You are on page 1of 3

starting at

$167.25
Circuit
Molded Case Circuit Breakers
P
begin on
page 28-4 (MCCB) UL 489
Provide branch and feeder circuit protection in
industrial control panels
• UL 489
• Up to 600 amps
• 65kA @ 240 VAC interrupting rating
• G-frame size 15 to 100 amps
• F-frame size 100 to 225 amps
• K-frame size 250 to 400 amps
• L-frame size 400 to 600 amps
Supply

MAIN CIRCUIT
Motor feeder short
circuit and ground
fault protection
Which type of Circuit Protection are you looking for?
Motor

UL 98
Circuit Protection Selection disconnecting
means
(NEC 430.101-
Current Rotary Manual Motor 430.113)
Molded Case Load Supplementary General
Limiting Disconnect Starters
Circuit Breakers Switches Protectors Fuses
Fuses Switches (MMS) Motor branch-
(MCCB) UL 489 UL 508 UL 1077 UL 248 circuit short
UL 248 UL 98 UL 508
circuit protection
page 28-4 page 28-73 page 28-30 page 16-26 page 28-53 (NEC 430.51-
430.58)
Short circuit and
ground fault protection
for feeder and branch YES YES YES NO NO NO NO
circuits

MOTOR CIRCUIT
Motor disconnecting Motor controller
means YES YES YES NO NO (NEC 430.81-
(NEC 430.101-430.113) 430.91)

UL 508
Motor branch-circuit
short circuit protection YES YES YES NO NO NO NO Motor overload
(NEC 430.51-430.58)
protection (NEC
430.21-430.44)
Motor controller
(NEC 430.81-430.91) YES YES YES NO NO NO NO
OSHA
Motor overload Lockout/tagout
protection YES YES YES YES NO NO NO disconnect
(NEC 430.21-430.44) (NEC 430.81-
430.91)
OSHA Lockout/tagout
disconnect YES YES YES YES YES NO NO
(NEC 430.81-430.91) Motor

UL 98 Rated Disconnect Switches


Heavy-duty fusible and non-fusible disconnects meeting all the
requirements of the UL 98 standard. Can be used as a motor
disconnecting means to meet NEC® 430.109 and meets NEC®
430.111 as a motor controller.
SIRCO series FUSERBLOC series
• Non-fusible rotary disconnect • Fusible rotary disconnect switches
switches • Makes/breaks loads up to 200 amps
• Makes/breaks loads up to • Front operated
800 amps • Uses Class CC and Class J fuses
• Front operated • Line side shrouding comes starting at
• Visible blade contacts
• Line-side shrouding comes
standard with switch
• Touch-safe fuse covers standard
$57.00
begin on
page 28-30
standard with switch with switch

28–2 Circuit Protection 1 - 80 0 - 633 - 0405


Protection PLC
Overview

DL05/06
PLC

DL105
Supplementary PLC

Protectors UL1077 DL205


PLC
Supplementary protectors are UL 1077
recognized and are used in applications DL305
where branch circuit protection is not PLC
required or is already provided DL405
WMS Series PLC
• DIN rail mountable
starting at Field I/O
• Full line of auxiliary switches, alarm switches and
padlock lockout accessories $8.50
begin on
• B trip curve 6 to 60 amps page 28-21 Software
• C trip curve 0.5 to 60 amps
C-more
• D trip curve 0.5 to 40 amps HMIs

Other HMI

AC Drives
starting at

$1.25 for 5-pack Motors


begin on
Supplementary page 28-59
CONTROL CIRCUIT

Protection Selection Steppers/


Servos
Supplementary General
Fuses
Protectors Fuses The Edison Fuse products are industry-standard fuses that Motor
Controls
UL 1077 UL 248-14 are designed using the highest quality materials and manu-
Control
Transformer
facturing methods. All Edison fuses can be directly cross Proximity
Sensors
page 28-21 page 28-76
referenced and used as replacements for other name-brand
fuses such as Littelfuse, Ferraz, Siemens, and many more. Photo
Anywhere Sensors
branch
circuit, Limit
YES YES overcurrent Switches
protection is
Encoders
already provided
PLC Contactor Relays or not needed
I/O Coils
Current
Sensors

Pushbuttons/
Lights

Process

Relays/
Timers

Comm.
UL 508 Rated Load Switches
The SD series of load switches are used TB’s &
for making and breaking equipment Wiring
loads. These switches can be used as a
Power
motor controller meeting NEC® 430,
Part VII. Typical applications include local
motor isolation. Circuit
Protection
SD Series
Enclosures
• 35mm DIN rail mountable or
starting at
direct mountable
$20.00 • Loads from 16 to 125 amps Appendix
begin on
page 28-53 • IP20 degree of protection
Part Index

w w w. a u to m at i o n d i re c t . c o m / c i rc u i t _ p rote c t i o n Circuit Protection 28–3


Molded Case Circuit Breakers
Overview Features
Designed to provide branch and feeder • UL489 listed performance for branch
circuit protection in industrial control circuit overcurrent protection and
panels, this line of Molded Case Circuit disconnecting means
Breakers supplies protection against • Patented contact conductor designs
overload in conductors and short circuit featuring high-speed “blow-open”
in connected equipment such as motors. action, providing superior performance
They are UL listed for installation in UL when high level fault currents produce
508 control panels. Their small size, in extra-ordinary electromechanical forces
relation to standard circuit breakers or • Advanced arc extinguishing technology
other comparable devices, saves panel • Toggle handle provides three positions
space. Four frame sizes and all standard (on/off/tripped) along with visual
accessories are available. indicators
• Manufactured in ISO 9000 certified
facilities
Listings • HACR (heating, air conditioning and Made by Eaton Electric Inc.,
• UL 489 MCCB, File: E7819 refrigeration) rated Manufacturer of Cutler-Hammer Products
• Field-installed accessories: • G-Frame and F-Frame breakers are
UL file E64983 CHECK OUT OUR PRICES
suitable for reverse feed
AutomationDirect Square D ABB
• CSA 22.2 No.5, File: 43556 • K-Frame and L-Frame breakers include Circuit Breakers Price/Part Number Price/Part Number Price/Part Number

• IEC 157-1 3-pole adjustable magnetic trip. 100A Breaker


• NEMA Standards Pub. No. AB1-1993 Panel Area (mm2) 9,424 17,328 9,360

Ic kA @ 480/277V AC 22 18 20
List Price $
$
167 616 $
459
G3P-100 FAL34100 S1N100TL

225A Breaker
Panel Area (mm2) 15,808 23,142 17,850
Note: These parts available for sale to North American locations only. Ic kA @ 480/277V AC 35 25 25
List Price $
$
384 1,733 $
1,131
F3P-225 KAL36225 S3N225TW

All prices are U.S. published prices. AutomationDirect prices are from October 2007 Price List. Square D prices
are from http://www.squared.com 7/20/07. ABB prices are from http://www.abb-control.com 7/20/07.

Molded Case Circuit Breakers Technical Specifications


UL 489 Interrupting Ratings
Ampere Volts Type Federal
Circuit Breaker No. (rms Symmetrical Amperes) (kA)
Rating at of Specification Volts AC (50/60 Hz) Volts DC
Type Poles
40°C AC DC Trip* W-C-375b
240 480 600 250**
G-Frame 15 -100 3 480 250 N.I.T.U 13b 65 22 – 10
F-Frame 60 - 225 3 480 250 N.I.T.U 22a 65 35 18 10
K-Frame 250 - 400 3 600 250 I.T.U 23a 65 35 25 10
L-Frame 400 - 600 3 600 250 I.T.U 23a 65 35 25 22

*Note: N.I.T.U denotes non-interchangeable trip unit. I.T.U denotes interchangeable trip unit.
**Note: Two poles of 3-pole circuit breaker

Molded Case Circuit Breakers Part Numbering System


G 3P - 020 - AUX
Accessory Description Code
AUX: auxiliary contact UVAC: undervoltage release
STAC: shunt trip AC UVDC: undervoltage release
STDC: shunt trip DC

Amp Rating

3 Pole

Molded Case Circuit Breaker Series (by frame size)


G: 15 to 100 Amp F: 60 to 225 Amp
K: 250 to 400 Amp L: 400 to 600 Amp

28–4 Circuit Protection 1 - 80 0 - 633 - 0405