1. General
This document is a Specification and Drawing of Coal Bunker Microcell (Load Cell) (Coal
Bunker Weighing System) for COCHRANE THERMOELECTRIC POWER PLANT, PULVERIZED
COAL FIRED BOILER project.
2. System Overview
Each Coal Bunker is supported on 4 legs (box shape of 400mm x 400mm x t32mm). Two Strain
Gauge Sensors per leg will be supplied. Each of the pair of sensors will be connected to one (1)
Junction Box by means of a cable supplied by Kistler-Morse. Wire from each Junction Box to a
Stahl Barrier Assembly. Stahl Barrier Assembly to be located within approximately 10 feet
distance from Weight Indicator, Model SVS2000. Interconnecting cable from Junction Box to
Stahl Barrier Assembly and from Stahl Barrier Assembly to Weight Indicator to be supplied by
Kistler- Morse.
1 pc.
4 pcs.
400 ft.
1 pc.
P/N SBMVS -S4-1 Stahl Barrier Assembly, Single Vessel. Stainless Steel Enclosure,
1 pc.
JOB NO.
CODE NO.
5411-C46
F734A01
(Microcell)
JOB NO.
CODE NO.
5411-C46
F734A01
Microcell
Bolt-on, strain gauge, sensor technology for measuring
inventory weights on vessels with support structures.
TECHNICAL SPECIFICATIONS
When you need weight inventory you want to use a weighing system. The Microcell is a highly
sensitive and thermally stable semiconductor strain gauge sensor, Kistler-Morse pioneered bolt-on
technology for measuring the contents of a wide range of bulk storage vessels. This sensor is still
the standard way to measure the weight-induced strain in a vessel with a leg support structure.
When Microcells are bolted on the vertical legs of a vessel, it converts the vessel into a weighing
system. Adding weight to a vessel compresses the gauge, changing the Microcells resistance which
produces an electrical output proportional to the material weight change.
The Microcell is quickly and easily installed while the vessel is still in productive use. An empty vessel
is not required for installation or calibration. For use on existing vessels with legs, the Microcell is a
cost-effective weighing solution compared to having to modify vessels for other types of weighing
sensors.
In combination with your existing vessels, the versatility of the Microcell can supply a cost effective,
easy to install, easy to maintain, highly reliable industrial strength weighing system. For cost and
performance, nothing can compare with the Microcell when weight is needed and weight is wanted.
FEATURES
AnD BEnEFITS
Bolt-on Technology
Creates a weighing system
by mounting Microcells to the
vessels support structure.
Simple Mounting
no specialized tools for
installation.
Uses Existing Vessel
Structure
no need to empty vessel or
take out of production to
install or service.
75 years MTBF
Unprecedented long-term
reliability.
Unique Design
Continuous weighing that
is immune to material
characteristics.
HOW TO ORDER
MC
(Notes 1, 2)
CABLE
015 = 15 ft. (4.6m) of Cable (note 3)
___ = Custom Length (in feet)
COVER SHAPE
n = no Cover
F = Flat Cover
S = Small Diameter Curved Cover (3 to 6)
L = Large Diameter Curved Cover (6 to 8 or larger)
VESSEL MATERIAL
X = Carbon Steel
A = Aluminum
S = Stainless Steel
SENSOR TYPE
S = Standardized, Light Blue Cover (note 5)
n = non-Standardized, Dark Blue Cover
A = Standardized, Light Blue Cover (note 5) with ATEX Approval (notes 4, 5)
X = non-Standardized, Dark Blue Cover with ATEX Approval (note 4)
SENSOR SIZE
3 = 3 inch
2 = 2 inch (note 5)
MICROCELL BOLT-ON SENSOR ASSEMBLY
note 1.
note 2.
note 3.
note 4.
note 5.
Specifications
FUNCTIONAL
Excitation Voltage
Excitation Current
Insulation Resistance
Strain Gage to Sensor Frame
Breakdown Voltage
Red to White & Black to
White Resistance
Stress Level
Fatigue Life
PERFORMANCE
PHYSICAL
Rating
Temperature Range
Weight
Steel Base
Cable
Cable Length
OPTIONS
3" Microcells
Junction Box
Test Meter
Aluminum Base
Stainless Steel Base
Installation Hardware
APPROVALS
ATEX, CE
97-7026-01 Rev. G
SVS2000TM
A full-featured, high performance weight indicator for
in-process weighing and batching or inventory weighing
applications.
TECHNICAL SPECIFICATIONS
FEATURES
AND BENEFITS
Quick Config
Adjusts system parameters and
precalibrates unit without special load
cells.
SentryTM DSP Filter
Separates mixer and plant vibrations
from weight changes. This provides
accurate and reliable weight readings.
High-speed, High-resolution Weight
Conversion
Performance for demanding
applications with up to 21-bit resolution.
Alphanumeric Backlit LCD Display
Simple, understandable operator
messages eliminates special coding/
decoding, cryptic setup and diagnostic
messages.
Displays the weight as a bar graph or
digital readout.
NEMA-4X Enclosure
ABS or optional stainless steel offers the
right protection for your environment.
HOW TO ORDER
SVS2000A
SLOT 1
A = Isolated 4-20 mA Output Card
B = Isolated Serial Card, RS232/RS422
N = None
SLOT 2
A = 0 mA Output Card
B = Isolated Serial Card, RS-232/RS-422
E = EtherNet/IP Card
F = DeviceNet Card
G = Profibus DP Card
N = None
ENCLOSURE TYPE
A = NEMA 4X, Plastic
B = NEMA 4X, Plastic with Bezel for Panel Mounting
S = NEMA 4X, SS
OPERATING VOLTAGE
A = AC Voltage (100 VAC to 120/230 VAC, 50/60 Hz)
SVS2000 WEIGHT INDICATOR
10
Specifications
FUNCTIONAL
Voltage - Operating Range
AC Power: 115 VAC 10%, 50/60 Hz; 230 VAC 10%, 50/60 Hz 30 VA
Operating Temperature
-4 to 122 F (-20 to 50 C)
PERFORMANCE
Transducer/Sensor Input
Excitation
Resolution
Conversion Speed
Span
Temperature Stability
100 db min @ 60 Hz
2 relay outputs; Form "C" SPDT, programmable, 10 A 110 VAC, 8 A 230 VAC non-inductive;
for motors and other large inductive loads, contractors rated for the load are required.
PHYSICAL
Display
Back lit alphanumeric liquid crystal, one line of 16 characters, selectable bar graph or engineering
units format
Programming/
Parameter Entry
Setup
Menu-driven prompts
Memory
Non-volatile RAM
Enclosure
Humidity
1% to 95% (non-condensing)
Storage
-4 to 140 F (-20 to 60 C)
Dimensions
Shipping Weight
ABS version: 6 lbs (2.6 kg). SS version: 11.3 lbs (5.1 kg)
OPTIONS
PCBs
RS-422, RS-485: (optical isolation standard), baud rate 1200, 2400, 4800, 9600 or 19.2K.
PLC interfaces: DeviceNet (polled slave), Profibus DP, Ethernet I/P.
Analog Output: 0-20 or 4-20 mA, 14 bit resolution, 500 VAC isolation, maximum load 600
ohms with internal loop supply
APPROVALS
CE, UL (US and Canada): General Purpose
97-7052 Rev. F
11
12
13
14
15
16
A2
A2
A2
A2
www.stahl.de
A2
A2
Series 9001 A2
09965E00
A2
R.STAHL safety barriers INTRINSPAK series 9001 are used for
various applications in the arena of automation. Based on the broad
range of versions and the possibility of various interconnections it
offers for almost all tasks.
The safety barriers enable the intrinsic safe operation of HART
transmitter, proximity switches, potential-free contacts and
temperature sensors, strain gauge, solenoid valves, indicators e.t.c.
The compact design allows a space saving and flexible installation
in the cabinet. The mounting is very comfortable and easy due to
the fact that installation on the DIN-rail and the contact to the
potential equalization is made in one step.
A2
A2
A2
ATEX / IECEX /
NEC 500
GOST
Class I
Zone
0 1 2 20 21 22
Zone
Ex i interfaces
x x x x
Ex i interfaces
Installation in
*)
x
x
Installation in
0 1
20 21 22
Division
Ex i interfaces
Installation in
x*)
A2
x*)
A2
A2
WebCode
2013-03-12AK00IIIen
9001A
A2
Safety Barriers
A2/1
17
Europe (ATEX)
Gas and dust
USA (NEC)
Gas and dust
Russia (GOST-R)
Gas
Certificates and approvals
Certificates
Further parameters
Installation
Further information
Technical data
Electrical data
Transmission
characteristic
Leakage current at UN
Temperature effect
Transmission
frequency
At resistive current
limitation
Im ( 50 mA
Im ) 50 mA
At electronic current
limitation
Ambient conditions
Ambient temperature
Storage temperature
Maximum relative
humidity
Mechanical data
Ingress protection
terminal enclosure
Casing
Enclosure material
Connection
Weight
A2/2
Safety Barriers
( 50 kHz
( 100 kHz
( 10 kHz
2013-03-12AK00IIIen
18
A2
Selection Table
Version
Description
Type
Page
Single-channel
barriers
9001/01
9001/01
9001/01
9001/01
9001/01
9001/00
10
9001/02
11
9001/02
13
9001/03
14
9001/51
15
9001/51
17
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
2013-03-12AK00IIIen
Safety Barriers
A2/3
19
Safe area
-Ue
+Ue
Intrinsically safe
field device
Control room
equipment
UN
0V
+Ue / 0V
0V
/ PA
05495E01
Selection Table
UN
Rmin
Rmax
Imax
Order number
Safety values
Uo
Io
Po
IIC
IIB
Lo
Co
mA
mA
mW
mH
mF
mH
mF
12
64
73
< 100
< 1.4
15.8
270
1067
0.23
0.478
2.2
2.88
9001/01-158-270-101
46
53
< 100
< 1.4
15.8
390
1541
0.16
0.478
0.89
2.88
9001/01-158-390-101
16
57
66
< 100
< 1.4
19.9
390
1940
0.89
1.42
9001/01-199-390-101
24
111
124
< 100
< 1.4
28
280
1960
0.6
0.65
9001/01-280-280-101
*) Ambient
Lo
Co
*)
temperature - 20 ... + 50 C
A2/4
UN
Nominal voltage
Imax
Po
Maximum power
IN
Nominal current
UN - U
IN =
Rmax + RL
Lo
Rmin
Minimum resistance of
the safety barriers
Uo
Maximum voltage
Co
Rmax
Maximum resistance of
the safety barriers
Io
Maximum current
RL
Safety Barriers
2013-03-12AK00IIIen
20
A2
Single-Channel Safety Barriers for Positive Polarity
Hazardous area
Grounded cicuit
Allows the connection of regulated power
supplies, UN
Approved for installation in Division 2 and
Zone 2
Safe area
+Ue
+Ue
Intrinsically safe
field device
UN
-Ue / 0V
Control room
equipment
A2
0V
A2
0V
/ PA
05438E02
Selection Table
UN
Rmin
Rmax
V
1 ... 3
6
10
12
16
20
24
42
24
864
452
195
129
64
39
27
681
178
93
215
120
872
377
235
2096
1052
539
415
282
149
378
1435
599
415
340
286
263
177
49
27
963
501
218
144
73
44
32
698
199
106
240
135
965
420
262
2321
1165
598
462
241
168
421
1590
666
462
375
319
294
198
A2
Imax
mA
61
222
6
11
27
41
82
136
187
11
40
75
41
88
12
28
45
6
13
26
34
66
95
47
15
36
51
64
75
81
121
Safety values
Uo
Io
V
5
8.3
8.6
8.6
8.6
8.6
8.6
8.6
8.6
12.6
12.6
12.6
13.7
15.8
16.8
16.8
16.8
19.9
19.9
19.9
19.9
19.9
19.9
25.2
28
28
28
28
28
28
28
mA
150
442
10
20
50
75
150
270
390
20
75
150
65
150
20
50
75
10
20
38
50
100
150
70
20
50
75
85
100
110
165
Order number
Po
mW
187.5
917.2
21.5
43
107.5
161.3
322.5
580.5
839
63
236
473
222.6
593
84
210
315
50
100
189
249
498
746
441
140
350
525
595
700
770
1155
IIC
Lo
mH
1.3
0.1
300
90
15
6.7
1.3
0.23
0.16
90
6.7
1.3
8.8
1
90
15
6.7
330
90
26
15
4
1.3
4.5
50
8.5
3.3
2.4
1.6
1.2
Co
mF
100
7.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
1.15
1.15
1.15
0.79
0.478
0.39
0.39
0.39
0.223
0.223
0.223
0.223
0.223
0.223
0.107
0.083
0.083
0.083
0.083
0.083
0.083
IIB
Lo
mH
7
0.5
1000
330
56
25
7
2.2
1
330
25
7
34
7
330
56
25
1000
330
95
56
15
7
25
50
25
21
16
11
9
3.5
Co
mF
1000
73
55
55
55
55
55
55
55
7.4
7.4
7.4
5
2.88
2.29
2.29
2.29
1.42
1.42
1.42
1.42
1.42
1.42
0.82
0.65
0.65
0.65
0.65
0.65
0.65
0.65
A2
9001/01-050-150-101
9001/01-083-442-101
9001/01-086-010-101
9001/01-086-020-101
9001/01-086-050-101
9001/01-086-075-101
9001/01-086-150-101
9001/01-086-270-101
9001/01-086-390-101
9001/01-126-020-101
9001/01-126-075-101
9001/01-126-150-101
9001/01-137-065-101
9001/01-158-150-101
9001/01-168-020-101
9001/01-168-050-101
9001/01-168-075-101
9001/01-199-010-101
9001/01-199-020-101
9001/01-199-038-101
9001/01-199-050-101
9001/01-199-100-101
9001/01-199-150-101
9001/01-252-070-101
9001/01-280-020-101
9001/01-280-050-101
9001/01-280-075-101
9001/01-280-085-101
9001/01-280-100-101
9001/01-280-110-101
9001/01-280-165-101
A2
A2
A2
A2
A2
A2
A2
Nominal voltage
Imax
Maximum current
through the safety barrier
Po
Maximum power
Rmin
Minimum resistance
of the safety barrier
Uo
Maximum voltage
Lo
Maximum permissible
external inductance
Rmax
Maximum resistance
of the safety barrier
Io
Maximum current
Co
Maximum permissible
external capacity
A2
A2
2013-03-12AK00IIIen
Safety Barriers
A2/5
21
Safe area
Hazardous area
4 ... 20 mA
9001/01-280-110-101
11331E01
Operating data
Operating voltage
UN = + 24 V
Operating current
IN = 0 ... 22 mA
Umax (6.5 V
Safety data
Maximum voltage
Uo = 28 V
Maximum current
Io = 110 mA
Maximum permissible
external inductance
Lo
IIC
2.2 mH
IIB
9 mH
Maximum permissible
external capacity
Co
IIC
0.08 F
IIB
0.65 F
Maximum power
Po = 770 mW
Hazardous area
4 ... 20 mA
Safe area
+24 V DC
9001/01-280-110-101
09952E01
Application note
This safety barrier is used if the control system measures the current in the supply line.
The transmitter and the control system are earthed, regulated power supply must be used.
Discrete 2-wire output for magnet reed switches, LEDs and audible alarm indicators
Schematic
Hazardous area
Safe area
+24 V DC
9001/01-280-110-101
06603E01
Application note
A2/6
Safety Barriers
This barrier is suitable for use with regulated power supplies and earthed return circuits.
The rated voltage is 24 V. 9001/01-280-165-101 and 9001/01-280-280-101 should be used for
applications which require higher power and for use exclusively in gas groups IIB and IIA.
2013-03-12AK00IIIen
22
A2
Safe area
-Ue
+Ue
Intrinsically safe
field device
UN
Control room
equipment
+Ue
-Ue / 0V
A2
0V
A2
/ PA
05494E02
Selection Table
UN
Rmin
Rmax
Imax
Uo
Io
Po
IIC
IIB
Lo
Co
mA
mA
mW
mH
mF
mH
mF
20 ... 35
454
505
40
25.2
57
359
6.3
0.107
25
0.82
* ) Maximum
A2
Order number
Safety values
Lo
Co
9001/01-252-057-141
A2
*)
A2
Nominal voltage
Lo
Rmin
Minimum resistance of
the safety barriers
Uo
Maximum voltage
Co
Rmax
Maximum resistance of
the safety barriers
Io
Maximum current
RL
Imax
Po
Maximum power
A2
A2
Application
Binary input with switch (load to +) Field circuit earthed
Schematic
Hazardous area
Safe area
Supply Voltage
A2
+20 ... 35 V DC
9001/01-252-057-141
RL
A2
01721E01
Operating data
Operating voltage
Open-circuit output voltage
(3 -> 4, In = 0)
Operating current
UN = + 20 ... 35 V
UL )
UN (24 V
UN > 24 V
UN - 3 V
21 V
A2
IN = UL / 505 + RL
Safety data
Maximum voltage
Uo = 25.2 V
Maximum current
Io = 57 mA
A2
Maximum permissible
external inductance
Lo
IIC
6.3 mH
IIB
25 mH
Maximum permissible
external capacity
Co
IIC
0.107 F
IIB
0.82 F
Maximum power
Po = 359 mW
Application note
A2
A2
2013-03-12AK00IIIen
Safety Barriers
A2/7
23
Safe area
-Ue
+Ue
Intrinsically safe
field device
UN
Control room
equipment
+Ue
-Ue / 0V
0V
/ PA
05440E02
Selection Table
UN
Rmin
Rmax
Imax
Order number
Safety values
Uo
Io
Po
IIC
IIB
Lo
Co
mA
mA
mW
mH
mF
mH
mF
20 ... 35
454
505
40
25.2
60
378
6.2
0.107
25
0.82
* ) Maximum
Lo
Co
9001/01-252-060-141
*)
Nominal voltage
Lo
Rmin
Minimum resistance of
the safety barriers
Uo
Maximum voltage
Co
Rmax
Maximum resistance of
the safety barriers
Io
Maximum current
RL
Imax
Po
Maximum power
Application
Binary input with switch (load on ground) Field circuit earthed
Schematic
Hazardous Location
Nonhazardous Location
Supply Voltage
+20 ... 35 V DC
9001/01-252-060-141
RL
09955E01
Operating data
Operating voltage
Open-circuit output voltage
(3 -> 4, In = 0)
Operating current
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note
A2/8
Safety Barriers
UN = + 20 ... 35 V
UL )
UN (24 V
UN > 24 V
UN - 3 V
21 V
IN = UL / 505 + RL
Uo = 25.2 V
Io = 60 mA
Lo
IIC
6.2 mH
IIC
0.107 F
IIB
25 mH
IIB
0.82 F
Co
Po = 378 mW
This safety barrier is particularly suitable for relay control.
A binary input (optocoupler) of an automation device can be used as load.
2013-03-12AK00IIIen
24
A2
Single-Channel Safety Barriers for Positive Polarity
Hazardous area
Application specific for the connection of solenoid valves, LEDs or audible alarms
Grounded circuit
Allows the connection of unregulated power
supplies, UN between + 20 to 35 V DC
Approved for installation in Division 2 and
Zone 2
Safe area
+Ue
+Ue
Intrinsically safe
field device
Control room
equipment
UN
0V
-Ue / 0V
A2
A2
0V
/ PA
05501E02
A2
Selection Table
UN
Rmin
Rmax
Imax
Order number
Safety values
Uo
Io
Po
IIC
IIB
Lo
Co
mA
mA
mW
mH
mF
mH
mF
20 ... 35
259
268
78
25.2
100
630
0.107
11
0.82
*)
Lo
Co
A2
9001/01-252-100-141
*)
A2
Nominal voltage
Imax
Maximum current
through the safety barrier
Po
Maximum power
Rmin
Minimum resistance
of the safety barrier
Uo
Maximum voltage
Lo
Maximum permissible
external inductance
Rmax
Maximum resistance
of the safety barrier
Io
Maximum current
Co
Maximum permissible
external capacity
A2
A2
Application
Binary output (current source) for valves, LEDs etc. Field circuit earthed
Schematic
Nonhazardous Location
Hazardous Location
A2
+20 ... 35 V DC
9001/01-252-100-141
A2
06602E01
Operating data
Operating voltage
Open-circuit output voltage
(3 -> 4, In = 0)
Operating current
Safety data
Maximum voltage
Maximum current
Maximum permissible external inductance
Maximum permissible external capacity
Maximum power
UN = + 20 ... 35 V
UL )
UN (24 V
UN > 24 V
UN - 3 V
21 V
A2
IN = UL / 268 + RL
Uo = 25.2 V
Io = 100 mA
Lo
Co
Po = 630 mW
A2
IIC
2 mH
IIC
0.107 F
IIB
11 mH
IIB
0.82 F
A2
A2
2013-03-12AK00IIIen
Safety Barriers
A2/9
25
Grounded cicuit
Allows the connection of regulated power
supplies, UN
Approved for installation in Division 2 and
Zone 2
Safe area
-Ue
-Ue
Intrinsically safe
field device
Control room
equipment
UN
+Ue / 0V
0V
0V
/ PA
05428E02
Selection Table
UN
Rmin
Rmax
Imax
Order number
Safety values
Uo
Io
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
1 ... 3
42
49
61
150
187.5
1.3
100
1000
9001/00-050-150-101
24
28
214
8.3
442
917.2
0.1
7.2
0.5
73
9001/00-083-442-101
864
963
8.6
10
21.5
300
6.2
1000
55
9001/00-086-010-101
452
501
11
8.6
20
43
90
6.2
330
55
9001/00-086-020-101
195
218
27
8.6
50
107.5
15
6.2
56
55
9001/00-086-050-101
92
103
58
8.6
100
215
6.2
15
55
9001/00-086-100-101
64
73
82
8.6
150
322.5
1.3
6.2
55
9001/00-086-150-101
39
45
136
8.6
270
580.5
0.23
6.2
2.2
55
9001/00-086-270-101
27
32
187
8.6
390
839
0.16
6.2
55
9001/00-086-390-101
12
120
135
88
15.8
150
593
0.478
2.88
9001/00-158-150-101
16
1052
1165
13
19.9
20
100
90
0.223
330
1.42
9001/00-199-020-101
539
598
26
19.9
38
189
26
0.223
95
1.42
9001/00-199-038-101
415
462
34
19.9
50
248.8
15
0.223
56
1.42
9001/00-199-050-101
149
168
95
19.9
150
746
1.3
0.223
1.42
9001/00-199-150-101
1435
1590
15
28
20
140
50
0.083
50
0.65
9001/00-280-020-101
599
666
36
28
50
350
8.5
0.083
25
0.65
9001/00-280-050-101
340
375
64
28
85
595
2.4
0.083
16
0.65
9001/00-280-085-101
286
319
75
28
100
700
1.6
0.083
11
0.65
9001/00-280-100-101
263
294
81
28
110
770
1.2
0.083
0.65
9001/00-280-110-101
177
198
121
28
165
1155
3.5
0.65
9001/00-280-165-101
24
A2/10
UN
Nominal voltage
Imax
Maximum current
through the safety barrier
Po
Maximum power
Rmin
Minimum resistance
of the safety barrier
Uo
Maximum voltage
Lo
Maximum permissible
external inductance
Rmax
Maximum resistance
of the safety barrier
Io
Maximum current
Co
Maximum permissible
external capacity
Safety Barriers
2013-03-12AK00IIIen
26
A2
Series 9001/02
Grounded circuit
Suitable for AC and DC circuits
Approved for installation in Division 2 and
Zone 2
Safe area
+/-Ue
+/-Ue
Intrinsically safe
field device
UN
A2
Control room
equipment
+/-Ue/0V
+/-Ue/0V
A2
0V
/ PA
05502E02
A2
Selection Table
UN
Rmin
Rmax
Imax
Order number
Safety values
Uo
Io
Po
IIC
IIB
Lo
Co
mA
mA
mW
mH
mF
mH
mF
0.7
119
134
1.6
15
160
100
560
1000
9001/02-016-015-101
*)
38
43
16
1.6
50
20
15
100
56
1000
9001/02-016-050-101
*)
39
40
17
1.6
50
20
15
100
56
1000
9001/02-016-050-111
*)
20
35
1.6
150
60
1.3
100
1000
9001/02-016-150-101
*)
19.9
20.1
35
1.6
150
60
1.3
100
1000
9001/02-016-150-111
*)
11
14
50
1.6
320
128
0.19
100
1.6
1000
9001/02-016-320-101
*)
3141
3472
1.7
9.3
6.975
1000
4.1
1000
31
9001/02-093-003-101
319
354
16
9.3
30
69.8
40
4.1
150
31
9001/02-093-030-101
195
218
27
9.3
50
116.3
15
4.1
56
31
9001/02-093-050-101
148
165
36
9.3
75
174.4
6.7
4.1
25
31
9001/02-093-075-101
70
79
75
9.3
150
348.8
1.3
4.1
31
9001/02-093-150-101
36
166
9.3
390
906.8
0.16
4.1
0.89
31
9001/02-093-390-101
10
102
115
86
13.3
150
498.8
1.3
0.91
5.6
9001/02-133-150-101
12
378
421
28
17.5
50
219
15
0.339
56
1.97
9001/02-175-050-101
197
222
54
17.5
100
437.5
0.339
15
1.97
9001/02-175-100-101
101
114
105
17.5
200
875
0.5
0.339
1.97
9001/02-175-200-101
16
148
167
95
19.6
150
735
1.3
0.235
1.47
9001/02-196-150-101
24
320
357
67
28
90
630
2.2
0.083
14
0.65
9001/02-280-090-101
36
456
509
70
41.2
95
979
0.287
9001/02-412-095-101
*)
Maximum leakage
Tolerance
Lo
Co
A2
A2
A2
A2
A2
A2
Ileak ( 10 mA
0.5 %
A2
Nominal voltage
Imax
Maximum current
through the safety barrier
Po
Maximum power
Rmin
Minimum resistance
of the safety barrier
Uo
Maximum voltage
Lo
Maximum permissible
external inductance
Rmax
Maximum resistance
of the safety barrier
Io
Maximum current
Co
Maximum permissible
external capacity
A2
A2
A2
2013-03-12AK00IIIen
Safety Barriers
A2/11
27
Hazardous area
Safe area
RTD
Input
9002/22-032-300-111
9001/02-016-150-111
Supply
Voltage
09960E01
Operating data
Operating voltage
UN ( 1.4 V
Series resistance of
the safety barriers
R = 3 x (20 0.1 )
Measuring range
Safety data
A2/12
Maximum voltage
Uo = 3.2 V
Maximum current
Io = 450 mA
Maximum permissible
external inductance
Lo
IIC
0.12 mH
IIB
0.5 mH
Maximum permissible
external capacity
Co
IIC
0.10 F
IIB
1000 F
Safety Barriers
2013-03-12AK00IIIen
28
A2
Single-Channel Safety Barriers for Alternating Polarity
Hazardous area
Safe area
+/-Ue
+/-Ue
Intrinsically safe
field device
UN
Control room
equipment
Grounded circuit
Suitable for AC and DC circuits
Current limitation to < Imax
Approved for installation in Division 2 and
Zone 2
A2
+/-Ue/0V
+/-Ue/0V
A2
0V
/ PA
05526E02
A2
Selection Table
UN
Rmin
Rmax
Imax
Order number
Safety values
Uo
Io
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
16
63
72
< 80
< 1.4
21.7
390
2116
0.89
1.17
9001/02-217-390-101
24
143
162
< 65
< 1.4
30.8
230
1771
0.7
0.524
9001/02-308-230-101
A2
A2
Nominal voltage
Imax
Po
Maximum power
IN
Nominal current
UN - U
IN =
Rmax + RL
Lo
Rmin
Minimum resistance of
the safety barriers
Uo
Maximum voltage
Co
Rmax
Maximum resistance of
the safety barriers
Io
Maximum current
A2
A2
A2
A2
A2
A2
A2
A2
2013-03-12AK00IIIen
Safety Barriers
A2/13
29
+Ue
Intrinsically safe
field device
Grounded circuit
For DC current signal returns
Approved for installation in Division 2 and
Zone 2
Safe area
+Ue
Control room
equipment
UN
0V
-Ue / 0V
0V
/ PA
05541E02
Selection Table
UN
Imax
Order number
Safety values
Uo
Io
Po
IIC
IIB
Lo
Co
mA
mA
mW
mH
mF
mH
mF
< 150
3.5
8.6
1000
6.2
1000
55
9001/03-086-000-101
*)
12
< 100
3.5
16.8
1000
0.39
1000
2.29
9001/03-168-000-101
*)
16
< 100
3.5
19.9
1000
0.223
1000
1.42
9001/03-199-000-101
*)
9001/03-280-000-101
*) **)
24
< 100
3.5
28
*)
**)
Ambient temperature
- 20 C ... + 50 C
Lo
Co
50
0.083
50
0.65
Nominal voltage
Po
Maximum power
IN
Nominal current
UN - U
IN =
Rmax + RL
Uo
Maximum voltage
Lo
Imax
Io
Maximum current
Co
Application
3-wire 4 ... 20 mA transmitter
Schematic
Hazardous area
Safe area
9001/01-280-100-101
4 ... 20 mA
+24 V DC
Signal
9001/03-280-000-101
15294E01
A2/14
Safety Barriers
2013-03-12AK00IIIen
30
A2
Series 9001/51
Safe area
Power supply
+20 V ... 35 V
0V
Is
+Ue
Intrinsically safe
field device
UN
Control room
+Ue equipment
-Ue / 0V
A2
A2
RL
0V
/ PA
05561E01
A2
Selection Table
UN
Safety values
Uo
Io
Order number
Po
IIC
IIB
Lo
Co
mA
mW
mH
mF
mH
mF
20 ... 35
28
91
637
2.2
0.083
14
0.65
9001/51-280-091-141
20 ... 35
28
110
770
1.2
0.083
0.65
9001/51-280-110-141
Technical data
Version
Supply current
Accuracy
Temperature influence
Longterm drift
Rated operational current
Load
Transmitter supply voltage
Lo
Co
A2
A2
9001/51-280-091-141
Is ( 50 mA
0.05 %
0.1 % / 10 K
0.05 %
IN = 3.6 mA ... 22 mA
RL ( 350
Umin (IN = 20 mA)
UN - 9.5 V
14 V
9001/51-280-110-141
Is ( 50 mA
0.05 %
0.1 % / 10 K
0.05 %
IN = 3.6 mA ... 22 mA
RL ( 500 (UN ( 23.5 V)
RL ( 750 (UN > 23.5 V)
UN
( 23.5 V
> 23.5 V
UN
( 23.5 V
> 23.5 V
A2
A2
Nominal voltage
Po
Maximum power
Uo
Maximum voltage
Lo
Maximum permissible
external inductance
Io
Maximum current
Co
Maximum permissible
external capacity
A2
A2
A2
A2
A2
A2
2013-03-12AK00IIIen
Safety Barriers
A2/15
31
Safe area
Hazardous area
+20 ... 35 V DC
4 ... 20 mA
9001/51-280-110-141
09950E01
Operating data
Operating voltage
UN = + 20 ... 35 V
Load
Operating voltage of
the transmitter
UN
UN - 8.5 V
( 23.5 V
15 V
> 23.5 V
Safety data
A2/16
Maximum voltage
Uo = 28 V
Maximum current
Io = 110 mA
Maximum permissible
external inductance
Lo
IIC
1.2 mH
IIB
9 mH
Maximum permissible
external capacity
Co
IIC
0.083 F
IIB
0.65 F
Maximum power
Po = 770 mW
Application note
Safety Barriers
2013-03-12AK00IIIen
32
A2
Series 9001
Figure
Description
Art. no.
Weight
158964
0.008 /
0.018
158977
0.002 /
0.004
158973
0.005 /
0.011
158826
0.006 /
0.013
165283
0.004 /
0.009
NS 35 / 15 (meter length)
103714
1.410 /
3.109
112760
0.012 /
0.026
kg / lbs
Back-up fuse
09919E00
09920E00
Labelling paper
A2
A2
09921E00
Adaptor
A2
09922E00
Mounting attachment
moulded plastic
09924E00
DIN rail
03856E00
Earth terminal
A2
A2
09926E00
Earth terminal
A2
112599
0.030 /
0.066
A2
09926E00
Fuse holder
158834
0.020 /
0.044
158828
0.023 /
0.051
A2
09927E00
09928E00
A2
A2
A2
A2
A2
2013-03-12AK00IIIen
Safety Barriers
A2/17
33
12 mm / 0.47 "
72 mm / 2.83 "
09929E00
76 mm / 3.00 "
95 mm / 3.74 "
80 mm / 3.15 "
09930E00
66 mm
2.60 "
66 mm
2.60 "
38 mm
1.50 "
09933E00
38 mm
1.50 "
09932E00
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice.
The illustrations cannot be considered binding.
A2/18
Safety Barriers
2013-03-12AK00IIIen
34
A2
A2
A2
A2
www.stahl.de
A2
A2
Series 9002 A2
04101E00
A2
The R. STAHL INTRINSPAK safety barriers of Series 9002 can be
used for various tasks in the field of automation. The wide product
range and scope of different combinations offer you a large field of
applications.
The safety barriers allow the intrinsically safe operation of HART
transmitters, proximity sensors, potential-free contacts,
temperature sensors, DMS, solenoid valves, indicators and others.
Due to the compact width, space-saving and flexible installation in
the switch cabinet is possible. Thanks to DIN-rail mounting and
simultaneous connection of the equipotential bonding, the
installation can be performed very easily.
ATEX / IECEX
Zone
0 1 2 20 21 22
Zone
Ex i interface
x x x x
Ex i interface
Installation in
*) For
x
x
Installation in
A2
A2
A2
NEC 500
Class I
0 1
20 21 22
Division
Ex i interface
Installation in
x*)
A2
x*)
A2
A2
WebCode
2013-05-24AK00IIIen
9002A
A2
Safety barriers
A2/1
35
Explosion Protection
Global (IECEx)
Gas and dust
Europe (ATEX)
Gas and dust
Certificates
Certificates
Further parameters
Installation
Further information
Technical Data
Electrical data
Transmission
characteristic
Leakage current at UN
Temperature influence
( 0.25 % / 10 K
Transmission
frequency
In case of resistive
current limiting
Im ( 50 mA
( 50 kHz
Im ) 50 mA
In case of electronic
current limiting
Ambient conditions
Ambient temperature
Storage temperature
Maximum relative
humidity
Mechanical data
Degree of protection
Terminal support
Enclosure
Enclosure material
Connection type
Weight
A2/2
Safety barriers
( 100 kHz
( 10 kHz
2013-05-24AK00IIIen
36
A2
Selection table
Version
Description
Type series
Page
Dual-channel barriers
9002/11
A2/4
9002/11
A2/6
9002/11
A2/7
9002/00
A2/8
9002/10
A2/9
9002/22
A2/11
A2
A2
A2
9002/22
A2/13
Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Connection to unregulated power supply on UN to channel 1
Nominal current limited to 35 mA
9002/13
A2/14
Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Connection to regulated power supply UN
9002/13
A2/16
Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Nominal current limited to 40 mA at 250 load
Connection to unregulated power supply on UN to channel 1
9002/13
A2/18
Evaluation barrier for direct current signals with max. output current Io
Suitable for potential-free contacts and floating 4/20 mA signals
Positive potential of both channels
9002/33
A2/19
Evaluation barrier for direct current signals with max. output current Io
Application for passive signals of 4/20 mA (transmitter with 4 conductors
or more) with insulated analog input on the control system
Channel for positive and negative potential in one module
9002/34
A2/20
9002/77
A2/21
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/3
37
Series 9002/11
Safe area
+ve
+ve
Intrinsically safe
field device(s)
Control room
equipment
UN
+ve
+ve
0V
/ PA
05820E01
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Order number
Uo
Io
Po
IIC
mA
mA
mW
mH
mF
mH
mF
1
2
1+2
9
9
--
1043
1043
--
1156
1156
--
7.7
7.7
--
12
12
12
12
12
24
40
40
70
240
240
63
1.41
1.41
1.1
850
850
230
9
9
7.1
9002/11-120-024-001
1
2
1+2
10
1
--
45
45
--
52
52
--
100
19
--
13
1.6
13
321
39
360
1040
16
1170
0.19
24
0.17
1
100
0.79
1.6
91
1.3
6
100
5
9002/11-130-360-001
1
2
1+2
10
10
--
953
953
--
978
978
--
10
10
--
13.7
13.7
13.7
14.5
14.5
29
50
50
100
160
160
43
0.79
0.79
0.67
560
560
160
5
5
4.18
9002/11-137-029-001
1
2
1+2
16
16
--
1423
1423
--
1576
1576
--
10
10
--
19.9
19.9
19.9
15
15
30
75
75
150
160
160
40
0.223
0.223
0.223
560
560
150
1.42
1.42
1.42
9002/11-199-030-001
1
2
1+2
22.5
17.5
--
321
416
--
358
463
--
62
37
--
26
20
26
87
51
138
570
260
850
2.7
14
0.81
0.099
0.22
0.087
15.4
54
5.1
0.77
1.41
0.67
9002/11-260-138-001
1
2
1+2
25
25
--
321
321
--
358
358
--
69
69
--
28
28
28
93
93
186
650
650
1300
2
2
--
0.083
0.083
--
13
13
2.8
0.65
0.65
0.551
9002/11-280-186-001
1
2
1+2
25
6
--
321
59
--
358
68
--
69
88
--
28
9.6
28
89
180
269
630
430
1050
2.2
0.6
--
0.083
3.6
--
14
5
0.56
0.65
26
0.62
9002/11-280-293-001
IIB
*)
A2/4
UN
Nominal voltage
Imax
Po
Maximum power
Rmin
Uo
Maximum voltage
Lo
Rmax
Io
Maximum current
Co
Safety barriers
2013-05-24AK00IIIen
38
A2
Application case
Load cell (DMS) 350 or 700
6 conductors + 16 V, field circuit unearthed
Schematic
Hazardous area
A2
Safe area
+16 V
9002/13-199-225-001
A2
0V
9002/11-199-030-001
9002/11-199-030-001
A2
09963E01
Operating data
Operating voltage
Voltage for load cell and
electric line
Current for load cell
IL (at UN = + 16 V)
Number of the load cells
connected in parallel
1
2
3
4
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note
A2
UN ( + 16 V
UL (at UN = + 16 V)
Uo = 19.9 V
Io = 285 mA
Lo
IIC
0.2 mH
IIC
0.223 F
350
UL (V)
10.4
8.3
6.9
5.9
ImA (V)
30
47
60
67
700
UL (V)
12.1
10.4
9.5
8.3
A2
ImA (V)
17
30
41
47
A2
IIB
1.8 mH
IIB
1.42 F
A2
Co
Po = 1.42 W
For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 255 mA, the
maximum power to Po = 1.3 W.
3-wire NPN inputs (negative switching) of proximity switches, photocells and encoders
Schematic
Hazardous area
Safe area
A2
A2
+24 V DC
Supply
9002/11-280-186-001
+0 V
NPN
A2
06601E01
Discrete 2-wire output for solenoid valves, LEDs and signalling devices
Schematic
Safe area
Hazardous area
A2
9002/11-280-186-001
+24 V DC
+24 V DC
A2
06606E01
2013-05-24AK00IIIen
Safety barriers
A2
A2/5
39
Safe area
+ve
+ve
Intrinsically safe
field device(s)
Control room
equipment
UN
RL
+ve
+ve
0V
/ PA
05823E01
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
1
2
1+2
Io
Order number
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
24
24
--
264
11979
--
296
12221
--
91
2
--
28
28
28
109
3
112
760
20
780
1.3
50
0.76
0.083
0.083
0.065
9
150
84
0.65
0.65
0.551
9002/11-280-112-001
Nominal voltage
Imax
Po
Maximum power
Rmin
Uo
Maximum voltage
Lo
Rmax
Io
Maximum current
Co
Application case
3-wire NPN inputs (negative switching) of proximity switches, photocells and encoders
Schematic
Hazardous area
Safe area
+24 V DC
Supply
9002/11-280-112-001
0V
NPN
06597E01
Application note
A2/6
Safety barriers
With this barrier all loop voltages must be checked to ensure correct function.
2013-05-24AK00IIIen
40
A2
Two-channel safety barriers, potential: + / +
Hazardous area
Safe area
+ve
+ve
Intrinsically safe
field device(s)
A2
Control room
equipment
UN
+ve
+ve
A2
0V
/ PA
05824E01
A2
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
1
2
1+2
Io
Order number
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
25
6
--
321
59
--
358
68
--
69
88
--
28
9.6
28
89
180
269
630
430
1050
2.2
0.6
--
0.083
3.6
--
14
5
0.56
0.65
26
0.62
A2
9002/11-280-293-021
A2
Nominal voltage
Imax
Po
Maximum power
Rmin
Uo
Maximum voltage
Lo
Rmax
Io
Maximum current
Co
A2
Application case
A2
Hazardous area
4 ... 20 mA
Safe area
9002/11-280-293-021
A2
+24 V DC
+1 ... 5 V
Input
A2
11332E01
Application note
This safety barrier is used if the automation system only accepts signals from 1 to 5 V.
This barrier contains a 250 resistor to convert the signal 1 ... 5 V.
A2
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/7
41
Series 9002/00
Safe area
-ve
-ve
Intrinsically safe
field device(s)
Control room
equipment
UN
-ve
-ve
0V
/ PA
05822E01
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
Io
Order number
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
1
2
1+2
9
9
--
1043
1043
--
1156
1156
--
7.7
7.7
--
12
12
12
12
12
24
40
40
70
240
240
63
1.41
1.41
1.1
850
850
230
9
9
7.1
9002/00-120-024-001
1
2
1+2
22.5
17.5
--
321
416
--
358
463
--
62
37
--
26
20
26
87
51
138
540
245
785
2.7
14
0.81
0.099
0.22
0.087
15.4
54
5.1
0.77
1.41
0.67
9002/00-260-138-001
1
2
1+2
25
25
--
321
321
--
358
358
--
69
69
--
28
28
28
93
93
186
650
650
1300
2
2
--
0.083
0.083
--
13
13
2.8
0.65
0.65
0.551
9002/00-280-186-001
Nominal voltage
Imax
Po
Maximum power
Rmin
Uo
Maximum voltage
Lo
Rmax
Io
Maximum current
Co
Application case
Vibration sensor
Schematic
Hazardous area
Safe area
-24 V DC max.
Sensor
9002/00-260-138-001
Transducer
Input
0V
06615E01
Operating data
Operating voltage
Series resistance of the
safety barrier
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note
A2/8
Safety barriers
UN = - 24V
R = 358
Uo = 26 V
Io = 138 mA
Lo
IIC
0.81 mH
IIC
0.087 F
IIB
5.1 mH
IIB
0.67 F
Co
Po = 850 mW
Application of the barrier for Bentley Nevada and Metrix position transducer. This barrier has negative
potential; for a positive potential, use the barrier 9002/11-260-138-001.
2013-05-24AK00IIIen
42
A2
Series 9002/10
Safe area
+ve
+ve
Intrinsically safe
field device(s)
A2
Control room
equipment
UN
-ve
-ve
A2
0V
/ PA
05821E01
A2
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
Io
Order number
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
1
2
1+2
6
6
--
490
490
--
543
543
--
11
11
--
9.33
9.33
18.7
20
20
20
50
50
90
90
90
90
3.9
3.9
0.27
330
330
330
29
29
1.64
9002/10-187-020-001
1
2
1+2
6
6
--
42
42
--
49
49
--
122
122
--
9.33
9.33
18.7
270
270
270
630
630
1260
0.23
0.23
0.23
3.9
3.9
0.27
2.2
2.2
2.2
29
29
1.64
9002/10-187-270-001
A2
A2
Nominal voltage
Imax
Po
Maximum power
Rmin
Uo
Maximum voltage
Lo
Rmax
Io
Maximum current
Co
A2
A2
A2
A2
A2
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/9
43
Application case
Load cell (DMS) 350 or 700
6 conductors +/- 7.5 V (15 V), field circuit unearthed
Schematic
Hazardous area
Safe area
+7,5 V
9002/10-187-270-001
-7,5 V
9002/10-187-020-001
9002/77-093-040-001
09962E01
Operating data
Operating voltage
Voltage for load cell and
electric line
Current for load cell
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note
A2/10
Safety barriers
350
UL (V)
ImA (V)
UL (V)
ImA (V)
11.6
35
13.2
19
9.6
55
11.6
35
70
10.6
45
80
9.6
55
Uo = 18.7 V
Io = 330 mA
Lo
IIC
0.18 mH
IIC
0.27 F
700
IIB
1.45 mH
IIB
1.64 F
Co
Po = 1.45 W
For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 310 mA,
the maximum power to Po = 1.36 W.
2013-05-24AK00IIIen
44
A2
Series 9002/22
Safe area
+/-ve
+/-ve
Intrinsically safe
field device(s)
Control room
equipment
UN
+/-ve
+/-ve
A2
A2
0V
/ PA
05835E01
A2
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
1
2
1+2
Io
Order number
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
0.7
0.7
1.4
19.9
19.9
--
20.1
20.1
--
33
33
--
1.6
1.6
3.2
150
150
300
60
60
120
1.3
1.3
0.2
100
100
100
7
7
1.8
1000
1000
1000
A2
9002/22-032-300-111
*)
A2
Nominal voltage
Imax
Po
Maximum power
Rmin
Uo
Maximum voltage
Lo
Rmax
Io
Maximum current
Co
A2
A2
A2
A2
A2
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/11
45
Application case
Pt100, 2-wire circuit, field circuit unearthed
Schematic
Hazardous area
Safe area
RTD
Input
9002/22-032-300-111
09959E01
Operating data
Operating voltage
UN ( 1.4 V
Measuring range
Safety data
Maximum voltage
Uo = 3.2 V
Maximum current
Io = 300 mA
Maximum permissible
external inductance
Lo
IIC
0.2 mH
IIB
1.8 mH
Maximum permissible
external capacity
Co
IIC
100 F
IIB
1000 F
Hazardous area
Safe area
RTD
Input
9002/22-032-300-111
9001/02-016-150-111
Supply
Voltage
09960E01
Operating data
Operating voltage
UN ( 1.4 V
Measuring range
Safety data
A2/12
Maximum voltage
Uo = 3.2 V
Maximum current
Io = 450 mA
Maximum permissible
external inductance
Lo
IIC
0.12 mH
IIB
0.5 mH
Maximum permissible
external capacity
Co
IIC
100 F
IIB
1000 F
Safety barriers
2013-05-24AK00IIIen
46
A2
Two-channel safety barriers, potential: ~ / ~
Hazardous area
Safe area
A2
+/-ve
+/-ve
Intrinsically safe
field device(s)
Control room
equipment
UN
+/-ve
+/-ve
A2
0V
/ PA
05845E01
A2
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
Io
Order number
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
1
2
1+2
5.5
5.5
11
84
84
--
95
95
--
57
57
--
7.9
7.9
15.8
100
100
200
198
198
395
4
4
0.5
8.8
8.8
0.478
15
15
4
115
115
2.88
9002/22-158-200-001
1
2
1+2
9
9
18
1043
1043
--
1156
1156
--
7.7
7.7
--
12
12
24
12
12
24
40
40
80
240
240
41
1.41
1.41
0.125
850
850
145
9
9
0.93
9002/22-240-024-001
1
2
1+2
9
9
18
158
158
--
177
177
--
50
50
--
12
12
24
80
80
160
240
240
480
6
6
0.7
1.41
1.41
0.125
22
22
4
9
9
0.93
9002/22-240-160-001
A2
A2
A2
Nominal voltage
Imax
Po
Maximum power
Rmin
Uo
Maximum voltage
Lo
Rmax
Io
Maximum current
Co
A2
A2
Application case
with RS 232
Schematic
Safe area
Hazardous area
A2
RS-232
Tx / Rx
Intrinsically Safe GND
Field Device
Tx / Rx
9002/22-240-160-001
GND
Interface
Module
A2
06624E01
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/13
47
Series 9002/13
Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for
channel 2
Nominal current limited to 40 mA at 250
load
Connection to unregulated power supply on
UN to channel 1
Installation permitted in Division 2 and Zone 2
Safe area
+ve
+ve
Intrinsically safe
field device(s)
Control room
equipment
UN
+ve
+ve
0V
/ PA
05439E01
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
1
2
1+2
*)
Io
Order number
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
20 - 35
22
--
216
---
243
---
86
---
-3.5
--
25.2
25.2
25.2
118
0
121
740
20
760
1.3
50
1.25
0.107
0.107
0.104
7.4
150
7.35
0.82
0.82
0.8
9002/13-252-121-041
*)
A2/14
UN
Nominal voltage
Rmin
Uo
Maximum voltage
Rmax
Io
Maximum current
Imax
Po
Maximum power
Safety barriers
Co
2013-05-24AK00IIIen
48
A2
Application case
Analog output (current source) for I/P converter etc., field circuit unearthed
Schematic
Hazardous area
A2
Safe area
+20 ... 35 V DC
4 ... 20 mA
9002/13-252-121-041
A2
09953E01
A2
Operating data
Operating voltage
UN = + 20 ... 35 V
Operating current
IN = 0 ... 22 mA
Umax ( 8.9 V
A2
Safety data
Maximum voltage
Uo = 25.2 V
Maximum current
Io = 121 mA
Maximum permissible
external inductance
Lo
IIC
1.25 mH
IIB
7.35 mH
Maximum permissible
external capacity
Co
IIC
0.104 F
IIB
0.8 F
Maximum power
Po = 763 mW
A2
A2
Analog output (current source) for I/P converter etc., field circuit unearthed
Schematic
Safe area
Hazardous area
A2
+20 ... 35 V DC
9002/13-252-121-041
A2
06604E01
Operating data
Operating voltage
UN = + 20 ... 35 V
UL)
Operating current
IN = UL / 243 + RL
UN ( 24 V
UN - 3.5 V
A2
UN > 24 V
21 V
Safety data
A2
Maximum voltage
Uo = 25.2 V
Maximum current
Io = 121 mA
Maximum permissible
external inductance
Lo
IIC
1.25 mH
IIB
7.35 mH
Maximum permissible
external capacity
Co
IIC
0.104 F
IIB
0.8 F
Maximum power
Po = 760 mW
Application note
This safety barrier is used if the automation system activates the analog output signal in the return
(negative) line. The field device and automation system are not earthed and unregulated power supply
can be used.
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/15
49
Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Connection to regulated power supply UN
Installation permitted in Division 2 and Zone 2
Safe area
+ve
+ve
Intrinsically safe
field device(s)
Control room
equipment
UN
+ve
+ve
0V
/ PA
05826E01
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
Io
Order number
Po
IIC
IIB
Lo
Co
mA
mA
mW
mH
mF
mH
mF
1
2
1+2
16
16
--
95
---
108
---
148
---
-2
--
19.9
19.9
19.9
222
3
225
1100
15
1120
0.39
1000
0.37
0.223
0.223
0.213
3.18
1000
3.15
1.42
1.42
1.38
9002/13-199-225-001
1
2
1+2
24
24
--
321
---
358
---
67
---
-2
--
28
28
28
90
3
93
630
21
651
2.2
50
2
0.083
0.083
0.08
14
150
13
0.65
0.65
0.636
9002/13-280-093-001
1
2
1+2
24
24
--
269
---
290
---
82
---
-2
--
28
28
28
107
3
110
749
21
770
1.35
50
1.25
0.083
0.083
0.08
9.6
150
9
0.65
0.65
0.635
9002/13-280-110-001
*)
Lo
Co
*)
A2/16
UN
Nominal voltage
Rmin
Uo
Maximum voltage
Rmax
Io
Maximum current
Imax
Po
Maximum power
Safety barriers
Co
2013-05-24AK00IIIen
50
A2
Application case
Load cell (DMS) 350 or 700
6 conductors + 16 V, field circuit unearthed
Schematic
Hazardous area
A2
Safe area
+16 V
9002/13-199-225-001
A2
0V
9002/11-199-030-001
9002/11-199-030-001
A2
09963E01
Operating data
Operating voltage
Voltage for load cell and electric
line
Current for load cell
UN ( + 16 V
UL (at UN = + 16 V)
A2
IL (at UN = + 16 V)
Number of the load cells
connected in parallel
1
2
3
4
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note
350
UL (V)
10.4
8.3
6.9
5.9
ImA (V)
30
47
60
67
700
UL (V)
12.1
10.4
9.5
8.3
ImA (V)
17
30
41
47
A2
Uo = 19.9 V
Io = 285 mA
A2
IIC
0.2 mH
IIC
0.223 F
Lo
IIB
1.8 mH
IIB
1.42 F
Co
Po = 1.42 W
For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating data remains
unchanged. The safety-relevant maximum current is reduced to Io = 255 mA, the maximum power to Po = 1.3 W.
Discrete 2-wire output for solenoid valves, LEDs and signalling devices
Schematic
Hazardous area
A2
Safe area
A2
+24 V DC
9002/13-280-110-001
A2
06605E01
Application note
This barrier is suitable for use with regulated power supplies and earthed return circuits. The nominal voltage is 24 V.
2-wire 4/20 mA I/P converters and control valves - standard and HART, 4/20 mA indicators
Schematic
Hazardous area
4 ... 20 mA
Safe area
+24 V DC
9002/13-280-110-001
A2
11334E01
Application note
A2
This safety barrier is used if the automation system activates the analog output signal in the return (negative) line.
The field device and automation system are not earthed and a regulated power supply must be used. At an operating
current of 0 ... 22 mA, the maximum voltage drop across the barrier will be 8.4 V.
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/17
51
Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Connection to unregulated power supply on
UN to channel 1
Nominal current limited to 35 mA
Installation permitted in Division 2 and Zone 2
Safe area
+ve
+ve
Intrinsically safe
field device(s)
Control room
equipment
UN
+ve
+ve
0V
/ PA
05827E01
Selection table
Channel
UN
Rmin
Rmax
Imax
Safety data
Uo
1
2
1+2
*)
Io
Order number
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mW
mH
mF
mH
mF
20 - 35
26
--
292
---
327
---
52
---
-3.5
--
28
28
28
97
0
100
679
21
700
1.8
50
1.55
0.083
0.083
0.08
12
150
11
0.65
0.65
0.635
9002/13-280-100-041
*)
Nominal voltage
Rmin
Uo
Maximum voltage
Rmax
Io
Maximum current
Imax
Po
Maximum power
Co
Application case
3-wire PNP inputs (positive switching) of proximity switches, photocells and encoders
Schematic
Hazardous area
Safe area
Supply
+20 ... 35 V DC
9002/13-280-100-041
V
+0 V
PNP
06595E01
A2/18
Safety barriers
2013-05-24AK00IIIen
52
A2
Series 9002/33
+ve
Intrinsically safe
field device(s)
Safe area
Hazardous area
+ve
Control room
equipment
UN
A2
+ve
+ve
A2
0V
/ PA
05829E01
A2
Selection table
Channel
UN
Imax
Safety data
Uo
1
2
1+2
*)
Io
Order number
IIC
IIB
Lo
Co
Lo
Co
mA
mA
mH
mF
mH
mF
25.5
25.5
--
60
60
--
3.5 *)
3.5 *)
--
28
28
28
0
0
0
1000
1000
1000
0.083
0.083
0.083
1000
1000
1000
0.65
0.65
0.65
A2
9002/33-280-000-001
A2
2.5 V to 20 mA
Nominal voltage
Uo
Maximum voltage
Imax
Io
Maximum current
Co
A2
A2
A2
A2
A2
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/19
53
Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: Series 9002/34
Series 9002/34
Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: Hazardous area
+ve
Intrinsically safe
field device(s)
Safe area
+ve
UN
RL
Control room
equipment
-ve
-ve
0V
/ PA
05828E01
Selection table
Channel
UN
Imax
Safety data
Uo
1
2
1+2
*)
mA
+ 16
-5
21
100
100
--
3.5
3.5
--
*)
*)
Io
Order number
IIC
IIB
Lo
Co
Lo
Co
mA
mH
mF
mH
mF
28
8
28
0
0
0
1000
1000
1000
0.22
8.4
0.083
1000
1000
1000
1.14
100
0.65
9002/34-280-000-001
2.5 V to 20 mA
Nominal voltage
Uo
Maximum voltage
Imax
Io
Maximum current
Co
Application case
Vibration sensor
Schematic
Safe area
Hazardous area
4 ... 20 mA
9002/34-280-000-001
09951E011
Operating data
Operating current
IN = 0 ... 22 mA
Load
RL (750
Umax ( 3.5 V
Safety data
A2/20
Maximum voltage
Uo = 28 V
Maximum current
Io = 0 mA
Maximum permissible
external inductance
Maximum permissible
external capacity
Co
Maximum power
Po = 0 mW
Application note
Safety barriers
IIC
0.083 F
IIB
0.65 F
2013-05-24AK00IIIen
54
A2
Series 9002/77
Safe area
+ve/-ve
+ve/-ve
Intrinsically safe
field device(s)
UN
+ve/-ve
A2
Control room
equipment
+ve/-ve
A2
0V
/ PA
05836E01
A2
Selection table
Channel
UN
Rmin
Rmax
Safety data
Uo
1
2
1+2
1
2
1+2
1
2
1+2
1
2
1+2
1
2
1+2
1
2
1+2
1
2
1+2
*)
Order number
Io
Po
IIC
IIB
Lo
Co
Lo
Co
mA
mW
mH
mF
mH
mF
545
545
--
9.3
9.3
9.3
20
20
40
50
50
90
90
90
23
4.1
4.1
4.1
330
330
87
31
31
31
9002/77-093-040-001
492
492
--
82.1
82.1
--
9.3
9.3
9.3
150
150
300
350
350
700
1.3
1.3
0.2
4.1
4.1
4.1
7
7
1.8
31
31
31
9002/77-093-300-001
71
71
--
69.2
69.2
--
10
10
10
200
200
400
500
500
1000
0.5
0.5
0.15
3
3
3
4
4
0.8
20.2
20.2
20.2
9002/77-100-400-001
60
60
--
126
126
--
15
15
15
150
150
300
560
560
1130
1.3
1.3
0.2
0.58
0.58
0.58
7
7
1.8
3.55
3.55
3.55
9002/77-150-300-001
12
111
111
--
358
358
--
22
22
22
73
73
146
400
400
800
7
7
1.4
0.165
0.165
0.165
26
26
7.4
1.14
1.14
1.14
9002/77-220-146-001
*)
18
321
321
--
180
180
--
22
22
22
148
148
296
810
810
1630
1.35
1.35
0.24
0.165
0.165
0.165
7.2
7.2
1.84
1.14
1.14
1.14
9002/77-220-296-001
18
159
159
--
*)
730
730
--
28
28
28
47
47
94
330
330
660
10.1
10.1
1.96
0.083
0.083
0.083
30
30
12.5
0.65
0.65
0.65
9002/77-280-094-001
24
657
657
--
A2
A2
A2
A2
A2
A2
Nominal voltage
Uo
Maximum voltage
Lo
Rmin
Io
Maximum current
Co
Rmax
Po
Maximum power
A2
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/21
55
Application case
Load cell (DMS) 350 or 700
6 conductors +/- 7.5 V (15 V), field circuit unearthed
Schematic
Hazardous area
Safe area
+7,5 V
9002/10-187-270-001
-7,5 V
9002/10-187-020-001
9002/77-093-040-001
09962E01
Operating data
Operating voltage
Voltage for load cell and
electric line
Current for load cell
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note
Vibration sensor
Schematic
350
UL (V)
ImA (V)
UL (V)
ImA (V)
11.6
35
13.2
19
9.6
55
11.6
35
70
10.6
45
80
9.6
55
Uo = 18.7 V
Io = 330 mA
Lo
IIC
0.18 mH
IIC
0.27 F
700
IIB
1.45 mH
IIB
1.64 F
Co
Po = 1.42 W
For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 310 mA, the
maximum power to Po = 1.36 W.
Hazardous area
Safe area
Voltage
Input
9002/77-093-300-001
09958E01
Operating data
Maximum series resistance
of the safety barrier
Sensor voltage
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
A2/22
Safety barriers
Rmax = 2 x 82.1
U ( +/- 4 Veff / 6 Vpp
Uo = 9.3 V
Io = 300 mA
Lo
Co
IIC
0.2 mH
IIC
4.1 F
IIB
1.8 mH
IIB
31 F
2013-05-24AK00IIIen
56
A2
Series 9002
Figure
Description
Art. no.
Weight
158964
0.008
158977
0.002
158973
0.005
158826
0.006
165283
0.004
103714
1.410
112760
0.012
kg
Back-up fuse
09919E00
Label carrier
09920E00
Labelling sheet
A2
A2
09921E00
Adapter
A2
09922E00
Clamping base,
moulded material
09924E00
DIN rail
03856E00
Protective conductor
terminal
A2
A2
09926E00
Earthing terminal
A2
112599
0.030
A2
09926E00
Fuse holder
158834
0.020
158828
0.023
09927E00
Insulation and
fastening material
A2
09928E00
A2
A2
A2
A2
A2
2013-05-24AK00IIIen
Safety barriers
A2/23
57
12 mm / 0.47 "
72 mm / 2.83 "
09929E00
76 mm / 3.00 "
95 mm / 3.74 "
80 mm / 3.15 "
09930E00
66 mm
2.60 "
66 mm
2.60 "
38 mm
1.50 "
09933E00
38 mm
1.50 "
09932E00
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice.
The illustrations cannot be considered binding.
A2/24
Safety barriers
2013-05-24AK00IIIen
58
/E
Added