You are on page 1of 16

 !

"#$%&" '()*+
q_b^=p~=i=q~~=`~=`KIi

^~=o~  !



!"#

All Aluminum Conductor and Aluminum Conductor Steel-Reinforced



 !"#$%&" '()*+,-./0123&"456
 !"#$%$&'()*+,
 !"#$% !"#$%&'()*+)",-%&./0123-4567/89 !"#$
NRMMs  ! !"#$% !"#$ QMM  !"OMMMM  !"#$%&'()
  NNMs  !"#$%&'( ! !"# !"#$%&OOMs  !"#$
 !"#$%&'() !"#$%RMMs  !"#$%&'()*+,-.TRMsJNMMMs 
 !"#$"%&'()*+,-./012345678
 !"#$%&'()*+,-./0
 !"#$ !"#$%& !"#$%&'("#)*+,- !"#$% !"
  !  !"  !"  !"#$%&'()*NNMsOOMs 
 OMMM  !"#$%& OMMQ  !"#$%&'(

TBEA Shandong Luneng Taishan Cable Co., Ltd., which locates at the foot of famous mountain Mount
Tai, is one of the biggest wire and cable companies in China. She owns the right to Import and Export
directly. There is a national class center and the biggest XLPE cable test hall among cable companies.
The company has the ability to produce and test four sorts of cables including bare conductors, 1~500kV
power cables, wires and cables electrical equipment and special cables, totally over 400 types and 20,
000 specifications. Among them, 110kV cable is the first to be certified by Two Ministry and it is
advanced in China. 220kV XLPE cable is the first to be used in national power grid and has world-class
level. The company is the first one to produce 500kV cable in China. The 750kV~1000kV diameter
extension conductor and generatrix is the highest voltage wire in China, and we are the first one to
make it and put it into use. It has reached high level in the world. Our products have been used in
BeiJing Tianan Men lighting line reconstruction, Beijing International Airport, Shanghai Pudong International Airport. Three Gorges hydraulic engineering project and other important projects. The products
have been exported to more than twenty countries and areas including Singapore, Australian, UAE,
Philippines, Republic of Yemen, Venezuela, Peru, Parkistan, Mongolia, and Hongkong. 110kV and 220kV
cross-linked power cable have been ever used in Sydney Olympic Games in 2000 and Beijing Olympic
Games Gymnasium Center in 2004.

Brief Introduction
of Company

 !"#$%&'()
*+,-.
/-%0
 !"#$%
&'%
()%
*%
+,-./01
 !"#
$%&'()*+,-./
0123,
 !"#$%&'()*+,-./0123
 !"#$%
 &'()!"OP !"#
P !"#$%OM



Advanced
Equipments

This company has solid power for scientific research. It has a team
of doctorate and postgraduate students for scientific research,
design, craft, production and after-sale service. Experts from Shanghai Electric Cable Research Institute, Wuhan High Voltage Cable
Research Institute, and Xian Jiaotong University were invited to
our company as our technical advisors. We hold 23 patent rights, 3
invention patents and 20 utilities and new-type patents.

 !"#$%&' #()*+,+-.
!"#$NRMMEF
 !"#$%&'
!"OOMs
RMMs !"#$%&'()
`bb`l !"#$%&
'(phbq !
!"
#$qolbpqbo !"#$%&'()
 !"#$%&'()*+,-./01
 !"#$%&'(
)*+,-./012!
 !"#$%






 !"#$%&'()*+,-./0
 !TRMs !"#$%&'()*(+
TRMs !"
#!RMMs !"#$%&
 !"# $%&'()*+,-./0
 !"#$%&
'()*$&
+,-./01
 !"#$%&' ()*+,- ./0
 !"#$%&'(
)*+,-./01$%
 !"#$%&

 !"750kV !"#$%I !"#$


 !"#$%&'
The first 750kV test hall with entire shield in China.
The main test equipment was imported from Haefely
Corporation, Swiss.

!"

Scientific
research
and Talents

The company has 1,500 sets of manufacturing and testing


equipments, which are advanced home and abroad. Among
them, the 220kV and 500kV VCV line were imported from Nokia
Co., Finland; Frame stranding machine came from CEECO Co.,
Canada; Reel stranding machine from SKET Co., Germany; and
Double sheath extruded machine from TROESTER Co.,
Germany.
The equipments in our company are at the top level in this area
in China. Solid foundation has been set up for researching high
voltage power cable and improving qualitiy of products stably.

The company has 750kV test hall with entire shield, which is the
highest voltage class. Complete test items for high voltage cable
can be done here. Test equipment include 750kV test facility for
partial discharge, high voltage SCHERING bridge, measuring
instrument of dielectric resistance, spectrum analyzer, Online
instrumentation of pore and impurity, non-rotor vulcanization
meter for rubber, speed meter of melt flow, projecting apparatus
of low times, and test equipment for heating cycle.

 !"#$%&
Online instrumentation of Pore and impurity



 !
Test ability

MELCHERS-FERROSTALL !"#  !"


 !"#$%&'(
Spectrum analyzer
Advanced torque rheometer in the world from
MELCHERS-FERROSTALL Corporation,
Germany



Market
application

 !"#$%&'()
'*)
+
 !
"!
#$%&'()*+,
 !"#$%&'()*+,-.
/
 !"#
$%&' !"#
()*
 !"#$% &'()*
+,
 !"#
$%&'#
()*#
+,-#
 !"#$ %& '()* +,  !"#$%&'()
NNMs
OOMs
 !"OMMM !"#$%&
OMMQ !"#$%&'(

ZR-YJLW02 64/110kV 1x800mm2 !"


 !"#$%
64/110kV 1x800mm2 XLPE power cable for
Beijing Tianan men line reconstruction.

YJLW02 110kV 1x1000mm2  !"#$%&'(


 !"#
110kV 1x1000mm 2 XLPE power cable for Sydney
Olympic Stadium.

 !"#$%&'()*+,-.
 !"#$%&'()*+!"#$%,
 !"#$%&'( )*+!",-.
^^^ !"#$%&'() !#*
 !"#$%&'()!"*+,-./
 !"#$
OMMQP !lep^pNUMMM !"
 !"#$%&'()*+
,-+./01
 !"#$%&'()*+",
OMMQVN!"#
$%&'()*+
 !"#$%&'()*+
OMMRPNR!"#
$%&%'()
 !"#$%&'()*+,
OMMRNO!"#
$%&'()*+,
 !"#$

02

Our products have been widely used for national economy development and
construction, such as electric power, telecommunication, railways, machinery and
electric, nuclear power and construction work etc. Our products have been used
in Beijing Tianan men lighting line reconstruction, Beijing International Airport,
Shanghai Pudong International Airport, Three Gorge hydraulic engineering Project,
and other important projects. Our products have been exported to more than 20
countries and areas including Singapore, Australia, UAE, Philippines, Republic
of Yemen, Venezuela, Peru, Pakistan, Mongolia, and Hong Kong. 110kV and
220kV cross-linked power cable have been ever used in Sydney Olympic Games
in 2000 and Beijing Olympic Games Center in 2004.

YJLW03 127/220kV 1x1000mm2  !"#


 !"#$%&'220kV !
127/220kV 1x1000mm 2 XLPE power cable
used in 220kV Zhang-er Transmission line in
Shanghai Cable Transmission and Distribution
Corporation.

The company was awarded as a Quality trustworthy enterprise


of China Machinery industry, the advanced enterprise of national
quality management, the advanced national Quality-Efficiency
Enterprise in machinery industry, China quality and service credit
AAA Rating Enterprise, the advanced national customer satisfying Enterprise, etc. The company also has the rights of import
and export.
In March, 2004, the company passed through OHSAS 18000
certificate of occupational health and safety management. And
realized Total Integrated of Management System.
On Sept. 1, 2004, Taishan brand cross-linked cables were
awarded as China famous products in China wire&cable industry.
On Mar. 15, 2005, Taishan brand cross-linked cables were
awarded as No. 1 brand of customer Satisfactory products of
China wire&cable industry.
In December, 2005, Taishan brand cross-linked cables were
awarded as national certificate for product exemption from quality surveillance inspection.

YJLW03 76/132kV 1x500mm2  !"#$


 !"#$%&
76/132kV 1x500mm2 XLPE power cable used
in Bangladesh parliament building project.



Qualification
and honour



!"#

All Aluminum Conductor and Aluminum Conductor Steel-Reinforced


 !"#$%&'()*
The product is suitable for aerial power line.


=

!=Product standards

 !"#$%&"GB1179-83 !"#$% !"&


'
 !"#$%&'()*GB1179-83 !"#$%&'
()*+
GB/T1179-1999 !"#ASTM B231ASTM B232BS215
DIN48201
IEC61089 !"#$%&'



As domestic users are accustomed to purchasing AAC or ACSR according to GB1179-83, the type, structure and performance of this
product will be in according with the above standard. According to
customers demand, we can produce according to GB/T1179-1999,
and can also produce according to abroad standard such as ASTM
B231, ASTM B232, BS215, DIN48201 and IEC61089.

!"#$%&=Type & Specification

N !"#$ N
Refer to table 1 about the type of cable

=N==Table 1
=Name

=Type
LJ

 =AAC

LGJ

 !"=ACSR

LGJF

 !"#$=Anti-corrosion ACSR

LGJX

 !"#$=ACSR with lanthanon in steel core

LGJXX

 !"#$%&'()=High anti-corrosion ACSR with double lanthanon

O !"#$%&'()* O P  !


Specifications and performance meet the requirements in Table 2, Table 3.
LJ =LJ type

=O==Table 2

E L

20C  !  !"
 !
Calculated
Nominal Cross- =Construc- Outer Dia.mm  D.C .
Resistance at
Breaking Load
sectional Area tion (No./Dia)
20C
mm
(no more than)
N
mm2
/ km

 !
Calculated
Weight
kg/km

 !
E F
Delivery Length
(no less than)
m

 !"
Continuous Carrying Capacity A
70C

80C

90C

16

7/1.70

5.10

1.802

2840

44

4000

84

100

111

25

7/2.15

6.45

1.127

4355

70

3000

112

133

147

35

7/2.50

7.50

0.8332

5760

94

2000

135

161

180

50

7/3.00

9.00

0.5786

7930

136

1500

168

202

227

70

7/3.60

10.80

0.4018

10950

195

1250

210

253

284

95

7/4.16

12.48

0.3009

14450

261

1000

250

304

338

120

19/2.85

14.25

0.2373

19420

334

1500

289

353

390

150

19/3.15

15.75

0.1943

23310

407

1250

327

400

454

185

19/3.50

17.50

0.1574

28440

503

1000

371

456

518

210

19/3.75

18.75

0.1371

32260

577

1000

403

497

575

240

19/4.00

20.00

0.1205

36260

657

1000

435

538

610

300

37/3.20

22.40

0.09689

46850

820

1000

496

617

707

400

37/3.70

25.90

0.07247

61150

1097

1000

588

738

851

500

37/4.16

29.12

0.05733

76370

1387

1000

674

852

982

630

61/3.63

32.67

0.04577

91940

1744

800

768

977

1140

800

61/4.10

36.90

0.03588

115900

2225

800

880

1129

1340

03

LGJ (LGJX LGJXX LGJF) =LGJ (LGJX LGJXX LGJF) type


E L F
 !
Construction (No./Dia) mm
L
Nominal Crosssectional Area
=Al.
=St.
(Al. St.) mm2

04


Outer Dia.
mm

=P==Table 3

20C  !  !"
 D.C .
Calculated
Resistance at
Breaking
20C
Load
(no more than)
N
/ km

 !
Calculated
Weight
kg/km

 !
E F
Delivery
Length (no
less than)
m

43

3000

 !"
Continuous Carrying Capacity A
70C

80C

90C

66

78

87

10/2

6/1.50

1/1.50

4.50

2.706

4120

16/3

6/1.85

1/1.85

5.55

1.779

6130

65

3000

85

100

113

25/4

6/2.32

1/2.32

6.96

1.131

9290

103

3000

111

131

149

35/6

6/2.72

1/2.72

8.16

0.8230

12630

141

3000

134

158

180

50/8

6/3.20

1/3.20

9.60

0.5946

16870

195

2000

161

191

218

50/30

12/2.32

7/2.32

11.60

0.5692

42620

372

3000

166

195

218

70/10

6/3.80

1/3.80

11.40

0.4217

23390

275

2000

194

232

266

70/40

12/2.72

7/2.72

13.60

0.4141

58300

511

2000

196

230

257

95/15

26/2.15

7/1.67

13.61

0.3058

35000

381

2000

252

306

351

95/20

7/4.16

7/1.85

13.87

0.3019

37200

409

2000

253

277

319

95/55

12/3.20

7/3.20

16.00

0.2992

78110

708

2000

250

270

301

120/7

18/2.90

1/2.90

14.50

0.2422

27570

379

2000

287

350

401

120/20

26/2.38

7/1.85

15.07

0.2496

41000

467

2000

285

348

399

120/25

7/4.72

7/2.10

15.74

0.2345

47880

527

2000

265

315

365

120/70

12/3.60

7/3.60

18.00

0.2364

98370

896

2000

258

301

335

150/8

18/3.20

1/3.20

16.00

0.1989

32860

461

2000

323

395

454

150/20

24/2.78

7/1.85

16.67

0.1980

46630

549

2000

326

400

461

150/25

26/2.70

7/2.10

17.10

0.1939

54110

601

2000

331

407

469

150/35

30/2.50

7/2.50

17.50

0.1962

65020

676

2000

331

407

469

185/10

18/3.60

1/3.60

18.00

0.1572

40880

584

2000

372

458

528

185/25

24/3.15

7/2.10

16.67

0.1542

59420

706

2000

379

468

540

185/30

26/2.98

7/2.32

18.88

0.1592

64320

733

2000

373

460

531

185/45

30/2.80

7/2.80

19.60

0.1564

80190

848

2000

379

469

541

210/10

18/3.80

1/3.80

19.00

0.1411

45140

651

2000

397

490

565

210/25

24/3.33

7/2.22

19.98

0.1380

65990

789

2000

405

501

579

210/35

26/3.22

7/2.50

20.38

0.1363

74250

854

2000

409

507

586

210/50

30/2.98

7/2.98

20.86

0.1381

90830

961

2000

409

507

586

240/30

24/3.60

7/2.40

21.60

0.1181

75620

922.2

2000

445

552

639

240/40

26/3.42

7/2.66

21.66

0.1209

83370

964.3

2000

440

546

633

240/55

30/3.20

7/3.20

22.40

0.1198

102100

1108

2000

445

554

641

300/15

42/3.00

7/1.67

23.01

0.09724

68060

940

2000

495

615

711

300/20

45/2.93

7/1.95

23.43

0.09520

75680

1002

2000

502

624

722

300/25

48/2.85

7/2.22

23.76

0.09433

83410

1058

2000

505

628

726

300/40

24/3.99

7/2.66

23.94

0.09614

92220

1133

2000

503

628

728

300/50

26/3.83

7/2.98

24.26

0.09636

103400

1210

2000

504

629

730

300/70

30/3.60

7/3.60

25.20

0.09463

128000

1402

2000

512

641

745

400/20

42/3.51

7/1.95

26.91

0.07104

88850

1286

1500

595

746

864

400/25

45/3.33

7/2.22

26.64

0.07370

95940

1295

1500

584

730

845

400/35

48/3.22

7/2.50

26.82

0.07389

103900

1349

1500

583

729

844

 !
E L F
L
Construction (No./Dia) mm
Nominal Crosssectional Area
=Al.
=St.
(Al. St.) mm2


Outer Dia.
mm

20C  !  !"
 D.C .
Calculated
Resistance at
Breaking
20C
Load
(no more than)
N
/ km

 !
Calculated
Weight
kg/km

 !
E F
Delivery
Length (no
less than)
m

70C

80C

90C

 !"
Continuous Carrying Capacity A

400/50

54/3.07

7/3.07

27.63

0.07232

123400

1511

1500

592

741

857

400/65

26/4.42

7/3.44

28.00

0.07236

135200

1611

1500

597

752

876

400/95

30/4.16

19/2.50

29.14

0.07087

171300

1860

1500

608

767

895

500/35

45/3.75

7/2.50

30.00

0.05712

119500

1642

1500

670

842

977

500/45

48/3.60

7/2.80

30.00

0.05912

128100

1688

1500

664

834

967

500/65

54/3.44

7/3.44

30.96

0.05760

154000

1897

1500

676

850

983

630/45

45/4.20

7/2.80

33.60

0.04633

148700

2060

1200

763

964

1120

630/55

48/4.12

7/3.20

34.32

0.04514

164400

2209

1200

775

979

1136

630/80

54/3.87

19/2.32

34.82

0.04551

192900

2388

1200

774

977

1131

800/55

45/4.80

7/3.20

38.40

0.03547

191500

2690

1000

830

1040

1220

800/70

48/4.63

7/3.60

38.58

0.03574

207000

2791

1000

887

1126

1310

800/100

54/4.33

19/2.60

38.98

0.03635

241100

2991

1000

884

1121

1301

 LGJF !"#$%&'()*+,-./012"#34-+56
781/012-.78"#3.1%
 !"#$%&'(&)*+,-./05%
Note:The calculated weight of the LGJF, add the weight of anti-corrosion coating to the value specified in above table. 3.1% should be added for anti-corrosion
coating on steel core. 5% should be added for anti-corrosion coating on steel and aluminum layer.



!"#$%&=Main mechanical performance of conductor

N !"#$%&' Q
Refer to table 4 about the mechanical performance of round aluminum wire.
 !
Nominal Diameter
mm

=Q==Table 4

 !=
Min. Tensile Strength
=Before Stranding

=After Stranding

Mpa

kgf/mm2

Mpa

kgf/mm2

1.25

200

20.4

190

19.4

1.26 ~ 1.50

195

19.9

185

18.9

1.51 ~ 1.75

190

19.4

181

18.4

1.76 ~ 2.00

185

18.9

176

17.9

2.01 ~ 2.25

180

18.4

171

17.4

2.26 ~ 2.50

175

17.9

166

17.0

2.51 ~ 3.00

170

17.3

162

16.5

3.01 ~ 3.50

165

16.8

157

16.0

3.51 ~ 5.00

160

16.3

152

15.5

 !
Wrapping Test

20C 

Max. Resistivity at
20C
mm2/m

0.028264

 !60r/min ! !"


 !"#$%&'86
  !"#$ !"#$
Tightly wrap 8 coils at a speed of 60r/
min and above on the stick which
equal to its size, rewrap tightly after
unwrapping 6 coils, no broken.

O !"#$%&'()*+,-./0 R 
The mechanical performance of galvanized steel wire and the technical requirement of zinc coating. (see Table 5)
 !
Nominal
Diameter
mm

 1% 

Min. Stress
at 1%
N/mm2

 !=
Min. Tensile Strength Mpa


Before Stranding After Stranding

 !
E F
Min. Weight of
Zinc Coating
g/mm2

 %
Elongation
L=250mm

1.24 ~ 1.50

1170

1340

1273

185

3.0

1.51 ~ 1.75

1170

1340

1273

200

3.0

1.76 ~ 2.25

1170

1340

1273

215

3.0

2.26 ~ 2.75

1140

1310

1244

230

3.0

2.76 ~ 3.00

1140

1310

1244

230

3.5

3.01 ~ 3.50

1100

1290

1226

245

3.5

3.51 ~ 4.25

1100

1290

1226

260

4.0

4.26 ~ 4.75

1100

1290

1226

275

4.0

4.75 ~ 5.50

1100

1290

1226

290

4.0

 !
Wrapping Test

N  !"#
 U  !
Tightly wrap 8
coils on stick
with same diameter as the aluminum wire, no
crack.

=R==Table 5

 !"
Adhesion of Coating

 !"#$%&'( U I 
 !"# !"#$%&
 !"#$
d3.5= ! =4d
d>3.5  ! =5d
Tightly wrap 8 coils on the corresponding stick, the zinc layer
should not crack, or without peeled
loss when scraped by hand.
Of which:
d3.5, mandrel diameter = 4 d,
d>3.5, mandrel diameter d = 5

05



Hard Copper Stranded Conductor


=

!=Manufacturing standards

Q/09 TDL016-2007

=Uses
 !"#$%&'()*&+,-)./&012
The product is used for aerial power line and power system of electrical railway.



!"#$=Name and manufacturing range

 !
TJ
 !16 ~ 500mm2

Name: Hard Copper Stranded Conductor


Type: TJ
Manufacturing Range:16 ~ 500mm2

 !"#$%&' S
Main Performances of round copper single wire (see Table 6)
=S==Table 6
 ! Dia. Of Single Wire mm
 =Nominal Value

=Tolerance

 !
Cross-section of
Conductor
mm2

 !=Tensile Strength N/mm

20C  !"#
Conductor Resistivity
 !=Min. Value  !=Min. Value
at 20C
before Stranding
after Stranding
mm2/m
2

12.7

1.35

1.43

1.50

1.77

1.75

2.41

21.5

3.14

28.0

2.00

0.03

0.01796

15.3

35.4

2.25

3.98

2.50

4.91

2.70

5.94

52.9

7.07

62.9

8.30

73.8

3.00
3.25

0.04

422

392

 NK !"#$%&'()%*+,-./0 !()%1


OK !"#2.00mmI20C !"#$%0.01796mm2/m
Note:1.Other values between the adjacent diameter can be allowed and their tolerance is the same as the next bigger diameters.
2.Resistivity of the conductor at 20C shall be 0.01796mm2/m, if the nominal diameter is less than 2.00mm.

06


Weight
kg/km

0.01777

43.7

 !"#$ !"#$%&'( T


Specification, structure and technical data. (see Table 7)
=T==Table 7
 !
Nominal Crosssection
mm2

 Single Wire

 !
Overall Diameter
of the Stranded
Conductor mm

 !"
Calculated
Breaking Load
KN

20C  !"#
 !"
 !
Continuous
 Max D.C
Calculated Weight
Resistance at 20C Carrying Capacity
kg/km
A
/km

=No. of wires

=mm Dia.

10

1.35

4.1

4.02

1.8156

90

90

16

1.70

5.1

6.37

1.1450

125

143

25

2.10

6.3

9.72

0.7424

160

218

35

2.50

7.5

13.77

0.5238

200

310

50

3.00

9.0

19.84

0.3638

250

446

50

19

1.80

9.0

19.38

0.3781

250

437

70

19

2.10

10.5

26.38

0.2747

310

596

95

19

2.50

12.5

37.39

0.1939

380

845

120

19

2.80

14.0

46.90

0.1546

440

1060

127

19

2.92

14.6

51.00

0.1422

470

1163

150

37

2.25

15.8

58.98

0.1232

510

1337

185

37

2.50

17.5

72.81

0.09981

585

1649

240

61

2.25

20.3

97.23

0.07490

700

2209

300

61

2.50

22.5

120.04

0.06067

800

2725

400

61

2.89

26.0

160.42

0.04540

960

3640

500

61

3.23

29.1

200.38

0.03635

1110

4545

 NK !"#$%&8.9kg/dm3 !"#$%&'


OK !"#$%0.6m/s
 !"#35C !"#$%&'()*+,-.70C60Hz !"#$
%&'()!*+,-./ 0
12345 6
30%
Note:1. The weight of stranded conductor is calculated by the density of 8.9kg/dm3 and average lay ratio.
2. For the 60Hz and below line, we recommend operation conditions as follows. The wind speed is 0.6m/s, the ambient temperature with sunlight is 35C, and max
temperature of aerial transmission conductor is 70C. In the special situation of static air, the capacity shall decrease about 30% in averagely.

07



!"#$%&'

!"#$

Heat-resistant aluminum alloy conductor and heat-resistant aluminum alloy conductor steel-reinfored


!"#$%&'()

The product is suitable for aerial power lines

08

 !"#$%&'()*+,-
N !"#$%&'()
O !"#$%&'()*+,
P !"#$%&'(=
Q61T !"#$%

Heat-resistant aluminum alloy conductor includes four main products:


1.Ordinary heat-resistant aluminum alloy conductor;
2.High-strength heat-resistant aluminum alloy conductor with gap;
3.Super heat-resistant aluminum alloy conductor with low sag and high capacity;
4.61T heat-resistant aluminum alloy conductor.

 !"#$%&'()*+,
N
 !"#$150C
 !"#$%&'()70C
1.14 !"#$%&'()60%X
O !"#$%= 90%
P != 58%IACS
Q150C !"#90C !"

Technical characteristics of ordinary heat-resistant aluminum alloy conductor:


1.Long-term operation temperature is 150C, conductor 1.14 times highter than ordinary aluminum conductor. Carrying capacity is increased by 60% and above compared with the ordinary aluminum conductor;
2.Retention rate of tensile strength 90%;
3.Conductivity 58% IACS;
4.The creep of it at 150C is smaller than the hard aluminums at 90C.

 !"#$%&'()*+,-./
N
 !"#$150C
 !"#$%&'()70C
1.14 !"#$%&'()60%
O !"#$%= 90%
P != 60%IACS
Q150C !"#90C !"
R !"#$%&'()!*+ ,)-./
S !"#$%&$'()*+,-./0("#1
 !"#$%
T
 !"#$%&'(#)*+,-.
/01234

U !"#$%&'()*+,-./0120(
)
 !"#$%&'()*+,- ./01

Technical characteristics of the high strength heat-resistant aluminum alloy


conductor with gap:
1.Long-term operation temperature is 150C, conductor 1.14 times highter than ordinary aluminum conductor. Carrying capacity is increased by 60% and above compared with the ordinary aluminum conductor;
2.Retention rate of tensile strength 90%;
3.Conductivity 60% IACS;
4.The creep of it at 150C is smaller than the hard aluminums at 90C;
5.High strength steel wires are used for core, so the sag will be deereased;
6.The special heat-resistant ointment is filled into the gap between the conductor and
steel core.The steel core bears tensile strength separately;
7.Problems such as limited lines and insufficient head room can be solved by using
this kind of conductor;
8.When this kind of conductor is used for upgrading grid, cost for line reconstruction
can be reduced greatly. There is no need to increase the strength and height of the
tower, and there is no need to reconstruct the infrastructure.

 !"#$%&'()*+,
N
 !"#$210C
 !"#$%&'()70C
3 !"#$%&'()*+2X
O !"#$%= 90%
P != 60%IACS
Q210C !"#90C !"
R !"#$%!&'
( )*+,-'
./0-1
S !"#$%&'()*+,-./#0123
 !"#$%&'
T !"#$%&'()*+,-./0120(
)
 !"#$%&'()
*+,-./012345


Ultra- heat low slacken and times capacity wires technical features:
1.Long-term operation temperature is 210C, conductor 2 times highter than ordinary
aluminum conductor. Carrying capacity is increased by 60% and above compared
with the ordinary aluminum conductor;
2.Retention rate of tensile strength 90%;
3.Conductivity 60% IACS;
4.The creep of it at 210C is smaller than the hard aluminums at 90C;
5.Invar steel wires are used for steel core, so the linear expansion coefficient and sag
are all reduced;
6.Problems such as limited lines and insufficient head room can be solved by using
this kind of conductor;
7.When this kind of conductor is used for upgrading grid,cost for line reconstruction
can be reduced greatly. There is no need to increase the strength and height of the
tower, and there is no need to change hardware.

61T  !"#$
N
 !"#$150C
 !"#$%&'()70C1.14 !
 !"#$%60%X
O !"#$%= 90%
P != 61%IACS
Q150C !"#90C !"

61T heat-resistant aluminum alloy conductor:


1.Long-term operation temperature is 150C, conductor 1.14 times
highter than ordinary aluminum conductor. Carrying capacity is increased by 60% and above compared with the ordinary aluminum
conductor;
2.Retention rate of tensile strength 90%;
3.Conductivity 61% IACS;
4.The creep of it at 150C is smaller than the hard aluminums at 90C.

 !"#$%&'()*+,-./012
34/501%&
 !"#
$%&'()*#
+,-.&/0123
456789:
 !"#$
%&'()*+,-./0123.45'6"7
89
 !"#$%&'%&()*+,.&/0123'45678
 !"#$%&'()*+,'-./01!'-23456

Four kinds of heat-resistant aluminum alloy conductor's operation temperature has greatly enhanced ,which can greatly increase the transmission capacity of wire ,improve the utilization of aluminum, and save
relatively construction cost. In addition, they each have their own
unique: High strength heat-resistance aluminum alloy conductor usages is particularly suitable for large span, and for the super heatresistant aluminum alloy conductor with low sag and high capacity,
the sag is very small. The head room of the line can be saved and
investment for the line can be decrease by using this kind of product.


=

!"#=Manufacturing standards

 !"#$%&Q/09 TDL030-2007
The product is manufactured according to enterprise standary Q/09 TDL030-2007.

=Uses
 !"#$%&#$'()
Applicable to line expansion and reconstruction of the old line.

=Characteristics
N
O
P
Q

!"#$58%IACS20C !"#$0.029726mm2/mX
!230C 1h !"#$
%&'()*+,90%
!"#0.000023 1/C
!"#$0.0039 1/C



!=Type of products

N !"#$%
Heat-resistant aluminum alloy conductor
NR

LH

1.Relative conductance: 58%IACS (Max. resistivity at 20C: 0.


029726mm2/m).
2.After heating to 230C hold for 1h, and cooling to room temperature,
the tensile strength remained not less than 90%.
3.Linear expansion coefficient is 0.000023 1/C.
4.Temperature coefficient of resistance is 0.0039 1/C.

58 J

O !"#$%&'
Heat-resistant aluminum alloy conductor steel-reinforced
NR


Stranded conductor
 !" RUB
Relative conductance: 58%

Aluminum alloy

Heat-resistant

LH

58 GJ
 !
Stranded conductor
 !" RUB
Relative conductance: 58%

Aluminum alloy

Heat-resistant

P !"#$%&'()*NRLH58GJF
Anti-corrosion heat-resistant aluminum alloy stranded Conductor

09




!"#$= Specification

!"#$=NRLH58J Heat-resistant aluminum alloy conductor NRLH58J

E L
 !
Nominal Cross- =Construcsectional Area tion (No./Dia)
mm
mm2


Outer Dia.
mm

20C  !  !"
=D.C .Max, Calculated
Resistance at Breaking Load
20C
N
/ km

=U==Table 8

 !
Calculated
Weight
kg/km


 !
Delivery
Length
m

 !"
Calculated Carrying Capacity A
90C

110C

150C

35

7/2.50

7.50

0.8763

5125

94.2

2000

185

195

216

50

7/3.00

9.00

0.6085

7380

135.7

1500

227

272

340

70

7/3.60

10.80

0.4226

10289

195.4

1250

281

337

423

95

7/4.16

12.48

0.3165

13287

260.9

1000

341

411

517

120

19/2.85

14.25

0.2496

18079

334.0

1500

396

479

604

150

19/3.15

15.75

0.2043

21381

408.0

1250

456

552

699

185

19/3.50

17.50

0.1655

26396

503.7

1000

521

633

803

210

19/3.75

18.75

0.1442

30302

578.2

1000

564

687

873

240

19/4.00

20.00

0.1267

33343

657.9

1000

614

749

954

300

37/3.20

22.40

0.1019

42969

821.6

1000

707

865

1104

400

37/3.70

25.90

0.07622

57447

1098.5

1000

848

1042

1337

500

37/4.16

29.12

0.06030

70230

1388.6

1000

975

1202

1549

630

61/3.63

32.67

0.04803

86362

1746.8

800

1121

1389

1799

800

61/4.10

36.90

0.03765

106549

2228.4

800

1289

1605

2092

 !"#$%&=NRLH58GJ(NRLH58GJF)
Heat-resistant aluminum alloy conductor steel-reinforced NRLH58GJ (NRLH58GJF)
E L F
 !
Construction (No./Dia) mm
L
Nominal Crosssectional Area
=Al.
=St.
(Al. St.) mm2

10


20C  !  !"
Outer Dia.  =D.C . Calculated
mm
Breaking
Resistance at
Load
20C (no more
N
than) / km

=V==Table 9

 !
 !E
Calculated F Delivery
Weight
Length (no
kg/km
less than)
m

 !"
Calculated Carrying Capacity A
90C

110C

150C

50/8

6/3.20

1/3.20

9.60

0.6254

16200

195

2000

216

256

326

70/10

6/3.80

1/3.80

11.40

0.4435

22850

275

2000

256

317

407

70/40

12/2.72

7/2.72

13.60

0.4356

57230

511

2000

249

303

401

95/20

7/4.16

7/1.85

13.87

0.3176

36040

409

2000

295

355

490

95/55

12/3.20

7/3.20

16.00

0.3147

76760

708

2000

298

365

498

120/7

18/2.90

1/2.90

14.50

0.2547

26180

379

2000

337

469

594

120/25

7/4.72

7/2.10

15.74

0.2467

46420

527

2000

335

467

591

120/70

12/3.60

7/3.60

18.00

0.2486

97150

896

2000

383

410

570

150/8

18/3.20

1/3.20

16.00

0.2092

30870

461

2000

438

533

676

150/20

24/2.78

7/1.85

16.67

0.2083

44920

549

2000

452

550

699

185/10

18/3.60

1/3.60

18.00

0.1653

39070

584

2000

508

620

789

185/25

24/3.15

7/2.10

16.67

0.1622

56850

706

2000

510

623

792

185/30

26/2.98

7/2.32

18.88

0.1674

62140

733

2000

512

625

796

210/10

18/3.80

1/3.80

19.00

0.1484

43530

651

2000

545

664

847

210/25

24/3.33

7/2.22

19.98

0.1452

63530

789

2000

555

676

863

210/35

26/3.22

7/2.50

20.38

0.1434

71280

854

2000

565

690

882

210/50

30/2.98

7/2.98

20.86

0.1452

88400

961

2000

570

695

887

240/30

24/3.60

7/2.40

21.60

0.12420

73170

922

2000

613

756

967

E L F
 !
Construction (No./Dia) mm
L
Nominal Crosssectional Area
=Al.
=St.
(Al. St.) mm2


20C  !  !"
Outer Dia.  =D.C . Calculated
mm
Resistance at
Breaking
20C (no more
Load
than) / km
N

 !
 !E
Calculated F Delivery
Weight
Length (no
kg/km
less than)
m

 !"
Calculated Carrying Capacity A
90C

110C

150C

240/40

26/3.42

7/2.66

21.66

0.1271

80570

964

2000

610

746

956

240/55

30/3.20

7/3.20

22.40

0.1260

98770

1108

2000

612

758

969

300/15

42/3.00

7/1.67

23.01

0.1023

64570

940

2000

695

848

1082

300/20

45/2.93

7/1.95

23.43

0.1001

72140

1002

2000

697

850

1084

300/25

48/2.85

7/2.22

23.76

0.0992

79830

1058

2000

698

851

1085

300/40

24/3.99

7/2.66

23.94

0.1011

89880

1133

2000

700

858

1090

300/50

26/3.83

7/2.98

24.26

0.1014

101000

1210

2000

702

861

1105

300/70

30/3.60

7/3.60

25.20

0.09952

125000

1402

2000

718

882

1134

400/20

42/3.51

7/1.95

26.91

0.07471

86270

1286

1500

816

998

1275

400/25

45/3.33

7/2.22

26.64

0.07751

90410

1295

1500

817

999

1276

400/35

48/3.22

7/2.50

26.82

0.07772

98510

1349

1500

819

998

1270

400/50

54/3.07

7/3.07

27.63

0.07606

117900

1511

1500

821

998

1269

400/65

26/4.42

7/3.44

28.00

0.07610

130400

1611

1500

826

1015

1270

400/95

30/4.16

19/2.50

29.14

0.07453

166000

1860

1500

863

1065

1374

500/35

45/3.75

7/2.50

30.00

0.06112

114600

1642

1500

944

1156

1481

500/45

48/3.60

7/2.80

30.00

0.06218

123300

1688

1500

948

1157

1480

500/65

54/3.44

7/3.44

30.96

0.06058

148000

1897

1500

950

1159

1478

630/45

45/4.20

7/2.80

33.60

0.04873

140600

2060

1200

1083

1325

1701

630/55

48/4.12

7/3.20

34.32

0.04747

156100

2209

1200

1088

1328

1700

630/80

54/3.87

19/2.32

34.82

0.04786

187900

2388

1200

1091

1331

1698

800/55

45/4.80

7/3.20

38.40

0.03731

181800

2690

1000

1268

1559

2012

800/70

48/4.63

7/3.60

38.58

0.03759

197300

2791

1000

1265

1557

2010

800/100

54/4.33

19/2.60

38.98

0.03823

231600

2991

1000

1251

1508

1933

1440/120

84/4.67

19/2.80

51.36

0.02114

344600

4898

700

1871

2352

3093

 NRLH58GJF !"#$%&'()*+,-./012"#34-+56
781/012-.78"#3.1%
 !"#$%&'(&)*+,-./
5%
k WWThe calculated weight of the NRLH58GJF, add the weight of anti-corrosion coating to the value specified in above table. 3.1% should be added for anticorrosion coating on steel core. 5% should be added for anti-corrosion coating on steel and aluminum layer.

11

1000kV 

!"#$%&'()*+,

Heat-resistant diameter extension generatrix for 1000 kV and


below transmission and transformer projects
=


!=Manufacturing standards

!Q/09 TDL068 - 2007

=Uses
1000kV  !"#$%
Generatrix for 1000 kV and below substation.



!=Type and specification

JLHN58K-1600



!"#$=Main technical of parameter (see Table 6)


==q

= L 
Structure No./ Dia.
(mm)

The cross-sectional area
(mm2)

=NM==Table 10
=JLHN58K-1600

==Outer layer

Al: 45/4.38

 ==Adjacent outer

Al: 39/4.38

==Inner

 !=Corrugated lines aluminum tubes 52.5/41.5, =Wall thickness

 !"==Heat-resistant aluminum alloy

2mm

==Aluminum tubes

1265

 ==A total area

317

 !==Calculated diameter (mm)

1580

 !"==Calculated breaking load (kN)

70.0

 !"==Permitted breaking load (kN)

>200

 ! x10 Elasticity coefficient x 10 (MPa)

>50

 !==Calculated weight (kg/km)

50

 !" x10 Linear expansion coefficient x 10 (C )

45322%

20C  !"==DC Resistance at 20C (/km)

22.2

 !"#$=(A) 150C Allowable long-term carrying capacity (A) 150C

0.01970

-6



-6

-1

3500

!"=Structure
 !
Supporting aluminum tubes
52.5/41.5
 !"#$
Heat-resistant aluminum alloy wire
4.38

 !"2004 !"#$%750kV !"#$% !


 !"#$%& !"
'()*+,750kV !"#$%&
'(
 !"#$%&

12

The product was applied to Northwest Power Grid for the first demonstration project of 750 kV transmission Project, from Guanting transformer substation to Lanzhou east substation. (China's first 750 kV
EHV transmission project) The condition was well since run.

 !"#$%&
This

is

the

world

oriented

TBEA

 !"
#$%&'("
)*+,-./01234567ON !"#$%&'()*
+,-./01
 !"#$%&'()*+,-./012345)678
9:;<=>?@0A@BC@DE)FGH.
IJK
 !"#$%&'#$
()*#+,-./01234$
56$
789:;<=>?@A7BC,DE1<=>FG
 !"#$%&'()*+,-."#$/
TBEA Shandong Luneng Taishan Cable Co.,Ltd. has showed its power in the 21st century which sees the great
development of economy. TBEA, in its fulI power, boosts the world energy economy and electric industry; it
transports light and warmth into every corner of the globe and creates new Iife for people. It focuses on organize,
talent, market, economical globalization, and alI along follows the managerial philosophy that "Satisfied Customers,
Contented employees, Assured shareholders". It is creating the future of Chinese power industry, the world
electric industry and the development of the world economy with its ideaI, foresight, strength and self-confidence.

 !"#$%&" '()*+
 !"#$%& 568 
271200
(538) 7238818
(538) 7222439
http://www.tbea-ll.com

TBEA Shandong Luneng Taishan Cable Co., Ltd


A d d: No.568, Jindou Road, Xintai city,Shandong Province,China
P . C: 271200
T e l: +86 538 7238818
F a x: +86 538 7222439
Web: http: //www.tbea-ll.com

 !"
(538) 7238657
(538) 7222255
 
13583837018

Import and Export Department


T e l: +86 538 7238657
F a x: +86 538 7222255
Contact: Wang Songwei
Mobile: 13583837018

 !
(538) 7238680
(538) 7238693
  ====
13853899916 13562860789

Sales Department
T e l: +86 538 7238680
F a x: +86 538 7238693
Contact: Wang Fengxiang Wang Zhong
Mobile: 13853899916 13562860789

You might also like