Professional Documents
Culture Documents
-*--
"
---a-
"
--------
BYWILLIAM
J. COAD
-.
z
"-
HeatingIPipinglAir Conditioning
October 1982
n e e d e d , t h e changeover p o i n t
would normally be closer to 50 F
HeatinglPipingIAir Conditioning
October 1982
the connected system on economizer cycle operation. This solution has created additional probThe fixed parasitic plant burdens, such as chilled water pumps,
condenser water pumps, and cooling tower fans, make the specific
power ( K W per ton) quite high.
The chillers cannot be operated a t the extremely low loads imSince performance, in this case,
is the paramount problem, the latter problem has been solved in a
number of ways. I t is not uncommon to see a modification to a large
chiller consisting of a hot gas bypass system to allow it to serve
these low loads. In such cases, the
energy consumed by the chiller
generally exceeds that required for
the load by several hundred per-
HeatinglPipingIAir Conditioning
October 1982