You are on page 1of 22

Large Bolted Joints

TESTS OF A490 BOLTS


(Preliminary Report)

by
Gordon Sterling
John W. Fisher

March 1964

SYNO-PSIS

Presented in this report are the results of calibration tests


t,

of individual ASTM A490 alloy steel bolts.

The b'olts tested were 7/8 in.

nominal diameter. ' Results of'twenty direct tension and thirty torqued
tension tests are reported.
This is a preliminary report and will eventually be re-written
to include information on similar tests conducted on the same bolt lots

'at, the University of Illinois.

INTRODUCTION

At the February 14, 1963 meeting of Committee 15 of the Research


Council on Riveted and Bolted Structural Joints, it was recommended that
Lehigh University and the University of

~llinois

conduct tests on bolts

from the same 'lot to determine if -testing procedures constitute a variable.

Each university was to test bolts in direct tension and torqued

tension using its own standard calibration procedures.


This report discusses the results of the tests conducted at
Lehigh.

The bolts were purposely ordered near the minimum specified

tensile strength.

-1-

TEST PREPARATION

Two lots of 7/8 in. diameter, heavy hexagon head, A490 bolts
were tested.'

B'efore testing', all bolts were st'arriped with a lot designation

and bolt nu~ber.

,of the' head and

In additio~, each ,bolt had ho~es ~ril1ed in the centers

nut 'ends ,to

accommodate the C-frame extensometer.

~~lts designate~ as AB ~ot were'9~ in. long wit~ 1~ in. of cut

thread.

'Those labelled' Lot' :U were 5~ in. long with 1% in. of rolled

thread.

In

al~

tests, one hardened washer was used under .n A194 Grade

2Hnut (heavy hexagon).

of
Lot

~hread

'

Each lot w~s tested with 1/8 in. and 9/16 in.

in the grip . This gave grip lengths of 8\ and 8-11/16 in. for

AB.. bolts, .and 4-1/8 in. and 4-9/16 in. grip for the, LI bolts.
A representative sample of twenty bolts and nuts from the AB

lot were'checked for tolerance by using the NC2A go and no-go ring gages
and the NC2B
able.

~o

and no-go plug gages.

All specimens tested were accept-

The AB lot bolts were received with a light coating of shipping oil.
The L1 lot bolts were received with a greasy film, but were not

, as'well lubricated as the AB bolts.


with the NC2A gages.

This lot of bolts was not checked

'The, same keg of nuts and washers was used in the

tests of both the AB and LI lots.

-2-

TEST PROCEDURE

a.

~ORQUED

TENSION TESTS

Specimens from both lots were tested in the Model M SkidmoreWilhelm calibrating device.

Ten bolts from the L1 lot were also tested

in a solid block of' A440 steel.


For all tests conducted in the Skidmore-Wilhelm calibrator
the nut was turned by using a hand wrench until a lI'snug" tension of
ten kips was reached in the bolt.

Bolt load, elongation and turn-of-

the-nu,t (in degrees) measurements were taken at 5 and 10 kips.

The nut

was then rotated in 45 increments (1/8 tur'n-of-the-nut) with a pneumatic impact wrench until failure oc'curred either by fracture or by

thread stripping.

Bolt elongation and load data were taken at each

45 increment of nut rotation.


From the tests done

in

the Skidmore-Wilhelm device a mean

elongation at a "snug" lo'ad of ten kips was determined for the L1 lot

specimens.

This mean elongation was applied to

thos~

specimens being

tested to failure in the solid A440 steel block by using a hand wrench
to turn the nut.
in~rements,

The bolt was then tested b~. turning the nut', in 45

using a pneumatic impact wrench.

Bolt elongation measure-

ments were taken at -each posi tioIJ, of, nut rotation.


al1owe~

This procedu're

a direct comparison of the nut rotation VB. elongation charac-

teristics of bolts tested by torquing in a block of A440 steel and in


the less rigid Skidmore-Wilhelm device.

-3-

-4..
,

b. DIRECT TENSION TESTS


As. a preliminary check the bolt being tested was loaded to the
specified proof load and then unloaded to check the ASTM requirement of

minimum 'permissible set (0.0005 in.).

No bolts were rejected by this

test. ,The 'bolt wa's then' reloaded and elongation readings were, taken

. at ten kip interva1s until the inelastic range was reached.

At this

point load readings were taken for every 0.01 in. of elongation in the
. bolt . The direct tension tests were conducted in a 300 kip Baldwin

hydraulic testing machine at a, strain rate of approximately 0.01 in. per


'minute.

A detailed description of the procedures used, in the calibrating


of bolts is given in Reference 1.

The reader is referred specifically to

Figures 1 and 2 of this ,report for the specific set ups used in the
direct and torqued tension tests$

liEST RESULTS

Table 1 and Figures 1 throughU summarize the test results.

The

actual test points are given on most figures, and, therefore, Table 1

merely indicates the significant mean values determined from all the tests.
The 'specified proof load'for these 7/8 in. diameter, A490 bolts is

1) John L. Rumpf ,and John W. Fisher


"Calibration of A325 Bolts", Journal of the Structural Division,
Va 89, No. ST6, Prec. Paper 3731, December, 1963, pp. 215-234.

~5.45

ASC~,

-5-

kips, (i,e. the load

to

which the bolt may be loaded so that after un-

loadi.ng there is no more than 0.0005

i~.

permanent set), and

the speci-

fied minimum ultimate load is 69.3 kips.


All the ,AB lot bolts failed

Four failure 'modes were noticed.

in the direct tension tests on a jagged diagonai through the threads.


Two of the AB lot bolts tested in torqued tension with 1/8 in. thread in

grip failed by thread stripping as did two L1 bolts in direct tension


'with the same amount 0, thread under the nut.

In all four cases, the

nut and bolt thread was so badly damaged that it was impossible to tell

which thread had originally failed.

The LI specimens tested in direct

tension with 9/16 in. thread in grip failed on a jagged diagonal as


noticed with the AB direct tension tests.

However, three bolts with

1/8 in. thread in the grip, failed on a level plane, through the threads,
The other two LI

at the juncture of the thread runout and bolt shank.


bolts failed in the diagonal manner previously noted.

All bolts tested

in torqued tension (with the exception of the two AB lot bolts that
stripped) failed by "twisting off" on' a level plane through the first
thread under the nut at the time of failure.
Figures 1 through 4 relate the load-elongation characteristics
of the bolts tested in direct and torqued tension.

In all cases bolts

tested with 1/8" thread in grip gave.greater ultimate load than bolts
from the same lot tested in the same manner with 9/16" thread' in grip;
however, the specimens with 9/16" thread in grip sustained greater deformations before failure.

-6Figure 5 'shqws a typical relationship between the direct and

torqued tension tests.'

Bo'1ts tested in direct tension gave greater

ulti~

mate loads and sustained greater deformations to failure than did those
tested in torqued tension.
Bolts tested' in the' solid A440 steel blo.ck gave greater loads
for, fewe"r turns" as,

is

indicated in Fig. 6.

Although there is, a broad

scatter of the data associated with each test there is a definite separation

of' 'the two mean curves.


The bolt load is related to the number of turns from a "snug"

bolt load of 10 kips in Figs. 7, 8, 9 and 10.

The data s,hown in Figse

7 and 8 refers to tests conducted in the Skidmore-Wilhelm calibrator.


Figure 8 presents the results of tests done in a solid A440 steel block.

The mean

~urves

from ;Figs. 8 and 9 (with 1/8" thread in grip) are plotted

in Fig. 10 to compare with results of tests on A325 bolts(l).

The "snug"

load for the' A325 bolts was 8 kips.


The load-elongation relationship of A490 and A325 bolts torqued

in the Skidmore-Wilhelm calibrator are

co~pared

in Fig. 11..

7/8" x 9-!" bolts there is practically no difference at

For "the

turn from snug o

(Again, for the A325 bolts "snug" was defined as 8 kips whereas for the
A490 "snug" was 10 kips).
The effect of exposed thread under the nut is given in Fig. 12

and compared with results obtained on A325 bolts(l).

This plot shows

that the A325 bolts ,sustain slightly more rotation to failure than do the
"A490 bolts, especially at 9/16" thread in. grip.

CONCLUSIONS

The following conclusions are based on the results of 50 tests


of individual bolts.

(Twenty 7/8" x 9~" bolts and thirty 7/8" x 5~ bolts).

These results and conclusions are ,not greatly different from those'

reported in a more comprehensive study of A354 alloy steel bolts(2).


Similar results and conclusions, based on a limited number of tests,
were also

~eported

in Ref. 3.'

1. Bolts from the, same lot, and' with the' same amount of ,thread

in grip, gave

B'

greater ultimate strength in direct tension .tests than

was achieved in torqued tension tests.

For the AB l?t specimens this

increase was 10 to 15 percent of the ultimate torqued, tension value, and


for the L1 lot bolts the increase was about 26 'percent.'

2. A lesser amount of thread in grip gave an

ultimate bolt strength in both the

(Sei

Figures 1 to

torqu~d

in~rease

in the

and direct tension tests.

4).

3. For specimens with 1/8 in,. thread in grip the LI lot bolts

required in average of

1~

turns from "snug" to failure; the AB lot bo1ts

needed an average of 1-3/8 turns.

With 9/16 in. thread under the nut

this requirements increased to 1-5/8 and 1-3/4 turns for the LI and All
lot bolts respectively.

Thus an increase from 1/8 in. to 9/16 in. thread

in grip required an additional 3/8 turn' to failure for both bolt lots.

(2) Richard J. Ch+istopher and John W. Fisher


"Calibration of A354 Bolts", Fritz' Engineering Laboratory Report No

288.9, March 1963.


(3) E. Chesson, Jr. and W. H. Munse .
"St\ld'ies of the B~haVior of High Strength Bolts and Bolted Joints",

Dept. of Civil Engineering, University of Illinois, Urbana, Illinois,


Dec. 1963
'

-7-

-8-

4. The

'aver~ge

load at ~ turn from "snug" was less than the

specified proof load for both lots tested in the Skidmore-Wilhelm device.
Three o~ the ten 5~, in. long LI lot bolts tested did give loads greater

than. the specified proof load (55.45 kips) at

the AB lot bolts reached proof load at

% turn from snug.

turn from snug e

(See

None of
Figs~

arid 4, ,and 7 and 8).

5. Figure 6 indicates that the LI specimens, with 1/8" thread in


grip, torqu'ed in solid steel did reach proof load at ~ turn from "snug".

,Also this plot shows that, to achieve the same bolt elongation) fewer turns

of the nut are required in specimens torqued in the solid steel block
than is required for
If one

assume~

t~ose

tested in the less rigid Skidmore-Wilhelm device.

that the load vs'. elongation characteristics of the bolts,

tested in torqued tension, are not' influenced by the material gripped,

then (from Fig. 6) one observes that the bolt load at

~ tu~n

above proof load for those tested in the solid steel block.
shows that proof load was also reached at
qued in solid steel with 9/16"

t~read ~n

is indeed
Figure 8

% turn for most specimens torgrip.

6. The A325 and A490 bolts tested in the Skidmore-Wilhelm gave


substantially the same load-turns relationship up to the elastic limit
of the A325 bolts.

(With such a broad scatter of data (see Figs. 7 and 8)

it is strictly fortuitous that the mean curves fallon the exact same
line However, in the" elastic range of the bolts one would expect
the mean curves to be very

close~

7. The 7/8 x 9~" A490 and A325 bolts (with similar amounts of

exposed thread under the nut,) behaved similarly in

to~qued

the A490 bolts merely going to a higher "plateau".

However, ,for the shorter

tension tests, with

bolts the A490 tests indicate a relatively quick load drop off as compared
to the A325 bolts.

Note that at

turn from snug the load in the long bolts

was approximately the same regardless of typee (See Fig. 11).

- 9-

TABLE 1

A490' BOLTS - 7/8" DIAMETER


DIRECT TENSION

AB

Bolt Lot
Nominal Grip
Thread in Grip

'ins.

8%

ins~

. 1/8

.Noe of Specimens Tested

AB

TORQUED TENSION (in


Skidmore Wilhelm)

L1

L1

AB

AB
8-1~

8-11/16 4-1/8 4-9/16 8t

L1

LI

4-1/8 4-9/16

9/16

1/8

9/16

1/8

555

.9/16

1/8

9/16

Mean Ult. Load

kips

73.2

70~8

76.0

72.1

65.4

61.8

61.1

58.4

Std. Dev. from Ult. Load

kips

1.59

;1.69

0.54

0.17

2.80

2.18

2.80

3.00

Mean Eloug. at Ult.

ins.

0.0779 0.0846

Mean Rupture Load

kips

65

Mean Elong. after rupture

ins.

Mean Elong. at Proof Load

ins.

% Min. Spec. Ult. Load

Mean Load at

Turn

0.051 0.065

0.053 0.070 0.026 0.031

61

67

52

0.12

0.18

0.137 0.245 .0.08

0.028

0.029

0.015 0.017

106

102

110

59

40

0.114 0.075 0.11

0.028 0.031 0.016 0.018

41.1 53.4
1-3/8 1-3/4 1% '

1-5/8

0.90

0.87

0.80

0.77

48.8

Ave. Turns to Failure

34

104

kips

(Torqued Tension Ult)'


(Direct Tension UIto)
No. of Stripping Failures

50

50.0

TORQUED TENSION (in


solid block)
L1

Thread in Grip

No. of Stripping

in o
~ailures

Mean Elong. after Rupture

in.

Ave. Turns to "Snug" from "Finger Tight"

Ave. Turns,to Failure' from "Snug"


Ave. Turns to Proof Load from "Snug"
Proof Load = 55.4S k
Specified Minimum Ult. Load = 69.3 k

LI

1/8

9/16

0'

.09'6

.10

.20

.28

1.30

1.44

0.29

0.41

liS Thread in Grip

80

--t= -tf- ~_.... .-.

~~j~~in.Sp~~d Ultimate

60
Proof Load,
- -55.45 kips --

BOLT LOAD
(kips) _

40
grip

-wi.

~8x9~i bolts, CutThreads

20

J
o

.02

-9-

-+- Fracture of Bolt

t= thread in grip

.04

.06

.08 .

.10

.12

BOLT ELONGATION (inches)

FIG o 1

DIRECT TENSION CALIBRATION AB-LOT-BOLTS

.14

.16

80

lIe Thread in Grip


o

60

1..

'

proof JD0..9,_
~5.45 kips-

- ------ --.- -- - ..... -<?- 1-

9"6T hreod in Grip

BOLT LOAD
(kips)

--Q-~-

40

i'2 T;I urn- 0 f Nut f rom ..SnugII

'la x9 lti bolts, CutThreads


--, -+-

20

.0

.02

.04

.06
BOL~

Flf}g 2

TORQUED

.08

Fracture of Bolt

.10

.12

ELONGATION (inches)

TE~SION

CALIBRATION At1-LOT SOLTS

.14

.-.-.

aThread in Grip

__ ~ -,
BOLT LOAD

e _..

. - II'_.-tZ: -

.9'r6Threod

PrO~~t~
55.45 kips _

-.-.'. .: .
d

69.3kips,M~n. Specified
Ulti.mate Load.-

l/

80

60

~..

' ,-

-'-. -,

.. '--. _

... -

..

--- .

in Grip

.. (kips)

40

7,

20

o .

.02

.0-4

.06

X 5 ~2 bolts, Rolled

.06

Threads

!IQ

BOLT ELONGATION -(inches)


FIG. 3 DIRECT TENSION CALIBRATION LI-LOT BOLTS

.12.

-.14

80

"i

Thread in Grip

60

Proof Load ,55.4~ kips

--------

BOLT LOAD

"(kips)

-40

++

-+t-.

~ -rl.:'~ ..

9
116 Thread ~n "Grip

20
Y8 x 5~2 bolts, Rolled Threads
U

.02

.04"

.06

.08

.10

.12

.14 .

BOLT ELONGATION (inches)

FIG o "4

TORQUED TENSION CALIBRATION LI-LOT BOLTS

"'f
~r

++

80

_Direct TniQl'

e
e-- " e__ ____
. Proof Lood
~
. -55.45 kips \-

60:
BOLT LOAD
(kips)

40

-4-

. Torqued in
Skidmore~Wilhelm

'l8X5~2 Bolts
~8Thread in Grip

20--

.02

.04

.06

.08

.10

'~12

BOLT ELONGATION (inches)


FIG. 5

COMPM-ISON OF LOAD-ELONGATION CHARACTERISTICS OF

LI-LOT BOLTS, FOR DIFFERENT LOADING METHODS

" .14'

~4-

, 1.50

-1.25

TorquecJ in'
1.00

Colibroti ng
Device-'- ~---Torqued

in _.
Solid Steel
Block

TURNSOF~THE 0'15

NUT

FROM, '
, "SNUG II

0.50

~ux5~"
8
2 Bolts

'0.25

I/s,Thread

60

BOLT

in Grip

Proof Load
- , -----,
55.45 kips

Mean Load Curve


, , From Fig. 4'~8 Thread
in Gr,ip

40

LOAD
.' (kips)

.02

.04

.06

~08

.10

BOLT ELONGATION (inches)


FIG. 6 ELONGATION-NUT ROTATION CHARACTERISTICS
OF LI-LOT BOLTS

.12

"

-'

.r~ J. _

_ . ~~~.

~ ,

-ao

I/a Thread. in Grip


60

_ Proof .!OO<155".45 kips .

BOLT "LOAD
(kips)

40

916Thread in Grip
Comparison of Load-Turns Data for Different

20

Lengths of Thread in Grip. ~8 x 9~2 Bolts .

o' ;;; :::n'a) ---0.5 .

'"

(Tests Conducted in

Skidmore~Wilhelm')

'"

If"'

1.0

"0.5

1-.5

AVERAGE NUMBER OF TURNS FROM "SNUG" OF. 10 KIPS


"

Fig o 7

I "

2.0"

:,....

-80
l/aThreod in Grip

60
BOLT LOAD
(kips)

40

9'16Thread in Grip

.:.......

~~-

Comparison of Load-Turns Data for D-ifferent -

20

a 5ri Bolts

Lengths of Thread in Grip.1 x

(Tests Conducted in Skidmore-Wilhe-Im)

F7'C"::_

0.5

&'

>

i'C

c;

' "

.0.5

1~0

, .

. 1.5

AVERAGE NUMBER OF TURNS FROM "SNUG" OF, 10 KIPS


Fig. 8

2.0.

+.

i!.--

80

9~; llwead in Grip - _-

60

.'

---

Proof" "11VV4. '.' "--.45iipr--~-""

BOLT LOAD
. (kipS)

40
~8 Thread in Grip
Comparison of Load~Turns Data for Different

20..

Lengths of Thread in Grip. J x 5~;Bolts .


(Tests Oondvcted in Solid Steel Block)

o'

,a=:

0.5

5 2 'FtC

'0.5

1.0

- 1.5

2.0'

AVERAGE -NUMBER OF -TURNS FROM SNUG ELONGATION OF ~


II

Fig. 9

I"
i'

.!I

80

60
BOLT- LOAD

A490 ~oof Loa~


55.45 kips

- - --- -- - ---- - ----

...... ......

~- .........

-- - -" - ~ ~~A325,8B LOT


........

(kips)

.........

40

-A325 Proof Load 136.05 kips

- - - -- - - - - -

"",
- - - - -"

-, - - - -""

- - - Torqued in S.-W.

Torqued in" Solid Steel Block

"

20

la' x 5 ~21

bolts, Rolled Threads

~8Thread in Grip

0.5

--

0.5-

1.0

AVERAGE NU MBER OF TURNS -FROM "SNUG"


Fig. 10

COMPA.TZISON OF LOAD:-TVRt-rs DATA FOR


7/8" x 5~" A325 A:ND A490 BOLTS

1.5

2.0

I'

" 80

LOT
60

5~.45kips

BOLT LOAD

A325,8B LOT

: (kips)
II- Turn

40

from
. liS
- nugII

,.~

_____

20 .

36.05 klEL

~8 II x5 Y2 at Bolts, Rolled Threads'


!I~Thread in Grip

o __
~

_ _--.-IIooo.--_ _- - , - ,

----..I~

Aa LOT'1 A490 BOLTS


9~~ Thread in Grip

60
l

1i
'!

BOLT LOAD
(kips)

40

~2 Turn from
IISnug"

H LOT 1 A325 BOLTS


~2 Thread in Grip
_ -..- ,36.00 JUgs

20

.02

.04

.06

.08

BOLT ELONGATION (inches)


Fig. 11

COMPARISON OF LOAD VS. ELONGATION DATA FOL"',


A325 AND A490 'i~OLTS, TORQUED TENSION 'J:'ESTS

.10

.12

LI Lot ,Tested in Solid Block


U Lot t i l ' II Skidmore-Wilhelm

3
Mean Curve
-Establised' for A325
. Bolts Showing
....".-~,-..-.. ..........,..

TH READ LENGTH
UNDER THE
2

Scatter Band

NUT, (inches)

--=.... .. ~.~.-:,.....: .--

TURNS TO FAILURE
Fig. 12

EFFECT OF THREAD LENGTH ON


ROTATION CAPACITY

You might also like