgrandopeningdates,whichdrivesupthecostofaproject.Today,
however,thesesamelargeboxretailownersaregettingboth,quickconstructionschedulesaswellas
lessexpensiveprojects.Inthisarticle,wewilldiscussandcomparehowtheinstallationofEDCunitsis
oneofthewaysthatownershavebeenabletoachievethisgoal.
2. TypesandMethodsofMeasurements

TherearemanyfactorsthatcomprisethecompleteinstallationofanyEDCsuchasthe
undergroundroughinofconduitstootherEDCunitsorpanelboards,aswellastheoverhead
installationofrooftopunits.However,thispaperwillonlyfocusontheactualinstallationofanEDC
unit.Anypieceofswitchgearcannotactuallybeconsideredinstalleduntilithasbeenfedfromits
powersource.

Forourpurposesinthisarticle,wewillfocusontheinstallationofa3,000Aunitthatwillbe
installedinsidealargeboxretailstore.Hereareafewthingsthatanestimatorwillneedtoknowin
ordertoproperlyaccountforthematerialandlabortoinstallthisunit:

Itisimperativetoobtainthemanufacturersshopdrawings,riggingdiagrams,andequipment
specificationsoftheunit.
Itisalsoimportanttoknowtheweightoftheunit(wewilldiscussreasonslateron).
Ifatallpossible,theestimatorshouldtouranexistingstorewhichhasanEDCinplaceorbetter
yet,requestpermissiontoviewtheinstallationprocessduringanongoingconstructionprocess.

AftertheestimatorhasreviewedthespecificationsregardingtheEDChouseanditsphysical
layout,itisnowtimetoreviewtheEDChousethatisdrawnwithintheelectricalsheetsoftheproject.
WhenweturntotheonelinedrawingschematicofthisEDChouse,wewillnoticeseveralthingsof
importance(refertosheet9forschematicdrawing).

Oneofthefirstthingstheestimatorwillnoticeisthebolderdashedlinethatdesignatesallthe
panelboardsandotherequipmentlocatedwithintheEDCHouse(EDC1perthesketch).Theseitems
haveallbeenpreinstalledfromthefactory.Theseconditemtonoticeisthesmallerdashedlines
runningfromtheMSBtootherpanelboardsorequipmentwithintheunit.Theselinesrepresentthe
conduitandwiringthathasbeeninstalledbytheEDCmanufacturerofthespecificunitatthefactory.
However,itisimportanttoknowthatpertheelectricalspecifications,theinstalleroftheEDCunitis
responsibletocheckeveryterminationthatwasmadeatthefactoryandretorque,ifrequired,perthe
manufacturersinstructions.

ThenextphaseoftheestimateweconsideristheroughinportionoftheEDChouse.Thereare
typicallymanyundergroundfeedersleavingalargeEDCunit,suchasweareestimatingtoday.Any
looseswitchboard,panelboard,orothersmallerEDCunit,whichisnotinstalledwithinthemainEDC
unit,willeitherbefedunderground,suchasthesecondaryserviceentrance,oroverheadtopowerthe
AHU.Theonelinediagramshowsanexampleofthesetwofeeders.

FortheMainSwitchboardwithintheEDC1unit,weareinstallinga3000amp,480/277V,3
phase,4wiresystem.Thereforewearetoinclude(8)setsof4PVCschedule40conduitswitheach
conduitcontaining(4)#750kcmilaluminumwires.Theestimatorwillnoticethatonthisoneline
diagram,anoptiontoruncopperoraluminumisoffered.Tobemostcompetitive,aluminumwiring
shouldbechosen,duetothefactthataluminumwiringislessexpensivetopurchasethancopper
wiring.Typically,thissecondaryservicewillbeoneofthelargestsingleassembliesinyourestimate;so
muchconsiderationshouldbegiveninordertoestimateitaccuratelyandcompetitively.

Forthispaperhowever,wewillonlyfocusonthesettinginplaceoftheEDCunitandthehours
andmaterialsassociatedwithit.

Oncetheestimatorcompletestheundergroundroughinportionoftheestimate,thatisany
feederenteringorleavingundergroundfromtheEDCunit,includingthegroundingtofootersandwater
pipe,aswellasanystuboutsforthetelephoneservice,itistimetoreviewtheinstallationofthe3,000A
EDCunit.

Itmustbeunderstoodthatcertainscopesofworkmustbecompletedinsequencetoallowfora
smoothproject.Allpartieshavetheirroletoplay.Thebuildingpadhastobeprepared,thenthe
conduitsaretoberoughedinplace,afterthistheconcretecanbepouredaroundtheconduits.Once
theblockwallshavebeeninstalled,wearereadytoplacetheEDCunit.

OnthedayofthearrivaloftheEDCunit,severalhourswillberequiredtoensurethatthereisa
smoothtransitionandplacementoftheEDCunitontothepadsafelyfromthedeliverytruck.A10ton
craneisrecommendedtounloadanEDCunitofthissize.Itisrecommendedthattheestimatorsubout
thisportionoftheproject.Acranecompanyistypicallymoreexperiencedinsettinglargeequipment,
andthereforeabletoperformthetaskofunloadingtheunitwithmoreefficiencythanthatofthe
ElectricalContractor.Theestimatorshouldincludeinhisestimateacompanythatisfamiliarwith
unloadinglargepiecesofequipmentandislicensedandinsured.Acrewof34experienced
techniciansisrequiredtoassistthecranecompanywiththesettingoftheunitinitscorrectlocation.
Thisprocesswillrangeintimefrom14hoursdependingonthesizeoftheEDCunit.Itisrecommended
fora3,000Aunit,4hoursfor4menbeincluded.

DuringtheshippingprocessoftheEDCunitfromthefactorytothejobsite,itisverylikelythat
someofthefactoryterminationshaveworkedloose,andthereforetheverificationprocessofeach
terminationfallsontheresponsibilityoftheelectricalcontractor.Documentationmustbedoneinthe
fieldverifyingthisworkwasinspectedandcompleted.
3. SpecificFactorsinTakeoffandPricing

ConsiderationfortheinstallationoftheEDChouseneedstooccurmanyweekspriortothe
completionoftheundergroundroughin.Itistypicallytheresponsibilityoftheelectricalcontractorto
ensureproperdeliveryoftheunit.TheestimatorwillneedtoincludethecostforacranetosettheEDC
houseinplace.Itisrecommendedthattheestimatorcallpriortobiddayforpricingfromatleasttwo
differentsources,andshouldonlydealwiththosefirmswhoarefamiliarwithsettinglargerEDChouses.
Theestimatorshouldensurethatthecranecompanyisincludingacranelargeenoughtopickupthe
EDChousefromthedeliverytruckandsetitdirectlyonthepad.Theestimatorshouldalsoverifythe
pricingincludesspreaderbarstoeliminatethepossibilityoftheslings,whichareusedtohoisttheunit,
frompinchingthesidesanddamagingtheunit.

Fluctuationofmaterialcostsisalwayssomethinganestimatorshouldconsider.Steel,copper
andevenaluminumproductstendtofluctuateonaweeklybasis.Itisrecommendedthattheestimator
sendouthisbillofmaterialfortheseproductstoanelectricalsupplyhouseforaccurateanduptodate
pricing.

Historically,eachEDCisfurnishedbytheowner.Eventhoughtheunitisprovidedbyothers,
thisissomethingthattheestimatorshouldconsider.Whentheestimatorhascompletedthetakeoff
andhasarrivedatjobcost,thepercentageofmarkupsshouldbeadjustedslightlyhigherduetothe
factthattheelectricalcontractordoesnotgettoincludemarkuponthequotedmaterials.
4. OverviewofLabor,Material,Equipment,IndirectCostsandApproachtoMarkUps

ThetotalpricetoinstallanElectricalDistributionCentercanbrokendownintothefollowing
categories:labor,material,equipment,indirectcosts,andmarkups(overheadandprofit).Anelectrical
estimatorshouldtaketimetoreviewallplandocumentsandspecificationstoaccuratelyprovidea
proposaltotheGC.Wewilltakeadetailedlookateachofthesecategories.

Labor

Laborisobviouslyacriticalpartinanysuccessfulproject.Asmartcrewleader,alongwith
competentskilledelectriciansisthekeytosuccess.Thecrewiscomposedofmanymen,allwithvarying
degreesofskill,experience,andhourlycompensation.Theestimatorisrequiredtoknow(oratleast
closelyanticipate)thecrewrateforeachprojectinordertoprovidetheelectricalcontractorwiththe
bestchanceofsuccess.Belowisanexampleofhowacrewratewasderivedfortheinstallationofa
3,000AEDCunit.

LaborType
Crew Hours Rate$ Subtotal
Brdn BrdnTotal
Total FullRate
FOREMAN
1
17.15 $30.00 $514.50
30% $154.35
$668.85$39.00

JOURNEYMAN
2
34.30 $25.00 $857.50
30% $257.25
$1,114.75$32.50

APPRENTICE 2
34.30 $15.00 $514.50
30% $154.35
$668.85$19.50

Itisimportantfortheestimatortobefamiliarwiththeburdenratethatisaddedontopofthe
hourlyrateperelectricianandtomakesurethiscostisincludedinhis/herestimate.

Eachprojectcould,andmostlikelywill,requiredifferentcrewrates.Thelargerprojectscould
haveonetotwoadditionalforemen.AdiscussiononbiddaywiththeGeneralSuperintendantscanbe
veryadvantageousfortheestimator.Forexample,theGeneralSuperintendantcaninformthe
estimatorofcertainemployeesthatwillbeavailableforthisprojectshoulditbeawardedinthefuture.
Iftheestimateisbuiltaroundthisfactor,itwillincreasethechanceofsuccess.

TheestimatorisalsorequiredtoknowwhethertheprojectwillrequirePrevailingWageRates,
suchasforagovernmentfacility.Ifso,theestimatorshouldfamiliarizehimselfwiththeDavisBacon
Act.Thisdocumentwillinstructhimonthehourlyraterequiredtopay,aswellasthefringebenefits.

Material

Accuratelyestimatingthecostofmaterialsformostprojectscanbedifficult.Withthedailyups
anddownsinthecommoditymarkets,agoodestimatecangosouthovernight.Thejobofanestimator
istogetthebestpriceofhis/hermaterialonbiddayandconsiderthefollowing;whenwillthisproject
beawarded?Thisanswercandeterminehowaggressivetheestimatorcanbewiththematerials.Itis
recommendedanotebeaddedtothescopeletterindicatingtheelectricalproposalisgoodfor30days,
whichisstandard.

Equipment

Foreveryprojectcarefulconsiderationshouldbegiventowhattypeofliftswillberequiredand
howmanyliftswillbeneededtosuccessfullymeetcriticaldeadlines.Havingtherightequipmentonsite
canleadtoasuccessfulproject.Forexample,utilizingcranestosettheEDCinsteadoftwoskytracks
willsavemoneyandtime,butgreatestofallisitissafermethodofinstallation.

IndirectCosts

Indirectcostsaresimplythosecostsnotdirectlyassociatedwiththeconstructionoftheproject,
atleastnot100%ofthetime.Forexample,someofthemajorindirectcostsofaprojectwillbethe
ProjectManagerandtheGeneralSuperintendant.Neitheroneofthesepositionsislocatedonthe
constructionsitefulltime,yetbotharecriticalinthesuccessoftheproject.Toproperlyaccountforthis
cost,apercentageofhoursshouldbeincludedintheestimate.Projectsthatwillrequiredailywork
fromtheProjectManagerorweeklyjobsitevisitsbytheGeneralSuperintendantwillrequireahigher
percentage.Atypicallargeboxretailstoreshouldinclude5%oftheoverallestimatedhoursforeachof
thesepositions.Atypicalgovernmentfacilityprojectshouldinclude15%oftheoverallestimatedhours.

Largerprojects,thoseover10,000manhoursshouldalsoconsidertimeforamaterialpersonon
site.Manyhoursarewastedbyanelectricianonadailybasisroundingupthematerialhe/sheneedsto
install.Amaterialpersoncanhelpalleviatethesewastedhours.

MarkUps

Aprojectcanbedeemedsuccessfulindifferentwaysandfordifferentreasons,butultimately,
thesuccessofaprojectisdeterminedbytheprofitsattheendofanyproject.Everyestimateshould
includemarkups,alsoknownasoverheadandprofits.

Thepercentageofprofitsthatanestimatorshouldincludeisbasedonthedifficultyofthe
project.Someotherfactorsthatshouldbeconsideredarethedurationandlocationoftheproject.A
10%markupforoverheadand5%markupforprofitsisgoodstartingpoint.Difficultprojectsshould
haveincreasedlevels.

8
5. SpecialRiskConsiderations

Thereareseveralitemstoconsidershouldyoubeawardedthisproject.Firstisthedeliveryof
theEDCunittothejobsite.Inordertobeasefficientaspossible,andtomaintaintheprofitsincludedin
theestimate,thepadfortheEDCshouldbepouredandreadytoreceivetheEDCunitwhenitarrives.If
thepadisnotready,andtheEDCunitarrives,theonlychoiceistounloadtheEDCunitandsetitoffto
thesidewiththecrane.Thenwhenthepadisready,thecraneisneededforasecondtimetoputthe
EDCunitinplace.Thissecondtripforthecrane,isnotincludedintheoriginalestimateandnorshould
itbe,thereforeitcanonlybepaidoutoftheanticipatedprofitsfigured.Coordinationwithallother
subsisimperativetoensureaprofitableproject.Asecondconcernisthattheroofofthebuildingnot
beinstalledpriortotheEDCunitarrival.Ifso,usingacraneisnolongeranoption,andthiswillbring
aboutadditionallaborhourstoinstalltheEDCunit.ItismandatoryfortheECtokeepupwiththe
projecttoensureitmeetsthesecriticaldatesoftheproject.
6. RatiosandAnalysis

Anestimateisjustthat,anestimate.Theonlymethodthatisproventodeterminean
estimatesaccuracyisthehistoricaldatafromsimilarpreviousprojects.However,itisimperativeto
knowthatevenprojectsthatareidenticalasfaraslayout,otherfactorsshouldbeconsidered.The
locationoftheprojectshouldbeconsideredforthedeliveryofmaterialstothejobsiteinatimely
manner.TheGeneralContractorisanothervariabletoconsider.AnexperiencedGeneralContractor,
whomaintainstheschedulecanincreasethebottomlineforasubcontractor.
7. Misc.PertinentInformation

Onethinganestimatorneedsinordertoperformanaccurateestimateistime.Todaymany
contractorsaretryingtobidtoomanyprojectsandnotallowingtheestimatorsufficienttimefor
thoroughbidprocess.Timeisrequiredinordertoreviewallprojectdocumentsincludingthe
architecturaldrawings.


9
8. SampleSketch

9. SampleTakeOffandPricing
Description

#12WIREPOWERTERM
#10WIREPOWERTERM
#8WIREPOWERTERM
#6WIREPOWERTERM
#4WIREPOWERTERM
#3WIREPOWERTERM
#2WIREPOWERTERM

Qty
240
130
30
14
2
2
6

U
E
E
E
E
E
E
E

Cost
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Labor
0.09
0.11
0.14
0.17
0.21
0.23
0.25

Unit
E
E
E
E
E
E
E

TotalMat
0.00
0.00
0.00
0.00
0.00
0.00
0.00

TotalHrs
21.60
14.30
4.20
2.38
0.42
0.46
1.50

10

#1WIREPOWERTERM
#1/0WIREPOWERTERM
#3/0WIREPOWERTERM
#4/0WIREPOWERTERM
#250WIREPOWERTERM
#350WIREPOWERTERM
UNLOADEDCANDSETPLACE
CLEAN/WIPEDOWNEDC
REMOVEWPROOF

REMOVEDOORPACKAGING

LaborType
Crew Hours
FOREMAN
1.00 17.15
JOURNEYMAN
2.00 34.30
APPRENTICE 2.00 34.30

5
85.76

IndirectLabor
Lbr%
PROJECTMANAGER
5.000
GENERALFOREMAN 5.000

Equipment

CRANE10TON(perHour)

FinalPricing

DatabaseMaterial

MaterialTax9%

MaterialTotal

DirectLabor

IndirectLabor

LaborTotal

Equipment

TotalCost

Overhead10%

Subtotal

Profit5%

SellingPrice

4
8
16
6
4
12
1
1
1
1

E
E
E
E
E
E
E
E
E
E

0.00
0.00
0.00
0.00
0.00
0.00
0.00
5.00
0.00
0.00

0.29
0.32
0.39
0.43
0.47
0.54
16.00
1.00
2.00
1.00

E
E
E
E
E
E
E
E
E
E

Rate Sub
Brdn% BrdnTot
$30.00 514.50 30.000 154.35
$25.00 857.50 30.000 257.25
$15.00 514.50 30.000 154.35
$22.00 1,886.50
565.95
Hrs
4.29
4.29
8.58

Qty
1.00

0.00
0.00
0.00
0.00
0.00
0.00
0.00
5.00
0.00
0.00
5.00

Total
$668.85
$1,114.75
$668.85
$2,452.45

1.16
2.56
6.24
2.58
1.88
6.48
16.00
1.00
2.00
1.00
85.76
FullRate
39.00
32.50
19.50
28.60

Rate
Total
$25.00
107.25 (Notethatsincethesepositions
$35.00
150.15 aresalaried,thereisnoburden)
$30.00
$257.40

Hrs
P/Hr
Total
4.00 $200.00
$800.00

Value($)
5.00
0.45
5.45
2,452.45
257.40
2,709.85
800.00
3,515.30
351.53
3,866.83
193.34
4,060.17

11
10. Glossary
EDCorElectricalDistributionCenter:apreassembledunitofacertainampacitythatmayinclude480V
panels,stepdowntransformers,208Vpanels,communicationboards,lighting,andreceptacles.All
itemsareprewiredfromtheEDCmanufacturersfacilityandshippedcompletetoanylocation.
LooseSwitchgear:anypanel,480Vorotherwise,thatisnotincludedwithintheEDCunit.
AHU:AirHandlingunit
Feeders:theconduitandwiringthatisinstalledfromonepanelorpowersourcetoanother.Feeders
canbeinstalledundergroundoroverhead.
GRC90:GRCisanacronym,itstandsforGalvanizedRigidConduit.90isatermusedintheroutingofa
feeder.Theconduitfeederturns90degrees.AGRC90isafittingthatisusedonlargerconduitsinlieu
ofbendingtheconduitto90degrees.
GeneralSuperintendant:apositionwithinanorganizationwhooverseesnumerousprojectsatatime.
AjobsiteSuperintendantwillworkdirectlyforaGeneralSuperintendant.
FringeBenefits:isthecompensationtoemployeesinadditiontotheirhourlyrateofpay.Thefringe
benefitsofaprojectvaryfromonetotheotherandfromcitytocityandstatetostate.
Overhead:simplystated,overheadisthecostofdoingbusinessonadailybasis.

You might also like