Professional Documents
Culture Documents
Infiltration Drivers
zgP 1
1
2R Toa Tia
Wind Effect
Wind effect occurs as air moves over the top of the building. The
moving air increases the pressure on the windward side of the building.
As the air passes over the building it entrains air on the leeward side
into the air stream, creating a negative pressure on the leeward side of
the building. This pressure difference between the windward and
leeward sides of the building drives infiltration. The pressure
difference is proportional to the square of wind velocity V; hence wind
effect is typically greater during winter when wind speeds are higher.
v
2
Combustion Effect
Combustion effect occurs when combustion devices such as furnaces
use indoor air for combustion, and then expel exhaust gasses through
stacks to the outdoors. Air must leak into the building to make up the
air lost through the exhaust stack. Combustion effect is greatest
during winter when combustion furnaces, boilers, are hot water heaters
are more active.
Exterior Ducts
In warm climates it is common to run air supply ducts through
unconditioned spaces such as attics. Air supply ducts are rarely tightly
sealed and typically leak air. Air leaked from supply ducts into
unconditioned spaces is replaced through infiltration. Research shows
that this can be a major driver of infiltration. For example, the average
infiltration rate in 50 houses in Florida with exterior ducts increased
from 0.46 when the air conditioner was off to 2.10 when the air
conditioner was on.
ma
minf
50 houses in Florida:
ac,off 2.10
N
ac,on .46
N
AC
return ducts are not located in the same room, rooms with supply ducts
are over-pressurized and rooms with return ducts are underpressurized. These pressure differences increase air infiltration. Thus,
recommended practice is for each room to have equally sized supply
and return ducts.
returnineachroom 0
N
centralreturn 1.5N
otherwise
N
where
Toa
m1
Tia
m2
Example
inf for a 1,500 ft2 house with 8 ft ceilings if
Calculate Q
1.0,Tia 72F, Toa 30F.
N
inf VN
cp (Tia Toa)
Q
1
Btu
Btu
(1500
8)ft3 1.0
.018 3
(72 30) F 9,072
hr
hr
ft F
Qlatent)
In summer, A/C removes sensible & latent heat (dries air), Thus
Q
in f
Q
i nf, sen sib
le
in f,
l aten t
V
N
c
T
p (T
1
2 )
in f,sen sib
le
in f,
l atent
where
wh
fg
a
1
2
VN
hfg
1
2
V volumeof houseft3
airchanges
N
perhour1
hr
densityof air .075lba 3
ft
energy
required
to c ond
h
f
Example
Calculate the sensible & latent infiltration loads on a 1,500 ft2 house
with 8 ft ceilings if
inf,sensib
Q
le V N cp Toa Tia
1
Btu
Btu
1500 8 ft3 1.0
.018 3
90 70 F 4,320
hr
hr
ft F
inf,latent V N
Q
oa ia hfg
inf,latent
Q
1500
8 ft3
Btu
inf,latent 16,463
Q
hr
1.0
hr
lba
.075
ft3
.0248
.0078
lbw
lba
1,076
Btu
inf Q
inf,sensib
20,783
Q
16,463
le Qinf,latent 4,320
hr
a b Tia Toa
N
or ACH50
CFM50 60
V ft3
50 is:
from N
The Princeton Method to estimate the average N
N50
N
20
or ACH
ACH50
20
50 is:
from N
The Sherman Methodto estimate the average N
50
N
C H S L
or ACH
ACH50
C H S L
where the following coefficients can be estimated from the graph and
tables that follow.
C = leakage infiltration ratio: 26 (hot climate) < C < 14 (cold climate)
H = height correction factor
S =wind shielding correction factor
L = leakiness correction factor
CFM50[cfm]
0.35
A ft2
Example
The measured infiltration rate at 50 Pa indoor/outdoor pressure
difference in a 1,500 ft2 house is 1,800 cfm. Determine whether the
house meets the U.S. Energy Star criteria for air leakage.
CFM50 1,800cfm
1.2 0.35
A ft2
1,500ft2
The house does not meet the U.S. Energy Star criteria for air leakage.
ASHRAE Standard 62-1989
ASHRAE Standard 62-1989 recommends that all houses have
ventilation rates exceeding 0.35 ACH to remove air contaminants.
Thus, in very tight houses in which the natural infiltration rate is less
than 0.35 ACH, recommended practice is to install an air-to-air heat
exchanger, which continually brings in and exhausts outdoor air but
recovers energy between the two air streams.
10
11
ACH calculation
1. Calculate the volume of the house. You can find area of the floor
on housing.udayton.edu. Multiply the area by about 8 to get the
volume of the house in cubic feet.
CFM(measur
ed) 60
2. ACH at 50 Pascals, or ACH50
.
Volume
3. Find N C H S L .
4. Let C = 19, S = 1, L = 1 (normal house), 0.7 (drafty house), H =
1 (one story), 0.8 (2 stories).
ACH50
5. ACH
.
N
If you cant reach 50 Pa, then your house is either
big or very leaky. Use the Cant Reach Fifty (CRF)
Factor on the speed dial of the fan. Then multiply
your ACH50 by this CRF.
12
13
14
15
References :
(1)(http://www.energysavers.gov/your_home/insulation_airsealing/in
dex.cfm/mytopic=11310).
17