NOJA-522-06

DNP3
Device Profile Document
For

NOJA Power

Switchgear

RC10 Controller
Revision Date: 09-01-2014

NOJA-522-06

DEVICE PROFILE REVISION HISTORY


Rev

Author

Date

BOS/AZ

14-05-2013

Added new points. TCP, MDI and LGVT included.

Comment

OA

09-01-2014

Negative Phase Sequence and Changes to Live Line

Source: S:\Marketing-500\User Manuals\SCADA Protocols\ NOJA-522-06 RC10 DNP3 Device Profile.docx

NOJA Power and OSM are registered trademarks of NOJA Power Switchgear Pty Ltd. This document is
copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains information
that is the intellectual property of NOJA Power Switchgear and the document, or any part thereof, should not be
copied or reproduced in any form without written permission from NOJA Power Switchgear.
NOJA Power Switchgear applies a policy of ongoing development and reserves the right to change product
without notice. NOJA Power Switchgear does not accept any responsibility for loss or damage incurred as a
result of acting or refraining from action based on information in this User Manual.

NOJA Power Switchgear Pty Ltd 2002 - 2014


www.nojapower.com.au

DNP3 Device Profile Document


Vendor Name: NOJA Power Switchgear
Device Name:
RC10 Controller

NOJA-522-06

Page 2
09-01-2014

NOJA-522-06
Contents
1
1.1

Introduction......................................................................................................................................... 7
Device Identification .......................................................................................................................... 9
1.1.1
Device Function: ...................................................................................................................... 9
1.1.2
Vendor Name: .......................................................................................................................... 9
1.1.3
Device Name: ........................................................................................................................... 9
1.1.4
Device manufacturers hardware version string: ...................................................................... 9
1.1.5
Device manufacturers software version string: ....................................................................... 9
1.1.6
Device Profile Document Version Number: .......................................................................... 10
1.1.7
DNP Levels Supported for: .................................................................................................... 10
1.1.8
Supported Function Blocks: ................................................................................................... 10
1.1.9
Notable Additions: ................................................................................................................. 11
1.1.10 Methods to set Configurable Parameters: .............................................................................. 11
1.1.11 DNP3 XML files available On-Line: ..................................................................................... 11
1.1.12 External DNP3 XML files available Off-line: ....................................................................... 12
1.1.13 Connections Supported: ......................................................................................................... 12
1.2 Serial Connections ............................................................................................................................ 13
1.2.1
Port Name............................................................................................................................... 13
1.2.2
Serial Connection Parameters: ............................................................................................... 13
1.2.3
Baud Rate: .............................................................................................................................. 13
1.2.4
Hardware Flow Control (Handshaking): ................................................................................ 13
1.2.5
Interval to Request Link Status: ............................................................................................. 14
1.2.6
Supports DNP3 Collision Avoidance: .................................................................................... 14
1.2.7
Receiver Inter-character Timeout:.......................................................................................... 15
1.2.8
Inter-character gaps in transmission: ...................................................................................... 15
1.3 IP Networking................................................................................................................................... 16
1.3.1
Port Name............................................................................................................................... 16
1.3.2
Type of End Point: ................................................................................................................. 16
1.3.3
IP Address of this Device: ...................................................................................................... 16
1.3.4
Subnet Mask: .......................................................................................................................... 16
1.3.5
Gateway IP Address: .............................................................................................................. 16
1.3.6
Accepts TCP Connections or UDP Datagrams from: ............................................................ 16
1.3.7
IP Address(es) from which TCP Connections or UDP Datagrams are accepted: .................. 16
1.3.8
TCP Listen Port Number: ....................................................................................................... 16
1.3.9
TCP Listen Port Number of remote device: ........................................................................... 17
1.3.10 TCP Keep-alive timer: ........................................................................................................... 17
1.3.11 Local UDP port: ..................................................................................................................... 17
1.3.12 Destination UDP port for DNP3 Requests (Master Only): .................................................... 17
1.3.13 Destination UDP port for initial unsolicited null responses (UDP only Outstations): ........... 17
1.3.14 Destination UDP port for responses: ...................................................................................... 17
1.3.15 Multiple outstation connections (Masters only): .................................................................... 18
1.3.16 Multiple master connections (Outstations Only):................................................................... 18
1.3.17 Time synchronization support: ............................................................................................... 18
1.4 Link Layer ........................................................................................................................................ 19
1.4.1
Data Link Address:................................................................................................................. 19
1.4.2
DNP3 Source Address Validation: ......................................................................................... 19
1.4.3
DNP3 Source Address(es) expected when Validation is Enabled: ........................................ 19
1.4.4
Self Address Support using address 0xFFFC: ........................................................................ 19
1.4.5
Sends Confirmed User Data Frames: ..................................................................................... 19
DNP3 Device Profile Document
Vendor Name: NOJA Power Switchgear
Device Name:
RC10 Controller

NOJA-522-06

Page 3
09-01-2014

NOJA-522-06
1.4.6
Data Link Layer Confirmation Timeout: ............................................................................... 20
1.4.7
Maximum Data Link Retries: ................................................................................................. 20
1.4.8
Maximum number of octets Transmitted in a Data Link Frame: ........................................... 20
1.4.9
Maximum number of octets that can be Received in a Data Link Frame: ............................. 20
1.5 Application Layer ............................................................................................................................. 21
1.5.1
Maximum number of octets Transmitted in an Application Layer Fragment other than File
Transfer: 21
1.5.2
Maximum number of octets Transmitted in an Application Layer Fragment containing File
Transfer: 21
1.5.3
Maximum number of octets that can be Received in an Application Layer Fragment: ......... 21
1.5.4
Timeout waiting for Complete Application Layer Fragment: ................................................ 22
1.5.5
Maximum number of objects allowed in a single control request for CROB (group 12): ..... 22
1.5.6
Maximum number of objects allowed in a single control request for Analog Outputs (group 41):
22
1.5.7
Maximum number of objects allowed in a single control request for Data Sets (groups 85,86,87):
22
1.5.8
Supports mixing object groups (AOBs, CROBs and Data Sets) in the same control request:22
1.6 Fill Out The Following Items For Masters Only .............................................................................. 23
1.7 Fill Out The Following Items For Outstations Only......................................................................... 24
1.7.1
Timeout waiting for Application Confirm of solicited response message: ............................ 24
1.7.2
How often is time synchronization required from the master? .............................................. 24
1.7.3
Device Trouble Bit IIN1.6: .................................................................................................... 24
1.7.4
File Handle Timeout: ............................................................................................................. 24
1.7.5
Event Buffer Overflow Behavior: .......................................................................................... 24
1.7.6
Event Buffer Organization: .................................................................................................... 25
1.7.7
Sends Multi-Fragment Responses: ......................................................................................... 25
1.7.8
Last Fragment Confirmation: ................................................................................................. 25
1.7.9
DNP Command Settings preserved through a device reset: ................................................... 25
1.8 Outstation Unsolicited Response Support ........................................................................................ 26
1.8.1
Supports Unsolicited Reporting: ............................................................................................ 26
1.8.2
Master Data Link Address:..................................................................................................... 26
1.8.3
Unsolicited Response Confirmation Timeout: ....................................................................... 26
1.8.4
Number of Unsolicited Retries: .............................................................................................. 27
1.9 Outstation Unsolicited Response Trigger Conditions....................................................................... 28
1.9.1
Number of class 1 events: ...................................................................................................... 28
1.9.2
Number of class 2 events: ...................................................................................................... 28
1.9.3
Number of class 3 events: ...................................................................................................... 28
1.9.4
Total number events from any class: ..................................................................................... 28
1.9.5
Hold time after class 1 event: ................................................................................................. 28
1.9.6
Hold time after class 2 event: ................................................................................................. 28
1.9.7
Hold time after class 3 event: ................................................................................................. 28
1.9.8
Hold time after event assigned to any class: .......................................................................... 29
1.9.9
Retrigger Hold Timer: ............................................................................................................ 29
1.9.10 Other Unsolicited Response Trigger Conditions:................................................................... 29
1.10
Outstation Performance ............................................................................................................... 30
1.10.1 Maximum Time Base Drift (milliseconds per minute): ......................................................... 30
1.10.2 When does outstation set IIN1.4?........................................................................................... 30
1.10.3 Maximum Internal Time Reference Error when set via DNP (ms):....................................... 30
1.10.4 Maximum Delay Measurement error (ms): ............................................................................ 30
1.10.5 Maximum Response time (ms): ............................................................................................. 30
DNP3 Device Profile Document
Vendor Name: NOJA Power Switchgear
Device Name:
RC10 Controller

NOJA-522-06

Page 4
09-01-2014

NOJA-522-06
1.10.6
1.10.7
1.10.8

Maximum time from start-up to IIN 1.4 assertion (ms): ........................................................ 31


Maximum Event Time-tag error for local Binary and Double-bit I/O (ms):.......................... 31
Maximum Event Time-tag error for local I/O other than Binary and Double-bit data types (ms):
31
1.11
Individual Field Outstation Parameters: ...................................................................................... 32
1.11.1 User-assigned location name or code string (same as g0v245): ............................................. 32
1.11.2 User-assigned ID Code/number string (same as g0v246): ..................................................... 32
1.11.3 User-assigned name string for the outstation (same as g0v247): ........................................... 32
1.11.4 Device Serial Number string (same as g0v248): .................................................................... 32
1.12
SECURITY PARAMETERS ...................................................................................................... 33
1.12.1 DNP3 device support for secure authentication ..................................................................... 33
2
MAPPING TO IEC 61850 OBJECT MODELS............................................................................... 34
3
CAPABILITIES AND CURRENT SETTINGS FOR DEVICE DATABASE (OUTSTATION ONLY)
35
3.1 Single-Bit Binary Inputs ................................................................................................................... 36
3.1.1
Static Variation reported when variation 0 requested: ........................................................... 36
3.1.2
Event Variation reported when variation 0 requested: ........................................................... 36
3.1.3
Event reporting mode: ............................................................................................................ 36
3.1.4
Binary Inputs included in Class 0 response:........................................................................... 36
3.2 Double-bit Input Points..................................................................................................................... 37
3.3 Binary Output Status and Control Relay Output Block .................................................................... 38
3.3.1
Minimum pulse time allowed with Trip, Close, and Pulse On commands: ........................... 38
3.3.2
Maximum pulse time allowed with Trip, Close, and Pulse On commands: .......................... 38
3.3.3
Binary Output Status included in Class 0 response: ............................................................... 38
3.3.4
Reports Output Command Event Objects: ............................................................................. 38
3.3.5
Static Variation reported when variation 0 requested: ........................................................... 38
3.3.6
Event Variation reported when variation 0 requested: ........................................................... 38
3.3.7
Command Event Variation reported when variation 0 requested: ......................................... 38
3.3.8
Event reporting mode: ............................................................................................................ 39
3.3.9
Command Event reporting mode: .......................................................................................... 39
3.3.10 Maximum Time between Select and Operate: ....................................................................... 39
3.4 Counters/Frozen Counters ................................................................................................................ 40
3.4.1
Static Counter Variation reported when variation 0 requested: ............................................. 40
3.4.2
Counter Event Variation reported when variation 0 requested: ............................................. 40
3.4.3
Counters included in Class 0 response: .................................................................................. 40
3.4.4
Counter Event reporting mode: .............................................................................................. 40
3.4.5
Static Frozen Counter Variation reported when variation 0 requested: ................................. 41
3.4.6
Frozen Counter Event Variation reported when variation 0 requested: ................................. 41
3.4.7
Frozen Counters included in Class 0 response: ...................................................................... 41
3.4.8
Frozen Counter Event reporting mode: .................................................................................. 41
3.4.9
Counters Roll Over at:............................................................................................................ 41
3.4.10 Counters frozen by means of:................................................................................................. 42
3.5 Analog Input Points .......................................................................................................................... 43
3.5.1
Static Variation reported when variation 0 requested: ........................................................... 43
3.5.2
Event Variation reported when variation 0 requested: ........................................................... 43
3.5.3
Event reporting mode: ............................................................................................................ 43
3.5.4
Analog Inputs Included in Class 0 response: ......................................................................... 44
3.5.5
How Deadbands are set: ......................................................................................................... 44
3.5.6
Analog Deadband Algorithm: ................................................................................................ 44
3.5.7
Static Frozen Analog Input Variation reported when variation 0 requested: ......................... 44
DNP3 Device Profile Document
Vendor Name: NOJA Power Switchgear
Device Name:
RC10 Controller

NOJA-522-06

Page 5
09-01-2014

NOJA-522-06
3.5.8
Frozen Analog Input Event Variation reported when variation 0 requested: ......................... 45
3.5.9
Frozen Analog Inputs included in Class 0 response:.............................................................. 45
3.5.10 Frozen Analog Input Event reporting mode: .......................................................................... 45
3.6 Analog Output Status and Analog Output Control Block ................................................................ 46
Not Supported ........................................................................................................................................ 46
3.7 Sequential File Transfer .................................................................................................................... 47
3.7.1
File Transfer Supported:......................................................................................................... 47
3.8 Octet String Points ............................................................................................................................ 48
3.8.1
Event reporting mode: ............................................................................................................ 48
3.8.2
Octet Strings Included in Class 0 response: ........................................................................... 48
3.9 Virtual Terminal Port Numbers (Points) .......................................................................................... 49
3.10
Data Set Prototype ....................................................................................................................... 50
3.11
Data Set Descriptor Contents and Characteristics ....................................................................... 51
3.12
Data Set Descriptor Point Index Attributes .............................................................................. 52
4
IMPLEMENTATION TABLE ......................................................................................................... 53
5
DATA POINTS LIST (OUTSTATION ONLY) .............................................................................. 61
5.1 Definition of Binary Input Point List:............................................................................................... 62
5.2 Definition of Double-bit Input Point List: ........................................................................................ 74
5.3 Definition of Binary Output Status/Control relay output block (CROB) Point List: ....................... 75
5.4 Definition of Counter/Frozen Counter Point List: ............................................................................ 79
5.5 Definition of Analog Input Point List: .............................................................................................. 84
5.6 Definition of Analog Output Status/Analog Output Control Block Point List: ................................ 91
5.7 Definition of File Names that may be read or written: ..................................................................... 92
5.8 Definition of Octet String Point List: ............................................................................................... 93
5.9 Definition of Virtual Terminal Port Numbers: ................................................................................. 94
5.10
Definition of Data Set Prototypes:............................................................................................... 95
5.11
Definition of Data Set Descriptors: ............................................................................................. 96
5.12
Data Set Descriptor Point Index Attributes .............................................................................. 97
6
Internal Indications ........................................................................................................................... 98
7
Buffer Size ........................................................................................................................................ 99
8
DNP3 settings ................................................................................................................................. 100
8.1 Static and Event object default variations....................................................................................... 104
8.2 Dial Out Settings............................................................................................................................. 106

DNP3 Device Profile Document


Vendor Name: NOJA Power Switchgear
Device Name:
RC10 Controller

NOJA-522-06

Page 6
09-01-2014

NOJA-522-06

1 Introduction
This DNP3 protocol implementation is fully compliant with DNP3 Subset Definition Level 2, contains
many Subset Level 3 features and contains some functionality beyond Subset Level 3.
Functionality included in this implementation is based on the Triangle MicroWorks, Inc. Slave Source
Code Library except for the following objects:

Short Floating Point Analog representation;


Obj30, var5; Obj32, var5, var7; Obj34, var3; Obj40, var3; Obj41 var3

Long Floating Point Analog representation;


Obj30, var6; Obj32, var6, var8; Obj40, var4; Obj41 var4

Analog Output Points


Obj40, all variations; Obj41, all variations

Sequential File Transfer


Obj 70, all variations

Virtual Terminal Objects


Obj 112, Obj 113

Applicability
This manual describes the DNP3 Protocol Implementation for RC10 software versions from 1.8.y.0
onwards. If you have a software version earlier than this then this document does not apply. Please
contact your NOJA Power representative for further information.
The software version can be read from the RC10 LCD screen by navigating to the Identification
screen as described in the recloser user manual.
Connection Management
The RC10 DNP3 interface is intended for use with a single DNP3 master station with a single set of
event buffers interfaced through a single communications port (either serial or Ethernet). In general, it
is recommended that it is only used in this manner.
If a user is intending to use redundant paths or multiple master stations please refer to NOJA-565-01
RC10 SCADA Interface Description for considerations and limitations.
In particular the user should note:

Operation over redundant paths is dependent on the master stations capabilities.

There is no configuration that permits normal DNP3 event polling operation to be performed
concurrently from more than one master station or control centre without errors.

A restricted subset of DNP3 operations with multiple different master stations is possible, but
care must be taken to ensure that event reporting functions are either not used, or are only

DNP3 Device Profile Document


Vendor Name: NOJA Power Switchgear
Device Name:
RC10 Controller

NOJA-522-06

Page 7
09-01-2014

NOJA-522-06
used very selectively. This is not normal DNP3 usage and may require specific configuration
settings to be made in both the masters and in the RC10 in order to avoid errors.

A very high level of understanding of the modes of operation of DNP3 may be required in
order to correctly configure a multi-master system in such a manner as to avoid errors.

DNP3 Device Profile Document


Vendor Name: NOJA Power Switchgear
Device Name:
RC10 Controller

NOJA-522-06

Page 8
09-01-2014

NOJA-522-06
1.1

DEVICE
IDENTIFICATION

1.1.1

Device Function:

Capabilities

If configurable,
list methods

Outstation

Masters send DNP requests, while


Outstations send DNP responses. If a
single physical device can perform
both functions, a separate Device
Profile Document must be provided for
each function.

1.1.2

Vendor Name:

The name of the organization


producing the device.
Note: The current value of this
outstation parameter is available
remotely using protocol object Group
0 Variation 252.

1.1.3

Device Name:

The model and name of the device,


sufficient to distinguish it from any
other device from the same
organization.
Note: The current value of this
outstation parameter is available
remotely using protocol object Group
0 Variation 250.

1.1.4

Device manufacturers
hardware version string:

Note: The current value of this


outstation parameter is available
remotely using protocol object Group 0
Variation 243.

1.1.5

Device manufacturers
software version string:

Note: The current value of this


outstation parameter is available
remotely using protocol object Group 0
Variation 242.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 9
09-01-2014

NOJA-522-06
1.1

DEVICE
IDENTIFICATION

1.1.6

Device Profile Document


Version Number:

Capabilities

If configurable,
list methods

Version of the Device Profile


Document is indicated by a whole
number incremented with each new
release. This should match the latest
version shown in the Revision History
at the beginning of this document.

1.1.7

DNP Levels Supported for:

Indicate each DNP3 Level to which


the device conforms fully. For
Masters, requests and responses can
be indicated independently.

Masters Only
Requests Responses
None
Level 1
Level 2
Level 3
Level 4
Outstations Only
Requests and Responses
None
Level 1
Level 2
Level 3
Level 4

1.1.8

Supported Function Blocks:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Self-Address Support
Data Sets
File Transfer
Virtual Terminal
Mapping to IEC 61850 Object Models
defined in a DNP3 XML file
Function code 31, activate
configuration
Secure Authentication (if checked
then see 1.12)

NOJA-522-06

Page 10
09-01-2014

NOJA-522-06
1.1

DEVICE
IDENTIFICATION

Capabilities

If configurable,
list methods

For static (non-change-event) object requests,


request qualifier codes 00 and 01 (start-stop), 07 and
A brief description intended to quickly
08 (limited quantity), and 17 and 28 (index) are
identify for the reader the most obvious supported in addition to request qualifier code 06 (no
features the device supports in addition range or all points).
to the Highest DNP Level Supported.
The complete list of features is
Static object requests received with qualifiers 00, 01,
described in the Implementation Table. 06, 07, or 08, will be responded with qualifiers 00 or

1.1.9

Notable Additions:

01.
Static object requests received with qualifiers 17 or 28
will be responded with qualifiers 17 or 28. For changeevent object requests, qualifiers 17 or 28 are always
responded.
16-bit and 32-bit Analog Change Events with Time are
supported.
Analog Input Deadbands, Object 34, variations 1
through 3, are supported.

1.1.10 Methods to set


Configurable Parameters:

1.1.11 DNP3 XML files available


On-Line:

XML Loaded via DNP3 File Transfer


XML Loaded via other transport mechanism
Terminal ASCII Terminal Command Line
Software Vendor software named CMS
Proprietary file loaded via DNP3 file transfer
Proprietary file loaded via other transport
mechanism
Direct Keypad on device front panel
Factory Specified when device is ordered
Protocol Set via DNP3 (e.g. assign class)
Other explain _______________________
No online XML File available.

XML configuration file names that can


be read or written through DNP3 File
Transfer to a device
A devices currently running
configuration is returned by DNP3 online XML file read from the device.
DNP3 on-line XML file write to a
device will update the devices
configuration when the Activate
Configuration (function code 31) is
received.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 11
09-01-2014

NOJA-522-06
1.1

DEVICE
IDENTIFICATION

1.1.12 External DNP3 XML files


available Off-line:

Capabilities

If configurable,
list methods

No external XML file available.

XML configuration file names that can


be read or written from an external
system, typically from a system that
maintains the outstation configuration.
External off-line XML file read permits
an XML definition of a new
configuration to be supplied from offline configuration tools.
External off-line XML file write permits
an XML definition of a new
configuration to be supplied to off-line
configuration tools.

1.1.13 Connections Supported:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Serial (complete section 1.2)


IP Networking (complete section 1.3)
Other, explain ________________________

NOJA-522-06

Page 12
09-01-2014

NOJA-522-06
1.2

SERIAL CONNECTIONS

1.2.1

Port Name

Name used to reference the


communication port defined in this
section.

If
configurable,
list methods

Capabilities

Three USB ports and one RS232 port are available. RS232,
USBA, USBC,
USBC.

1.2.2

Serial Connection Parameters:

Asynchronous - 8 Data Bits, 1 Start Bit, 1 Stop


Bit, No Parity
Other, explain __________________________

1.2.3

Baud Rate:

Fixed at _______
Configurable, range 300 to 115,200
Configurable, selectable from ____,____,____
Configurable, other, describe_______________

1.2.4

Hardware Flow Control


(Handshaking):

Describe hardware signaling


requirements of the interface.
Where a transmitter or receiver is
inhibited until a given control signal is
asserted, it is considered to require that
signal prior to sending or receiving
characters.
Where a signal is asserted prior to
transmitting, that signal will be maintained
active until after the end of transmission.
Where a signal is asserted to enable
reception, any data sent to the device
when the signal is not active could be
discarded.

None
RS-232 / V.24 / V.28 Options:
Asserts:
RTS before Tx
DTR before Tx
RTS before Rx
DTR before Rx
Always RTS
Always DTR

Both None
and Hardware
Handshaking
methods
supported.
Push to Talk
asserts RTS
to key a radio
transmitter.

Requires before Tx:


CTS
Asserted Deasserted
DCD Asserted Deasserted
DSR
Asserted Deasserted
RI
Asserted Deasserted
Requires Rx inactive before Tx
Requires before Rx:
CTS
Asserted
DCD Asserted
DSR
Asserted
RI
Asserted

Deasserted
Deasserted
Deasserted
Deasserted

Always ignores:
CTS
DCD
DSR
RI
Other: DCD can be set to Ignore or Block
Tx for RS 232 only

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 13
09-01-2014

NOJA-522-06
1.2

SERIAL CONNECTIONS

1.2.5

Interval to Request Link


Status:

Indicates how often to send Data Link


Layer status requests on a serial
connection. This parameter is separate
from the TCP Keep-alive timer.

1.2.6

Supports DNP3 Collision


Avoidance:

Indicates whether a device uses a


collision avoidance algorithm.
Collision avoidance may be implemented
by a back-off timer with two parameters
that define the back-off time range or by
some other vendor-specific mechanism.
The recommended back-off time is
specified as being a fixed minimum delay
plus a random delay, where the random
delay has a maximum value specified.
This defines a range of delay times that
are randomly distributed between the
minimum value and the minimum plus the
maximum of the random value.
If a back-off timer is implemented with
only a fixed or only a random value, select
the Back-off time method and set the
parameter that is not supported to Fixed
at 0 ms.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Capabilities

If
configurable,
list methods

Not Supported
Fixed at_________ seconds
Configurable, range _____ to ______ seconds
Configurable, selectable from ___,___,___
seconds
Configurable, other, describe
________________
No
Yes, using Back-off time = (Min + Random)
method
Minimum Back-off time:
Fixed at_________ ms
Configurable, range _____ to ______ ms
Configurable, selectable from __,___,___ms
Configurable, other,
describe________________
Maximum Random Back-off time component:
Fixed at_________ ms
Configurable, range _____ to ______ ms
Configurable, selectable from ___,___,___
ms
Configurable, other,
describe________________
Other, explain ________________________

NOJA-522-06

Page 14
09-01-2014

NOJA-522-06
1.2

SERIAL CONNECTIONS

1.2.7

Receiver Inter-character
Timeout:

When serial interfaces with asynchronous


character framing are used, this
parameter indicates if the receiver makes
a check for gaps between characters (i.e.
extension of the stop bit time of one
character prior to the start bit of the
following character within a message). If
the receiver performs this check and the
timeout is exceeded then the receiver
discards the current data link frame. A
receiver that does not discard data link
frames on the basis of inter-character
gaps is considered to not perform this
check.

Capabilities

If
configurable,
list methods

Not checked
No gap permitted
Fixed at _____ bit times
Fixed at _____ ms
Configurable, range ____ to ____ bit times
Configurable, range ____ to ____ ms
Configurable, Selectable from ___,___,___bit
times
Configurable, Selectable from ____, ____, ____
ms
Configurable, other, describe
__________________
Variable, explain ____

Where no asynchronous serial interface is


fitted, this parameter is not applicable. In
this case none of the options shall be
selected.

1.2.8

Inter-character gaps in
transmission:

When serial interfaces with asynchronous


character framing are used, this
parameter indicates whether extra delay
is ever introduced between characters in
the message, and if so, the maximum
width of the gap.

None (always transmits with no inter-character


gap)
Maximum _____ bit times
Maximum _____ ms

Where no asynchronous serial interface is


fitted, this parameter is not applicable. In
this case none of the options shall be
selected.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 15
09-01-2014

NOJA-522-06
1.3

IP NETWORKING

1.3.1

Port Name

Capabilities

If configurable,
list methods

Name used to reference the


communication port defined in this
section.

1.3.2

Type of End Point:

TCP Initiating (Master Only)


TCP Listening (Outstation Only)
TCP Dual (required for Masters)
UDP Datagram (required)

When
Unsolicited is
ON, TCP Dual is
active.
When
Unsolicited is
OFF, TCP
Listening is
active.
Configurable

1.3.3

IP Address of this
Device:

1.3.4

Subnet Mask:

Configurable

1.3.5

Gateway IP Address:

Configurable

1.3.6

Accepts TCP
Connections or UDP
Datagrams from:

1.3.7

IP Address(es) from
which TCP Connections
or UDP Datagrams are
accepted:

1.3.8

TCP Listen Port Number:

If Outstation or dual end point


Master, port number on which to
listen for incoming TCP connect
requests. Required to be
configurable for Masters and
recommended to be configurable for
Outstations.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Allows all (show as *.*.*.* in 1.3.7)


Limits based on an IP address
Limits based on list of IP addresses
Limits based on a wildcard IP address
Limits based on list of wildcard IP addresses
Other validation, explain_________________
Configurable

Not Applicable (Master w/o dual end point)


Fixed at 20,000
Configurable, range 1 to 65534
Configurable, selectable from ____,____,____
Configurable, other, describe________________

NOJA-522-06

Page 16
09-01-2014

NOJA-522-06
1.3

IP NETWORKING

1.3.9

TCP Listen Port Number


of remote device:

If Master or dual end point


Outstation, port number on remote
device with which to initiate
connection. Required to be
configurable for Masters and
recommended to be configurable for
Outstations.

1.3.10 TCP Keep-alive timer:


The time period for the keep-alive
timer on active TCP connections.

1.3.11 Local UDP port:


Local UDP port for sending and/or
receiving UDP datagrams. Master
may let system choose an available
port. Outstation must use one that is
known by the master.

Capabilities

Not Applicable (Outstation w/o dual end point)


Fixed at 20,000
Configurable, range 1 to 65534
Configurable, selectable from ____,____,____
Configurable, other, describe_______________

Fixed at ___________ms
Configurable, range 1 to 172800s
Configurable, selectable from ____,____,____ms
Configurable, other, describe_______________
Fixed at 20,000
Configurable, range 1 to 65534
Configurable, selectable from ____,____,____
Configurable, other, describe_______________
Let system choose (Master only)

1.3.12 Destination UDP port for


DNP3 Requests (Master
Only):

Fixed at 20,000
Configurable, range _______ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe_______________

1.3.13 Destination UDP port for


initial unsolicited null
responses (UDP only
Outstations):

None
Fixed at 20,000
Configurable, range 1 to 65534
Configurable, selectable from ____,____,____
Configurable, other, describe_______________

For a UDP only Outstation, the


destination UDP port for sending
initial unsolicited Null response

1.3.14 Destination UDP port for


responses:
For a UDP only Outstation, the
destination UDP port for sending all
responses other than initial
unsolicited Null Response.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

Not Applicable

None
Fixed at 20,000
Configurable, range 1 to 65534
Configurable, selectable from ____,____,____
Configurable, other, describe_______________
Use source port number

NOJA-522-06

Page 17
09-01-2014

NOJA-522-06
1.3

Capabilities

IP NETWORKING

1.3.15 Multiple outstation


connections (Masters
only):

If configurable,
list methods

Supports multiple outstations (Masters only)

Not Applicable

Supports multiple masters (Outstations only)

Not Applicable

Master only. Indicates whether


multiple outstation connections are
supported.

1.3.16 Multiple master


connections (Outstations
Only):
Outstation only. Indicates whether
multiple master connections are
supported and the method that can
be used to establish connections.

If supported, the following methods may be used:


Method 1 (based on IP address) - required
Method 2 (based on IP port number) recommended
Method 3 (browsing for static data) - optional

1.3.17 Time synchronization


support:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

DNP3 LAN procedure (function code 24)


DNP3 Write Time (not recommended over LAN)
Other, explain _________________________
Not Supported

NOJA-522-06

Page 18
09-01-2014

NOJA-522-06
1.4

LINK LAYER

1.4.1

Data Link Address:

Indicates if the link address is


configurable over the entire valid
range of 0 to 65,519. Data link
addresses 0xFFF0 through 0xFFFF
are reserved for broadcast or other
special purposes.

1.4.2

DNP3 Source Address


Validation:

Indicates whether the device will


filter out messages not from a
specific source address.

1.4.3

DNP3 Source
Address(es) expected
when Validation is
Enabled:

Selects the allowed source


address(es).

1.4.4

Self Address Support


using address 0xFFFC:

Capabilities

If configurable,
list methods

Fixed at______
Configurable, range 0 to 65519
Configurable, selectable from ____,____,____
Configurable, other, describe________________

Never
Always, one address allowed (shown in 1.4.3)
Always, any one of multiple addresses allowed
(each selectable as shown in 1.4.3)
Sometimes, explain________________

Configurable to any 16 bit DNP Data Link Address


value
Configurable, range _______ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe________________

If Validate
Master Address
is enabled then
only messages
from the
Unsolicited
Response
Master Address
setting will be
accepted.
This setting is
called the
Unsolicited
Response
Master Address
in the RC10
Controller.

Yes (only allowed if configurable)


No

If an Outstation receives a message


with a destination address of
0xFFFC it shall respond normally
with its own source address. It must
be possible to disable the feature if
supported.

1.4.5

Sends Confirmed User


Data Frames:

A list of conditions under which the


device transmits confirmed link layer
services (TEST_LINK_STATES,
RESET_LINK_STATES,
CONFIRMED_USER_DATA).

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Always
Sometimes, only for multi-frame messages
Never

NOJA-522-06

Page 19
09-01-2014

NOJA-522-06
1.4

LINK LAYER

1.4.6

Data Link Layer


Confirmation Timeout:

This timeout applies to any


secondary data link message that
requires a confirm or response (link
reset, link status, user data, etc)

1.4.7

Maximum Data Link


Retries:

The number of times the device will


retransmit a frame that requests Link
Layer confirmation.

1.4.8

Maximum number of
octets Transmitted in a
Data Link Frame:

This number includes the CRCs.


With a length field of 255, the
maximum size would be 292.

1.4.9

Maximum number of
octets that can be
Received in a Data Link
Frame:

Capabilities

If configurable,
list methods

None
Fixed at______ ms
Configurable, range 0 to 60s
Configurable, selectable from ___,___,___ms
Configurable, other, describe________________
Variable, explain _______________________
Never Retries
Fixed at ___________
Configurable, range 0 to 32767
Configurable, selectable from ____,____,____
Configurable, other, describe______________
Fixed at 292
Configurable, range 64 to 292
Configurable, selectable from ____,____,____
Configurable, other, describe________________

Fixed at 292
Configurable, range ________ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe_______________

This number includes the CRCs.


With a length field of 255, the
maximum size would be 292. The
device must be able to receive 292
octets to be compliant.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 20
09-01-2014

NOJA-522-06
1.5

APPLICATION LAYER

Capabilities

1.5.1

Maximum number of
octets Transmitted in an
Application Layer
Fragment other than File
Transfer:

Fixed at 2048
Configurable, range ________ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe_______________

If configurable,
list methods

This size does not include any


transport or frame octets.
Masters must provide a setting less

than or equal to 249.

Outstations must provide a setting

less than or equal to 2048.


Note: The current value of this
outstation parameter is available
remotely using protocol object Group
0 Variation 240.

1.5.2

Maximum number of
octets Transmitted in an
Application Layer
Fragment containing File
Transfer:

Fixed at ___________
Configurable, range ________ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe_______________

1.5.3

Maximum number of
octets that can be
Received in an
Application Layer
Fragment:

Fixed at 2048
Configurable, range ________ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe_______________

Not Applicable

This size does not include any


transport or frame octets.
Masters must provide a setting

greater than or equal to 2048.

Outstations must provide a setting

greater than or equal to 249.

Note: The current value of this


outstation parameter is available
remotely using protocol object Group
0 Variation 241.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 21
09-01-2014

NOJA-522-06
1.5

APPLICATION LAYER

1.5.4

Timeout waiting for


Complete Application
Layer Fragment:

Timeout if all frames of a message


fragment are not received in the
specified time. Measured from time
first frame of a fragment is received
until the last frame is received.

1.5.5

Maximum number of
objects allowed in a
single control request for
CROB (group 12):

Note: The current value of this


outstation parameter is available
remotely using protocol object Group
0 Variation 216.

Capabilities
None
Fixed at______ ms
Configurable, range _______ to _______ms
Configurable, selectable from ___,___,___ms
Configurable, other, describe________________
Variable, explain _______________________

Fixed at10
Configurable, range ________ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe_______________
Variable, explain _______________________

1.5.6

Maximum number of
objects allowed in a
single control request for
Analog Outputs (group
41):

Fixed at 0
Configurable, range ________ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe_______________
Variable, explain _______________________

1.5.7

Maximum number of
objects allowed in a
single control request for
Data Sets (groups
85,86,87):

Fixed at 0
Configurable, range ________ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe_______________
Variable, explain _______________________

1.5.8

Supports mixing object


groups (AOBs, CROBs
and Data Sets) in the
same control request:

Not applicable only CROB supported


Yes
No

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

NOJA-522-06

Page 22
09-01-2014

NOJA-522-06
1.6

FILL OUT THE


FOLLOWING ITEMS
FOR MASTERS ONLY

Capabilities

If configurable,
list methods

Not Applicable

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 23
09-01-2014

NOJA-522-06
1.7

FILL OUT THE


FOLLOWING ITEMS
FOR OUTSTATIONS
ONLY

Capabilities

1.7.1

Timeout waiting for


Application Confirm of
solicited response
message:

None
Fixed at______ ms
Configurable, range 0 to 3600s
Configurable, selectable from ___,___,___ms
Configurable, other, describe________________
Variable, explain _______________________

1.7.2

How often is time


synchronization required
from the master?

Never needs time


Within 1 second after IIN1.4 is set
Periodically, fixed at _______ seconds
Periodically, between ___ and ___ seconds

Details of when the master needs to


perform a time synchronization to
ensure that the outstation clock does
not drift outside of an acceptable
tolerance. If the option to relate this
to IIN1.4 is used then details of
when IIN1.4 is asserted are in
section 1.10.2.

1.7.3

Device Trouble Bit IIN1.6:

If IIN1.6 device trouble bit is set


under certain conditions, explain the
possible causes.

1.7.4

File Handle Timeout:

If there is no activity referencing a


file handle for a configurable length
of time, the outstation must do an
automatic close on the file. The
timeout value must be configurable
up to 1 hour. When this condition
occurs the outstation will send a File
Transport Status Object (group 70
var 6) using a status code value of
file handle expired (0x02).

1.7.5

Event Buffer Overflow


Behavior:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

Never used
Reason for setting - Set if a device malfunction is
detected refer to Malfunctions section of Binary
Inputs and/or the user manual for a description of
possible causes.
Not applicable, files not supported
Fixed at______ ms
Configurable, range _______ to _______ms
Configurable, selectable from ___,___,___ms
Configurable, other, describe________________
Variable, explain _______________________

Discard the oldest event


Discard the newest event
Other, explain _________________________

NOJA-522-06

Page 24
09-01-2014

NOJA-522-06
1.7

1.7.6

FILL OUT THE


FOLLOWING ITEMS
FOR OUTSTATIONS
ONLY
Event Buffer
Organization:

Explain how event buffers are


arranged (per Object Group, per
Class, single buffer, etc,) and
provide their sizes

1.7.7

Capabilities

Object 2 (binary)
Object 22 (counters)
Object 23 (frozen counters)
Object 32 (Analog)

Sends Multi-Fragment
Responses:

If configurable,
list methods

- 500 events;
- 400 events;
- 350 events;
- 350 events.

Yes
No

Indicates whether an Outstation


sends multi-fragment responses
(Masters do not send multi-fragment
requests).

1.7.8

Last Fragment
Confirmation:

Indicates whether the Outstation


requests confirmation of the last
fragment of a multi-fragment
response.

1.7.9

DNP Command Settings


preserved through a
device reset:

If data associated with any of these


requests are written through the
DNP protocol but not preserved
through a restart of the Outstation,
the Master will have to write them
again anytime the Restart IIN bit is
set

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

When Always is
selected for Link
Layer
Confirmation
Mode

Always
Sometimes,
Never

Assign Class
Analog Deadbands
Data Set Prototypes
Data Set Descriptors
Function Code 31 Activate Configuration

NOJA-522-06

Page 25
09-01-2014

NOJA-522-06
1.8

1.8.1

OUTSTATION
UNSOLICITED
RESPONSE
SUPPORT
Supports Unsolicited
Reporting:

Capabilities

If configurable,
list methods

Not Supported
Configurable, selectable from On and Off

When the unsolicited response


mode is configured off, the device
is to behave exactly like an
equivalent device that has no
support for unsolicited responses. If
set to On, the Outstation will send a
null Unsolicited Response after it
restarts, then wait for an Enable
Unsolicited Response command
from the master before sending
additional Unsolicited Responses
containing event data.

1.8.2

Master Data Link


Address:

The destination address of the


master device where the unsolicited
responses will be sent.

1.8.3

Unsolicited Response
Confirmation Timeout:

This is the amount of time that the


outstation will wait for an Application
Layer confirmation back from the
master indicating that the master
received the unsolicited response
message. As a minimum, the range
of configurable values must include
times from one second to one
minute. This parameter may be the
same one that is used for normal,
solicited, application confirmation
timeouts, or it may be a separate
parameter.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Fixed at______
Configurable, range 0 to 65534
Configurable, selectable from ____,____,____
Configurable, other, describe________________

Fixed at______ ms
Configurable, range 0 to 86400s
Configurable, selectable from ___,___,___ms
Configurable, other, describe________________
Variable, explain _______________________

NOJA-522-06

Page 26
09-01-2014

NOJA-522-06
1.8

1.8.4

OUTSTATION
UNSOLICITED
RESPONSE
SUPPORT
Number of Unsolicited
Retries:

This is the number of retries that an


outstation transmits in each
unsolicited response series if it does
not receive confirmation back from
the master. The configured value
includes identical and regenerated
retry messages. One of the choices
must provide for an indefinite (and
potentially infinite) number of
transmissions.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Capabilities

If configurable,
list methods

None
Fixed at ___________
Configurable, range 0 to 255
Configurable, selectable from ____,____,____
Configurable, other, describe______________
Always infinite, never gives up

NOJA-522-06

Page 27
09-01-2014

NOJA-522-06
1.9

OUTSTATION
UNSOLICITED
RESPONSE TRIGGER
CONDITIONS

Capabilities

1.9.1

Number of class 1 events:

Class 1 not used to trigger Unsolicited Responses


Fixed at ___________
Configurable, range 1 to 255
Configurable, selectable from ____,____,____
Configurable, other, describe______________

1.9.2

Number of class 2 events:

Class 2 not used to trigger Unsolicited Responses


Fixed at ___________
Configurable, range 1 to 255
Configurable, selectable from ____,____,____
Configurable, other, describe______________

1.9.3

Number of class 3 events:

Class 3 not used to trigger Unsolicited Responses


Fixed at ___________
Configurable, range 1 to 255
Configurable, selectable from ____,____,____
Configurable, other, describe______________

1.9.4

Total number events


from any class:

Total Number of Events not used to trigger


Unsolicited Responses
Fixed at ___________
Configurable, range ________ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe______________

1.9.5

Hold time after class 1


event:

Class 1 not used to trigger Unsolicited Responses


Fixed at ___________ ms
Configurable, range 0 to 86400s
Configurable, selectable from ____,____,____ ms
Configurable, other, describe______________

A configured value of 0 indicates


that responses are not delayed due
to this parameter.

1.9.6

Hold time after class 2


event:

A configured value of 0 indicates


that responses are not delayed due
to this parameter.

1.9.7

Hold time after class 3


event:

A configured value of 0 indicates


that responses are not delayed due
to this parameter.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

Class 2 not used to trigger Unsolicited Responses


Fixed at ___________ ms
Configurable, range 0 to 86400s
Configurable, selectable from ____,____,____ ms
Configurable, other, describe______________
Class 3 not used to trigger Unsolicited Responses
Fixed at ___________ ms
Configurable, range 0 to 86400s
Configurable, selectable from ____,____,____ ms
Configurable, other, describe______________

NOJA-522-06

Page 28
09-01-2014

NOJA-522-06
1.9

1.9.8

OUTSTATION
UNSOLICITED
RESPONSE TRIGGER
CONDITIONS

Capabilities

Hold time after event


assigned to any class:

Class events not used to trigger Unsolicited


Responses
Fixed at ___________ ms
Configurable, range ________ to _______ ms
Configurable, selectable from ____,____,____ ms
Configurable, other, describe______________

A configured value of 0 indicates


that responses are not delayed due
to this parameter.

1.9.9

Retrigger Hold Timer:

Hold-time timer will be retriggered for each new


event detected (may get more changes in next
response)
Hold-time timer will not be retriggered for each
new event detected (guaranteed update time)

The hold-time timer may be


retriggered for each new event
detected (increased possibly of
capturing all the changes in a single
response) or not retriggered (giving
the master a guaranteed update
time).

1.9.10 Other Unsolicited


Response Trigger
Conditions:

_________________________________________
_________________________________________
_________________________________________

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

NOJA-522-06

Page 29
09-01-2014

NOJA-522-06
1.10

OUTSTATION
PERFORMANCE

1.10.1 Maximum Time Base Drift


(milliseconds per minute):
If the protocol is synchronized by
DNP, what is the clock drift rate over
the full operating temperature range.

1.10.2 When does outstation set


IIN1.4?
When does the outstation set the
internal indication NEED_TIME.

1.10.3 Maximum Internal Time


Reference Error when set
via DNP (ms):
The difference between the time set
in a DNP Write Time message, and
the time actually set in the
Outstation.

1.10.4 Maximum Delay


Measurement error (ms):
The difference between the time
reported in the delay measurement
response and the actual time
between receipt of the delay
measurement request and issuing
the delay measurement reply.

1.10.5 Maximum Response time


(ms):
The amount of time an Outstation
will take to respond upon receipt of a
valid request. This does not include
the message transmission time.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Capabilities

If configurable,
list methods

Fixed at 3.5 ms
Range 0 to 12 ms
Selectable from ____,____,____ ms
Other, describe______________

Never
Asserted at startup until first Time Synchronization
request received
Periodically, range 0 to 69120 minutes
Periodically, selectable from ____,____,___
seconds
Range 0 to 69120 minutes after last time sync
Selectable from___,___,___ seconds after last time
sync
When time error may have driftedby range
____to____ ms
When time error may have drifted by selectable
from ____,____,___

1) Supported
Range for Need
Time,

Fixed at 1000 ms
Range ________ to _______ ms
Selectable from ____,____,____ ms
Other, describe______________

Rounded down
to nearest
second.

0-69120min.
2) If Need Time
set to zero then
IIN 1.4 is not set.

Fixed at 100 ms
Range ________ to _______ ms
Selectable from ____,____,____ ms
Other, describe______________

Fixed at 1000 ms
Range ________ to _______ ms
Selectable from ____,____,____ ms
Other, describe______________

NOJA-522-06

Page 30
09-01-2014

NOJA-522-06
1.10

OUTSTATION
PERFORMANCE

Capabilities

1.10.6 Maximum time from startup to IIN 1.4 assertion


(ms):

Fixed at 90000 ms
Range ________ to _______ ms
Selectable from ____,____,____ ms
Other, describe______________

1.10.7 Maximum Event Time-tag


error for local Binary and
Double-bit I/O (ms):

Fixed at 100 ms
Range ________ to _______ ms
Selectable from ____,____,____ ms
Other, describe______________

The error between the time-tag


reported and the absolute time of the
physical event. This error includes
the Internal Time Reference Error.

If configurable,
list methods

Note: The current value of this


parameter is available remotely
using protocol object Group 0
Variation 217.

1.10.8 Maximum Event Time-tag


error for local I/O other
than Binary and Doublebit data types (ms):

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Fixed at 100 ms
Range ________ to _______ ms
Selectable from ____,____,____ ms
Other, describe______________

NOJA-522-06

Page 31
09-01-2014

NOJA-522-06
1.11

INDIVIDUAL FIELD
OUTSTATION PARAMETERS:

Value of Current Setting

If configurable,
list methods

1.11.1 User-assigned location name or code


string (same as g0v245):
1.11.2 User-assigned ID Code/number
string (same as g0v246):
1.11.3 User-assigned name string for the
outstation (same as g0v247):
1.11.4 Device Serial Number string (same
as g0v248):

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 32
09-01-2014

NOJA-522-06
1.12

SECURITY
PARAMETERS

Capabilities

1.12.1 DNP3 device support for


secure authentication
The support for secure
authentication is optional in DNP3
devices. Indicate here if the device
supports secure authentication.

If configurable,
list methods

Secure Authentication not supported


If Secure Authentication is supported, what Version(s)
are supported:

If the device does not support


secure authentication then ignore
the rest of this section.

Fixed at ___________
Configurable, selectable from ____,____,____

If the device does support secure


authentication then specify the
version(s) that are supported in the
device. The version number is an
integer value defined in the protocol
document DNP3Spec-V2-Sup1SecureAuthentication. The volume
2 supplement shows version
numbers of all associated
documents that comprise that
version of Secure Authentication.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 33
09-01-2014

NOJA-522-06

2 MAPPING TO IEC 61850 OBJECT MODELS


This optional section allows each configuration parameter or point in the DNP Data map to be tied to an
attribute in the 61850 object models. The 61850 mappings are stored in the XML version of the Device Profile
Document as a list of XPath references to the tags representing real-time data from DNP under each data point
(for example value, timestamp, and quality for Analog inputs) paired with an IEC 61850 Object Reference in the
form of a flattened ACSI (Abstract Communication Service Interface) name of the object and attributes as
specified in IEC 61850 parts 7-4 and 7-3. The XPath reference into the DNP XML file may also contain a
reference to a constant value, a formula or conditional expression involving one or more XML tags, or a
reference to a configuration parameter that is not associated with a particular data point.
A graphical or table representation may be generated from the XML and shown here in the printed version of
the Device Profile Document to give an idea of the Logical Devices, Logical Notes, and Attributes available via
the DNP interface. The following is an example table format:

IEC 61850 Object

DNP3 XPATH Reference

Comments

This section is not


applicable.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 34
09-01-2014

NOJA-522-06

3 CAPABILITIES AND CURRENT SETTINGS FOR


DEVICE DATABASE (OUTSTATION ONLY)
The following tables identify the capabilities and current settings for each DNP3 data type. Details defining the
data points available in the device are shown in part 5 of this Device Profile.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 35
09-01-2014

NOJA-522-06
3.1

SINGLE-BIT BINARY
INPUTS
Capabilities

Static (Steady-State) Group


Number: 1
Event Group Number: 2

3.1.1

Static Variation reported


when variation 0
requested:

Variation 1 Single-bit Packed format


Variation 2 Single-bit with flag
Based on point Index

3.1.2

Event Variation reported


when variation 0
requested:

Variation 1 without time


Variation 2 with absolute time
Variation 3 with relative time
Based on point Index

Note: The support for binary input


events can be determined remotely
using protocol object Group 0
Variation 237.

3.1.3

Event reporting mode:

When responding with event data


and more than one event has
occurred for a data point, an
Outstation may include all events or
only the most recent event. All
events are typically reported for
Binary Inputs.

3.1.4

Binary Inputs included in


Class 0 response:

If Binary Inputs are not included in


the Class 0 response, Binary Input
Events (group 2) may not be
reported.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

Only most recent


All events

Always
Never
Only if point is assigned to Class 1, 2, or 3
Based on point Index (add column to table in part
5)

NOJA-522-06

Page 36
09-01-2014

NOJA-522-06
3.2

DOUBLE-BIT INPUT
POINTS

Static (Steady-State) Group


Number: 3
Event Group Number: 4

Capabilities

If configurable,
list methods

Double-Bit Input Points not supported

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 37
09-01-2014

NOJA-522-06
3.3

BINARY OUTPUT
STATUS AND
CONTROL RELAY
OUTPUT BLOCK

Binary Output Status Group


Number: 10
Binary Output Event Group
Number: 11
CROB Group Number: 12
Binary Output Command Event
Object Num: 13

Capabilities

3.3.1

Minimum pulse time


allowed with Trip, Close,
and Pulse On commands:

Fixed at 0 ms (hardware may limit this further)


Based on point Index (add column to table in part
5)

3.3.2

Maximum pulse time


allowed with Trip, Close,
and Pulse On commands:

Fixed at 4,294,967,295 ms (hardware may limit


this further)
Based on point Index (add column to table in part
5)

3.3.3

Binary Output Status


included in Class 0
response:

Always
Never
Only if point is assigned to Class 1, 2, or 3
Based on point Index (add column to table in part
5)

If Binary Output Status points are not


included in the Class 0 response,
Binary Output Status Events (group
11) may not be reported.

If configurable,
list methods

3.3.4

Reports Output Command


Event Objects:

Never
Only upon a successful Control
Upon all control attempts

3.3.5

Static Variation reported


when variation 0
requested:

Variation 1 Continuous control


Variation 2 Continuous control, binary output
status
Based on point Index

3.3.6

Event Variation reported


when variation 0
requested:

Variation 1 without time


Variation 2 with absolute time
Based on point Index

Not Supported

Variation 1 without time


Variation 2 with absolute time
Based on point Index (add column to table in part
5)

Not Supported

Note: The support for binary output


events can be determined remotely
using protocol object Group 0
Variation 222.

3.3.7

Command Event Variation


reported when variation 0
requested:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 38
09-01-2014

NOJA-522-06
3.3.8

Event reporting mode:

When responding with event data and


more than one event has occurred for
a data point, an Outstation may
include all events or only the most
recent event.

3.3.9

Command Event reporting


mode:

Only most recent


All events

Not Supported

Only most recent


All events

Not Supported

When responding with event data and


more than one event has occurred for
a data point, an Outstation may
include all events or only the most
recent event.

3.3.10 Maximum Time between


Select and Operate:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Not Applicable
Fixed at _____ seconds
Configurable, range 0 to 3600 seconds
Configurable, selectable from___,___,___
seconds
Configurable, other, describe________________
Variable, explain _______________________
Based on point Index (add column to table in part
5)

NOJA-522-06

Page 39
09-01-2014

NOJA-522-06
3.4

COUNTERS/FROZEN
COUNTERS

Static Counter Group Number: 20


Static Frozen Counter Group
Number: 21
Counter Event Group Number: 22
Frozen Counter Event Group
Number: 23

Capabilities

3.4.1

Static Counter Variation


reported when variation 0
requested:

Variation 1 32-bit with flag


Variation 2 16-bit with flag
Variation 5 32-bit without flag
Variation 6 16-bit without flag
Based on point Index

3.4.2

Counter Event Variation


reported when variation 0
requested:

Variation 1 32-bit with flag


Variation 2 16-bit with flag
Variation 5 32-bit with flag and time
Variation 6 16-bit with flag and time
Based on point Index

Note: The support for counter events


can be determined remotely using
protocol object Group 0 Variation
227.

3.4.3

Counters included in
Class 0 response:

If Counters are not included in the


Class 0 response, Counter Events
(group 22) may not be reported.

3.4.4

Counter Event reporting


mode:

When responding with event data


and more than one event has
occurred for a data point, an
Outstation may include all events or
only the most recent event. Only the
most recent event is typically
reported for Counters. When
reporting only most recent, the
counter value reported in the
response may be the value at the
time of the original event or it may
be the value at the time of the
response.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

Always
Never
Only if point is assigned to Class 1, 2, or 3
Based on point Index

A: Only most recent (value at time of event)


B: Only most recent (value at time of response)
C: All events
Based on point Index (add column to table in part
5)

NOJA-522-06

Page 40
09-01-2014

NOJA-522-06
3.4

COUNTERS/FROZEN
COUNTERS

Static Counter Group Number: 20


Static Frozen Counter Group
Number: 21
Counter Event Group Number: 22
Frozen Counter Event Group
Number: 23

Capabilities

3.4.5

Static Frozen Counter


Variation reported when
variation 0 requested:

Variation 1 32-bit with flag


Variation 2 16-bit with flag
Variation 5 32-bit with flag and time
Variation 6 16-bit with flag and time
Variation 9 32-bit without flag
Variation 10 16-bit without flag
Based on point Index

3.4.6

Frozen Counter Event


Variation reported when
variation 0 requested:

Variation 1 32-bit with flag


Variation 2 16-bit with flag
Variation 5 32-bit with flag and time
Variation 6 16-bit with flag and time
Based on point Index

Note: The support for frozen counter


events can be determined remotely
using protocol object Group 0
Variation 225.

3.4.7

Frozen Counters included


in Class 0 response:

If Frozen Counters are not included


in the Class 0 response, Frozen
Counter Events (group 23) may not
be reported.

3.4.8

Frozen Counter Event


reporting mode:

When responding with event data


and more than one event has
occurred for a data point, an
Outstation may include all events or
only the most recent event. All
events are typically reported for
Frozen Counters.

3.4.9

Counters Roll Over at:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

Always
Never
Only if point is assigned to Class 1, 2, or 3
Based on point Index

A: Only most recent frozen value


B: All frozen values
Based on point Index

16 Bits
(65,535)
32 Bits (4,294,967,295)
Other Fixed Value _________
Configurable; range _________ to__________
Configurable, selectable from ___,___,___
Configurable, other, describe________________
Based on point Index (add column to table in part
5)

NOJA-522-06

Page 41
09-01-2014

NOJA-522-06
3.4

COUNTERS/FROZEN
COUNTERS

Static Counter Group Number: 20


Static Frozen Counter Group
Number: 21
Counter Event Group Number: 22
Frozen Counter Event Group
Number: 23

3.4.10 Counters frozen by


means of:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Capabilities

If configurable,
list methods

Master Request
Freezes itself without concern for time of day
Freezes itself and requires time of day
Other, explain
_____________________________

NOJA-522-06

Page 42
09-01-2014

NOJA-522-06
3.5

ANALOG INPUT
POINTS

Static (Steady-State) Group


Number: 30
Static Frozen Group Number: 31
Event Group Number: 32
Frozen Analog Input Event Group
Number: 33
Deadband Group Number: 34

Capabilities

3.5.1

Static Variation reported


when variation 0
requested:

Variation 1 32-bit with flag


Variation 2 16-bit with flag
Variation 3 32-bit without flag
Variation 4 16-bit without flag
Variation 5 single-precision floating point with
flag
Variation 6 double-precision floating point with
flag
Based on point Index (add column to table in part
5)

3.5.2

Event Variation reported


when variation 0
requested:

Variation 1 32-bit without time


Variation 2 16-bit without time
Variation 3 32-bit with time
Variation 4 16-bit with time
Variation 5 single-precision floating point w/o
time
Variation 6 double-precision floating point w/o
time
Variation 7 single-precision floating point with
time
Variation 8 double-precision floating point with
time
Based on point Index (add column to table in part
5)

Note: The support for analog input


events can be determined remotely
using protocol object Group 0
Variation 231.

3.5.3

Event reporting mode:

When responding with event data


and more than one event has
occurred for a data point, an
Outstation may include all events or
only the most recent event. Only the
most recent event is typically
reported for Analog Inputs. When
reporting only most recent, the
analog value reported in the
response may be the value at the
time of the original event or it may
be the value at the time of the
response.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

A: Only most recent (value at time of event)


B: Only most recent (value at time of response)
C: All events
Based on point Index (add column to table in part
5)

NOJA-522-06

Page 43
09-01-2014

NOJA-522-06
3.5

ANALOG INPUT
POINTS

Static (Steady-State) Group


Number: 30
Static Frozen Group Number: 31
Event Group Number: 32
Frozen Analog Input Event Group
Number: 33
Deadband Group Number: 34

3.5.4

Analog Inputs Included in


Class 0 response:

If Analog Inputs are not included in


the Class 0 response, Analog Input
Events (group 32) may not be
reported.

Capabilities

Always
Never
Only if point is assigned to Class 1, 2, or 3
Based on point Index (add column to table in part
5)

3.5.5

How Deadbands are set:

A. Global Fixed
B. Configurable through DNP
C. Configurable via other means
D. Other, explain
_____________________________
Based on point Index - column in part 5 specifies
which of the options applies, B, C, or D

3.5.6

Analog Deadband
Algorithm:

Simple
Integrating
Other, explain
_____________________________
Based on point Index (add column to table in part
5)

simple -

just compares the


difference from the
previous reported value

integrating - keeps track of the


accumulated change
other -

3.5.7

If configurable,
list methods

Using CMS or
(SCADA)

indicating another
algorithm

Static Frozen Analog


Input Variation reported
when variation 0
requested:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Variation 1 32-bit with flag


Variation 2 16-bit with flag
Variation 3 32-bit with time-of-freeze
Variation 4 16-bit with time-of-freeze
Variation 5 32-bit without flag
Variation 6 16-bit without flag
Variation 7 Single-precision, floating-point with
flag
Variation 8 Double-precision, floating-point with
flag
Based on point Index (add column to table in part
5)

NOJA-522-06

Not Supported

Page 44
09-01-2014

NOJA-522-06
3.5

ANALOG INPUT
POINTS

Static (Steady-State) Group


Number: 30
Static Frozen Group Number: 31
Event Group Number: 32
Frozen Analog Input Event Group
Number: 33
Deadband Group Number: 34

3.5.8

Frozen Analog Input


Event Variation reported
when variation 0
requested:

Note: The support for frozen analog


input events can be determined
remotely using protocol object Group
0 Variation 230.

3.5.9

Frozen Analog Inputs


included in Class 0
response:

If Frozen Analog Inputs are not


included in the Class 0 response,
Frozen Analog Input Events (group
33) may not be reported.

3.5.10 Frozen Analog Input


Event reporting mode:
When responding with event data
and more than one event has
occurred for a data point, an
Outstation may include all events or
only the most recent event. All
events are typically reported for
Frozen Analog Inputs.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Capabilities

Variation 1 32-bit without time


Variation 2 16-bit without time
Variation 3 32-bit with time
Variation 4 16-bit with time
Variation 5 Single-precision, floating-point
without time
Variation 6 Double-precision, floating-point
without time
Variation 7 Single-precision, floating-point with
time
Variation 8 Double-precision, floating-point with
time
Based on point Index (add column to table in part
5)
Always
Never
Only if point is assigned to Class 1, 2, or 3
Based on point Index (add column to table in part
5)

A: Only most recent frozen value


B: All frozen values
Based on point Index (add column to table in part
5)

NOJA-522-06

If configurable,
list methods

Not Supported

Not Supported

Not Supported

Page 45
09-01-2014

NOJA-522-06
3.6

ANALOG OUTPUT
STATUS AND
ANALOG OUTPUT
CONTROL BLOCK

Analog Output Status Group


Number: 40
Analog Output Control Block Group
Number: 41
Analog Output Event Group
Number: 42
Analog Output Command Event
Group Number: 43

Capabilities

If configurable,
list methods

Not Supported

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 46
09-01-2014

NOJA-522-06
3.7

SEQUENTIAL FILE
TRANSFER

Capabilities

Group Number: 70

3.7.1

File Transfer Supported:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

If configurable,
list methods

Yes
No (do not complete any further entries in
section 3.7)

NOJA-522-06

Page 47
09-01-2014

NOJA-522-06
3.8

OCTET STRING POINTS

Static (Steady-State) Group Number: 110


Event Group Number: 111

3.8.1

Event reporting mode:

When responding with event data and more


than one event has occurred for a data point,
an Outstation may include all events or only
the most recent event.

3.8.2

Octet Strings Included in Class 0


response:

If Octet Strings are not included in the Class


0 response, Octet String Events (group 111)
may not be reported.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Capabilities

If configurable,
list methods

Only most recent


All events

Always
Never
Only if point is assigned to Class 1, 2, or 3
Based on point Index (add column to table
in part 5)

NOJA-522-06

Page 48
09-01-2014

NOJA-522-06
3.9

VIRTUAL TERMINAL
PORT NUMBERS
(POINTS)

Static (Steady-State) Group


Number: 112
Event Group Number: 113

Capabilities

If configurable,
list methods

This version of the Device Profile document has no requirement for describing Virtual Terminal point capabilities
and current settings. This page is intentionally left blank, existing as a placeholder for future use.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 49
09-01-2014

NOJA-522-06
3.10

DATA SET
PROTOTYPE

Group Number: 85
Variation Number: 1

Capabilities

If configurable,
list methods

This version of the Device Profile document has no requirement for describing Data Set Prototype capabilities and
current settings. This page is intentionally left blank, existing as a placeholder for future use.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 50
09-01-2014

NOJA-522-06
3.11

DATA SET
DESCRIPTOR
CONTENTS AND
CHARACTERISTICS

Capabilities

If configurable,
list methods

Group Number: 86
Variation Number: 1

This version of the Device Profile document has no requirement for describing Data Set Descriptor capabilities and
current settings. This page is intentionally left blank, existing as a placeholder for future use.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 51
09-01-2014

NOJA-522-06
3.12

DATA SET DESCRIPTOR POINT INDEX ATTRIBUTES

Group Number: 86
Variation Number: 3

This version of the Device Profile document has no requirement for describing Data Set Prototype capabilities
and current settings. This page is intentionally left blank, existing as a placeholder for future use.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 52
09-01-2014

NOJA-522-06

4 IMPLEMENTATION TABLE
The following implementation table identifies which object groups and variations, function codes and
qualifiers the device supports in both requests and responses. The Request columns identify all
requests that may be sent by a Master, or all requests that must be parsed by an Outstation. The
Response columns identify all responses that must be parsed by a Master, or all responses that may
be sent by an Outstation.
For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be
responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always used.

OBJECT
Object
Number
1

Variation
Number
0

Description
Binary Input (Variation 0 is
used to request default
variation)

REQUEST
(Library will parse)
Function Codes Qualifier Codes
(dec)
(hex)
1 (read)
00, 01(start-stop)
22(assign class)

RESPONSE
(Library will respond with)
Function
Qualifier
Codes (dec)
Codes (hex)

06(no range, or
all)
07, 08 (limited
qty)
17, 28 (index)

Binary Input

Binary Input with Status

(default
see note
1)

1 (read)
22 (assign class)

1 (read)
22 (assign class)

Binary Input Change


(Variation 0 is used to
request default variation)

1 (read)

Binary Input Change without


Time

1 (read)

00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
06(no range, or
all)

2
(default
see note
1)

Binary Input Change with


Time

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

07, 08 (limited
qty)
06(no range, or
all)
07, 08 (limited
qty)

129(response) 00, 01 (startstop)

1 (read)

06(no range, or
all)
07, 08 (limited
qty)

NOJA-522-06

129(response) 17, 28 (index)


130 (unsol.
resp)
129(response) 17, 28 (index)
130 (unsol.
resp)

Page 53
09-01-2014

NOJA-522-06
OBJECT
Object
Number
2

Variation
Number
3

Description
Binary Input Change with
Relative Time

REQUEST
(Library will parse)
Function Codes Qualifier Codes
(dec)
(hex)
1 (read)
06(no range, or
all)
07, 08 (limited
qty)

10

Binary Output Status


(Variation 0 is used to
request default variation)

1 (read)

10

Binary Output

1 (read)

10

Binary Output with Status

1 (read)

(default
see note
1)

12

Control Relay Output Block

3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)

12

Pattern Control Block

12

Pattern Mask

20

Binary Counter (Variation 0


is used to request default
variation)

3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. noack)

20

32-Bit Binary Counter

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

22 (assign class)
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl.noack)
22 (assign class)
NOJA-522-06

RESPONSE
(Library will respond with)
Function
Qualifier
Codes (dec)
Codes (hex)
129(response) 17, 28 (index)
130 (unsol.
resp)

00, 01 (startstop)
06(no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
07, 08 (limited
qty)
17, 28 (index)

129
(response)

00, 01 (startstop)
17, 28 (index
see note 1)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

129(response)

echo of
request

7 (limited
quantity)

129(response)

echo of
request

00, 01 (startstop)

129(response)

echo of
request

00, 01 (startstop)
06(no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

Page 54
09-01-2014

NOJA-522-06
REQUEST
(Library will parse)
Function Codes Qualifier Codes
Description
(dec)
(hex)
16-Bit Binary Counter
1 (read)
00, 01 (start7 (freeze)
stop)
8 (freeze noack)
06 (no range, or
9 (freeze clear)
all)
10 (frz. cl.noack) 07, 08 (limited
22 (assign class) qty)
17, 28 (index)
32-Bit Binary Counter without 1 (read)
00, 01 (startFlag
7 (freeze)
stop)
8 (freeze noack)
06 (no range, or
9 (freeze clear)
all)
10 (frz. cl.noack) 07, 08 (limited
22 (assign class) qty)
17, 28 (index)
16-Bit Binary Counter without 1 (read)
00, 01 (startFlag
7 (freeze)
stop)
8 (freeze noack)
06 (no range, or
9 (freeze clear)
all)
10 (frz. cl.noack) 07, 08 (limited
22 (assign class) qty)
17, 28 (index)
Frozen Counter (Variation 0 1 (read)
00, 01 (startis used to request default
stop)
variation)
06(no range, or
all)

OBJECT
Object
Number
20

Variation
Number
2

20

5
(default
see note
1)

20

21

21

21

32-Bit Frozen Counter

16-Bit Frozen Counter

1 (read)

1 (read)

21

32-Bit Frozen Counter with


Time Of Freeze

1 (read)

21

16-Bit Frozen Counter with


Time Of Freeze

1 (read)

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)

RESPONSE
(Library will respond with)
Function
Qualifier
Codes (dec)
Codes (hex)
129(response) 00, 01 (startstop)
17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 1)

129(response) 00, 01 (startstop)


17, 28 (index
see note 1)

Page 55
09-01-2014

NOJA-522-06
OBJECT
Object
Number
21

Variation
Number
9
(default
see note
1)

21

10

22

22

22

22

5
(default
see note
1)

Description
32-Bit Frozen Counter
without Flag

16-Bit Frozen Counter


without Flag

Counter Change Event


(Variation 0 is used to
request default variation)

REQUEST
(Library will parse)
Function Codes Qualifier Codes
(dec)
(hex)
1 (read)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
1 (read)
00, 01 (start-stop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
1 (read)
06(no range, or
all)

32-Bit Counter Change


Event

1 (read)

16-Bit Counter Change


Event

1 (read)

32-Bit Counter Change


Event with Time

1 (read)

16-Bit Counter Change


Event with Time

1 (read)

23

Frozen Counter Event


(Variation 0 is used to
request default variation)

1 (read)

23

32-Bit Frozen Counter Event

1 (read)

23

16-Bit Frozen Counter Event

1 (read)

23

32-Bit Frozen Counter Event


with Time

1 (read)

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

07, 08 (limited
qty)

22

(default
see note
1)

RESPONSE
(Library will respond with)
Function
Qualifier
Codes (dec)
Codes (hex)
129(response) 00, 01 (startstop)

NOJA-522-06

06 (no range, or
all)
07, 08 (limited
qty)
06 (no range, or
all)
07, 08 (limited
qty)
06 (no range, or
all)
07, 08 (limited
qty)

129(response) 17, 28 (index)

129
(response)
130 (unsol.
resp)

17, 28 (index)

06 (no range, or
all)
07, 08 (limited
qty)
06 (no range, or
all)
07, 08 (limited
qty)
06 (no range, or
all)
07, 08 (limited
qty)
06 (no range, or
all)
07, 08 (limited
qty)
06 (no range, or
all)
07, 08 (limited
qty)

129
(response)
130 (unsol.
resp)

17, 28 (index)

129
(response)
130 (unsol.
resp)
129
(response)
130 (unsol.
resp)
129
(response)
130 (unsol.
resp)

17, 28 (index)

130 (unsol.
resp)
129(response) 17, 28 (index)
130 (unsol.
resp)

17, 28 (index)

17, 28 (index)

Page 56
09-01-2014

NOJA-522-06
OBJECT
Object
Number
23

Variation
Number
6

30

30

Description
16-Bit Frozen Counter Event
with Time

Analog Input (Variation 0 is


used to request default
variation)

32-Bit Analog Input

(default
see note
1)

30

30

30

32

32

32

16-Bit Analog Input

32-Bit Analog Input without


Flag

16-Bit Analog Input without


Flag

1 (read)
22 (assign class)

1 (read)
22 (assign class)

1 (read)
22 (assign class)

1 (read)

32-Bit Analog Change Event


without Time

1 (read)

16-Bit Analog Change Event


without Time

1 (read)

NOJA Power Switchgear

Device Name:
RC10 Controller

1 (read)
22 (assign class)

Analog Change Event


(Variation 0 is used to
request default variation)

DNP3 Device Profile Document


Vendor Name:

REQUEST
(Library will parse)
Function Codes Qualifier Codes
(dec)
(hex)
1 (read)
06 (no range, or
all)
07, 08 (limited
qty)
1 (read)
00, 01 (startstop)
22 (assign class) 06(no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
06(no range, or
all)

RESPONSE
(Library will respond with)
Function
Qualifier
Codes (dec)
Codes (hex)
129
17, 28 (index)
(response)
130 (unsol.
resp)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

129(response) 00, 01 (startstop)


17, 28 (index
see note 2)

07, 08 (limited
qty)

NOJA-522-06

06 (no range, or
all)
07, 08 (limited
qty)
06 (no range, or
all)
07, 08 (limited
qty)

129(response) 17, 28 (index)


130 (unsol.
resp)
129(response) 17, 28 (index)
130 (unsol.
resp)

Page 57
09-01-2014

NOJA-522-06
OBJECT
Object
Number
32

Variation
Number
3
(default
see note
1)

Description
32-Bit Analog Change Event
with Time

REQUEST
(Library will parse)
Function Codes Qualifier Codes
(dec)
(hex)
1 (read)
06 (no range, or
all)
07, 08 (limited
qty)

RESPONSE
(Library will respond with)
Function
Qualifier
Codes (dec)
Codes (hex)
129
17, 28 (index)
(response)
130 (unsol.
resp)
129
(response)
130 (unsol.
resp)

17, 28 (index)

129
(response)

00, 01 (startstop)
17, 28 (index
see note 2)

129
(response)

00, 01 (startstop)
17, 28 (index
see note 2)

129
(response)

00, 01 (startstop)
17, 28 (index
see note 2)

32

16-Bit Analog Change Event


with Time

1 (read)

34

Analog Input Reporting


Deadband (Variation 0 is
used to request default
variation)

1 (read)

34

16-Bit Analog Input


Reporting Deadband

1 (read)

(default
see note
1)

2 (write)

34

32-Bit Analog Input


Reporting Deadband

1 (read)

2 (write)

50

Time and Date

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

1 (read)

NOJA-522-06

06 (no range, or
all)
07, 08 (limited
qty)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
07, 08 (limited
qty)
17, 28 (index)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)

Page 58
09-01-2014

NOJA-522-06
OBJECT
Object
Number
50

Variation
Number
1

Description
Time and Date

(default
see note
1)

REQUEST
(Library will parse)
Function Codes Qualifier Codes
(dec)
(hex)
1 (read)
00, 01 (startstop)
06 (no range, or
all)
07 (limited qty=1)
08 (limited qty)
17, 28 (index)
2 (write)
00, 01 (startstop)
07(limited qty=1)

RESPONSE
(Library will respond with)
Function
Qualifier
Codes (dec)
Codes (hex)
129
00, 01 (start(response)
stop)
17, 28 (index
see note 2)

08 (limited qty)
17, 28 (index)
51

51

52

Time and Date CTO


(synchronized)

129(response) 07(limited qty)

Time and Date CTO


(unsynchronized)

129(response) 07(limited qty)

Time Delay Fine

129(response) 07(limited qty)

130 (unsol.
resp)

130 (unsol.
resp)

(qty = 1)

(qty = 1)

(qty = 1)
60

Class 0 Data

1 (read)
22 (assign class)

06(no range, or
all)

60

Class 1 Data

06(no range, or
all)

(read)

07, 08 (limited
qty)

60

Class 2 Data

20 (enbl. unsol.)
21 (dsbl. unsol.)
22 (assign class)
1 (read)

06 (no range, or
all)
06(no range, or
all)
07, 08 (limited
qty)

60

Class 3 Data

20 (enbl. unsol.)
21 (dsbl. unsol.)
22 (assign class)
1 (read)

06 (no range, or
all)
06(no range, or
all)
07, 08 (limited
qty)

20 (enbl. unsol.)
21 (dsbl. unsol.)
22 (assign class)

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

06 (no range, or
all)

Page 59
09-01-2014

NOJA-522-06
REQUEST
(Library will parse)
Variation
Function Codes Qualifier Codes
Description
Number
(dec)
(hex)
0
Internal Indications (Variation 1 (read)
00, 01 (start0 is used to request default
stop)
variation)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
1
Internal Indications
1 (read)
00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
17, 28 (index)
2 (write)
00 (start-stop)
(see note 4)
01 (start-stop)
07, 08 (limited
qty)
17, 28 (index)
string
Octet String Object
1 (read)
06 (no range, or
length
all)
07, 08 (limited
qty)
2 (write)
00, 01 (startstop)
07, 08 (limited
qty)
17, 28 (index)
22 (assign class) 00, 01 (startstop)
06 (no range, or
all)
07, 08 (limited
qty)
No Object (function code only) See
13(cold restart)
Note 3
OBJECT

Object
Number
80

80

110

No Object (function code only) See


Note 3
No Object (function code only)

RESPONSE
(Library will respond with)
Function
Qualifier
Codes (dec)
Codes (hex)

129
(response)

00, 01 (startstop)
17, 28 (index
see note 2)

129
(response)
130 (unsol.
resp)

17, 28 (index)

129
(response)

00, 01 (startstop)

14 (warm restart)
23(delay meas.)

Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1,
2, or 3 scans. Default variations may be configurable; however, default settings for the configuration parameters
are indicated in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent
with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08,
will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.)
Note 3: Both cold restart and warm restart affect ONLY the DNP process. The RC10 itself is not restarted.
Note 4: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7).

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 60
09-01-2014

NOJA-522-06

5 DATA POINTS LIST (OUTSTATION ONLY)


This part of the Device Profile shows, for each data type. a table defining the data points available in the device
or a description of how this information can be obtained if the database is configurable. Tables for data types not
supported may be deleted. Additional columns may be added to the point list table if necessary.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 61
09-01-2014

NOJA-522-06
5.1

DEFINITION OF BINARY INPUT POINT


LIST:

List all addressable points. Points that do not exist (for


example, because an option is not installed) shall be
omitted from the table.

Fixed, list shown in table below


Configurable (current list may be shown in table
below)
Other, explain_____________________

Note: the number of binary inputs present in the device,


and the maximum binary input index, are available
remotely using object Group 0 Variations 239 and 238.

Static (Steady-State) Object Number:

Change Event Object Number:

Request Function Codes supported:

1 (read), 22 (assign class)

Default Static Variation reported when variation 0 requested:

(Note 1) 1 (Binary Input without status)

Default Change Event Variation reported when


variation 0 requested:

(Note 1) 2 (Binary Input Change with Time)

Status bits supported:

on-line, local forced data, state

Note 1: The actual variation reported in response to a variation 0 request can be configured on a per-point
basis.

Note: All binary inputs are considered permanently online On-line (0), local forced data (1).
Binary input change events are detected by the IED at the time they occur and are not subject to a
scan rate. Time stamps associated with change events correspond to the time stamp appearing on
the HMI or CMS Event, CO Operation or Change Messages logs.
The value in the Default DNP ID column represents the default setting. This parameter is user
configurable between 0 and 255, individual points can be selected for mapping or disabled using the
CMS software.
Changes to class allocation arising from use of DNP3 function 22 are saved to volatile memory.

Data
group

Default
DNP ID

Database ID

Conditions when set (=1)

Conditions when clear (=0)

Default
Class

Single
Phase
Recloser

General
0

Indication

Dummy Control

Dummy Control ON

Dummy Control OFF

Yes

Disabled
1

Indication
Indication

Test Mode
Lockout

Test Mode is OFF


ACR is not in the Lockout
state

0
1

Yes
Yes

Disabled

Indication

79_Lockout

Test Mode is ON
ACR is in the open state
and will not close
automatically
Lockout due to any
Protection Operation and
with any number of trips

Recloser is not in Lockout


state due to Protection
Operation

Yes

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 62
09-01-2014

NOJA-522-06
Data
group

Default
DNP ID

Indication

Single
Phase
Recloser

Database ID

Conditions when set (=1)

Conditions when clear (=0)

Default
Class

Remote Control

Control mode is set


Remote

Control mode is set Local.

Yes

Yes

Yes

Yes

Trip request by Group 1


protection settings
Trip request by Group 2
protection settings
Trip request by Group 3
protection settings
Trip request by Group 4
protection settings
Maximum Number of Trips
exceeded

No AR initiated or Pickup
signals detected
Control mode is set
Remote
No Group 1 protection trip
request detected.
No Group 2 protection trip
request detected.
No Group 3 protection trip
request detected.
No Group 4 protection trip
request detected.
Maximum Number of Trips
not exceeded

Yes

Yes

Yes

Yes

Yes

Pickup output of any


element is activated
Pickup output of OC1+
activated
Pickup output of OC2+
activated
Pickup output of OC3+
activated
Pickup output of OC1activated
Pickup output of OC2activated
Pickup output of OC3activated
Pickup output of NPS1+
activated
Pickup output of NPS2+
activated
Pickup output of NPS3+
activated
Pickup output of NPS1activated
Pickup output of NPS2activated
Pickup output of NPS3activated
Pickup output of EF1+
activated
Pickup output of EF2+

No Pickup output of any


element activated
Pickup output of OC1+ not
activated
Pickup output of OC2+ not
activated
Pickup output of OC3+ not
activated
Pickup output of OC1- not
activated
Pickup output of OC2- not
activated
Pickup output of OC3- not
activated
Pickup output of NPS1+
activated
Pickup output of NPS2+
activated
Pickup output of NPS3+
activated
Pickup output of NPS1activated
Pickup output of NPS2activated
Pickup output of NPS3activated
Pickup output of EF1+ not
activated
Pickup output of EF2+ not

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

Indication

AR initiated

Indication

Prot initiated

Disabled

Indication

Local Control

Disabled

Indication

Group 1 Trip

Disabled

Indication

Group 2 Trip

Disabled

Indication

Group 3 Trip

Disabled

Indication

Group 4 Trip

Disabled

Indication

MNT Exceeded

Disabled

Indication

Pickup

Disabled

Indication

P(OC1+)

Disabled

Indication

P(OC2+)

Disabled

Indication

P(OC3+)

Disabled

Indication

P(OC1- )

Disabled

Indication

P(OC2- )

Disabled

Indication

P(OC3- )

Disabled

Indication

P(NPS1+)

Disabled

Indication

P(NPS2+)

Disabled

Indication

P(NPS3+)

Disabled

Indication

P(NPS1-)

Disabled

Indication

P(NPS2-)

Disabled

Indication

P(NPS3-)

Disabled

Indication

P(EF1+)

Disabled

Indication

P(EF2+)

Any of AR
OC/NPS/EF/SEF, AR VE
or ABR elements are set in
an open state, and a
reclose operation is
pending
Logical OR of AR initiated
and Pickup signals
Control mode is set Local

IIN1-5 Local mode


indicator is set
None of AR OC/EF/SEF,
AR VE or ABR elements
are set in an open state
with a pending reclose
operation.

Pickup

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 63
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group
Database ID

Disabled

Indication

P(EF3+)

Disabled

Indication

P(EF1-)

Disabled

Indication

P(EF2- )

Disabled

Indication

P(EF3- )

Disabled

Indication

P(SEF+)

Disabled

Indication

P(SEF- )

Disabled

Indication

P(OCLL1)

Disabled

Indication

P(OCLL2)

Disabled

Indication

P(OCLL3)

Disabled

Indication

P(NPSLL1)

Disabled

Indication

P(NPSLL2)

Disabled

Indication

P(NPSLL3

Disabled

Indication

P(EFLL1)

Disabled

Indication

P(EFLL2

Disabled

Indication

P(EFLL3)

Disabled

Indication

P(SEFLL)

Disabled

Indication

P(PhA)

Disabled

Indication

P(PhB)

Disabled

Indication

P(PhC)

Disabled

Indication

P(PhN)

Disabled

Indication

P(UV1)

Disabled

Indication

P(UV2)

Disabled

Indication

P(UV3)

Disabled

Indication

P(OV1)

Disabled

Indication

P(OV2)

Disabled

Indication

P(UF)

Disabled

Indication

P(OF)

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Conditions when set (=1)

Conditions when clear (=0)

activated

activated

Pickup output of EF3+


activated
Pickup output of EF1activated
Pickup output of EF2activated
Pickup output of EF3activated
Pickup output of SEF+
activated
Pickup output of SEFactivated
Pickup output of OCLL1
activated
Pickup output of OCLL2
activated
Pickup output of OCLL3
activated
Pickup output of NPSLL1
activated
Pickup output of NPSLL2
activated
Pickup output of NPSLL3
activated
Pickup output of EFLL1
activated
Pickup output of EFLL2
activated
Pickup output of EFLL3
activated
Pickup output of SEFLL
activated
Pickup output of Phase A
activated by OC element
Pickup output of Phase B
activated by OC element
Pickup output of Phase C
activated by OC element
Pickup output of Phase N
activated by EF element
Pickup output of UV1
activated
Pickup output of UV2
activated
Pickup output of UV3
activated
Pickup output of OV1
activated
Pickup output of OV2
activated
Pickup output of UF
activated
Pickup output of OF

Pickup output of EF3+ not


activated
Pickup output of EF1- not
activated
Pickup output of EF2- not
activated
Pickup output of EF3- not
activated
Pickup output of SEF+ not
activated
Pickup output of SEF- not
activated
Pickup output of OCLL1
not activated
Pickup output of OCLL2
not activated
Pickup output of OCLL3
not activated
Pickup output of NPSLL1
activated
Pickup output of NPSLL2
activated
Pickup output of NPSLL3
activated
Pickup output of EFLL1 not
activated
Pickup output of EFLL2 not
activated
Pickup output of EFLL3 not
activated
Pickup output of SEFLL not
activated
Pickup output of Phase A
not activated
Pickup output of Phase B
not activated
Pickup output of Phase C
not activated
Pickup output of Phase N
not activated
Pickup output of UV1 not
activated
Pickup output of UV2 not
activated
Pickup output of UV3 not
activated
Pickup output of OV1 not
activated
Pickup output of OV2 not
activated
Pickup output of UF not
activated
Pickup output of OF not

NOJA-522-06

Default
Class

Single
Phase
Recloser

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

Yes

No

No

No

Yes

No

Yes

Yes

No

Yes

Yes
Page 64
09-01-2014

NOJA-522-06
Data
group

Default
DNP ID

Database ID

Conditions when set (=1)

Conditions when clear (=0)

activated
Pickup output of Uabc>
activated
Pickup output of Urst>
activated
Pickup output of Uabc<
activated
Pickup output of Urst<
activated
Pickup output of Loss of
Supply Detector activated

activated
Pickup output of Uabc> not
activated
Pickup output of Urst> not
activated
Pickup output of Uabc< not
activated
Pickup output of Urst< not
activated
Pickup output of Loss of
Supply Detector not
activated
Voltage on A bushing is
below LSD level
Voltage on B bushing is
below LSD level
Voltage on C bushing is
below LSD level
Voltage on R bushing is
below LSD level
Voltage on S bushing is
below LSD level
Voltage on T bushing is
below LSD level

Disabled

Indication

P(Uabc>)

Disabled

Indication

P(Urst>)

Disabled

Indication

P(Uabc<)

Disabled

Indication

P(Urst<)

Disabled

Indication

P(LSD)

Disabled

Indication

P(Ua)

Disabled

Indication

P(Ub)

Disabled

Indication

P(Uc)

Disabled

Indication

P(Ur)

Disabled

Indication

P(Us)

Disabled

Indication

P(Ut)

Indication

Open(Any)

Indication

Open(Prot)

Indication

Open(OC1+)

PS=0 irrespective of
source
Open due to any
protection trip
Open due to OC1+ tripping

Indication

Open(OC2+)

Open due to OC2+ tripping

Indication

Open(OC3+)

Open due to OC3+ tripping

Disabled

Indication

Open(OC1-)

Open due to OC1- tripping

Disabled

Indication

Open(OC2- )

Open due to OC2- tripping

Disabled

Indication

Open(OC3- )

Open due to OC3- tripping

Disabled

Indication

Open(NPS1+)

Disabled

Indication

Open(NPS2+)

Disabled

Indication

Open(NPS3+)

Disabled

Indication

Open(NPS1-)

Disabled

Indication

Open(NPS2-)

Disabled

Indication

Open(NPS3-)

Open due to NPS1+


tripping
Open due to NPS2+
tripping
Open due to NPS3+
tripping
Open due to NPS1tripping
Open due to NPS2tripping
Open due to NPS3tripping

Voltage on A bushing is
above LSD level
Voltage on B bushing is
above LSD level
Voltage on C bushing is
above LSD level
Voltage on R bushing is
above LSD level
Voltage on S bushing is
above LSD level
Voltage on T bushing is
above LSD level

Default
Class

Single
Phase
Recloser

Yes

Yes

Yes

Yes

Yes

Yes

No

No

Yes

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

Open

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

PS=1 irrespective of
source
Not open due to any
protection trip
Not open due to OC1+
tripping
Not open due to OC2+
tripping
Not open due to OC3+
tripping
Not open due to OC1tripping
Not open due to OC2tripping
Not open due to OC3tripping
Not open due to NPS1+
tripping
Not open due to 2+
tripping
Not open due to NPS3+
tripping
Not open due to NPS1tripping
Not open due to NPS2tripping
Not open due to NPS3tripping

NOJA-522-06

Page 65
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group
Database ID

Conditions when set (=1)

Conditions when clear (=0)

10

Indication

Open(EF1+)

Open due to EF1+ tripping

11

Indication

Open(EF2+)

Open due to EF2+ tripping

12

Indication

Open(EF3+)

Open due to EF3+ tripping

Disabled

Indication

Open(EF1-)

Open due to EF1- tripping

Disabled

Indication

Open(EF2-)

Open due to EF2- tripping

Disabled

Indication

Open(EF3-)

Open due to EF3- tripping

13

Indication

Open(SEF+)

Open due to SEF+ tripping

Disabled

Indication

Open(SEF-)

Open due to SEF- tripping

Disabled

Indication

Open(PhA)

Disabled

Indication

Open(PhB)

Disabled

Indication

Open(PhC)

Disabled

Indication

Open(PhN)

Disabled

Indication

Open(OCLL1)

Disabled

Indication

Open(OCLL2)

Disabled

Indication

Open(OCLL3)

Disabled

Indication

Open(NPSLL1)

Disabled

Indication

Open(NPSLL2)

Disabled

Indication

Open(NPSLL3)

Disabled

Indication

Open(EFLL1)

Disabled

Indication

Open(EFLL2)

Disabled

Indication

Open(EFLL3)

Disabled

Indication

Open(SEFLL)

16

Indication

Open(UV1)

Open due to Phase A


tripping by OC element
Open due to Phase B
tripping by OC element
Open due to Phase C
tripping by OC element
Open due to Phase N
tripping by EF element
Open due to OCLL1
tripping
Open due to OCLL2
tripping
Open due to OCLL3
tripping
Open due to NPSLL1
tripping
Open due to NPSLL2
tripping
Open due to NPSLL3
tripping
Open due to EFLL1
tripping
Open due to EFLL2
tripping
Open due to EFLL3
tripping
Open due to SEFLL
tripping
Open due to UV1 tripping

17

Indication

Open(UV2)

Open due to UV2 tripping

18

Indication

Open(UV3)

Open due to UV3 tripping

Disabled

Indication

Open(OV1)

Open due to OV1 tripping

Disabled

Indication

Open(OV2)

Open due to OV2 tripping

Not open due to EF1+


tripping
Not open due to EF2+
tripping
Not open due to EF3+
tripping
Not open due to EF1tripping
Not open due to EF2tripping
Not open due to EF3tripping
Not open due to SEF+
tripping
Not open due to SEFtripping
Not open due to Phase A
tripping
Not open due to Phase B
tripping
Not open due to Phase C
tripping
Not open due to Phase N
tripping
Not open due to OCLL1
tripping
Not open due to OCLL2
tripping
Not open due to OCLL3
tripping
Not open due to NPSLL1
tripping
Not open due to NPSLL2
tripping
Not open due to NPSLL3
tripping
Not open due to EFLL1
tripping
Not open due to EFLL2
tripping
Not open due to EFLL3
tripping
Not open due to SEFLL
tripping
Not open due to UV1
tripping
Not open due to UV2
tripping
Not open due to UV3
tripping
Not open due to OV1
tripping
Not open due to OV2
tripping

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Default
Class

Single
Phase
Recloser

No

No

No

No

No

No

No

No

Yes

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

Yes

No

Page 66
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group

Default
Class

Single
Phase
Recloser

Database ID

Conditions when set (=1)

Conditions when clear (=0)

Disabled

Indication

Open(UF)

Open due to UF tripping

Yes

Disabled

Indication

Open(OF)

Open due to OF tripping

Yes

19

Indication

Open (Remote)

Yes

Disabled

Indication

Open(SCADA)

Yes

Disabled

Indication

Open(I/O)

Yes

20

Indication

Open(Local)

Yes

Disabled

Indication

Open(HMI)

Yes

Disabled

Indication

Open(PC)

Yes

Disabled

Indication

Open(Manual)

Yes

Disabled

Indication

Open(Undefined)

Not open after On (Power)


or switch reconnection.

Yes

Disabled

Indication

Yes

Indication

Not open due to ABR


AutoOpen operation.
Not open due to Auto
Change Over control signal

Disabled

Open(ABR
AutoOpen)
Open(ACO)

Open due to Remote


mode control signal
Open due to SCADA
control signal
Open due to I/O control
signal
Open due to Local mode
control signal or manual
tripping
Open due to HMI control
signal
Open due to PC control
signal
Open due to manual
tripping (no origin
detected)
Open state recognized
after On (Power) or switch
reconnection
Open due to ABR
AutoOpen operation
Open due to Auto Change
Over control signal

Not open due to UF


tripping
Not open due to OF
tripping
Not open due to Remote
mode control signal
Not open due to SCADA
control signal
Not open due to I/O control
signal
Not open due to Local
mode control signal or
manual tripping
Not open due to HMI
control signal
Not open due to PC control
signal
Not open due to manual
tripping

Yes

21

Indication

Alarm (Any)

Yes

Disabled

Indication

A(OC1+)

Yes

Disabled

Indication

A(OC2+)

Yes

Disabled

Indication

A(OC1-)

Yes

Disabled

Indication

A(OC2-)

Yes

Disabled

Indication

A(NPS1+)

Yes

Disabled

Indication

A(NPS2+)

Yes

Disabled

Indication

A(NPS1-)

Yes

Disabled

Indication

A(NPS2-)

Yes

Disabled

Indication

A(EF1+)

No

Disabled

Indication

A(EF2+)

No

Disabled

Indication

A(EF1-)

No

Disabled

Indication

A(EF2-)

No Alarm output of any


element activated
Alarm output of OC1+ not
activated
Alarm output of OC2+ not
activated
Alarm output of OC1- not
activated
Alarm output of OC2- not
activated
Alarm output of NPS1+ not
activated
Alarm output of NPS2+ not
activated
Alarm output of NPS1- not
activated
Alarm output of NPS2- not
activated
Alarm output of EF1+ not
activated
Alarm output of EF2+ not
activated
Alarm output of EF1- not
activated
Alarm output of EF2- not
activated

No

Alarms

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Alarm output of any


element activated
Alarm output of OC1+
activated
Alarm output of OC2+
activated
Alarm output of OC1activated
Alarm output of OC2activated
Alarm output of NPS1+
activated
Alarm output of NPS2+
activated
Alarm output of NPS1activated
Alarm output of NPS2activated
Alarm output of EF1+
activated
Alarm output of EF2+
activated
Alarm output of EF1activated
Alarm output of EF2activated

NOJA-522-06

Page 67
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group

Default
Class

Single
Phase
Recloser

Database ID

Conditions when set (=1)

Conditions when clear (=0)

Disabled

Indication

A(SEF+)

No

Indication

A(SEF-)

No

Disabled

Indication

A(PhA)

Yes

Disabled

Indication

A(PhB)

No

Disabled

Indication

A(PhC)

No

Disabled

Indication

A(PhN)

No

Disabled

Indication

A(UV1)

Yes

Disabled

Indication

A(UV2)

No

Disabled

Indication

A(UV3)

Yes

Disabled

Indication

A(OV1)

Yes

Disabled

Indication

A(OV2)

No

Disabled

Indication

A(UF)

Yes

Disabled

Indication

A(OF)

Alarm output of SEF+ not


activated
Alarm output of SEF- not
activated
Alarm output of Phase A
not activated
Alarm output of Phase B
not activated
Alarm output of Phase C
not activated
Alarm output of Phase N
not activated
Alarm output of UV1 not
activated
Alarm output of UV2 not
activated
Alarm output of UV3 not
activated
Alarm output of OV1 not
activated
Alarm output of OV2 not
activated
Alarm output of UF not
activated
Alarm output of OF not
activated

Disabled

Alarm output of SEF+


activated
Alarm output of SEFactivated
Alarm output of Phase A
activated by OC element
Alarm output of Phase B
activated by OC element
Alarm output of Phase C
activated by OC element
Alarm output of Phase N
activated by EF element
Alarm output of UV1
activated
Alarm output of UV2
activated
Alarm output of UV3
activated
Alarm output of OV1
activated
Alarm output of OV2
activated
Alarm output of UF
activated
Alarm output of OF
activated

Yes

22
23

Indication
Indication

Closed(Any)
Closed(AR)

Yes
Yes

Indication

Yes

Disabled

Indication

Closed(AR
OCNPSEFSEF)
Closed(AR VE)

Yes

Disabled

Indication

Closed(ABR)

Yes

Disabled

Indication

Closed (Remote)

Yes

Disabled

Indication

Closed (SCADA)

Yes

24

Indication

Closed(I/O)

Yes

25

Indication

Closed (Local)

Yes

Disabled

Indication

Closed(HMI)

Yes

Disabled

Indication

Closed(PC)

Yes

Disabled

Indication

Closed(Undefined)

Yes

Disabled

Indication

Closed(ABR
AutoOpen)

PS=0 irrespective of origin


Not closed due to AR
OC/EF/SEF, AR UV, ABR
control signal
Not closed due to AR
OC/EF/SEF reclosing
Not closed due to AR VE
reclosing
Not closed due to ABR
closing
Not closed due to Remote
control signal
Not closed due to SCADA
control signal
Not closed due to I/O
control signal
Not closed due to Local
control signal
Not closed due to HMI
control signal
Not closed due to PC
control signal
Not closed after On
(Power) or switch
reconnection.
Not closed due to an ABR
Auto Open operation.

0
0

Disabled

PS=1 irrespective of origin


Closed due to AR
OC/EF/SEF, AR VE, ABR
control signal
Closed due to AR
OC/NPS/EF/SEF reclosing
Closed due to AR VE
reclosing
Closed due to ABR closing

Yes

Closed

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Closed due to Remote


control signal
Closed due to SCADA
control signal
Closed due to I/O control
signal
Closed due Local control
signal
Closed due to HMI control
signal
Close due to PC control
signal
Closed state recognized
after On (Power) or switch
reconnection.
Closed due to a ABR
operation while an ABR

NOJA-522-06

Page 68
09-01-2014

NOJA-522-06
Default
DNP ID

Disabled

Data
group
Database ID

Default
Class

Single
Phase
Recloser

Conditions when set (=1)

Conditions when clear (=0)

Auto Open operation count


is active
Closed due to a ACO
control signal

Not closed due to an ACO


control signal

Yes

Indication

Closed (ACO)

26

Indication

Group1 On

Active Group 1

Active Group 2, 3 or 4

Yes

27

Indication

Group2 On

Active Group 2

Active Group 1, 3 or 4

Yes

28
29

Indication
Indication

Group3 On
Group4 On

Active Group 3
Active Group 4

Active Group 1,2 or 4


Active Group 1, 2 or 3

0
0

Yes
Yes

30

Indication

Prot On

Protection is switched On

Protection is switched Off

Yes

Disabled

Indication

NPS On

Yes

Indication

EF On

No

32

Indication

SEF On

No

33

Indication

UV On

Yes

Disabled

Indication

UF On

Yes

Disabled

Indication

OV On

Yes

Disabled

Indication

OF On

Yes

34

Indication

CLP On

Yes

35

Indication

LL On

Yes

36

Indication

AR On

Yes

37

Indication

ABR On

Yes

Disabled

Indication

Hot Line Tag On

Negative Phase Sequence


Off
Earth overcurrent element
is switched Off
Sensitive Earth fault
element is switched Off
Undervoltage element is
switched Off
Underfrequency element is
switched Off
Overvoltage element is
switched Off
Overfrequency element is
switched Off
Cold load pickup element
is switched Off
Live line element is
switched Off
OC/EF/SEF and VE
reclosing is switched Off
Automatic backfeed
restoration is switched Off
Hot Line Tag is turned off

31

Negative Phase Sequence


On
Earth overcurrent element
is switched On
Sensitive Earth fault
element is switched On
Undervoltage element is
switched On
Underfrequency element is
switched On
Overvoltage element is
switched On
Overfrequency element is
switched On
Cold load pickup element
is switched On
Live line element is
switched on
OC/EF/SEF and VE
reclosing is switched On
Automatic backfeed
restoration is switched On
Hot Line Tag is turned on

Yes

Disabled

Indication

Yes

Disabled

Indication

Yes

Disabled

Indication

DFT On

Yes

Disabled

Indication

Block Close On

Maximum Number of Trips


to Lockout is not set to 2
Maximum Number of Trips
to Lockout is not set to 3
Short Sequence Mode is
not selected
Disable Fast Trips is
disabled
Block Close is OFF

Yes

Indication

Maximum Number of Trips


to Lockout is set to 2
Maximum Number of Trips
to Lockout is set to 3
Short Sequence Mode is
selected
Disable Fast Trips is
enabled
Block Close is ON

Disabled

79-2 Trips to
Lockout
79-3 Trips to
Lockout
SSM On

Yes

Disabled

Indication

ACO On

Auto Change Over is ON

Auto Change Over is OFF

Yes

Disabled

Indication

MNT On

Maximum Number of Trips


is ON

Maximum Number of Trips


is OFF

Yes

Malfunction

Any malfunction signal


activated
IIN1-6 Device Trouble
Indicator set

No malfunction signal
activated

Yes

Status

Malfunctions
38

Indication

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 69
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group

Default
Class

Single
Phase
Recloser

Database ID

Conditions when set (=1)

Conditions when clear (=0)

Disabled

Indication

External load
overload

External load overload not


detected

Yes

Disabled

Indication

Battery charger
fault

Battery charger status is


other than 'Fail'.

Yes

Disabled

Indication

OSM Fault

OSM fault not detected

Yes

Disabled

Indication

SIM Module Fault

SIM Module fault not


detected

Yes

Disabled

Indication

SIM Comms Error

External load overload


detected
IIN1-6 Device Trouble
Indicator set
Battery charger status is
'Fail'.
IIN1-6 Device Trouble
Indicator set
Active due to 1, 2 or 3xCoil
OC; Limit switch fault, Coil
SC , excessive To,
excessive Tc
IIN1-6 Device Trouble
Indicator set
SIM Module Fault
detected.
IIN1-6 Device Trouble
Indicator set
No response from SIM.

Yes

I/O1 Comms Error

IIN1-6 Device Trouble


Indicator set
No response from I/O1.

SIM comms error not


detected

Yes

I/O2 Comms Error

IIN1-6 Device Trouble


Indicator set
No response from I/O2.

I/O1 comms error not


detected
I/O2 comms error not
detected

Yes

The Excessive To flag is


reset.

Yes

The Excessive Tc flag is


reset

Yes

OSM coil open circuit not


detected

Yes

OSM coil short circuit not


detected

Yes

Disabled

Disabled

Indication

Indication

Disabled

Indication

Excessive To

Disabled

Indication

Excessive Tc

Disabled

Indication

OSM Coil OC

Disabled

Indication

OSM Coil SC

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

IIN1-6 Device Trouble


Indicator set
The most recent trip
request failed because the
opening time exceeded
60ms or no confirmation
received that open
command was executed
successfully.
IIN1-6 Device Trouble
Indicator set
The most recent close
request failed because the
time to close exceeded
100ms, or no confirmation
received that open
command was executed
successfully
IIN1-6 Device Trouble
Indicator set
OSM coil open circuit
detected.
IIN1-6 Device Trouble
Indicator set
OSM coil short circuit
detected.
IIN1-6 Device Trouble
Indicator set

NOJA-522-06

Page 70
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group

Default
Class

Single
Phase
Recloser

Database ID

Conditions when set (=1)

Conditions when clear (=0)

Disabled

Indication

OSM Limit Switch


Fault

OSM limit switch fault not


detected

Yes

Disabled

Indication

Capacitor Voltage
Abnormal

No fault with capacitor


voltage detected.

Yes

Disabled

Indication

Module Comms
Error

No fault with SIM or I/O


comms detected

Yes

Disabled

Indication

Panel Comms
Error

No fault with panel comms


detected

Yes

Disabled

Indication

Controller Fault

No fault with controller


detected

Yes

Disabled

Indication

Controller Module
Fault

No controller module fault


detected

Yes

Disabled

Indication

Panel Module fault

No Internal fault of Panel


module detected

Yes

Disabled

Indication

Relay Module fault

No Internal fault of relay


module detected

Yes

Disabled

Indication

CAN Bus
Malfunction

OSM limit switch fault


detected.
IIN1-6 Device Trouble
Indicator set
Close volt drop too high,
Trip volt drop too high, Trip
volt drop on close
IIN1-6 Device Trouble
Indicator set
SIM or I/O module comms
error detected
IIN1-6 Device Trouble
Indicator set
Panel comms error
detected
IIN1-6 Device Trouble
Indicator set
Active due to CAN bus
Malfunction, module fault,
comms error or Ext. load
overload
IIN1-6 Device Trouble
Indicator set
Active due to Panel
module, SIM
disconnected, SIM fault,
I/O1 fault, I/O2 fault or
relay fault
IIN1-6 Device Trouble
Indicator set
Internal fault of Panel
module detected
IIN1-6 Device Trouble
Indicator set
Internal fault of relay
module detected
IIN1-6 Device Trouble
Indicator set
Error reported on CAN bus

No error detected on CAN


bus

Yes

No I/O1 internal fault


detected

Yes

No I/O2 internal fault


detected

Yes

No warning signal
activated
OSM position status is
available

Yes

Yes

Disabled

Disabled

Indication

Indication

I/O1 fault

IIN1-6 Device Trouble


Indicator set
I/O1 internal fault detected

I/O2 fault

IIN1-6 Device Trouble


Indicator set
I/O2 internal fault detected
IIN1-6 Device Trouble
Indicator set

Warnings
39

Indication

Warning

Disabled

Indication

OSM Position
Status Unavailable

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Any warning signal


activated
OSM position status is
unavailable due to being

NOJA-522-06

Page 71
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group
Database ID

40

Indication

OSM
Disconnected
OSM Mechanically
Locked Out

Disabled

Indication

Disabled

Indication

Disabled

Indication

Disabled

Indication

Disabled

Indication

Disabled

Indication

Disabled

Indication

Disabled

Indication

Close Blocked

Disabled

Indication

AC Supply High

Disabled

Indication

Source Not
Healthy

Disabled

Indication

ACO Unhealthy

SIM Caps Not


Charged
Battery Status
Abnormal
Battery Charger
State: Low Power
Battery Off
(AC Supply)
AC Off
(Battery Supply)
Critical Battery
Level

Default
Class

Single
Phase
Recloser

Conditions when set (=1)

Conditions when clear (=0)

disconnected or a
malfunction
OSM disconnected

OSM connected

Yes

OSM mechanically locked


out, trip ring pulled down

OSM is not mechanically


locked out.

Yes

SIM actuator driver not


ready
Battery is either high, low
or disconnected
Battery charger state is in
low power mode
UPS is in 'Battery Off' state

SIM actuator driver ready

Yes

Battery status is normal

Yes

Battery charger state is


normal
UPS is not in 'Battery Off'
state
UPS is not in 'AC Off' state

Yes

Yes

Yes

System shutdown in less


than 5 min due to low
battery level
Close is blocked by any
source
AC voltage high

Battery level is non-critical

Yes

Close is not blocked

Yes

AC voltage is not high

Yes

Source detected as
outside specified supply
parameters
Conditions detected not to
allow an ACO operation

Source supply healthy

Yes

Conditions allow an ACO


operation

Yes

UPS is in 'AC Off' state

IO Modules
Disabled

Indication

Local Input IN1

Input asserted

Input not asserted

Yes

Disabled

Indication

Local Input IN2

Input asserted

Input not asserted

Yes

Disabled

Indication

Local Input IN3

Input asserted

Input not asserted

Yes

Disabled

Indication

IO1 Input 1

Input asserted

Input not asserted

Yes

Disabled

Indication

IO1 Input 2

Input asserted

Input not asserted

Yes

Disabled

Indication

IO1 Input 3

Input asserted

Input not asserted

Yes

Disabled

Indication

IO1 Input 4

Input asserted

Input not asserted

Yes

Disabled

Indication

IO1 Input 5

Input asserted

Input not asserted

Yes

Disabled

Indication

IO1 Input 6

Input asserted

Input not asserted

Yes

Disabled

Indication

IO1 Input 7

Input asserted

Input not asserted

Yes

Disabled

Indication

IO1 Input 8

Input asserted

Input not asserted

Yes

Disabled

Indication

IO2 Input 1

Input asserted

Input not asserted

Yes

Disabled

Indication

IO2 Input 2

Input asserted

Input not asserted

Yes

Disabled

Indication

IO2 Input 3

Input asserted

Input not asserted

Yes

Disabled

Indication

IO2 Input 4

Input asserted

Input not asserted

Yes

Disabled

Indication

IO2 Input 5

Input asserted

Input not asserted

Yes

Disabled

Indication

IO2 Input 6

Input asserted

Input not asserted

Yes

Disabled

Indication

IO2 Input 7

Input asserted

Input not asserted

Yes

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 72
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group

Default
Class

Single
Phase
Recloser

Database ID

Conditions when set (=1)

Conditions when clear (=0)

IO2 Input 8

Input asserted

Input not asserted

Yes

Logic Variables
Disabled Indication

VAR1

Logic Variable 1 True

Logic Variable 1 False

Yes

Disabled

Indication

VAR2

Logic Variable 2 True

Logic Variable 2 False

Yes

Disabled

Indication

VAR3

Logic Variable 3 True

Logic Variable 3 False

Yes

Disabled

Indication

VAR4

Logic Variable 4 True

Logic Variable 4 False

Yes

Disabled

Indication

VAR5

Logic Variable 5 True

Logic Variable 5 False

Yes

Disabled

Indication

VAR6

Logic Variable 6 True

Logic Variable 6 False

Yes

Disabled

Indication

VAR7

Logic Variable 7 True

Logic Variable 7 False

Yes

Disabled

Indication

VAR8

Logic Variable 8 True

Logic Variable 8 False

Yes

Disabled

Indication

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 73
09-01-2014

NOJA-522-06
5.2

DEFINITION OF DOUBLE-BIT INPUT


POINT LIST:
List all addressable points. Points that do not exist
(for example, because an option is not installed)
shall be omitted from the table.

Fixed, list shown in table below


Configurable (current list may be shown in table
below)
Other, explain Not Supported

Note: the number of double-bit inputs present in the


device, and the maximum double-bit input index, are
available remotely using object Group 0 Variations 236
and 235.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 74
09-01-2014

NOJA-522-06
5.3

DEFINITION OF BINARY OUTPUT


STATUS/CONTROL RELAY OUTPUT
BLOCK (CROB) POINT LIST:

Fixed, list shown in table below


Configurable (current list may be shown in table
below)
Other, explain_____________________

List all addressable points. Points that do not exist (for


example, because an option is not installed) shall be
omitted from the table.
Note: the number of binary outputs present in the device,
and the maximum binary output index, are available
remotely using object Group 0 Variations 224 and 223.
Object Number:
Request Function Codes supported:
Default Variation reported when variation 0 requested:
Status bits supported:

10
1 (read)
(Note 1) 2 (Binary Output with Status)
on-line, communications lost, local forced data,
state
Note 1: The actual variation reported in response to a variation 0 request can be configured on a per-point
basis.
Notes: The count, on-time, off-time, queue, and clear parameters are ignored for all points.
Condition(s) for Obj 10 var 2 status for each point is indicated below where applicable, also refer notes
at the end of the table.
Control Relay Output Blocks
Object Number: 12
Request Function Codes supported:
Accepted control types are:

3 (select), 4 (operate),
5 (direct operate), 6 (direct operate, noack)
Control Type
Control Code
Accepted by
Pulse ON
0x01
All Points
Pulse OFF
0x02
All Points
Latch ON
0x03
All Points
Latch OFF
0x04
All Points
Close
0x41
All Points
Trip
0x81
All Points

The recommended control type is shown in the table below.


Set (1)

Close, Pulse ON, Latch ON

Cleared (0)

Trip, Pulse OFF, Latch OFF

The value in the Default DNP ID column represents the default setting. This parameter is user
configurable between 0 and 255, individual points can be selected for mapping or disabled using CMS
software.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 75
09-01-2014

NOJA-522-06
Default
DNP ID

Single
Phase
Recloser
Yes

Data
group
Control

Database ID
Dummy Control

Set = 1
Dummy Control ON

Clear = 0
Dummy Control OFF

Disabled

Control

Test Mode

Test Mode ON

Test Mode OFF

Recommended control
type
Can be used to test all
control types
Latch ON / Latch OFF

Control

Trip/Close

Close OSM

Trip OSM

CLOSE / TRIP

Yes

Control

Group 1 On

Group 1 Active

No Action

Pulse ON

Yes

Control

Group 2 On

Group 2 Active

No Action

Pulse ON

Yes

Control

Group 3 On

Group 3 Active

No Action

Pulse ON

Yes

Control

Group 4 On

Group 4 Active

No Action

Pulse ON

Yes

Control

Prot On

Protection ON

Protection OFF

Latch ON / Latch OFF

Yes

Disabled

Control

NPS On

NPS ON

NPS OFF

Latch ON / Latch OFF

No

Control

EF On

Earth Fault ON

Earth Fault OFF

Latch ON / Latch OFF

No

Control

SEF On

Sensitive Earth Fault ON

Sensitive Earth Fault


OFF
Under Voltage OFF

Latch ON / Latch OFF

No

Latch ON / Latch OFF

Yes

Over Voltage OFF


Under Frequency
OFF
Over Frequency OFF

Latch ON / Latch OFF


Latch ON / Latch OFF

Yes
Yes

Latch ON / Latch OFF

Yes

Latch ON / Latch OFF

Yes

Yes

Control

UV On

Under Voltage ON

Disabled
Disabled

Control
Control

OV On
UF On

Over Voltage ON
Under Frequency ON

Disabled

Control

OF On

Over Frequency ON

10

Control

CLP On

Cold Load Pickup ON

11

Control

LL On

Live Line ON

Cold Load Pickup


OFF
Live Line OFF

Latch ON / Latch OFF

Yes

12

Control

AR On

Auto Reclose ON

Auto Reclose OFF

Latch ON / Latch OFF

Yes

13

Control

ABR On

Yes

Control

Pulse ON

Yes

Disabled

Control

Dnp3 Reset
Communication
Watchdog Timer
Hot Line Tag On

Auto Backfeed
Restoration OFF
No Action

Latch ON / Latch OFF

Disabled

Auto Backfeed Restoration


ON
Resets Communication
Watchdog timer to its
maximum value
Hot Line Tag ON

Hot Line Tag OFF

Latch ON / Latch OFF

Yes

Disabled

Control

Latch ON / Latch OFF

Yes

Control

No Action

Latch ON / Latch OFF

Yes

Disabled

Control

Sets Maximum Number of


Trips to Lockout to 2
Sets Maximum Number of
Trips to Lockout to 3
Short Sequence Mode ON

No Action

Disabled

79-2 Trips to
Lockout
79-3 Trips to
Lockout
SSM On

Latch ON / Latch OFF

Yes

Disabled

Control

DFT On

Disable Fast Trips is ON

Latch ON / Latch OFF

Yes

Disabled

Control

Reset Binary Fault


Targets

Resets to 0 the value in


following points (note 1):
Open(Prot), Open(OC1+),
Open(OC2+),
Open(OC3+), Open(OC1-),
Open(OC2-), Open(OC3-),
Open(EF1+), Open(EF2+),
Open(EF3+), Open(EF1-),
Open(EF2-), Open(EF3-),
Open(SEF+), Open(SEF-),
Open(OCLL), Open(EFLL),
Open(UV1), Open(UV2),
Open(UV3), Open(OV1),
Open(OV2), Open(OF),
Open(UF), Open(PhA),
Open(PhB), Open(PhC),
Open(PhN), Open(ABR
AutoOpen),
MNT Exceeded.

Short Sequence Mode


OFF
Disable Fast Trips is
OFF
No Action

Pulse ON

No,
EF/SEF/
UV2/OV2

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 76
09-01-2014

NOJA-522-06
Recommended control
type
Pulse ON

Single
Phase
Recloser
Yes

Latch ON / Latch OFF

Yes

Latch ON / Latch OFF

Yes

Block Close

Maximum Number of Trips


is ON
Block Close is ON

Auto Change Over


OFF
Maximum Number of
Trips is OFF
Block Close is OFF

Latch ON / Latch OFF

Yes

NPS On

NPS is ON

NPS is OFF

Latch ON / Latch OFF

Yes

Erase Fault
Counters
Erase SCADA
counters
Erase energy
meters
Erase
Oscillography Files
Erase Interruption
Counters and
Duration Counters
Erase Sag/Swell
Counters and
Duration Counters

Erase Fault Counters

No Action

Pulse ON

Yes

Erase SCADA counters

No Action

Pulse ON

Yes

Erase energy meters

No Action

Pulse ON

Yes

Erase Oscillography Files

No Action

Pulse ON

Yes

Erase Interruption Counters


and Duration Counters

No Action

Pulse ON

Yes

Erase Sag/Swell Counters


and Duration Counters

No Action

Pulse ON

Yes

Default
DNP ID
Disabled

Data
group
Control

Disabled

Control

ACO On

Disabled

Control

MNT On

Disabled

Control

Disabled

Control

14

Erase

16

Erase

15

Erase

18

Erase

19

Erase

20

Erase

Database ID
Reset Trip
Currents

Set = 1
Resets to 0 the value in
following Analog Input
Points:
Ia Trip, Ib Trip, Ic Trip, In
Trip, I2 Trip
Auto Change Over ON

Clear = 0
No Action

Erase

IO Modules (note 2)
Disabled

Control

IO1 Output 1

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO1 Output 2

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO1 Output 3

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO1 Output 4

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO1 Output 5

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO1 Output 6

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO1 Output 7

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO1 Output 8

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO2 Output 1

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO2 Output 2

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO2 Output 3

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO2 Output 4

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO2 Output 5

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO2 Output 6

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO2 Output 7

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

IO2 Output 8

Output ON

Output OFF

Latch ON / Latch OFF

Yes

Disabled

Control

VAR1

Set Variable 1 True

Set Variable 1 False

Latch ON / Latch OFF

Yes

Disabled

Control

VAR2

Set Variable 2 True

Set Variable 2 False

Latch ON / Latch OFF

Yes

Disabled

Control

VAR3

Set Variable 3 True

Set Variable 3 False

Latch ON / Latch OFF

Yes

Disabled

Control

VAR4

Set Variable 4 True

Set Variable 4 False

Latch ON / Latch OFF

Yes

Disabled

Control

VAR5

Set Variable 5 True

Set Variable 5 False

Latch ON / Latch OFF

Yes

Variables

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 77
09-01-2014

NOJA-522-06
Clear = 0
Set Variable 6 False

Recommended control
type
Latch ON / Latch OFF

Single
Phase
Recloser
Yes

Set Variable 7 True

Set Variable 7 False

Latch ON / Latch OFF

Yes

Set Variable 8 True

Set Variable 8 False

Latch ON / Latch OFF

Yes

Default
DNP ID
Disabled

Data
group
Control

Database ID
VAR6

Set = 1
Set Variable 6 True

Disabled

Control

VAR7

Disabled

Control

VAR8

Each of the RC10 SCADA communications ports can be configured as either Local or Remote.

All controls from any source except for Trip Command are rejected if RC Local/Remote Mode does not
match with Local/Remote Mode of Communication Port or IO/Relay Inputs/Logic Input.

When in Local Control mode, the status bits of all other CROB points are shown as offline.

Notes:

1. These point values are also reset to zero automatically when the recloser closes. This control is used to
reset them to zero while open.
2. The following conditions are necessary to control IO Modules from SCADA:
- IO mode is enabled in I/O settings;
- IO Output# has Type equal to generic output or input in I/O settings;
- IO faults are absent;

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 78
09-01-2014

NOJA-522-06
5.4

DEFINITION OF COUNTER/FROZEN
COUNTER POINT LIST:

List all addressable points. Points that do not exist (for


example, because an option is not installed) shall be
omitted from the table.

Fixed, list shown in table below


Configurable (current list may be shown in table
below)
Other, explain_____________________

Note: the number of counters present in the device, and


the maximum counter index, are available remotely using
object Group 0 Variations 229 and 228.

Static (Steady-State) Object Number:


Change Event Object Number:
*)
Request Function Codes supported :

20
22
1 (read), 7 (freeze), 8 (freeze noack) 9 (freeze and clear), 10 (freeze
and clear, noack), 22 (assign class)

Static Variation reported when variation 0 requested:


Change Event Variation reported when variation 0 requested:

6 (16-Bit Binary Counter without Flag)


1 (16-Bit Counter Change Event with Time)

Frozen Counters
Static (Steady-State) Object Number:
Change Event Object Number:
Request Function Codes supported:
Static Variation reported when variation 0 requested:
Change Event Variation reported when variation 0 requested:

21
23
1 (read), 22 (assign class)
10 (16-Bit Frozen Binary without Flag)
6 (16-Bit Frozen Counter Event with Time)

Note: Counter points are always considered online and the on-line status bit is always set. No other status bits
are supported for counter objects.

The value in the Default DNP ID column represents the default setting. This parameter is user
configurable between 0 and 255, individual points can be selected for mapping or disabled using CMS
software
Changes to class allocation arising from use of DNP3 function 22 are saved to volatile memory.
Time stamps associated with Fault counter change events correspond to the time stamps appearing
in the HMI or CMS CO Operations log.

Counter objects can be individually disabled by Object type for each counter.

*)

Request Functions Code 9 (freeze and clear) and 10 (freeze and clear, noack) are supported for SCADA Counters only.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 79
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group

Valid
Range

Resolution
scale
factor

Default
Reporting
Deadband

Default
Class

Single
Phase
Recloser

Database ID

Description
Overcurrent
protection trips
on A phase
Overcurrent
protection trips
on B phase
Overcurrent
protection trips
on C phase
Neg. Phase
Sequence
protection trips
Earth Fault
protection trips
Sensitive Earth
Fault
Protection
Trips
Under Voltage
protection
Trips
Over Voltage
protection
Trips
Under
Frequency
protection trips
Over
Frequency
protection trips

0 to 65535

Yes

0 to 65535

No

0 to 65535

No

0 to 65535

No

0 to 65535

No

0 to 65535

No

0 to 65535

Yes

0 to 65535

Yes

0 to 65535

Yes

0 to 65535

Yes

Number of
Close Open
operations
Mechanical
wear
consumed;
expressed as
a percentage
Maximum
vacuum
Interrupter
contact wear
consumed on
any one
phase;
expressed as
a percentage

0 to 65535

20

Yes

0 to 100%

10%

Yes

0 to 100%

10%

Yes

A phase total
forward energy

0 to
4294967295
kVAh

Yes

Fault Counters
0

Indication

OC A Trips

Indication

OC B Trips

Indication

OC C Trips

Disabled

Indication

NPS Trips

Indication

EF Trips

Indication

SEF Trips

Indication

UV Trips

Disabled

Indication

OV Trips

Disabled

Indication

UF Trips

Disabled

Indication

OF Trips

Lifetime Counters
6

Indication

CO Total

Indication

Mechanical
Wear

Indication

Max phase
Contact Wear

Energy Meters
Disabled

Indication

A +kVAh

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 80
09-01-2014

NOJA-522-06
Default
DNP ID
Disabled

Data
group
Indication

Database ID
B +kVAh

Description
B phase total
forward energy

Disabled

Indication

C +kVAh

C phase total
forward energy

Disabled

Indication

A +kVArh

Disabled

Indication

B +kVArh

Disabled

Indication

C +kVArh

Disabled

Indication

A -kVAh

A phase
reactive
forward energy
B phase
reactive
forward energy
C phase
reactive
forward energy
A phase total
reverse energy

Disabled

Indication

B -kVAh

B phase total
reverse energy

Disabled

Indication

C -kVAh

C phase total
reverse energy

Disabled

Indication

A -kVArh

Disabled

Indication

B -kVArh

Disabled

Indication

C -kVArh

Indication

+kVAh

Disabled

Indication

+kVArh

10

Indication

-kVAh

Disabled

Indication

-kVArh

Disabled

Indication

A +kWh

A phase
reactive
reverse energy
B phase
reactive
reverse energy
C phase
reactive
reverse energy
Three phase
total forward
energy
Three phase
reactive
forward energy
Three phase
total reverse
energy
Three phase
reactive
reverse energy
A phase active
forward energy

Disabled

Indication

B +kWh

B phase active
forward energy

Disabled

Indication

C +kWh

C phase active
forward energy

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Valid
Range
0 to
4294967295
kVAh
0 to
4294967295
kVAh
0 to
4294967295
kVArh
0 to
4294967295
kVArh
0 to
4294967295
kVArh
0 to
4294967295
kVAh
0 to
4294967295
kVAh
0 to
4294967295
kVAh
0 to
4294967295
kVArh
0 to
4294967295
kVArh
0 to
4294967295
kVArh
0 to
4294967295
kVAh
0 to
4294967295
kVArh
0 to
4294967295
kVAh
0 to
4294967295
kVArh
0 to
4294967295
kWh
0 to
4294967295
kWh
0 to
4294967295
kWh

Resolution
scale
factor
1

Default
Reporting
Deadband
0

Default
Class
0

No

Yes

No

No

Yes

No

No

Yes

No

No

100000
kVAh

No

No

100000
kVAh

No

No

Yes

No

No

NOJA-522-06

Single
Phase
Recloser
No

Page 81
09-01-2014

NOJA-522-06
Default
DNP ID
Disabled

Data
group
Indication

Database ID
A -kWh

Description
A phase active
reverse energy

Disabled

Indication

B -kWh

B phase active
reverse energy

Disabled

Indication

C -kWh

C phase active
reverse energy

Disabled

Indication

+kWh

Disabled

Indication

-kWh

Three phase
active forward
energy
Three phase
active reverse
energy

Valid
Range
0 to
4294967295
kWh
0 to
4294967295
kWh
0 to
4294967295
kWh
0 to
4294967295
kWh
0 to
4294967295
kWh

Resolution
scale
factor
1

Default
Reporting
Deadband
0

Default
Class
0

Single
Phase
Recloser
Yes

No

No

No

No

SCADA Counters
Disabled

Indication

Call Drop outs

Disabled

Indication

Calls Failed

11

Indication

Tx Frames

12

Indication

Rx Frames

13

Indication

Length errors

14

Indication

CRC errors

Disabled

Indication

Dnp3
Communication
Watchdog
Timeout

The number of
modem calls
where RC10
did not initiate
hanging up.
Increments
when Slave
does not
connect to the
base station
modem.
Transmitted
frame count
Received
frame count
Frame length
error count
Frame CRC
error count
Number of
times
communication
Watchdog
timer timed out

0 to
4294967295

Yes

0 to
4294967295

Yes

0 to
4294967295
0 to
4294967295
0 to
4294967295
0 to
4294967295
0 to 65535

100

Yes

100

Yes

100

Yes

100

Yes

Yes

Maximum
Demand A
phase current
today
Maximum
Demand B
phase current
today
Maximum
Demand C
phase current
today

0 to 16000
A

Yes

0 to 16000
A

No

0 to 16000
A

No

Maximum Demand Counters


Disabled

Indication

la MDI Today

Disabled

Indication

lb MDI Today

Disabled

Indication

lc MDI Today

(1)

(1)

(1)

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 82
09-01-2014

NOJA-522-06
Default
DNP ID
Disabled

Data
group
Indication

Disabled

Indication

lb MDI
(1)
Yesterday

Disabled

Indication

lc MDI
(1)
Yesterday

Disabled

Indication

la MDI Last
(1)
Week

Disabled

Indication

lb MDI Last
(1)
Week

Disabled

Indication

lc MDI Last
(1)
Week

Database ID
la MDI
(1)
Yesterday

Description
Maximum
Demand A
phase current
yesterday
Maximum
Demand B
phase current
yesterday
Maximum
Demand C
phase current
yesterday
Maximum
Demand A
phase current
last week
Maximum
Demand B
phase current
last week
Maximum
Demand C
phase current
last week

Resolution
scale
factor
1

Default
Reporting
Deadband
0

Default
Class
0

0 to 16000
A

No

0 to 16000
A

No

0 to 16000
A

Yes

0 to 16000
A

No

0 to 16000
A

No

Valid
Range
0 to 16000
A

Single
Phase
Recloser
Yes

Note: Change event generation:


Change event is generated under conditions:
X = Last Reported Value
Y = New Value
D = Deadband Value
Y > (X + D) or Y < (X - D)

Note 1: Maximum Demand Indication (MDI) is implemented only as Protocol Points and report only values of
currents (Ia, Ib, Ic and In). The RMS value of current in phases A, B, C and In are averaged in accordance with
Load Profile configuration.
Load Profile is user configurable for the intervals of 1/2/5/10/15/30/60/120 minutes. For customer, to have
average MDI time of 15 minutes, the Load Profile time must be set to 15 minutes. All of the MDI values are
volatile and will be reset back to zero when the controller is reset.
The MDI records are reported as for TODAY, YESTERDAY and LAST WEEK.
Definitions of these are:
The TODAY Load Profile is monitored for the highest value in the records from last midnight till now.
The YESTERDAY Load Profile is monitored for the highest value in the records for the 24 hours till
last midnight.
The LAST WEEK Load Profile is monitored for the highest record during the last 7 days till last
midnight.
The values for record types (YESTERDAY and LAST WEEK) are updated only on expiration of the relevant
period. The value for record type TODAY is updated when a new maximum for TODAY is detected.
DNP3 Device Profile Document
Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 83
09-01-2014

NOJA-522-06
5.5

DEFINITION OF ANALOG INPUT POINT


LIST:

List all addressable points. Points that do not exist (for


example, because an option is not installed) shall be
omitted from the table.

Fixed, list shown in table below


Configurable (current list may be shown in table
below)
Other, explain_____________________

Note: the number of analog inputs present in the device,


and the maximum analog input index, are available
remotely using object Group 0 Variations 233 and 232.

The following table lists Analog Inputs (Object 30).


This implementation uses fixed deadband reporting, the value in the Default Deadband column
represents the absolute amount by which the point must change before an analog change event will
be generated. The value in the Default Class column represents the class (1, 2, 3, or none) in which
detected change events will be reported. Only the default values for these items are documented here
because the values may change in operation due to either local (user-interface) or remote (through
DNP) configuration control.
Changes to class allocation arising from use of DNP3 function 22 are saved to volatile memory.
Changes to reporting deadband arising from use of DNP3 function 2 are saved to volatile memory.
Static (Steady-State) Object Number:

30

Change Event Object Number:

32

Reporting Deadband Object Number:

34

Request Function Codes supported: 1 (read), 2 (write, deadbands only), 22 (assign class)
Default Static Variation reported when variation 0 requested:
Input).

(Note 1) 2 (16-Bit Analog

Default Change Event Variation reported when variation 0 requested:


Event with Time)

(Note 1) 3 (Analog Change

Reporting Deadband Variation reported when variation 0 requested:


Deadband)

1 (16-Bit Reporting

Status bits supported: over range, local forced data


Note 1: The actual variation reported in response to a variation 0 request can be configured on a per-point
basis.

Note: Analog inputs are always considered online and the on-line status bit is always set.
Resolution scale factor shows on what coefficient it is necessary to multiply the obtained value to
receive true.
Analog input change events are detected by the IED at the time they occur and are not subject to a
scan rate. Time stamps associated with Analog change events depend on the analog in question.
Measurement values are updated every 16 cycles of power frequency; a change event is generated if
deadband is exceeded for any point. Protection related analog change events have time stamps that
correspond to the related CO Operations event.
DNP3 Device Profile Document
Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 84
09-01-2014

NOJA-522-06
The value in the Default DNP ID column represents the default setting. This parameter is user
configurable between 0 and 255, individual points can be selected for mapping or disabled using CMS
software.
The values in the Range column represent analog values that may be transmitted depending on the
ratings of the OSM connected to the RC cubicle. RC measurement accuracy is defined in the
Specifications section of the OSM User Manual.

Default
DNP ID

Data
group

Database ID

Description

Valid
Range

Resolution
scale
factor

Default
Reporting
Deadband

Default
Class

Single
Phase
Recloser

10 A

Yes

10 A

No

10 A

No

0.001

0 kV

Yes

0.001

0 kV

No

0.001

0 kV

No

0.001

0 kV

Yes

0.001

0 kV

No

0.001

0 kV

No

0.001

0.5 kV

No

0.001

0.5 kV

No

0.001

0.5 kV

No

0.001

0 kV

No

0.001

0 kV

No

0.001

0 kV

No

1A

No

1A

No

0 kVA

Yes

Measured Data
0

Indication

Ia

A phase current

Indication

Ib

B phase current

Indication

Ic

C phase current

Disabled

Indication

Ua

Disabled

Indication

Ub

Disabled

Indication

Uc

Disabled

Indication

Ur

Disabled

Indication

Us

Disabled

Indication

Ut

Indication

Uab

Indication

Ubc

Indication

Uca

Disabled

Indication

Urs

Disabled

Indication

Ust

Disabled

Indication

Utr

Disabled

Indication

I2

Phase to earth
voltage Ua
Phase to earth
voltage Ub
Phase to earth
voltage Uc
Phase to earth
voltage Ur
Phase to earth
voltage Us
Phase to earth
voltage Ut
Line to Line
voltage Uab
Line to Line
voltage Ubc
Line to Line
voltage Uca
Line to Line
voltage Urs
Line to Line
voltage Ust
Line to Line
voltage Utr
Neg. Phase
Sequence

Indication

In

Neutral current

Disabled

Indication

A kVA

A phase kVA

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

0 to
16,000
A
0 to
16,000
A
0 to
16,000
A
0 to 30.0
kV
0 to 30.0
kV
0 to 30.0
kV
0 to 30.0
kV
0 to 30.0
kV
0 to 30.0
kV
0 to 38.0
kV
0 to 38.0
kV
0 to 38.0
kV
0 to 38.0
kV
0 to 38.0
kV
0 to 38.0
kV
0 to
16,000
A
0 to
16,000
A
0 to
65535
kVA
NOJA-522-06

Page 85
09-01-2014

NOJA-522-06
Default
DNP ID
Disabled

Data
group
Indication

Database ID
B kVA

Description
B phase kVA

Disabled

Indication

C kVA

C phase kVA

Disabled

Indication

A kW

A phase kW

Disabled

Indication

B kW

B phase kW

Disabled

Indication

C kW

C phase kW

Disabled

Indication

A kVAr

A phase kVAr

Disabled

Indication

B kVAr

B phase kVAr

Disabled

Indication

C kVAr

C phase kVAr

Indication

kVA

Three phase kVA

Indication

kW

Three phase kW

Indication

kVAr

Three phase kVAr

10

Indication

F ABC

ABC side
frequency

Disabled

Indication

F RST

RST side
frequency

11

Indication

PF

Disabled

Indication

A PF

Disabled

Indication

B PF

Disabled

Indication

C PF

12

Indication

Phase seq.
ABC

Three phase
power factor
A phase power
factor
B phase power
factor
C phase power
factor
Phase sequence
from ABC side
ABC = 1

Valid
Range
0 to
65535
kVA
0 to
65535
kVA
0 to
65535
kW
0 to
65535
kW
0 to
65535
kW
0 to
65535
kVAr
0 to
65535
kVAr
0 to
65535
kVAr
0 to
65535
kVA
0 to
65535
kW
0 to
65535
kVAr
46.00 to
65.00
Hz
46.00 to
65.00
Hz
0.00 to
1.00
0.00 to
1.00
0.00 to
1.00
0.00 to
1.00
0 to 2

Resolution
scale
factor
1

Default
Reporting
Deadband
0 kVA

Default
Class
0

Single
Phase
Recloser
No

0 kVA

No

0 kW

Yes

0 kW

No

0 kW

No

0 kVAr

Yes

0 kVAr

No

0 kVAr

No

500 kVA

No

500 kW

No

500 kVAr

No

0.001

0.1 Hz

Yes

0.001

0 Hz

Yes

0.001

No

0.001

Yes

0.001

No

0.001

No

No

No

ACB = 0
Unresolved = 2
Disabled

Indication

Phase seq.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Phase sequence

0 to 2
NOJA-522-06

Page 86
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group

Database ID
RST

Description
from RST side

Valid
Range

Resolution
scale
factor

Default
Reporting
Deadband

Default
Class

Single
Phase
Recloser

RST = 1
RTS = 0
Unresolved = 2
Disabled

Indication

Phase
Configuration

Disabled

Indication

LGVT Ia

(9)

Disabled

Indication

LGVT Ib

(9)

Disabled

Indication

LGVT Ic

(9)

Disabled

Indication

DE OC

Disabled

Indication

DE NPS

Disabled

Indication

DE EF

Phases
Configured as
ABC = 0, ACB = 1,
BCA = 2, CAB = 3,
BAC = 4, CBA = 5
A phase current
value recorded
before Recloser
operated.
B phase current
value recorded
before Recloser
operated.
C phase current
value recorded
before Recloser
operated.

1 to 5

No

0 to
16,000
A

10A

Yes

0 to
16,000
A

10A

No

0 to
16,000
A

10A

No

OC power flow
direction
Positive = 0
Negative = 1
Unresolved = 2
NPS power flow
direction
Positive = 0
Negative = 1
Unresolved = 2
EF Power flow
direction
Positive = 0

0 to 2

Yes

0 to 2

Yes

0 to 2

No

0 to 2

No

0 to
16,000
A
0 to
16,000
A

0A

Yes

0A

No

Protection

Negative = 1
Unresolved = 2
Disabled

Indication

DE SEF

SEF Power flow


direction
Positive = 0
Negative = 1

Disabled

Indication

Ia max Trip

Disabled

Indication

Ib max Trip

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Unresolved = 2
Maximum phase A
current prior to any
OCEF element trip
Maximum phase B
current prior to any
OCEF element trip

NOJA-522-06

Page 87
09-01-2014

NOJA-522-06
Default
DNP ID
Disabled

Data
group
Indication

Database ID
Ic max Trip

Disabled

Indication

I2 max Trip

Disabled

Indication

In max Trip

Disabled

Indication

UV min Trip

Disabled

Indication

OV max Trip

Disabled

Indication

UF min Trip

Disabled

Indication

OF max Trip

Disabled

Indication

Ia Trip

Disabled

Indication

Ib Trip

Disabled

Indication

Ic Trip

Disabled

Indication

I2 Trip

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Description
Maximum phase C
current prior to any
OCEF element trip
Maximum I2
current prior to any
NPS element trip
Maximum In
current prior to any
EF element trip
Minimum voltage
prior to any UV
elements trip
Maximum voltage
prior to any OV
elements trip
Minimum
frequency prior to
UF element trip
Maximum
frequency prior to
OF element trip
Value of current in
A phase at the
time when Trip
command is
issued. Value is
stored until next
protection trip or
when cleared by
command from
Master
Value of current in
B phase at the
time when Trip
command is
issued. Value is
stored until next
protection trip or
when cleared by
command from
Master
Value of current in
C phase at the
time when Trip
command is
issued. Value is
stored until next
protection trip or
when cleared by
command from
Master
Value of current at
the time when Trip
command is
issued. Value is

Resolution
scale
factor
1

Default
Reporting
Deadband
0A

Default
Class
0

0A

No

0A

No

0.001

0kV

Yes

0 to
38.0kV

0.001

0kV

Yes

46.00 to
65.00
Hz
46.00 to
65.00
Hz
0 to
16,000
A

0.001

0Hz

Yes

0.001

0Hz

Yes

0A

Yes

0 to
16,000
A

0A

No

0 to
16,000
A

0A

No

0 to
16,000
A

0A

No

Valid
Range
0 to
16,000
A
0 to
16,000
A
0 to
16,000
A
0 to
38.0kV

NOJA-522-06

Single
Phase
Recloser
No

Page 88
09-01-2014

NOJA-522-06
Default
DNP ID

Data
group

Database ID

Disabled

Indication

In Trip

Description
stored until next
protection trip or
when cleared by
command from
Master
Value of residual
current at the time
when Trip
command is
issued. Value is
stored until next
protection trip or
when cleared by
command from
Master

Resolution
scale
factor

Default
Reporting
Deadband

Default
Class

0 to
16,000
A

0A

No

Yes

0.01

1V

Yes

0.01

0.5A

Yes

10

Yes

0.001

0V

Yes

Valid
Range

Single
Phase
Recloser

Lifetime Counters
Disabled

Indication

CO Total

Number of Close
Open Operations

0 to
65535
0.00 40.95
-4.00 to
+4.00 A
0 to
100%
0.00 40.95

UPS Status
13

Indication

Ubt

Battery voltage

14

Indication

Ibt

15

Indication

Cbt

Disabled

Indication

Ubt Scaled

Battery charge
current
Battery residual
capacity
Battery voltage
(Scaled)

Notes:
1. Data representation:
(0 to 65535) non-negative integer number occupies 2 bytes, except for Data base ID Ibt (32768 to
32767)
(0 to 4294967296) non-negative integer number occupies 4 bytes.
2. Step value in Valid Range is equal 1*Resolution scale factor.
3. Power values (single and three phase kVA, kVAr and kW) have a maximum range of 65535. Values
higher than this are represented as 65535 and the Over-range status bit is set to 1.
4. If there is a situation when it is not possible to calculate power factor or frequency, a value equal to
0xFFFF is reported.
5. Valid Range is given as supplemental information.
6. Change event generation:
Change event is generated under conditions:
X = Last Reported Value;
Y = New Value;
D = Deadband Value;
Y > (X + D) or Y < (X - D)

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 89
09-01-2014

NOJA-522-06
7. The Ia max Trip, Ib max Trip, Ic max Trip, I2 max Trip, In max Trip, UVmin Trip, OVmax Trip, UFmin
Trip, OFmax Trip values are updated when a new record is generated during a CO operation. Only the
point related to the phase that caused the trip is updated.
8. All the Ia Trip, Ib Trip, Ic Trip and In Trip analogs are updated when a trip occurs.
They can be reset to zero using the Reset Trip current Values binary output point.
9. Last Good Value Trapped (LGVT) measured data is implemented only as Protocol Points (Analogue
Input Points for DNP3 and Measured Values for IEC 60870-5-101/104) and report only values of phase
currents (Ia, Ib, Ic). LGVT is calculated as 1 minute average value. The LGVT will be frozen at its
previous 1-minute average value while the current is 0 Amps or Pickup_LSD flag is set.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 90
09-01-2014

NOJA-522-06
5.6

DEFINITION OF ANALOG OUTPUT


STATUS/ANALOG OUTPUT CONTROL
BLOCK POINT LIST:

Fixed, list shown in table below


Configurable (current list may be shown in table
below)
Other, explain Not Supported

List all addressable points. Points that do not exist (for


example, because an option is not installed) shall be
omitted from the table.
Note: the number of analog outputs present in the device,
and the maximum analog output index, are available
remotely using object Group 0 Variations 221 and 220.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 91
09-01-2014

NOJA-522-06
5.7

DEFINITION OF FILE NAMES THAT


MAY BE READ OR WRITTEN:

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Fixed, list shown in table below


Configurable(current list may be shown in table
below)
Other, explain Not Supported

NOJA-522-06

Page 92
09-01-2014

NOJA-522-06
DEFINITION OF OCTET STRING POINT
LIST:

5.8

List all addressable points. Points that do not exist (for


example, because an option is not installed) shall be
omitted from the table.

Fixed, list shown in table below


Configurable (current list may be shown in table
below)
Other, explain_____________________

This object provides support for HMI password and the version and serial number strings.
Default DNP ID

Database ID

Max string length

Permitted characters
A Z; 0 9; space

HMI Password

Relay Version String

40

A Z; a z; 0 9; space

Disabled

Relay Serial Number

13

A Z; a z; 0 9; Space

Disabled

Relay Hardware Version

40

A Z; a z; 0 9; Space

Disabled

Relay FPGA version

40

A Z; a z; 0 9; Space

Disabled

SIM Hardware Version

40

A Z; a z; 0 9; Space

Disabled

SIM Software Version

40

A Z; a z; 0 9; Space

Disabled

SIM Serial Number

13

A Z; a z; 0 9; Space

Disabled

Panel Serial Number

13

A Z; a z; 0 9; Space

Disabled

Panel HMI Version

40

A Z; a z; 0 9; Space

Disabled

Panel Hardware Version

40

A Z; a z; 0 9; Space

Disabled

Panel Software Version

40

A Z; a z; 0 9; Space

Disabled

OSM Serial Number

13

A Z; a z; 0 9; Space

Disabled

OSM Model Number

40

Disabled

IO1 Serial Number

13

A Z; a z; 0 9; Space
A Z; a z; 0 9; Space

Disabled

13

A Z; a z; 0 9; Space

Disabled

IO2 Serial Number


IO1 Software Version

40

A Z; a z; 0 9; Space

Disabled

IO2 Software Version

40

A Z; a z; 0 9; Space

Disabled

IO1 Hardware Version

40

A Z; a z; 0 9; Space

Disabled

IO2 Hardware Version

40

A Z; a z; 0 9; Space

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 93
09-01-2014

NOJA-522-06
5.9

DEFINITION OF VIRTUAL TERMINAL


PORT NUMBERS:

List all addressable points. Points that do not exist (for


example, because an option is not installed) shall be
omitted from the table.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Fixed, list shown in table below


Configurable (current list may be shown in table
below)
Other, explain Not Supported.

NOJA-522-06

Page 94
09-01-2014

NOJA-522-06
5.10

DEFINITION OF DATA SET


PROTOTYPES:

List of all data set prototypes. The following table is


repeated for each Data Set Prototype defined.

Fixed, Data Set Prototypes are shown in table below


Configurable, list methods:
(a list of currently defined Data Set Prototypes may be
shown in tables below)
Other, explain Not Supported

Note: the numbers of data set prototypes known to


the device are available remotely using the protocol
object Group 0 Variations 212 and 213.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 95
09-01-2014

NOJA-522-06
5.11

DEFINITION OF DATA SET


DESCRIPTORS:

List of all data set descriptors. The following tables are


repeated for each Data Set Descriptor defined. Note:
the numbers of data sets known to the device are
available remotely using the protocol object Group 0
Variations 214 and 215.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Fixed, Data Set Descriptors are shown in table below


Configurable (current list may be shown in table
below)
Other, explain Not Supported

NOJA-522-06

Page 96
09-01-2014

NOJA-522-06
5.12

DATA SET DESCRIPTOR POINT INDEX ATTRIBUTES

The following table is optional and correlates data set elements to point indexes of standard DNP3 Data Objects.
The element number below refers to the position in the present value (object 87) or event (object 88) data set
and will not match the element number in the data set descriptor or data set prototype tables above.
Duplicate this table for each Data Set Descriptor defined

Not Supported.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 97
09-01-2014

NOJA-522-06

6 INTERNAL INDICATIONS
The following table lists Internal Indications (IINs), and the conditions that would cause them.
Standard DNP3 IINs are reported in every response message.
This table lists standard DNP3 IINs.
Internal Indications
Object Number: 80
Request Function Codes supported:
1 (read), 2 (write)
Default Variation reported when variation 0 requested: 1
Poi
nt
Descriptions and Conditions
Ind
ex
0
IIN1-0 All Stations set after a broadcast message (any message using a destination
address of 0xfff0 or above) has been received. Does not indicate an error condition.
1
IIN1-1 Class 1 event data available. Can be set at any time and does not indicate an error
condition.
2
IIN1-2 Class 2 event data available. Can be set at any time and does not indicate an error
condition.
3
IIN1-3 Class 3 event data available. Can be set at any time and does not indicate an error
condition.
4
IIN1-4 Time synchronization required. Can be set at any time and does not indicate an error
condition.
5
IIN1-5 Local mode. Set if the device is in an operating mode that will block commands from
the Master.
(RC10 communications ports can be configured as either a local or remote user)
6
IIN1-6 Device Trouble. Set if a device malfunction is detected refer to Malfunctions section
of Binary Inputs and/or the user manual for a description of possible causes.
7
IIN1-7 Device restarts. Set only under specific conditions. Does not indicate an error
condition.
8
IIN2-0 Function Unknown. Generally means that the function code (octet 2 of the request
header) cannot be processed.
9
IIN2-1 Object Unknown. Generally means that the function code could be processed but the
object group / variation could not be processed.
10
IIN2-2 Parameter Error. Generally indicates that both the function code and object group /
variation could be processed but that the qualifier / range field is in error.
11
IIN2-3 Buffer Overflow. Indicates that an event buffer has overflowed, and that change
events, of at least one type, have been lost.
12
IIN2-4 Already Executing.
NOT SUPPORTED
13
IIN2-5 Bad configuration.
14
IIN2-6 Reserved. Always 0.
15
IIN2-7 Reserved. Always 0.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Writabl
e?
No
No
No
No
No
No

No
Yes
No
No
No
No
NA
No
NA
NA

Page 98
09-01-2014

NOJA-522-06

7 BUFFER SIZE
Maximum number of events held in volatile RAM buffers:
object 2 (binary)
object 22 (counters)
object 23 (frozen counters)
object 32 (analog)

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

- 500 events;
- 400 events;
- 350 events;
- 350 events.

NOJA-522-06

Page 99
09-01-2014

NOJA-522-06

8 DNP3 SETTINGS
Yes

HMI
(Control)
Yes

never

Yes

No

3s

Yes

No

Yes

No

64 to 292
octets step
size 1

292

Yes

No

On (Ticked)
Off (Unticked)

Off

Yes

No

0 to 3600s

5s

Yes

No

Yes

No

Name

Explanation

Range

Link Layer
Slave Address
Link Layer
Confirmation
Mode
Link Layer
Confirmation
Timeout

The DNP Link address of this device.

0 to 65534
Step size 1
Never,
Sometimes,
Always
0 to 60s

Link Layer
Maximum
Retries

This parameter is used to determine if or when the device


may request confirmation from the DNP master of data link
layer frames transmitted to the master.
Timeout value, in seconds, used to wait for DNP master to
confirm a previously transmitted link layer frame with a
request for confirmation. This value is independent of Appl
Cf Timeout; if link confirmations are being used (see Link Cf
Mode), the application confirmation timer is not started until a
link confirmation is received.
The maximum number of times this device will re-transmit a
link layer frame for which a confirmation had been requested
but not received within Link Cf Timeout. Note that this
number is in addition to the initial attempt to transmit the
frame; i.e., if the value of this parameter is 2, then an
unsuccessful transmission will send a total of 3 identical
frames.
Maximum size of frame to transmit

Link Layer
Maximum
Transmitted
Frame Size
Link Layer
Specify whether or not to validate the master address in
Validate Master received frames. DNP3 frames
Address
contain both a master address field and a
slave address field. If OFF then TMW DNP3 SCL will not
validate the master address and frames whose slave
address matches a configured slave session will be
accepted.
Setting this to ON requires both master and slave addresses
to match a local slave session before the frame is accepted.
Application
Amount of time, in seconds, after a select command is
Layer
received before which an operate command must be
SBO Timeout
received. If this time is exceeded, the select will be aborted
(SBO = Select and any subsequent operate will not be executed.
Before
Operate)
Application
This parameter is used to determine if or when the device
Layer
may request confirmation from the DNP master of application
Confirmation
layer frames transmitted to the master.
Mode

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Default
value
5

CMS

Step size 1s

0 to 32767
Step size 1

Step Size 1s

Events (only Events


when
and Mult
reporting
event data)
Events and
Multi-Packets
(when
reporting
events or
multi
fragment
messages)

Page 100
09-01-2014

NOJA-522-06

Yes

HMI
(Control)
No

Yes

No

0 to 65530ms 5000ms
Step size 1
ms

Yes

No

The time, in ms, encoded in a response to a request from a


0 to 65530ms 1000ms
master for a warm restart. The master is thereby notified to
Step size 1
wait this amount of time after receiving the response before it ms
can resume polling this device.

Yes

No

Name

Explanation

Range

Application
Layer
Confirmation
Timeout

Timeout value, in seconds, used to wait for DNP master to


confirm a previous response to the master containing a
request for confirmation. This value is independent of Link
Cf Timeout; if link confirmations are being used (see Link Cf
Mode), the application confirmation timer is not started until a
link confirmation is received.
This parameter is also used as part of the control for when
an unconfirmed unsolicited response can be re-generated
and re-transmitted. See Unsol Retry Delay.
To ensure correct operation of confirm timeouts if Link Cf
Mode is set to sometimes or always the RC10 checks that
Appl Cf Timeout >= ((Link Max Retries + 1) x Link Cf TO x 7).
If the user enters a value less than this the RC10 will
overwrite it with the above value.
The amount of time, in minutes, after a DNP master executes
a time synchronization with this device before this device
sets the need time Internal Indication (IIN) bit to request
another time synchronization. This value indicates the rate at
which the internal clock of this device becomes out-of-sync
with the masters clock. If this parameter is set to 0, the
need time IIN bit will never be set.
The time, in ms, encoded in a response to a request from a
master for a cold restart. The master is thereby notified to
wait this amount of time after receiving the response before it
can resume polling this device.

0 to 3600s

Application
Layer
Need Time
Delay

Application
Layer
Cold Restart
Delay
Application
Layer Warm
Restart Delay

Unsolicited
Response

If On, unsolicited responses are permitted; if Off, they are


not. If permitted, the device will transmit an initial null
unsolicited response, and will continue to send it until an
application layer confirmation of it is received from the DNP
Master device.
From that point on, the DNP Master must issue an
unsolicited enable request message for one or more of the
three event classes of data (class 1, 2, or 3) before any more
unsolicited response messages will be transmitted.
If false, then unsolicited enable and unsolicited disable
messages from the DNP Master device will not be allowed
a BAD CONFIGURATION Internal Indication (IIN) response
will be returned.
Unsolicited
Specifies the DNP link address destination (a DNP master)
Response
of unsolicited responses. If unsolicited responses are
Master Address enabled (see Unsolicited), then all unsolicited response
messages, including the initial null unsolicited response, are
transmitted to this address at startup.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Default
value
84s

CMS

Step Size 1s

0 to 69120
min

1440 min

Step Size
1min

On (Ticked)
Off (Unticked)

Off

Yes

Yes

0 to 65534

Yes

Yes

Step Size 1

Page 101
09-01-2014

NOJA-522-06
Name

Explanation

Range

Unsolicited
Response
Retry Delay

This parameter specifies the minimum amount of time


between unsuccessfully confirmed unsolicited responses.
If an unsolicited response is not confirmed within Appl Cf
Timeout, this parameter controls how soon another
unsolicited response will be sent. If this parameter is zero or
less than Appl Cf Timeout, the "retry" unsolicited response
will be sent as soon as Appl Cf Timeout expires.
During the time set by Appl Cf Timeout, any received read
request received from the DNP Master device will be
postponed until after Appl Cf Timeout has expired. If
multiple read requests are received, only the last read
request would be postponed; the previous read-requests will
be ignored entirely.
Once the number of retries is equal to Unsol Retries, the
interval between retries is then controlled by Unsol Offline
Interval, not Unsol Retry Delay.
The maximum number of times this device will re-transmit an
unsolicited response without receiving a confirmation from a
Master at an interval defined by Unsol Retry Delay. Once
this value is reached, the unsolicited response will continue
to be retransmitted but at a potentially different interval
defined by Unsol Offline Interval.
If an unsolicited response has been retried Unsol Max
Retries times without a confirmation then this parameter
defines the time interval between unsolicited retries from that
point forward. It allows the interval between retries to be
increased if no confirmation is being received while still
allowing an infinite number of unsolicited retries.
Specify the initial/new state of the unsolicited event mask.
This mask is used to determine which event class(es) will
generate unsolicited
responses. According to the DNP3 User Guide, unsolicited
responses should be disabled until an 'Enable Unsolicited
Response' request is received from the master. Hence this
value should generally be 0, but some masters do not
generate the 'Enable Unsolicited Response' message in
which case they must be enabled here.

0 to 86400s

Unsolicited
Response
Retries

Unsolicited
Response
Offline Interval

Unsolicited
Response
Mask
Class 1
Class 2
Class 3

Unsolicited
Response
Events
Class 1
Class 2
Class 3

Used to specify conditions under which an unsolicited


response is generated. For each class, if the number of
events occurring for that class meets or exceeds this value,
then an unsolicited response will be generated (as long as
the DNP Master device has enabled the class -- see
Unsolicited).
Note that other conditions may cause an unsolicited
response to be generated see C1, C2, C3 Delay.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Default
value
60s

Yes

HMI
(Control)
No

255

Yes

No

300s

Yes

No

0x00
Yes
(Unsolicite
d for class
1, 2, 3
disabled)

No

3
5
10

No

CMS

Step Size 1s

0 to 255
Step Size 1

0 to 86400s
Step Size 1s

(0x00 0x07)
Any
combination
of
0x01
(Unsolicited
for class 1
enabled)
0x02
(Unsolicited
for class 2
enabled)
0x04
(Unsolicited
for class 3
enabled)
1 to 255
Step Size 1

Yes

Page 102
09-01-2014

NOJA-522-06
Name

Explanation

Unsolicited
Response
Delay
Class 1
Class 2
Class 3

Used to specify conditions under which an unsolicited


response is generated. For each class, if the amount of time
since an event has occurred for that class meets or exceeds
this value, then an unsolicited response will be generated (as
long as the DNP Master device has enabled the class see
Unsolicited).
If the value for this parameter is 0 for a class, then this
parameter is disabled for that class, and only C1, C2, C3
Events controls conditions under which will generate an
unsolicited response for that class.
Note that other conditions may cause an unsolicited
response to be generated see C1, C2, C3 Delay.
Communication If the protocol is not polled within a user set time period then
Watchdog
the external supply will be reset. This timer is reset whenever
Poll Timeout
protocol is polled. This timer overrides the External Load
Reset Timer.
Communication If the binary control is not activated within a user set time
Watchdog
period then the external supply will be reset. This timer is
Binary Control reset whenever allocated binary control point is modified.
This timer overrides the External Load Reset Timer.
SCADA Time
Used to set internal clock to Local or GMT/UTC.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Step Size 1s

Default
value
3s
5s
10s

0 to 86400s

60 min

Yes

No

Step Size
1min
0 to 86400s

60 min

Yes

No

GMT/UTC

Yes

No

Range

NOJA-522-06

0 to 86400s

Step Size
1min
Local/
GMT/UTC

Yes

HMI
(Control)
No

CMS

Page 103
09-01-2014

NOJA-522-06
STATIC AND EVENT OBJECT DEFAULT VARIATIONS

8.1

The default variation is used whenever variation 0 is requested and in response to class polls. The RC10 allows
per-point individual configuration of default variation. In addition, the reporting mode of analog input events may
be specified for variations that do not include a timestamp. The reporting mode may be either:
-

Report All: Which will create one event object for every event that has occurred between responses.

Report Last: Which will have a maximum of one event object for each point in each response, the object will
represent the most recent event.

Name

Explanation

Binary
Input
Object 01

Specifies the default variation for object 01,


binary input. The default variation is used
whenever variation 0 is requested, and in
responses to class polls.
Binary
This value specifies the default variation for
Input
object 02, binary input change events. The
Object 02
default variation is used whenever variation 0
is requested, and in responses to class polls.
Binary Output This value specifies the default variation for
Object 10
object 10, binary output. The default variation
is used whenever variation 0 is requested,
and in responses to class polls.
Binary Counter This value specifies the default variation for
Object 20
object 20, binary (running) counters. The
default variation is used whenever variation 0
is requested, and in responses to class polls.

Binary
Counter
Object 21

This value specifies the default variation for


object 21, frozen counters. The default
variation is used whenever variation 0 is
requested, and in responses to class polls.

Binary
Counter
Object 22

This value specifies the default variation for


object 22, binary (running) counter change
events. The default variation is used
whenever variation 0 is requested, and in
responses to class polls.

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

Default
value
2

CM
S
Yes

HMI
(Control)
No

1 (without time),
2 (with time)
3 (with relative time)

Yes

No

1 (without status),
2 (with status)

Yes

No

1 (32-bit binary counters


with status)
2 (16-bit binary counters
with status)
5 (32-bit binary counters
without status)
6 (16-bit binary counters
without status)
255 (disabled)
1 (32-bit frozen counters
with status)
2 (16-bit frozen counters
with status)
5 (32-bit frozen counters
with time)
6 (16-bit frozen counters
with time)
9 (32-bit frozen counters
without status)
10 (16-bit frozen counters
without status)
255 (disabled)
1 (32-bit binary counters
without time)
2 (16-bit binary counters
without time)
5 (32-bit binary counters
with time)
6 (16-bit binary counters
with time)
255 (disabled)

Yes

No

Yes

No

Yes

No

Range
1 (without status),
2 (with status)

NOJA-522-06

Page 104
09-01-2014

NOJA-522-06
Default
value
5

Name

Explanation

Range

Binary
Counter
Object 23

This value specifies the default variation for


object 23, frozen counter events. The default
variation is used whenever variation 0 is
requested, and in responses to class polls.

Analog
Input
Object 30

This value specifies the default variation for


object 30, analog input. The default variation
is used whenever variation 0 is requested,
and in responses to class polls.

Analog Input
Object 32

This value specifies the default variation for


object 32, analog input change events. The
default variation is used whenever variation 0
is requested, and in responses to class polls.

1 (32-bit binary counters


without time)
2 (16-bit binary counters
without time)
5 (32-bit binary counters
with time)
6 (16-bit binary counters
with time)
255 (disabled)
1 (32 bit analog with status), 1
2 (16 bit analog with status),
3 (32 bit analog without
status),
4 (16 bit analog without
status)
1 (32 bit analog without
3
time)
2 (16 bit analog without
time)
3 (32 bit analog with time)
4 (16 bit analog with time)

Analog Input
Object 34

In addition, the reporting mode of the without


time variations may be specified.
This value specifies the default variation for
object 34, analog input reporting deadband.
The default variation is used whenever reads
of variation 0 is requested.

1 (16 bit analog)


2 (32 bit analog)

CM
S
Yes

HMI
(Control)
No

Yes

No

Yes

No

Yes

No

Deadband values can be changed within the RC10 over SCADA by DNP3 function code 22.
Default deadbands are user set for all analog points and can be mapped into any particular configuration using
CMS software

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 105
09-01-2014

NOJA-522-06
8.2

DIAL OUT SETTINGS

Setting

Description

Range

Dial Out

Enable RC10 dial out

Predial
string
Dial
Numbers

Set of modem commands sent to modem before dialing


a number.
A maximum of five telephone numbers for dialing out
and connecting to a master. Each number can be a
maximum of 18 characters; a comma (,) is used to
generate a pause of 1 sec.
If the first number fails to respond, the RC10 waits for
the Autodial Interval to expire and tries the next
available number in the list.
Interval between failure to connect to one number
before initiating a call to the next.
Setting to zero (0) disables the interval and the next
number is dialed immediately the preceding number
fails.
The length of time the RC10 will wait after dialing a
number for a connection to be established.

Autodial
Interval

Connection
Timeout

On (Ticked)
Off (Un-ticked)
Predefined AT
commands.
5 strings,
each 18
characters
long without
AT prefix.
See dialing
chars*
0 to 255s
Step size 1s

Default
for
Modem
On

Accessib
le from
CMS
Yes

Accessib
le from
HMI
No

ATD

Yes

No

Yes

No

Yes

No

60s

Yes

No

0 to 255s
Step size 1s

* The following characters can be used in the pre-dial string and dial numbers:
Character
0-9
#
*
P

Description
Dialing digits.

Tone dialing

, (comma)

Pause. Used to set a pause between digits.

; (semicolon)

Return to command state after dialing.

Hook flash.

Wait for 5 seconds before proceeding.

Reverse handshake (go on-line in auto-answer mode).

Waits for second dial tone.

Pulse dialing.

For full details on configuring the communications refer to the


document RC10 SCADA Interface Description (NOJA-565-00)

DNP3 Device Profile Document


Vendor Name:

NOJA Power Switchgear

Device Name:
RC10 Controller

NOJA-522-06

Page 106
09-01-2014