Professional Documents
Culture Documents
$167.25
Circuit
Molded Case Circuit Breakers
P
begin on
page 28-4 (MCCB) UL 489
Provide branch and feeder circuit protection in
industrial control panels
• UL 489
• Up to 600 amps
• 65kA @ 240 VAC interrupting rating
• G-frame size 15 to 100 amps
• F-frame size 100 to 225 amps
• K-frame size 250 to 400 amps
• L-frame size 400 to 600 amps
Supply
MAIN CIRCUIT
Motor feeder short
circuit and ground
fault protection
Which type of Circuit Protection are you looking for?
Motor
UL 98
Circuit Protection Selection disconnecting
means
(NEC 430.101-
Current Rotary Manual Motor 430.113)
Molded Case Load Supplementary General
Limiting Disconnect Starters
Circuit Breakers Switches Protectors Fuses
Fuses Switches (MMS) Motor branch-
(MCCB) UL 489 UL 508 UL 1077 UL 248 circuit short
UL 248 UL 98 UL 508
circuit protection
page 28-4 page 28-73 page 28-30 page 16-26 page 28-53 (NEC 430.51-
430.58)
Short circuit and
ground fault protection
for feeder and branch YES YES YES NO NO NO NO
circuits
MOTOR CIRCUIT
Motor disconnecting Motor controller
means YES YES YES NO NO (NEC 430.81-
(NEC 430.101-430.113) 430.91)
UL 508
Motor branch-circuit
short circuit protection YES YES YES NO NO NO NO Motor overload
(NEC 430.51-430.58)
protection (NEC
430.21-430.44)
Motor controller
(NEC 430.81-430.91) YES YES YES NO NO NO NO
OSHA
Motor overload Lockout/tagout
protection YES YES YES YES NO NO NO disconnect
(NEC 430.21-430.44) (NEC 430.81-
430.91)
OSHA Lockout/tagout
disconnect YES YES YES YES YES NO NO
(NEC 430.81-430.91) Motor
DL05/06
PLC
DL105
Supplementary PLC
Other HMI
AC Drives
starting at
Pushbuttons/
Lights
Process
Relays/
Timers
Comm.
UL 508 Rated Load Switches
The SD series of load switches are used TB’s &
for making and breaking equipment Wiring
loads. These switches can be used as a
Power
motor controller meeting NEC® 430,
Part VII. Typical applications include local
motor isolation. Circuit
Protection
SD Series
Enclosures
• 35mm DIN rail mountable or
starting at
direct mountable
$20.00 • Loads from 16 to 125 amps Appendix
begin on
page 28-53 • IP20 degree of protection
Part Index
Ic kA @ 480/277V AC 22 18 20
List Price $
$
167 616 $
459
G3P-100 FAL34100 S1N100TL
225A Breaker
Panel Area (mm2) 15,808 23,142 17,850
Note: These parts available for sale to North American locations only. Ic kA @ 480/277V AC 35 25 25
List Price $
$
384 1,733 $
1,131
F3P-225 KAL36225 S3N225TW
All prices are U.S. published prices. AutomationDirect prices are from October 2007 Price List. Square D prices
are from http://www.squared.com 7/20/07. ABB prices are from http://www.abb-control.com 7/20/07.
*Note: N.I.T.U denotes non-interchangeable trip unit. I.T.U denotes interchangeable trip unit.
**Note: Two poles of 3-pole circuit breaker
Amp Rating
3 Pole