3TF, 3TH, 3TG, 3TB, 3TD, 3TE, 3TK, 3TC Contactors

Technical data
Page

General technical data


Permissible mounting position, mounting instructions

Page

Further specific technical data

3/115, 3/122

3TF2

3/119

Ratings of the auxiliary contacts

3/116

3TH2

3/122

Positively driven operation

3/116

3TH4

3/122, 3/125

Endurance of the auxiliary contacts

3/117

3TG10

3/127

Endurance of the main contacts

3/117

3TF40 to 3TF47

3/129

3TF50 to 3TF69

3/133

3TB48 to 3TB56

3/141

3TD contactor assemblies

3/144

3TE contactor assemblies

3/144

3TK50 to 3TK56

3/147

3TK1

3/150

3TC44 to 3TC56

3/152

3TC74 and 3TC78

3/154

Permissible mounting position, mounting instructions


Contactor type

Permissible mounting position

3TF2, 3TG10

Any

22,5 22,5

3TF40 to 3TF69

90

90

22,5 22,5 22,5 22,5

3TF50 to 3TF69 (AC operation)1)2)


3TF40 to 3TF43 (DC solenoid system)
3TF50 to 3TF69 (DC economy circuit)1)2)

3TF44 to 3TF47 (DC solenoid system) 1)

3TB48 to 3TB56

3TB48 to 3TB563)

3TK5

3TK5

3TK1

3TK14)

3TC4, 3TC5, 3TC7

3TC4, 3TC5, 3TC7

3TD

3TD50 to 3TD68 (AC operation)1)2)

operation)1)2)

3TE

NS2-5508a

22,5 22,5
NS2-5506c

360

NS2-5507a

The contactors are designed for operation on a vertical mounting surface.


For designs for upright mounting, see below.

3TE50 to 3TE68 (AC

Mounting instructions

Upright mounting

1) A minimum clearance of 30 mm is recommended between contactor types


3TF44 or larger as well as between 3TK4 and 3TK5 in order to simplify the
replacement of the laterally mounted auxiliary switches.

The following contactors can also be supplied for use in the upright position.
In this case the Order No. must be supplemented with "-Z" and the order
code "B01".

2) If the contactors are mounted at a 90 angle (conducting paths


horizontally one above the other), the following reductions apply:
Operating
3TF52 to 3TF69 80% of the standard value
frequency:
3TK52 and 3TK54 80% of the standard value

Type
3TC44
3TC48
3TC52
3TC56

Mechanical
endurance:

3TF50 to 3TF57 8 million operating cycles for


AC operation
3TK56 50% of the standard value

3) No deviations from the vertical axis are allowed for reversing operation
without a mechanical interlock.
4) 3TK1: upright mounting also permissible.

Siemens NS K 2000

3TF40 to
3TF46 to
3TF52 to
3TF56 to

Additional charge

3TF45
3TF51
3TF55
3TF69

3TK50
3TK52 and 3TK54
3TK56

3/115

3TF, 3TG, 3TK, 3TC, 3TB Contactors


Technical data
Contactor

Type

3TF2

3TG10

3TF40
to
3TF43

3TF44
to
3TF69

3TK1

3TC4
and
3TC7

3TC5

3TB48
and
3TB50

3TB52
to
3TB56

3TK48
to
3TK56

acc. to IEC 60 947-5-1/DIN VDE 0660 Part 200

Ratings of the auxiliary contacts

acc. to IEC 60 158-1

Rated insulation voltage Ui: 690 V (pollution degree 3)


Conventional thermal current Ith =
rated operational current Ie/AC-12

A 10

201)2)

10

10

10

10

10

Ie/AC-1
10

Ie/AC-1
10

Load ratings with AC


Rated operational current Ie/AC-15/AC-14
at rated operational voltage Ue
24 V
110 V
125 V
220 V
230 V
380 V

A
A
A
A
A
A

4
4
4
4
4
3

4
4
4
4
4
3

10
10
10
10
9.6
6

10
10
10
6
5.6
4

6
6
6
6
6
4

10
10
10
6
5.6
4

10
10
10
6
5.6
4

Ie/AC-11
10
10
10
6
5.6
4

Ie/AC-11
10
10
10
6
5.6
4

400 V
500 V
660 V
690 V

A
A
A
A

3
2
1
1

3
2
1
1

5.5
4
2
1.8

3.6
2.5
2.5
2.3

4
1
1
1

3.6
2.5
2.5

3.6
2.5
2.5

24 V
48 V
110 V
125 V

A
A
A
A

4
2.2
1.1
1.1

16
8
2
1.7

10
10
2.1

10
10
3.2
2.5

10
10
3.2
2.5

220 V
440 V
600 V

A 0.5
A
A

0.8
0.6
0.6

0.9
0.33
0.22

24 V
48 V
110 V
125 V

A
A
A
A

3
1.2
0.5
0.4

10
5
0.9

10
5
1.14
0.98

220 V
440 V
600 V

A 0.3
A
A

0.48
0.13
0.07

Load ratings with DC


Rated operational current Ie/DC-12
at rated operational voltage Ue

Rated operational current Ie/DC-13


at rated operational voltage Ue

Contactor

2.1
1.1
0.5
0.5

Type

0.27

3TF2 and
3TG10..-0...

0.45
0.25
0.2

10
10
8
6

0.9
0.33
0.22

2
0.6
0.4

6
6
1.8

10
5
1.14
0.98

10
5
2.4
2.1

0.6

0.48
0.13
0.07

1.1
0.32
0.21

3.6
2.5
2.5

3.6
2.5
2.5

Ie/DC-1
10
10
3.2
2.5

Ie/DC-1
10
10
8
6

0.9
0.33
0.22

2
0.6
0.4

Ie/DC-11
10
(10)3)
5
( 7)
1.14 ( 3.2)
0.98 ( 2.5)
0.48 ( 0.9)
0.13 ( 0.33)
0.075 ( 0.22)

3TF40 to
3TF69

3TK50 to
3TK56

3TC44
to 3TC56

3TB48
to 3TB56

600

600

600

A 600, P 600

A 600, P 600

A 600, P 600

3TF40 to 3TF43

3TF44 to 3TF694)

3TC44 to 3TC564)

Ie/DC-11
10
(10)3)
5
( 4)
2.4 ( 1.8)
2.1 ( 1.6)
1.1 ( 0.9)
0.32 ( 0.27)
0.21 ( 0.18)

3TK1

s, u and U ratings of the auxiliary contacts


Rated voltage

max. AC V 600
Auxiliary switch
blocks: 300

Making and breaking capacity

A 600, Q 300
Conventional
thermal current:
10 A at AC 240 V

Contactor

Type

3TF2

Positively driven operation between welded main


contacts and auxiliary NC contacts:

3TB48 to 3TB56

3TK50 to 3TK56

Positively driven contacts of 3TF, 3TK, 3TC, 3TB contactors


The contacts are positively driven if they are linked together mechanically in such a way that the NO and NC contacts cannot be
closed at the same time (positively driven operation between welded main contacts and auxiliary NC contacts).
Basic unit

Basic unit and mounted


auxiliary switches

Basic unit and laterally mounted


auxiliary switches

1) With tab connectors 16 A.


2) If the three main conducting paths are loaded
with 20 A and I > 10 A, the permissible ambient
temperature for the the auxiliary conducting.

3/116

path is 40 C.
3) The values in brackets apply to auxiliary
contacts with a late-opening NC contact.

4) In the case of the 3TF44/45, 3TF68 and 3TF69


as well as the 3TC44, one NC contact belonging
to each of the left and right auxiliary switch
blocks must be connected in series.

Siemens NS K 2000

3TF, 3TK5, 3TB Contactors


Technical data
3TF40 to 3TF69 and 3TK50 to 3TK56
contactors AC 230/220 V AC
4

A N S 2 -5 5 2 5 d

3
2
O p e r a tin g c y c le s

Endurance of the auxiliary contacts


The contact endurance for the
AC-12 and AC-15/AC-14
utilization categories is mainly
dependent on the breaking
current. It is assumed that the
operating mechanisms are
switched randomly, i.e. not
synchronized with the phase
angle of the supply system.

3 T F 4 0 to 3 T F 4 3
7

1 0
8
6

4
3

3 T F 4 4 to 3 T F 6 9
3 T K 4 8 to 3 T K 5 6
2
6

1 0
8
6
4
3
2

1 0

Legend:
PN = Ratings of
three-phase motors with
squirrel-cage rotor at 400 V
Ia = Breaking current
Ie = Rated operational current

4
3

-1

8 1 0
6

3
4

1 0

4
2
6 8 1 0
3
B r e a k in g c u r r e n t I a ( A )

C o n ta c to r T y p e
3 T B 5 0
3 T B 5 4
3 T B 5 2
3 T B 5 6
3 T B 4 8
7

O p e r a tin g c y c le s a t 4 0 0 V

1 0
8
6
4

A N S 2 -5 5 4 6 c

2
6

1 0
8
6
4
2
5

1 0
8
6
4
2
4

1 0
8
6
4
2
3

1 0

3 0

1 0

4 0

5 0 6 0

8 0 1 0 0
1 1 0
7 5
3 7

5 5

1 7 0

2 0 0

2 5 0

4 0 0
4 0 0

3 0 0

a (A ) 4 0 0 0

2 0 0 0

2 0 0

1 3 2

9 0

6 0 0 8 0 0 1 0 0 0

Ie (A )
N

(k W )

3TF2 contactors
C o n ta c to r ty p e

3 T F 2 8

2
5

1 0
8
6
4

1 0

1 0

2
5

2
4

1 0
8
6
4

2
2

1 0
8
6
4

1 0
8
6
4

1 0
8
6
4

3 T F 2 0
3 T K 2
A N S 2 -5 9 0 7 c

1 0
8
6
4

1 0
8
6
4
5

1 0
8
6
4

1 0
8
6
4

1 0
8
6
4

4
4

1 0
8
6
4

6
6

1 0
8
6
4

8
7

1 0
8
6

1 0
8
6
4

2
1 0

6
5

2 ,2

Siemens NS K 2000

8
6

3TB48 to 3TB56 contactors

O p e r a tin g c y c le s a t 4 0 0 V

Where:
X Contact endurance for mixed
operation in operating cycles
A Contact endurance for normal
operation (Ia = Ie) in operating
cycles
B Contact endurance for inching
(Ia = multiple of Ie) in operating
cycles
C Inching operations as a
percentage of total switching
operations

O p e r a tin g c y c le s a t 6 9 0 V

If a shorter endurance is
sufficient, the rated operational
current Ie/AC-4 can be
increased.

A
X = ---------------------------------------------------------C A
1 + --------- ---- 1
100 B

-2

O p e r a tin g c y c le s a t 5 0 0 V

The rated operational current Ie


for the AC-4 utilization category
(breaking six times the rated
operational current) is designed
for a contact endurance of
approximately 200 000
operating cycles.

For mixed operation, i.e. normal


switching (breaking the rated
operational current according to
the AC-3 utilization category) in
combination with intermittent
inching (breaking several times
the rated operational current
according to the AC-4 utilization
category), the contact endurance
can be calculated approximately
from the following equation:

O p e r a tin g c y c le s a t 2 3 0 V

Endurance of the main contacts


The characteristic curves show
the contact endurance of the
contactors when used to switch
resistive and inductive threephase loads (AC-1/AC-3),
depending on the breaking
current and the rated operational
voltage. It is assumed that the
operating mechanisms are
switched randomly, i.e. not
synchronized with the phase
angle of the supply system.

1 0

1 0
9
4

2 0

3 0

4 0 5 0 6 0
Ia (A )
Ie (A )
P
N

8 0

(k W )

3/117

3TF and 3TC Contactors


Technical data
Contact erosion indication for 3TF68 and 3TF69 vacuum contactors
order to ensure maximum
replaced if the distance
The contact erosion of the
reliability.
indicated by one of the double
vacuum interrupters can be
Important information about
slides is less than 0.5 mm while
monitored in the closed position
how to assess contact erosion
the contactor is in the closed
by means of three white double
can be found in the brochure
position. It is advisable to
slides on the contactor base.
entitled "Contacts of the 3TF
replace all three interrupters in
The vacuum interrupter must be

Contactors: Robust and


Durable".
Order No.:
E20001-P285-A495-X-7600

3TF50 to 3TF69 contactors


Contactor Type

10 6
8
6
4
2
10
8
6

10
8
6

4
2
10
8
6

3TF54

3TF55
3TF56/57

3TF69

3TF68

ANS2-3145f

10
8
6

4
2
10
8
6

2
10
8
6

3TF56
3TF57

4
2
10
8
6

2
4

10
8
6

10
8
6

2
2

3TF50

10 4
8
6

10
8
6

3TF53
3TF52

Operating cycles at 400 V

Operating cycles at 690 V

8
6

Operating cycles at 500 V

Operating cycles at 230 V

10 7
8
6

10
8
6

3TF51

10 3

10

2
10

20

30

40

50 60

80 100
110

200
140

55

170

205

90
75

600

400
250

300

132
110

400

475

200
160

1000

630

2000

I e (A)
PN (kW)

820

335
450

250

I a (A) 4000I

Endurance of the main contacts


3TC74 and 3TC78 contactors

1 0
8
6
4

7
A N S K -7 1 3 1 a

3 T C 4 4
2

3 T C 4 8

3 T C 5 2

3 T C 5 6

1 0
8
6
4
2
5

1 0
8
6
4

2 0
M ill.
1 8

O p e r a tin g c y c le s a t 5 0 0 V

O p e r a tin g c y c le s a t 5 0 0 V

3TC44 to 3TC56 contactors

1 6
1 4
1 2
1 0
8

6
4

1 0
8
4

A N S K -7 1 3 2 b

4
6

2
2

1 0

0 ,5
3

1 0

3/118

2 0

4 0

1 0 0

2 0 0

4 0 0

6 0 0

1 0 0 0

2 0 0 0

Ia (A ) 4 0 0 0

5 0

1 0 0

1 5 0

2 0 0

2 5 0

3 0 0

Ia (A ) 4 0 0

Siemens NS K 2000

3TF2 Contactors
SIMICONT
Technical data
Type

3TF20
DC operation:

mill.

30

690

Rated impulse withstand voltage Uimp

screw connection

kV

Permissible ambient temperature

in operation
when stored

C
C

25 to +55
55 to +80

Mechanical endurance
Rated insulation voltage Ui (pollution degree 3)

Degree of protection acc. to IEC 60 947-1 and IEC 60 529 (VDE 0470 Part 1)
Power consumption of the coils
at Us
(with coil in cold state 1 x Us
closing = closed)

24 V
110 V

Permissible residual current of the electronics3)


(with 0 signal)

DC operation max.

IP 00/open type or IP 20 with screw connection,


coil system IP 40

W
W

24 V

6 mA x ---------
U
s
0.7 to 1.25 Us

Coil voltage tolerance


Operating times
of the 3TF2 contactors
Break-time =
opening time + arcing time
with coil in cold state or at
operating temperature

0.7 x Us

NO
NC

ms
ms

40 to 48
8 to 14

1.0 x Us

NO
NC

ms
ms

24 to 29
6 to 12

1.25 x Us

NO
NC

ms
ms

17 to 19
6 to 12

0.7 to 1.25 x Us

NO
NC

ms
ms

4 to 10
16 to 44

arcing time

ms

10 to 15

without aux. sw. block


rectangular pulse
sine pulse

g/ms
g/ms

11.3/5 and 9.2/10


17.4/5 and 12.9/10

closing time at

opening time at

Shock resistance
for DC operation

2
3

Short-circuit protection of contactors without overload relays

For short-circuit protection of contactors with overload relays, see


Part 4, for fuseless motor feeders, see Part 5.

Main circuit
Fuse links, utilization category gL/gG

NH
DIAZED
NEOZED

Type 3NA
Type 5SB
Type 5SE

acc. to IEC 60 947-4-1/


IEC 60 947-4-1
(DIN VDE 0660 Part 102)

Type of coord. "1" 1)


Type of coord. "21)2)
Weld-free

Miniature circuit-breaker with C-characteristic

A
A

25
10

10

10

A
A

6
6

Auxiliary circuit (short-circuit current Ik 1 kA)


Fuse links, utilization category gL/gG

DIAZED
NEOZED

Type 5SB
Type 5SE

1) According to excerpt from IEC 60 947-4, DIN VDE 0660 Part 102:
Type of coordination "1":
Destruction of the contactor and the overload relay is permissible.
The contactor and/or overload relay must be replaced if necessary.
Type of coordination "2":
No damage can be tolerated to the overload relay,.but contact welding on
the contactor is permitted if the contacts can be easily separated.

Siemens NS K 2000

2) For type of coordination "2", the following short-circuit current applies:


Iq 6 kA.
3) The 3TX4 490-1J additional load module is recommended for higher residual
currents (see NS E Catalog).

3/119

3TF2 Contactors
SIMICONT
Technical data
Contactor

Type

3TF20

Conductor cross-sections
Main conductor and auxiliary conductor for designs with screw connections
screw connection

M3

finely stranded with end sleeve

mm2
mm2

2 x (0.5 to 1.5)
1 x 2.5

pin-end connector (DIN 46 231)

mm2

1 x 1 to 2.5

solid

mm2
mm2
AWG

2 x (0.5 to 2.5)
1x4
2 x (20-14), 1 x 12

Nm
lb.in

0.8 to 1.3
7 to 11

1/h

10000

1/h
1/h
1/h
1/h

1000
500
1000
250

Specified tightening torque of terminal screws


Operating frequency z in operating cycles per hour
Contactors without overload relays

No-load operating
frequency

Rated operation

for AC-1
for AC-2
for AC-3
for AC-4
Dependence of the operating frequency z on the rated operational current
and the rated operational voltage:
Ie 400 V
z = z ---- ---------- 1.5 1/h
I U
Contactors with overload relays (mean value)

1/h

15

70

0.3

up to 400 V
690 V

A
A

18
18

up to 400 V
690 V

A
A

16
16

kW
kW
kW
kW

6.0
10
13
17

10 s current

Thermal load
Power loss per conducting path at Ie/AC-3

Load ratings with AC


AC-1 utilization category, switching resistive load
Rated operational currents Ie
at 40 C
at 55 C
Ratings of three-phase loads
p.f. = 1

at 230 V
400 V
500 V
690 V

Minimum conductor cross-section with Ie load


AC-2 and AC-3 utilization categories
Rated operational currents Ie

Ratings of motors with slipring or squirrel-cage


rotor at 50 Hz and 60 Hz

up to 380 V
400 V
500 V
690 V
230 V
400 V
500 V
690 V

AC-4 utilization category


(contact endurance approx. 200 000 operating cycles at Ia = 6 x Ie)
Rated operational currents Ie
up to 400 V
690 V
Ratings of motors with squirrel-cage rotor
at 50 Hz and 60 Hz

230 V
400 V
500 V
690 V

mm2

2.5

A
A
A
A

9.0
8.4
6.5
5.2

kW
kW
kW
kW

2.5
4.0
4.0
4.0

A
A

2.6
1.8

kW
kW
kW
kW

0.67
1.15
1.45
1.15

Max. permissible rated operational current


Ie/AC-4 q Ie/AC-3 up to 500 V
with reduced contact endurance
and reduced operating frequency

3/120

Siemens NS K 2000

3TF2 Contactors
SIMICONT
Technical data
Contactor

Type

3TF20

Load ratings with DC

L
DC-1 utilization category, switching resistive load (contact endurance 0.1 106 operating cycles) ( ---- 1 ms)
R
up to 24 V
A
16
Rated operational currents Ie (at 55 C)
with 1 conducting path
60 V
A
6
110 V
A
2
220/240 V
A
0.8
with 2 conducting paths connected in series

up to 24 V
60 V
110 V
220/240 V

A
A
A
A

16
16
6
1.6

with 3 conducting paths connected in series

up to 24 V
60 V
110 V
220/240 V

A
A
A
A

16
16
16
6

A
A
A

10
0.5
0.15

L
DC-3 and DC-5 utilization categories, shunt and series motors ( ---- 15 ms)
R
up to 24 V
Rated operational currents Ie (at 55 C)
with 1 conducting path
60 V
110 V
220/240 V
with 2 conducting paths connected in series

up to 24 V
60 V
110 V
220/240 V

A
A
A

16
5
0.35

with 3 conducting paths connected in series

up to 24 V
60 V
110 V
220/240 V

A
A
A
A

16
16
16
1.75

AC

600

Free air and enclosed

16

hp
hp
hp
hp

Single-phase
1/
2
1
11/2

3UA7
6.3 to 10

s and u ratings
Rated insulation voltage
Conventional thermal current

Maximum horsepower ratings (s and u-approved values)


Ratings of three-phase motors
at 60 Hz

Overload relay

Siemens NS K 2000

at 115 V
200 V
230 V
460/575 V
Type
Setting range

3-phase

3
3
5

3/121

3TH2, 3TH4 Contactor Relays


Technical data
Type

3TH2

3TH4

Any

The contactors are designed for operation


on a vertical mounting surface.

Permissible mounting position

22, 5 22, 5
90

90

NS K-66 03

Upright mounting position

Possible with standard design

NS K-66 02

Special design
The Order No.must be supplemented with "-Z" and
the order code "B01".
Additional charge:

Positively driven operation of the contacts


The contactor relays fulfil the conditions for positively driven operation as required by the safety rules for
control units on power-operated presses in the metal-working industry (ZH1/457) and also correspond to the
accident prevention regulations of the Schweizer Unfallversicherungsanstalt (Swiss institute for accident
insurance). There is positively driven operation if it is ensured that the NC and NO contacts cannot be closed
at the same time.
Basic unit or cabinet unit

ZH1/457, SUVA

ZH1/457, SUVA

Contact endurance for AC-15/AC-14


and DC-13 utilization categories
The contact endurance is mainly dependent on the breaking current. It is assumed that the operating
mechanisms are switched randomly, i.e. not synchronized with the phase angle of the supply system.
If magnetic circuits other than the contactor coil systems or solenoid valves are present, e.g. magnetic
brakes, protective measures for the load circuits are necessary.
RC elements and freewheeling diodes would be suitable as protective features.
3TH2

3TH4
In te rfa c e s

1 0

C o n ta c to r r e la y s + In te r fa c e s
5

D C -1 3
2 2 0 V

2
1

D C -1 3
1 1 0 V
D C -1 3
2 4 V

0 ,5

A C -1 5 /A C -1 4

0 ,1

A N S K -6 5 9 1 b

1 0
A C -1 5 /A C -1 4
5
4
3

D C -1 3
1 1 0 V
2

D C -1 3
2 4 V
D C -1 3
2 2 0 V

1
0 ,5

0 ,0 5

0 ,0 1

3 0

A N S K -6 5 9 0 a

M illio n o p e r a tin g c y c le s ( 1 0 6 )

M illio n o p e r a tin g c y c le s ( 1 0 6 )

3 0

0 ,0 1

0 ,0 3

0 ,0 5

0 ,1

0 ,3

0 ,5

I e -D C -1 3
1 1 0 V

1
2

I e -D C -1 3
2 4 V

4 5

7 1 0

I
a

(A )

A C -1 5 /A C -1 4
2 3 0 V

e -

I e -D C -1 3
2 2 0 V

0 ,1
0 ,0 1

0 ,0 3

0 ,0 5

0 ,1

0 ,3

I e -D C -1 3
2 2 0 V

0 ,5

I e -D C -1 3
1 1 0 V

1 0

I a (A )

I e -D C -1 3
2 4 V
I
e

-A C -1 5 /A C -1 4
2 3 0 V

Legend:
Ie = Rated operational current
Ia = Breaking current

3/122

Siemens NS K 2000

3TH2 Contactor Relays


SIMICONT
Technical data
Type

3TH2

General data
Mechanical endurance

Operating cycles (DC operation)

Rated insulation voltage Ui (pollution degree 3)


Rated impulse withstand voltage Uimp (pollution degree 3)
in operation
when stored

Permissible ambient temperature

30 million
V

690

kV

C
C

25 to +55
55 to +80

Degree of protection acc. to IEC 60 947-1 and IEC 60 529 (VDE 0470 Part 1)
Power consumption of the coils (with coil in cold state and 1.0 x Us)
at Us
(with coil in cold state;
closing = closed)
Permissible residual current of the electronics1)
(with 0 signal)

24 V
110 V

IP 00/open type or IP 20 with screw connection,


coil system IP 40

W
W

2
3

V
6 mA x 24
---------
U

DC operation

Coil voltage tolerance

0.7 Us to 1.25 Us

Surge suppression in the coil

Varistor integrated in the coupling relay


U

Operating times
(break-time = opening time
+ arcing time)
The values apply with the
coil in the cold state and at
operating temperature for
the voltage tolerance

closing time at 0.7 x Us

NO
NC

ms
ms

39 to 53
7 to 13

1.0 x Us

NO
NC

ms
ms

24 to 30
7 to 14

1.25 x Us

NO
NC

ms
ms

18 to 22
7 to 12

NO
NC

ms
ms

5 to 11
16 to 48

opening time at 0.7 to 1.25 x Us


arcing time
Shock resistance

ms

10

rectangular
pulse

DC operation

g/ms

10/5 and 6/10

sine pulse

DC operation

g/ms

13/5 and 8/10

mm2
mm2

M3
2 x (0.5 to 1.5)
2 x (0.5 to 2.5)

Short-circuit protection
(weld-free protection at Ik 1 kA)
Fuse links,
utilization category gL/gG

NH
DIAZED
NEOZED

Type 3NA
Type 5SB
Type 5SE

Conductor cross-sections
for designs with screw connections
Screw connection
Finely stranded with end sleeve
Solid

1) The 3TX4 490-1J additional load module is


recommended for higher residual currents (see
NS E Catalog).

Siemens NS K 2000

3/123

3TH2 Contactor Relays


SIMICONT
Technical data
Type

3TH2

Rated operational currents


Ie/AC -12
Ie/AC -15/AC -14 at Ue

up to 230 V/220 V
at 400 V/380 V
500 V
690 V/660 V

10

A
A
A
A

4
3
2
1

Conducting paths
connected in series

Ie/DC-12 at U e

24 V
60 V
110 V
240 V220 V

A
A
A
A

41)
21)
1.1 1)
0.5 1)

10
10
4
2

10
10
6
2.5

Ie/DC-13 at U e

24 V
60 V
110 V
240 V/220 V

A
A
A
A

2.1
0.9
0.52
0.27

10
3.5
1.3
0.9

10
4.7
3
1.2

110 V
230 V/220 V
400 V/380 V
500 V
690 V/660 V

kW
kW
kW
kW
kW

0.2
0.55
1.1
1.5
1.5

AC-12/DC-12
AC-2
AC-3
AC-15/AC-14
or DC-13

1/h
1/h
1/h

1000
500
1000

1/h

1200

1/h

10 000

Ratings of three-phase motors


AC-2 and AC-3 utilization categories

Operating frequency z
in operating cycles per hour for
rated operation with utilization category

Dependence of the operating frequency z


on the rated operational current
and the rated operational voltage:
I
U
z = z ---e- ----e- 1.5 1/h
I U
No-load operating
frequency

s and u ratings
Rated control supply voltage

AC
DC

V
V

max. 500
max. 250

Conventional thermal current

at AC 240 V

10

Making and breaking capacity

A 600/Q 300

1) Contact endurance 0.1 x 106 operating cycles.

3/124

Siemens NS K 2000

3TH4 Contactor Relays


Technical data
Type

3TH40,
3TH42 62
3TH42 53

3TH42 44

General data
30 million

30 million

Rated insulation voltage Ui (pollution degree 3)

690

690

Rated impulse withstand voltage Uimp

kV

Safe isolation acc. to DIN VDE 0106 Part 101 and A1 (draft 2/89)
between coil and contacts

up to 500

up to 500

C
C

50 to +701)
55 to +80

50 to +701)
55 to +80

IP 20

IP 20

2.3
4.6
7.2

2.6
5.2
8.2

Mechanical endurance

Operating cycles

in operation
when stored

Permissible ambient temperature

Degree of protection acc. to IEC 60 947-1 and IEC 60 529 (VDE 0470 Part 1)
Power consumption of the coils (with coil in cold state and 1.0 x Us)
at Us
0.7 x Us
(with coil in cold state;
1.0 x Us
closing = closed)
1.25 x Us

W
W
W

Permissible residual current of the electronics


(with 0 signal)

DC operation

10 mA x 24
---------V
Us

10 mA x 24
---------V
Us

Coil voltage tolerance

DC operation

0.7 x Us to 1.25 x Us

0.7 x Us to 1.25 x Us

Operating times (break-time = opening time + arcing time)


Closing

Opening

0.7 x Us

ON-delay
OFF-delay

NO
NC

ms
ms

70 to 200
28 to 33

70 to 200
28 to 33

1 x Us

ON-delay
OFF-delay

NO
NC

ms
ms

45 to 80
30 to 34

45 to 80
30 to 34

1.25 x Us

ON-delay
OFF-delay

NO
NC

ms
ms

40 to 60
31 to 35

40 to 60
31 to 35

0.7 to 1.25 x Us

ON-delay
OFF-delay

NO
NC

ms
ms

20 to 30
22 to 32

20 to 30
22 to 32

ms

10

10

Arcing time
Shock resistance

rectangular
pulse

DC operation

g/ms

9.3/5 and 5.4/10

9.3/5 and 5.4/10

sine pulse

DC operation

g/ms

14.7/5 and 8.5/10

14.7/5 and 8.5/10

16

16

quick A

20

20

A
A

16
16

16
16

mm2
mm2
mm2
mm2

M3.5
2 x (0.5 to 1)
2 x (1 to 2.5)
1x4
2 x (0.75 to 2.5)

M3.5
2 x (0.5 to 1)
2 x (1 to 2.5)
1x4
2 x (0.75 to 2.5)

Short-circuit protection
(weld-free protection at Ik 1 kA)

Fuse links, utilization category gL/gG


NH
3NA
DIAZED
5SB
NEOZED
5SE
Miniature circuit-breaker

Type
Type
Type
C-characteristic
B-characteristic

Conductor cross-sections
screw connection
solid
finely stranded with end sleeves

1) For ambient temperatures >+55 C or


< 25 C, see description on page 3/159.
Siemens NS K 2000

3/125

3TH4 Contactor Relays


Technical data
Contactor type

3TH4

Rated operational currents


Ie/AC-12
Ie/AC-15/AC-14 at Ue

up to 230 V/220 V
at 400 V/380 V
500 V
690 V/660 V

16

A
A
A
A

10
6
4
2

Conducting paths
connected in series

Ie/DC-12 at Ue

24 V/48 V
110 V
220 V
440 V
600 V

A
A
A
A
A

10
2.1
0.8
0.6
0.6

10
10
1.6
0.8
0.7

10
10
10
1.3
1

Ie/DC-13 at Ue

24 V
48 V
110 V
220 V
440 V
600 V

A
A
A
A
A
A

10
5
0.9
0.45
0.25
0.2

10
10
2.5
0.75
0.5
0.4

10
10
10
2
0.9
0.8

230 V/220 V
400 V/380 V
500 V
690 V/660 V

kW
kW
kW
kW

2.4
4
4
4

AC-12/DC-12
AC-2
AC-3
AC-15/AC-14
or DC-13

1/h
1/h
1/h

1000
500
1000

1/h

3600

1/h

10 000

AC
DC
acc. to u DC

V
V
V

max. 600
230
240

AC
DC

V
V

600
600

Ratings of three-phase motors


AC-2 and AC-3 utilization categories

Operating frequency z in operating cycles per hour


for rated operation with utilization category

Dependence of the operating frequency z


on the rated operational current and the
rated operational voltage:
Ie U e
z = z ---- ----- 1.5 1/h
I U
No-load operating
frequency

s and u ratings
Rated control supply voltage

Rated voltage
Making and breaking capacity

3/126

A 600, P 600

Siemens NS K 2000