Calculation sheet
Two 400mm pipes are used to handle the condenser water of Block 07(supply & return). We use a base platform at LL3 to cater the total weight of the pipes.
1. Calculations for base platform
Data
- Selected beam for base platform
150x150
B
D
t
Ix-x
mm
mm
mm
cm4
S 275
- Technical data for anchor bolts are taken from fischer catalog
- Condensor water riser height (m)
- Linear density of pipe (400mm),sch 40 with water
16 mm
275 Mpa
46.667 m
237.3 kg/m
Notes/Assumptions:
- Self weight of I - beam is negligible
- Load on the platform is considered as an UDL
- Concreate wall is considered as cracked concreate
- Beam is considered as simply supported beam
Block 07
Calculation sheet
w
A
RA
l
x
RB
5
2.5
108.64
2
217.27
326
130.40
26.08
9
32.60
m
kN
kN
kN/m
kN/m
Nos
kN
20.38 kNm
188.31 Mpa
OK
Block 07
Calculation sheet
250
UDL (w)
543.33 kN/m
2
Maximum moment (wl /8)
0.04 kNm
Bending stress
3.32 Mpa
Therefore plate does not fail due to bending
OK
wl
Figure 3 : Bending moment on base plate
Block 07
Fischer
model
FAZ ll
16
Permissible
shear load V
perm
Calculation sheet
Nos of
bolts
per
beam
RA (RA/Vpe Required
(kN)
min bolts
rm)
31.4 32.60
OK
10
RA
C2
C1
Figure 4 : Shear force on side plate of the base platform at LL3