You are on page 1of 6

Bulletin 5715-477

Installation Manual
Series EQ104

Power Amplifier for


Hydraulic Pump PV

Parker Hannifin GmbH


Hydraulic Controls Division
Gutenbergstr. 38
41564 Kaarst, Germany
Tel.:
(+) 2131-513-0
Fax:
(+) 2131-513-230
www.parker.com
Copyright 2000, Parker Hannifin GmbH

Contents

Power Amplifier for Hydraulic Pump PV


Series EQ104

Installation Manual

Note
This document and other information from Parker Hannifin GmbH, its
subsidiaries, sales offices and authorized distributors provide product or
system options for further investigation by users having technical
expertise. Before you select or use any product or system it is important
that you analyse all aspects of your application and review the information
concerning the product or system in the current product catalogue. Due
to the variety of operating conditions and applications for these products
or systems, the user, through his own analysis and testing, is solely
responsible for making the final selection of the products and systems
and assuring that all performance and safety requirements of the
application are met. The products are subject to change by Parker
Hannifin GmbH at any time without notice.

IA EQ104 UK.PM6.5 RH 03.08.00

Home

Parker Hannifin GmbH


Hydraulic Controls Division

Power Amplifier for Hydraulic Pump PV


Series EQ104

Installation Manual
An electronic module for controlling a proportional
pressure relief valve on the pressure regulator of
axial pumps, whose slew chamber position is
given by a transducer. By this means, a set value
can be used to preselect a volume flow and control
it by means of a closed loop control circuit in the
module.
Technical Features

Processing and amplification of the externally


supplied positive set values into appropriate
output signals for controlling slew-angle.
DIP-switch from internal ramp generation to
external ramp setting.
Can be combined with EZ150 or external progammable controller.
Closed loop control with feedback from the
slew-angle transducer.
Pulsed low loss amplifier power stage with
supporting constant current control for constant temperature independent solenoid force.
Dither generator with applied frequency to improve static characteristics.

Diagnosis by means of diagnostic sockets as


well as LEDs for indicating working conditions.

Technical Data
Power supply
Power required
Set value voltage
Ramp disable voltage
Reference output
Solenoid output current max.
Ramp times
Ambient temperature
Connection
Shielded cable connections
Fuse

[V]
[VA]
[V]
[V]
[V]
[A]
[sec.]
[C]

[A]

filtered: 22...38, unfiltered: 18...26


max. 40
0...+10
5...30
+10, max. 10mA
1.3
0...5
0...+70
31pole male connector, DIN 41617
Supply connections and valve: AWG16; Commands: AWG20
2, medium lag, DIN 41571

Ordering Code

104

EQ
Electronic Module
Axial Piston Pump
Code

Pump Size

01
02
03
04
05
06

PV 016 / 020 / 023


PV 032 / 040 / 046
PV 063 / 080 / 092
PV 130 / 180
PV 250
PV 500

Pump
Size

Module
Type

Design
Series
Code

Module Type

104

Amplifier, adjustable
Min/Max-limiters,
Up/Down ramps

IA EQ104 UK.PM6.5 RH 03.08.00

Home

Parker Hannifin GmbH


Hydraulic Controls Division

Power Amplifier for Hydraulic Pump PV


Series EQ104

Installation Manual
EMC
EN 50081-2
EN 50082-2

EN 55011
ENV 50140

EN 61000-4-4

ENV 50204

EN 61000-4-5

EN 61000-4-2

EN 61000-4-6

Block Diagram

Connector (Elevation B)

14
16
18

Input command voltage 0...+10 VDC


Output +10V reference
Input 24VDC supply

22
24
26

Input external option


Output to control solenoid
Output to control solenoid

9
11
13

Reference potential 0V to transducer


Reference potential 0V supply
Input ramp disable

19

Input transducer signal

23
27

Output transducer supply


Input external ramp option

31

Reference potential 0V set value

IA EQ104 UK.PM6.5 RH 03.08.00

Home

Parker Hannifin GmbH


Hydraulic Controls Division

Power Amplifier for Hydraulic Pump PV


Series EQ104

Installation Manual
Operating and Diagnostic Elements
(Elevation A)
Notes
Turn off the electrical power
to this board whenever the
hydraulic supply to the valve
is not on.

1 MIN-limiting for matching the smalest


slew-position angle
2 MAX-limiting for matching the largest
slew-position angle
3 Not used
4 Red socket for slew chamber position
diagnostic
5 Black socket for slew chamber position
diagnostic (0V potential)
6 Red LED (A) for
function indicator control solenoid
(B unused here)
7 Yellow LED for:
correct voltage supply
correct transducer connection
8 Grey grip strip with reference information for measured values
9 UP ramp potentiometer
10 Down ramp potentiometer

Always turn off the power to


this board before removing
it from the card holder.

Dimensions

IA EQ104 UK.PM6.5 RH 03.08.00

Home

Parker Hannifin GmbH


Hydraulic Controls Division

Power Amplifier for Hydraulic Pump PV


Series EQ104

Installation Manual

INSTALLATION GUIDE TO ELECTRONIC MODULES


TO PROVISION OF ELECTROMAGNETIC COMPATIBILITY.
Power Supply
The utilized power supply has to comply with the EMC-standards (CE-sign, certificate of conformity).
Parker is offering the following power supplies:
EX00-N01
EX00-N04
EX00-N08

( 2.5 Amp.)
( 5.0 Amp.)
(10.0 Amp.)

Relais and solenoids operating from the same supply circuit than the valve electronics has to be fitted
by surge protection elements.
Wiring Cable
The wires between the installation site of the module and the peripheral units, as power supply, valve
solenoids, position transducer, command signal source has to be shielded. The following wire sizes
must be reached: power supply AWG 16, other connections AWG 20. The capacity should not exceed
a value of approx. 130 pF/m (wire/wire). The maximum cable length is 50m. No power current lines may
be placed within the wired shielded cables to the electronic module. The cable shield has to be
connected to earth ground at both ends (see also chapter Grounding). Please be aware of ground
loops.
Connectors
The connection of the position transducer needs a sensor connector 4pin+E featuring metal case and
integrated cable shield coupling. Parker can provide suitable connectors:
5004108

(Connector 4pin+E)

The connectors has to be installed according the connection diagram, the cable shield has to be tied
on the whole periphery to the provided coupling clamp.
Installation
The module has to be mounted within a conductive, shielded enclosure. Usable is i.e. an EMC-approved
control cabinet. A perfect grounding of the enclosure is mandatory (see also chapter "Grounding")
Grounding
The mounting plate of the valve has to be connected to the grounded metal machine frame. The cable
shields must be tied to ground at the control cabinet. A low-ohmic potential compensation wire has to
be provided between the control cabinet and the machine frame (cable wire >AWG 7 cross section) to
prevent ground loops.