You are on page 1of 2

Power Quality and Measurements

SIPROTEC 7KE85
Fault Recorder

Description
The SIPROTEC 7KE85 is a powerful fault recorder with
integrated measuring of synchrophasors (PMU) according
to IEEE C37.118 and Power Quality measurement according to IEC 61000-4-30. Due to the high flexibility of trigger
functions, the SIPROTEC 7KE85 is ideally suited to monitor
the entire energy value chain from generation to distribution. The powerful automation and flexible configuration
with DIGSI 5 complements the range of functions.
Main function
Inputs and outputs

Hardware flexibility

Housing width

Fault Recorder
4 predefined standard variants
with up to 40 current and 40
voltage transformers, 43 binary
inputs, 33 binary outputs
Flexibly adjusted and expandable
I/O quantity structure within the
scope of the SIPROTEC 5 modular
system
1/3 to 1/1 x 19

Fault recorder SIPROTEC 7KE85 (1/3 device with 1/6 expansion module
and LED indications)

Power fluctuations and power swing processes


Test runs during commissioning

Functions
Up to 40 analog channels

Application Areas

Fast scan recorder

The fault recorder SIPROTEC 7KE85 is designed for medium-voltage systems, high-voltage systems and extra-high
voltage systems and power plants. The SIPROTEC 7KE85
provides a clearly structured and event-related evaluation
and documentation of your power system processes. It
enables you to analyze disturbances and to optimize your
power system.

Up to 2 slow scan recorders

Typical processes are:


Power system incidents such as critical load cases or
short circuits
Disturbances of the supply quality
Dynamic behavior of generators
Starting and switch-off processes of transformers (saturation behavior)

Up to 5 continuous recorders and 2 trend recorders


Power Quality recordings according to IEC 61000-4-30
(Harmonics, THD, TDD in preparation)
Sequence of event recorder for continuous recording of
binary status changes and IEC 61850 GOOSE Messages
Applicable as Phasor Measurement Unit (PMU) according to IEEE C37.118 standard
Transmission of records and triggering via IEC 61850
GOOSE messages
Sampling frequencies parameterizable from 1 kHz to
16 kHz
The user can allocate the 16-gigabyte buffer (16 GByte)
to the various recorders

Intelligent monitoring routines of the storage medium


ensure a high security of the archived data

Benefits

Loss-free data compression

Clearly structured and event-related evaluation and


documentation of your power system processes

Time synchronization via Precision Time Protocol (PTP)


IEEE 1588 Protocol, IRIG-B, DCF77 and SNTP

Data security and transparency throughout the entire


life cycle of the system save time and reduce costs

Free routing of measured values to the individual recorders

Clear and easy-to-use devices and software thanks to


user-friendly design

Free combination of the measuring groups for power


calculation

Increased quality and reliability of the engineering


process

Quality Attributes for representing the current signal


quality in a time signal view

High-performance communications components


guarantee safe and effective solutions

The trigger functions of a function block are the value of


the fundamental component, RMS value, zerosequence/positive sequence/ negative-sequence system,
frequency, active power/ reactive power / apparent
power

Full compatibility with IEC 61850 Edition 1 and 2


Highly available Ethernet communication due to Redundancy Protocols PRP and HSR

Level trigger and gradient trigger for each trigger


function
Flexible cross, network and manual trigger
Creating of own trigger functions using the graphic
automation editor CFC (Continuous Function Chart)
Trigger functions by combining single-point/doublepoint indications, analog values, binary signals, Boolean
signals and GOOSE messages
Cyber Security according NERC CIP and BDEW Whitepaper

Please contact us for an individual consultation.


We are looking forward to your request!
Published by:
Siemens AG 2015
Energy Management Division
Humboldtstr. 59
90459 Nuremberg
Germany
www.siemens.com/siprotec

For more information, please contact your Siemens-Partner or


our Customer Support Center.
Phone: +49 180 524 70 00
Fax:
+49 180 524 24 71
(Charges depending on the provider)
E-Mail: support.energy@siemens.com
SIPROTEC 7KE85 V7_profile.docx

All rights reserved.


Trademarks mentioned in this document are the property of
Siemens AG, its affiliates, or their respective owners.
Subject to change without prior notice.
The information in this document contains general descriptions
of the technical options available, which may not apply in
all cases. The required technical options should therefore
be specified in the contract.

For all products using security features of OpenSSL


the following shall apply:
This product includes software developed by the
OpenSSL Project for use in the OpenSSL Toolkit
(www.openssl.org).
This product includes cryptographic software written
by Eric Young (eay@cryptsoft.com).

You might also like