Professional Documents
Culture Documents
AC Current Source
ElmIac
DIgSILENT GmbH
Heinrich-Hertz-Str. 9
72810 - Gomaringen
Germany
T: +49 7072 9168 0
F: +49 7072 9168 88
http://www.digsilent.de
info@digsilent.de
Version: 15.2
Edition: 1
Copyright 2014, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT GmbH.
No part of this document may be reproduced, copied, or transmitted in any form, by any means
electronic or mechanical, without the prior written permission of DIgSILENT GmbH.
AC Current Source (ElmIac)
Contents
Contents
1 General Description
1.1 Model Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3
3 Short-Circuit Analysis
5 Frequency Sweep
6 Dynamic Simulation
A Parameter Definitions
10
B Signal Definitions
10
List of Figures
11
List of Tables
12
General Description
The AC Current Source model represents a constant current injection in the system. It should be
connected to 3 phase AC terminals, as it does not support 2 phase and single phase systems.
ElmIac could be used for balanced and unbalanced calculations and could be useful for:
Wind turbine modelling
HVDC system modelling
Photovoltaic modelling
b) Negative Sequence Network
Injection of harmonic currents in the system
General circuit analysis
In the Basic Data page of the AC Current Source the main parameter to be entered is the Rated
Current Ir.
1.1
Model Diagrams
I1
U1
Isetp
G1
B1
I2
U2
(
(Isetp Cos + U1 G1 ) + j(Isetp Sin + U1 B1 ) if pf Capacitive
b) Negative Sequence Network
I1 =
(Isetp Cos + U1 G1 ) j(Isetp Sin + U1 B1 ) if pf Inductive
(1)
I0
U0
Isetp
G0
B0
G2
B2
Short-Circuit Analysis
I0
I1
U0
U1
G0
Isetp
G1
B0
B1
c) a)
Zero
Sequence Network
Positive Sequence Network
I2
U2
G2
B2
I0
U0
I0 = U0 G0 + jU0 B0
G0
(2)
B0
I2 = U2 G2 + jU2 B2
(3)
Equations 1 to 3 are used for unbalanced load flow calculations. The balanced option only
c)1.Zero Sequence Network
considers equation
Short-Circuit Analysis
For VDE/IEC and ANSI Short-Circuit calculation there is no defined short-circuit contribution for
AC Current Sources.
In the Complete Short-Circuit calculation data of the internal conductance and susceptance for
positive, negative and zero sequence are needed. The ElmIac behaves as a constant current source for symmetrical faults. For unsymmetrical faults, it behaves as a constant current
source in the positive sequence network and as a constant admittance in the negative and zero
sequence networks.
Frequency Sweep
The AC current source can be used to define harmonic current injections into the network.
Figure 4.1 shows how to define the harmonic currents injection. To define the harmonics it
is possible to select a spectrum which contains the harmonic currents, for more information
regarding how to define a spectrum refer to Users Manual Definition of Harmonic Injections.
The harmonic current can be referred to either the fundamental or rated current.
Frequency Sweep
In the frequency sweep calculation the internal current of the current source is set to 0 A and 0
deg (open-circuit). The parameter Spectral Density of the Current Magnitude/Angle (didf, ddf
in p.u./Hz, deg/Hz) and the corresponding frequency dependent characteristic allows for the
definition of an internal current according to equations (4) and (5).
AC Current Source (ElmIac)
Frequency Sweep
ii (h ) = didf ichar (h )
(4)
Ii (h ) = ddf I,char (h ) Ii
(5)
Ii = Ii Iref
(6)
where
and didf and ddf are constant input parameters used to scale the frequency characteristics
ichar and I,char in (4). The characteristics can be either polynomial (using the PowerFactory
ChaPol object) or a vectorial characteristic (using the ChaVec object) with a frequency scale
(using the TriFreq object). The angle Ii accounts for the angle deviation between the current
and the system reference voltage angle.
A common application is the analysis of the transfer function of a part of the system or the
propagation of a current impulse in frequency domain. To do this the amplitude and phase of
the spectrum current can be defined and using the frequency sweep function, the voltage at the
remote end can be calculated.
isetp
G1
B1
Dynamic Simulation
i2
u2
Dynamic Simulation
isetp
G2
B2
For the RMS/EMT simulation we can independently control the phases A, B and C. Please note
that this is not the case of the LDF calculations. For RMS and EMT simulations there is the
option for balanced and unbalanced models as shown in Figure 6.1.
b) Negative Sequence Network
i1
isetp
G1
B1
isetp
G1
i0
i1
u1
u0
u1
isetp
B1
G0
B0
Positive sequence
(b) ZeroNetwork
sequence
a) Positive(a)
Sequence
Network
c) Zero Sequence
a) Positive Sequence Network
i2
i2
u2
isetp
G2
B2
isetp
G2
u2
I1
B2
Isetp
U1
G1
B1
6.1
RSM
isetp Simulation
I2
U2
G0
B0
For RMS simulation the user has the option to control the current source in two different ways
depending of which signals from defined in Table B.1 are used. When the current (i0, I0) and
G2
B2
frequencyc)(f0,
input
are connected together with the additional angle magnitude, phase
ZeroF0Hz)
Sequence
Network
c)
Zero
Sequence
Network
and frequency of the AC current source are controlled. The resulting output current is defined
by equation 7.
G0 isetpB0
i = i0 cos(2f 0t + phiiI+
dphii) + j sin(2f 0t + phii + dphii) I0
(7)
1
I1
U
0
U1
U1
Also is possible independently control magnitude and phase for A, B and C components using
the signals: I A, I B, I C, phii B, phii C and dphii. PowerFactory internally applies the Park
G0
B0
Isetp
1
B1 components.
Transformation
to worksGwith
dq0
for phase A can be configured with
Isetp
G1 TheBangle
1
the input parameter dphii and the internal reference phii, both in rad. phii is calculated internally
by PowerFactory and can change if the network conditions change. The power factor set point
defines the steady state initial value of dphii. The derivative of phii is being changed if there is a
Zero Sequence Network
Positive Sequence
Network the derivative ofc)
frequencya)change:
f0 is connected,
phii is set to 2 P I f (f 0 f ref ); f0 is not
a) Positive Sequence Network
connected, the derivative of phii is set to 2 P I F 0Hz 2 P I f f ref . fref is automatically
set and should not be connected.
I2
I2
U2
U2
The current source gives an injection with current phase angle defined
as follows:
G2
B2
AC Current Source (ElmIac)
G2
B2
Dynamic Simulation
A = phii + dphii
(8)
B = A + phii B
(9)
C = A + phii C
(10)
If the two angle signals phii B and phii C are not connected, the program will use a default
120 shift to calculate the two angles.
6.2
B = A 120
(11)
C = A + 120
(12)
EMT Simulation
In EMT studies positive, negative and zero sequence models shown in Figures 1.1 to 1.3 are
considered. And as for RMS simulation it is possible to control the source in two different ways.
When inputs i0, I0, f0, F0Hz are connected the current injection is the same as defined by
equation 7 but there is also a negative sequence current defined by the differential equation 13.
i0 (t) = G0 u0 (t) +
B0
u0 (t)
2f t
(13)
When magnitude and phase signals are connected the model is defined as in RMS simulation.
The use of input and output signals from the dynamic model shown in Figure 6.2 could be used
to control the current injection into a system. This is useful to model a current impulse source
or to define a lightning current standard model.
With the help of a composite model, the user can use a Fourier source ElmFsrc to inject harmonic currents during an EMT simulation. For more information please refer to Fourier Source
Technical Reference.
Dynamic Simulation
i0
I0
f0
F0Hz
I_A
I_B
I_C
RMS
Simulation
xspeed
phii_B
phii_C
i0
I0
dphii
f0
fref
F0Hz
I_A
I_B
RMS
i0
phii_B
I0
phii_C
f0
dphii
F0Hz
fref
I_A
EMT
Simulation
I_B
I_C
dphii
i0
I0
f0
F0Hz
I_A
EMT
Simulation
I_B
I_C
dphii
Signal Definitions
Parameter Definitions
Table A.1: Parameters of AC Current Source
Parameter
Description
Unit
loc name
outserv
chr name
for name
bus1
bus1 bar
cpZone
cpArea
Ir
isetp
cosini
i cap
G1
B1
G2
B2
G0
B0
dcurdf
fchardcur
dphidf
fchardphi
phmc
icurref
iAstabint
cTypHmc
Inom
Name
Out of Service
Characteristic Name
Foreign Key
Terminal (StaCubic)
Terminal
Zone
Area
Rated Current
Positive Sequence Current Setpoint
Positive Sequence Power Factor
Positive Sequence Reactive Power
Positive Sequence Internal Conductance
Positive Sequence Internal Susceptance
Negative Sequence Internal Conductance
Negative Sequence Internal Susceptance
Zero Sequence Internal Conductance
Zero Sequence Internal Susceptance
Spectral Density of Current Magnitude
Frequency Dependency
Spectral Density of Current Angle
Frequency Dependency
Harmonic Current Injections
Harmonic Current Injections Referred to
A-stable integration algorithm
Harmonic Current Injections: Type of Harmonic Sources
Harmonic Current Injections: Rated Current
A
p.u.
S
S
S
S
S
S
p.u./Hz
A
deg/Hz
Signal Definitions
Table B.1: Input/Output signals
Name
Description
Unit
Type
Model
i0
I0
f0
F0Hz
IA
IB
IC
phii B
phii C
dphii
fref
xspeed
Current-Input
Current-Input
Frequency-Input
Frequency-Input
Current, Magnitude
Current, Magnitude
Current, Magnitude
Current, Angle, Phase b
Current, Angle, Phase c
Additional Angle
Reference Frequency
Frequency
p.u.
kA
p.u.
Hz
kA
kA
kA
deg
deg
rad
p.u.
p.u.
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
OUT
RMS, EMT
RMS, EMT
RMS, EMT
RMS, EMT
RMS, EMT
RMS, EMT
RMS, EMT
RMS
RMS
RMS, EMT
RMS
RMS
10
List of Figures
List of Figures
1.1 Positive sequence AC current source model . . . . . . . . . . . . . . . . . . . . .
11
List of Tables
List of Tables
A.1 Parameters of AC Current Source . . . . . . . . . . . . . . . . . . . . . . . . . .
10
10
12