You are on page 1of 105

National Frame Builders Association Post-Frame Building Design Manual

Chapter 1: INTRODUCTION TO POST-FRAME BUILDINGS

1.1 General or masonry foundation. Figure 1.1 illustrates the


structural components of a post-frame building.
1.1.1 Main Characteristics. Post-frame build-
ings are structurally efficient buildings composed 1.1.2 Use. Post-frame construction is well-
of main members such as posts and trusses and suited for many commercial, industrial, agricul-
secondary components such as purlins, girts, tural and residential applications. Post-frame
bracing and sheathing Snow and wind loads are offers unique advantages in terms of design and
transferred from the sheathing to the secondary construction flexibility and structural efficiency.
members. Loads are transferred to the ground For these reasons, post-frame construction has
through the posts that typically are embedded in experienced rapid growth, particularly in non-
the ground or surface-mounted to a concrete agricultural applications.

Roof cladding
Ridge cap

Purlin

Truss
Wall cladding

Doorway
Pressure
preservative
treated post
Pressure preservative treated splash board

Concrete footing
Wall
girt

Figure 1.1. Simplified diagram of a post-frame building. Some components such as per-
manent roof truss bracing and interior finishes are not shown.

1-1
National Frame Builders Association Post-Frame Building Design Manual

1.2 Evolution tion on post and foundation design (Knight,


1990). New roof panel constructions using high-
strength steel and customized screw fasteners
1.2.1 The concept of pole-type structures is not
have dramatically improved diaphragm stiffness
new. Archeological evidence exists in abun-
and strength.
dance that pole buildings have been used for
human housing for thousands of years. In Amer-
ica, pole buildings began appearing on farms in 1.3 Advantages
the 19th century (Norum, 1967).
1.3.1 Reliability. Outstanding structural per-
1.2.2 Pole-type construction resurfaced in 1930 formance of post-frame buildings under adverse
when Mr. H. Howard Doane introduced the conditions such as hurricanes is well-
"modern pole barn" as an economical alternative documented. Professor Gurfinkel, in his wood
to conventional barns (Knight, 1989). Mr. Doane engineering textbook, cites superior perform-
was the founder of Doane's Agricultural Service, ance of post-frame buildings over conventional
a firm specializing in managing farms for absen- construction during hurricane Camille in 1969
tee owners. These early pole barns were con- (Gurfinkel, 1981). Harmon et. al (1992) reported
structed with red cedar poles that were naturally that post-frame buildings constructed according
resistant to decay, trusses spaced 2 ft on- to engineered plans generally withstood hurri-
center, 1-inch nominal purlins and galvanized cane Hugo (wind gusts measured at 109 mph).
steel sheathing. Since post-frame buildings are relatively light
weight, seismic forces do not control the design
In the 1940s, pole barn construction was refined unless significant additional dead loads are ap-
by using creosote preservative-treated sawn plied to the structure (Faherty and Williamson,
posts, wider truss and purlin spacings, and im- 1989; Taylor, 1996).
proved steel sheathing. Mr. Bernon G. Perkins,
an employee of Doane's, is credited for many of 1.3.2 Economy. Significant savings can be ob-
the refinements to Doane's original pole barn. In tained with post-frame construction in terms of
1949, Mr. Perkins applied for the first patent on materials, labor, construction time, equipment
the pole building concept through Doane's Agri- and building maintenance. For example, post-
cultural Service, and the patent was issued in frame buildings require less extensive founda-
1953. Rather than protecting their patent, they tions than other building types because the wall
publicized the concept and encouraged its use sections between the posts are non-load bear-
throughout the world. In 1995, the post-frame ing. Embedded post foundations commonly
building concept was recognized as an Historic used in post-frame require less concrete, heavy
Agricultural Engineering Landmark by the equipment, labor, and construction time than
American Society of Agricultural Engineers. conventional perimeter foundations. Additionally,
embedded post foundations are better-suited for
1.2.3 In the past two decades, post-frame con- wintertime construction.
struction has been further enhanced by the de-
velopments of metal-plate connected wood 1.3.3 Versatility. Post-frame construction facili-
trusses, nail- and glue-laminated posts, high- tates design flexibility. Posts can be embedded
strength steel sheathing, fasteners and dia- into the ground or surface-mounted to a con-
phragm design methods. Composites such as crete foundation. Steel sheathing can be re-
laminated posts and structural composite lumber placed with wood siding, brick veneer, and con-
offer advantages of superior strength and stiff- ventional roofing materials, to satisfy the ap-
ness, dimensional stability, and they can be ob- pearance and service requirements of the cus-
tained in a variety of sizes and pressure pre- tomer. One-hour fire-rated wall and roof/ceiling
servative treatments. Developments in metal- constructions have been developed for wood
plate connected wood truss technology allow framed assemblies. Exposed glued-laminated
clear spans of over 80 feet. Design procedures and solid-sawn timbers can be substituted for
were introduced in the early 1980s to more ac- trusses made from dimension lumber to achieve
curately account for the effect of diaphragm ac- desired architectural effects.

1-2
National Frame Builders Association Post-Frame Building Design Manual

1.4 Industry Profile ASAE: The Society for engineering in agricul-


tural, food, and biological systems (formerly
1.4.1 Post-frame construction has experienced American Society of Agricultural Engineers).
tremendous growth since World War II. This
growth was fueled by the abundant supplies of Anchor Bolts: Bolts used to anchor structural
steel and pressure preservative-treated wood, members to a foundation. Commonly used in
together with the need for low-cost structures. In post-frame construction to anchor posts to the
the 1950s and 1960s, the pole barn industry concrete foundation.
was characterized by large numbers of inde-
pendent builders (Knight, 1989). During this ASCE: American Society of Civil Engineers.
time, pole builders were expanding from their
traditional agricultural base into other construc- AWC: American Wood Council. The wood prod-
tion markets. This expansion into code-enforced ucts division of the American Forest & Paper
construction required rigorous documentation of Association (AF&PA).
engineering designs and more involvement in
the building code arena. AWPB: American Wood Preservers Bureau.

1.4.2 NFBA. Approximately 20 builders met in Bay: The area between adjacent primary frames
1969 to discuss challenges facing the post- in a building. In a post-frame building, a bay is
frame building industry. The group voted in favor the area between adjacent post-frames.
of forming the National Frame Builders Associa-
tion (NFBA). The NFBA became incorporated in Bearing Height: Vertical distance between a
1971 and the first national headquarters was pre-defined baseline (generally the grade line)
established in Chicago, Illinois. Today, the Na- and the bearing point of a component.
tional Frame Builders Association is headquar-
tered in Lawrence, Kansas and includes over Bearing Point: The point at which a component
300 contractors and suppliers, with regional is supported.
branches throughout the U.S. In addition, a Ca-
nadian Division of NFBA was created in 1984. Board: Wood member less than two (2) nominal
inches in thickness and one (1) or more nominal
1.4.3 The post-frame industry has become one inches in width.
of the fastest growing segments of the total con-
struction industry. Based on light-gauge steel Board-Foot (BF): A measure of lumber volume
sales, post-frame industry revenues are esti- based on nominal dimensions. To calculate the
mated to be from 2 to 2.5 billion dollars in 1990. number of board-feet in a piece of lumber, multi-
ply nominal width in inches by nominal thickness
in inches times length in feet and divide by 12.
1.5 Terminology
BOCA: Building Officials & Code Administrators
AF&PA: American Forest & Paper Association International, Inc. The organization responsible
(formerly National Forest Products Association). for maintaining and publishing the National
Building Code.
AITC: American Institute of Timber Construc-
tion. Bottom Chord: An inclined or horizontal mem-
ber that establishes the bottom of a truss.
ALSC: American Lumber Standard Committee.
Bottom Plank: See Splashboard.
ANSI: American National Standards Institute
Butt Joint: The interface at which the ends of
APA: The Engineered Wood Association (for- two members meet in a square cut joint.
merly the American Plywood Association)

1-3
National Frame Builders Association Post-Frame Building Design Manual

Camber: A predetermined curvature designed Fascia: Flat surface (or covering) located at the
into a structural member to offset the anticipated outer end of a roof overhang or cantilever end.
deflection when loads are applied.
Flashing: Sheet metal or plastic components
Check: Separation of the wood that usually ex- used at major breaks and/or openings in walls
tends across the annual growth rings (i.e., a split and roofs to insure weather-tightness in a struc-
perpendicular-to-growth rings). Commonly re- ture.
sults from stresses that build up in wood during
seasoning. Footing: Support base for a post or foundation
wall that distributes load over a greater soil area.
Cladding: The exterior and interior coverings
fastened to the wood framing. Frame Spacing: Horizontal distance between
post-frames (see post-frame and post-frame
Clear Height: Vertical distance between the building). In the absence of posts, the frame
finished floor and the lowest part of a truss, raf- spacing is generally equated to the distance be-
ter, or girder. tween adjacent trusses (or rafters). Frame spac-
ing may vary within a building.
Collars: Components that increase the bearing
area of portions of the post foundation, and thus Gable: Triangular portion of the endwall of a
increase lateral and vertical resistance. building directly under the sloping roof and
above the eave line.
Components and Cladding: Elements of the
building envelope that do not qualify as part of Gable Roof: Roof with one slope on each side.
the main wind-force resisting system. In post- Each slope is of equal pitch.
frame buildings, this generally includes individ-
ual purlins and girts, and cladding. Gambrel Roof: Roof with two slopes on each
side. The pitch of the lower slope is greater
Diaphragm: A structural assembly comprised of than that of the upper slope.
structural sheathing (e.g., plywood, metal clad-
ding) that is fastened to wood or metal framing Girder: A large, generally horizontal, beam.
in such a manner the entire assembly is capable Commonly used in post-frame buildings to sup-
of transferring in-plane shear forces. port trusses whose bearing points do not coin-
cide with a post.
Diaphragm Action: The transfer of load by a
diaphragm. Girt: A secondary framing member that is at-
tached (generally at a right angle) to posts. Girts
Diaphragm Design: Design of roof and ceiling laterally support posts and transfer load be-
diaphragm(s), wall diaphragms (shearwalls), tween wall cladding and posts.
primary and secondary framing members, com-
ponent connections, and foundation anchorages Glued-Laminated Timber: Any member com-
for the purpose of transferring lateral (e.g., wind) prising an assembly of laminations of lumber in
loads to the foundation structure. which the grain of all laminations is approxi-
mately parallel longitudinally, in which the lami-
Dimension Lumber: Wood members from two nations are bonded with adhesives.
(2) nominal inches to but not including five (5)
nominal inches in thickness, and 2 or more Grade Girt: See Splashboard.
nominal inches in width.
Grade Line (grade level): The line of intersec-
Eave: The part of a roof that projects over the tion between the building exterior and the top of
sidewalls. In the absence of an overhang, the the soil, gravel, and/or pavement in contact with
eave is the line along the sidewall formed by the the building exterior. For post-frame building
intersection of the wall and roof planes.

1-4
National Frame Builders Association Post-Frame Building Design Manual

design, the grade line is generally assumed to Seismic Load: Lateral load acting in the
be no lower than the lower edge of the splash- horizontal direction on a structure due to the
board. action of earthquakes.

Header: A structural framing member that sup- Snow Load: A load imposed on a structure
ports the ends of structural framing members due to accumulated snow.
that have been cut short by a floor, wall, ceiling,
or roof opening. Wind Loads: Loads caused by the wind
blowing from any direction.
Hip Roof: Roof which rises by inclined planes
from all four sides of a building. Lumber Grade: The classification of lumber in
regard to strength and utility in accordance with
IBC: International Building Code. the grading rules of an approved (ALSC accred-
ited) lumber grading agency.
ICBO: International Conference of Building Offi-
cials. The organization responsible for maintain- LVL: see Laminated Veneer Lumber.
ing and publishing the Uniform Building Code.
Main Wind-Force Resisting System: An as-
Knee Brace: Inclined structural framing member semblage of structural elements assigned to
connected on one end to a post/column and on provide support and stability for the overall
the other end to a truss/rafter. structure. Main wind-force resisting systems in
post-frame buildings include the individual post-
Laminated Assembly: A structural member frames, diaphragms and shearwall
comprised of dimension lumber fastened to-
gether with mechanical fasteners and/or adhe- Manufactured Component. A component that
sive. Horizontally- and vertically-laminated as- is assembled in a manufacturing facility. The
semblies are primarily designed to resist bend- wood trusses and laminated columns used in
ing loads applied perpendicular and parallel to post-frame buildings are generally manufactured
the wide face of the lumber, respectively. components.

Laminated Veneer Lumber (LVL) A structural MBMA: Metal Building Manufacturers Associa-
composite lumber assembly manufactured by tion.
gluing together wood veneer sheets. Each ve-
neer is orientated with its wood fibers parallel to NDS®: National Design Specification® for
the length of the member. Individual veneer Wood Construction. Published by AF&PA.
thickness does not exceed 0.25 inches.
Mechanically Laminated Assembly: A lami-
Loads: Forces or other actions that arise on nated assembly in which wood laminations have
structural systems from the weight of all perma- been joined together with nails, bolts and/or
nent construction, occupants and their posses- other mechanical fasteners.
sions, environmental effects, differential settle-
ment, and restrained dimensional changes. Metal Cladding: Metal exterior and interior cov-
erings, usually cold-formed aluminum or steel
Dead Loads: Gravity loads due to the sheet, fastened to the structural framing.
weight of permanent structural and non-
structural components of the building, such NFBA: National Frame Builders Association.
as wood framing, cladding, and fixed service
equipment. NFPA: National Fire Protection Association

Live Loads: Loads superimposed by the Nominal size: The named size of a member,
construction, use and occupancy of the usually different than actual size (as with lum-
building, not including wind, snow, seismic ber).
or dead loads.

1-5
National Frame Builders Association Post-Frame Building Design Manual

Orientated Strand Board (OSB): Structural Post-Frame Building: A building system whose
wood panels manufactured from reconstituted, primary framing system is principally comprised
mechanically oriented wood strands bonded of post-frames.
with resins under heat and pressure.
Post Height: The length of the non-embedded
Orientated Strand Lumber (OSL): Structural portion of a post.
composite lumber (SCL) manufactured from
mechanically oriented wood strands bonded Pressure Preservative Treated (PPT) Wood:
with resins under heat and pressure. Also Wood pressure-impregnated with an approved
known as laminated strand lumber (LSL) preservative chemical under approved treatment
and quality control procedures.
OSB: See Orientated Strand Board.
Primary Framing: The main structural framing
Parallel Strand Lumber (PSL): Structural com- members in a building. The primary framing
posite lumber (SCL) manufactured by cutting members in a post-frame building include the
1/8-1/10 inch thick wood veneers into narrow columns, trusses/rafters, and any girders that
wood strands, and then gluing and pressing the transfer load between trusses/rafters and col-
strands together. Individual strands are up to 8 umns.
feet in length. Prior to pressing, strands are ori-
ented so that they are parallel to the length of PSL: See Parallel Strand Lumber.
the member.
Purlin: A secondary framing member that is
Pennyweight: A measure of nail length, abbre- attached (generally at a right angle) to rafters/
viated by the letter d. trusses. Purlins laterally support rafters and
trusses and transfer load between exterior clad-
Plywood: A built-up panel of laminated wood ding and rafters/trusses.
veneers. The grain orientation of adjacent ve-
neers are typically 90 degrees to each other. Rafter: A sloping roof framing member.

Pole: A round, unsawn, naturally tapered post. Rake: The part of a roof that projects over the
endwalls. In the absence of an overhang, the
Post: A rectangular member generally uniform rake is the line along the endwall formed by the
in cross section along its length. Post may be intersection of the wall and roof planes.
sawn or laminated dimension lumber. Com-
monly used in post-frame construction to trans- Ridge: Highest point on the roof of a building
fer loads from main roof beams, trusses or raf- which describes a horizontal line running the
ters to the foundation. length of the building.

Post Embedment Depth: Vertical distance be- Ring Shank Nail: See threaded nail.
tween the bottom of a post and the lower edge
of the splashboard. Roof Overhang: Roof extension beyond the
endwall/sidewall of a building.
Post Foundation: The embedded portion of a
structural post and any footing and/or attached Roof Slope: The angle that a roof surface
collar. makes with the horizontal. Usually expressed in
units of vertical rise to 12 units of horizontal run.
Post Foundation Depth: Vertical distance be-
tween the bottom of a post foundation and the SBC: Standard Building Code (see SBCCI).
lower edge of the splashboard.
SBCCI: Southern Building Code Congress In-
Post-Frame: A structural building frame consist- ternational, Inc. The organization responsible for
ing of a wood roof truss or rafters connected to maintaining and publishing the Standard Build-
vertical timber columns or sidewall posts. ing Code.

1-6
National Frame Builders Association Post-Frame Building Design Manual

Secondary Framing: Structural framing mem- span" for rafters and joists in conventional
bers that are used to (1) transfer load between construction.
exterior cladding and primary framing members,
and/or (2) laterally brace primary framing mem- Out-To-Out Span: Horizontal distance be-
bers. The secondary framing members in a tween the outer faces of supports. Com-
post-frame building include the girts, purlins and monly used in specifying metal-plate-
any structural wood bracing. connected wood trusses.

Self-Drilling Screw: A screw fastener that com- Overall Span: Total horizontal length of an
bines the functions of drilling and tapping installed horizontal or inclined member.
(thread forming). Generally used when one or
more of the components to be fastened is metal SPIB: Southern Pine Inspection Bureau.
with a thickness greater than 0.03 inches
Skirtboard: See Splashboard.
Self-Piercing Screw: A self-tapping (thread
forming) screw fastener that does not require a Splashboard: A preservative treated member
pre-drilled hole. Differs from a self-drilling screw located at grade that functions as the bottom
in that no material is removed during screw in- girt. Also referred to as a skirtboard, splash
stallation. Used to connect light-gage metal, plank, bottom plank, and grade girt.
wood, gypsum wallboard and other "soft" mate-
rials. Splash Plank: See Splashboard.

SFPA: Southern Forest Products Association Stitch (or Seam) Fasteners: Fasteners used to
connect two adjacent pieces of metal cladding,
Shake: Separation of annual growth rings in and thereby adding shear continuity between
wood (splitting parallel-to-growth rings). Usually sheets.
considered to have occurred in the standing tree
or during felling. Structural Composite Lumber (SCL): Recon-
stituted wood products comprised of several
Shearwall: A vertical diaphragm in a structural laminations or wood strands held together with
framing system. A shearwall is any endwall, an adhesive, with fibers primarily oriented along
sidewall, or intermediate wall capable of trans- the length of the member. Examples include
ferring in-plane shear forces. LVL and PSL.

Siphon Break: A small groove to arrest the cap- Threaded Nail: A type of nail with either annual
illary action of two adjacent surfaces. or helical threads in the shank. Threaded nails
generally are made from hardened steel and
Soffit: The underside covering of roof over- have smaller diameters than common nails of
hangs. similar length.

Soil Pressure: Load per unit area that the foun- Timber: Wood members five or more nominal
dation of a structure exerts on the soil. inches in the least dimension.

Span: Horizontal distance between two points. Top Chord: An inclined or horizontal member
that establishes the top of a truss.
Clear Span: Clear distance between adja-
cent supports of a horizontal or inclined TPI: Truss Plate Institute.
member. Horizontal distance between the
facing surfaces of adjacent supports. Truss: An engineered structural component,
assembled from wood members, metal connec-
Effective Span: Horizontal distance from tor plates and/or other mechanical fasteners,
center-of-required-bearing-width to center- designed to carry its own weight and superim-
of-required-bearing-width, or the "clear posed design loads. The truss members form a

1-7
National Frame Builders Association Post-Frame Building Design Manual

semi-rigid structural framework and are assem- Harmon, J.D., G.R. Grandle and C.L. Barth.
bled such that the members form triangles. 1992. Effects of hurricane Hugo on agricultural
structures. Applied Engineering in Agriculture
UBC: Uniform Building Code (see ICBO). 8(1):93-96.

Wane: Bark, or lack of wood from any cause, on Knight, J.T. 1989. A brief look back. Frame
the edge or corner of a piece. Building Professional 1(1):38-43.

Warp: Any variation from a true plane surface. Knight, J.T. 1990. Diaphragm design - technol-
Warp includes bow, crook, cup, and twist, or any ogy driven by necessity. Frame Building Profes-
combination thereof. sional 1(5):16,44-46.

Bow: Deviation, in a direction perpendicular Norum, W.A. 1967. Pole buildings go modern.
to the wide face, from a straight line drawn Journal of the Structural Division, ASCE, Vol.
between the ends of a piece of lumber. 93, No.ST2, Proc. Paper 5169, April, pp.47-56.

Crook: Deviation, in a direction perpendicu- Taylor, S.E. 1996. Earthquake considerations in


lar to the narrow edge, from a straight line post-frame building design. Frame Building
drawn between the ends of a piece of lum- News 8(3):42-49.
ber.

Cup: Deviation, in the wide face of a piece


of lumber, from a straight line drawn from
edge to edge of the piece.

Twist: A curl or spiral of a piece of lumber


along its length. Measured by laying lumber
on a flat surface such that three corners
contact the surface. The amount of twist is
equal to the distance between the flat sur-
face and the corner not contacting the sur-
face.

WCLIB: West Coast Lumber Inspection Bureau

Web: Structural member that joins the top and


bottom chords of a truss. Web members form
the triangular patterns typical of most trusses.

WTCA: Wood Truss Council of America.

WWPA: Western Wood Products Association.

1.6 References

Faherty, K.F. and T.G. Williamson. 1989. Wood


Engineering and Construction Handbook.
McGraw-Hill Publishing Company, New York,
NY.

Gurfinkel, G. 1981. Wood Engineering (2nd Ed.).


Kendall/Hunt Publishing Company, Dubuque,
Iowa.

1-8
National Frame Builders Association Post-Frame Building Design Manual

Chapter 2: BUILDING CODES, DESIGN SPECIFICATIONS


AND ZONING REGULATIONS

2.1 Introduction (SBCCI). These model building codes are com-


monly referred to as the UBC, BOCA and the
2.1.1 Definition. A building code is a legal Southern Building Code, respectively.
document that helps ensure public health and
welfare by establishing minimum standards for 2.2.2 Adoption. Most states have adopted (and
design, construction, quality of materials, use enforce) all or a major portion of one of the three
and occupancy, location and maintenance of all model building codes. As shown in figure 2.1,
buildings and structures. western states have adopted the UBC, north-
eastern states the BOCA code, and states in the
2.1.2 Model Versus Active Codes. A model southwest the Southern Building Code.
code is a code that is written for general use
(i.e., a code that is not written for use by a spe- 2.2.3 Development. Model building codes are
cific state, county, town, village, company or consensus documents continually studied and
individual). An active code is a model or spe- annually revised by building officials, industry
cially written code that has been adopted and is representatives and other interested parties.
enforced by a regulatory agency such as a state
or local government. It follows that in a given 2.2.4 International Building Code. On De-
jurisdiction, acceptance of a model building code cember 9, 1994, the three model building code
is voluntary until the model code becomes part agencies (BOCA, ICBO and SBCCI) created the
of the active code in the jurisdiction. International Code Council (ICC). The ICC was
established in response to technical disparities
2.1.3 Active Code Variations. The content and among the three major model codes. Since its
administration of active building codes varies not founding, the ICC has worked to create a single
only between states, but frequently between model building code for the U.S. This code,
municipalities within a state. Some states have which is entitled the International Building Code
established a hierarchy structure of state, county is now complete and will replace the three
and township/village/city building codes. In this model codes over the next couple years. With all
situation, more localized governing areas can states adopting the same model code, it will be
modify the state (or county) codes, provided the less difficult for building designers to work in
changes result in more strict provisions. different regions of the country.

Despite local differences in content and admini- 2.3 Building Classification


stration, most active building codes share the
common trait of regulating components of con-
struction based on building occupancy and use. 2.3.1 General. Building codes give criteria for
classifying buildings based on: (1) use or occu-
pancy, and (2) type of construction.
2.2 Major Model Building Codes
2.3.2 Occupancy Classifications. Occupancy
2.2.1 Current Codes. There are currently three classifications include assembly, business, edu-
primary model building codes in the United cational, factory and industrial, high-hazard, in-
States. These are the Uniform Building Code stitutional, mercantile, residential and storage.
(UBC) published by the International Congress Occupancy classifications have requirements on
of Building Officials, the National Building Code the number of occupants and building separa-
published by the Building Officials and Code tion, height and area. Other limits exist, for ex-
Administrators International (BOCA) and the ample on lighting, ventilation, sanitation, fire
Standard Building Code published by the
Southern Building Code Congress International

2-1
National Frame Builders Association Post-Frame Building Design Manual

Uniform Building Code (ICBO)


National Building
Code (BOCA)

Standard Building
Code (SBCCI)

Figure 2.1. Approximate areas of model building code influence. Wisconsin and New
York building codes are developed by their respective state code agencies and are not
necessarily influenced by current model codes.

protection and exiting, depending on the specific tain areas of noncombustible construction. The
classification and building code. superior fire resistance of large timber members
is recognized by the codes with the inclusion of
2.3.2 Types of Construction. Classification by a "heavy timber" classification. To qualify for
type of construction is primarily based on the fire heavy timber construction, nominal dimensions
resistance ratings of the walls, partitions, struc- of timber columns must be at least 6- by 8-
tural elements, floors, ceilings, roofs and exits. inches and primary beams shall have nominal
Specific requirements vary somewhat between width and depth of at least 6- by 10-inches.
model building codes.
2.3.2.1 NFBA Sponsored Fire Test. In
There are two primary source documents for January of 1990, the National Frame Build-
determining the fire resistance of assemblies: ers Association had Warnick Hersey Inter-
the Fire Resistance Design Manual, published national, Inc., conduct a one-hour fire en-
by the Gypsum Association, and the Fire Resis- durance test on the exterior wall shown in
tance Directory, published by Underwriters figure 2.2. The wall met all requirements for
Laboratories, Inc. a one-hour rating as prescribed in ASTM E-
119-88. The wall sustained an applied load
The fire resistance of wood framed assemblies of 10,400 lbf per column throughout the test.
can generally be increased by using fire retar- Copies of the fire test report can be obtained
dant treated (FRT) wood or larger wood mem- from NFBA.
bers. Codes allow FRT wood to be used in cer-

2-2
National Frame Builders Association Post-Frame Building Design Manual

Attach metal cladding 12 in. o.c. with 1.5 in.


hex head screws with neoprene washers Metal cladding 29 gage

Section A-A
B

Gold Bond 5/8 in. Fireshield G Type X,


Unexposed nominal 2- attached with 1-7/8 in. cement coated nails
by 4-inch nailers 24 (0.0195 in. shank, 1/4 head, 7 in. o.c.)
in. o.c.

Nominal 2- by 4-inch
nailers, 24 in. o.c.
Fire side nailers, A A
nominal 2- by 4-inches
10 ft
24 in. o.c. FIRE SIDE 4-1/16- by 5-1/4-inch
glue-laminated column

Nominal 2- by 2-inch
3- by 24- by 48-inch blocking between nailers
mineral wool, attach with (nailed to nominal 2- by
3 in. square cap nails (3 6-inch edge blocks)
per 48 in. width)
Nail-laminated column fabricated from 3 nominal
2- by 6-inch No. 2 KD19 SP members
Nominal 2- by 4-inch blocking attached to column

B
Section B-B
1 ft 8 ft 1 ft

Figure 2.2. Construction details for exterior wall that obtained a one-hour fire endurance
rating during a January 1990 test conducted for the National Frame Builders Association
by Warnock Hersey International, Inc. Details of the test are available from NFBA upon
request.

2.4 Specifications and Standards nical literature for wood design and construction
is somewhat fragmented. New design specifica-
tions and standards are continually under devel-
2.4.1 General. Design of buildings is covered in
opment, and existing documents are periodically
the model building codes either by direct provi-
revised. Keeping abreast of this literature re-
sions or by reference to approved engineering
quires a determined effort on the part of the de-
specifications and standards. Engineering speci-
sign professional. To assist in this effort, Table
fications and standards provide criteria and data
2.1 gives a partial list of engineering design
needed for load calculation, design, testing and
specifications, standards and other technical
material selection. They are based on the best
references specifically related to post-frame
available information and engineering judgment.
construction. The reader is encouraged to main-
tain communication with the organizations isted
2.4.2 Wood Design Specifications. The tech in Table 2.1 concerning new and revised publi-
cations.

2-3
National Frame Builders Association Post-Frame Building Design Manual

Of the documents listed in Table 2.1, the primary height, and density of population and activity.
engineering design specification cited by the Zoning laws may also dictate building appear-
model building codes for wood construction is ance and location on property, parking signs,
the National Design Specification® for Wood drainage, handicap accessibility, flood control
Construction (NDS®), published by the American and landscaping. Typically land is zoned for
Forest & Paper Association (AF&PA). The NDS residential, commercial, industrial or agricultural
was first issued in 1944 and in 1992 it became a uses.
consensus standard through the American Na-
tional Standards Institute (ANSI). 2.5.2 Development and Enforcement. Zoning
laws are developed by municipalities. They (and
2.5 Zoning Regulations building codes) are principally enforced by the
granting of building permits and inspection of
construction work in progress. Certificates of
2.5.1 General. Zoning laws are established to- occupancy are issued when completed buildings
control construction activities and regulate land satisfy all regulations.
use, in terms of types of occupancy, building

Table 2.1. Partial list of technical references related to post-frame building design and construction
Organization & Address Publications

Allowable stress design (ASD) manual for engineered wood


construction
National design specification® (NDS®) for wood construction
AF&PA
NDS commentary
American Forest & Paper Association
Design values for wood construction (NDS supplement)
1111 19th Street, N.W., Suite 800
Load and resistance factor design (LRFD) manual for engi-
Washington, D.C. 20036
neered wood construction
http://www.awc.org/
Wood frame construction manual (WFCM) for one-and two-
family dwellings
Span tables for joists and rafters

AITC
American Inst. of Timber Construction
Timber construction manual
7012 S. Revere Parkway, Suite 140
Englewood, CO 80112

ANSI
American National Standards Institute ANSI/AF&PA National design specification for wood construc-
11 West 42nd Street tion (see AF&PA)
New York, NY 10036 ANSI Standard A190 structural glued laminated
http://www.ansi.org/

2-4
National Frame Builders Association Post-Frame Building Design Manual

Table 2.1. Partial list of technical references related to post-frame building design and construction
Organization & Address Publications

APA
APA design/construction guide; residential and commercial
The Engineered Wood Association
Plywood design specification (PDS)
P.O. Box 11700
Diaphragms and shear walls
7011 South 19th Street
Performance standard for APA EWS I-joists
Tacoma, WA 98411
Panel handbook & grade glossary
http://www.apawood.org/

ASAE EP288 Agricultural building snow and wind loads


ASAE EP484.2 Diaphragm design of metal-clad, wood-frame
ASAE rectangular buildings
2950 Niles Road ASAE EP486 Post and pole foundation design
St. Joseph, MI 49085-9659 ASAE EP558 Load tests for metal-clad, wood-frame dia-
http://asae.org/ phragms
ANSI/ASAE EP559 Design requirements and bending proper-
ties for mechanically laminated columns

ASCE ASCE Standard 7 Minimum Design Loads for Buildings and


American Society of Civil Engineers Other Structures
1801 Alexander Bell Drive Standard for load and resistance factor design (LRFD) for engi-
Reston, Virginia 20191-4400 neered wood construction
http://www.asce.org/ Guide to the use of the wind load provisions of ASCE 7-95

Standard C2 lumber, timbers, bridge ties and mine ties - pre-


servative treatment by pressure processes
Standard C15 wood for commercial-residential construction -
AWPA preservative treatment by pressure processes
American Wood Preservers Assoc. Standard C16 wood used on farms - preservative treatment by
P.O. Box 5690 pressure processes
Granbury, TX 76049 Standard C23 round poles and posts used in building construc-
tion - preservative treatment by pressure processes
Standard M4 standard for the care of preservative-treated wood
products

AWPI
American Wood Preservers Institute
Answers to often-asked questions about treated wood
2750 Prosperity Avenue, Suite 550
Management of used treated wood products booklet
Fairfax, Virginia 22031-4312
http://www.awpi.org/

Gypsum Association
810 First St., NE, #510 Fire resistance design manual GA-600
Washington DC, 20002 Design data - gypsum board GA-530
http://www.gypsum.org/

2-5
National Frame Builders Association Post-Frame Building Design Manual

Table 2.1. Partial list of technical references related to post-frame building design and construction
Organization & Address Publications

ICC
International Code Council
http://www.intlcode.org/
International building code
International energy conservation code
BOCA International, Inc.
International zoning code
4051 West Flossmoor Road
International property maintenance code commentary
Country Club Hills, IL 50478-5794
International property maintenance code
http://www.bocai.org/
International fuel gas code
International mechanical code commentary
ICBO
International mechanical code
5360 Workman Mill Road
International mechanical code supplement
Whittier, CA 90601-2298
International private sewage disposal code
http://www.icbo.org/
International one and two family dwelling code
International plumbing code commentary
SBCCI, Inc.
International plumbing code
900 Montclair Road
Birmingham, AL 35213-1206
http://www.sbcci.org/

MBMA
Metal Building Manufacturers Assoc.
Low rise building systems manual
1300 Sumner Ave
Metal building systems
Cleveland, OH 44115-2851
http://www.mbma.com/

NFBA
National Frame Builders Association
4840 W. 15th St., Suite 1000 Post wall assembly fire test
Lawrence, KS 66049-3876
http://www.postframe.org/

NFPA NFPA 1: Fire prevention code


National Fire Protection Association NFPA 13: Installation of sprinkler
1 Batterymarch Park NFPA 70: National electrical code
Quincy, MA 02269-9101 NFPA 72: National fire alarm code
http://www.nfpa.org/ NFPA 101: Life safety code

SPIB
Southern Pine Inspection Bureau Grading rules
4709 Scenic Highway Standard for mechanically graded lumber
Pensacola, Fl. 32504-9094 Kiln drying southern pine
http://www.SPIB.org/

2-6
National Frame Builders Association Post-Frame Building Design Manual

Table 2.1. Partial list of technical references related to post-frame building design and construction
Organization & Address Publications

Southern pine use guide


SFPA & Southern Pine Council
Southern pine joists & rafters: construction guide
Southern Forest Products Association
Southern pine joists & rafters: maximum spans
P. O. Box 641700
Post-frame construction guide
Kenner, LA 70064-1700
Southern pine headers and beams
http://www.southernpine.com/
Pressure-treated southern pine
http://www.SFPA.org/
Permanent wood foundations: design & construction guide

ANSI/TPI 1-1995 National design standard for metal plate con-


nected wood truss construction
HIB-91 Summary sheet: handling, installing & bracing metal
TPI plate connected wood trusses
Truss Plate Institute HIB-98 Post frame summary sheet: recommendations for han-
583 D'Onofrio Drive, Suite 200 dling, installing & temporary bracing metal plate connected
Madison, WI 53719 wood trusses used in post-frame construction
HET-80 Handling & erecting wood trusses: commentary and
recommendations
DSB-89 Recommended design specifications for temporary
bracing of metal plate connected wood trusses

UL
Underwriters Laboratories, Inc.
333 Pfingsten Road Fire resistance directory
Northbrook, IL 60062-2096
http://www.ul.com/

WTCA
Metal plate connected wood truss handbook
Wood Truss Council of America
Commentary for permanent bracing of metal plate connected
One WTCA Center
wood trusses
6425 Normandy Lane
Standard responsibilities in the design process involving metal
Madison, WI 53711
plate connected wood trusses
http://www.woodtruss.com/

WWPA
Western Wood Products Association Western woods use book
522 SW Fifth Ave., Suite 500 Western lumber span tables
Portland, Oregon 97204-2122 Western lumber grading rules
http://www.wwpa.org/

2-7
National Frame Builders Association Post-Frame Building Design Manual

2-8
National Frame Builders Association Post-Frame Building Design Manual

Chapter 3: STRUCTURAL LOAD AND DEFLECTION CRITERIA

3.1 Introduction approval process, and then must be adopted by


the model building codes. Design professionals
3.1.1 Load Variations. Most structural loads should check the governing building code for the
exhibit some degree of random behavior. For latest adopted edition. For clarity of presenta-
example, weather-related loads such as snow, tion, this manual uses and will refer to ASCE 7-
wind and rain fluctuate over time and locations. 93.
Extensive research has been conducted to
characterize this load variation, and to refine ASCE 7-93 is the primary technical source used
procedures for determining design loads within by the model codes concerning dead, live,
the context of the intended building occupancy snow, wind, rain and seismic loads. Basically,
and use. the model codes attempt to distill the rigorous
ASCE 7-93 procedures into a simpler, easy-to-
3.1.2 Codes. Calculation procedures for mini- use format. Many specific load calculation pro-
mum design loads are given in the model build- cedures differ between the model codes; how-
ing codes. Buildings shall be designed to safely ever, most of the basic concepts mimic ASCE 7-
carry all loads specified by the governing build- 93. Background information on the wind load
ing code. In the absence of a code, minimum provisions in ASCE 7-88 (which are essentially
design loads shall be calculated according to the same as in ASCE 7-93) are given by Mehta
recommended engineering practice for the re- et al. (1991).
gion and application under consideration.
3.2.2 Low Rise Building Systems Manual.
It is impractical to describe detailed load calcula- The Low Rise Building Systems Manual, pub-
tion procedures in this chapter because of dif- lished by the Metal Building Manufacturers As-
ferences between building codes and frequent sociation (1986), is recognized by model build-
revisions of these codes. Instead, general con- ing codes as an excellent technical resource
cepts and key references related to structural document for calculating structural loads on low-
loads and deflection criteria are presented, with rise buildings (e.g. post-frame buildings). This
an emphasis on issues that apply to post-frame document will be referred to as MBMA-86
buildings. throughout this manual. Because wind and
crane loads frequently control the design of low-
rise metal buildings, the coverage of these loads
3.2 Technical References on within MBMA-86 is especially thorough. Another
Structural Load Determination attractive feature of MBMA-86 is the extensive
collection of example load calculations.
3.2.1 ANSI/ASCE 7 Standard. The National
Bureau of Standards published a report titled 3.2.3 ASAE EP288.5 Standard. Agricultural
Minimum Live Load Allowable for Use in Design buildings generally fall into a separate class
of Buildings in 1924. The report was expanded from other types of buildings due to the lower
and published as ASA Standard A58.1-1945. risks involved. The American Society of Agricul-
This standard has undergone several revisions tural Engineers publishes a snow and wind load
to become the current ASCE Standard standard, EP288.5, intended for agricultural
ANSI/ASCE 7 Minimum Design Loads for Build- buildings (ASAE, 1999). The major differences
ings and Other Structures. At the time this de- between agricultural and other types of buildings
sign manual was written, the most recent revi- are that lower values are used for importance
sion of ASCE 7 was 1999 (ASCE, 1999); how- and roof snow conversion factors (due to rela-
ever, the edition most commonly used is ASCE tively lower risk factors for property and non-
7-93. The ASCE 7 standard is periodically re- public use). If the local governing building code
vised and balloted through the ANSI consensus applies to agricultural buildings, then the design
load criteria in the code must be followed.

3-1
National Frame Builders Association Post-Frame Building Design Manual

Table 3.1. Approximate Weights of Construction Materials (from Hoyle and Woeste, 1989)
Weight Weight
Material Material
(lb/ft2) (lb/ft2)

Ceilings Roofs (continued)


Acoustical fiber tile 1.0 Plywood (per inch thickness) 3.0
Gypsum board (see Walls) Roll roofing 1.0
Mechanical duct allowance 4.0 Shingles
Suspended steel channel system 2.0 Asphalt 2.0
Wood purlins (see Wood, Seasoned) Clay tile 9.0-14.0
Light gauge steel (see Roofs) Book tile, 2-in. 12.0
Book tile, 3-in 20.0
Floors Ludowici 10.0
Hardwood, 1-in. nominal 4.0 Roman 12.0
Plywood (see Roofs) Slate, ¼ in. 10.0
Linoleum, 1/4-in. 1.0 Wood 3.0
Vinyl tile, 1/8-in. 1.4
Walls
Roofs Wood paneling, 1-in. 2.5
Corrugated Aluminum Glass, plate, 1/4-in. 3.3
14 gauge 1.1 Gypsum board (per 1/8-in. thick- 0.55
16 gauge 0.9 Masonry, per 4-in. thickness
18 gauge 0.7 Brick 38.0
20 gauge 0.6 Concrete block 20.0
Built-Up Cinder concrete block 20.0
3-ply 1.5 Stone 55.0
3-ply with gravel 5.5 Porcelain-enameled steel 3.0
5-ply 2.5 Stucco, 7/8-in. 10.0
5-ply with gravel 6.5 Windows, glass, frame, and sash 8.0
Corrugated Galvanized steel
16 gauge 2.9 Wood, Seasoned Density
18 gauge 2.4 lb/ft3
20 gauge 1.8 Cedar 32.0
22 gauge 1.5 Douglas-fir 34.0
24 gauge 1.3 Hemlock 31.0
26 gauge 1.0 Maple, red 37.0
29 gauge 0.8 Oak 45.0
Insulation, per inch thickness Poplar, yellow 29.0
Rigid fiberboard, wood base 1.5 Pine, lodgepole 29.0
Rigid fiberboard, mineral base 2.1 Pine, ponderosa 28.0
Expanded polystyrene 0.2 Pine, Southern 35.0
Fiberglass, rigid 1.5 Pine, white 27.0
Fiberglass, batt 0.1 Redwood 28.0
Lumber (see Wood, Seasoned) Spruce 29.0

3-2
National Frame Builders Association Post-Frame Building Design Manual

3.3 Minimum Design Loads


Technical Note
Sections 3.4, 3.5, 3.6, 3.7, and 3.8 give general Horizontal Uniform Dead Load Calculation
load requirements, sources of load data and
Many structural analysis programs (e.g. Purdue
references for making detailed load calculations.
Plane Structures Analyzer) require that the dead
Detailed calculation procedures are not provided
load associated with a sloping surface be repre-
due to differences between the model codes
sented as a uniform load, wDL, acting on a hori-
and the frequency of code revisions.
zontal plane as shown in figure 3.1. For a given
horizontal distance, bH, a sloping roof surface
3.4 Dead Loads contains more material and is heavier than a flat
one. Thus, wDL increases as roof slope in-
3.4.1 Definition. Dead loads are the gravity creases.
loads due to the combined weights of all perma-
nent structural and nonstructural components of Load wDL is obtained by multiplying the unit
the building, such as sheathing, trusses, purlins, weight of the roof assembly, wR, by the slope
girts and fixed service equipment. These loads length, bS, and dividing the resulting product by
are constant in magnitude and location through- the horizontal length, bH. Numerically, this is
out the life of the building. equivalent to dividing wR by the cosine of the
roof slope.
3.4.2 Code Application. Minimum design dead
loads shall be determined according to the gov- Example: For a roof at a 4:12 slope, with materi-
erning building code. In the absence of a build- als weighing 4 lbm for each square foot of roof
ing code, dead load data can be found in ASCE surface area, the equivalent load, wDL, to apply
7-93, or actual weights of materials and equip- to the horizontal plane would be:
ment can be used.
wDL = (4 lbm/ft2)/(cos 18.4°) = 4.21 lbm/ft2
3.4.3 Special Considerations. Design dead
loads that exceed the weights of construction
materials and permanent fixtures are permitted,
wDL
except for when checking building stability under
wind loading. Using inflated design dead loads
may lead to conservative designs for gravity
load conditions; however, it would not be a con- bH
servative assumption for designing anchorage to Roof assembly
counteract uplift, overturning and sliding due to with weight wR
wind loads. In the cases of wind uplift and over- per unit area
turning, the dead load used in design must not
exceed the actual dead load of the construction. Rafter or truss θ
top chord
3.4.4 Weights of Construction Materials. Ta-
bS
ble 3.1 lists approximate weights of materials.
commonly used in post-frame construction.

3.5 Live Loads Figure 3.1. Roof dead load represented by an


equivalent uniform load acting on a horizontal
plane.
3.5.1 Definition. Live loads are defined as the
loads superimposed by the construction, main-
tenance, use and occupancy of the building, and 3.5.2 Code Application. Design live loads shall
therefore do not include wind, snow, seismic or be determined so as to provide for the service
dead loads. requirements of the building, but should never
be lower than the minimum live load specified in

3-3
National Frame Builders Association Post-Frame Building Design Manual

the governing building code. In the absence of a pf = roof snow load in psf,
governing building code, the minimum live loads R = roof snow factor that relates roof
found in ASCE 7-93 are recommended. The load to ground snowpack,
minimum roof live load recommended for agri- Ce = snow exposure factor,
cultural buildings in ASAE Standard EP288.5 is Ct = roof temperature factor,
12 psf. Some agricultural buildings do not nec- I = importance factor,
essarily pose a "low risk", and the ASAE higher Cs = roof slope factor, and
minimum live load reflects the possibility of high- Pg = ground snow load in psf (50-yr
value agricultural constructions now common in mean recurrence).
the United States
The roof snow factor, R, varies from 0.6 for
3.5.3 Reductions. In some cases, reductions Alaska to 0.7 for the contiguous United States.
are allowed for uniform loads to account for the The snow exposure factor in the model codes
low likelihood of the loads simultaneously occur- accounts for the combined effects of R and Ce
ring over the entire tributary area. given in Equation 3-1. The thermal factor de-
fined in ASCE 7-93 varies from 1.0 for heated
structures to 1.2 for unheated structures. The
3.6 Snow Loads
thermal factor is not included in the model build-
ing codes. The importance factors range from
3.6.1 Code Application. Minimum design snow 0.8 to 1.2 depending on the specific building
loads shall be determined by the provisions of code. Roof slope factors vary linearly from 0 to 1
the governing building code. The presentation of as roof slope increases from 15 to 70 degrees.
snow loads varies among the model codes, but
they all follow the basic concepts presented in 3.6.5 Special Considerations. Several factors,
ASCE 7-93. In the absence of a building code, such as multiple gables, roof discontinuities, and
procedures given in ASCE 7-93 are recom- drifting can cause snow to accumulate unevenly
mended. For low-risk agricultural buildings, on roofs. These factors must be considered in
snow load calculation procedures given in ASAE the design. Specific recommendations and cal-
EP288.5 are permitted. culation procedures are given in the model
codes and ASCE 7-93.
3.6.2 Ground Snow Load Maps. ASCE 7-93
presents ground snow load maps that corre-
spond to a mean recurrence interval of 50 years. 3.7 Wind Loads
These maps do not give snow load values for
areas that are subject to extreme variations in 3.7.1 Controlling Factors. Wind loads are in-
snowfall, such as western mountain regions. In fluenced by wind speed, building orientation and
some regions, the best and only reliable source geometry, building openings and exposure.
for ground snow loads is local climatic records. Wind loading on structures is a complex phe-
nomenon and is being actively researched.
3.6.3 Roof Snow Loads. Roof snow loads are
influenced by a number of factors besides 3.7.2 Code Application. Minimum design wind
ground snow load. These factors include roof loads shall be determined by the provisions of
slope, temperature and coefficient of friction of the governing building code. In the absence of a
the roof surface, and wind exposure. Snow building code, procedures given in ASCE 7-93
loads are also adjusted by an importance factor or MBMA-86 are recommended. For low-risk
to account for risk to property and people. The agricultural buildings, wind load calculation pro-
basic form of the snow load calculation found in cedures given in ASAE EP288.5 are permitted.
ASCE 7-93 is:
3.7.3 Design Wind Speed. ASCE 7-93 gives a
pf = R Ce Ct I Cs Pg (3-1) map showing basic wind speeds throughout the
United States that correspond to a mean recur-
where: rence interval of 50 years. Local weather rec-

3-4
National Frame Builders Association Post-Frame Building Design Manual

ords should be used in regions that have un- model codes publish fewer exposure categories.
usual wind events. Detailed procedures and il- Importance factors vary from 0.95 for agricul-
lustrations for calculating wind loads on low-rise tural buildings (25-year recurrence interval) to
buildings are given in MBMA-86. 1.07 for buildings that represent a high hazard to
property and people in the event of failure (100-
year recurrence interval). Wind pressure is re-
Technical Note lated to the square of its speed, therefore the
Wind Speed terms V and I are squared in equation 3-2. The
model building codes simplify the calculation in
Wind speeds are derived from data which reflect equation 3-2 by publishing tables of effective
both magnitude and duration. Wind speeds can wind velocity pressures, Pb, for a base wind
be reported as peak gusts, or can be averaged speed and various heights.
over some time interval. The time interval may
be fixed, as with mean hourly speeds, or vari- 3.7.5 Pressure Coefficients. Wind loads are
able, as with “fastest-mile” wind speeds. Fast- calculated for each part of the building by multi-
est-mile wind speeds are used in ANSI/ASCE 7- plying the effective wind pressure by a pressure
93 to calculate design loads, and are defined on coefficient. The pressure coefficient, which may
the basis of the period of time that one mile of be different for each planar portion of the build-
wind takes to pass an anemometer at a stan- ing, accounts for building orientation, geometry
dard elevation of 10 meters. The U.S. National and load sharing. It also accounts for localized
Weather Service no longer collects fastest-mile pressures at eaves, overhangs, corners, etc.
wind speed data; instead, they record 3-second Wind pressures, qi, for the ith building surface
gust speeds. The 1995 and later revisions of are calculated by:
ASCE-7 base wind loads on 3-second gust wind
speeds. qi = Cpi qz (3-3)

where:
3.7.4 Effective Wind Velocity Pressure. The
first step in determining wind loads is to calcu- Cpi = ith pressure coefficient, and
late the effective wind velocity pressure. The qz = wind velocity pressure.
most severe exposure factors that will apply dur-
ing the service life of the structure should be The wind velocity pressure is based on the wall
used. Wind velocity pressure is a function of the height for the windward wall and on the mean
wind speed, exposure and importance. The roof height for the leeward wall and roof. Wind
equation for calculating wind velocity pressure, pressures act normal to the building surfaces.
qz , is given by: Inward pressures are denoted with positive
signs, while outward pressures (suction) are
qz = 0.00256 Kz (I V)2 (3-2) denoted with negative signs.

where:
Technical Note
Kz = velocity pressure exposure coeffi- Components of Wind Load
cient,
I = importance factor, and Many structural analysis programs require uni-
V = basic wind speed in mph (50-year form loads to be entered in terms of their hori-
mean recurrence interval). zontal and vertical components. Wind loads act
normal to building surfaces, so an adjustment is
The velocity pressure exposure coefficient is a needed for sloping members such as roof
function of height above ground and exposure trusses. The roof wind load, w, shown in figure
category. Exposure categories account for the 3.2a is equivalent to the horizontal and vertical
effects of ground surface irregularities caused components shown in figure 3.2b. The relation-
by natural topography, vegetation, location and ship depicted in figure 3.2 can be proven as fol-
building construction features. ASCE 7-93 lists lows:
four wind exposure categories, whereas the

3-5
National Frame Builders Association Post-Frame Building Design Manual

these members have relatively large tributary


1. Convert the uniform wind load, w, to its re- areas, localized wind effects tend to be aver-
sultant vector force. aged out over the tributary areas. Pressure coef-
ficients for main members reflect this averaging
R = w (span)/(cos θ) effect.

2. Multiply resultant force, R, by cos θ to obtain 3.7.7 Components and Cladding. Wind pres-
its vertical component. sures are higher on small areas due to localized
gust effects. This observation has been verified
Fy = R (cos θ) = w (span) by wind tunnel studies (MBMA, 1986), as well as
site inspections of wind-induced building failures
3. Divide the vertical component, Fy, by the (Harmon, et al., 1992). For this reason, compo-
span to obtain the horizontally projected up- nents and cladding have higher pressure coeffi-
lift pressure, whoriz. cients than main frames. Components and clad-
ding include members such as purlins, girts, cur-
whoriz = Fy /(span) = w (span)/(span) = w tain walls, sheathing, roofing and siding.

The vertically projected uniform load can be 3.7.8 Openings. Wind loads are significantly
proven similarly. A common mistake is to multi- affected by openings in the structure. ASCE 7-
ply the normal pressure by sine and cosine of 93 and the model building codes specify internal
the roof slope to obtain the two components. wind pressure coefficients (or adjustments to
external pressure coefficients) for structures with
different amounts and types of openings. Each
model code has slightly different definitions and
w wind load coefficients for open, closed and par-
tially open buildings. In general, "openings" refer
to permanent or other openings that are likely to
θ be breached during high winds. For example, if
window glazings are likely to be broken during a
(a) windstorm, the windows are considered open-
ings. However, if doors and windows and their
w supports are designed to resist design wind
loads, they need not be considered openings. It
should be noted that internal wind pressures act
against all interior surfaces and therefore do not
w contribute to sidesway loads on a building.
θ
3.8 Seismic Loads
(b)

Figure 3.2. Illustration of wind load acting nor- 3.8.1 Cause. Earthquakes produce lateral
mal to inclined surface and equivalent horizontal forces on buildings through the sudden move-
and vertical load components. A common mis- ment of the building’s foundation. Building re-
take is to multiply the normal load by sin(θ) and sponse to seismic loading is a complex phe-
nomenon and there is considerable controversy
cos(θ) for the vertical and horizontal compo-
as to how to translate knowledge gained through
nents, respectively.
research into practical design codes and stan-
dards.

3.7.6 Main Frames. Different pressure coeffi- 3.8.2 Code Application. Seismic loads shall be
cients are used to calculate wind loads on main determined by the provisions of the governing
frames as compared to components and clad- building code. In the absence of a building code,
ding. Main frames include primary structural sys- procedures given in ASCE 7-93 are recom-
tems such as rigid and braced frames, braced mended. Sweeping changes were made in the
trusses, posts, poles and girders. Since

3-6
National Frame Builders Association Post-Frame Building Design Manual

1993 revision of ASCE 7 with respect to seismic 3.9.2 Load Combinations. Except when appli-
loads. The seismic provisions in ASCE 7-93 cable codes provide otherwise, the following
were based on work by the Building Seismic load combinations shall be considered (as a
Safety Council under sponsorship of the Federal minimum) and the combination which results in
Emergency Management Agency. the most conservative design for each building
element shall be used. Note that different load
3.8.3 Lateral Force. Basic concept of seismic combinations may control the design of different
load determination for low-rise buildings is to components of the structure.
calculate an equivalent lateral force at the
ground line as follows: Case 1: Dead + Floor Live + Roof Live (or
Snow)
V = Cs W (3-4) Case 2: Dead + Floor Live + Wind (or Seismic)
Case 3: Dead + Floor Live + Wind + ½ Snow
where: Case 4: Dead + Floor Live + ½ Wind + Snow
Case 5: Dead + Floor Live + Snow + Seismic
V = total lateral force, or shear, at the
building base 3.9.3 Floor Live Loads. Most post-frame build-
W = total dead load, plus other applica- ings are single story and therefore would not
ble loads specified in the code or have floor live loads acting on the post-frames.
ASCE 7-93. For most single-story When a concrete floor is used in a single story
post-frame buildings, the only other building, consideration must be given to antici-
minimum applicable load is a por- pated live and equipment loading.
tion (20% minimum) of the flat roof
snow load. If the flat roof snow load 3.9.4 Reductions. Reductions in some of the
is less than 30 psf, the applicable load terms in Cases 1 through 5 are permitted,
load to be included in W is permitted depending on governing building code or refer-
to be taken as zero. ence document. With some exceptions, the
Cs = seismic design coefficient model building codes permit allowable stresses
= 1.2 Av S/(T2/3 R) used in allowable stress design to be increased
one-third when considering wind or seismic
Av = coefficient representing effective forces either acting alone or when combined
peak velocity-related acceleration with vertical loads. The allowable stress in-
S = coefficient for the soil profile charac- crease for wind loading can be traced back to
teristics the New York City Building Code of 1904 (Elli-
R = response modification factor fritt, 1977), and appears to be based on judg-
T = fundamental period of the building ment rather than engineering theory. It should
be noted that ASCE 7-93 does not include the
3.8.4 Seismic loads rarely control post-frame one-third increase factor, but instead specifies
building design because of the relatively low load combination factors that are intended to
building dead weight as compared with other account for the low probability of maximum live,
types of construction (Taylor, 1996; Faherty and seismic, snow and wind loads occurring simul-
Williamson, 1989). For post-frame buildings, taneously. The commentary of ASCE 7-93 im-
lateral loads from wind usually are much greater plies the stress increase for wind and seismic
than those from seismic forces. found in codes is not appropriate if the com-
bined load effects are also reduced by the load
3.9 Load Combinations for combination factors published in ASCE 7-93.
Finally, the National Design Specification (NDS)
Allowable Stress Design for Wood Construction (NF&PA, 199) addresses
the issue of load combination versus load dura-
3.9.1 Code Application. Every building ele- tion factors by stating, “The load duration fac-
ment shall be designed to resist the most critical tors, CD, in Table 2.3.2 and Appendix B are in-
load combinations specified in the governing dependent of load combination factors, and both
building code. shall be permitted to be used in design calcula-
tions.”

3-7
National Frame Builders Association Post-Frame Building Design Manual

3.10 Load Duration Factors for Wood flexibility of corrugated metal siding, girt deflec-
tions present no serviceability problems, and
consequently, girt size is generally only stress
It is well documented that wood has the property
dependent.
of being able to carry substantially greater loads
for short durations than for long durations of
loading. This property is accounted for in design 3.11.3 Time Dependent Deflection. In certain
through the application of load duration factors situations, it may be necessary to limit deflection
to all allowable design values except modulus of under long term loading. Published modulus of
elasticity and compression perpendicular to elasticity, E, values for wood are intended for the
grain. Additional restrictions and details on load calculation of immediate deflection under load.
duration adjustments can be found in Chapter 2 Under sustained loading, wood members exhibit
and Appendix B of the NDS (AF&PA, 1997). additional time-dependent deformation (i.e.
creep). It is customary practice to increase cal-
culated deflection from long-term loading by a
3.10.1 Snow Load. The cumulative duration of
factor of 1.5 for glued-laminated timber and sea-
maximum snow load over the life of a structure
soned lumber, or 2 for unseasoned lumber (see
is generally assumed to be two months. It
Appendix F, AF&PA, 1997). Thus, total deflec-
should be emphasized that the two-month pe-
tion is equal to the immediate deflection due to
riod does not necessarily mean that the design
long-term loading times the creep deflection fac-
snow load from any one event would last two
tor, plus the deflection due to the short-term or
months. Rather, it means that the total time that
normal component of load. For applications
the roof supports the full design snow load over
where deflection is critical, the published value
the life of the structure is two months. If the cu-
of E (which represents the average) may be re-
mulative full design load is two months, an al-
duced as deemed appropriate by the designer.
lowable stress increase of 15 percent is allowed
The size of the reduction depends on the coeffi-
(AF&PA, 1997). However, in some situations,
cient of variation of E. Typical values of E vari-
such as unheated or heavily insulated buildings
ability are available for different wood products
in cold climates, longer snow load durations may
(see Appendix F, AF&PA, 1997).
occur and the stress increase may not be justi-
fied.
3.11.4 Shear Deflection. Shear deflection is
3.10.2 Wind Load. The cumulative duration of usually negligible in the design of steel beams;
maximum wind (and seismic) loads over the life however, shear deflection can be significant in
of a structure is generally assumed to be 10 wood beams. Approximately 3.4 percent of the
minutes (AF&PA, 1997), if design wind loads are total beam deflection is due to shear for wood
based on ASCE 7-93, and the corresponding beams of usual span-to-depth proportions (i.e.
load duration factor is 1.6. Other load duration 15:1 to 25:1). For this reason, the published
adjustments may be appropriate when design value of E in the Supplement to the National De-
wind loads are based on earlier versions of sign Specification is 3.4 percent less than the
ASCE 7-93 or other standards (with different true flexural value (AF&PA, 1993). This correc-
wind gust duration assumptions). tion compensates for the omission of the shear
term in handbook beam deflection equations.
For span-to-depth ratios over 25, the predicted
3.11 Deflection deflection using the published E value will ex-
ceed the actual deflection. Similarly, for span-to-
3.11.1 Code Application. Post-frame building depth ratios less than 15, predicted deflections
components must meet deflection limits speci- will be significantly less than actual. This could
fied in the governing building code. lead to unconservative designs (with respect to
serviceability) for post-frame members such as
3.11.2 Exception to Code Requirements. door headers. Practical information on the ef-
Girts supporting corrugated metal siding are fects of shear deformation on beam design is
typically not subjected to deflection limitations given in Appendix D of Hoyle and Woeste
unless their deflection compromises the integrity (1989) for rectangular wood beams and Triche
of an interior wall finish. Because of the inherent (1990) for wood I-beams.

3-8
National Frame Builders Association Post-Frame Building Design Manual

3.12 References

American Forest & Paper Association (AF&PA).


1997. ANSI/AF&PA NDS-1997 - National Design
Specification for Wood Construction. AF&PA,
Washington, D.C.

American Forest & Paper Association (AF&PA).


1993. Commentary to the National Design
Specification for Wood Construction. AF&PA,
Washington, D.C.

ASAE. 1999. ASAE EP288.5: Agricultural build-


ing snow and wind loads. ASAE Standards
1999, 46th edition, ASAE, St. Joseph, MI.

American Society of Civil Engineers (ASCE).


1993. Minimum design loads for buildings and
other structures. ANSI/ASCE 7-93, ASCE, New
York, NY.

American Society of Civil Engineers (ASCE).


1999. Minimum design loads for buildings and
other structures. ANSI/ASCE 7-99, ASCE, New
York, NY.

Ellifritt, D.S. 1977. The mysterious 1/3 stress


increase. American Institute of Steel Construc-
tion Engineering Journal (4):138-140.

Faherty, K.F. and T.G. Williamson. 1989. Wood


Engineering and Construction Handbook.
McGraw-Hill, New York, NY.

Hoyle, R.J. and F.E. Woeste. 1989. Wood


Technology in the Design of Structures. Ames,
IA: Iowa State University Press.

Mehta, K.C., R.D. Marshall and D.C. Perry.


1991. Guide to the Use of the Wind Load Provi-
sions of ASCE 7-88 (formerly ANSI A58.1).
American Society of Civil Engineers, New York,
NY.

Metal Building Manufacturers Association


(MBMA). 1986. Low rise building systems man-
ual. MBMA, Cleveland, OH.

Taylor, S.E. 1996. Earthquake considerations in


post-frame building design. Frame Building
News 8(3):42-49.

3-9
National Frame Builders Association Post-Frame Building Design Manual

3-10
National Frame Builders Association Post-Frame Building Design Manual

Chapter 4: STRUCTURAL DESIGN OVERVIEW

4.1 Introduction and ceiling diaphragms are formed that can add
considerable rigidity to the building. In many
post-frame buildings, diaphragms and shear-
4.1.1 General. The aim of this chapter is to give
walls are carefully designed and become an in-
a broad overview of post-frame building design,
tegral part of the main wind-force resisting sys-
and then highlight unique aspects of post-frame
tem. Roof and Ceiling Diaphragms are covered
that require special design considerations. Post-
in Section 4.9 and Shearwalls in Section 4.10.
frame is a special case of light-frame wood con-
struction. Light-frame construction is accepted
by all model building codes, and the design pro- 4.1.5 Limitations. The structural design of
cedures are well documented. The design rules buildings involves making many judgments,
that apply to light-frame wood construction also such as determining design loads, structural
apply to post-frame. However, there are some analogs and analyses, and selecting materials
aspects of post-frame that are not as familiar to that can safely resist the calculated forces. New
building designers, such as diaphragm design, research or testing could justify a change of de-
interaction between post-frames and dia- sign procedure for the industry or for an individ-
phragms, and post foundation design. Hence, ual designer. The considerations presented here
Chapters 5, 6, 7 and 8 focus on these topics in are not exhaustive, since many issues in a spe-
more detail. cific building design will require unique treat-
ment.
4.1.2 Primary Framing. Primary framing is the
main structural framing in a building. In a post- 4.2 Posts
frame building, this includes the columns,
trusses (or rafters), and any girders that transfer 4.2.1 General. The function of the wood post is
load between trusses and columns. Each truss to carry axial and bending loads to the founda-
and the post(s) to which it is attached form an tion. Posts are embedded in the ground or at-
individual "post-frame". Post-frames collect and tached to either a conventional masonry or con-
transfer load from roof purlins and wall girts to crete wall or a concrete slab on grade. Posts
the foundation. In the context of wind loading in can be solid sawn, mechanically laminated,
standards and building codes, post-frames are glued-laminated or wood composite. Any portion
an integral part of the main wind-force resisting of a post that is embedded or exposed to
system. Specific sections dedicated to primary weather must be pressure-treated with pre-
framing include: Section 4.2 Posts, Section 4.3 servative chemicals to resist decay and insect
Trusses, Section 4.4 Girders, and Section 4.5 damage.
Knee braces.
4.2.2 Controlling Load Combinations. The
4.1.3 Secondary Framing. Secondary framing load combination that usually controls post de-
includes any framing member used to (1) trans- sign is dead plus wind plus one-half snow; how-
fer load between cladding and primary framing ever, local codes may stipulate different load
members, and/or (2) laterally brace primary combinations. It is possible for any one of the
framing members. The secondary framing combinations to be critical; therefore, they all
members in a post-frame building include the should be considered for a specific building de-
girts, purlins and any structural wood bracing sign. For example, maximum gravity load will
such as permanent truss bracing. Specific sec- govern truss-to-post bearing and post founda-
tions dedicated to secondary framing include: tion bearing; whereas wind minus dead load will
Section 4.6 Roof Purlins, Section 4.7 Wall Girts, govern the truss-to-post connection (for uplift).
and Section 4.8 Large Doors.
4.2.3 Force Calculations. The diaphragm
4.1.4 Diaphragms and Shearwalls. When analysis method presented in Chapter 5 is the
cladding is fastened to the wood frame of a most accurate method to determine design
post-frame building, large shearwalls and roof

4-1
National Frame Builders Association Post-Frame Building Design Manual

moments, and axial and shear forces in posts. 4.2.7 Connections. Truss-to-post connection
Historically, some designers calculated the must be designed for bearing as well as uplift.
maximum post moment for embedded posts by Connection design procedures are given in the
using the simple structural analog of a propped NDS (AF&PA, 1997). This connection should be
cantilever (i.e. fixed reaction at the post bottom modeled as a pin unless moment-carrying ca-
and pin reaction at the top). The implicit as- pacity can be justified. Direct end grain bearing
sumption of this analog is that the roof dia- is desirable and is often achieved by notching
phragm and shearwalls are infinitely stiff. This the post to receive the truss. When designing
model may be adequate for buildings with ex- the truss-to-post connection for uplift, it is impor-
tremely stiff roof diaphragms and for conserva- tant to accurately estimate the weights of con-
tively estimating shear forces in the roof dia- struction materials if any counteracting credit is
phragm; however, it may underestimate the to be taken.
maximum post moment for many post-frame
buildings. The analysis procedures described in For surface-attached posts, the bottom connec-
Chapter 5 are more reliable since they account tion needs to be checked for maximum shear
for the flexible behavior of the roof diaphragm. and uplift forces. For embedded posts attached
to collars or footings, the connections must be
If posts are embedded, generally two bending properly designed to withstand gravity and uplift
moments must be calculated - one at the loads, and corrosion-resistant fasteners must be
groundline and the other above ground. Ground- used.
line bending moment and shear values are used
in embedded post foundation design calcula- 4.2.8 Construction Alternatives. The posts in
tions. For surface-attached posts, the bottom post-frame buildings can be solid sawn, me-
reaction can be modeled as a pin, and generally chanically-laminated, glued-laminated or wood
only one bending moment is calculated. composite. Allowable design stresses are pub-
lished in the NDS or are available from the
4.2.4 Combined Stress Analysis. Forces in- manufacturers. Treated wood is used for the
volved in post design subject the posts to com- embedded part of the post, but no treatment is
bined stress (bending and axial) and must be required on the parts that are not in contact with
checked for adequacy using the appropriate in- the ground and are protected by the building
teraction equation from the NDS (AF&PA, 1997). envelope.
In theory, every post length increment must sat-
isfy the interaction equation, but in practice, a 4.2.9 Foundation. Post-frame building founda-
minimum of two locations are checked: the point tions include posts embedded in the ground or
of maximum interaction near the ground level surface-attached on a concrete foundation. Em-
(column stability factor, Cp, equal to 1.0) and the bedded posts shall be designed to resist sides-
upper section of the posts where the maximum way and overturning forces due to wind or seis-
moment occurs in conjunction with column ac- mic loads, as well as wind uplift, and gravity
tion (Cp<1.0). loads. Post foundation design is an important
aspect of post-frame building design that is not
4.2.5 Shear Stress. The shear stress due to well known in the structural engineering design
lateral loading (wind or seismic) rarely controls community, and therefore Chapter 8 is dedi-
post design, but should always be checked as a cated to this subject. If a concrete slab is used, it
matter of good practice. Other loads such as only needs to be designed for interior loads
bulk loads from stored materials may influence since exterior building loads are transferred di-
final post design. rectly to the ground through the posts.

4.2.6 Deflection. A post deflection limit is not Another option is to attach the posts to a con-
normally specified for post-frame buildings, but crete foundation. In this case, the concrete must
interior finishes may require it. Refer to the de- be designed to carry the exterior building loads
flection criteria in Chapter 3. as well as interior. Connections must be de-
signed to attach the posts to the concrete.

4-2
National Frame Builders Association Post-Frame Building Design Manual

4.2.10 Pressure Preservative Treatment


(PPT). Treated foundation systems have been copper arsenate (ACA), and ammoniacal copper
accepted by the model codes and have a history zinc arsenate. CCA is available in three formula-
of successful performance in residential wood tions: CCA-A, CCA-B, and CCA-C. CCA-C is the
construction. The most common pressure pre- most popular of the three formulations due to its
servative treatment used in post-frame construc- increased resistance to leaching.
tion is chromated copper arsenate (CCA). CCA
can increase the potential for metal-fastener Penta is an oil-borne preservative, and creosote
corrosion, and may require hot-dipped galva- is a coal-tar based preservative that is its own
nized or stainless steel fasteners. The minimum carrier. While penta and creosote offer superior
waterborne treatment retention for structural resistance in high salt environments, waterborne
posts used in post-frame buildings is 0.6 lb/ft3 preservatives are typically more popular since
(pcf) as defined in AWPA Standard C15 (AWPA, the final product has a clean surface, is pain-
1995a). table, and is relatively odorless. Waterborne pre-
servatives do provide a strong potential for cor-
rosion of metal connectors and fasteners; follow
Technical Note the manufacturers recommendations for the use
Wood Preservative Treatments of stainless or hot-dipped galvanized fasteners.

When the moisture content of wood exceeds While the major building codes endorse the use
20% on a dry weight basis in the presence of of preservative-treated wood for foundation ap-
oxygen, it is vulnerable to attack by insects and plications, it is imperative that the preservative
decaying fungi. Although some species of wood retention guidelines be followed. The American
(and the heartwood of other species) are natu- Wood Preservers Association has published
rally resistant to these types of attack, most standards for the preservative treatment of wood
structural woods used in North America are not. for various applications (AWPA, 1991). Care
These structural wood species must be chemi- must be taken that the appropriate standard is
cally treated to protect them from decay and considered when specifying treatment for post
maintain their strength throughout the structural foundation systems. For example, most water-
design life. borne preservative-treated lumber sold has a
preservative retention level of 0.4 pcf (pounds of
The chemicals used for preservative treatment preservative per cubic foot of wood), which is
of the wood are typically injected into the wood the retention level specified by AWPA Standard
using pressure processes. Wood that has been C2 for lumber in contact with the ground. This
chemically treated in this manner is accepted by differs, however, from the AWPA Standard C15
all major building codes. The type of preserva- governing the treatment of structural posts used
tive treatment and the required amount of reten- in foundations; the required preservative reten-
tion by the wood depends on the end use of the tion for waterborne preservatives under this
wood component. It is assumed that the de- standard is 0.6 pcf. The AWPA C15 required
signer is already familiar with the use of pre- retention level for post foundations using penta
servative treated wood for above-ground appli- as a preservative is 0.6 pcf, while the required
cations (such as wood decks); this section will retention level for creosote is 12.0 pcf.
concentrate specifically on preservative treat-
ments and retention levels appropriate for use in The rate at which treatments are absorbed into
post foundations. wood, and the depth of penetration of the treat-
ment, varies from wood species to wood spe-
Preservative chemicals abate wood decay by cies. Whereas Southern Pine species take
altering the wood as a potential food source for treatment quite well, most other species must be
insects and fungi. The preservatives typically incised to comply with AWPA retention require-
used in North America are waterborne arsenic- ments. Incising can adversely affect lumber
based, pentachlorophenol (penta) and creosote. strength properties. Consult AF&PA for specifi-
Waterborne arsenic-based preservatives include cations regarding the use of incised wood in
chromated copper arsenate (CCA), ammoniacal structural applications.

4-3
National Frame Builders Association Post-Frame Building Design Manual

Standard for Metal Plate Connected Wood


Quality assurance is critical to the performance Truss Construction.
of treated wood. The treating industry has de-
veloped a quality control and treatment quality 4.3.2 Design Loads. The controlling load com-
marking program accredited by the American bination for truss design often is snow plus dead
Lumber Standards Committee. Any treated load. The unbalanced snow load case should be
members specified for use in a post foundation checked per the applicable building code, or for
should be stamped by an approved agency agricultural buildings, engineering practice
(e.g., AWPA, Southern Pine Inspection Bureau ASAE EP288.5 (ASAE, 1999a) should be con-
(SPIB), etc.) to assure that the members have sulted. However, all other applicable load com-
been treated in accordance with AWPA Stan- binations must be checked. For example, a wind
dard C15 and to the appropriate retention level. load combination may cause stress reversal in
some truss elements as discussed later in this
Treated wood suppliers provide Material Safety chapter.
Data Sheets (MSDS) or Consumer Information
Sheets with the product. These sheets contain Truss loads are normally represented by listing
special instructions about the care, handling and the top-chord live and dead, and bottom-chord
disposal of treated wood. Federal law dictates live and dead loads, respectively. Truss design
that these sheets must be provided to all em- loads are typically expressed in units of pounds
ployees exposed to the materials. per square foot (psf). An example of truss load-
ing would be 20-4-0-1 (psf is implied). Both live
Saw cuts or drilled holes made after treatment and dead loads apply to the vertically projected
may expose untreated wood. This problem is tributary areas of the top and bottom chords.
especially critical if the newly exposed wood is Often, a bottom-chord live load is not required,
in the splash zone or in contact with the ground. so the preceding nomenclature would be short-
When using nail-laminated posts, the cut end of ened to 20-4-1 psf.
the treated lumber should be placed upward,
above the ground level; otherwise, brush- 4.3.3 Design. This design manual does not
applied, soaked, or dipped field treatments are present specifics of roof truss design. Metal-
recommended. AWPA Standard M4 outlines plate-connected wood trusses in the United
procedures for field treatment; some chemicals States are designed according to the provisions
require a certified pesticide applicators license of ANSI/TPI 1-1995. Other designs are based
to apply. The chemical suppliers should be con- on proprietary test information, along with de-
sulted for application restrictions. sign criteria from the NDS (AF&PA, 1997).
Model building codes recognize either of these
approaches.
4.3 Trusses ANSI-TPI 1-1995 mentions two types of struc-
tural analyses. The “simplified method” is a type
4.3.1 General. Together with posts, wood of pin joint analysis that has been calibrated to
trusses are primary structural elements of post- account for partial joint fixity. This method uses
frame buildings. Two excellent sources of tech- tables of factors to determine chord moments
nical information on trusses are the Truss Plate and member buckling lengths. The simplified
Institute (TPI) and the Wood Truss Council of method has been the predominate method for a
America (WTCA). Trusses must be properly de- number of years; however, it will eventually be
signed, handled and installed. These responsi- phased out by TPI. The other type of analysis
bilities are shared by the building owner, con- which is sometimes referenced as the “exact
tractor and designer, and the truss designer and method”, is a stiffness matrix method of analy-
manufacturer. The importance of a clear under- sis. Plane frame structures analyzers are be-
standing of responsibilities among these parties coming more commonly used and provide for
cannot be overstated, and is covered in WTCA more sophisticated and accurate analyses. Re-
1-1995 Standard Responsibilities in the Design gardless of analysis methods, structural model-
Process Involving Metal Plate Connected Wood ing assumptions are important and can dramati-
Trusses and ANSI/TPI-1-1995 National Design cally influence the design (Brakeman, 1994).

4-4
National Frame Builders Association Post-Frame Building Design Manual

For example, partial fixity at truss plate joints as load. This load case may not frequently control
well as eccentricity at heel joints, can be mod- the size of the truss chord lumber, but it makes
eled a variety of ways. The heel joint usually compression in the bottom chord possible. This
gets the most attention since heel joint modeling situation is one reason that lateral bracing of the
decisions can greatly influence truss design. bottom chord is required (TPI, 1989; 1991a;
1991b).
The size, and in some cases the orientation, of
truss plates is dependent on proprietary design 4.3.6 Temporary Bracing. Temporary bracing
values. These values are available from the is required to ensure stability of trusses during
manufacturers or from research reports pre- their installation and until permanent bracing for
pared by the model code agencies, Such as trusses and the building are in place. This area
ICBO, SBCCI and BOCA. is the most difficult to manage in the field.

Trusses can be obtained pre-engineered from According to WTCA 1-1995 and ANSI/TPI 1-
the manufacturer. It is important to consider 1995, determination and installation of tempo-
wind loading on trusses as stress reversals can rary bracing is the responsibility of the building
occur and overstress some members. This de- contractor. Truss Plate Institute (TPI) publication
sign is complicated by the fact that wind loads HIB-98 is a “summary sheet” that contains “rec-
are influenced by building geometry, so this in- ommendations for handling, installing and tem-
formation must be communicated to the truss porary bracing metal plate connected wood
designer. Any structural bracing (e.g. knee trusses used in post-frame construction.” An-
braces) or redundant supports must be included other TPI summary sheet (i.e., HIB-91) contains
in the truss design. similar recommendation for trusses with on cen-
ter spacings two feet or less and spans less
4.3.4. Truss-to-Post Connection. The connec- than 60 feet. Both HIB-98 and HIB-91 are for-
tion between the truss and post is critical. De- matted as accident-prevention brochures for use
signers must consider both gravity forces and by builders, building contractors, licensed con-
uplift forces. With some truss-to-post connection tractors, erectors, and erection contractors.
designs, it might be necessary to examine the
impact of the connection on the forces induced
4.3.7 Permanent Bracing. Permanent truss
in the truss chords, heel joints, and post. Obser-
bracing is critical to the performance of the roof
vations from several building investigations re-
system. Roof trusses are designed with the as-
vealed that the individual trusses and posts
sumption that their elements are held sufficiently
were designed properly, but the connection be-
in-plane (ANSI/TPI, 1995). The primary function
tween the two units was not. Many different
of permanent roof-truss bracing is to hold all
methods and hardware have been used to de-
trusses of the roof in the intended vertical plane.
sign the connection, such as bolts, nails, truss
HIB-98, provides guidance for the placement of
anchors, and combinations of the same. Unless
temporary truss bracing, which, if left in place,
otherwise governed by a specific code, the de-
may function as part of the permanent bracing
sign of this connection should meet NDS
system. Building designers are responsible for
(AF&PA, 1997) requirements.
designing permanent bracing. For trusses
spaced 4 ft or less, DSB-89 (TPI, 1989) provides
4.3.5 Stress Reversal. The trusses used in a calculation method for temporary and perma-
post-frame buildings are typically long span and, nent bracing designs. For trusses spaced
consequently, have long webs. When the truss greater than 4 ft (1.22 m) on-center, similar prin-
becomes part of a post-frame building, it is pos- ciples can be used, but designers must consider
sible, under certain loading conditions, for a ten- that the longer lengths involved may cause the
sion web in the truss design to become a com- bracing members to buckle. A commentary cov-
pression web. ering permanent bracing of metal plate con-
nected wood trusses is available from WTCA
Stress reversal can also occur in truss chords (1999).
due to a wind uplift loading combined with dead

4-5
National Frame Builders Association Post-Frame Building Design Manual

4.4 Girders the girder must be sized to handle additional


stresses due to torsion.
4.4.1 General. Girders are heavy beams used
to span large openings (e.g., doors) and to sup- 4.5 Knee Braces
port trusses located between posts. For exam-
ple, when roof truss spacing is less than the 4.5.1 General. Knee braces are intended to
post spacing, girders (sometimes called head- supplement the resistance of post frames under
ers) are needed to carry the intermediate lateral loads, and can influence the unsupported
trusses. This is a common occurrence over length of columns. They have been used less
large door openings. These beams are consid- and less in recent years.
ered main wind-force resisting members. Verti-
cally nail-laminated lumber, structural composite 4.5.2 Effectiveness. Knee brace effectiveness
lumber, glued-laminated beams and steel I- is highly dependent on the stiffness of its con-
beams are all commonly used as girders. There nections to the post and truss. If the connections
is an abundant supply of structural-composite at the ends of the brace are flexible or not very
lumber products from manufacturers who pub- stiff due to the use of a few nails, the roof dia-
lish their own allowable stresses. Often, the phragm carries the bulk of the load, and the
critical load combination is dead plus snow load, brace is ineffective (Gebremedhin and Woeste,
although all applicable load combinations must 1986). If the brace connections are made very
be checked. stiff (by installing many nails or bolts) the brace
could effectively resist the wind loading but
4.4.2 Design Criteria. Girders are designed as could overload the truss.
bending members. Any one of the four criteria
used for the design of bending members can 4.5.3 Analysis. Knee braces induce primary
control design (i.e. bending, shear, compression bending moments in truss chords if attached
perpendicular to grain, and deflection). Shear between panel points. Knee braces induce sec-
can often control girder design. Also note that ondary bending moments when attached directly
formulae found in most handbooks account for to panel points. If knee braces are to be used in
bending but not shear deflection. Designers a post-frame design, load sharing among the
should consider the impact of shear deflection truss, post, knee brace, connections, and dia-
on the total deflection of a girder. Hoyle and phragm (when applicable) must be included in
Woeste (1989) provide formulae for calculating the structural analysis.
shear deflection of wood beams.

4.4.3 Vertically Laminated Lumber. The de- 4.6 Roof Purlins


sign of girders for a post-frame building is rou-
tine structural design except when a girder is 4.6.1 General. Roof purlins are typically 2- by 4-
fabricated by vertically laminating three or more inch or 2- by 6-inch lumber, and are key struc-
pieces of dimension lumber. In this case, the tural elements of the roof assembly. They resist
allowable bending stress can be increased using gravity loads, wind loads, roof diaphragm chord
the repetitive member factors published in forces, and provide lateral bracing to truss top
ANSI/ASAE EP559 (ASAE, 1999b). These val- chords (or rafters). To fulfill the chord-bracing
ues are given in table 7.3. role, the purlins must be supported against lat-
eral movement by attachment to sheathing or
4.4.4 Connections. Girder attachment to posts metal cladding that provides the needed roof
and individual roof trusses is a fundamental part diaphragm strength. Not all roof cladding mate-
of girder design. When designing girder-to-post rials provide diaphragm strength and/or purlin
connections, both uplift and gravity must be lateral support; one example is standing seam
considered. When designing truss-to-girder roofing, which is fastened with clips that allow
connections, special consideration must be adjacent sheets to slide.
given to situations in which trusses are hung off
the side of the girder. In such cases truss-to- 4.6.2 Classification. Purlins in post-frame
girder connections should be designed to pre- buildings fall into the category of “component
vent rotation between the trusses and girder, or

4-6
National Frame Builders Association Post-Frame Building Design Manual

and cladding,” which is recognized by all three lins are recessed, and their capacity should be
model building codes. Components and clad- verified for the various loading cases. In general,
ding collect the loads and distribute them to the the provisions of the NDS (AF&PA, 1997) apply
primary structural elements, identified as the for the connections and stress analysis.
main wind-force resisting system. Wind loads
are much greater at eaves, ridges, edges, cor-
ners and other discontinuities. Purlin spacing 4.7 Wall Girts
and fasteners are critical in these areas. If these
areas fail under extreme wind loading, the build- 4.7.1 General. Girts are used to collect wind-
ing envelope will be breached, and internal wind induced wall loads and distribute them to the
pressures will change dramatically. post frames. For end walls, the wind loads are
distributed to structural end-wall posts.
4.6.3 Orientation. Purlins are installed on-edge
or flat. When they are used on-edge, they may 4.7.2 Classification. Girts belong to the “com-
be either placed on top of the truss or recessed ponent and cladding” category for determining
between the trusses. Purlins placed on-edge are the design wind load.
frequently overlapped and fastened together at
the overlap. When used flat, purlins are installed 4.7.3 Orientation. Girts are either installed flat
on top of the trusses. on post faces or recessed between the posts.
Girts recessed between posts are almost always
4.6.4 Truss Chord Bracing. Purlin spacing is a orientated with the narrow edge facing the clad-
factor in truss design since purlins provide lat- ding, and in this position, are frequently used to
eral support to the truss top chord. In some support both interior and exterior clad-
cases, the slenderness ratio for weak-axis truss ding/sheathing.
chord buckling between purlins can be greater
than that for strong-axis buckling. Therefore, 4.7.4 Post Bracing. Girts provide lateral sup-
when specifying trusses, the building designer port to side-wall columns. With girts securely
should inform the truss-design engineer of the installed, the slenderness ratio of the post weak
planned purlin spacing. axis is greatly reduced. Therefore, posts can
usually be designed to carry the axial loads us-
4.6.5 Design Loads. Purlin design often is con- ing the slenderness ratio of the strong axis.
trolled by the dead plus snow load combination,
or dead plus wind load (especially in the edge 4.7.5 Design Loads. Girts are normally de-
zones of the roof). Dead loads used for design signed to resist only wind load. Wind loads are
may exceed actual weights for gravity load cal- much greater at corners and other discontinui-
culations; however, inflated dead loads cannot ties. Girt spacing and fasteners are critical in
be used to offset wind uplift or wind overturn these areas. If these areas fail, the building en-
moments. In these cases, offsetting loads can- velope will be breached, and internal wind pres-
not exceed actual weights of materials. sures will change dramatically.

4.6.6 Design Criteria. Purlins members should The dead load of the girt and attached steel is
be checked for bending strength, shear capac- normally negligible for girt design. Cladding is
ity, and deflection. If the roof assembly is func- attached to the girts by nails or screws, and the
tioning as a structural diaphragm, purlins will stiffness of these connections does not allow the
also be subjected to axial forces. Purlins shall girts to undergo significant bending stress or
be designed to carry bending about both axes. deflection from the action of the small dead
Weak axis bending may be omitted if it can be loads present. However, the wall dead load
demonstrated by test or analysis that the roof should be included in total dead load calcula-
sheathing provides support. The connections tions for the post foundation.
between the purlins and rafters should be de-
signed for both gravity loads and wind uplift Girts must be design to resist forces induced by
forces. Purlin hangers are often used when pur- stored materials, especially granular materials
such as fertilizer or seeds/grain. Care should be

4-7
National Frame Builders Association Post-Frame Building Design Manual

taken to assure that the capacity of wall panels, 4.9.2 Design Properties. Diaphragm perform-
fasteners and girts are not exceeded by these ance depends on factors such as the steel, steel
forces. sheet-to-sheet fasteners, steel-to-wood fasten-
ers, and the wood frame. There is no standard
4.7.6 Design Criteria. Girts are designed as steel panel construction, so diaphragm strength
bending members for which the usual bending- and stiffness depend on the specific construc-
member design criteria apply. The critical con- tion used. Strength and stiffness data on labora-
nections between the girts and the post should tory test panels are generally required to derive
be checked for both wind pressure and suction. design values. Most post-frame buildings have
The top wall girt may be constructed to carry much greater spans than laboratory test panels;
chord forces from the roof diaphragm and, if so, therefore, test data must be extrapolated to
must be checked for the appropriate axial loads. prac-tical building sizes as explained in Chapter
The NDS (AF&PA, 1997) provisions apply for 6.
the connections and stress analysis.
4.10 Shearwalls
4.8 Large Doors
4.10.1 General. A large portion of the shear
4.8.1 General. Large doors are common in forces induced in roof and ceiling diaphragms is
post-frame buildings. Door components must be transferred to the building foundation by shear-
designed to withstand design wind loads, and walls. In many post-frame buildings, the only
are treated as “components and cladding” for walls available to transfer this shear are exterior
such calculations. walls (i.e., endwalls and sidewalls). Where pre-
sent, interior partition walls can be designed to
4.8.2 Open Doors. It is not uncommon for transfer additional shear.
building owners to leave large doors open, even
during periods of high wind. If an owner antici- 4.10.2 Endwalls. Endwalls in post-frame build-
pates that this will occur, the building must be ings resist wind loads perpendicular to the build-
designed accordingly. Note that a large opening ing end wall and simultaneously help transmit
on one side of the structure is generally associ- roof shears (due to parallel-to-end wall wind
ated with increased internal wind pressure coef- components) to the ground. In the diaphragm
ficients, and thus can significantly increase roof design procedure described in Chapter 5,
uplift forces. maximum roof shears occur at the endwalls.
The roof shear is transferred into the top truss
chord or rafter of the endwall, through the end-
4.9 Roof and Ceiling Diaphragms wall to the ground level, and finally to the ground
by posts or to posts connected to a concrete
4.9.1 General. Roof and ceiling diaphragms are slab. In addition to shear forces, the end wall is
used to resist lateral (sidesway) forces applied subject to overturning forces. Wirt et al. (1992)
to the building by wind, earthquake and stored have published procedures for analyzing and
material. Under lateral load, roof and ceiling dia- designing end-wall foundations.
phragms act as large stiff plates. These plates
support and distribute loads to wall posts. Con- 4.10.3 Wall Openings. Allowances must be
ceptually, diaphragm design is easy to under- made for openings in shearwalls. One common
stand, but the application of the procedure re- practice in post-frame construction is to place
quires analysis tools and data. large doorways in the building endwalls. Proce-
dures for accounting for the opening and ways
Diaphragms made from plywood are well docu- to reinforce the remaining wall are given in
mented, as well as those made entirely from Chapter 5.
steel. Less information is available about wood-
framed, metal-clad diaphragms which are preva- 4.10.4 Partitioning. Partitioning of the building
lent in the post-frame building industry. This is a into structural segments is one method to re-
major factor in post-frame building design and is duce maximum roof shears and endwall shears.
covered in more depth in Chapter 5. For example, if it is not practical to reinforce an

4-8
National Frame Builders Association Post-Frame Building Design Manual

endwall that has a large door installed, the alter- metal plate connected wood trusses. DSB-89.
native is to install a structural partition in the TPI, Madison, WI.
center of the building. The structural partition
must meet the shear requirements delivered by Truss Plate Institute (TPI). 1998. HIB-98 sum-
the roof diaphragm. Buttresses, inside or outside mary sheet. TPI, Madison, WI.
the walls, can be used to reduce the effective
length of the building with respect to maximum Truss Plate Institute (TPI). 1995. ANSI/TPI 1-
roof and end-wall shears. 1995 National design standard for metal plate
connected wood truss construction. TPI, Madi-
4.11 References son, WI.

Wirt, D.L., F.E. Woeste, D.E. Kline and T.E.


ASAE. 1999a. ASAE EP 288.5: Agricultural McLain. 1992. Design procedures for post-frame
building snow and wind loads. ASAE Standards, end walls. Applied Engineering in Agriculture
46th edition. ASAE, St. Joseph, MI. 8(1):97-105.
ASAE. 1999b. ANSI/ASAE EP 559: Design re- Wood Truss Council of America (WTCA). 1995.
quirements and bending properties for mechani- Standard responsibilities in the design process
cally-laminated posts. ASAE Standards, 46th involving metal plate connected wood trusses.
edition. ASAE, St. Joseph, MI. WTCA 1-1995. WTCA, Madison, WI.
American Forest & Paper Association (AF&PA). Wood Truss Council of America (WTCA). 1999.
1997. National design specification for wood Commentary for permanent bracing of metal
construction. AF&PA, Washington, D.C. plate connected wood trusses. WTCA, Madison,
WI.
American Wood-Preservers' Assc. (AWPA).
1995a. Wood for commercial-residential con-
struction. Preservative treatment by pressure
process, C-15. In Book of Standards. AWPA,
Stevensville, MD.

American Wood-Preservers’ Assc. (AWPA).


1995b. Lumber, timbers, bridge ties, and mine
ties, pressure treatment, C2-90. In Book of
Standards. AWPA, Stevensville, MD.

American Wood-Preservers' Assc. (AWPA).


1995c. Care of pressure treated wood products,
M4-90. In Book of Standards. AWPA, Stevens-
ville, MD.

Brakeman, D.B. 1994. Which truss design


method is the correct one? Peaks 16(1):1-3.

Gebremedhin, K.G., and F.E. Woeste. 1986.


Diaphragm design with knee brace slip for post-
frame buildings. Transactions of the American
Society of Agricultural Engineers 23(2):538-542.

Hoyle, R.J. and F.E. Woeste. 1989. Wood tech-


nology in the design of structures. Fifth edition.
Iowa State University Press, Ames, IA.

Truss Plate Institute (TPI). 1989. Recommended


design specifications for temporary bracing of

4-9
National Frame Builders Association Post-Frame Building Design Manual

4-10
National Frame Builders Association Post-Frame Building Design Manual

Chapter 5: DIAPHRAGM DESIGN

5.1 Introduction post-frame relative to that of other post-frames


and shearwalls. If a diaphragm is constructed in
such a way that it is quite stiff in shear, dia-
5.1.1 2-D Frame Analysis. Prior to the 1980’s,
phragm action will be enhanced and the dia-
the common method of analysis for post-frame
phragm will transfer load from post-frames with
structures in agricultural, commercial and light
low racking stiffness to shearwalls and post-
industrial applications was to consider the struc-
frames with high racking stiffness. However, if
ture as a system of independently-acting, two-
the shear stiffness of the diaphragm is relatively
dimensional (2-D) post-frames. Although a 2-D
low, load transfer will be minimal and the behav-
frame analysis method works well for designing
ior of the structure will be much more in accor-
frames under vertical loadings; it is often too
dance with the assumption of independently act-
conservative for designing buildings against
ing post-frames.
sidesway. In addition, many 2-D frames offer
little or no resistance to loads acting normal to
the frames (e.g., wind acting normal to the end-
walls). Eave displacement

5.1.2 Diaphragm Action. A considerable por-


tion of the horizontal load applied to many post-
frame structures is actually resisted by roof and Wind load
ceiling diaphragms and shearwalls. As previ-
ously stated (section 4.9), roof and ceiling dia-
phragms are large plates that are formed when
cladding is attached to roof and ceiling framing,
respectively. These large plates help redistribute Intermediate
load throughout the structure. This redistribution shearwall
of load by the diaphragms is called diaphragm Roof diaphragm
action. A shearwall is any wall – interior or exte-
rior – with a measurable amount of racking re- End shearwall
sistance. Most of the load to which a diaphragm Deformed structure
is subjected, is transferred to the foundation by
Undeformed structure
shearwalls orientated parallel to the direction of
applied load. Figure 5.1 illustrates a situation in
which wind load directed at a sidewall, is trans- Figure 5.1. Example of diaphragm action in
ferred via the roof diaphragm to the endwalls which the roof diaphragm transfers load to three
and one interior wall. Under this loading, the two shearwalls – one interior and two exterior walls.
endwalls and the one interior wall function as
shearwalls. When the same wind load is di- 5.1.4 Endwall Loadings. Virtually all post-
rected toward the endwall, the sidewalls function frame buildings are longer than they are wide. It
as shearwalls in transferring the load from the follows, that diaphragms in such buildings, when
roof diaphragm to the foundation system. viewed from the endwall, appear as narrow,
deep plates. For endwall loadings, these narrow,
5.1.3 Post-Frame Contributions. Whenever deep diaphragms are generally assumed to
load is applied normal to the sidewall of a struc- have an infinite shear stiffness, which means
ture, any post-frame with measurable racking that every structural element attached to the
resistance functions like the interior shearwall in diaphragm, shifts the same amount when the
figure 5.1. The amount of load that an individual diaphragm shifts without rotating. For example,
post-frame will transfer to the foundation is de- under an endwall loading, the roof diaphragm
pendent on (1) the in-plane shear stiffness of the would ensure equal displacement of the top of
diaphragm, and (2) the racking stiffness of the endwall posts and the top of each sidewall.

5-1
National Frame Builders Association Post-Frame Building Design Manual

5.1.5 Diaphragm Design. When diaphragm


action is accounted for in overall building design,
the design process is referred to as diaphragm
design. Diaphragm design is a relatively straight
forward process when a diaphragm is (1) as-
sumed to have infinite shear stiffness, and/or (2)
only attached to two shearwalls/post-frames (as
is generally the case with endwall loadings).
When neither of these conditions applies (gen-
erally true with loads normal to the sidewall)
diaphragm design is more complex.
(a)
5.1.6 ASAE EP484.2. The current diaphragm
design procedure is outlined in ANSI/ASAE
EP484.2: Diaphragm Design of Metal-Clad, Diaphragm "a"
Wood-Frame Rectangular Buildings (ASAE, Diaphragm "b"
1999a). This procedure, which is outlined in the
following sections, can be broken into five steps:
Step 1. Construct a finite element model of
Diaphragm "c"
the building by breaking the structure
into frame, shearwall, and diaphragm
elements (Section 5.2)
Step 2. Assign stiffness values to frames and (b)
shearwall elements (Section 5.3) and
diaphragm elements (Section 5.4).
Step 3. Calculate structural loads (i.e., eave 1 2 3 4 5
loads) for the model (Section 5.5).
Step 4. Determine the distribution of load to
individual elements (Section 5.6). 1a 2a 3a 4a
Step 5. Check to make sure that loads do not
exceed allowable values (Section 5.7).
1b 2b 3b 4b
5.2 Structural Model

5.2.1 General. The model developed in this (c)


section is only applicable for determining the
distribution of loads that are applied parallel to
individual post-frames (a.k.a., primary frames). 1 2 3 4 5
As previously stated, an individual post-frame
consists of an individual truss and any attached
posts.
1c 2c 3c 4c
5.2.2 Diaphragm Sectioning. The process of
modeling a post-frame building for diaphragm
design begins with the dividing of individual roof
and ceiling diaphragms into sections, herein re-
ferred to as diaphragm sections. Diaphragm
(d)
sectioning is a straight-forward process with in-
terior post-frames, interior shearwalls, ridge
lines and any other abrupt changes in roof and Figure 5.2. (a) Perspective view of a four-bay
ceiling slopes servings as lines of demarcation post-frame building with (b) roof and ceiling dia-
between diaphragm sections. phragms. Sectioning of (c) roof diaphragms, and
(d) ceiling diaphragm.

5-2
National Frame Builders Association Post-Frame Building Design Manual

Figures 5.2a shows a post-frame building with sent locations at the eave of each
three interior post-frames. Drawing a line along frame/shearwall.
each interior frame and the ridge results in the
eight (8) roof diaphragm sections shown in fig- Horizontal components of applied building loads
ure 5.2c, and the four ceiling diaphragm sec- are typically uniformly distributed along the
tions shown in figure 5.2d. length of the building as shown in figure 5.3a.
For modeling purposes, this uniform load is con-
To avoid confusion when assigning properties to verted into a set of equivalent concentrated
diaphragm sections, it is helpful to identify each loads that are applied at the nodes as shown in
diaphragm section with a two-digit identifier. The figure 5.3b. Because of the location of their ap-
first digit identifies the bay associated with the plication, these forces are referred to as eave
section. Bays are generally numbered from left- loads.
to-right, as shown in figures 5.2c and 5.2d. The
second digit identifies the specific roof or ceiling
slope. In figure 5.2, letters have been used to
identify these slopes, with letters “a” and “b” rep-
resenting different roof slopes, and letter “c” 1 2 3 4 5
used to identify ceiling sections.

5.2.3 Discretization. The process of breaking a


structure into elements for analysis is referred to 1 2 3 4
as discretization. For diaphragm design, a struc-
ture is broken into frame elements and dia-
phragm elements. Each post-frame is consid-
ered a separate frame element, as is each
shearwall orientated in the same direction as the
post-frames. The example building shown in
figure 5.2 would be modeled with five (5) frame
elements. These frame elements have been (a)
identified in figures 5.2c and 5.2d with the encir-
cled numbers (as with individual bays, number-
ing is generally from left-to-right). Each dia-
phragm element models the diaphragm sections k1 k2 k3 k4 k5
within a single bay. For example, diaphragm
sections 1a, 1b, and 1c in figure 5.2 would be
represented with a single diaphragm element. It
follows that the number of diaphragm elements
is equal to the number of building bays, which in
turn, is one less than the number of frame ele- Ch1 Ch2 Ch3 Ch4
ments. Discretization of a four-bay building is
shown in figure 5.3a. r1 r2 r3 r4 r5

5.2.4 Spring Model. To determine the distribu- (b)


tion of horizontally applied loads to individual
diaphragm and frame elements requires only a
single stiffness property for each element. For
this reason, diaphragm and frame elements are Figure 5.3. (a) Top view of a four-bay building
generally represented with simple springs. As showing individual elements and applied hori-
shown in figure 5.3b, frame elements are repre- zontal loads. Encircled numbers identify frame
sented with springs of stiffness, k, and dia- elements, other numbers identify diaphragm
phragm elements are represented as springs elements. (b) Corresponding spring model.
with stiffness Ch. The element (or spring) con-
nection points (a.k.a. nodes) are taken to repre-

5-3
National Frame Builders Association Post-Frame Building Design Manual

5.3 Frame Stiffness, k Post stiffness, kp, is graphically defined in figure


5.5. For a post with a constant flexural rigidity (E
x I) that is assumed to be fixed at the base, post
5.3.1 Definition. To be compatible with a model
stiffness is given as:
in which nodes represent points along the eave
line (figure 5.3b), frame element stiffness, k,
kp = 3 E I / Hp3 (5-3)
must equal the force required for a unit dis-
placement of the frame at the eave (figure 5.4).
where:
In equation form:

k = P/∆ (5-1) kp = stiffness of post that is fixed at the


base and pinned at the top, lbf/in
where: (N/mm)
E = modulus of elasticity of post, lbf/in2
k = frame stiffness, lbf/in (N/mm) (N/mm2)
P = load applied at eave, lbf (N) I = moment of inertia of post, in4 (mm4)
∆ = lateral displacement at eave result- Hp = post height from fixed base to truss
ing from applied load P, in (mm) connection post (see figure 5.5), in
(mm)


P ∆
k=P/∆ P

Post -to-truss
connection
Hp point

Figure 5.4. Definition of frame stiffness, k.


kp = P / ∆

5.3.2 Calculation. Frame stiffness is generally


obtained with a plane-frame structural analysis Figure 5.5. Definition of post stiffness, kp.
program, e.g., PPSA (Purdue Research Foun-
dation, 1993), METCLAD (Gebremedhin,
1987b), and SOLVER (Gebremedhin, 1987a). 5.3.3 Shearwalls. End shearwalls and interme-
For post-frames in which (1) all posts are as- diate shearwalls, like post-frames, are modeled
sumed to be pin-connected to the truss (or raf- as frame elements (see Section 5.2.3). Conse-
ters), and (2) there are no special members quently, their stiffness, like that for post-frames,
(e.g., knee braces) connecting posts to the is defined as the ratio of a horizontal force, P,
truss, frame stiffness can be calculated as: applied at the eave of the wall, to the resulting
horizontal eave displacement, ∆.
n
k = Σ kp,i (5-2) The stiffness of shearwalls can be obtained us-
i=1 ing validated structural models, or from tests of
functionally equivalent assemblies. ASAE
where: EP558 (1999b) gives laboratory test procedures
that can be used to determine the stiffness of
kp,i = stiffness of post i, lbf/in (N/mm) functionally equivalent walls. This topic is also
n = number of posts in the post-frame discussed in Section 6.5.

5-4
National Frame Builders Association Post-Frame Building Design Manual

Technical Note below grade. Meador (1997) developed similar


equations, but unlike Bohnhoff, Meador as-
Embedded Post Analogs
sumed that soil stiffness was not a function of
post width. Meador also investigated the as-
When a post is embedded in the soil, calculated
sumption of infinite post stiffness below grade,
post stiffness (and consequently calculated
and established limits for applicability of the
frame stiffness) is highly dependent on how the
equations he developed. McGuire (1998) used
embedded portion is modeled. Traditionally, en-
the work of both Bohnhoff and Meador to pro-
gineers have ignored soil properties and have
pose an analog where soil is modeled as a se-
modeled embedded posts using the analogs
ries of linear springs whose stiffness increases
shown in figures 5.6a and 5.6b. An inherent de-
linearly below grade (figure 5.6c). McGuire veri-
ficiency of these analogs is that the pin supports
fied Bohnhoff’s results and also showed that for
used to fix the post below grade do not allow the
the case of non-constrained posts, analogs like
post to naturally displace. For this reason, post
those shown in figure 5.6a may incorrectly pre-
stiffness values predicted using the analogs
dict the sense of base moment (see Chapter 8).
should be applied with caution. It should also be
noted that the analogs in figures 5.6a and 5.6b
Current impediments to the wide spread adop-
produce a reduced post stiffness when depth of
tion of analogs that account for soil stiffness in-
embedment, d, is increased. In reality, anytime a
clude: (1) complexity of equations, and (2) unre-
post is embedded deeper into the ground, the
alistically low post stiffness values obtained us-
stiffness associated with the post increases.
ing published soil stiffness data.
To accurately model post movement below
It is important for the post-frame designer to re-
grade requires accounting for soil stiffness.
alize that fixing the post at grade (figure 5.5)
Bohnhoff (1992) developed equations for pre-
generally produces conservative values for post
dicting post stiffness assuming soil stiffness in-
base moments, especially for the non-
creased linearly with depth below grade and
constrained post case. Conversely, forces calcu-
inversely with post width. Bohnhoff also as-
lated in the diaphragm using this model might be
sumed that the post had infinite flexural stiffness
non-conservative.

Hp Hp Hp

Ground
surface
Floor slab
0.34 d Springs
0.7 d
d d d used to
model soil
stiffness
0.1 d

(a) (b) (c)

Figure 5.6. Structural analog traditionally used for (a) non-constrained and (b) constrained
posts. (c) A more realistic non-constrained post analog that accounts for soil stiffness.

5-5
National Frame Builders Association Post-Frame Building Design Manual

5.4 Diaphragm Stiffness, Ch Ch = total horizontal shear stiffness of


diaphragm element, lbf/in (N/mm)
ch,i = horizontal shear stiffness of dia-
5.4.1 Definition. As shown in figure 5.7, the
phragm section i (from Section
stiffness of a diaphragm element is the horizon-
6.4.4), lbf/in (N/mm)
tal load required to cause a unit shift (in a direc-
n = number of diaphragm sections
tion parallel to the trusses/rafters) of the
comprising the diaphragm element
roof/ceiling assembly over a frame spacing
(a.k.a. bay width), s. This stiffness is commonly
referred to as the total horizontal shear stiffness, 5.5 Eave Loads, R
Ch, of the diaphragm.
5.5.1 Definition. For diaphragm design, build-
ing loads are replaced by an equivalent set of
horizontally acting, concentrated (i.e., point)
loads. These loads are located at the eave of
1 2 3 4
each frame element (i.e., post-frame and end
shearwall, and intermediate shearwall) and
therefore are referred to as eave loads. Eave
loads and applied building loads are equivalent
s1 s2 s3 s4 when they horizontally displace the eave an
equal amount.
(a)
Roof Gravity Loads

P P
s x qwr s x qlr

∆ R
i
C h,i = P / ∆
s xq ww

Ceiling Gravity Loads

s xqlw
si

Figure 5.8. Typical structural analog for obtain-


(b)
ing eave load, R.

Figure 5.7. (a) Top view of a four-bay building.


(b) Definition of diaphragm stiffness, Ch, for a 5.5.2 Calculation by Plane-Frame Structural
single diaphragm element. Analysis. A horizontal restraint (vertical roller)
is placed at the eave line as shown in figure 5.8
5.4.2 Calculation. The total horizontal shear and the structural analog is analyzed with all
stiffness of a diaphragm element is simply equal external loads in place. The horizontal reaction
to the sum of the horizontal shear stiffness val- at the vertical roller support is numerically equal
ues of the diaphragm sections that comprise the to the eave load, R. The vertical roller should
element. In equation form: always be placed at the same location that hori-
zontal load P was placed when determine frame
n stiffness (see figure 5.4). The value of R is very
Ch = Σ ch,i (5-4) dependent on the magnitude of forces with
i=1

where:

5-6
National Frame Builders Association Post-Frame Building Design Manual

horizontal components (i.e., wind and stored For symmetrical base restraint and frame ge-
materials). ometry, equation 5-5 reduces to:

5.5.3 Calculation Using Frame-Base Fixity R = s [hr (qwr – qlr) + hw f (qww – qlw)] (5-6)
Factors. When: (1) posts are assumed to be
pin-connected to trusses/rafters, (2) the only where:
applied loads with horizontal components are
due to wind, and (3) wind pressure is uniformly hr = roof height, ft (m)
distributed on each wall and roof surface, then hw = wall height, ft (m)
eave load, R, can be estimated as: f = frame-base fixity factor for both lee-
ward and windward posts
R = s (hwr qwr – hlr qlr +
hww fw qww – hlw fl qlw) (5-5) 5.6 Load Distribution
where:
5.6.1 General. The distribution of horizontal
R = eave load, lbf (N) loads to frames, shearwalls, and various dia-
s = frame spacing for interior post- phragm sections can be determined after stiff-
frames and shearwalls, ft (m) ness values have been assigned to each frame
= one-half the frame spacing for end- and diaphragm element, and eave loads have
walls, ft (m) been established.
hwr = windward roof height, ft (m)
hlr = leeward roof height, ft (m) 5.6.2 Analysis Tools. Any finite element or
hww = windward wall height, ft (m) plane-frame structural analysis program can be
hlw = leeward wall height, ft (m) used to analyze the structural model shown in
qwr = design windward roof pressure, figure 5.3b. However, to expedite this process,
lbf/ft2 (N/m2) computer program DAFI was developed
qlr = design leeward roof pressure, lbf/ft2 (Bohnhoff, 1992). Once eave loads and frame
(N/m2) and diaphragm element stiffness values are in-
qww = design windward wall pressure, put, DAFI calculates eave displacements, frame
lbf/ft2 (N/m2) element loads and diaphragm element shear
qlw = design leeward wall pressure lbf/ft2 forces. DAFI can be downloaded at no cost from
(N/m2) the NFBA web site (http://www.postframe.org/).
fw = frame-base fixity factor, windward
post An iterative method for hand-calculating load
fl = frame-base fixity factor, leeward distribution was developed by Anderson and
post others (1989). This method, which is referred to
as the force distribution method, is procedurally
Inward acting wind pressures have positive identical to the classical method of moment dis-
signs, outward acting pressures are negative tribution.
(figure 5.8). In buildings with variable frame
spacings, set s equal to the average of the 5.6.3 mS and mD Tables. Forces in the most
frame spacings on each side of the eave load. highly loaded diaphragm and frame elements,
can be calculated using tables 5.1 and 5.2 when
Frame-base fixity factors, fw and fl, determine all five of the following conditions exist: (1) all
how much of the total wall load is transferred to diaphragm elements have the same stiffness Ch,
the eave, and how much is transferred directly (2) all interior frame elements have the same
to the ground. The greater the resistance to ro- stiffness, k, (3) both exterior frame elements
tation at the base of a wall, the more load will be (i.e., the two elements representing the end-
attracted directly to the base of the wall. For walls) have the same stiffness, ke, (4) eave load,
substantial fixity against rotation at the ground- R, is the same at each interior frame, and (5) the
line, set the frame-base fixity factor(s) equal to eave load for each exterior frame is equal to
3/8. For all other cases, set the frame-base one-half that for an interior frame. These five
fixity factor(s) equal to 1/2. requirements are generally met in buildings with
a fixed bay spacing, endwalls that are virtually
identical in construction, and interior frames that

5-7
National Frame Builders Association Post-Frame Building Design Manual

don’t vary in overall design. When tables 5.1 and Q = sidesway restraining force, lbf (N)
5.2 are applicable, the analysis tools discussed mD = sidesway restraining force factor
in Section 5.6.2 are generally not needed. from Table 5.2
R = eave load at interior frame, lbf (N)
Input parameters required for tables 5.1 and 5.2
include: number of frame elements (i.e., the 5.6.4 In-Plane Shear Force in a Diaphragm
number of interior frames + 2); ratio of dia- Section, Vp. The analysis tools discussed in
phragm element to interior frame element stiff- Section 5.6.2 (and equation 5-7) output dia-
ness, Ch / k; and ratio of exterior to interior frame phragm element forces. In most cases, each
element stiffness, ke / k. element is comprised of two or more diaphragm
sections. The in-plane shear force in each of
The most highly loaded diaphragm element (in these diaphragm sections is calculated as:
any building that meets the preceding five condi-
tions) is the element located adjacent to the Vp,i = (ch,i / Ch) Vh / (cos θ i) (5-9)
endwalls. The maximum shear force in this dia-
phragm element, Vh, is equal to the appropriate where:
shear modifier value, mS, from table 5.1, multi-
plied by the eave load, R, for an interior frame. Vp,i = in-plane shear force in diaphragm
In equation form: section i, lbf (N)
Vh = horizontal shear force in the dia-
Vh = R mS (5-7) phragm element, lbf (N)
ch,i = horizontal shear stiffness of dia-
where: phragm section i, lbf/in. (N/mm)
θi = slope of diaphragm section i
Vh = maximum diaphragm element shear
force, lbf (N) 5.6.5 Forces Applied to Frames by Individual
mS = shear force modifier from Table 5.1 Diaphragms. The horizontal movement of most
R = eave load at interior frame, lbf (N) building frames is resisted by roof/ceiling dia-
phragms. The total horizontal resisting force ap-
The value obtained from equation 5-7 is simply plied to an individual frame by the roof/ceiling
equal to one-half of the total horizontal eave diaphragms was previously defined as the side-
load that is not carried by the interior frames. sway restraining force, Q. To accurately model a
frame with the resisting forces applied by the
The most highly loaded interior frame element roof and ceiling diaphragms, requires that the
(in any building that meets the preceding five sidesway restraining force, Q, first be divided up
conditions) is the element located closest to the between the individual diaphragms (e.g., dia-
building midlength. Because of diaphragm ac- phragms a, b, and c in figure 5.2b). This is ac-
tion, the total horizontal load that this critical complished using the following equation:
frame must resist is reduced from that which it
would have to resist without diaphragm action. Qi = Q (ch,i / Ch) (5-10)
The magnitude of this reduction is referred to
the horizontal restraining force because in real- where:
ity, it is a restraining force applied to the frame
by the roof (and/or ceiling) diaphragms. Numeri- Qi = sidesway resisting force due to dia-
cally, the horizontal restraining force, Q, is equal phragm i, lbf (N)
to the product of the eave load R, and the ap- Q = total sidesway resisting force acting
propriate sidesway restraining force factor, mD on the frame, lbf (N)
from table 5.2. In equation form: Ch = horizontal shear stiffness for a width
s of the roof/ceiling assembly, lbf/in.
Q = R mD (5-8) (N/mm)
ch,i = horizontal shear stiffness of dia-
where: phragm i with width s, lbf/in. (N/mm)

5-8
National Frame Builders Association Post-Frame Building Design Manual

Table 5.1. Shear Force Modifier (mS)


Number of frames (endwalls are counted as frames)
ke / k Ch / k
3 4 5 6 7 8 9 10 11 12 13 14 15 16

5 5 0.88 1.14 1.33 1.45 1.53 1.59 1.62 1.65 1.66 1.67 1.68 1.68 1.68 1.68
5 10 0.89 1.19 1.42 1.59 1.72 1.82 1.89 1.94 1.98 2.00 2.02 2.04 2.05 2.06
5 20 0.90 1.22 1.48 1.68 1.85 1.98 2.08 2.16 2.23 2.29 2.33 2.36 2.39 2.41
5 50 0.91 1.24 1.51 1.74 1.93 2.10 2.23 2.35 2.45 2.53 2.60 2.67 2.72 2.77
5 100 0.91 1.24 1.53 1.76 1.97 2.14 2.29 2.42 2.53 2.63 2.72 2.80 2.87 2.93
5 200 0.91 1.25 1.53 1.77 1.98 2.16 2.32 2.46 2.58 2.69 2.79 2.87 2.95 3.02
5 500 0.91 1.25 1.54 1.78 1.99 2.18 2.34 2.48 2.61 2.73 2.83 2.92 3.01 3.08
5 1000 0.91 1.25 1.54 1.78 2.00 2.18 2.35 2.49 2.62 2.74 2.84 2.94 3.02 3.10
5 10000 0.91 1.25 1.54 1.79 2.00 2.19 2.35 2.50 2.63 2.75 2.86 2.95 3.04 3.12

10 5 0.91 1.23 1.46 1.62 1.73 1.81 1.86 1.89 1.91 1.92 1.93 1.93 1.94 1.94
10 10 0.93 1.29 1.58 1.81 1.99 2.13 2.23 2.31 2.36 2.40 2.44 2.46 2.48 2.49
10 20 0.94 1.33 1.66 1.94 2.17 2.36 2.52 2.66 2.76 2.85 2.92 2.98 3.03 3.06
10 50 0.95 1.35 1.70 2.02 2.30 2.55 2.76 2.96 3.12 3.27 3.40 3.51 3.61 3.70
10 100 0.95 1.36 1.72 2.05 2.35 2.62 2.86 3.08 3.27 3.45 3.61 3.76 3.89 4.01
10 200 0.95 1.36 1.73 2.07 2.37 2.65 2.91 3.14 3.36 3.56 3.74 3.90 4.06 4.20
10 500 0.95 1.36 1.74 2.08 2.39 2.68 2.94 3.19 3.41 3.62 3.82 4.00 4.17 4.32
10 1000 0.95 1.36 1.74 2.08 2.40 2.68 2.95 3.20 3.43 3.64 3.84 4.03 4.20 4.37
10 10000 0.95 1.36 1.74 2.08 2.40 2.69 2.96 3.21 3.45 3.66 3.87 4.06 4.24 4.41

20 5 0.93 1.28 1.54 1.73 1.85 1.94 2.00 2.03 2.06 2.07 2.09 2.09 2.10 2.10
20 10 0.95 1.35 1.68 1.95 2.16 2.33 2.45 2.55 2.62 2.67 2.71 2.74 2.76 2.78
20 20 0.96 1.39 1.76 2.09 2.38 2.62 2.83 3.00 3.14 3.25 3.35 3.43 3.49 3.54
20 50 0.97 1.41 1.82 2.20 2.54 2.85 3.14 3.39 3.62 3.83 4.01 4.17 4.32 4.44
20 100 0.97 1.42 1.84 2.23 2.60 2.95 3.26 3.56 3.83 4.09 4.32 4.54 4.74 4.92
20 200 0.97 1.42 1.85 2.25 2.63 2.99 3.33 3.65 3.95 4.24 4.50 4.75 4.99 5.21
20 500 0.98 1.43 1.86 2.27 2.65 3.02 3.38 3.71 4.03 4.33 4.62 4.90 5.16 5.41
20 1000 0.98 1.43 1.86 2.27 2.66 3.03 3.39 3.73 4.06 4.37 4.66 4.95 5.22 5.48
20 10000 0.98 1.43 1.86 2.27 2.67 3.04 3.40 3.75 4.08 4.40 4.70 5.00 5.28 5.55

50 5 0.95 1.31 1.59 1.79 1.93 2.03 2.09 2.14 2.16 2.18 2.19 2.20 2.20 2.21
50 10 0.97 1.38 1.74 2.04 2.28 2.46 2.61 2.72 2.80 2.86 2.91 2.94 2.97 2.99
50 20 0.98 1.43 1.83 2.20 2.52 2.80 3.04 3.25 3.41 3.55 3.67 3.77 3.84 3.91
50 50 0.99 1.45 1.90 2.32 2.71 3.08 3.42 3.73 4.01 4.26 4.50 4.70 4.89 5.06
50 100 0.99 1.46 1.92 2.36 2.78 3.18 3.57 3.93 4.27 4.60 4.90 5.18 5.45 5.69
50 200 0.99 1.47 1.93 2.38 2.82 3.24 3.65 4.04 4.42 4.79 5.14 5.47 5.79 6.09
50 500 0.99 1.47 1.94 2.40 2.84 3.28 3.70 4.12 4.52 4.91 5.29 5.66 6.02 6.37
50 1000 0.99 1.47 1.94 2.40 2.85 3.29 3.72 4.14 4.55 4.96 5.35 5.73 6.11 6.47
50 10000 0.99 1.47 1.94 2.40 2.86 3.30 3.74 4.16 4.58 5.00 5.40 5.80 6.19 6.57

100 5 0.95 1.32 1.61 1.82 1.96 2.06 2.13 2.17 2.20 2.22 2.23 2.24 2.24 2.25
100 10 0.97 1.40 1.76 2.07 2.32 2.51 2.67 2.78 2.87 2.93 2.98 3.02 3.05 3.06
100 20 0.98 1.44 1.86 2.24 2.58 2.87 3.12 3.34 3.52 3.67 3.79 3.89 3.98 4.05
100 50 0.99 1.47 1.92 2.36 2.77 3.16 3.52 3.85 4.16 4.43 4.69 4.91 5.12 5.30
100 100 0.99 1.48 1.95 2.40 2.85 3.27 3.68 4.07 4.44 4.79 5.13 5.44 5.73 6.01
100 200 0.99 1.48 1.96 2.43 2.89 3.33 3.77 4.19 4.61 5.00 5.39 5.76 6.12 6.46
100 500 1.00 1.48 1.97 2.44 2.91 3.37 3.83 4.27 4.71 5.14 5.56 5.98 6.38 6.78
100 1000 1.00 1.48 1.97 2.45 2.92 3.39 3.85 4.30 4.75 5.19 5.62 6.05 6.48 6.89
100 10000 1.00 1.49 1.97 2.45 2.93 3.40 3.86 4.32 4.78 5.23 5.68 6.12 6.56 7.00

1000 5 0.95 1.33 1.63 1.84 1.99 2.09 2.16 2.20 2.23 2.25 2.27 2.27 2.28 2.28
1000 10 0.98 1.41 1.78 2.10 2.36 2.56 2.72 2.84 2.93 3.00 3.05 3.09 3.12 3.14
1000 20 0.99 1.45 1.88 2.28 2.63 2.93 3.20 3.43 3.62 3.78 3.91 4.02 4.11 4.18
1000 50 1.00 1.48 1.95 2.40 2.83 3.24 3.62 3.97 4.30 4.60 4.87 5.12 5.34 5.54
1000 100 1.00 1.49 1.97 2.45 2.91 3.36 3.79 4.21 4.61 4.99 5.35 5.69 6.02 6.32
1000 200 1.00 1.49 1.99 2.47 2.95 3.42 3.89 4.34 4.78 5.22 5.64 6.05 6.44 6.83
1000 500 1.00 1.50 1.99 2.49 2.98 3.46 3.95 4.42 4.90 5.37 5.83 6.29 6.74 7.18
1000 1000 1.00 1.50 2.00 2.49 2.98 3.48 3.97 4.45 4.94 5.42 5.90 6.37 6.85 7.31
1000 10000 1.00 1.50 2.00 2.50 2.99 3.49 3.98 4.48 4.97 5.47 5.96 6.45 6.94 7.43

10000 5 0.96 1.33 1.63 1.84 1.99 2.09 2.16 2.21 2.24 2.26 2.27 2.28 2.28 2.29
10000 10 0.98 1.41 1.79 2.10 2.36 2.57 2.72 2.85 2.94 3.01 3.06 3.10 3.12 3.14
10000 20 0.99 1.45 1.89 2.28 2.63 2.94 3.21 3.43 3.63 3.79 3.92 4.03 4.12 4.19
10000 50 1.00 1.48 1.95 2.40 2.84 3.25 3.63 3.98 4.31 4.61 4.89 5.14 5.36 5.57
10000 100 1.00 1.49 1.98 2.45 2.92 3.37 3.80 4.22 4.62 5.01 5.37 5.72 6.05 6.35
10000 200 1.00 1.50 1.99 2.48 2.96 3.43 3.90 4.35 4.80 5.24 5.66 6.08 6.48 6.87
10000 500 1.00 1.50 2.00 2.49 2.98 3.47 3.96 4.44 4.92 5.39 5.86 6.32 6.78 7.23
10000 1000 1.00 1.50 2.00 2.50 2.99 3.49 3.98 4.47 4.96 5.44 5.93 6.41 6.88 7.36
10000 10000 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 4.99 5.49 5.99 6.49 6.98 7.48

5-9
National Frame Builders Association Post-Frame Building Design Manual

Table 5.1. Shear Force Modifier (mS), cont.


Number of frames (endwalls are counted as frames)
ke / k Ch / k
17 18 19 20 21 22 23 24 25 26 27 28 29 30

5 5 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69
5 10 2.06 2.07 2.07 2.07 2.07 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08
5 20 2.43 2.44 2.46 2.46 2.47 2.48 2.48 2.49 2.49 2.49 2.49 2.49 2.50 2.50
5 50 2.81 2.84 2.87 2.89 2.92 2.94 2.95 2.97 2.98 2.99 3.00 3.01 3.01 3.02
5 100 2.98 3.03 3.07 3.11 3.14 3.18 3.20 3.23 3.25 3.27 3.29 3.30 3.32 3.33
5 200 3.09 3.14 3.19 3.24 3.28 3.32 3.36 3.39 3.42 3.45 3.48 3.50 3.52 3.54
5 500 3.15 3.22 3.28 3.33 3.38 3.43 3.47 3.51 3.55 3.58 3.61 3.64 3.67 3.70
5 1000 3.18 3.24 3.30 3.36 3.41 3.46 3.51 3.55 3.59 3.63 3.66 3.70 3.73 3.75
5 10000 3.20 3.27 3.33 3.39 3.45 3.50 3.54 3.59 3.63 3.67 3.71 3.74 3.78 3.81

10 5 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94
10 10 2.50 2.50 2.51 2.51 2.51 2.52 2.52 2.52 2.52 2.52 2.52 2.52 2.52 2.52
10 20 3.09 3.12 3.14 3.15 3.16 3.17 3.18 3.19 3.19 3.20 3.20 3.20 3.21 3.21
10 50 3.77 3.84 3.89 3.94 3.99 4.02 4.06 4.09 4.11 4.13 4.15 4.17 4.18 4.19
10 100 4.12 4.21 4.30 4.38 4.45 4.52 4.58 4.63 4.68 4.72 4.76 4.80 4.83 4.86
10 200 4.33 4.45 4.56 4.66 4.76 4.84 4.92 5.00 5.07 5.13 5.19 5.25 5.30 5.35
10 500 4.47 4.61 4.74 4.86 4.97 5.08 5.18 5.27 5.36 5.44 5.52 5.60 5.67 5.73
10 1000 4.52 4.66 4.80 4.93 5.05 5.16 5.27 5.37 5.47 5.56 5.65 5.73 5.81 5.88
10 10000 4.57 4.72 4.86 4.99 5.12 5.24 5.36 5.47 5.57 5.67 5.76 5.86 5.94 6.03

20 5 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10
20 10 2.79 2.80 2.80 2.81 2.81 2.81 2.82 2.82 2.82 2.82 2.82 2.82 2.82 2.82
20 20 3.58 3.62 3.64 3.66 3.68 3.69 3.71 3.71 3.72 3.73 3.73 3.74 3.74 3.74
20 50 4.56 4.65 4.74 4.82 4.88 4.94 4.99 5.03 5.07 5.11 5.14 5.16 5.18 5.20
20 100 5.08 5.24 5.38 5.51 5.62 5.73 5.83 5.91 5.99 6.07 6.13 6.20 6.25 6.30
20 200 5.42 5.61 5.80 5.97 6.13 6.28 6.42 6.55 6.67 6.79 6.90 7.00 7.09 7.18
20 500 5.65 5.88 6.09 6.30 6.50 6.69 6.87 7.04 7.20 7.36 7.51 7.65 7.78 7.91
20 1000 5.73 5.97 6.20 6.42 6.64 6.84 7.03 7.22 7.40 7.58 7.74 7.90 8.06 8.21
20 10000 5.81 6.06 6.30 6.54 6.77 6.98 7.20 7.40 7.60 7.79 7.97 8.15 8.33 8.50

50 5 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21
50 10 3.00 3.01 3.02 3.02 3.03 3.03 3.03 3.03 3.03 3.04 3.04 3.04 3.04 3.04
50 20 3.96 4.00 4.03 4.06 4.08 4.10 4.11 4.12 4.13 4.14 4.14 4.15 4.15 4.16
50 50 5.20 5.33 5.45 5.55 5.64 5.72 5.79 5.85 5.90 5.95 5.99 6.03 6.06 6.08
50 100 5.92 6.13 6.33 6.51 6.67 6.83 6.97 7.10 7.21 7.32 7.42 7.51 7.59 7.67
50 200 6.39 6.66 6.93 7.18 7.41 7.64 7.85 8.05 8.24 8.42 8.59 8.75 8.90 9.04
50 500 6.71 7.04 7.36 7.67 7.97 8.26 8.54 8.81 9.07 9.32 9.57 9.80 10.03 10.25
50 1000 6.83 7.18 7.52 7.85 8.18 8.50 8.80 9.10 9.40 9.68 9.96 10.23 10.50 10.75
50 10000 6.94 7.31 7.68 8.03 8.38 8.72 9.06 9.39 9.72 10.04 10.35 10.66 10.97 11.27

100 5 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25
100 10 3.08 3.09 3.10 3.10 3.11 3.11 3.11 3.11 3.11 3.12 3.12 3.12 3.12 3.12
100 20 4.10 4.14 4.18 4.21 4.23 4.25 4.27 4.28 4.29 4.30 4.30 4.31 4.31 4.31
100 50 5.46 5.61 5.74 5.85 5.95 6.04 6.12 6.19 6.24 6.30 6.34 6.38 6.42 6.45
100 100 6.26 6.50 6.72 6.93 7.12 7.29 7.45 7.60 7.74 7.86 7.98 8.08 8.18 8.27
100 200 6.79 7.10 7.41 7.69 7.97 8.23 8.48 8.72 8.94 9.15 9.35 9.54 9.72 9.89
100 500 7.16 7.54 7.91 8.27 8.62 8.96 9.29 9.62 9.93 10.24 10.53 10.82 11.10 11.37
100 1000 7.30 7.70 8.10 8.49 8.87 9.24 9.61 9.97 10.33 10.67 11.01 11.35 11.68 12.00
100 10000 7.43 7.85 8.28 8.69 9.11 9.51 9.92 10.32 10.72 11.11 11.50 11.88 12.27 12.64

1000 5 2.28 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
1000 10 3.15 3.16 3.17 3.18 3.18 3.18 3.19 3.19 3.19 3.19 3.19 3.19 3.19 3.19
1000 20 4.24 4.29 4.32 4.36 4.38 4.40 4.42 4.43 4.44 4.45 4.46 4.46 4.47 4.47
1000 50 5.72 5.88 6.02 6.15 6.26 6.36 6.44 6.52 6.59 6.65 6.70 6.74 6.78 6.81
1000 100 6.61 6.87 7.12 7.35 7.57 7.77 7.95 8.12 8.28 8.43 8.56 8.68 8.79 8.89
1000 200 7.20 7.56 7.90 8.23 8.55 8.85 9.14 9.41 9.68 9.93 10.17 10.39 10.61 10.81
1000 500 7.62 8.05 8.48 8.89 9.30 9.70 10.10 10.48 10.86 11.22 11.58 11.93 12.27 12.61
1000 1000 7.78 8.24 8.69 9.15 9.59 10.04 10.47 10.91 11.33 11.75 12.17 12.58 12.99 13.39
1000 10000 7.92 8.41 8.90 9.39 9.87 10.36 10.84 11.33 11.81 12.29 12.77 13.25 13.73 14.20

10000 5 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
10000 10 3.16 3.17 3.18 3.19 3.19 3.19 3.19 3.20 3.20 3.20 3.20 3.20 3.20 3.20
10000 20 4.25 4.30 4.34 4.37 4.40 4.42 4.43 4.45 4.46 4.46 4.47 4.48 4.48 4.48
10000 50 5.75 5.91 6.05 6.18 6.29 6.39 6.48 6.56 6.62 6.68 6.73 6.78 6.82 6.85
10000 100 6.64 6.91 7.17 7.40 7.62 7.82 8.01 8.18 8.34 8.49 8.62 8.74 8.86 8.96
10000 200 7.24 7.60 7.95 8.29 8.61 8.92 9.21 9.49 9.76 10.01 10.26 10.49 10.71 10.91
10000 500 7.67 8.11 8.54 8.96 9.38 9.78 10.18 10.57 10.96 11.33 11.70 12.06 12.41 12.75
10000 1000 7.83 8.30 8.76 9.22 9.67 10.12 10.57 11.01 11.44 11.88 12.30 12.72 13.14 13.55
10000 10000 7.98 8.47 8.97 9.46 9.96 10.45 10.94 11.44 11.93 12.42 12.91 13.40 13.89 14.38

5-10
National Frame Builders Association Post-Frame Building Design Manual

Table 5.2. Sidesway Restraining Force Modifier (mD)


Number of frames (endwalls counted as frames)
ke / k Ch / k
3 4 5 6 7 8 9 10 11 12 13 14 15 16

5 5 0.75 0.64 0.52 0.43 0.34 0.28 0.22 0.18 0.14 0.12 0.09 0.08 0.06 0.05
5 10 0.78 0.69 0.59 0.52 0.44 0.39 0.33 0.28 0.24 0.21 0.18 0.15 0.13 0.11
5 20 0.80 0.72 0.64 0.58 0.51 0.46 0.41 0.37 0.33 0.30 0.26 0.24 0.21 0.19
5 50 0.81 0.74 0.67 0.62 0.56 0.52 0.48 0.44 0.41 0.38 0.35 0.32 0.30 0.28
5 100 0.81 0.74 0.68 0.63 0.58 0.54 0.50 0.47 0.44 0.41 0.38 0.36 0.34 0.32
5 200 0.82 0.75 0.69 0.64 0.59 0.55 0.52 0.48 0.46 0.43 0.41 0.38 0.36 0.35
5 500 0.82 0.75 0.69 0.64 0.60 0.56 0.52 0.49 0.47 0.44 0.42 0.40 0.38 0.36
5 1000 0.82 0.75 0.69 0.64 0.60 0.56 0.53 0.50 0.47 0.45 0.42 0.40 0.39 0.37
5 10000 0.82 0.75 0.69 0.64 0.60 0.56 0.53 0.50 0.47 0.45 0.43 0.41 0.39 0.37

10 5 0.83 0.73 0.60 0.51 0.41 0.34 0.27 0.22 0.17 0.14 0.11 0.09 0.07 0.06
10 10 0.86 0.79 0.70 0.63 0.54 0.48 0.41 0.36 0.30 0.26 0.22 0.19 0.16 0.14
10 20 0.88 0.83 0.76 0.70 0.64 0.58 0.52 0.48 0.43 0.39 0.35 0.31 0.28 0.25
10 50 0.90 0.85 0.80 0.75 0.71 0.66 0.62 0.58 0.55 0.51 0.48 0.45 0.42 0.39
10 100 0.90 0.86 0.81 0.77 0.73 0.70 0.66 0.63 0.60 0.57 0.54 0.51 0.49 0.46
10 200 0.90 0.86 0.82 0.78 0.75 0.71 0.68 0.65 0.63 0.60 0.57 0.55 0.53 0.51
10 500 0.90 0.86 0.82 0.79 0.75 0.72 0.70 0.67 0.64 0.62 0.60 0.58 0.56 0.54
10 1000 0.90 0.86 0.83 0.79 0.76 0.73 0.70 0.67 0.65 0.63 0.61 0.59 0.57 0.55
10 10000 0.91 0.86 0.83 0.79 0.76 0.73 0.70 0.68 0.66 0.63 0.61 0.59 0.58 0.56

20 5 0.87 0.78 0.65 0.56 0.45 0.38 0.30 0.25 0.19 0.16 0.13 0.10 0.08 0.07
20 10 0.91 0.85 0.76 0.69 0.60 0.54 0.46 0.41 0.35 0.30 0.26 0.22 0.19 0.16
20 20 0.93 0.89 0.83 0.78 0.72 0.66 0.60 0.55 0.50 0.46 0.41 0.37 0.33 0.30
20 50 0.94 0.91 0.87 0.84 0.80 0.76 0.72 0.69 0.65 0.62 0.58 0.55 0.51 0.48
20 100 0.95 0.92 0.89 0.86 0.83 0.80 0.77 0.75 0.72 0.69 0.66 0.64 0.61 0.58
20 200 0.95 0.92 0.90 0.87 0.85 0.83 0.80 0.78 0.76 0.73 0.71 0.69 0.67 0.65
20 500 0.95 0.93 0.90 0.88 0.86 0.84 0.82 0.80 0.78 0.76 0.74 0.72 0.71 0.69
20 1000 0.95 0.93 0.91 0.88 0.86 0.84 0.82 0.81 0.79 0.77 0.75 0.74 0.72 0.71
20 10000 0.95 0.93 0.91 0.89 0.87 0.85 0.83 0.81 0.80 0.78 0.76 0.75 0.73 0.72

50 5 0.89 0.81 0.68 0.59 0.48 0.40 0.32 0.26 0.21 0.17 0.13 0.11 0.09 0.07
50 10 0.93 0.88 0.80 0.73 0.65 0.58 0.50 0.44 0.38 0.33 0.28 0.24 0.21 0.18
50 20 0.96 0.93 0.88 0.83 0.77 0.72 0.66 0.61 0.55 0.51 0.46 0.41 0.37 0.34
50 50 0.97 0.95 0.93 0.90 0.87 0.84 0.80 0.77 0.73 0.70 0.66 0.63 0.59 0.56
50 100 0.98 0.96 0.94 0.93 0.90 0.88 0.86 0.84 0.81 0.79 0.76 0.74 0.71 0.69
50 200 0.98 0.97 0.95 0.94 0.92 0.91 0.89 0.88 0.86 0.84 0.82 0.81 0.79 0.77
50 500 0.98 0.97 0.96 0.95 0.94 0.92 0.91 0.90 0.89 0.88 0.86 0.85 0.84 0.83
50 1000 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.86 0.85
50 10000 0.98 0.97 0.96 0.95 0.94 0.93 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.87

100 5 0.90 0.82 0.69 0.60 0.48 0.41 0.32 0.27 0.21 0.17 0.14 0.11 0.09 0.07
100 10 0.94 0.90 0.82 0.75 0.66 0.59 0.51 0.45 0.39 0.34 0.29 0.25 0.21 0.18
100 20 0.97 0.94 0.89 0.85 0.79 0.74 0.68 0.63 0.57 0.52 0.47 0.43 0.39 0.35
100 50 0.98 0.97 0.94 0.92 0.89 0.86 0.83 0.80 0.76 0.73 0.69 0.66 0.62 0.59
100 100 0.99 0.98 0.96 0.95 0.93 0.91 0.89 0.87 0.85 0.83 0.80 0.78 0.75 0.73
100 200 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.91 0.90 0.88 0.87 0.85 0.84 0.82
100 500 0.99 0.98 0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88
100 1000 0.99 0.98 0.98 0.97 0.97 0.96 0.95 0.95 0.94 0.93 0.93 0.92 0.91 0.91
100 10000 0.99 0.99 0.98 0.98 0.97 0.97 0.96 0.96 0.95 0.95 0.94 0.94 0.93 0.93

1000 5 0.91 0.83 0.70 0.61 0.49 0.41 0.33 0.27 0.22 0.18 0.14 0.11 0.09 0.07
1000 10 0.95 0.91 0.83 0.76 0.67 0.60 0.52 0.46 0.40 0.35 0.30 0.26 0.22 0.19
1000 20 0.98 0.95 0.91 0.87 0.81 0.76 0.70 0.65 0.59 0.54 0.49 0.45 0.40 0.36
1000 50 0.99 0.98 0.96 0.94 0.91 0.89 0.86 0.83 0.79 0.76 0.72 0.69 0.65 0.62
1000 100 0.99 0.99 0.98 0.97 0.95 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.79 0.77
1000 200 1.00 0.99 0.99 0.98 0.98 0.97 0.96 0.95 0.94 0.93 0.91 0.90 0.88 0.87
1000 500 1.00 1.00 0.99 0.99 0.99 0.99 0.98 0.98 0.97 0.97 0.96 0.95 0.95 0.94
1000 1000 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.98 0.98 0.98 0.97 0.97 0.97
1000 10000 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.99

10000 5 0.91 0.83 0.70 0.61 0.49 0.42 0.33 0.27 0.22 0.18 0.14 0.11 0.09 0.07
10000 10 0.95 0.91 0.83 0.76 0.68 0.61 0.53 0.46 0.40 0.35 0.30 0.26 0.22 0.19
10000 20 0.98 0.95 0.91 0.87 0.81 0.76 0.70 0.65 0.59 0.54 0.49 0.45 0.40 0.37
10000 50 0.99 0.98 0.96 0.94 0.92 0.89 0.86 0.83 0.79 0.76 0.72 0.69 0.65 0.62
10000 100 1.00 0.99 0.98 0.97 0.96 0.94 0.93 0.91 0.89 0.87 0.84 0.82 0.80 0.77
10000 200 1.00 1.00 0.99 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.90 0.89 0.87
10000 500 1.00 1.00 1.00 0.99 0.99 0.99 0.98 0.98 0.98 0.97 0.96 0.96 0.95 0.95
10000 1000 1.00 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.98 0.98 0.98 0.97
10000 10000 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00

5-11
National Frame Builders Association Post-Frame Building Design Manual

Table 5.2. Sidesway Restraining Force Modifier (mD), cont.


Number of frames (endwalls counted as frames)
ke / k Ch / k
17 18 19 20 21 22 23 24 25 26 27 28 29 30

5 5 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00 0.00 0.00
5 10 0.09 0.08 0.07 0.06 0.05 0.04 0.04 0.03 0.03 0.02 0.02 0.02 0.01 0.01
5 20 0.17 0.15 0.13 0.12 0.11 0.10 0.09 0.08 0.07 0.06 0.06 0.05 0.04 0.04
5 50 0.26 0.24 0.22 0.21 0.19 0.18 0.17 0.16 0.14 0.13 0.12 0.12 0.11 0.10
5 100 0.30 0.29 0.27 0.26 0.24 0.23 0.22 0.20 0.19 0.18 0.17 0.17 0.16 0.15
5 200 0.33 0.31 0.30 0.29 0.27 0.26 0.25 0.24 0.23 0.22 0.21 0.20 0.19 0.19
5 500 0.35 0.33 0.32 0.31 0.29 0.28 0.27 0.26 0.25 0.25 0.24 0.23 0.22 0.21
5 1000 0.35 0.34 0.33 0.31 0.30 0.29 0.28 0.27 0.26 0.25 0.25 0.24 0.23 0.23
5 10000 0.36 0.35 0.33 0.32 0.31 0.30 0.29 0.28 0.27 0.26 0.26 0.25 0.24 0.24

10 5 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00 0.00
10 10 0.12 0.10 0.09 0.08 0.06 0.06 0.05 0.04 0.03 0.03 0.03 0.02 0.02 0.02
10 20 0.23 0.20 0.18 0.16 0.15 0.13 0.12 0.11 0.09 0.08 0.08 0.07 0.06 0.05
10 50 0.36 0.34 0.32 0.30 0.28 0.26 0.24 0.23 0.21 0.20 0.18 0.17 0.16 0.15
10 100 0.44 0.42 0.40 0.38 0.36 0.34 0.33 0.31 0.29 0.28 0.27 0.25 0.24 0.23
10 200 0.49 0.47 0.45 0.43 0.42 0.40 0.39 0.37 0.36 0.34 0.33 0.32 0.31 0.30
10 500 0.52 0.50 0.49 0.47 0.46 0.44 0.43 0.42 0.40 0.39 0.38 0.37 0.36 0.35
10 1000 0.53 0.52 0.50 0.49 0.47 0.46 0.45 0.43 0.42 0.41 0.40 0.39 0.38 0.37
10 10000 0.54 0.53 0.51 0.50 0.49 0.47 0.46 0.45 0.44 0.43 0.42 0.41 0.40 0.39

20 5 0.05 0.04 0.03 0.03 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.01 0.00 0.00
20 10 0.14 0.12 0.10 0.09 0.07 0.06 0.05 0.05 0.04 0.03 0.03 0.03 0.02 0.02
20 20 0.27 0.24 0.22 0.20 0.17 0.16 0.14 0.13 0.11 0.10 0.09 0.08 0.07 0.06
20 50 0.45 0.42 0.40 0.37 0.35 0.33 0.30 0.28 0.27 0.25 0.23 0.22 0.20 0.19
20 100 0.56 0.53 0.51 0.49 0.47 0.45 0.43 0.41 0.39 0.37 0.35 0.34 0.32 0.31
20 200 0.63 0.61 0.59 0.57 0.55 0.53 0.52 0.50 0.48 0.47 0.45 0.44 0.42 0.41
20 500 0.67 0.66 0.64 0.63 0.61 0.60 0.59 0.57 0.56 0.55 0.53 0.52 0.51 0.50
20 1000 0.69 0.68 0.66 0.65 0.64 0.62 0.61 0.60 0.59 0.58 0.57 0.55 0.54 0.53
20 10000 0.71 0.69 0.68 0.67 0.66 0.65 0.64 0.63 0.62 0.61 0.60 0.59 0.58 0.57

50 5 0.06 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00
50 10 0.15 0.13 0.11 0.10 0.08 0.07 0.06 0.05 0.04 0.04 0.03 0.03 0.02 0.02
50 20 0.30 0.27 0.24 0.22 0.20 0.18 0.16 0.14 0.13 0.11 0.10 0.09 0.08 0.07
50 50 0.52 0.49 0.46 0.44 0.41 0.38 0.36 0.34 0.31 0.29 0.27 0.26 0.24 0.22
50 100 0.66 0.64 0.61 0.59 0.56 0.54 0.52 0.50 0.47 0.45 0.43 0.41 0.40 0.38
50 200 0.75 0.73 0.71 0.69 0.68 0.66 0.64 0.62 0.60 0.59 0.57 0.55 0.54 0.52
50 500 0.81 0.80 0.79 0.78 0.76 0.75 0.74 0.73 0.71 0.70 0.69 0.68 0.67 0.65
50 1000 0.84 0.83 0.82 0.81 0.80 0.79 0.78 0.77 0.76 0.75 0.74 0.73 0.72 0.71
50 10000 0.86 0.85 0.84 0.84 0.83 0.82 0.81 0.81 0.80 0.79 0.79 0.78 0.77 0.77

100 5 0.06 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00
100 10 0.16 0.13 0.11 0.10 0.08 0.07 0.06 0.05 0.04 0.04 0.03 0.03 0.02 0.02
100 20 0.31 0.28 0.25 0.23 0.20 0.18 0.16 0.15 0.13 0.12 0.11 0.09 0.08 0.08
100 50 0.55 0.52 0.49 0.46 0.43 0.41 0.38 0.36 0.33 0.31 0.29 0.27 0.25 0.24
100 100 0.70 0.68 0.65 0.63 0.60 0.58 0.56 0.53 0.51 0.49 0.47 0.45 0.43 0.41
100 200 0.80 0.78 0.77 0.75 0.73 0.71 0.69 0.68 0.66 0.64 0.62 0.61 0.59 0.57
100 500 0.87 0.86 0.85 0.84 0.83 0.82 0.81 0.80 0.79 0.77 0.76 0.75 0.74 0.73
100 1000 0.90 0.89 0.88 0.88 0.87 0.86 0.85 0.84 0.84 0.83 0.82 0.81 0.80 0.80
100 10000 0.92 0.92 0.91 0.91 0.90 0.90 0.90 0.89 0.89 0.88 0.88 0.87 0.87 0.86

1000 5 0.06 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00
1000 10 0.16 0.14 0.12 0.10 0.09 0.07 0.06 0.05 0.05 0.04 0.03 0.03 0.02 0.02
1000 20 0.33 0.29 0.26 0.24 0.21 0.19 0.17 0.15 0.14 0.12 0.11 0.10 0.09 0.08
1000 50 0.58 0.55 0.52 0.49 0.46 0.43 0.40 0.38 0.35 0.33 0.31 0.29 0.27 0.25
1000 100 0.74 0.72 0.69 0.67 0.64 0.62 0.60 0.57 0.55 0.53 0.50 0.48 0.46 0.44
1000 200 0.85 0.84 0.82 0.80 0.79 0.77 0.75 0.74 0.72 0.70 0.68 0.66 0.65 0.63
1000 500 0.93 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.83 0.82 0.81
1000 1000 0.96 0.96 0.95 0.95 0.94 0.94 0.93 0.93 0.92 0.92 0.91 0.90 0.90 0.89
1000 10000 0.99 0.99 0.99 0.99 0.99 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98

10000 5 0.06 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00
10000 10 0.16 0.14 0.12 0.10 0.09 0.07 0.06 0.05 0.05 0.04 0.03 0.03 0.02 0.02
10000 20 0.33 0.30 0.26 0.24 0.21 0.19 0.17 0.15 0.14 0.12 0.11 0.10 0.09 0.08
10000 50 0.58 0.55 0.52 0.49 0.46 0.43 0.40 0.38 0.36 0.33 0.31 0.29 0.27 0.25
10000 100 0.75 0.72 0.70 0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.51 0.49 0.47 0.45
10000 200 0.86 0.84 0.83 0.81 0.79 0.78 0.76 0.74 0.72 0.71 0.69 0.67 0.65 0.64
10000 500 0.94 0.93 0.92 0.92 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.83 0.82
10000 1000 0.97 0.96 0.96 0.96 0.95 0.95 0.94 0.94 0.93 0.93 0.92 0.91 0.91 0.90
10000 10000 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99

5-12
National Frame Builders Association Post-Frame Building Design Manual

FRAME FRAME APPLIED HORIZONTAL LOAD RESISTED FRACTION OF


NUMBER STIFFNESS LOAD DISPLACEMENT BY FRAME APPLIED LOAD
---------------------------------------------------------------------
1 10000.00 500.0 .1946696 1946.7 3.8934
2 100.00 1000.0 .3393392 33.9 .0339
3 100.00 1000.0 .3874022 38.7 .0387
4 100.00 1000.0 .3393392 33.9 .0339
5 10000.00 500.0 .1946696 1946.7 3.8934

DIAPHRAGM DIAPHRAGM SHEAR SHEAR


NUMBER STIFFNESS DISPLACEMENT LOAD
--------------------------------------------
1 10000.00 .1446696 1446.7
2 10000.00 .0480630 480.6
3 10000.00 .0480630 480.6
4 10000.00 .1446696 1446.7

Figure 5.9. Sample output from computer program DAFI.

When requirements for use of tables 5.1 and 5.2 Qp,i = Q i / (cos θ i)
are met, equation 5-8 can be used to calculate
the total sidesway resisting force, Q. In all other or
cases, analysis tools such as DAFI must be
used to obtain Q. A copy of output from program q p,i = Q i / (d i cos θ i) (5-11)
DAFI for a 4-bay building with Ch fixed at 10000,
ke at 10000, k at 100, and R at 1000 is shown in where:
figure 5.9. Although the sidesway resisting force
for each frame is not given in the DAFI output, it Q pi = in-plane force applied to frame by
is numerically equal to the difference between diaphragm i, lbf (N)
the load applied to the frame, and the load re- Qi = sidesway resisting force due to dia-
sisted by the frame – two values that are listed phragm i, lbf (N)
in the program’s output. For example, Q for the θi = slope of diaphragm i
critical middle frame (frame 3 in figure 5.9), q p,i = in-plane force applied to the frame
would be equal to the difference between per unit length of diaphragm i, lbf/ft
1000.0 and 38.7 or 961.3. (N/m)
di = slope length of diaphragm i, ft (m)
Since diaphragm construction typically doesn‘t
change from one side of a frame to the other 5.6.6 Simple Beam Analogy Equations.
side of the frame, Ch and ch,i values associated McGuire (1998) presented the concept of mod-
with either of the two diaphragm elements (that eling the diaphragm as a simple beam with an
are adjacent to the frame) can be used in equa- applied load inversely proportional to deflection.
tion 5-9. This analogy resulted in the following equations
for calculating diaphragm shear forces and lat-
Horizontal restraining forces calculated for the eral displacements for the special case when:
three diaphragms in figure 5.2b, are graphically (1) all diaphragm elements have the same stiff-
illustrated in figure 5.10a. For post-frame com- ness Ch, (2) all interior frame elements have the
ponent stress analysis, these restraining forces same stiffness, k, (3) both exterior frame ele-
should be applied as in-plane forces as shown ments (i.e., the two elements representing the
in figure 10b. In-plane forces are calculated from endwalls) have the same stiffness, ke, and (4)
the horizontal forces as follows: eave load, R, is the same at each interior frame.

5-13
National Frame Builders Association Post-Frame Building Design Manual

s = frame spacing, in. (mm)


Roof Gravity Loads y = lateral displacement of diaphragm at
a distance x from the endwall, in.
(mm)
ye = lateral displacement of the endwall,
s x qwr s x qlr in. (mm)
k = stiffness of interior frames, lbf/in.
Qa Qb (N/mm)
Qc ke = stiffness of endwall frames (or
shearwalls), lbf/in. (N/mm)
Ch = horizontal shear stiffness for a width
Ceiling Gravity Loads s of the diaphragm, lbf/in. (N/mm)
s xqww

s xqlw
L = Distance between endwalls, in.
(mm)
sinh = hyperbolic sine
cosh = hyperbolic cosine
(a)
( k / Ch )1/2
α =
Roof Gravity Loads s

A = ye – R/k
s x qwr s x qlr
A ( 1 – cosh(α L))
B =
sinh(α L)
q p,a q p,b
q p,c
ke sinh(α L)
D =
α Ch s (1 - cosh(α L))

Ceiling Gravity Loads


s xqww

5.7 Component Design


s xqlw

5.7.1 General. All building components must be


checked to ensure that actual loads do not ex-
(b) ceed allowable design values. In this section,
special attention is given to components that are
Figure 5.10 (a) Frame with diaphragm resisting involved in load transfer by diaphragm action.
forces. (b) Resisting forces applied as uniformly
distributed in-plane loads for frame component 5.7.2 Diaphragms. The maximum shear in a
stress analysis. diaphragm section, Vp,i, cannot exceed the al-
lowable shear strength of the section, va,i, multi-
plied by the diaphragm length.
Vh = Chαs[A sinh(α x) + B cosh(α x)] (5-12)
Vp,i < va,i d i (5-15)
y = A cosh(α x) + B sinh(α x) + R/k (5-13)
where:
ye = R / [ k (1 – D)] (5-14)
Vp,i = in-plane shear force in diaphragm
where: section i from equation 5-9 lbf (N)
va,i = allowable in-plane shear strength of
Vh = diaphragm shear force, lbf (N) diaphragm i (see Section 6.3.3),
x = distance from endwall, in. (mm) lbf/ft (N/m)
R = eave load, lbf (N) di = slope length of diaphragm i, ft (m)

5-14
National Frame Builders Association Post-Frame Building Design Manual

5.7.3 Diaphragm Chords. In addition to shear The bending moment applied to a roof/ceiling
forces, a roof/ceiling diaphragm assembly must diaphragm assembly is resisted by axial forces
also resist bending moment. The magnitude of (a.k.a. chord forces) in members orientated per-
this bending moment is dependent on a number pendicular to trusses/rafters. This includes roof
of factors. For design, this bending moment is purlins and analogous framing members in the
assumed to be no greater than: ceiling diaphragm. For bending moment calcula-
tions, these members are referred to as dia-
Md = Vh L / 4 (5-16) phragm chords (figure 5.11a). Any connection in
the chords, either between intermediate chord
where: members or where they are connected to the
endwalls, must be designed to resist the calcu-
Md = diaphragm bending moment, lbf-ft lated axial force.
(N m)
Vh = maximum total shear in roof/ceiling If the roof/ceiling assembly behaves as a single
diaphragm assembly, lbf (N) beam in resisting bending moment, the maxi-
L = distance between shearwalls, ft (m) mum chord force (which is located in the edge
chords) can be calculated as:
Equation 5-16 treats the roof/ceiling assembly
as a uniformly loaded beam that is simple sup- Pe = Md α / b (5-17)
ported by two shearwalls spaced a distance L
apart. Each shearwall is assumed to be sub- where:
jected to a force that is equal to the maximum
total shear in the roof/ceiling assembly, Vh. The Pe = axial force in edge chord, lbf (N)
maximum total shear in the roof/ceiling assem- Md = diaphragm bending moment from
bly, Vh, can be obtained from computer output equation 5-16, lbf-ft (N m)
(e.g. figure 5.9), or equation 5-7 or 5-12 if appli- α = reduction factor dependent on chord
cable. The uniform load on the roof/ceiling as- force distribution
sembly (w in figure 5.11a) is set equal to 2Vh/L. b = horizontal distance between edge
This quantity is multiplied by L2/8 to obtain Md. chords, ft (m)

Vh Vh

Shearwall Chords Trusses/rafters


(b) (c) (d)
(a)

Figure 5.11. (a) Plan view of a diaphragm under a uniform load, w. Chord force distribu-
tions when (b) moment resisted by edge chords only, (b) chord force distribution is linear,
and (c) chord force distribution is linear, but diaphragm halves assumed to act independ-
ently in resisting moment.

5-15
National Frame Builders Association Post-Frame Building Design Manual

The axial force in an edge chord is dependent


on chord force distribution as indicated by the Table 5.3. Reduction Factor, α, for Axial
presence of α in equation 5-17. The current Force in Edge Chords
ASAE EP484 diaphragm design procedure n* α n* α
(ASAE, 1999a) assumes that edge chords act 2 1.000 22 0.249
alone in resisting bending moment (figure 3 1.000 23 0.239
5.11b). For this case, α is numerically equal to 4 0.900 24 0.230
one (1). This is a conservative approach. Alter- 5 0.800 25 0.222
natively, many engineers assume a linear distri- 6 0.714 26 0.214
bution of chord forces as shown in figure 5.11c. 7 0.643 27 0.206
When a linear distribution is assumed, the re- 8 0.583 28 0.200
duction factor α is a function of chord location. If 9 0.533 29 0.193
chords are evenly spaced, then α is given as: 10 0.491 30 0.187
11 0.455 31 0.181
(n – 1 )2
α= n/2 when n is even 12 0.423 32 0.176
Σ (n – 2 i + 1)2 13 0.396 33 0.171
i =1 14 0.371 34 0.166
15 0.350 35 0.162
(n – 1 )2 16 0.335 36 0.158
α= (n-1)/2 when n is odd 17 0.314 37 0.154
Σ (n – 2 i + 1)2 18 0.298 38 0.150
i =1
19 0.284 39 0.146
20 0.271 40 0.143
where:
21 0.260 41 0.139
* n is the number of chord rows, including the
α = reduction factor when chords are
two rows of edge chords
evenly spaced and chord forces are
linearly distributed
n = number of chord rows, including the
two rows of edge chords
Technical Note
The preceding equations were used to calculate Chord Forces
the values given in table 5.3.
The axial force induced in an individual chord by
If a linear distribution of chord force is assumed applied building loads is a function of many
(figure 5.11c), and interior chords are evenly complex, interacting design variables. For this
spaced, the load in an interior chord, Pi, is given reason, designers have had to rely on simplify-
as: ing assumptions in order to approximate chord
forces.
Pi = 2 Pe x i / b (5-18)
One common assumption is that the roof/ceiling
where: assembly acts as a large deep beam that is
simply supported by two end shearwalls. This
Pi = axial force for chord in row i, lbf (N) assumption is used to calculate the maximum in-
Pe = axial force in edge chord from equa- plane bending moment to which a diaphragm is
tion 5-17, lbf (N) subjected. This assumption is conservative in
b = horizontal distance between edge that it neglects the resistance to in-plane bend-
chords, ft (m) ing contributed by sidewalls. Sidewalls help re-
xi = horizontal distance from center of sist (and thereby reduce) in-plane bending mo-
diaphragm to chord row i. ments in two ways. First they brace endwalls

5-16
National Frame Builders Association Post-Frame Building Design Manual

and other shearwalls, which limits rotation of the moment in their models was resisted almost en-
diaphragm at these shearwalls. Second, they tirely by the edge purlins. Bohnhoff and others
resist a change in eave length (and hence (1999) showed that as the shear stiffness of
changes in eave chord forces) by virtue of their cladding is increased, interior purlins get more
own in-plane shear stiffness. involved in resisting in-plane bending moments.

Because of the influence of sidewalls, the distri- Chord force distribution has also been shown to
bution of in-plane bending moment will not follow depend on the degree of interaction between
that for a typical simple supported beam (i.e., individual diaphragms. Figure 5.11d illustrates
zero moment at the supports, and maximum the distribution of chord forces when there is no
moment at midspan). For this reason, Pollock interaction between individual diaphragms on
and others (1996) recommend modeling the both sides of a ridge. Note that interaction be-
roof/ceiling assembly as a deep beam with fixed tween individual diaphragms on opposites sides
supports. of a ridge is highly dependent on: (1) the spac-
ing between ridge purlins, and (2) the rigidity of
Because of uncertainty surrounding variation in the ridge cap and other elements joining the two
in-plane bending moment with building length, diaphragms.
some designers will assign the maximum calcu-
lated in-plane bending moment (Md from equa-
tion 5-16) to every location along the length of
the building. This is obviously a conservative 5.7.4 Shearwalls. End and intermediate shear-
approach. walls must have sufficient strength to transmit
forces from roof and ceiling diaphragms to the
Another major assumption that a designer must foundation system. In equation form:
make involves the distribution of chord forces
across a building. Three different chord force va > Vs / (W – DT) (5-19)
distributions are shown in figure 5.11b, 5.11c,
and 5.11d. Whether or not edge chords resist where:
virtually all of the in-plane bending moment (fig-
ure 5.11b), or a linear distribution of axial forces va = allowable shear capacity of shear-
exists in chords between edge chords (figure wall, lbf/ft (N/m)
5.11c) is a question that is at the heart of ongo- Vs = force induced in shearwall, lbf (N)
ing research. In reality, the distribution of chord W = building width, ft (m)
forces lies somewhere in between these two DT = total width of door and window
extremes, exactly where being dependent on openings in the shearwall, ft (m)
specifics of the design and on the magnitude of
the applied load (Note: at higher load levels, The allowable shear capacity of end and inter-
load distributions change due to geometric and mediate shearwalls, va, is obtained from vali-
material nonlinearities). Presently, there is very dated structural models, or from tests as out-
little research data to support one specific de- lined in ASAE EP558 (see Section 6.5). The
sign procedure/assumption. The most extensive total force in the shear wall, Vs, is obtained from
investigation of chord forces was by Niu and computer output (e.g. figure 5.8), or equation 5-
Gebremedhin (1997) who strain gauged purlins 7 or equation 5-12 if applicable.
in a full-scale building and in a diaphragm test
assembly. The data collected in this study does The total width of door and window openings,
not strongly support any particular hypotheses DT, generally varies with height as shown in fig-
regarding chord force distribution. The only ure 5.12. At locations where DT is the greatest
other research of significance to chord force dis- (section b-b in figure 5.12) additional reinforcing
tribution was the comprehensive finite element may be required to ensure that the allowable
analyses of diaphragm assemblies by Wright shear stress is not exceeded.
(1992) and Williams (1999). Both of these re-
searchers found that in-plane bending The structural framing over a door or window
opening will act as a drag strut transferring

5-17
National Frame Builders Association Post-Frame Building Design Manual

shear across the opening. The header over the 5.7.6 Shearwall Overturning. Diaphragm load-
opening shall be designed to carry the force in ing produces overturning moment in shearwalls.
tension and/or compression across the opening. This moment induces vertical forces in shear-
wall-to-foundation connections that must be
added to vertical forces resulting from tributary
loads. In the case of embedded posts, increases
in uplift forces may require an increase in em-
bedment depth, and increases in downward
force may require an increase in footing size
(see Chapter 8).
a a
5.8 Rigid Roof Design
b b
5.8.1 General. When diaphragm stiffness is
considerably greater than the stiffness of interior
c W c post frames, the designer may want to assume
that the diaphragm and shearwalls are infinitely
Figure 5.12. Shearwall showing variations in stiff. Under this assumption, 100% of the applied
opening width, DT, with height. eave load, R, is transferred by the diaphragm to
shearwalls, and none of the applied eave load is
Shearwall strength can easily be increased resisted by the frames. Because all eave load is
when the applied load exceeds shearwall capac- assumed to be transferred to shearwalls, no
ity. For example, the density of stitch screws can special analysis tools or design tables are re-
be increased and additional fasteners can be quired to determine load distribution between
added in panel flats (on both sides of each ma- diaphragms and post-frames. This simplifies the
jor rib is the most effective). If only one side of entire diaphragm design process. This simplified
the wall has been sheathed, add wood paneling procedure is referred to as rigid roof design
or metal cladding to the other side. Metal diago- (Bender and others, 1991).
nal braces can also be added beneath any wood
paneling or corrugated metal siding. 5.8.2 Calculation. When (1) the shearwalls and
roof/ceiling diaphragm assembly are assumed to
5.7.5 Shearwall Connections. Connections be infinitely rigid, (2) the only applied loads with
that fasten (1) roof and ceiling diaphragms to a horizontal components are due to wind, and (3)
shearwall, and (2) shearwalls to the foundation wind pressure is uniformly distributed on each
system, must be designed to carry the appropri- wall and roof surface, then the maximum shear
ate amount of shear load. The design of these force in the diaphragm assembly is given as:
connections may be proved by tests of a typical
connection detail or by an appropriate calcula- Vh = L (hwr qwr – hlr qlr +
tion method. hww fw qww – hlw fl qlw) / 2 (5-20)

At end shearwalls it is not uncommon to use the where:


truss top chord to transfer load from roof clad-
ding to endwall cladding. Sidewall steel is fas- Vh = maximum diaphragm element shear
tened directly to the truss chord, as is the roof force, lbf (N)
steel when purlins are inset. In buildings with L = building length, ft (m)
top-running purlins, roof cladding can not be hwr = windward roof height, ft (m)
fastened directly to the truss. In such cases, hlr = leeward roof height, ft (m)
blocking equal in depth to the purlins is placed hww = windward wall height, ft (m)
between the purlins and fastened to the truss. hlw = leeward wall height, ft (m)
Roof cladding is then attached directly to this
blocking.

5-18
National Frame Builders Association Post-Frame Building Design Manual

qwr = design windward roof pressure, Output from a DAFI analysis of a building with
lbf/ft2 (N/m2) relatively high diaphragm and shearwall stiffness
qlr = design leeward roof pressure, lbf/ft2 values is presented in figure 5.9. This output
(N/m2) shows less than 3% of the total horizontal eave
qww = design windward wall pressure, load being resisted by the interior frames.
lbf/ft2 (N/m2)
qlw = design leeward wall pressure lbf/ft2 Although rigid roof design expedites calculation
(N/m2) of maximum diaphragm shear forces, the design
fw = frame-base fixity factor, windward procedure does not provide estimates of sides-
post way restraining force for interior post-frame de-
fl = frame-base fixity factor, leeward sign.
post
5.9 References
Inward acting wind pressures have positive
signs, outward acting pressures are negative
(figure 5.8). As previously noted, frame-base Anderson, G.A., D.S. Bundy and N.F. Meador.
fixity factors, fw and fl, determine how much of 1989. The force distribution method: procedure
the total wall load is transferred to the eave, and and application to the analysis of buildings with
how much is transferred directly to the ground. diaphragm action. Transactions of the ASAE
The greater the resistance to rotation at the 32(5):1781-1786.
base of a wall, the more load will be attracted
directly to the base of the wall. For substantial ASAE. 1999a. EP484.2 Diaphragm design of
fixity against rotation at the groundline, set the metal-clad wood-frame rectangular buildings.
frame-base fixity factor(s) equal to 3/8. For all ASAE Standards, 46th Ed., ASAE, St. Joseph,
other cases, set the frame-base fixity factor(s) MI.
equal to 1/2.
ASAE. 1999b. EP558.1 Load tests for metal-
For symmetrical base restraint and frame ge- clad wood-frame diaphragms. ASAE Standards,
ometry, equation 5-20 reduces to: 46th Ed., ASAE, St. Joseph, MI.

Vh = L [hr (qwr – qlr) + hw f (qww – qlw)] / 2 (5-21) Bender, D. A., T. D. Skaggs and F. E. Woeste.
1991. Rigid roof design for post-frame buildings.
where: Applied Engineering in Agriculture 7(6):755-760.

hr = roof height, ft (m) Bohnhoff, D. R., P. A. Boor, and G. A. Anderson.


hw = wall height, ft (m) 1999. Thoughts on metal-clad wood-frame dia-
f = frame-base fixity factor for both lee- phragm action and a full-scale building test.
ward and windward posts ASAE Paper No. 994202, ASAE, St. Joseph, MI.

Bohnhoff, D. R. 1992. Expanding diaphragm


5.8.3 Application. The Vh value calculated us- analysis for post-frame buildings. Applied Engi-
ing equation 5-20 (or 5-21) is always a conser- neering in Agriculture 8(4):509-517.
vative estimate of the actual maximum shear
force (due to wind) in a diaphragm assembly. Gebremedhin, K.G. 1987a. SOLVER: An inter-
This estimate becomes increasingly conserva- active structures analyzer for microcomputers.
tive as the amount of load resisted by interior (Version 2). Northeast Regional Agricultural En-
post-frames increases. It follows that equations gineering Service. Cornell University, Ithaca,
5-20 and 5-21 are most accurate when dia- NY.
phragm stiffness is considerably greater than
interior post-frame stiffness. This tends to be the Gebremedhin, K.G. 1987b. METCLAD: Dia-
case in buildings that are relatively wide and/or phragm design of metal-clad post-frame build-
high, and in buildings where individual posts ings using microcomputers. Northeast Regional
offer no resistance to rotation (i.e., the posts are Agricultural Engineering Service. Cornell Uni-
more-or less pin-connected at both the floor and versity, Ithaca, NY.
eave lines).

5-19
National Frame Builders Association Post-Frame Building Design Manual

McGuire, P.M. 1998. One equation for compati-


ble eave deflections. Frame Building News
10(4):39-44.

Meader, N.F. 1997. Mathematical models for


lateral resistance of post foundations. Trans of
ASAE, 40(1):191-201.

Niu, K.T. and K.G. Gebremedhin. 1997. Evalua-


tion of interaction of wood framing and metal-
cladding in roof diaphragms. Transactions of the
ASAE 40(2):465-476.

Pollock, D. G., D. A. Bender and K. G. Gebre-


medhin. 1996. Designing for chord forces in
post-frame roof diaphragms. Frame Building
News 8(5):40-44.

Purdue Research Foundation. 1986. Purdue


plane structures analyzer. (Version 3.0). De-
partment of Forestry and Natural Resources.
Purdue University, West Layfette, IN.

Williams, G. D. 1999. Modeling metal-clad


wood-framed diaphragm assemblies. Ph.D.
diss., University of Wisconsin-Madison, Madi-
son, WI.

Wright, B.W. 1992. Modeling timber-framed,


metal-clad diaphragm performance. Ph.D. diss.
The Pennsylvania State University, University
Park, PA.

5-20
National Frame Builders Association Post-Frame Building Design Manual

Chapter 6: METAL-CLAD WOOD-FRAME DIAPHRAGM PROPERTIES

6.1 Introduction mation of diaphragm strength and stiffness.

6.1.1 General. One of the first steps in dia- 6.1.3 ASAE EP558 and EP484. Construction
phragm design is to establish in-plane shear specifications and testing procedures for dia-
strength and stiffness values for each identified phragm test assemblies are given in ASAE
diaphragm section. In most post-frame build- EP558 Load Test for Metal-Clad Wood-Frame
ings, these diaphragm sections consist of corru- Diaphragms (ASAE, 1999b). EP558 also gives
gated metal panels that have been screwed or equations for calculating diaphragm test assem-
nailed to wood framing. Behavior of these metal- bly strength and stiffness. These calculations
clad wood-frame (MCWF) diaphragms is com- along with construction specifications and test-
plex, and consequently, has been the subject of ing procedures from EP558 are outlined in Sec-
considerable research during the past 20 years. tion 6.3: Diaphragm Assembly Tests. For addi-
In addition to improving overall design, this re- tional details and further explanation of testing
search has led to improved methods for predict- procedures, readers are referred to the ASAE
ing metal-clad wood-frame diaphragm strength EP558 Commentary (ASAE, 1999b).
and stiffness.
ASAE EP484, which was introduced in detail in
Chapter 5, contains the equations for extrapolat-
6.1.2 Predicting Diaphragm Behavior. There
ing diaphragm test assembly properties for use
are essentially three procedures for predicting
in building design. These calculations are pre-
the strength and stiffness of a building dia-
sented in Section 6.4: Building Diaphragm
phragm. First, an exact replica of the building
Properties.
diaphragm (a.k.a. a full-size diaphragm) can be
built and tested to failure. Second, a smaller,
representative section of the building diaphragm 6.2 Design Variables
can be built and laboratory tested. The strength
and stiffness of this test assembly are then ex- 6.2.1 General. Many variables affect the shear
trapolated to obtain strength and stiffness values stiffness and strength of a structural diaphragm,
for the building diaphragm. Lastly, diaphragm including: overall geometry, cladding character-
behavior can be predicted using finite element istics, wood properties, fastener type and loca-
analysis software. The latter requires that the tion, and blocking. A short description of each of
strength and stiffness properties of individual these variables follows.
component (e.g., wood framing, mechanical
connections, cladding) be known. 6.2.2. Geometry. Geometric variables include:
spacing between secondary framing members
Of the three procedures for predicting metal-clad (e.g. purlins), spacing between primary framing
wood-frame diaphragm properties, only the sec- members (e.g., trusses/rafters), and overall di-
ond one – extrapolation of diaphragm test as- mensions. With respect to overall dimensions,
sembly data - is commonly used. This is be- diaphragm depth is measured parallel to primary
cause testing full-size diaphragms is simply not frames, diaphragm length is measured perpen-
practical (a new test would have to be con- dicular to primary frames. In most structures, the
ducted every time overall dimensions changed), overall length of a roof diaphragm is equal to the
and finite element analysis of MCWF dia- length of the building.
phragms is, for practical purposes, still in a de-
velopmental stage. The later can be attributed to 6.2.3 Cladding. Cladding type (e.g., wood,
the fact that the large number of variables affect- metal, fiberglass, etc.) is a significant design
ing diaphragm structural properties, as well as variable. Coverage (and examples) in this de-
the nonlinear behavior of some variables, has sign manual is limited to corrugated metal clad-
thus far precluded the development of a quick ding. Important design characteristics of this
and reasonably accurate closed-form approxi- type of cladding include: base metal (e.g., steel,

6-1
National Frame Builders Association Post-Frame Building Design Manual

aluminum), base metal thickness, panel profile, shear strength and stiffness of a diaphragm.
and individual sheet width and length. Sheet-to-purlin fasteners are also defined by
their location (i.e., end, edge, and field). A
6.2.4 Wood Framing. The species, moisture sheet-to-purlin fastener may be located in a rib
content and specific gravity of wood used in the or in the flat of a corrugated metal panel. Locat-
framing system will not only affect the structural ing fasteners in the flat generally produces
properties of the wood members, but also the stronger and stiffer diaphragms. The nonlinear
shear stiffness and strength of mechanical con- nature of fastener performance is one of the
nections between wood members and between more complex variables affecting diaphragm
wood members and cladding. stiffness.

6.2.5 Mechanical Connections. Type (screw 6.2.6 Blocking. When secondary framing
or nail), size, and relative location of mechanical members are installed above primary framing
fasteners used to join components significantly (e.g. top running purlins) or below primary fram-
impact diaphragm properties. Fasteners are ing (e.g. bottom-running ceiling framing), clad-
primarily defined by what they connect. Major ding can only be fastened directly to the secon-
categories include purlin-to-rafter, sheet-to- dary framing (see figure 6.1). In such cases,
purlin, and sheet-to-sheet (see figure 6.1). blocking is often placed between the cladding
Sheet-to-sheet fasteners are more commonly and primary framing to increase shear transfer
referred to as stitch or seam fasteners. Remov- between the components. This is commonly
ing stitch fasteners can dramatically reduce the done at locations where diaphragms and shear-
walls intersect.

Sheet-to-Purlin Fasteners (Field)


Stitch Fastener Purlin-to-Rafter Fastener

Sheet-to-Purlin Fastener (Edge) Sheet-to-Purlin Fasteners (End)

Sidelap Seam Corrugated Metal Cladding

Rake Blocking between purlins Purlin Rafter/Truss Top Chord


Board

Figure 6.1. Components of a metal-clad wood-frame roof diaphragm.

6-2
National Frame Builders Association Post-Frame Building Design Manual

Applied
force, P
F Rafter / Truss chord G
2
Purlins
Notes:

b = Test assembly length


Cladding 1. Force P may be alternately applied at point H
2. Locate gages 2 and 4 on the edge purlins
3. Locate gages 1 and 3 on the rafter / truss chord

Corrugations
Direction of

4
E H
a = Test assembly width
Deflection gage location
and direction of measured
1 3 deflection (typ.)

(a)

3a = Test assembly width

Applied force, P/2 Applied force, P/2

F Rafter / Truss chord I K G

Purlins
b = Test assembly length

Cladding
corrugations
Direction of

E J L H

2 3
1 Deflection gage location 4
and direction of measured
deflection (typ.)

Notes: 1. The applied forces may alternately be applied at points J and L


2. Locate gages 1, 2, 3 and 4 on the rafters/ truss chords

(b)

Figure 6.2. (a) Cantilever test configuration, and (b) Simple beam test configuration for
diaphragm test assemblies.

6-3
National Frame Builders Association Post-Frame Building Design Manual

6.3 Diaphragm Test Assemblies When this reduction is not applied (as would be
the case when test assembly failure is not initi-
ated by wood failure), the NDS load duration
6.3.1 Construction. With the exception of
factor, CD, can not be used to increase the al-
overall length and width, a diaphragm test as-
lowable design shear strength during building
sembly is required to be identical to the dia-
design. Completely separate of the load duration
phragm in the building being designed. Specifi-
factor adjustment is the 30% increase in allow-
cally, frame members must be of identical size,
able strengths allowed by most codes for wind
spacing, species and grade; metal cladding
loadings (see Section 3.9.4).
must be identical in composition, profile and
thickness; and fastener type and location must
6.3.4 Shear Stiffness. The procedure for de-
be the same. ASAE EP558 has established
termining the effective shear modulus of a test
minimum sizes for diaphragm test assemblies to
assembly begins with calculation of the adjusted
ensure that there is not too great a difference
load-point deflection, DT. This value takes into
between the size of a diaphragm test assembly
account rigid body rotation/translation during
and the actual building diaphragm.
assembly test and is calculated as follows:
6.3.2 Test Configurations. ASAE EP558 al-
Cantilever test:
lows for two different testing configurations: a
DT = D3 – D1 – (a/b) (D2 + D4) (6-3)
cantilever test and a simple beam test (figures
6.2a and 6.2b, respectively). In both figures 6.2a
Simple beam test:
and 6.2b, variable “a” represents the spacing
DT = (D2 + D3 – D1 – D4) / 2 (6-4)
between rafters/trusses (a.k.a. the frame spac-
ing). This spacing should be equal to, or a multi-
where:
ple of, the frame spacing in the building being
designed.
DT = adjusted load point deflection, in.
(mm)
6.3.3 Shear Strength. The allowable design
D1, D2, D3, and D4 = deflection measure-
shear strength, of a diaphragm test assembly is
ments, in. (mm) (see figure 6.2)
equal to 40% of the ultimate strength of the as-
a = assembly width, ft (m)
sembly. In equation form:
b = assembly length, ft (m)
Cantilever test:
The effective in-plane shear stiffness, c, for a
va = 0.40 Pu / b (6-1)
diaphragm test assembly is defined as the ratio
of applied load to adjusted load point deflection
Simple beam test:
at 40% of ultimate load. In equation form:
va = 0.40 Pu / (2b) (6-2)
Cantilever test:
where:
c = 0.4 Pu / DT,d (6-5)
va = allowable design shear strength,
Simple beam test:
lbf/ft (N/m)
c = 0.2 Pu / DT,d (6-6)
Pu = ultimate strength, lbf (N)
= total applied load at failure
where:
b = assembly length, ft (m) (see figure
6.2)
c = effective in-plane shear stiffness,
lbf/in. (N/mm)
If one or more of the test assembly failures were
DT,d = adjusted load-point deflection, DT, at
initiated by lumber breakage or by failure of the
0.4 Pu, in. (mm)
fastenings in the wood, then the allowable de-
sign shear stress must be adjusted to account
The in-plane shear stiffness for the diaphragm
for test duration. To adjust from a total elapsed
test assembly, c, is converted to an effective
testing time of 10 minutes to a normal load dura-
shear modulus for the test assembly, G, as:
tion of ten years, divide va by a factor of 1.6.

6-4
National Frame Builders Association Post-Frame Building Design Manual

G = c (a/b) (6-7) 6.4.4 Horizontal Shear Stiffness. The horizon-


tal shear stiffness, ch, of a building diaphragm
where: section is related to its in-plane shear stiffness
as follows:
G = effective shear modulus of the test
assembly, lbf/in (N/mm) ch = cp cos2(θ) (6-10)

6.4 Building Diaphragm Properties or

ch = G bh cos(θ) / s (6-11)
6.4.1 General. As described in Chapter 5, each
building diaphragm is sectioned for analysis.
Each of these sections must be assigned a hori- 6.5 Building Shearwall Properties
zontal stiffness value, ch, and an allowable load,
va. 6.5.1 General. The same procedure used to
determine the strength and stiffness of building
6.4.2 Shear Strength diaphragms is used to determine the strength
The allowable design shear strength of a build- and stiffness of building shearwalls. That is, rep-
ing diaphragm is equal to that calculated for the resentative test assemblies are loaded to failure,
diaphragm test assembly. Consequently, to cal- to determine their shear strength and stiffness.
culate the total in-plane shear load that a build- These properties are then linearly extrapolated
ing diaphragm can sustain, simply multiply the to obtain strength and stiffness values for the
allowable design shear strength, va, by the slope building shearwall(s).
length of the building diaphragm.
6.5.2 Shearwall Test Assemblies. ASAE
6.4.3 In-Plane Shear Stiffness. The in-plane EP558 also contains guidelines for construction
shear stiffness, cp, of a building diaphragm sec- and testing of shearwall test assemblies. With
tion is calculated from the effective shear the exception of overall length and width, a
modulus, G, of the diaphragm test assembly shearwall test assembly is required to be identi-
using the following equation: cal to the shearwall in the building being de-
signed. Specifically, frame members must be of
G bs identical size, spacing, species and grade; clad-
cp = (6-8)
s ding must be identical; and fastener type and
or location must be the same.
G bh
cp = (6-9)
s cos(θ) 6.6 Tabulated Data
where:
6.6.1 Sources. Testing replicate samples of
G = effective shear stiffness of test as- diaphragm test assemblies can get expensive.
sembly, lbf/in (N/mm) For this reason, a designer may choose not to
bS = slope length of building diaphragm conduct his/her own diaphragm tests, relying
section being modeled, ft (m) instead on designs that have been previously
s = width of the building diaphragm sec- tested by others. Information on many tested
tion being modeled, ft (m) designs is available in the public domain. Clad-
bh = horizontal span length of building ding manufacturers may have additional test
diaphragm section, ft (m) information on assemblies that feature their own
θ = slope of the building diaphragm sec- products.
tion, degrees
6.6.2 Example Tabulated Data. Table 6.1 con-
Implicit in equation 6-8 is the assumption that tains design details and engineering properties
the total shear stiffness of a building diaphragm for roof diaphragm tests assemblies. The infor-
is a linear function of length. mation in this table represents a small percent-
age of available data.

6-5
National Frame Builders Association Post-Frame Building Design Manual

Table 6.1. Steel-Clad Roof Diaphragm Assembly Test Data

Test Assembly Number 1 2 3 4


Test Configuration Cantilever Cantilever Cantilever Cantilever
Cladding
Wick Agri Wick Agri Wick Agri Midwest Manu-
Manufacturer/Trade Name
Panel Panel Panel facturing.
Base Metal Thickness Gauge 28 28 29 29
Major Rib Spacing, inches 12 12 12 12
Major Rib Height, inches 0.75 0.75 0.75 1.0
Major Rib Base Width, inches 1.25 1.25 1.25 2.5
Major Rib Top Width, inches 0.375 0.375 0.375 0.5
Yield Strength, ksi 50 50 80 80
Overall Design
Width, feet 9 9 9 6
Length, b , feet 12 12 12 12
Purlin Spacing, feet 2 2 2 2
Rafter Spacing, feet 9 9 9 6
Purlin Location Top running Top running Top running Top running
Purlin Orientation On edge On edge On edge On edge
Number of Internal Seams 2 2 2 2
Wood Properties
Purlin Size 2- by 4-inch 2- by 4-inch 2- by 4-inch 2- by 4-inch
Purlin Species and Grade No.1 & 2 SPF No.1 & 2 SPF No.1 & 2 SPF No.2 SYP
Rafter Species and Grade No. 1 SYP No. 1 SYP No. 1 SYP No. 1 SYP
Stitch Fastener
Type None Screw Screw EZ Seal Nail
Length, inches 1.0 1.0 2.5
Diameter #10 #10 8d
On Center Spacing, inches 24 24 24
Sheet-to-Purlin Fasteners
Type Screw Screw Screw EZ Seal Nail
Length, inches 1.0 1.0 1.0 2.5
Diameter #10 #10 #10 8d
Location in Field In Flat In Flat In Flat Major Rib
Location on End In Flat In Flat In Flat In Flat
Avg. On-Center Spacing in Field, in. 12 12 12 12
Avg. On-Center Spacing on End, in. 6 6 6 12
60d Threaded 60d Threaded 60d Threaded 60d Threaded
Purlin-to-Rafter Fastener
Hardened Nail Hardened Nail Hardened Nail Hardened Nail
Engineering Properties
Ultimate Strength, Pu, lbf. 2140 3390 3220 1930
Allowable Shear Strength, va, lbf/ft 71 113 107 64
Effective In-Plane Stiffness, c ,lbf/in 1625 2720 2720 1590
Effective Shear Modulus, G, lbf/in 1220 2040 2040 795
Anderson, Anderson, Anderson, Wee & Ander-
Reference
1989 1989 1989 son, 1990

6-6
National Frame Builders Association Post-Frame Building Design Manual

Table 6.1. cont., Steel-Clad Roof Diaphragm Assembly Test Data

Test Assembly Number 5 6 7 8


Test Configuration Cantilever Cantilever Cantilever Cantilever
Cladding
Midwest Manu- Walters
Manufacturer/Trade Name Grandrib 3 Grandrib 3
facturing STR-28
Base Metal Thickness Gauge 29 29 29 28
Major Rib Spacing, inches 12 12 12 12
Major Rib Height, inches 1.0 0.75 0.75 0.94
Major Rib Base Width, inches 2.5 1.75 1.75
Major Rib Top Width, inches 0.5 0.5 0.5
Yield Strength, ksi 80 80 80 80
Overall Design
Width, feet 6 9 9 9
Length, b , feet 12 12 12 16
Purlin Spacing, feet 2 2 2 2
Rafter Spacing, feet 6 9 9 9
Purlin Location Top running Top running Top running Top running
Purlin Orientation On edge On edge On edge On edge
Number of Internal Seams 2 2 2 2
Wood Properties
Purlin Size 2- by 4-inch 2- by 4-inch 2- by 4-inch 2- by 4-inch
Purlin Species and Grade No.2 SYP No.2 DFL No.2 SPF No.2 SYP
Rafter Species and Grade No. 1 SYP No. 2 DFL No. 2 SPF 1950f1.7E SYP
Stitch Fastener
Type EZ Seal Nail None None Screw
Length, inches 2.5 1.5
Diameter 8d #10
On Center Spacing, inches 24 24
Sheet-to-Purlin Fasteners
Type Screw Screw Screw Screw
Length, inches 0.75 1.0 1.0 1.5
Diameter #12 #10 #10 #10
Location in Field In Flat In Flat In Flat In Flat
Location on End In Flat In Flat In Flat In Flat
Avg. On-Center Spacing in Field, in. 6 12 12 12 and 18
Avg. On-Center Spacing on End, in. 6 6 6 12
60d Threaded 1-60d Spike + 1-60d Spike + 60d Threaded
Purlin-to-Rafter Fastener
Hardened Nail 2-10d Toenails 2-10d Toenails Hardened Nail
Engineering Properties
Ultimate Strength, Pu, lbf. 3995 3300 2775 4884
Allowable Shear Strength, va, lbf/ft 133 110 93 122
Effective In-Plane Stiffness, c ,lbf/in 2980 2920 2950 3890
Effective Shear Modulus, G, lbf/in 1490 2190 2210 2190
Wee & Ander- Lukens & Lukens & Bohnhoff and
Reference
son, 1990 Bundy, 1987 Bundy, 1987 others, 1991

6-7
National Frame Builders Association Post-Frame Building Design Manual

Table 6.1. cont., Steel-Clad Roof Diaphragm Assembly Test Data

Test Assembly Number 9 10 11 12


Test Configuration Simple Beam
Cladding
Type Regular Leg Extended Leg Regular Leg Extended Leg
Base Metal Thickness Gauge 29
Major Rib Spacing, inches 9
Major Rib Height, inches 0.62
Major Rib Base Width, inches 1.75
Major Rib Top Width, inches 0.75
Yield Strength, ksi 80
Overall Design
Width, feet 36
Length, b , feet 12
Purlin Spacing, feet 2
Rafter Spacing Pair of rafters every 12 feet (each pair spaced 6 in. apart)
Purlin Location Top running and lapped Inset
Purlin length, ft 13.2 and 12.0 11.25
To special blocking nailed be- To joist hanger attached to raf-
Purlin Attachment
tween each pair of rafters ters
Purlin Orientation On edge
Number of Internal Seams 11
Wood Properties
Purlin Size 2- by 6-inch
Purlin Species and Grade No.2 DFL and 1650f DFL
Rafter Species and Grade No. 2 DFL
Stitch Fastener*
Type None Screw* None Screw*
Length, inches 1.5 1.5
Diameter #10 #10
On Center Spacing, inches 24 24
Sheet-to-Purlin Fasteners
Type Screw
Length, inches 1.5
Diameter #10
Location in Field In Flat
Location on End In Flat
Avg. On-Center Spacing in Field, in. 9
Avg. On–Center Spacing on End, in. 9
Engineering Properties
Ultimate Strength, Pu, lbf. 6950 7850 6400 6950
Allowable Shear Strength, va, lbf/ft 116 131 107 116
Effective In-Plane Stiffness, c ,lbf/in 4700 7500 3700 4400
Effective Shear Modulus, G, lbf/in 4700 7500 3700 4400
Reference NFBA, 1996
* Because of the extended leg, screws installed in the flat at overlapping seams function as stitch fasteners.

6-8
National Frame Builders Association Post-Frame Building Design Manual

Table 6.1. cont., Steel-Clad Roof Diaphragm Assembly Test Data

Test Assembly Number 13 14 15


Test Configuration Simple Beam Simple Beam Simple Beam
Cladding
Metal Sales Pro Metal Sales Pro McElroy Metal
Manufacturer/Trade Name
Panel II Panel II Max Rib
Base Metal Thickness Gauge 30 30 29
Major Rib Spacing, inches 9.0 9.0 9.0
Major Rib Height, inches 0.75
Major Rib Base Width, inches 1.75
Major Rib Top Width, inches
Yield Strength, ksi 104 104 80
Overall Design
Width, feet 24 24 24
Length, b , feet 12 12 12
Purlin Spacing, feet 2.33 2.33 2
Pair of rafters every Pair of rafters every
Rafter Spacing, feet 12 feet (each pair 12 feet (each pair 8
spaced 6 in. apart) spaced 6 in. apart)
Purlin Location Top running Top running Top running
Purlin Orientation On edge On edge NA
Number of Internal Seams 8 8 7
Wood Properties
Purlin Size 2- by 6-inch 2- by 6-inch Mac-Girt steel hat
section: 1.5 in. tall,
Purlin Species and Grade 1650f 1.5E SPF 1650f 1.5E SPF 3.2 in. wide, 18 ga.
Rafter Species and Grade 1650f 1.5E SPF 1650f 1.5E SPF 2250f 1.9E SP
Stitch Fastener
Type Screw None None
Length, inches 0.625
Diameter #12
On Center Spacing, inches 9
Sheet-to-Purlin Fasteners
Type Screw Screw Screw
Length, inches 1.5 1.5 1.0
#10 in field
Diameter #10 #14
#14 in ends
Location in Field In Flat In Flat In Flat
Location on End In Flat In Flat In Flat
Avg. On-Center Spacing in Field, in. 9 9 18 (3 screws/sheet)
Avg. On-Center Spacing on End, in. 4.5 4.5 9 (4 screws/sheet)
Two - #12 x 1.6 in.
Purlin-to-Rafter Fastener
screws/joint
Engineering Properties
Ultimate Strength, Pu, lbf. 9600 6600 8645
Allowable Shear Strength, va, lbf/ft 160 110 144
Effective In-Plane Stiffness, c ,lbf/in 7680 7100 10700
Effective Shear Modulus, G, lbf/in 7680 7100 7130
Reference Townsend, 1992 Townsend, 1992 Myers, 1994

6-9
National Frame Builders Association Post-Frame Building Design Manual

6.7 Example Calculations

A designer wishes to find ch and va for roof diaphragm sections in a gable-roofed building
with roof slopes of 4-in-12. Distance between eaves is 36 feet, and post-frame spacing,
s, is 10 feet.

A cantilever test of a representative diaphragm test assembly with a width, a, of 10 feet


and a length, b, of 12 feet, yields an ultimate strength, Pu of 3900 lbf and an effective in-
plane stiffness, c, of 4000 lbf/in. The test assembly failure was not wood related, there-
fore the ultimate strength was not adjusted for load duration.

Equation 6-1: va (test assembly) = 0.40 Pu / b

va (test assembly) = 0.40 (3900 lbf) /12 ft = 130 lbf/ft

Equation 6-7: G = c (a/b)

G = (4000 lbf/in) (10 ft/12 ft) = 3333 lbf/in.

Equation 6-11: ch = G bh cos(θ) / s

ch = (3333 lbf/in) (36 ft / 2) (cos 18.4°) / 10 ft = 5690 lbf/in.

The horizontal stiffness, ch of 5690 lbf/in represents a single diaphragm section that
runs from eave to ridge and has a width of 10 feet.

va (diaphragm) = 1.30 va (test diaphragm) = 1.3 (130 lbf/ft) = 169 lbf/ft

As described in Section 3.9.4, the allowable strength of a diaphragm can generally


be increased by 30% when wind or seismic loads are acting in combination with
other loads.

6.8 References Lukens, A.D., and D.S. Bundy. 1987. Strength


and stiffnesses of post-frame building roof pan-
Anderson, G.A. 1989. Effect of fasteners on the els. ASAE Paper No. 874056. ASAE, St. Jo-
stiffness and strength of timber-framed metal- seph, MI.
clad roof sections. ASAE Paper No. MCR89-
501. ASAE, St. Joseph, MI. Myers, N.C. 1994. McElroy Metal Post Frame
Roof Diaphragm Test. Test Report 94-418. Pro-
ASAE. 1999a. EP484.2: Diaphragm design of gressive Engineering, Inc., Goshen, IN.
metal-clad, wood-frame rectangular buildings.
ASAE Standards, 46th Edition. St. Joseph, MI. NFBA. 1996. 1996 Diaphragm Test. National
Frame Builders Association, Inc., Lawrence, KS.
ASAE. 1999b. ASAE EP558: Load tests for
metal-clad wood-frame diaphragms. ASAE Townsend, M. 1992. Alumax test report: dia-
Standards, 46th edition. ASAE, St. Joseph, MI. phragm loading on roofs and end wall sections.
Alumax Building Products, Perris, CA.
Anderson, and P.A. Boor. 1991. Influence of
insulation on the behavior of steel-clad wood Wee, C.L. and G.A. Anderson. 1990. Strength
frame diaphragms. Applied Engineering in Agri- and stiffness of metal clad roof section. ASAE
culture 7(6):748-754. Paper No. 904029. ASAE, St. Joseph, MI.

6-10
National Frame Builders Association Post-Frame Building Design Manual

Chapter 7: POST PROPERTIES

7.1 Introduction 7.1, a post must be graded by an approved


grading agency and stamped accordingly.
7.1.1 Types. Several different post types are 7.2.4 Current Demand. Solid-sawn post use in
currently used in post-frame construction. The post-frame construction is on the decline, pri-
most common of these are laminated lumber marily because posts of acceptable size, length
posts. Solid-sawn posts are still used by most and quality are increasingly difficult to obtain.
builders, but not to the extent they were a dec- The scarcity of long posts in structural sizes has
ade ago. Parallel strand lumber (PSL) and made laminated posts more price competitive.
laminated veneer lumber (LVL) products are Additionally, laminated post prices are typically
gaining in popularity. Use of these and other constant on a per-foot basis regardless of
engineered lumber products as posts in post- length, while the cost of solid-sawn posts in-
frame buildings can only be expected to in- creases exponentially with length.
crease as the relative cost of these products
decreases.
7.3 Laminated Lumber Posts
7.1.2 Preservative Treatment. If posts are to
be embedded, they must be preservative treated 7.3.1 General. Laminated lumber posts are
to avoid decay. General issues of preservative posts that are fabricated by joining together
treatment have already been presented in individual pieces of dimension lumber, most
Chapter 4. Discussion in this chapter will focus commonly 2- by 6-inch, 2- by 8-inch and 2- by
on the structural aspects of post selection and 10-inch members. Structural properties of the
design. finished product vary significantly depending on
the means of lamination and the presence or
absence of joints in individual layers. Laminates
7.2 Solid-Sawn Posts are either glued together or joined together with
mechanical fasteners (i.e., nails, screws, bolts,
7.2.1 Size. Post size varies considerably with shear transfer plates, metal plate connectors).
building geometry and design loads. The most
common sizes are 6- by 6-inch, 6- by 8-inch, 7.3.2 Advantages. By combining individual
and 4- by 6-inch. Although both S4S (Surfaced laminates to build up a desired cross-section,
on 4 Sides) and rough sawn posts are available, the statistical probability that a strength-reducing
most rough sawn posts are not graded and characteristic of wood (such as a knot) would
therefore are generally only used in code ex- exist through the entire cross section is greatly
empt applications. diminished. Consequently, laminated posts have
more uniform strength and stiffness properties
7.2.2 Wood Species. Species of wood used in than solid-sawn posts. This increased reliability
posts depends on local availability and on results in higher allowable design values.
preservative treatment needs. Commonly used
species includes Southern Pine, Douglas Fir and 7.3.3 Laminate Orientation. Laminated post
Ponderosa Pine. strength is dependent on orientation of individual
laminates with respect to the principal load
7.2.3 Design Properties. NDS design values direction. If a post is designed (and positioned
for species and grades typically used in post- within the structure) to resist loads acting on the
frame construction are given in table 7.1. These edge, or narrow face, of the laminates, the post
values have been adjusted for conditions of use is said to be vertically-laminated (figure 7.1a). If
in which wood moisture content exceeds 19% a post is oriented such that the applied load acts
for extended time periods, as is the case for on the wide face of the laminates, the post is
embedded posts. To apply the values in table said to be horizontally-laminated (figure 7.1b).

7-1
National Frame Builders Association Post-Frame Building Design Manual

Table 7.1. Design Stresses for Selected Species and Grades of Solid-Sawn Posts *

Design Values in Pounds per Square Inch (psi)


Species and Tension Shear Compression Compression
Grade Bending, Modulus of
Parallel to Parallel to Perpendicular Parallel to
Fb Elasticity, E
Grain, Ft Grain, Fv to Grain, Fc┴ Grain, Fc

Douglas Fir-Larch
Sel Str 1500 1000 85 420 1045 1,600,000
No. 1 1200 825 85 420 910 1,600,000
No. 2 750 475 85 420 430 1,300,000

Northern Pine
Sel Str 1150 800 65 290 820 1,300,000
No. 1 950 650 65 290 730 1,300,000
No. 2 500 375 65 290 340 1,000,000

Ponderosa Pine
Sel Str 1000 675 65 360 730 1,100,000
No. 1 825 550 65 360 635 1,100,000
No. 2 475 325 65 360 295 900,000

Southern Pine
Sel Str 1500 1000 110 375 950 1,500,000
No. 1 1350 900 110 375 825 1,500,000
No. 2 850 550 100 375 525 1,200,000

* From the National Design Specifications (NDS) for wood under wet-use conditions, AF&PA (1997b).
Values are for lumber in the size category “Posts and Timbers”.

7.4 Glued-Laminated (Glulam) Posts


Load Load 7.4.1 Advantages. For a given species and
grade of lumber, glued-laminated posts have
higher allowable design values than solid-sawn
posts and most spliced mechanically-laminated
H V posts (see Section 7.6). Glued-laminated posts
exhibit complete composite action, that is, the
glue interface is of sufficient integrity that it is
assumed that there is no slip between laminates
V V H H regardless of load level. With no slip between
layers, glued-laminated posts behave much like
solid-sawn posts, and are very effective in
carrying biaxial bending loads.
H V

(a) (b) 7.4.2 Vertical Lamination. Glued-laminated


posts that have a rather square cross-section
Figure 7.1. (a) Vertically laminated, and (b) are typically designed as vertically-laminated
horizontally laminated post cross-sections. components; that is, they are designed to resist
primary bending moments about an axis per-
pendicular to the wide faces of individual lamina-
tions (Axis V-V, figure 7.1b). This class of posts

7-2
National Frame Builders Association Post-Frame Building Design Manual

(cross-sectional aspect ratios less than 1.5) are of curved members.


commonly used as posts in post-frame build-
ings. 7.4.4 Design Properties. Design properties for
both horizontally- and vertically-laminated glu-
7.4.3 Horizontal Lamination. In contrast to the lams are published by American Institute of
glued-laminated posts commonly used in post- Timber Construction (AITC, 1985) and AF&PA
frame construction, deep glulam beams (e.g. (1997b). Values for selected vertically-laminated
door headers) are generally designed as hori- assemblies are listed in table 7.2. These values
zontally laminated components (figure 7.1a). are for dry-use conditions and normal load
Lumber is used more efficiently in these assem- duration. In actual application, glulam design
blies by placing higher grade lumber in outer values must be adjusted by applicable factors
laminates where bending stresses are higher, involving curvature, volume, beam stability and
and using lower grade lumber near the center column stability. These factors (and direction
where bending stresses are low. In addition, regarding their application) can also be found in
horizontal lamination facilitates the manufacture the two references cited in this paragraph.

Table 7.2. Design Values for Vertically Glued Laminated Posts a

Extreme Fiber in Bending, psi


Compression Parallel
AITC Bending about Tension
MOE, to Grain, psi
Combin V-V Axis. Bending Parallel
Lumber Grade million
ation 4 or about to Grain, 4 or
psi 2 or 3
Symbol 3 Lams More H-H Axis. psi More
Lams
Lams Lams

Douglas Fir- Larch


13 Dense Sel Str 2.0 2300 2400 2200 1600 1950 2300
12 Sel Str 1.8 1950 2100 1900 1400 1650 1950
11 No. 1 Dense 2.0 2100 2300 2100 1500 1700 2300
10 No. 1 1.8 1750 1950 1750 1300 1450 1950
9 No. 2 Dense 1.8 1800 1850 1600 1150 1350 1800
8 No. 2 1.6 1550 1600 1350 1000 1150 1550

Hem-Fir
21 Sel Str 1.6 1650 1750 1500 1100 1350 1450
20 No. 1 1.6 1500 1550 1350 975 1250 1450
19 No. 2 1.4 1300 1350 1150 850 975 1300

Southern Pine
52 Dense Sel Str 1.9 2300 2400 2100 1500 1850 2200
51 Sel Str 1.7 1950 2100 1750 1300 1600 1900
50 No. 1 Dense 1.9 2100 2100 b 1800 b 1550 1700 2300
49 No. 1 1.7 1750 1850 b 1550 b 1350 1450 2100
48 No. 2 Dense 1.7 1800 1850 b 1600 b 1400 1350 2200
47 No. 2 1.4 1550 1600 b 1350 b 1200 1150 1900

Wet Service Factor, CM c 0.833 0.80 0.80 0.80 0.80 0.73 0.73
a
From the National Design Specifications (NDS), AF&PA (1997b).
b
Values reflect the removal of the more restrictive slope-of-grain requirements.
c
The tabulated values are applicable when in-service moisture content is less than 16%. To obtain
wet-use values, multiply the tabulated values by the factors shown.

7-3
National Frame Builders Association Post-Frame Building Design Manual

7.4.5 Manufacturing Requirements. For glu- which nails, screws, bolts, and/or shear transfer
lam design values apply, tight quality control plates (STPs) have been used to join individual
must be maintained during the laminating proc- laminates. Nails are the most commonly used
ess. The AITC has published standards for the mechanical fastener and posts that only feature
design (AITC, 1985) and manufacturing (AITC, nails are often referred to as nail-laminated
1988) of glued-laminated members. Fabrication posts. STPs are medium-gage metal plates that
procedures for the members must conform to an are stamped such that teeth protrude from both
additional standard (AITC, 1983), which covers surfaces.
physical construction issues as well as quality
control, testing and marking procedures. The Mechanical fasteners that connect preservative
rigorous requirements for construction, as well treated lumber should be AISI type 304 or 316
as the planing that must be performed (individ- stainless steel, silicon bronze, copper, hot-
ual laminates prior to lamination, and the fin- dipped galvanized (zinc-coated) steel nails or
ished member after lamination completion), hot-tumbled galvanized nails.
combine to essentially eliminate the possibility of
on-site fabrication. These factors also increase 7.5.3 Advantages. Unspliced mechanically-
product price, however, for many applications, laminated posts generally cost less than solid-
higher design properties justify the higher cost. sawn posts, and they are stronger than similarly
sized solid-sawn posts when bent around axis
7.4.6 End Joints. Posts of any length can be V-V (figure 7.1a). As previously noted, this is
created by end-joining individual laminates. The due to the fact that strength reducing defects are
most common glued end joint is the finger joint. spread out in laminated assemblies. Also,
Although finger joining is a common manufactur- pressure preservative treatment retention is
ing process, only a few manufacturing facilities more uniform in the narrower laminates of a
have the capability of producing finger joints that mechanically-laminated post than it is in wide
meet AITC quality standards for structural joints solid-sawn posts.
(i.e., the type of joints required in glulams).
Joints that do not meet criteria established for 7.5.4 Disadvantages. When mechanically-lami-
structural joints are likely to fail when subjected nated posts are bent around axis H-H (figure
to design level stresses. 7.1b), there can be considerable slip between
laminates. For this reason, the bending strength
7.4.7 Glulams for Post-Frame Buildings. A and stiffness of mechanically-laminated assem-
handful of companies now manufacture and blies bent about axis H-H is relatively low. To
market glulams specifically for use in post-frame compensate for this weakness, mechanically-
buildings. These posts are intended for soil laminated posts are generally only used where:
embedment, with pressure preservative treated (1) there is adequate weak axis support (i.e., the
wood on one end, and non-treated wood on the posts are part of a sheathed wall), (2) cover
other. Fabrication of such posts requires special plates can be added to increase bending
resins and procedures for joining and laminating strength and stiffness about axis H-H (figure
treated wood to non-treated wood. 7.2), or (3) the bending moment about axis H-H
is relatively low or non-existent.
7.5 Unspliced Mechanically-
Laminated Posts

7.5.1 General. The majority of posts used in


post-frame construction with an overall length
less than 18 feet are unspliced, mechanically-
laminated posts. An unspliced post is any lami-
nated post that does not contain end joints. This
means that each layer is comprised of a single Figure 7.2. Cover plates used to increase the
uncut piece of dimension lumber. bending capacity of a mechanically laminated
post about axis H-H.
7.5.2 Fasteners. As previously noted, a me-
chanically laminated post is a laminated post in

7-4
National Frame Builders Association Post-Frame Building Design Manual

7.5.5 Bending About Axis V-V. Allowable wet use, load duration, temperature, and in
design stresses for bending of unspliced me- certain cases, special preservative and fire
chanically-laminated posts about axis V-V are treatments.
calculated in accordance with ANSI/ASAE
EP559 Design Requirements and Bending
Properties for Mechanically Laminated Columns
(ASAE, 1999). The procedure outlined in Table 7.3. Repetitive Member Factors*
ANSI/ASAE EP559 is identical to procedures Number of laminations
outlined in the NDS (AF&PA, 1997a) with the
exception of two adjustment factors: the repeti- 3 4
tive member factor, Cr, and the beam stability Visually graded 1.35 1.40
factor, CL.
Mechanically graded 1.25 1.30
7.5.5.1 Repetitive Member Factor. ANSI/ * For mechanically-laminated dimension lumber
ASAE EP559 allows the use of the repetitive assemblies with minimum interlayer shear
member factors in Table 7.3 when: (1) each capacities as specified in Table 7.4. From
lamination is between 1.5 and 2.0 inches, ANSI/ASAE EP559 (ASAE, 1999).
(2) all laminations have the same depth
(face width), (3) faces of adjacent lamina-
tions are in contact, (4) the centroid of each Table 7.4. Minimum Required Interlayer
lamination is located on the centroidal axis Shear Capacities*
of the post (axis V-V in figure 7.1a), that is, Minimum required
Nominal face
no laminations are offset, (5) all laminations interlayer shear capacity
width of lamina-
are the same grade and species of lumber, per interface per unit
tions, inches
(6) concentrated loads are distributed to the length of post, lb/in.
individual laminations by a load distributing 6 12
element, and (7) the mechanical fasteners 8 15
joining the individual layers meet the criteria
in table 7.4. Note that if one or more of these 10 19
criteria are not met, the NDS repetitive 12 24
member factor of 1.15 should be used if it * For unspliced mechanically-laminated posts.
applies.
From ANSI/ASAE EP559 (ASAE, 1999).
7.5.5.2 Beam Stability Factor. The beam
stability factor, CL, is a function of the slen-
derness ratio, RB, which in turn, is a function 7.5.6 Bending About Axis H-H. When all
of: beam thickness, b; depth, d; and effec-
laminates are the same size, species and grade
tive span length, Le. ANSI/ASAE EP559
of lumber, the allowable design bending strength
states that for mechanically-laminated posts about axis H-H is conservatively taken as the
being bent about axis V-V, thickness, b,
sum of the bending strengths of the individual
shall be equated to 60% of the actual post
layers. The bending strength of an individual
thickness, and depth, d, to the actual face layer is equated to the product of the “flatwise”
width of a lamination. The effective span
section modulus of an individual laminate and
length, Le, is a function of the unsupported the NDS adjusted design bending stress. For
length, Lu. The unsupported length shall be flatwise bending, the NDS adjusted design
set equal to the on-center spacing of bracing
bending stress, Fb’, is equal to tabulated design
that keeps the post from buckling laterally. bending stress, Fb, multiplied by the appropriate
flat use factor, a repetitive member factor of
7.5.5.3 Design Values. Tables 7.5a and
1.15, and all other applicable factors. Note that
7.5b contain design values for assemblies the beam stability factor is equal to 1.0 for
fabricated from visually graded and machine flatwise bending.
stress rated dimension lumber, respectively.
The design bending stresses have been ad-
justed for repetitive member use. They must
be further adjusted to account for stability,

7-5
National Frame Builders Association Post-Frame Building Design Manual

Table 7.5a Design Values for Unspliced Mechanically-Laminated Posts in Bending About Axis V-V.
Extreme Fiber Bending Stress*, psi
Nominal Width of Individual Layers, inches Modulus
of
6 8 10 12
Elasticity,
Grade Number of laminations x 106 psi
3. 4. 3. 4. 3. 4. 3. 4.
Douglas Fir-Larch
Sel Str 2540 2640 2350 2440 2150 2230 1960 2030 1.9
No. 1 & Better 2020 2090 1860 1930 1710 1770 1550 1610 1.8
No. 1 1760 1820 1620 1680 1490 1540 1350 1400 1.7
No. 2 1540 1590 1420 1470 1300 1350 1180 1230 1.6

Hem Fir
Sel Str 2460 2550 2270 2350 2080 2160 1890 1960 1.6
No. 1 & Better 1840 1910 1700 1760 1560 1620 1420 1470 1.5
No. 1 1670 1730 1540 1600 1410 1460 1280 1330 1.5
No. 2 1490 1550 1380 1430 1260 1310 1150 1190 1.3

Southern Pine
Dense Sel Str 3650 3780 3310 3430 2900 3010 2770 2870 1.9
Sel Str 3440 3570 3110 3220 2770 2870 2570 2660 1.8
Non-Dense SS 3170 3290 2840 2940 2500 2590 2360 2450 1.7
Dense No. 1 2360 2450 2230 2310 1960 2030 1820 1890 1.8
No. 1 2230 2310 2030 2100 1760 1820 1690 1750 1.7
Non-Den. No. 1 2030 2100 1820 1890 1620 1680 1550 1610 1.6
Dense No. 2 1960 2030 1790 1960 1620 1680 1550 1610 1.7
No. 2 1690 1750 1620 1690 1420 1470 1320 1370 1.6
Non-Den. No.2 1550 1610 1490 1540 1280 1330 1220 1260 1.4
* For dry posts under normal load duration. Size and repetitive member factors applied. For other appli-
cable modification factors, see NDS (AF&PA, 1997a).

Table 7.5b Design Values for Unspliced Mechanically-Laminated Posts in Bending About Axis V-V.
Extreme Fiber Bending Stress*, psi Extreme Fiber Bending Stress*, psi
Grade Grade
3 Laminates 4 Laminates 3 Laminates 4 Laminates
900f-1.0E 1130 1170 1950f-1.5E 2440 2540
900f-1.2E 1130 1170 1950f-1.7E 2440 2540
1200f-1.2E 1500 1560 2100f-1.8E 2630 2730
1200f-1.5E 1500 1560 2250f-1.6E 2810 2930
1350f-1.3E 1690 1760 2250f-1.9E 2810 2930
1350f-1.8E 1690 1760 2400f-1.7E 3000 3120
1450f-1.3E 1810 1890 2400f-2.0E 3000 3120
1500f-1.3E 1880 1950 2550f-2.1E 3190 3320
1500f-1.4E 1880 1950 2700f-2.2E 3380 3510
1500f-1.8E 1880 1950 2850f-2.3E 3560 3710
1650f-1.4E 2060 2150 3000f-2.4E 3750 3900
1650f-1.5E 2060 2150 3150f-2.5E 3940 4100
1800f-1.6E 2250 2340 3300f-2.6E 4130 4290
1800f-2.1E 2250 2340
* For dry posts under normal load duration. Repetitive member factors applied. For other applicable
modification factors, see NDS (AF&PA, 1997a).

7-6
National Frame Builders Association Post-Frame Building Design Manual

7.5.7 Flexural Rigidity. To calculate deflections 7.5.9 Field Fabrication. A distinct advantage of
due to bending requires that the flexural rigidity mechanically-laminated posts is that fabrication
of the member be known. The flexural rigidity of can be performed using tools and equipment
a solid-sawn member is equal to its modulus of readily available on the job site. With unspliced
elasticity times its moment of inertia about the posts that will be embedded in the ground, it is
axis it is being bent. The flexural rigidity of an common to construct the post so that an interior
unspliced laminated post when bent around axis laminate is left shorter than the surrounding
V-V is simply equal to the sum of the flexural laminates. When the post is installed with this
rigidities of the individual laminates about axis V- feature located on the top of the post, the truss
V. In other words, the flexural rigidity about axis can be set in the resulting pocket, enabling a
V-V is not dependent on the properties of the double shear connection between the post and
mechanical fasteners. This is not the case with truss. The interior laminate is generally signifi-
respect to bending about axis H-H. The bending cantly shorter (approximately 1 foot) than
stiffness about axis H-H axis is highly dependent needed to accommodate the truss. This is done
on the shear stiffness of the mechanical connec- to compensate for varying depths of embed-
tions between the individual laminates. A high ment. After posts are installed, a spacer (or
bound for flexural rigidity about axis H-H is block) of the same cross-sectional size as the
obtained by assuming complete composite shortened laminate is placed in between the
action between layers (no interlayer slip). A shortened laminate and the truss. A schematic
lower bound is obtained by assuming no com- of this procedure is shown in Figure 7.3.
posite action (no interlayer connections). In the
latter case, the total flexural rigidity is equal to
the sum of the flexural rigidities of the individual
laminates. Special analysis procedures, such as
that developed by Bohnhoff (1992) are available
for more accurate estimates of deformation due
to bending about axis H-H. Use of these pro-
grams requires knowledge of the shear stiffness Block Block
properties of the mechanical connections. Height

7.5.8 Compressive Properties. The allowable


compressive load for an unspliced mechanically
1. Post set, bottom of 2. Truss set on 3. Block nailed into
laminated post is typically calculated by treating truss marked, and block block and bolted place and top of outer
the individual laminates as discrete columns. height measured into place. layers cut off.
This method conservatively assumes no com-
posite action between laminates. An allowable Figure 7.3. On-site truss placement in a me-
compressive stress is first calculated for each chanically laminated post.
laminate for buckling about axis V-V. This allow-
able stress is then multiplied by the cross-
sectional area of the laminate to obtain an
allowable load for buckling about axis V-V. This 7.6 Spliced Mechanically-Laminated
calculation is repeated for each layer, and the Posts
resulting individual laminate loads are summed
to obtain a total allowable column load for buck- 7.6.1 Types. A spliced post is any post in which
ling about axis V-V. The entire process is re- at least one laminate contains one or more end-
peated to obtain a total allowable load for buck- joints (i.e., is comprised of two or more individual
ling about axis H-H. pieces of lumber). Major end-joint types used in
spliced mechanically-laminated posts include:
The NDS (AF&PA, 1997a) presents methods for simple butt joints, reinforced butt joints, and
calculating a compressive load capacity that glued finger joints. Butt joints are generally
accounts for some composite action; however, reinforced by pressing metal plate connectors
connectors used in fastening the laminations into one or both sides of each joint.
must meet criteria outlined in the NDS.

7-7
National Frame Builders Association Post-Frame Building Design Manual

Level
line of
sight

(a) (b) (c)

Figure 7.4. (a) Treated portions of 3-layer spliced posts are embedded in the soil. (b)
Top of treated portions cut so that tops at same elevation. (c) Untreated post portions
spliced to treated portions.

7.6.2 Use. Virtually all mechanically-laminated the upper portions will have the same overall
posts with overall lengths exceeding 20 foot are length (figure 7.4c). This eliminates cutting and
spliced posts. blocking like that associated with the special
construction shown in figure 7.3.
7.6.3 Advantages. Splicing enables the fabrica-
tion of long posts from shorter, less expensive 7.6.4 Disadvantages. Spliced mechanically-
lengths of dimension lumber. Splicing also laminated posts have the same disadvantages
enables the construction of posts with preserva- as unspliced mechanically-laminated posts (see
tive treated lumber on only one end. This re- Section 7.5.4). In addition, a simple (non-
duces the quantity of treated lumber used in a reinforced) butt joint can significantly reduce
building, which in turn reduces the number of bending strength and stiffness in the vicinity of
special corrosion-resistant fasteners needed to the joint. If a post contains a simple butt joint in
join treated lumber. each laminate, and these joints are all located
within 1 or 2 feet of each other, engineers will
With simple butt joints, the attachment of non- often model that portion of the post as a hinge
treated lumber to treated lumber is sometimes connection.
done in the field. This attachment is done after
the treated pieces have been laminated and 7.6.5 Design Properties. Design properties for
embedded in the ground (figure 7.4a). Prior to spliced mechanically-laminated posts are highly
attaching the untreated top-portion of each post, dependent on the type and relative location of
the embedded treated portions are all cut so that end joints, and on the type and relative location
their tops are at the same elevations (note: of mechanical fasteners, especially those lo-
because of differing depths-of-embedment, the cated in the vicinity of end joints. Procedures for
top of each embedded section is generally at a designing and determining the bending strength
different height above grade). With the embed- and stiffness of spliced nail-laminated posts are
ded portions at the same elevation (figure 7.4b), outlined in ANSI/ASAE EP559 (ASAE, 1999).

7-8
National Frame Builders Association Post-Frame Building Design Manual

The design portion of EP559 includes require- American Forest and Paper Association
ments for joint arrangement, overall splice (AF&PA). 1997b. NDS Supplement - Design
length, nail strength, nail density, nail diameter, values for wood construction. American Forest
and nail location. If these design requirements and Paper Association, Washington, D.C.
are followed, the bending strength and stiffness
of the nail-laminated post can be calculated American Institute of Timber Construction
using the equations in the EP. It is important to (AITC). 1983. Structural glued laminated timber.
note that the intent of the EP559 design re- ANSI/AITC A190.1-1983. Englewood, CO.
quirements is to maximize the bending strength
of the splice region, while minimizing overall American Institute of Timber Construction
splice length. Overall splice length is defined as (AITC). 1985. Design standard specifications for
the distance between the two farthest removed structural glued laminated timber of softwood
end joints in a post that contains one end joint in species. AITC 117.85. Englewood, CO.
each laminate. Reducing overall splice length
generally reduces the amount of preservative American Institute of Timber Construction
treated lumber used in a post. (AITC). 1988. Manufacturing standard specifica-
tions for structural glued laminated timber of
7.6.6 Laboratory Tests. Engineers must gen- softwood species. AITC 117.88. Englewood,
erally rely on laboratory tests to determine CO.
design properties for spliced posts that do not
meet the design requirements of ANSI/ASAE ASAE. 1999. ANSI/ASAE EP559: Design re-
EP559. In recognition of this, a laboratory test quirements and bending properties for mechani-
procedure specifically for spliced mechanically cally laminated columns. ASAE Standards, 46th
laminated posts is outlined in ANSI/ASAE edition. ASAE, St. Joseph, MI.
EP559.
Bohnhoff, D.R. 1992. Modeling horizontally nail-
7.6.7 Computer Modeling. Discontinuities at laminated beams. ASCE Journal of Strucutral
butt joints result in a post with a varying bending Engineering 118(5):1393-1406.
stiffness along its length. If the overall splice
length is rather short (i.e., all joints are located
within a distance equal to 1/4th the post length),
the post is generally sectioned into three ele-
ments for computer frame analysis: a middle
element that contains all the joints, and two
“joint-free” outer elements. The joint-free ele-
ments are treated like unspliced mechanically-
laminated posts with flexural rigidities calculated
as described in Section 7.5.7. The element
containing the joints is assigned an effective
flexural rigidity that will cause it to deform like
actual laboratory tested posts. A procedure for
“backing-out” an effective flexural rigidity from
bending test data is given in ANSI/ASAE EP559.
The EP also contains an equation for calculating
the flexural rigidity of the splice region of any
nail-laminated post that meets the design re-
quirements of the EP.

7.7 References

American Forest and Paper Association


(AF&PA). 1997a. National Design Specifications
for Wood Construction (NDS). American Forest
and Paper Association, Washington, D.C.

7-9
National Frame Builders Association Post-Frame Building Design Manual

7-10
National Frame Builders Association Post-Frame Building Design Manual

Chapter 8 - POST FOUNDATION DESIGN

8.1 Introduction The most comprehensive current design guide-


line is ASAE EP486 (ASAE, 1999a). The mate-
rial in this chapter is largely based on this engi-
8.1.1 General. A distinct advantage of post-
neering practice.
frame construction is the opportunity to transfer
structural loads to the soil via embedded posts,
CL
thereby eliminating the need for a traditional B/2 B/2
foundation.

8.1.2 Post Loads. Post loads (i.e., structurally


Post
induced shear, bending moment and axial
q
loads) are obtained using procedures presented
in Chapter 5. Most post foundation design equa- 2.0B 1.5B 1.0B 1.0B 1.5B 2.0B
tions require that post loads be specified at the 0.9q

ground surface. 0.5B


0.8q

0.7q
0.6q
8.1.3 Post Foundation Classification. Based 1.0B
on their depth, post foundations are categorized 0.4q
0.5q
0.1q
as shallow foundations. Shallow foundations 1.5B
exhibit behavior quite different from that of 0.3q
deeper systems such as pilings. Specifically, 2.0B
post deformation below grade is relatively insig- 0.2q

nificant compared to the deformation of the soil 2.5B


around the post. Soil deformation around a post
is a three-dimensional phenomena. Figure 8.1 3.0B
shows the lines of constant soil pressure (in a
horizontal plane of soil) that form when a post 3.5B
moves laterally. The greater the distance be-
tween two posts, the less influence one post will Figure 8.1. Constant Pressure Lines in a Hori-
have on the soil pressure near the other. For zontal Plane of Soil.
design purposes, individual embedded posts are
considered isolated foundations when post
spacing is six times greater than post width. 8.2 Post Constraint
Higher allowable lateral soil bearing pressures
are justified for a foundation featuring isolated 8.2.1 Nonconstrained Post. The most basic
posts instead of a continuous foundation wall. type of post foundation consists of a post simply
embedded in the ground, with no attachments or
8.1.4 Design Variables. Factors that influence additional support (figure 8.2). If the rotation and
the strength and stiffness of a post foundation lateral displacement of the post are resisted
include: embedment depth, post constraint (Sec- solely by the soil, the post foundation is said to
tion 8.2), soil properties (Section 8.3), footing be non-constrained.
size (Section 8.4), collar size (Section 8.5),
backfill properties (Section 8.6), and post di- 8.2.2 Constrained Post. If a post bears on (or
mensions (Section 8.7). is attached to) an additional “immovable” struc-
tural element such that the lateral displacement
8.1.5 Design Guides. The first design manual at some point at or above the ground surface is
for post foundations was originally published by essentially equal to zero, the post foundation is
the American Wood Preservers Institute (Patter- said to be constrained. An example of a con-
son, 1969). The basic design approach and strained post foundation would be when the post
guidelines for post embedment analysis have is installed immediately adjacent to a concrete
been accepted by several major building codes. slab floor in the building (figure 8.3).

8-1
National Frame Builders Association Post-Frame Building Design Manual

8.2.3 Varying Constraint. It is important to note was pushing on the slab, the post would be con-
that a single post can be both constrained or sidered constrained. However, if the wind were
non-constrained, depending on the load case. blowing in the opposite direction, the post would
Using the previous example of a slab floor, and not be supported by the slab; hence, the post
assuming that the post is not attached to the would be analyzed for that load case as non-
slab, if the wind loading was such that the post constrained.

Ma Ma
Ground Level Ground Level
Va Va

Resultant
Post Soil Force
do do

d d

Rotation Axis
Resultant
Soil Force Rotation Axis

Soil Forces Footing Footing

LOAD CASE A LOAD CASE B

Figure 8.2. Free body diagrams of non-constrained post foundations. Load Case A:
groundline shear and moment both cause clockwise rotation of embedded portion of
post. Load Case B: groundline shear and moment cause clockwise and counter clock-
wise rotation, respectively, of embedded portion of post.
Ma
Ground Level Va
R

Floor

Resultant
Soil Force Post

Soil Forces
Footing

Figure 8.3. Free body diagram of a constrained post foundation.

8-2
National Frame Builders Association Post-Frame Building Design Manual

8.3 Soil Properties contains soil properties as tabulated in ASAE


are referred to as presumptive values and
should only be used if there is no active building
8.3.1 General. The capability of a soil to handle
code in effect, and site-specific soil properties
loads transmitted to it by a post depend on such
are unavailable.
characteristics as: particle size and size distribu-
tion (a.k.a. soil classification), moisture content,
density, and depth below grade. These soil The vertical soil pressures given in table 8.1 are
characteristics control the allowable vertical and for the first foot (300 mm) of footing width and
lateral soil pressures. first foot below grade. A twenty percent increase
in allowable soil pressure is allowed for each
additional foot (300 mm) of foundation width or
8.3.2 Soil Classification. Soil is classified by
depth, up to a maximum of three times the origi-
the size of individual particles and the distribu-
nal value.
tion of sizes within the sample. There are four
major particle (grain) sizes: gravel, sand, silt,
The lateral soil pressure values in table 8.1 are
and clay. The most popular classification system
per unit depth. To obtain the allowable lateral
in the U.S. (i.e., the Unified Soil Classification
pressure at a point below grade, SL, multiple the
(USC) system) classifies gravels as grains be-
lateral soil pressure value, S, by the distance
tween 0.2 and 3.0 inches, sands as particles
below grade of the point in question. For exam-
between 0.003 and 0.2 inches, silts as grains
ple, the lateral pressure per unit depth, S, for a
between 0.003 and 0.00008 inches, and clays
firm sandy gravel is 300 lbm/ft2 per foot of depth.
as all particles finer than 0.00008 inches. The
This equates to an allowable pressure of 1200
distribution of these particles within a given soil
lbf/ft2 (4 ft x 300 lbm/ft2 per ft x 1lbf/lbm) for
has a major impact of soil behavior. A soil with a
points four feet below grade. [Note: use of
wide distribution of particle sizes is referred to
as a well-graded soil. A poorly graded soil is variable SL to represent S when adjusted for
comprised of similar sized particles. The best depth, is unique to this design manual, and
soils for foundation design are gravels and is done to avoid confusion between values
sands, with well-graded gravels and sands, bet- that have and have not been adjusted for
ter than poorly graded gravels and sands. Or- depth. It is important to realize that SL and S
ganic silt, peat and soft clay soils are not suit- have different units.]
able for post foundations, as they have neither
the strength nor the stability to support structural 8.3.6 Soil Tests. Site-specific soil test results
loads. are often used to determine allowable soil pres-
sures. Such calculations generally result in
8.3.3 Soil Moisture Content. The effective higher allowable design values than would be
shear strength of a soil can be reduced signifi- obtained using table 8.1. This is because pre-
cantly when soil is allowed to saturate with wa- sumptive values are the lowest values associ-
ter. To avoid water saturation of soils around ated with a broad classification of soils, each at
posts, install rain gutters, and slope the finish their minimum strength conditions.
grade away from the building. A minimum 2%
slope for a distance of at least 6 ft (2 m) from the 8.3.7 Soil Sampling. Soil samples should be
building walls is recommended. gathered from the applicable location in the soil
profile: one-third the foundation depth for lateral
8.3.4 Soil Density and Depth. Allowable verti- soil pressure calculations for non-constrained
cal and lateral soil pressures increase with in- posts; and at footing depth for lateral soil pres-
creases in soil density and depth. This is be- sure calculations for constrained posts and for
cause soil confinement pressures increase as vertical soil pressure calculations. From each
both of these variables increase. soil sample, the cohesion, c, angle of internal
friction φ, and bulk density, w, must be deter-
8.3.5 Tabulated Design Values. Table 8.1 mined.

8-3
National Frame Builders Association Post-Frame Building Design Manual

Table 8.1. Presumed Soil Properties for Post Foundation Design (ASAE, 1999). For use in ab-
sence of codes or test.
Lateral Pressure Lateral
Density Vertical Friction
Per Unit Depth, S Sliding Density, w ±
or Con- Pressure, Sv ↓ Angle,
Class of Material ↑ Coeffi-
sistency 2 degrees
lbf/ft kPa per cient
← lbf/ft
2
kPa ° lbm/ft
2
kg/m
3
per ft m →

1. Massive crystalline bedrock - 1200 180 0.79 4000 200 - - -

2. Sedimentary and foliated rock - 400 60 0.35 2000 100 - - -

3. Sandy gravel and/or gravel (GW firm 300 45 - - - 38 120 2000


and GP) loose 200 30 0.35 2000 100 32 90 1500

4. Sand, silty sand, clayey sand, firm 200 30 - - - 30 105 1750


silty gravel and clayey gravel
(SW, SP, SM, SC, GM, and GC) loose 150 22.5 0.25 1500 75 26 85 1400

5. Clay, sandy clay, silty clay and medium 130 20 ″ - - 15 120 2000
clayey silt (CL, ML, MH and CH) soft 100 15 - 1000 50 10 90 1500

← Firm consistency of class 4 and the medium consistency of class 5 can be molded by strong finger pressure, and the firm con-
sistency of class 3 is too compact to be excavated with a shovel.
↑ The hydrostatic increase in lateral pressure per unit depth has been included in the equations of this chapter. Source: Table 29-
B UBC modified with the addition of firm and medium values from Hough (1969).
→ Sliding resistance source: Table 29-B UBC.
↓ Allowable foundation pressures are for footings at least 1 ft (300 mm) wide and 1 ft (300 mm) deep into natural grade. Pressure
may be increased 20% for each additional 1 ft (300 mm) of width and/or depth to a maximum of three times the tabulated value.
Source: Table 29-B UBC.
° Soil friction angle varies from soft to medium density for clay materials, and from loose to firm for sand and gravel materials.
Source: Merritt (1976).
± Soil density varies from soft to medium density for clay materials, and from loose to firm for sand and gravel materials. Source:
Hough(1969).
″ Multiply an assumed lateral sliding resistance of 130 lbf/ft (6 kPa) by the contact area. Use the lesser of the lateral sliding resis-
2

tance and one-half the dead load.

8.3.8 Allowable Vertical Soil Pressure c = soil cohesion, lbf/ft2 (Pa)


From Soil Test Data. The allowable vertical soil φ = soil angle of internal friction, de-
pressure for round or square footings, Sv, can grees
be estimated from site-specific soil test as: w = soil bulk density, lbm/ft3 (kg/m3)
g = gravitational constant, 1 lbf/lbm
Sv = SBC / FS (8-1) (0.00981 kPa m2/kg)
y = depth where soil allowable pressure
where: is calculated, ft (m)
b = footing diameter or length of one
Sv = allowable vertical soil pressure, side, ft (m)
lbf/ft2 (kPa)
FS = factor of safety (2.3 to 3.0) For shallow foundations, a factor of safety be-
SBC = ultimate soil bearing capacity, lbf/ft2 tween 2.3 and 3.0 is typically applied to vertical
(kPa) soil pressure (Whitlow, 1995). Equation 8.2 is a
modified Terzaghi-Meyerhoff equation taken
SBC = 0.6 g w b (Nq + 1) tan φ + from Whitlow (1995). Values compiled in table
(Nq - 1+ Nq tan φ)(g w y + c/tanφ) (8-2) 8.2 can be used to facilitate calculation of the
ultimate soil bearing capacity, SBC.
Nq = eπ tanφ tan2(φ/2 + 45)

8-4
National Frame Builders Association Post-Frame Building Design Manual

Table 8.2. Ultimate Bearing Capacity* For lateral earth pressures in drained soils, a
SBC = 0.6 w b T1 + factor of safety between 1.5 and 2.0 is typical
φ T2(w y + c T3) (Whitlow, 1995). Equation 8-2 assumes drained
Nq
deg. soils (i.e., the water table is located below the
T1 T2 T3
10 2.471 0.612 1.907 5.671 top of the footing). Equation 8-2 does not ac-
12 2.974 0.845 2.606 4.705 count for soil cohesion, therefore the equation is
14 3.586 1.143 3.480 4.011 conservative for clays. Values for the Rankine
passive pressure are given in table 8.3.
16 4.335 1.530 4.578 3.487
18 5.258 2.033 5.966 3.078
Table 8.3. Rankine Passive Soil Pressures
20 6.399 2.693 7.729 2.747 for Drained, Cohesiveless Soils
22 7.821 3.564 9.981 2.475 SRP, lbf/ft2 per ft
24 9.603 4.721 12.879 2.246 φ
Soil Density, lbm/ft3
26 11.854 6.269 16.636 2.050 deg.
95 100 105 110 115 120
28 14.720 8.358 21.547 1.881
10 135 142 149 156 163 170
30 18.401 11.201 28.025 1.732
12 145 152 160 168 175 183
32 23.177 15.107 36.659 1.600
14 156 164 172 180 188 197
34 29.440 20.532 48.297 1.483
16 167 176 185 194 203 211
36 37.752 28.155 64.181 1.376
18 180 189 199 208 218 227
38 48.933 39.012 86.164 1.280
20 194 204 214 224 235 245
40 64.195 54.705 117.061 1.192
22 209 220 231 242 253 264
42 85.374 77.771 161.244 1.111
24 225 237 249 261 273 285
44 115.308 112.317 225.659 1.036
26 243 256 269 282 295 307
46 158.502 165.169 321.635 0.966
28 263 277 291 305 319 332
50 319.057 381.429 698.295 0.839
30 285 300 315 330 345 360
* See Equation 8.2 for variable descriptions.
32 309 325 342 358 374 391
34 336 354 371 389 407 424
8.3.9 Allowable Lateral Soil Pressure From 36 366 385 404 424 443 462
Soil Test Data. The allowable lateral pressure 38 399 420 441 462 483 504
per foot of depth, S, can be estimated from site- 40 437 460 483 506 529 552
specific soil test data as: 42 479 504 530 555 580 605
44 527 555 583 611 638 666
S = SRP / FS (8-3) 46 582 613 643 674 704 735
50 717 755 793 830 868 906
where:

S = allowable lateral soil pressure, lbf/ft2 8.3.10 Adjustment to Allowable Vertical


per ft, (kPa per m) Pressure. Most codes allow for a 33% increase
FS = factor of safety (1.5 to 2.0) in the allowable vertical pressure values, Sv,
SRP = Rankine passive pressure for when post loads result from wind and seismic
drained, cohesiveless soils, lbf/ft2 forces acting alone or in combination with verti-
per ft, (kPa per m). cal forces (see Section 3.9.4). This adjustment
would apply directly to the Sv value from equa-
SRP = w g tan2(45 + φ/2) (8-4) tion 8-1, and is cumulative with the adjustments
described in Section 8.3.5 for the presumptive
w = soil bulk density, lbm/ft3 (kg/m3) Sv values listed in table 8.1. In this manual, a
φ = soil angle of internal friction, de- prime (‘) will be used to denote an allowable Sv
grees value that has been adjusted (i.e., Sv Î Sv’).
g = gravitational constant, 1 lbf/lbm
(0.00981 kPa m2/kg) 8.3.11 Adjustment to Allowable Lateral
Pressure. In addition to the 33% increase gen-
erally allowed when post loads result from wind

8-5
National Frame Builders Association Post-Frame Building Design Manual

and seismic forces (acting alone or in combina- when assessing the post lateral load resistance
tion with vertical forces), the allowable lateral capabilities. Also, the friction between the post
pressure, S, can be doubled when posts have a (and/or collar) and the surrounding soil are as-
spacing at least six times their width. This in- sumed to be negligible when assessing the ver-
crease is due to the multi-dimensional nature of tical load-carrying capability of a given post
pressure distribution in the soil around isolated foundation design.
posts as depicted in figure 8.1, and described in
Section 8.1.3. In this manual, a prime (‘) will be 8.5 Collars
used to denote an allowable S value that has
been adjusted (i.e., S Î S’).
8.5.1 General. When lateral soil pressures ex-
ceed allowable values, additional lateral surface
8.4 Footings area can be obtained by increasing post depth,
or by adding a structural element called a collar.
8.4.1 General. Typically, the soil is not able to A collar is typically either concrete cast around
resist applied vertical loads when those loads the base of the post (and considered to be at-
are transferred through the post alone. There- tached to the post) or built-up wood attached to
fore, the post is set on some type of footing, the post. These structural elements are repre-
which is installed in the hole prior to post place- sented in figure 8.4.
ment. Footings in post-frame construction are
usually poured concrete. This type of footing is 8.5.2 Location. The collar increases the lateral
depicted in Figure 8.4. Generally there is no load resistance capability of the post foundation
mechanical attachment of the footing to the post. by increasing the bearing area in the region of
the post where lateral soil capability is relatively
8.4.2 Friction. A footing is assumed to only re- high. Collars are typically not placed at the top of
sist vertical loads; the friction between the foot- the post foundation (at the surface of the
ing and the post is assumed to be negligible ground) due to the possibility of frost heave.

Ground level

Post

Original excavated post


hole and backfill region

Poured concrete collar


Built-up wood collar

Footing

(a) (b)

Figure 8.4. Examples of common post foundation elements with (a) a poured concrete
collar, and (b) a built-up wood collar.

8-6
National Frame Builders Association Post-Frame Building Design Manual

8.5.3 Attachment. Whether poured concrete or effective post width, b, which in turn, is a func-
wood, the collar must be attached to the post in tion of post size and shape.
a manner sufficient to carry the structural loads
involved. As with any wood structural element For posts whose narrow face is pushing on the
exposed directly to the soil, appropriate pre- soil:
servatives and fastener systems must be em-
ployed to maintain structural integrity over the b = 1.4 B (8-5)
design life of the building.
where:
8.6 Backfilling
b = effective post width, ft (m)
B = width of post face pushing on the
8.6.1 General. The details of backfilling are of- soil, ft (m)
ten overlooked by the designer, and with poten-
tially dire consequences. After the footing and For posts whose wide face is pushing on the
post are installed (and the collar, if required), the soil, b is equal to the diagonal dimension of the
hole that was dug or drilled is backfilled. Essen- post.
tially, the material used for backfill is the medium
through which some, if not all, transverse loads For poles, the effective post width, b, is equal to
are passed from the post to the virgin soil. Back- the pole diameter.
fill material is subjected to higher pressures than
the surrounding virgin soil due to its proximity to
the post. Therefore, material used for backfill 8.7 Design for Lateral Loadings
and its installation are critically important for the
successful performance of a post foundation 8.7.1 General. Bending moments and post
design. shears cause lateral movement of the post
foundation. Designers must insure that this
8.6.2 Materials. Typical materials for backfill movement does not induce soil stresses that
include concrete, well-graded granular aggre- exceed allowable lateral soil pressures. If the
gate, gravel, sand, or soil initially excavated from allowable lateral soil pressure is exceeded, the
the post hole. These alternatives are listed in the designer must increase the lateral soil bearing
order of decreasing stiffness. area by adding a collar, by increasing embed-
ment depth, d, and/or by increasing effective
8.6.3 Concrete. While concrete is the stiffest post width, b. In the majority of cases, the most
backfill material, it is also the most expensive. economical way to increase bearing area is to
Concrete backfill essentially increases post increase post depth. For this reason, embed-
width, b. It must be installed with attention to the ment depth, d, is the dependent variable in most
possibility of frost heave (discussed later). design equations. Occasionally a designer will
add an extra laminate to the embedded portion
8.6.4 Excavated Soil. The most common back- of a laminated post to increase effective width.
fill material is the excavated soil. If used as More often, designers will backfill all or a portion
backfill, it should be free of topsoil and organic of the hole with concrete, which is akin to adding
matter. Silt- or clay-based soils should be moist a concrete collar.
(not wet) and well packed.
8.7.2 Assumptions. Equations in 8.7.3 and
8.6.5 Compaction. Backfill materials should be 8.7.4 assume that only the post (and not the
tamped or vibrated upon backfill in maximum footing) resists lateral loads. This is because
layers (a.k.a. lifts) of 8 inch (400 mm). variations in vertical post loads make it impossi-
ble to rely on post-to-footing friction for lateral
8.7 Post Dimensions load resistance.

8.7.3 Required Embedment Depth for Non-


8.7.1 Effective Width. Design equations for Constrained Posts Without Collars. Two dif-
lateral loading (Section 8.7) are a function of ferent load cases for a non-constrained, non-
collared post are shown in figure 8.2: The first

8-7
National Frame Builders Association Post-Frame Building Design Manual

load case (a.k.a. Load Case A ) represents con-


ditions where groundline shear and groundline where:
bending moment both cause the embedded por-
tion of the post to rotate in the same direction. A = 2.34 P / (SL’ b)
Load Case B represents conditions where b = effective post width, ft (m)
groundline bending moment causes the embed- d = post embedment depth, ft (m)
ded portion of the post to rotate in an opposite P = applied lateral force, lbf (N)
direction than the rotation caused by groundline h = distance from ground surface to
shear. Minimum post embedment depth, d, for point of application of force P, ft (m)
both Load Case A & B is calculated using one of SL’ = adjusted allowable lateral soil pres-
the following equations. sure at one-third the embedment
depth, lbf/ft2 (kPa)
From ASAE EP486 (1999a), AWPI (Patterson,
1969), and the UBC (ICBO, 1994): Equation T-1 was developed for point-loaded
posts that behave as pure cantilevered beams.
7.02 Va + 7.65 Ma / d Unfortunately, posts in post-frame buildings are
d 2= (8-6)
S’ b not point-loaded, and embedded posts are sup-
ported in such a way that they behave more like
From ASAE EP486.2 (1999b): propped cantilevers.

6 Va + 8 Ma / d To adjust equation T-1 so that it can be applied


d2= (8-7)
S’ b to posts subjected to a variety of loadings and
“above-grade” constraint conditions, load P is
where: replaced with an equivalent shear force and
bending moment located at the ground surface.
d = minimum embedment depth, ft (m) Using predefined nomenclature: Va is substi-
Va = shear force applied to foundation at tuted into equation T-1 for P, and Ma is substi-
ground surface, lbf (N) tuted for the product of P and h. In addition, the
Ma = bending moment applied to founda- adjusted allowable lateral soil pressure at one-
tion at ground surface, ft-lbf (N-m) third the embedment depth, SL’, is replaced by
S’ = adjusted allowable lateral soil pres- the quantity S’ d / 3. This substitution eliminates
sure, lbf/ft per ft (kPa/m per m) having to recalculate SL’ every time the embed-
b = effective post width, ft (m), see Sec- ment depth changes. With these substitutions,
tion 8.7.1 equation T-1 appears in ASAE EP486 (1999a)
as:
Equations 8-6 and 8-7 must be solved by itera-
tion. For Load Case B, Va and Ma must be input d 2 = 3.51Va/(S’ b)[1+(1+(0.62 Ma S’ b d)/ Va2)1/2]
with opposing signs. Note that equation 8-6 is in
a slightly different form than appears in any of Because it is somewhat confusing, the ASAE
the three referenced documents. See the follow- EP486 equation was rewritten for this design
ing technical note on equation development for manual in the form of Equation 8-6.
additional information.
The first major revision to ASAE EP486 (due for
release in 2000) will contain several changes,
Technical Note including a switch from equation 8-6 to equation
Non-Constrained Post Equations 8-7. Equation 8-7 is based on five common as-
sumptions: (1) only the post (and not the footing)
Equation 8-6 for the embedment depth, d, of resists lateral loads, (2) the post behaves as a
non-constrained, non-collared posts appears in rigid body below grade (3) soil type remains
most code documents as: constant, (4) at a given depth, soil resisting
pressure, q, is equal to the product of soil stiff-
d = 0.5 A [1 + (1 + 4.36 h / A)1/2] (T-1) ness, k, and lateral post movement at that
depth, and (5) soil stiffness, k, at a distance, y,

8-8
National Frame Builders Association Post-Frame Building Design Manual

below grade is equal to the product of the hori- soil pressure, q, does not exceed the adjusted
zontal subgrade reaction, nh, and the distance allowable lateral soil pressure, SL’ = S’ y. It can
below grade, y. In equation form, the soil resist- be shown that every time a designer does this,
ing pressure, q, for a non-constrained, non- the depth at which the actual soil pressure is
collared post is given by Meador (1997) as: closest to the allowable pressure is right at the
surface. In other words, for a non-constrained
q = nh ∆ (y – y2/do) (T-2) post, the designer does not need to compare S’
y and q from equation T-5 at every value of y,
where: instead, the designer only needs to check it at y
= 0. It follows that the embedment depth, d,
q = actual soil pressure at a depth y needed to ensure that the actual soil pressure
below grade, lbf/ft2 (kPa) does not exceed the allowable soil pressure at
nh = constant of horizontal subgrade re- the surface (or any point below the surface) is
action, lbf/ft4 (N/m4) given as:
∆ = lateral post deflection at grade, ft
(m) d 2 = (18 Va + 24 Ma / d )/(S’ b) (T-6)
y = depth below grade, ft (m)
do = distance from surface to point of Equation T-6 is not used in practice as field and
post rotation in soil, ft (m), (see fig- laboratory tests have shown that it is extremely
ure 8.2) conservative for non-constrained posts. This is
because when actual soil pressures at the sur-
Equation T-2 is a parabolic function that pro- face equal the allowable soil pressure, the ac-
duces the soil pressure profile shown in figure tual soil pressure at points below the surface are
8.2. If a summation of the horizontal forces in below (and in most cases substantially below)
figure 8.2 is set equal to zero, and the bending allowable soil pressures. Consequently, non-
moment around any point is equated to zero, the constrained post foundations are no where near
following two equations can be obtained for the failure when allowable soil pressures near the
grade deflection ∆, and distance to post rotation surface are exceeded. A more realistic embed-
point, do. ment depth is obtained by replacing S’ in equa-
tion T-6 with 3S’. The resulting equation is equa-
∆ = (24 Ma + 18 Va d)/(d 3 nh b) (T-3) tion 8-7. Note that when this equation is used,
actual soil pressure will exceed allowable soil
do = (3 Va d + 4 Ma)/(4 Va + 6 Ma /d) (T-4) pressure for points between y = 0 and y = 2do/3,
and for points deeper than y = 4do/3.
Examination of equation T-4 shows that the
point of post rotation is two-thirds the embed- For an in-depth discussion and greater detail on
ment depth when there is no shear in the post at non-constrained post foundation equation de-
the ground surface (Va = 0). When there is no velopment see Meador (1997).
moment in the post at the ground surface (Ma =
0), the point of post rotation is located at three-
quarters of the embedment depth. If both Va and 8.7.4 Required Embedment Depth for Con-
Ma are positive and non-zero, the point of rota- strained Posts Without Collars. A free body
tion is between two-thirds and three-fourths of diagram of a constrained, non-collared post is
the embedment depth. shown in figure 8.3. Minimum post embedment
depth, d, for the constrained, non-collared case
Substitution of equation T-3 into equation T-2 is calculated using one of the following equa-
yields the following equation for soil pressure: tions.

q = (18 Va + 24 Ma/d)(y – y 2/do)/(d 2 b) (T-5) From ASAE EP486 (1999a), AWPI (Patterson,
1969), and the UBC (ICBO, 1994):
Typically, a designer selects a value for d, such
1/3
that for all points below the surface, the actual 4.25 Ma
d= (8-8)
S’ b

8-9
National Frame Builders Association Post-Frame Building Design Manual

From ASAE EP486.2 (1999b):


of these is a switch from equation 8-8 to equa-
1/3
4 Ma tion 8-9. Equation 8-9 is based on the same as-
d= (8-9) sumptions as described for equation 8-7. These
S’ b
assumptions result in the following equation for
where: actual soil resisting pressure, q, for a con-
strained, non-collared post (Meador, 1997):
d = minimum embedment depth, ft (m)
Ma = bending moment applied to founda- q = nh y 2 ∆ / d (T-2)
tion at ground surface, ft-lbf (N-m)
S’ = adjusted allowable lateral soil pres- where:
sure, lbf/ft per ft (kPa/m per m)
b = effective post width, ft (m), see Sec- q = actual soil pressure at a depth y
tion 8.7.1 below grade, lbf/ft2 (kPa)
nh = constant of horizontal subgrade re-
Note that equation 8-8 is in a slightly different action, lbf/ft4 (N/m4)
form than appears in any of the three referenced ∆ = lateral movement of post at a depth
documents. See the following technical note on y = d, ft (m)
equation development for additional information. y = depth below grade, ft (m)

Equation T-2 is a parabolic function that pro-


duces the soil pressure profile shown in figure
Technical Note 8.3. If the bending moment around any point in
Constrained Post Equations figure 8.3 is equated to zero, the following equa-
tion is obtained for the lateral movement, ∆, of
Equation 8-8 for the embedment depth, d, of the post at a depth, d.
constrained, non-collared posts appears in most
code documents as: ∆ = 4 Ma /(d 3 nh b) (T-3)
1/2
d = [4.25 P h / (SL’ b)] (T-1) Substitution of equation T-3 into equation T-2
yields the following equation for soil pressure:
where:
q = 4 Ma y 2/(d 4 b) (T-4)
d = post embedment depth, ft (m)
P = applied lateral force, lbf (N) The actual soil pressure increases at an increas-
h = distance from ground surface to ing rate as y increases. The allowable lateral
point of application of force P, ft (m) soil pressure, SL’, increases at a constant rate
SL’ = adjusted allowable lateral soil pres- as y increases (note: SL’ = S’ y). This means that
sure at the full embedment depth, if a designer ensures that the actual soil pres-
lbf/ft2 (kPa) sure, q does not exceed the allowable pressure
b = effective post width, ft (m) at a depth, y = d, then the actual stress will be
less than the allowable for all points between the
Equation 8-8 is derived from equation T-1 by ground surface and y = d. In equation form:
substituting bending moment, Ma, for the product
of P and h, and replacing SL’ with the quantity S’ y > q = 4 Ma y 2/(d 4 b) for y = d (T-5)
S’d. This latter substitution eliminates having to
recalculate SL’ every time the embedment depth Equation T-5 becomes equation 8.9 after it is
changes. rearranged so that d is the dependent variable.
As described in the previous technical note on For an in-depth discussion and greater detail on
non-constrained posts, the first major revision to constrained post foundation equation develop-
ASAE EP486 will contain several changes. One ment see Meador (1997).

8 - 10
National Frame Builders Association Post-Frame Building Design Manual

8.7.5 Required Embedment Depth for Posts


With Collars. This design manual does not con- Ground
tain embedment equations for posts with collars. Level
For such equations, see ASAE EP486 (1999a,
1999b) and Meador (1997).
Post
8.8 Design for Downward Loadings

8.8.1 Required Footing Area. Downward Ap dT


φ
forces are resisted by the footing. The footing
area, A, required to resist these forces is:

A = P / SV’ (8-10)

where:

A = required footing area, ft2 (m2) r / tan φ


P = vertical foundation load, lbf (N) Collar
SV’ = adjusted allowable vertical soil Footing
pressure, lbf/ft2 (kPa) (see Section
8.3.10)
2r

8.9 Design for Uplift Loadings Figure 8.5. Schematic of relevant uplift resis-
tance components for post foundation with an
8.9.1 General. If the net vertical force acting on attached circular collar.
a post is upward, either the footing or a collar
must be attached to the post. When the footing
or a collar is attached to the post, upward
movement of the post foundation cannot occur
without displacing a cone-shaped mass of soil. Ground
The mass of this of soil depends on foundation Level
depth, footing (or collar) size, soil density, and
soil internal friction angle.
Post
8.9.2 Skin Friction. An attached footing or col-
lar is required to resist uplift forces because skin
friction between a post and backfill cannot be
relied on to resist such forces. AP
dT
φ
8.9.3 Concrete Backfill. Concrete cast against
undisturbed soil and mechanically fastened to
the post adds uplift resistance of both the con-
crete mass and the skin friction between the
concrete and soil. Note that this practice is not Collar
recommended in soils with a high susceptibility
to frost heave
l1 l2
8.9.4 Volume of Displaced Soil. The volume of
soil that must be displaced when pushed up- Unattached Footing
ward by a footing or collar is dependent on the
shape of the footing or collar. Figures 8.5 and Figure 8.6. Schematic of relevant uplift resis-
8.6 show configurations for circular and rectan- tance components for post foundation with an
gular foundation elements, respectively. attached rectangular collar.

8 - 11
National Frame Builders Association Post-Frame Building Design Manual

The volume of displaced soil, VS, is calculated forced upward.


using the following equations:
8.10.2 Problems. Frost heave can induce
For circular footings and collars: large differential movements in the foundation.
This differential movement can crack building
VS = π dT [r 2 + dT r tanφ + dT 2 tan2φ / 3] – finishes, and induce significant stress in struc-
dT Ap tural connections and components. When ice
lenses thaw, soil moisture content increases
For rectangular footings and collars: dramatically. The soil is generally in a saturated
state with reduced strength. As soil water drains
VS = dT (l1 l2 - Ap) + dT2 tanφ (l1 + l2) + from the soil, effective soil stresses increase and
dT 3π tan2φ / 3 the foundation will generally settle.

where: 8.10.3 Minimizing Frost Heave. Frost heave


VS = volume of displaced soil, ft3 (m3) can be minimized by: (1) avoiding clays and
dT = distance from ground surface to top silts, (2) extending footings below the frost line,
of collar, or to top of footing if collar and (3) providing good drainage.
is not present, ft (m)
r = radius of collar, or footing if collar is 8.10.3.1 No Silts and Clays. Fine grained
not present, ft (m) soils such as clays and silts are more sus-
φ = angle of internal soil friction ceptible to frost heave because (1) water is
Ap = post cross-sectional area, ft2 (m2) drawn upward by the fine pores which func-
l1, l2 = length and width of a rectangular tion as capillaries, and (2) there is much
collar or footing, ft (m) more surface area in a unit volume of fine
grained soil, and therefore more surface
8.9.5 Uplift Resistance, U. The resistance to area for water adsoprtion.
uplift, U, is calculated as:
8.10.3.2 Footing Depth. The most sure
U = g ( MF+ w VS ) (8-11) fire way to avoid frost heave problems is to
locate the footing where water never freeze.
where: It is for this reason that codes require foun-
dations to be located below the frost line.
U = uplift resisting force, lbf (N) Exceptions include footings on rock and
MF = mass of all foundation elements that floating foundation systems. A floating foun-
are attached to the post, lbm (kg) dation is reinforced so that it can float as a
w = soil density, lbm/ft3 (kg/m3) monolithic unit as the soil swells and
dT = distance from ground surface to top shrinks.
of collar, or to top of footing if collar
is not present, ft (m) 8.10.3.3 Water Drainage. Proper surface
VS = volume of displaced soil, ft3 (m3) and subsurface drainage can reduce frost
g = gravitational constant, 1 lbf/lbm heave. Drainage of surface waters from a
(9.81 N/kg) builder is enhanced by installing rain gutters,
adequately sloping the finish grade away
from the building, and raising the building
8.10 Frost Heave Considerations elevation to a level above that of the sur-
rounding area. Subsurface drainage is
8.10.1 General. Freezing temperatures in the achieved with the placement of drain tile or
soil result in the formation of ice lenses in the coarse granular material below the maxi-
spaces (a.k.a. pores) between soil particles. mum frost depth, with drainage to an outlet.
Under the right conditions, these ice lenses will Such drainage lowers the water table and
continue to attract water and increase in size. interrupts the flow of water moving both ver-
This expansion of the ice lenses increases soil tically and horizontally through the soil.
volume. If this expansion occurs under a footing,
or alongside a foundation element with a rough
surface, that portion of the foundation will be

8 - 12
National Frame Builders Association Post-Frame Building Design Manual

8.10.4 Concrete Floors. If the ground beneath Merritt, F.S. 1976. Standard Handbook for Civil
a concrete floor can freeze, the floor should be Engineers, pp. 7-53.
installed such that its vertical movement is not
restricted by embedded posts or by structural Patterson, D. 1969. Pole Building Design.
elements attached to embedded posts. While American Wood Preservers Institute (AWPI),
concrete shrinkage may break bonds between a Washington D.C.
floor and surrounding components, more proac-
tive measures will ensure independent vertical Whitlow, R. 1995. Basic Soil Mechanics. 3rd edi-
behavior. For example, plastic film can be tion. John Wiley & Sons, Inc. New York, NY
placed against surrounding surfaces prior to
pouring the floor.

8.10.5 Concrete Backfill. The use of poured


concrete as a backfill material may actually in-
crease the likelihood of frost heave. The rough
soil-to-concrete backfill interface provides the
potential for significant vertical uplift forces due
to frost heave. Also, the placement of concrete
in holes that decrease in diameter with depth
provide additional risk for frost heave.

8.10.6 Top Collars. Although common in past


years, placement of collars at the ground sur-
face (to increase lateral load resistance) has all
but been abandoned due to frost heave consid-
erations.

8.11 References

ASAE. 1999a. ASAE EP486: Post and pole


foundation design. Shallow post foundation de-
sign. ASAE Standards, 46th Edition. ASAE,. St.
Joseph, MI

ASAE. 1999b. ASAE EP486.2: Shallow post


foundation design. In review. ASAE. St. Joseph,
MI.

Hough, B.K. 1969. Basic Soils Engineering, 2nd


Edition. Ronald Press Co. Table 7-2, p. 249.

International Conference of Building Officials


(ICBO). 1994. Uniform Building Code, 1994 Edi-
tion. ICBO, Whittier, CA

McGuire, P. M. 1998. Overlooked assumption in


nonconstrained post embedment. ASCE Prac-
tice Periodic on Structural design and Construc-
tion, 3(1):19-24.

Meador, N.F. 1997. Mathematical models for


lateral resistance of post foundations. Trans of
ASAE, 40(1):191-201.

8 - 13
National Frame Builders Association Post-Frame Building Design Manual

8 - 14
National Frame Builders Association Post-Frame Building Design Manual

Chapter 9: DESIGN EXAMPLE

9.1 Introduction 9.2 Step 1: Modeling

9.1.1 General. Structurally efficient post-frame 9.2.1 General. The structural model for this ex-
buildings utilize the roof as a diaphragm to resist ample building follows that in Section 5.2. The
horizontal wind forces. This chapter presents an frames are numbered from one to seven begin-
example of diaphragm design following the five ning on the left end. That portion of the roof dia-
steps outlined in Section 5.1.4. phragm between each frame is broken into two
discrete segments labeled 1a, 1,b, …6a, 6b.
9.1.2 Building Specifications. Table 9.1 lists See Figure 9.1.
design parameters for the example building.
1 2 3 4 5 6 7
Table 9.1. Example Building Specifications
Width (truss length) 36 ft
Length (along ridge) 60 ft 1a 2a 3a 4a 5a 6a
Height at post bearing 12 ft
Roof slope 4/12 (18.43°) 1b 2b 3b 4b 5b 6b
Bay spacing 10 ft
Number of frames
7
(including end walls)
Figure 9.1. Identification of frame elements and
Post embedment depth 4 ft roof diaphragm segments.
Post grade & species No.2 S. Pine
Post size Nom. 6- by 6-in. 9.3 Step 2: Stiffness Properties
Roof snow load 30 psf
Roof dead load 5 psf 9.3.1 Frame Stiffness, k. One reliable way to
Concrete slab? Yes determine frame stiffness is to use a plane-
frame analysis program such as the PPSA pro-
Ceiling? No gram mentioned in Section 5.3.2. In this exam-
ple, all posts will be considered fixed at the
grade line and pin connected to trusses (figure
9.1.3 Wind Loads. It is assumed that the ex- 5.5). Consequently, the stiffness of each em-
ample building is located in a jurisdiction that bedded post can be calculated using equation 5-
has adopted the 1994 Uniform Building Code. 3 which is given as:
Design wind loads calculated according to this
code are presented in Table 9.2 kp = 3 E I / Hp3

Table 9.2. Wind Loads For the nominal 6- by 6-inch No. 2 Southern
Wind speed 80 mph Pine posts:
Exposure category B
E = 1.2 x 106 lbf/in.2 (No adjustment for
Windward wall, qww 8.13 psf wet conditions is necessary for
Leeward wall, qlw -5.08 psf * Southern Pine timbers. It is gener-
Windward roof, qwr 3.05 psf ally required for laminated posts.)
Leeward roof, qlr -7.12 psf * I = 76.26 in.4
Hp = 144 in.
* Negative loads act away from the surface in
question. Positive loads act toward the sur- Thus, kp = 91.9 lbf/in.
face in question.

9-1
National Frame Builders Association Post-Frame Building Design Manual

Frame stiffness, k, is obtained by summing indi- 9.3.3 Shearwall Stiffness, ke. There are no
vidual post stiffness values (equation 5-2). This large doors in the endwalls of the example build-
summation yields: ing. Lacking a specific tested endwall assembly,
the 12 ft high endwalls will be assumed to have
k = 184 lbf/in. the same shear stiffness as an 8 ft section of the
roof diaphragm; that is, ke will be set equal to Ch
9.3.2 Diaphragm Stiffness, Ch. The diaphragm or 12,640 lbf/in.
assembly used in this example is Test Assembly
11 in Table 6.1. Its properties are summarized in
Table 9.3. 9.4 Step 3: Eave Loads

Table 9.3. Diaphragm Properties 9.4.1 Windward Roof Pressures. As noted in


Metal thickness 29 gage Section 9.1.3, this example uses wind loads cal-
culated in accordance with the 1994 UBC. Pres-
Assembly width, 3 x a 36 ft
sure coefficients (from UBC table 16-H) for
Assembly length, b 12 ft windward roof slopes between 2/12 and 9/12
Allowable shear strength, va 107 lbf/ft are -0.9 (outward) and 0.3 (inward). It is impor-
Effective in-plane shear tant to recognize the significant impact that wind
3700 lbf/in.
stiffness, c direction (inward or outward) has on calculated
Effective shear modulus, G 3700 lbf/in. eave loads. The 3.05 psf design windward roof
pressure listed in table 9.2 was calculated using
In-plane shear stiffness for a single diaphragm the 0.3 pressure coefficient. When combined
section is calculated using equation 6-9, which with the negative pressure of 7.12 psf on the
is given as. leeward roof, the net lateral roof pressure is
10.17 psf. If the –0.9 pressure coefficient would
G bh have been used, the net lateral roof pressure
cp = would have been –2.03 psf.
s cos(θ)

Substitution of appropriate values yields: 9.4.2 Fixity Factors, f. Based on the assump-
tion of a post fixed at the groundline (see Sec-
tion 9.3.1), a fixity factor of 3/8 is appropriate for
(3700 lbf/in.)(18 ft)
cp = this example.
(10 ft)(cos(18.43))
9.4.3 Eave Load, R. Since this example uses
cp = 7020 lbf/in.
symmetrical base restraint and frame geometry,
equation 5-6 may be used.
The horizontal shear stiffness, ch, of a single
diaphragm section is calculated using equation
R = s [hr (qwr – qlr) + hw f (qww – qlw)]
6-10 which is given as:
where:
ch = cp cos2 (θ)
hr = (36 ft /2) (4/12) = 6 ft
Substitution of appropriate values yields:
hw = 12 ft
s = 10 ft
ch = (7020 lbf/in.) cos2(18.43°) f = 0.375
= 6320 lbf/in.
or
Total horizontal shear stiffness of a diaphragm
element, Ch, is found by summing the stiffness R = 10 ft [6 ft (3.05 psf + 7.12 psf) +
values of the two sections that comprise each 12 ft (.375)(8.13 psf + 5.08 psf)]
diaphragm element (see equation 5-4).
R = 1205 lbf
Ch = 6320 + 6320 = 12,640 lbf/in.

9-2
National Frame Builders Association Post-Frame Building Design Manual

For later calculations, it is convenient to calcu- Q = mD R = 0.90(1205 lbf) = 1085 lbf


late R in terms of its components – roof, wind-
ward wall and leeward wall. The difference between eave load, R, and the
horizontal restraining force, Q, is the amount of
RR = 10(6)(3.05 + 7.12) = 610.2 lbf the eave load that is transferred by the center
RW = 10(12)(.375)(8.13) = 365.8 lbf post-frame to the foundation.
RL = 10(12)(.375)(-5.08) = -228.6 lbf
RR + RW – RL = 1205 lbf R – Q = 120 lbf

The eave deflection, ∆, for a post-frame with


9.5 Step 4: Load Distribution stiffness, k, subjected to an eave load, R, and
horizontal restraining force, Q, is given as:
9.5.1 Introduction. For this example problem,
diaphragm shear stiffness, Ch, frame stiffness, k, ∆ = (R – Q) / k
endwall stiffness, ke, and eave load, R, are all
constant. Consequently, in addition to analysis Eave deflection for the center post-frame is
methods such as DAFI, load distribution can be given as:
determined using the ANSI/ASAE EP484.2 ta-
bles (Section 5.6.3) and the simple beam anal- ∆ = (1205 lbf – 1085 lbf) / 184 lbf/in.
ogy equations (Section 5.5.6). For comparison
purposes, all three methods are demonstrated ∆ = 0.652 in.
here (Sections 9.5.2 – 9.5.4). The information
obtained from these analyses is then used to 9.5.3 Simple Beam Analogy Equations. As
determine the maximum diaphragm shear force previously noted, the simple beam analogy
(Section 9.5.6) and maximum post forces (Sec- equations for diaphragm shear force, Vh, and
tion 9.5.7). diaphragm displacement, y, can be used when
R, k, ke and Ch are constant. These two equa-
9.5.2 ANSI/ASAE EP484.2 Tables. In this de- tions are given in Section 5.6.6 as:
sign manual, the ANSI/ASAE EP484.2 tables
are tables 5.1 and 5.2. Table 5.1 contains shear Vh = Ch α s [A sinh(α x) + B cosh(α x)]
force modifiers or “mS” values. The product of
this modifier and eave load, R, is the maximum y = A cosh(α x) + B sinh(α x) + R/k
shear force in the diaphragm, Vh. Table 5.2 con-
tains sidesway restraining force modifiers or Input parameters and calculated equation con-
“mD” values. The product of this modifier and stants for the simple beam analogy equations
eave load, R, is referred to as the horizontal re- have been compiled for this example analysis in
straining force, Q, which is the amount of eave Table 9.4.
load transferred away from the center post-
frame(s) by the diaphragm. Maximum diaphragm shear is calculated by set-
ting x = 0 in., or:
Use of tables 5.1 and 5.2 requires two ratio: ke/k
and Ch/k. For this example analysis, both ratios Vh = 12,640 lbf/in.(1.0054x10-3 in.-1)
are equal to 69 (12640/184). Using linear inter- •(120 in.)[-6.286 in.(0) + 2.181 in.(1)]
polation, the mS value from table 5.1 is 2.77,
and the mD value from table 5.2 is 0.90. Vh = 3326 lbf

The maximum diaphragm shear force, Vh, which Maximum diaphragm displacement is calculated
occurs adjacent to each endwall, is given as: by setting x = L/2 = 360 in. , or:

Vh = mS R = 2.77(1205 lbf) = 3340 lbf y = -6.286 in.( 1.0662)


+ 2.181 in.( 0.3699)
The horizontal restraining force, Q, that must be + 1205 lbf/(184 lbf/in.)
applied to the center post frame (i.e., frame 4 in
figure 9.1) is given as: y = 0.6535 in.

9-3
National Frame Builders Association Post-Frame Building Design Manual

Table 9.4. Parameters for Simple Beam Anal- The force transferred to the foundation by the
ogy Equations center frame (frame 4) is equal to the product of
R 1205 lbf eave displacement, y, and frame stiffness, k, or:
s 120 in.
yk = 0.6535 in. (184 lbf/in.) = 120.2 lbf
L 720 in.
ke 12,640 lbf/in. The horizontal restraining force, Q, for the frame
k 184 lbf/in. 4 is equal to the difference between the eave
load, R, and the 120.2 lbf, or
R/ k 6.549 in.
Ch 12,640 lbf/in. Q = 1205 lbf – 120.2 lbf = 1084.8 lbf
α 1.0054x10-3 in.-1 *
αL 0.7239 Note that ye in table 9.4 is the eave displace-
ment of the endwall.
cosh(α L) 1.2737
sinh(α L) 0.7888 9.5.4 DAFI. As previously mentioned, DAFI is a
D -23.890 * computer program specifically written for deter-
ye 0.2631 in. * mining load distribution between diaphragms
and frames. DAFI can be downloaded free from
A -6.286 in. * the NFBA web site (www.postframe.org).
B 2.181 in. *
cosh(0) 1 The maximum shear force in the diaphragm. Vh,
sinh(0) 0 is numerically equal to the load resisted by the
endwall frame. In figure 9.2, this value is given
cosh(α 360 in.) 1.0662 as 3353.2 lbf. Note that this value is more pre-
sinh(α 360 in.) 0.3699 cise than the 3340 lbf value calculated from the
* Equations for calculation of these values are mS values in table 5.1 because the values in
given in Section 5.6.6. table 5.1 are only given to three significant fig-
ures. It is important to note that the shear load

FRAME FRAME APPLIED HORIZONTAL LOAD RESISTED FRACTION OF


NUMBER STIFFNESS LOAD DISPLACEMENT BY FRAME APPLIED LOAD
---------------------------------------------------------------------
1 12640.00 602.5 .2652868 3353.2 5.5655
2 184.00 1205.0 .4829074 88.9 .0737
3 184.00 1205.0 .6122254 112.6 .0935
4 184.00 1205.0 .6551232 120.5 .1000
5 184.00 1205.0 .6122254 112.6 .0935
6 184.00 1205.0 .4829074 88.9 .0737
7 12640.00 602.5 .2652867 3353.2 5.5655

DIAPHRAGM DIAPHRAGM SHEAR SHEAR


NUMBER STIFFNESS DISPLACEMENT LOAD
--------------------------------------------
1 12640.00 .2176206 2750.7
2 12640.00 .1293180 1634.6
3 12640.00 .0428978 542.2
4 12640.00 .0428979 542.2
5 12640.00 .1293180 1634.6
6 12640.00 .2176206 2750.7

Figure 9.2. Output from computer program DAFI for example building.

9-4
National Frame Builders Association Post-Frame Building Design Manual

listed for each diaphragm in the DAFI output is Diaphragm elements 1 and 6 are both subjected
essentially an average shear load in the dia- to the maximum horizontal shear, Vh, of 3350
phragm. For example, the average shear load in lbf. Consequently, the in-plane shear force in
diaphragm 1 is listed as 2750.7 lbf. To calculate diaphagm sections 1a, 1b, 6a and 6b is given
the maximum shear load in each diaphragm as:
element, simply add the quantity R/2 to the av-
erage value. For this example analysis, half the 6320 lbf/in (3350 lbf)
Vp =
eave load is 602.5 lbf. Adding this to the aver- 12,640 lbf/in (cos 18.43°)
age shear load in diaphragm 1 yields the ex-
pected maximum shear force in the diaphragm Vp = 1766 lbf
of 3353.2 lbf.
Dividing the in-plane shear force by the slope
The amount of eave load transferred to the length of a diaphragm section yields the in-plane
foundation by each frame is listed in figure 9.2 shear force on a unit length basis, vp.
under the column heading “load resisted by
frame.” The difference between this value and vp = 1766 lbf /(18 ft / cos (18.43°))
the eave load, R, is the horizontal restraining
force, Q. The load resisted by the most heavily vp = 93.1 lbf/ft
loaded frame (i.e., frame 4) is 120.5 lbf. This
equates to a horizontal restraining force for 9.5.7. Post Forces. The most critical posts from
frame 4 of 1084.5 lbf (1205 lbf – 120.5 lbf). a design perspective are those associated with
the most heavily loaded frame. In the example
9.5.5 Comparison of Methods. The ANSI/ building this is the center post-frame (a.k.a.
ASAE EP484.2 tables (tables 5-1 and 5-2), sim- frame 4).
ple beam analogy equations, and program DAFI
yield identical values for maximum diaphragm There are two basic methods for determining
shear, horizontal restraining force, and eave post forces. The first is to analyze the frame with
deflections. Again, it is important to note that the a plane-frame structural analysis program, the
ANSI/ASAE EP484.2 tables and the simple second is to assume the truss is rigid and then
beam analogy equations are restricted to de- use a series of equations to calculate post
signs with fixed values of Ch, k, R, and ke. Al- forces.
though DAFI is more versatile, a DAFI analysis
requires computer access. The simple beam A structural analog for a plane-frame structural
analog equations can be quickly solved with a analysis of frame 4 is shown in figure 9.3a. Post
hand calculator that supports hyperbolic trigo- forces obtained with this analog are given in fig-
nometric functions. ure 9.3b. For this example analysis, the load
combination of “full dead + full wind + ½ snow “
9.5.6 Diaphragm Shear. The maximum in- was used, with a roof dead load of 5 psf and a
plane shear force, Vp, in a diaphragm section is roof snow load of 30 psf (Note: in practice, the
calculated from the maximum horizontal shear building designer must check all applicable load
force, Vh, in the diaphragm elements using cases). The force applied to the frame by the
equation 5-9 which is given as: diaphragm, qp, was applied as a force of 30.12
lbf per foot of top chord. This force was obtained
Vp,i = (ch,i / Ch) Vh / (cos θ i) by first combining equations 5-10 and 5-11 into
the following equation:
For this example analysis, all six diaphragm
elements have the same Ch, and all twelve of q p,i = Q (c h,i / Ch ) / b i (9-1)
the diaphragm sections shown in figure 9.1 have
the same horizontal stiffness, ch and slope, θ, where: Q is the horizontal restraining force
that is: (1084.5 lbf for frame 4); ch,i is the horizontal
stiffness of diaphragm segment i (6320 lbf/in); Ch
Ch = 12,640 lbf/in. is the horizontal stiffness of diaphragm element i
ch,i = 6320 lbf/in. (12,640 lbf/in); and bi is the horizontal span of
θ = 18.43° diaphragm segment i (18 ft).

9-5
National Frame Builders Association Post-Frame Building Design Manual

s x (5 psf + 30 psf /2)


3820 lbf 2650 lbf

0 in.-lbf 0 in.-lbf
sx
7.1
psf 2p 313 lbf 161 lbf
x 3
.05 sf
s
Windward post
ft 30.1
lbf/ 2
12 lbf/f
30. t Leeward post

662 lbf 449 lbf


s x 8.13 psf

s x 5.08 psf
25100 in.-lbf 20700 in.-lbf

3821 lbf 2646 lbf

(a) (b)

Figure 9.3. (a) Structural analog for frame 4 of the example building (s = 10 ft). (b) Re-
sulting forces on post ends. Lateral deflection at the top of the windward and leeward
posts were 0.572 and 0.735 inches, respectively.

Roof dead + 1/2 snow = 7200 lbf

Vertical component of windward roof Vertical component of leeward roof


pressure = 549 lbf pressure = -1281.6 lbf
+ +
Vertical component of diaphragm Vertical component of diaphragm
restraining force = 180.75 lbf restraining force = -180.75 lbf

9 ft 9 ft 9 ft 9 ft
Horizontal component of windward Horizontal component of leeward roof
roof pressure = 183 lbf pressure = -427.2 lbf
3 ft 3 ft
+ +
Horizontal component of diaphragm 3 ft 3 ft Horizontal component of diaphragm
restraining force = -542.25 lbf restraining force = 542.25 lbf
Vtw Vtl

Pw = 3821 lbf Pl = 2646 lbf

Figure 9.4. Resultant of forces applied to truss of frame 4.

In lieu of a computer analysis, post axial forces


for a two-post frame can be obtained by drawing To obtain post shears and bending moments
a free-body diagram of the truss and summing without reliance on a computer is a straight for-
forces about each truss-to-post connection. ward process if the truss is assumed to be com-
Such a free-body diagram for frame 4 of the ex- pletely rigid. When this assumption is made, the
ample building is shown in figure 9.4. The axial lateral movement, ∆, of all posts at their truss
forces (Pw and Pl) obtained in this manner are attachment point will be equal to that obtained
identical to those obtained via the computer using the methods outlined in Sections 9.5.2,
analysis (figure 9.3). 9.5.3 and 9.5.4. Post shear and post bending

9-6
National Frame Builders Association Post-Frame Building Design Manual

moment can then be calculated using the follow- Using equation 9-2, the shears at the top, Vt,
ing equations which assume zero bending mo- and bottom, Vb, of the windward post of frame 4
ment at the top of the post. are:

Vy = kp ∆ – R i + s q (Hp – y) (9-2) Vt = (91.9 lbf/in.)(0.655 in.) – 365.8 lbf


+ (10 ft)(8.13 psf) (12 ft – 12 ft)
My = (s q / 2)(Hp – y)2 + Vt (Hp – y) (9-3)
Vt = –305.6 lbf
Mmax = - Vt2 / (2 s q) (9-4)
Vb = (91.9 lbf/in.)(0.655 in.) – 365.8 lbf
where: + (10 ft)(8.13 psf) (12 ft – 0 ft)

Vy = post shear at distance y from base, Vb = 670.0 lbf


lbf (N)
kp = post stiffness, lbf/in. (N/mm) and the shears at the top, Vt, and bottom, Vb, of
∆ = lateral movement of post top, in. the leeward post of frame 4 are:
(mm)
Ri = contribution of wall pressure to eave Vt = (91.9 lbf/in.)(0.655 in.) – 228.6 lbf
load, lbf (N) + (10 ft)(5.08 psf) (12 ft – 12 ft)
= RW for windward wall
= RL for leeward wall Vt = –168.4 lbf
s = frame spacing
q = wall pressure, lbf/ft2 (N/m2) Vb = (91.9 lbf/in.)(0.655 in.) – 228.6 lbf
Hp = post height, ft (m) + (10 ft)(5.08 psf) (12 ft – 0 ft)
y = distance from post base, ft (m)
My = bending moment in post at distance Vb = 441.2 lbf
y from base, lbf-ft (N-m)
Vt = Vy at y = Hp, lbf (N) Equation 9-3 yields bending moments at the
Mmax = bending moment at y = Hp + Vt /(sq) base of the windward and leeward posts of
(i.e., at the point of zero post shear) 26200 and 19640 lbf-in., respectively. The dif-
ference between these values and those in fig-
Positive sign conventions for the preceding vari- ure 9.3b are due to the rigid truss assumption.
ables are illustrated in figure 9.5.
According to equation 9-4, bending moments at
∆ the point of zero shear in the windward and lee-
ward posts are 6890 and 3350 lbf-in., respec-
tively.

9.6 Step 5: Check Allowable Values


y
9.6.1 Diaphragm Shear. The actual maximum
Vy
diaphragm shear stress of 93.1 lbf/ft (Section
s xq

Hp My 9.5.6) is less than the allowable of 107 lbf/ft (ta-


ble 9.3) so the diaphragm has sufficient
Vy
strength.

9.6.2 Windward Post Stresses. Posts are sub-


ject to combined bending and compression and
must be checked per the requirements of the
1997 NDS Section 3.9.2 and NDS equation 3.9-
Figure 9.5. Positive sign convention for vari- 3. This equation, simplified for uniaxial bending
ables used in equations 9-2 and 9-3. is:

9-7
National Frame Builders Association Post-Frame Building Design Manual

CSI = ( fc / Fc’ )2 +
f b / {Fb’ [ 1 – ( fc / FcE)]} < 1.0 (9-5) CD = 1.60 since the shortest duration load
in the combination of loads is wind
where: CM = 1.00 for modulus of elasticity, com-
pression and bending of Southern
CSI = combined stress index Pine timber regardless of moisture
fc = actual compressive stress content
fb = actual bending stress CF = 1.00 for nominal 6- by 6-inch No.2
Fc’ = allowable compressive stress Southern Pine
= Fc •CD •CM •CF •Ci •CP Ci = 1.00 since Southern Pine does not
Fb’ = allowable bending stress need to be incised for pressure
= Fb •CD •CM •CF •Ci •CL•Cr •Cf •CV treatments
FcE = critical buckling design stress CL = 1.00 since post is square
= K E’ I / ( le / d )2 Cr = 1.00 because post spacing exceeds
24 inches. Note that this value is
and: non-zero for mechanically laminated
posts
Fc = tabulated compressive stress Cf = 1.00 since posts are rectangular
Fb = tabulated bending stress CV = 1.00 since posts are not glued-
CD = load duration factor laminated
CM = wet service factor CP = 1.00 at the base of the post where
CF = size factor support is provided in both direc-
Ci = incising factor tions
CP = column stability factor CP = is less than 1.00 at locations re-
CL = beam stability factor
moved from supports that keep the
Cr = repetitive member factor
post from buckling. For such cases,
Cf = form factor
CP is calculated using NDS equation
CV = volume factor
3.7-1.
E’ = E •CM •Ci
I = moment of inertia
le /d = slenderness ratio It follows that at the base of both the windward
K = 0.3 for visually graded lumber and leeward posts:
= 0.384 for machine evaluated lumber
Fc’ = ( 525 lbf/in.2)(1.60) = 840 lbf/in.2
Actual stresses for the windward post are: Fb’ = ( 850 lbf/in.2)(1.60) = 1360 lbf/in.2
FcE = A very large number if the effective
fc = PW / A = 3821 lbf / (30.25 in.2) buckling length, le, is assumed to be
= 126 lbf/in.2 very small because of support at the
base. As a result, the ratio fc / FcE in
fb = M / S = 26200 lbf-in. / (27.73 in.3) equation 9-5 is assumed to equal
= 945 lbf/in.2 (at the base) zero.

fb = 6890 lbf-in. / (27.73 in.3) and at the base of the windward post:
= 248 lbf/in.2 (at point of zero shear)
CSI = ( 126 / 840 )2 + ( 945 / 1360 )
For No. 2 Southern Pine timber, the tabulated = 0.02 + 0.70 = 0.72 < 1.0 OK
compression and bending stresses and modulus
The other critical location to check the combined
of elasticity are:
stress index (CSI) is at the point of maximum
bending moment (point of zero shear) in the up-
Fb = 850 lbf/in.2
per portion of the post. At this location, the col-
Fc = 525 lbf/in.2
umn stability factor is generally based on an ef-
E = 1,200,000 lbf/in.2
fective column buckling length of 0.8 Hp (see
Applicable adjustment factors are:

9-8
National Frame Builders Association Post-Frame Building Design Manual

NDS Appendix G), which results in the following


slenderness ratio: The minimum embedment depth, d, is:
1/3
le / d = 0.8 (144 in.) / 5.5 in. = 20.9 4.25 (2180 lbf-ft)
d =
(532 lbf/ft3) (0.64 ft)
thus:
d = 3.00 ft < 4 ft OK
2 2
FcE = 0.3 (1200000 lbf/in. ) / (20.9)
= 820 lbf/in.2 9.6.4 Leeward Post Stresses. Because (1) the
axial force and maximum bending moments as-
The ratio of FcE / Fc is 0.976. This yields a Cp of sociated with the leeward post are all less than
0.682, resulting in the following allowable com- those for the windward post, (2) the windward
pressive stress, Fc’. and leeward posts are similarly supported, and
(3) the windward post is not overstressed, there
Fc’ = ( 525 lbf/in.2)(1.60)(0.682) is not need to check stresses in the leeward
= 573 lbf/in.2 post.

The CSI at the point of maximum moment in the 9.6.5 Leeward Post Embedment. Unless the
upper portion of the post is: post-frame designer makes special provisions to
tie the base of the leeward post to the floor slab,
CSI = ( 126 / 573 )2 it will be non-constrained. Since this is a UBC
+ 248 / [1360 (1 - 126/820)] jurisdiction, embedment depth will be checked
= 0.05 + 0.22 = 0.27 < 1.0 OK using equation 8-6, which is given as follows:

7.02 Va + 7.65 Ma / d
9.6.3 Windward Post Embedment. The wind- d2 =
ward post is constrained by the floor slab. Since S’ b
our example building is in an UBC jurisdiction,
embedment depth will be checked using equa- Solution of this equation is an iterative process.
tion 8-8 which is given as: The values for S’ and b are as determined for
the windward post. Leeward post base shear
1/3 and bending moment where previously calcu-
4.25 Ma
d= lated as 441 lbf and 1640 lbf-ft, respectively
S’ b
7.02(441 lbf) + 7.65(1640 lbf-ft)/d
For this example, the soil is assumed to be a d2 =
(532 lbf/ft3) (0.64 ft)
firm silty sand which puts it in class 4 (firm) of
Table 8.1 – a soil with a tabulated lateral soil
d = 4.22 ft > 4 ft
pressure of 200 lbf/ft per foot of depth. In accor-
dance with the UBC, the tabulated lateral pres-
At this point, the post-frame designer must apply
sure can be adjusted for wind loading by a factor
engineering judgement. It is important to re-
of 1.33. Since the posts are more than six di-
member that the analogs in this example pro-
ameters apart, the allowable lateral pressure
duce conservative values for base moments and
can also be doubled for isolated conditions.
shears, especially for the non-constrained case.
Thus, the allowable lateral soil bearing pressure
The designer must also consider what is known
is:
about the soil type and its variability on the build-
ing site. If an embedment of 4 ft rather than
S' = (200 lbf / ft2 / ft)(1.33)(2)
4.22 ft satisfies uplift requirements as calculated
= 532 lbf / ft2 / ft
elsewhere (not included in this example) an ex-
perienced post-frame designer could validly
As previously calculated, the moment at grade is
judge that an embedment of 4 ft. is OK.
26200 lbf-in or 2180 lbf-ft.

The effective width of the post, b, is:

b = (1.4)(5.5 in)/12 = 0.64 ft

9-9
National Frame Builders Association Post-Frame Building Design Manual

9.7 Example Summary

There are many items that the post-frame de-


signer must still check. These include but are
not limited to:

• The interconnection between diaphragms


and shearwalls
• Diaphragm chords
• Footings for gravity loads
• Uplift checks for embedded posts
• All secondary members and headers
• The connections of all members, especially
truss to post
• End wall posts
• Diaphragms and shearwalls for wind against
the endwall

This example has focused solely on those items


that are unique to post-frame. The post-frame
designer should be able to perform the remain-
ing checks and designs using commonly ac-
cepted practices and techniques.

9-10

You might also like