Professional Documents
Culture Documents
OM5510#05.0
General
The electronic pneumatic positioner is used as the final control element of a
pneumatic linear actuator or a part-turn actuator (rotary movements). The positioner
converts a current output signal (4 to 20 mA) from a process controller or control
system to a set point value and into a corresponding movement. The positioner
changes the pressure in a pneumatic actuator chamber or cylinder until the position
corresponds to the set point value.
The positioner can be set up either as a single-action positioner or a double-action
positioner. The single-action positioner is mainly used together with a control valve.
The opposite movement for the control valve is supplied by means of springs. The
double-action positioner is mainly used to control an air damper via a pneumatic
cylinder (actuator). All movements of the pneumatic cylinder are supplied by the
positioner. An illustration of the function diagram for the positioner is shown in
Figure 1. The function diagram is shown with option modules.
Language UK
Electric connection
Pneumatic connection
Commissioning
Page 1/16
OM5510#05.0
Figure 1
sips2_5a.tif
Language UK
Page 2/16
OM5510#05.0
Step C: Push the roll (5), spring (13), and guide washer (22) onto the pin (4).
Step D: Insert the pin in the lever (6) and assemble with nut (18), spring washer
(14), and U-washer (12).
Step E: The value of the stroke range specified on the actuator should be set or if
this does not exist as a scaling value, the next greatest scaling value should
be set. The centre of the pin must be in line with the scaling value. The
same value can be set later under parameter 3.YWAY in commissioning
to display the way in [mm] after initialisation.
Step F: Assemble the hexagon socket cap screw (17), spring washer (16), washer
(12), and square nut (19) on the lever.
Step G: Push the pre-mounted lever onto the positioner axis up to the stop and fix
with the hexagon socket cap screw (17).
Step H: Fit the mounting bracket (1) with two hexagon head screws (9), lock
washer (10), and flat washer (11) on the rear of the positioner.
Step I: Selection of the row of holes depends on the width of the actuator yoke. The
roll (5) should engage in the pick-up bracket (2) as close as possible to the
spindle but may not touch the clamping assembly.
Step J: Hold the positioner with the mounting bracket on the actuator so that the pin
(4) is guided within the pick-up bracket (2).
Step K: Tighten the pick-up bracket.
Step L: Position the mounting parts according to the type of actuator.
Actuator with ledge: hexagon head screw (8), flat washer (11), and lock washer
(10).
Actuator with plane surface: four hexagon head screws (8), flat washer (11), and
lock washer (10).
Actuator with columns: two U-bolts (7), four hexagon nuts (21) with flat washer
(11), and lock washer (10).
Step M: Secure the positioner onto the yoke using the previously positioned
mounting parts.
Note: Set the height of the positioner so that the horizontal lever position is
reached as close to the stroke centre as possible. The lever scale can be
used as orientation. It must be guaranteed that the horizontal lever
position is passed through within the stroke range.
Language UK
Page 3/16
OM5510#05.0
Figure 2
Language UK
sips2_5b.tif
Page 4/16
OM5510#05.0
Language UK
Page 5/16
OM5510#05.0
Figure 3
Language UK
sips2_5c.tif
Page 6/16
OM5510#05.0
Figure 4
sips2_5d.tif
Pneumatic connection
Ensure that the air quality is suitable. Grease-free instrumental air with a solid
content < 30 m and a pressure dew point 20 K below the lowest ambient
temperature must be supplied.
Warning: For reasons of safety, pneumatic power may only be supplied after
assembly when the positioner is switched to operating level P
manual operation with electrical signal applied.
Language UK
Page 7/16
OM5510#05.0
Commissioning
Commissioning (initialisation) is carried out automatically to a large extend. During
initialisation, the micro controller automatically determines the zero value, full-scale
value, direction of action and positioning speed of the actuator. It uses these to
determine the minimum pulse time and dead zone, hereby optimising the control.
The positioner can also be operated manually by the pushbuttons and the LCD of the
SIPART PS2.
The commissioning of the positioner can be divided into the following steps:
Preparation for initialisation
Language UK
Page 8/16
OM5510#05.0
Figure 5
sips2_5e.tif
Language UK
Page 9/16
OM5510#05.0
Step B: Check that the pneumatic supply power (inlet air) is present. The operating
pressure should be at least one bar greater than is necessary for
closing/opening the valve during initialisation.
Step C: Without initialisation the positioner is in P manual mode and NOINIT
flashes in the display. This level can also be reached by using 55.PRST
function (see Table 1).
Step D: Check the free running of the mechanics in the whole actuating range by
moving the actuator with the keys and and driving to the respective
end position.
Step E: With linear actuators drive the actuator to horizontal lever position. The
display must indicate 48% to 52%. If necessary, correct the value by
adjusting the sliding clutch. After the check is completed, the actuator must
be approximately half way along its stroke. This is due to establishment of
the action direction during automatic initialisation.
Language UK
Page 10/16
OM5510#05.0
Step H: Start the initialisation (4.INITA) by pressing the key for longer than 5
seconds.
Step I: During the initialisation phase RUN1 to RUN5 appear one after another
in the bottom of the display. Please note that the initialisation process may
last up to 15 minutes depending on the actuator.
Note: The ongoing initialisation can be aborted at any time by pressing the
hand symbol key. The previous settings are retained. All the parameters
are reset to the factory setting only after performing a preset 55.PRST.
Step J: If problems occur, carry out the measures as described in the table Possible
messages shown in Figure 7.
Step K: The initialisation is completed when FINSH appears in the bottom of the
display.
Step L: When pressing the hand symbol key briefly the menu item line 4.INITA is
displayed.
Step M: To exit the configuration operating mode, press the hand symbol key for
longer than 5 seconds. The software version is displayed after about 5
seconds. The instrument is in manual operation after releasing the key.
Step N: The positioner can be changed to automatic mode by pressing the key
once as indicated in Figure 5.
Step O: The automatic mode is the normal mode. In this mode the positioner
compares the set point current with the current position and moves the
actuator until the control deviation reaches the dead zone.
Operation in the configuration mode
Figure 6
Language UK
sips2_5f.tif
Page 11/16
OM5510#05.0
Initialisation process
Automatic initi al start-up (starting with factory setting)
Step
1.)
Me aning
Possible messages
Display
Me aning
Part-t urn
actuator
turn
90
1 YF CT
2 YAGL
Linear
actuator
WAY
33
Strt
1 YF CT
2 YAGL
3 YWAY
32.4
RU N 1
Actuator does
not move
32.4
Strt
4 INITA
Acknowled ge message
using the hand symbol key
Check restr ictor (6) and open
if necessar y
Drive actuator to working range
using the up and down keys
ERR OR
2.)
Me asures
3.)
4.)
5.)
6.)
7.)
8.)
32.4
R UN 1
92.4
R UN 2
82.4
R UN 3
32.4
R UN 4
52.4
R UN 5
32.4
FINSH
88.4
d u IU
Down tolerance
band violated
6.4
d 0 IU
Then only
Continue us ing the down key
S Et
Determina tion of minimum incre ment length
MID DL
98.3
UP
>
Up tolerance b and
violated
92.8
90_9 5
19.8
U-d <
Up/down span
violated
Acknowledge message
using the ha nd symbol key
Set the nex t lowest travel
value on the lever
Restart initi alisation
1.3
NO ZZL
1.8
NO ZZL
Figure 7
Actuator does
not move.
Positioning
time is possibl e
to adjust
sips2_5g.cdr
5.3 Parameters
After the initialisation process, the positioner can be configured to meet the
requirements of a specified task. The factory settings correspond to the requirements
for a typical application. This means that normally only a few parameters will need
to be changed.
Table 1 shows the parameter list for the positioner. The parameter name is written in
plain text in the menu line column. The function of the parameter is described
briefly in the Function column. In addition, the possible parameter values, the
physical unit and the factory setting of the parameters are shown.
Language UK
Page 12/16
OM5510#05.0
Parameter list
Menu line
1.YFCT
2.YAGL1)
Function
Parameter values
Type of actuator
4.INITA
5.INITM
Initialisation (automatically)
Initialisation (manually)
6.SCUR
7.SDIR
8.SPRA
9.SPRE
10.TSUP
11.TSDO
0 to 20 mA
4 to 20 mA
rising
falling
13.SL03)
14.SL1
to
32.SL19
33.SL20
Linear
Equal-percentage 1:25, 1:33, 1:50
Inverse equal-percentage 1:25, 1:33, 1:50
Freely adjustable
Set point turning point at
0%
5%
to
95%
100%
34.DEBA
12.SFCT
35.YA
36.YE
37.YNRM
38.YDIR
39.YCLS
40.YCDO
41.YCUP
Language UK
Factory setting
Customer
setting
WAY
Degrees
33
mm
OFF
OFF
3.YWAY2)
Unit
5 , 10 , 15 , 20
(short lever 33)
25 , 30 , 35
(short lever 90)
40 , 50 , 60 , 70 ,
90 , 110 , 130
(long lever 90)
noini / no / ###.# / Strt
noini / ###.# / Strt
0 MA
4 MA
riSE
FALL
0.0 to 100.0
0.0 to 100.0
Auto
0 to 400
0 to 400
no
no
4 MA
riSE
%
%
0.0
0.0
Lin
125 , 133 , 150
n125 , n133 , n150
FrEE
0.0 to 100.0
Auto
0.1 to 10.0
0.0 to 100.0
0.0 to 100.0
MPOS
FLOW
riSE
FALL
no
uP
do
uP do
0.0 to 100.0
0.0 to 100.0
Lin
0.0
5.0
to
95.0
100.0
Auto
%
%
0.0
100.0
MPOS
riSE
no
%
%
0.5
99.5
Page 13/16
OM5510#05.0
42.BIN14)
43.BIN2
4)
44.AFCT5)
45.A1
46.A2
47.FCT6)
48.TIM
49.LIM
Function
Function of BI 1:
None
Only message (NO/NC contact)
Block configuring (NO contact)
Block configuring and manual (NO contact)
Drive valve to pos. up (NO/NC contact)
Drive valve to pos. down (NO/NC contact)
Block movement (NO/NC contact)
Function of BI 2:
None
Only message (NO/NC contact)
Drive valve to pos. up (NO/NC contact)
Drive valve to pos. down (NO/NC contact)
Block movement (NO/NC contact)
Without
A1=min. A2=max.
Alarm function
A1=min. A2=min.
A1=max. A2=max.
Response threshold of alarm 1
Response threshold of alarm 2
Function of alarm output
On fault
Fault + not automatic
Fault + not automatic + BI
(+ means logical OR operation)
Monitoring time for fault message
control deviation
Response threshold for fault message
control deviation
50.STRK
51.DCHG
52.ZERO
53.OPEN
54.DEBA
55.PRST
Parameter values
Unit
OFF
on / -on
bLoc1
bLoc2
uP / -uP
doWn / -doWn
StoP / - StoP
OFF
on / -on
uP / -uP
doWn / -doWn
StoP / -StoP
oFF
N , NA
N,N
NA , NA
0.0 to 100.0
0.0 to 100.0
Factory setting
Customer
setting
OFF
OFF
OFF
%
%
10.0
90.0
nA
nAb
Auto
0 to 100
Auto
0.0 to 100.0
OFF
1 to 1.00E9
OFF
1 to 1.00E9
OFF
0.0 to 100.0
OFF
0.0 to 100.0
OFF
0.0 to 100.0
Auto
Auto
OFF
OFF
OFF
OFF
OFF
no
Strt
oCAY
Table 1
1)
Language UK
Page 14/16
OM5510#05.0
Diagnosis
In the diagnostic mode the current operating data (such as number of strokes,
number of changes in direction, number of fault messages, etc.) can be displayed.
From the automatic or manual modes the diagnostic mode can be reached by
simultaneously pressing all three keys for at least 2 seconds.
Table 2 shows an overview of the displayable values. The diagnostic display has a
similar structure as the parameter menu displays. The respective next diagnostic
value can be selected with the hand symbol key. Certain values can be set to zero by
pressing the key for at least 5 seconds. These are menu item line 1, 2, 3, and 4.
Some diagnostic values may be greater than 99999. In this case the display switches
to exponential display.
Diagnostic list
No.:
Abbreviation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
STRKS
CHDIR
CNT
A1CNT
A2CNT
HOURS
WAY
TUP
TDOWN
LEAK
P0
P100
IMPUP
IMPDN
DBOP
DBDN
SSUP
SSDN
TEMP
TMIN
TMAX
T1
T2
T3
T4
T5
T6
T7
T8
T9
VENT1
VENT2
33
STORE
Meaning
Number of strokes
Changes of direction
Fault counter
Alarm counter 1
Alarm counter 2
Operating hours
Determined actuating path
Travel time up
Travel time down
Leakage
Potentiometer value below stop (0%)
Potentiometer value bottom stop (100%)
Impulse length up
Impulse length down
Dead zone up
Dead zone down
Short step zone up
Short step zone down
Current temperature
Minimum temperature
Maximum temperature
Number of operating hours in Temperature range 1
Number of operating hours in Temperature range 2
Number of operating hours in Temperature range 3
Number of operating hours in Temperature range 4
Number of operating hours in Temperature range 5
Number of operating hours in Temperature range 6
Number of operating hours in Temperature range 7
Number of operating hours in Temperature range 8
Number of operating hours in Temperature range 9
Number of cycles pre-control valve 1
Number of cycles pre-control valve 2
Store current values as last maintenance
Press the up key for at least 5 seconds (store)
Displayable
value
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 130
0 to 1000
0 to 1000
0.0 to 100.0
0.0 to 100.0
0.0 to 100.0
2 to 100
2 to 100
0.1 to 100.0
0.1 to 100.0
0.1 to 100.0
0.1 to 100.0
-45 to 85
-45 to 85
-45 to 85
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
0 to 4.29E9
-
Unit
Hours
mm or
s
s
%
%
%
ms
ms
%
%
%
%
C
C
C
Hours
Hours
Hours
Hours
Hours
Hours
Hours
Hours
Hours
-
Table 2
Language UK
Page 15/16
OM5510#05.0
Language UK
Page 16/16