One Product Numerous Applications


Electronic Controllers for Heating, Cooling,
Ventilation and Air Condition

Electronic Controllers from Danfoss:


Only a Few Products for an Endless Number
of Applications

The ECL Comfort and ECL Apex 10


product ranges consist of electronic
controllers for temperature control in
heating and domestic hot water (DHW)
systems. The controllers ensure a high
comfort level and optimum energy
utilization.
The components of ECL Comfort
The ECL Comfort range consists of ECL
Comfort 100, 200 and 300 each in an
elegant and timeless design.
ECL Comfort 100 is the choice for
simple heating systems, for which the
installer or user prefers the traditional,
plain and analog operation.
ECL Comfort 200 appeals to users
who prefer a digital user interface
and the increased number of options
this provide. The series offers many
functional options and can be used
for commercial installations.
ECL Comfort 300 is the advanced
controller with a large number of
functions, such as: Two control circuits
+ thermostatic function, optimizer
function, 3 point control, LON
communication etc. The intelligent
card concept ensures optimum
user-friendliness of this advanced
controller.

The range also comprises an elegantly


designed remote control in two
versions, which is connected to the
controller via a two-wire cable.
ECL Comfort
The future is in the Cards
The ECL Comfort range and its
advanced chip card not only meet
your present demands but also the
future requirements you might have
for heating control.
With ECL Comfort 300 new demands
are covered by new cards with new
settings. The few basic models and
the large variety of ECL Cards give you
a considerably better and quicker
overview of the unique application
opportunities offered by the ECL
Comfort range.

Some advantages of ECL Comfort:


Optimizer and boost function
Return temperature limitation
based on outdoor temperature
Frost protection
Heating cutout function
Year clock and automatic changeover between summer and winter
time
Copy function to/from the
intelligent ECL Card
Anti-bacteria function (DHW circuit)
Communication via the
standardized LonTalk Protocol,
RS 232, and M-bus options

By means of the chosen card, it is easy


to set the controller and simple to
change the factory settings precisely
to the relevant type of system and
required settings.
The schedule in the ECL Comfort can
be programmed for each day in the
week. The building will be heated in
the comfort periods you request. This
is environmentally sound and saves
money.

Flexibility and Easy Operation

Auto tuning and motor protection


A precondition for a well functioning
heating system is that the correct
settings are made before it is put
to use. Adjustments are necessary
to preset the control parameters.
Presetting gives the following benefits:
A high degree of comfort

The introduction of automatic setting


of control parameters on the controller
itself, i.e. auto tuning and motor
protection, gives optimum control
of the DHW system. This ensures a
high degree of comfort, stable control
during idle operation and, subsequently,
longer motor life.
The setting of control parameters can
thus be reduced to one simple and
reliable procedure. Auto tuning is
especially necessary in DHW systems.

Improved protection against lime


deposits in DHW heat exchangers

All applications, updates and other


information are placed on the Danfoss
Heating Portal from where it can be
downloaded.

Remote service possibilities with


WebAccess
The WebAccess makes your ECL
Comfort 200 and 300 accessible via
Internet or modem.

Energy saving
Long operating life
Minimum service

You can define different levels of access


going from monitoring to wide control
of parameters in the ECL controller.

Some advantages of the


ECL Apex 10:
Temperature, pressure and
flow control

The WebAccess is used in a LON network communicating with up to


4 ECL controllers. Other components
such as energy meters can also be
monitored via the WebAccess.

Data logging facilities


Alarm functions associated to
either system, application or
monitoring failures
ECL Apex 10 configurable controller
The ECL Apex 10 is a dedicated district
heating controller preprogrammed
with all relevant control functions and
applications. The controller is applicable
in large substations and distributor
stations and can be connected as stand
alone or in network.

Easy and cost-effective


commissioning and service;
a variety of application templates
are ready for use
Back up/restore function for
similar applications
Different user levels for simple
controlling or programming

Auto Tuning

The result of
80

Auto Tuning with ECL Comfort

Tap Water (C)

70

Open for the tap water to get a constant


tapping load

60
50

Activate Auto Tuning by pushing a button

40
30

Flow Rate (m3/h)

Tap
Water Temperature (C)

As a consequence it can be used


in supervisory control and data
acquisition systems (SCADA).
The ECL Apex 10 can be extended
with a number of modules to fit
any heating application with up to
5 circuits within heating or DHW.

Sec. Flow (m3/h)

20
10
0

4 0.00
Time (min.)

5.00

10.00

15.00

20.00

25.00

30.00

Wait 7-25 minutes to complete the tuning

Advanced Controlling in a Simple User Interface


ECL Comfort displays for
end users and installers
With ECL Comfort it is possible
to control all stages of the heat
consumption right down to the
smallest detail and at the same
time take external factors into
account such as the outdoor

Controller mode:

Shift button:

Circuit selector:

Used to switch between manual operation,


scheduled operation, constant comfort
temperature, constant setback temperature,
and stand-by mode.

Switches between the various settings you can


change: Temperature, changeover point etc.

Switches between the heating circuit and


DHW/heating circuit.

+/- buttons:
Arrow buttons:

End user displays

Installer displays
1

1035
3
0

Temperature control:
This display provides a quick overview of the outdoor and indoor
temperatures, the requested comfort
temperature, and the status mode of
the system.

Adjust different values and manual operation.

Move from line to line in the menus.

temperature, the insulation of the


heated area and the radiator capacity
of the building. It is an easy task to
operate ECL Comfort 200 and 300.
You only have to push a few buttons
to enter all the settings.

12

15

18

21

24

Normal display:
This display gives you a quick overview of the time, the outdoor and
indoor temperatures, the selected
comfort periods of the day, and the
status mode of the system.

ON

ON

12

15

ON

ON

ON

10

18
65

1035

19
6

ON

18

21

30

14

24

Time programming:
This display informs you about the
time interval of the comfort periods
if additional and personal comfort
periods have been entered to meet
the special demands you might have.

Control of system components:


Displays a status of the pumps,
motorized valves etc. in the heating
system as well as the current system
temperatures (flow and return
temperatures).

Control of system temperature:


Here the heat curve is set the
relationship between required
flow temperature and outdoor
temperature.

Optimum start function:


The calculation of the optimum start
and stop times includes factors such
as insulation, radiators and system
capacity to ensure that the requested
temperature is reached at the
requested time.

Adjustment of control parameters


where each parameter has a short
description and the actual value is
shown. The primary values of the
heating circuit are shown in the top
of the window.

The primary parameters and sensor


values of the heating circuit.

Overview of all circuits;


heating and DHW.

ECL Apex 10 - Flexible user


interface and control functions
The controller and its service tool can
be operated by means of a PDA or a
PC and either on-site or remotely via
modem. The service tool offer four
different user levels: supervisor, service
user, daily user and default user.

Schedule (comfort/setback)

The required flow temperature is


typically based on the outdoor
temperature (weather compensation)
but can also be influenced by:

Return temperature, flow and


energy limitation

Optimized time control


Boost function
Maximum and minimum flow
temperature limitation

Anti-bacteria function
(DHW circuit)

Select Your ECL Comfort

Card
type

ECL Comfort
100B
100M

Type
of circuit

Boiler circuit

Heating circuit

Cooling
circuit

Hot water circuit

Others

P16
A
B
C
A
B
C

1
2
3
4
5
6
7

200

1
2
3
4
5
6
7
ECL Comfort

P17
P20
P30

Room panel
ECA 60/61/62/63
An ECA room or
remote panel for
installation in your
living room or your entrance hall makes
it possible to display and override your
ECL Comfort settings remotely.

Main features:
Mode selection
(comfort temperature, reduced
temperature, automatic operation).
Display of time, actual outdoor and
room temperature as well as the
lowest and highest outdoor
temperature since midnight.
Setting of desired comfort and
reduced room temperature level
Room temperature control via
built-in room sensor.
Setting of periods - comfort
temperature or reduced temperature
depending on whether you are
present in the building or not.

C14
C25
C35
300

A
B
C
A
B
C

1
2
3
4
5
6
7

1
2
3
4
5
6
7
ECL Comfort

C37

*1

C47

*1

C55

*1

C60/C62
C66
*1

C67

C75
L05
301

A
B
C

1
2
3
4
5
6
7

*1

L66

*1

L76

*2

ECL Comfort

*1: Some systems need an optional relay module (ECA 80)


*2: Only together with 'ECL Comfort 301 with ECA 83'

Select Your ECL Apex 10


Controller and extension modules
Analog inputs (AI)

Accessories for the controller


series ECL Comfort

ECL Comfort 100

ECL Comfort 200

ECL Comfort
300/301

Type

ECA 60/62, Room panel

ECL Apex 10

ECA 61/63, Remote control

24 Va.c.

SIG

C37/C47 1), C55 2), C75 3)

ECA 84, M-Bus module

C37/C47/C66

ECA 86, I/O and alarm option

BUS

DO4

Alarm

C66

SIG

GND

SIG

GND

10

11

12

SIG

GND

13

14

+12V

+5V

SHLD

SHLD

15

16

17

18

AI 8

AI 9

AI 10

11

Low voltage
(max 80 V)

High voltage
(max 260 V)

Analog
outputs (AO)
0-10 V d.c.

Module with
switches
for override of
relay outputs

AI 11

SIG

GND

SIG

GND

SIG

GND

SIG

GND

+12V

+5V

SHLD

SHLD

19

20

21

22

23

24

25

26

27

28

29

30

A B
BUS
Service Tool

Service Pin
BUS Address

8
SIG

DI 1

DI 2

DI 3

SIG

N
DI 4

4
GND
AI 2

5
SIG

SIG

GND

10

11

12

13

GND

SIG

+12V

+5V

SHLD

SHLD

SIG

GND

GND

SIG

AI 3

GND

SIG

GND

AI 4

SIG

SIG

GND

16

17

GND

SIG

GND

14

15

GND

SIG

AI 1

AI 2

SIG

GND

18

19

GND

SIG

AI 3

+12V

+5V

SHLD

SHLD

20

21

22

23

24

GND

+12V

+5V

SHLD

SHLD

AI 4

Comm

ECA-XM 102B

No. 087B2621

Extension 8 DIH

No. 087B2750

Extension 8 AI / DO

Digital
Input

Relay

ECA-XM 205A

Override

8
8
X

8
SIG

1
L
DI 1

DI 2

DI 3

8
N
DI 4

1
SIG

GND

SIG

AI 1

4
GND
AI 2

5
SIG

7
SIG

Comm

5
6

ECA-XM 102B

No. 087B2621

Extension 8 DIH

6
7
8
Relay

SIG

GND

10

11

12

13

+12V

+5V

SHLD

SHLD

SIG

GND

SIG

GND

AI 4

Power

Comm

Digital
Input

SIG

8
GND

GND

6
GND
AI 3

Power

ECA-XM 205B

1) Control of a circulation pump and an alarm output signal


2) Control of a DHW pump or change-over valve
3) Control of two additional burner steps
4) Module to communicate the ow and energy parameter from a heat meter
5) Module to monitor temperatures and data points from the controller

3
SIG

Power

Comm

ECA-XM 102B

2
GND
AI 1

Power

ECA-XM 205A

Room panel, ECA 62


(as ECA 60 but with humidity sensor)

ECA-XM 204B

LON module for network


connection

GND

BEA 0050, Auxiliary relay

Relay module for extended


functionality

No. 087B2500

11 AI/ 8 DO
24 Va.c.
50/60 Hz 8 VA
MADE IN DENMARK

Servi
ce Pin

ECA 9010, Override module

Remote control, ECA 63


(as ECA 61 but with humidity sensor)

SIG

GND

ECL Apex 10

DO6

ECA 100, Analog time switch, week program

Remote control, ECA 61

SIG

DO5

ECA-XM 102A

5)

ECA-XM 204A

Room panel, ECA 60 with


built-in room temperature sensor

Service Tool

DO3

ECA-XM 101A

4)

ECA 87, RS232 remote control and data log

Analog clock for ECL Comfort


100B and 100M

GND

Triac

ON/OFF inputs (DI), opto

Extension modules

ECA 82, LON module

Connector set for panel mounting

SIG

Status

DO2

DO7

ECA 80, 2 x relay

Accessories
Socket for wall mounting

GND

Relay (SPDT)

Comm
DO1

ON/OFF outputs (DO)

For temperature, pressure,


ow and energy
transmitters, etc.
Power

DO8

All these product features are relevant


in order to obtain the best economically and individually adjusted heating
control.

*1

L32

A
B
C

1
2
3
4
5
6
7

Setting of the service parameters:


heating cut out, minimum/
maximum room temperature
inuence (only ECA 61/63).
Setting of the time schedules for
the week program (only ECA 61/63).
Humidity monitoring via built-in
humidity sensor (only ECA 62/63).

SIG

SIG

GND

16

17

GND

SIG

GND

14

15

GND

SIG

AI 1

AI 2

SIG

GND

18

19

GND

SIG

AI 3

+12V

+5V

SHLD

SHLD

20

21

22

23

24

GND

+12V

+5V

SHLD

SHLD

AI 4

3
4
5
6

ECA-XM 205A

No. 087B2750

Extension 8 AI / DO

Override

ECA-XM 210A*

X
2

The following extension module must be placed on the base part in the controller. There is only room for one module.
ECA-OB 003A

*) ECA-XM 210A is equipped with the M-Bus communication acc. to EN1434-3 and pulse input for frequencies up to 200 Hz.

Temperature sensors
Outdoor
Room

ECL Apex 10 in SCADA1) systems


ECL Apex 10 can communicate with
components and systems through
RS232 communication or modem

connection. The controller operates


with a standard interface supporting
an OPC data access server (OLE for
Process Control). The OPC is used to

move data from the ECL Apex 10 to


the SCADA system enabling network
monitoring.

Surface
Immersion
1) Supervisory Control And Data Acquisition.

RS232 module for PC connection


9

Index for Cards and Applications


ECL Comfort

Card

Electronic temperature controller for weather compensated


flow temperature control of boiler systems.

11

100M

Electronic temperature controller for weather compensated flow


temperature control of directly or indirectly connected heating systems.

11

200

Electronic temperature controller, pre-programmed for a


variety of different applications. Each application has its own card
that describes the settings.

A
B
C

1
2
3
4
5
6
7

1
2
3
4
5
6
7

1
2
3
4
5
6
7

A
B
C

1
2
3
4
5
6
7

Page

100B

A
B
C

A
B
C

Application

ECL Comfort

100B

ECL Comfort
Weather compensated flow temperature
control of boiler systems.

System type

P16

12

P17

13

P20

14

P30

15

Boiler heated system

ECL Comfort

A
B
C
A
B
C

1
2
3
4
5
6
7

Electronic temperature controller programmed with ECL Cards for


large numbers of different systems.

300

1
2
3
4
5
6
7
ECL Comfort

A
B
C

A
B
C

1
2
3
4
5
6
7

1
2A
3B
4C
5
61
A
72
3 Comfort B
ECL
4
C
5
6
1
7

A
B
C

1
2
3
4
5
6
7

2
3
4
5
6
7

A
B
C

ECL Comfort

1
2
3
4
5
6
7
ECL Comfort

A
B
C
A
B
C

1
2
3
4
5
6
7

1
2
3
4
5
6
7
ECL Comfort

A
B
C

A
B
C

1
2
3
4
5
6
7

1
2
3
4
5
6
7
ECL Comfort

A
B
C
A
B
C

1
2
3
4
5
6
7

C14

16

C25

18

C35

19

C37

20

C47

22

C55

24

C60

25

C62

26

Weather compensated flow temperature control

C66

27

of directly or indirectly connected heating systems

C67

28

and boiler systems.

C75

30

System type 1:

System type 2:

Indirectly connected heating system

Boiler system with 4-way rotary valve

1
2
3
4
5
6
7

ECL Comfort Master / Slave Applications System type 1

31

ECL Comfort Master / Slave Applications System type 2

32

ECL Comfort

A
B
C

1
2
3
4
5
6
A
7
B

A
B
C

1
2
3
4
5
6
7

1
2
3
4
5
6
7

301

1
2
3
4
5
6
7
ECL Comfort

A
B
C

1
2
3
4
5
6
7

8
AI

SIG

1 GND
2 SIG
3 GND
4 SIG
5 GND
6 SIG
7 GND
8 SIG
9 GND
10 SIG
11 GND
12 SIG
13 GND
14 +12V
15 +5V
16 SHLD
17 SHLD
18

SIG

AI
9
19 GND
20 SIG
AI
10
21 GND
22 SIG
AI
11
23 GND
24 SIG
25 GND
26 +12V
27 +5V
SHLD
28
SHLD
29
30

ECL Comfort

24 Va.c.

A B
BUS
Service

Tool

Pin
Service ss
Addre
BUS

10

Electronic temperature controller programmed with ECL Cards for


large numbers of different systems.

L05

33

L10

36

L32

37

L66

38

L76

39

ECL Comfort

A
B
C

1
2
3
4
5
6
7

A
B
C

100M

ECL Comfort

ECL Apex 10

ECL code numbers

40

ECL Comfort Cards and Instructions

41

ECL Apex 10

42

ECL Apex 10 and ECA-XM modules

43
11

P16

ECL Comfort 200


Constant temperature control for DHW
circuits with flow system or storage tank
with built-in heating coil.

P17

ECL Comfort 200


Constant temperature control of DHW
circuits with storage charging system.

System type 1:

System type 2:

System type 1:

System type 2:

Constant temperature control of the DHW circuit

Constant temperature control of the DHW circuit


with storage tank with built-in heating coil

Constant temperature control of DHW circuit


with storage charging system

Constant temperature control of DHW circuit


with storage charging system

System type 3:
Constant temperature control of the DHW circuit

12

13

ECL Comfort 200

P20

P30

ECL Comfort 200

Weather compensated flow temperature


control of boiler systems.

Weather compensated flow temperature


control of heating systems with fixed
return temperature limitation.

System type 1:

System type 1:

System type 2:

Boiler heated system

Indirectly connected heating system

Directly connected heating system

System type 3:

System type 4:

Boiler system with 3-way valve

Boiler system with 4-way rotary valve

14

15

C14

ECL Comfort 300


Constant temperature control
(heating/cooling) of ventilation systems.

C14

ECL Comfort 300


Constant temperature control
(heating/cooling) of ventilation systems.

System type 1:

System type 2:

System type 5:

System type 6:

Unit heater system with constant room temperature control

Ventilation system with constant supply air control

Ventilation system with constant room temperature control


heating and cooling

Ventilation system with constant room temperature control


heating and heat recovery

System type 3:

System type 4:

System type 7:

System type 8:

Ventilation system with constant room temperature control

Ventilation system with constant room temperature


control and fresh air supply

Cooling system with constant cooling temperature

Cooling system with constant room temperature

16

17

C25

ECL Comfort 300


Weather compensated flow temperature
control of boiler heated systems and
constant temperature control of DHW
circuits.

C35

ECL Comfort 300


Weather compensated flow temperature
control of secondarily connected DHW
control of systems with fixed return
circuits with storage tank with built-in
temperature limitation. Constant temperature heating coil. Optional ON/OFF control

of the DHW circuit in connection with


primarily connected storage tank with
built-in heating coil.

System type 1:

System type 2:

System type 1:

System type 2:

Heating system with constant temperature


control of the DHW circuit

Heating system with constant temperature


control of the DHW circuit (DHW priority)

Indirectly connected heating system and secondarily


connected DHW storage tank with built-in heating coil
(DHW priority)

Indirectly connected heating system and secondarily


connected DHW storage tank with built-in heating coil
(optional DHW priority)

System type 3:

System type 3:

System type 4:

Weather compensated control of the heating system

Indirectly connected heating system and primarily


connected DHW storage tank with built-in heating coil
(optional DHW priority)

Directly connected heating system and DHW storage


tank with built-in heating coil (optional DHW priority)

18

19

C37

ECL Comfort 300


Weather compensated flow temperature
control of systems with sliding return
temperature limitation. Constant
temperature control of secondarily

connected DHW circuits with storage


charging system or storage tank with
built-in heating coil. Optional ON/OFF
control of the DHW circuit in connection

with primarily connected storage tank


with built-in heating coil.

C37

ECL Comfort 300


Weather compensated flow temperature
control of systems with sliding return
temperature limitation. Constant
temperature control of secondarily

connected DHW circuits with storage


charging system or storage tank with
built-in heating coil. Optional ON/OFF
control of the DHW circuit in connection

System type 1:

System type 2:

System type 5:

Indirectly connected system and secondarily connected


storage charging system (optional DHW priority)

Indirectly connected system and secondarily


connected storage charging system (DHW priority)

Indirectly connected system and primarily connected


storage tank with built-in heating coil (optional DHW priority)

with primarily connected storage tank


with built-in heating coil.

Please note: The following systems are only applicable


with the relay module ECA 80.

System type 3:

System type 4:

System type 6:

System type 7:

Indirectly connected system and secondarily connected


storage tank with built-in heating coil (optional DHW priority)

Indirectly connected system and secondarily connected


storage tank with built-in heating coil (DHW priority)

Indirectly connected system and secondarily connected


storage charging system (optional DHW priority)

Indirectly connected system and secondarily connected


storage charging system (DHW priority)

20

21

C47

ECL Comfort 300


Weather compensated flow temperature
control of systems with sliding return
temperature limitation. Constant

temperature control of DHW circuits


with storage charging system.

C47

ECL Comfort 300


Weather compensated flow temperature
control of systems with sliding return
temperature limitation. Constant
temperature control of DHW circuits

with storage charging system.


Please note: The following systems are
only applicable with the relay module
ECA 80.

System type 1:

System type 2:

System type 4:

System type 5:

Indirectly connected heating system with mixing loop


and secondarily connected storage tank with built-in
heating coil (optional DHW priority)

Indirectly connected heating system and primarily


connected storage charging system (optional DHW priority)

Indirectly connected heating system with mixing loop


and secondarily connected storage charging system (optional
DHW priority)

Indirectly connected heating system and secondarily


connected storage charging system with mixing circuit
(optional DHW priority)

System type 2a:

System type 3:

System type 6:

System type 6a:

Indirectly connected heating system and primarily


connected storage charging system (optional DHW priority)

Indirectly connected heating system and primarily


connected storage tank with built-in heating coil (optional
DHW priority)

Indirectly connected heating system and primarily connected


storage charging system with pre-controlled circuit (optional
DHW priority)

Indirectly connected heating system and primarily connected


storage charging system with pre-controlled circuit (optional
DHW priority)

22

23

C55

ECL Comfort 300


Boiler controller with constant
temperature control of DHW circuits
and weather compensated flow

temperature control of a mixed and an


unmixed heating circuit.

Please note: Relay module ECA 80 is a


necessary accessory!

C60

ECL Comfort 300


Weather compensated flow
temperature control with sliding
temperature limitation for two
independent heating circuits.

System type 1:

System type 2:

System type 1:

System type 2:

Weather compensated control of a mixed and an unmixed heating circuit and constant temperature control of the DHW circuit

Weather compensated control of a mixed and an unmixed heating circuit and constant temperature control of the DHW circuit

Two indirectly connected weather compensated


heating systems

Two directly connected weather compensated heating


systems

System type 3:

System type 3:

System type 4:

Weather compensated control of a mixed and an


unmixed heating circuit

Indirectly connected weather compensated heating


systems with mixing circuit

Weather compensated control of two mixed heating circuits

24

25

C62

ECL Comfort 300


Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation for two
independent heating circuits.

C66

ECL Comfort 300


Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation. Constant

temperature control of DHW circuits


with flow system or storage tank with
built-in heating coil.

System type 1:

System type 2:

System type 1:

System type 2:

Two indirectly connected weather compensated


heating systems

Two directly connected weather compensated


heating systems

Indirectly connected heating system and DHW circuit

Direcly connected heating system and DHW circuit

System type 3:
Indirectly connected weather compensated heating
system with additional mixing circuit

26

27

C67

ECL Comfort 300


Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation for two
independent heating circuits. Constant

temperature control of the secondarily


connected DHW circuits with storage
tank with built-in heating coil. Optional
ON/OFF control of DHW circuits in

connection with primarily connected


storage tank with built-in heating coil.
Please note: Relay module ECA 80 is a
necessary accessory!

C67

ECL Comfort 300


Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation for two
independent heating circuits. Constant

temperature control of the secondarily


connected DHW circuits with storage
tank with built-in heating coil. Optional
ON/OFF control of DHW circuits in

connection with primarily connected


storage tank with built-in heating coil.

System type 1:

System type 1a:

System type 4:

System type 4a:

Two indirectly connected heating systems and secondarily


connected storage tank with built-in heating coil (optional
DHW priority)

Two indirectly connected heating systems and secondarily


connected storage tank with built-in heating coil (DHW
priority)

Indirectly connected heating system with or without mixing


circuit and secondarily connected storage tank with built-in
heating coil (DHW priority)

Indirectly connected heating system with or without mixing


circuit and secondarily connected storage tank with built-in
heating coil (DHW priority)

System type 2:

System type 3:

System type 5:

System type 5a:

Two indirectly connected heating systems and primarily


connected storage tank with built-in heating coil (optional
DHW priority)

Indirectly connected heating system with or without mixing


circuit and primarily connected storage tank with built-in
heating coil (optional DHW priority)

Indirectly connected heating system with or without mixing


circuit and secondarily connected DHW storage charging
system (optional DHW priority)

Indirectly connected heating system with or without


mixing circuit and secondarily connected DHW storage
charging system (DHW priority)

28

29

C75

ECL Comfort 300


Multistage boiler controller with
constant temperature control of DHW
circuits and weather compensated flow

ECL Comfort Master / Slave Applications

control of a mixed and an unmixed


heating circuit. Please note: Relay
module ECA 80 is a necessary accessory!

System type 1:

System type 2a:

System type 1:

2-stage boiler control of a mixed and an unmixed heating


circuit and constant temperature control of the DHW circuit

3-stage boiler control of a mixed and an unmixed heating


circuit and constant temperature control of the DHW circuit

Example of connection of more (with address) ECL Comfort


controllers on the same BUS. The advantage is that only one
outdoor temperature sensor has to be connected to the

System type 2b:

System type 3:

3-stage boiler control of a mixed and an unmixed heating


circuit and constant temperature control of the DHW circuit

2-stage boilers with radiator circuit, mixing circuit


and DHW circuit

master. Via the BUS, the outdoor temperature signal,


time and date are sent to the slaves.

In the example above, the master can be ECL Comfort 200 with P30
application or ECL Comfort 300 with C35 / C37 / C47 / C60 / C62 /
C66 / C67. One slave is ECL Comfort 300 with C37, another slave is
ECL Comfort 100M.

30

31

ECL Comfort Master / Slave Applications

Weather compensated flow temperature


control for heat pump system (up to 2
stages), additional heating circuit and

System type 2:
Example of connection of more (with address) ECL Comfort
controllers on the same BUS. The advantage is that only
one outdoor temperature sensor has to be connected to the
master. Via the BUS, the outdoor temperature signal, time and

date are sent to the slaves. The slaves (with address) send the
desired flow temperature to the master. The master ensures
that the highest demand from the slaves is met.

L05

ECL Comfort 301


temperature control for DHW circuit.
Please note: Relay module ECA 80 is
a necessary accessory!

System type 1:

System type 2:

Weather compensated 1-stage heat pump with additional


electrical heat for heating and DHW circuits (DHW priority)

Weather compensated 2-stage heat pump for heating


and DHW circuits (DHW priority)

System type 3:

System type 4:

Weather compensated 1-stage heat pump with additional


electrical heat for heating

Weather compensated 2-stage heat pump for heating

In the example above, the master is ECL Comfort 300 with C47.
The slaves are ECL Comfort 300 with C62.

32

33

L05

ECL Comfort 301


Weather compensated flow temperature
control for heat pump system (up to 2
stages), additional heating circuit and
temperature control for DHW circuit.

ECL Comfort 301


Weather compensated flow temperature
control for heat pump system (up to 2
stages), additional heating circuit and
temperature control for DHW circuit.

System type 5:

System type 6:

System type 9:

Weather compensated 1-stage heat pump with additional


electrical heat for heating mixing circuit and DHW circuit
(DHW priority operation)

Weather compensated 1-stage heat pump with additional


electrical heat for heating mixing circuit and DHW circuit
(DHW priority or parallel operation)

Weather compensated 1-stage heat pump with additional


solar heating for heating mixing circuit and DHW circuit
(DHW priority or parallel operation)

System type 7:

System type 8:

Weather compensated 2-stage heat pump with additional


electrical heat for mixing circuit and DHW circuit (priority
operation)

Weather compensated 1-stage heat pump or boiler control for


heating mixing circuit

34

L05

The heat pump can optionally be operated with a solar system.


If a solar system is chosen, the ECA 86 module must be used
(instead of the ECA 80 module).

35

L10

ECL Comfort 301


Flow temperature control for keeping
areas snow and ice free.

L32

ECL Comfort 301


Weather compensated flow temperature
control in combined heating and
cooling systems, typically floor systems.

In addition, dew point and slab


temperatures are considered.

System type 1:

System type 2:

System type 1:

System type 2:

Flow temperature control based on two outdoor temperature


ranges

Flow temperature control based on two outdoor temperature


ranges and boiler return temperature protection

Weather compensated heating / cooling considering


dew point and slab temperature (typical system)

Weather compensated heating. Room and slab temperature


sensors can be connected (simple system)

System type 3:

System type 3:

System type 3:

Flow temperature control based on two outdoor temperature


ranges and slab temperature control

Flow temperature control based on two outdoor temperature


ranges and snow/ice detector*

Weather compensated heating and cooling operation


irrespective of dew point and slab temperature
(minimum system)

* Devireg 850, product from DEVI A/S

36

37

L66

ECL Comfort 301


Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation and twin-

pump control. Constant temperature


control of DHW circuits with twinpump control.

Please note: Relay module ECA 80 is a


necessary accessory!

L76

ECL Comfort 301


Weather compensated flow temperature
control of two independent heating
systems with sliding return temperature

limitation. Constant temperature


control of DHW with flow switch
control.

System type 1:

System type 2:

System type 1:

System type 2:

Indirectly connected heating and DHW circuit

Directly connected heating circuit and


indirectly connected DHW circuit

Indirectly connected heating systems and DHW circuit with


flow switch control

Indirectly connected heating system and DHW circuit with


flow switch control

38

39

ECL Comfort

Code Numbers

ECL Comfort Cards and Instructions

Code Numbers

WebAccess accessories

1764

4692

4667

4686

4678

4668

4687

Czech

1762

Turkish

Russian

Hungarian

1765

Romanian

Slovenian

1754

Bulgarian

Estonian

1760

Croatian

Latvian

1761

Code
no.
087B-

ECL Comfort 100B (instructions only)


100B

1753

1750

1751

1752

ECL Comfort 100M (kit with ECL Card and instructions)


100M

1755

1756

1768

1758

1766

1767

1759

1763

ECL Comfort 200 (instructions only)


P16

4655

4663

4669

4693

4665

P17

4656

4664

4670

4679

4697

P20

4654

4660

4661

4662

P30

4650

4653

4657

4658

4677

4688

4675
4676

4651

4652

4674

4673

4671

4694

4843

4681

4666

4659

ECL Comfort 300 (kit with ECL card and instructions)

ECL Comfort accessories


ECA 60
ECA 61
ECA 62
ECA 63
ECA 80
ECA 82
ECA 84
ECA 86
ECA 87

Lithuanian

087B1188
087B1198

Dutch

WAH analog interface


WAS analog input, 4 channels

Swedish

087B1187
087B1194
087B1195
087B1196
087B1197

Spanish

WAH pulse interface


WAS digital input, 1 channel
WAS digital input, 2 channels
WAS digital input, 3 channels
WAS digital input, 4 channels
Analog

1757

Polish

Type
WebAccess

French

Code no.
087B1173
087B1189
087B1174
087B1179

WebAccess

German

Designation
WebAccess kit incl. 1 LON module and transformer
WebAccess kit with GSM modem incl. 1 LON module and transformer
LON extension module
WAS energy measuring module
Digital

087B1154
087B1149
087B1148
087B1145

English

Code no.
087B1100
087B1110
087B1120
087B1124
087B1130
087B1134
087B1131
087B1834
087B1835
087B1836

Finnish

ECL Comfort 100B/100M


ECL Comfort 200/300/301
ECL Comfort
ECL Comfort

Designation
Universal hardware - 230 V a.c.
Universal hardware - 230 V a.c.
Universal hardware - 230 V a.c.
Universal hardware - 24 V a.c.
Universal hardware - 230 V a.c.
Universal hardware - 24 V a.c.
Universal hardware - 230 V a.c. with 2 additional pulse connectors for heat meter
Universal hardware - 230 V a.c.
Universal hardware - 230 V a.c. with 2 additional pulse connectors for heat meter
Universal hardware - 230 V a.c. with 2 additional analog inputs and 2 analog
outputs
Socket for wall mounting
Socket for wall mounting
Connector set for panel mounting
Mounting kit for DIN rail

Danish

Type
ECL Comfort 100B
ECL Comfort 100M
ECL Comfort 200
ECL Comfort 200
ECL Comfort 300
ECL Comfort 300
ECL Comfort 300 with ECA 88
ECL Comfort 301
ECL Comfort 301 with ECA 88
ECL Comfort 301 with ECA 83

Language

ECL Comfort controllers and enclosures

Room panel with sensor


Remote control with 1 zone clock and sensor
Room panel with sensors (C and % RH)
Remote control with sensors (C and % RH)
Relay module - 2 x SPCO
LON communication module
M-Bus communication module
Temperature monitoring and alarm module
RS 232 remote control and data log
Modem cable (1.5 m) for ECA 87
PC cable (1.5 m) for ECA 87

087B1140
087B1141
087B1169
087B1143
087B1150
087B1152
087B1155
087B1158
087B1160
087B1171
087B1172

ECA 99

24 V transformer, Lbke (35 VA)

087B1156

ECA 100

Analog clock for ECL Comfort 100

087B1147

ECA 9010

Override module (for controller time programs)

087B3081

C14

4769

4824

4789

4836

C25

4782

4770

4771

4772

C35

4761

4774

C37

4762

4758

4775

C47

4823

4821

4818

4783

4807

4809

4756

4778

4810

C55

4828

4837
4860

4798

4830
4801

C62

4819

4760

4842

C66

4753

4757

4780

4754

4820

4817

4764

4825

4827

4776

4813

4750

C67

4840

4812

C60

C75

4848

4863

4833

4751

4831

4800
4752

4802

4846

4829

4847

4826

4779

4805

4851

4781

4806

4853
4755

4845

4795

4794

4803

4852

ECL Comfort 301 (kit with ECL card and instructions)


L05
L32

4870
4854

4877
4873

L66
L76

4871
4878

4879

Example: Code no. for a C47 card in German is 087B4818.

Data sheets are available on www.heating.danfoss.com under Documentation.

40

41

ECL Apex 10

ECL Apex 10 and ECA-XM Modules

Code Numbers

The ECL Apex 10 is a configurable


controller for temperature control in
district heating systems.

Example 1:

Example type 2:

Indirectly connected heating circuit with flow/energy limiting,


twin-pumps and makeup water

Indirectly connected heating and DHW circuit with filter guard


and twin-pumps

Type
ECL Apex 10
ECA-XM 101A
ECA-XM 102A
ECA-XM 102B
ECA-XM 204A
ECA-XM 204B
ECA-XM 205A
ECA-XM 205B
ECA-XM 210A
ECA-OB 003A

Designation
Main controller: 11 analog inputs, 4 digital outputs (relays) and 2x2 triac outputs
Extension module: 8 analog inputs
Extension module: 8 digital inputs for low voltage (galvanically separated)
Extension module: 8 digital inputs for high voltage (galvanically separated)
Extension module: 8 digital outputs (relays)
Extension module: 8 digital outputs (relays) with switches which allow each relay
to be controlled manually or automatically
Extension module: 8 analog inputs and 8 digital outputs (relays)
Extension module: 8 analog inputs and 8 digital outputs (relays) with switches
which allow each relay to be controlled manually or automatically
Extension module: M-Bus master (EN1434-3), 7 analog inputs, 2 digital inputs
for low voltage (for pulse input), 2 analog outputs (0 - 10 V) and 3 digital outputs
(relays)
Extension module: 2 analog outputs (0 - 10 V) with a resolution of 40 mV

Code no.
087B2500
087B2610
087B2620
087B2621
087B2740
087B2741

Designation
Service tool software for operation of the ECL Apex 10 controller (CD-ROM)
Cable between PC and ECL Apex 10 controller
Cable between PDA cable and ECL Apex 10 controller or
cable between null modem cable and ECL Apex 10 controller
24 V transformer, Lbke (35 VA)

Code no.
087B2510
080Z0262
080Z0261

087B2750
087B2751
087B2760
087B2530

ECL Apex 10 accessories


Type
ECA-ST 101A
ECA 99

087B1156

Temperature sensors for ECL Comfort and ECL Apex 10


Example 3:

Example 4:

Indirectly connected heating systems and DHW circuit with


flow registration

Indirectly connected heating circuit with flow/energy limiting,


twin-pumps and markup water and indirectly connected 2stage DHW circuit.

Pt 1000 (1000 / 0 oC)


Type
ESMT
ESM-10
ESM-11
ESMB-12
ESMC
ESMU-100
ESMU-250
ESMU-100
ESMU-250

Designation
Outdoor temperature sensor
Room temperature sensor
Surface sensor
Universal sensor with 2.5 m cable
Surface sensor with 2 m cable
Immersion sensor, 100 mm, copper
Immersion sensor, 250 mm, copper
Immersion sensor, 100 mm, stainless steel
Immersion sensor, 250 mm, stainless steel

Code no.
084N1012
087B1164
087B1165
087B1184
087N0011
087B1180
087B1181
087B1182
087B1183

Designation
Immersion, stainless steel 100 mm, for ESMU-100, Cu (087B1180)
Immersion, stainless steel 250 mm, for ESMU-250, Cu (087B1181)
Immersion, stainless steel 100 mm, for ESMB-12 (087B1184)
Immersion, stainless steel 250 mm, for ESMB-12 (087B1184)

Code no.
087B1190
087B1191
087B1192
087B1193

Sensor pockets
Type
Pocket
Pocket
Pocket
Pocket

Data sheets are available on www.heating.danfoss.com under Documentation.

42

43

A Comprehensive Range of Electronic


Controllers and Motorized Control Valves

As a result of the strong commitment


of Danfoss to innovation and product
development, your demands will be
met in the best possible way.
These continuous development eorts
have formed the basis of our range of
electronic controllers and motorized
controls valves which performs perfectly
in combination or independently in an
application.

Danfoss A/S DK-6430 Nordborg Denmark Tel.: +45 74 88 22 22 Fax: +45 74 49 03 95


Homepage: www.heating.danfoss.com E-mail: heating@danfoss.com