Professional Documents
Culture Documents
Faculty of Electrical and Electronics Engineering, HCMC University of Technology and Education, 1 Vo Van Ngan Str., Thu Duc Dist., Ho Chi Minh City, Viet Nam
Dong An Polytechnic, 30/4 Str., Di An Dist., Binh Duong Province, Viet Nam
Ha Noi University of Technology, 1 Dai Co Viet Str., Ha Noi, Viet Nam
a r t i c l e
i n f o
Article history:
Received 4 September 2015
Received in revised form 3 December 2015
Accepted 17 December 2015
Keywords:
Distribution network reconfiguration
Distributed generator
Adaptive cuckoo search algorithm
Power loss reduction
Voltage stability enhancement
a b s t r a c t
This paper proposes a new methodology to optimize network topology and placement of distributed generation (DG) in distribution network with an objective of reduction real power loss and voltage stability
enhancement. A meta-heuristic cuckoo search algorithm (CSA) inspired from the obligate brood parasitism of some cuckoo species which lay their eggs in the nests of other birds of other species for solving
optimization problems is adapted to simultaneously reconfigure and identify the optimal location and
size of DG units in a distribution network. The graph theory is used to determine the search space which
reduces infeasible network configurations of reconfiguration process and check the radial constraint of
each configuration of distribution network. The effectiveness of the proposed method has been validated
on three different distribution network systems at seven different scenarios. The obtained results show
well the effectiveness and performance of the proposed method in distribution network reconfiguration
with optimal location and size of DG problems.
2015 Elsevier Ltd. All rights reserved.
Introduction
A distribution network is the last stage in delivery of electric
power. It carries electricity from the transmission system to consumers. Distribution systems usually have high system losses
and poor voltage regulation because of the high current and low
voltage level in distribution systems [1,2]. In addition, due to the
rapid expansion of distribution networks, the voltage stability of
distribution systems has become an important issue. Therefore,
many efforts have been made to decrease the losses and improve
the voltage stability in distribution systems. Network reconfiguration and distributed generator placement are among those efforts
to mitigate this problem [3].
Distribution network reconfiguration (DNR) is the process of
varying the topology of distribution network by changing the
closed/open status of sectionalizing and tie switches while respecting system constraints upon satisfying the operators objectives
[4]. The first publication about the DNR problem was presented
by Merlin and Back [5]. They solved DNR problem through a
Corresponding author at: Dong An Polytechnic, 30/4 Str., Di An Dist., Binh
Duong Province, Viet Nam. Tel.: +84 0916664414.
E-mail address: thuan.dap@gmail.com (T.T. Nguyen).
http://dx.doi.org/10.1016/j.ijepes.2015.12.030
0142-0615/ 2015 Elsevier Ltd. All rights reserved.
802
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
Nomenclature
Prec
loss
P0loss
Nbr
Nbus
NDG
Pi
Qi
Vi
PDgmax,i
Vmin
Vmax
Ii
Imax,i
Rk
Xk
Problem formulation
Objective functions
One of the main advantages of the optimal network reconfiguration and DG installation is the reduction in power loss. The net
power loss reduced (DP Rloss ) is taken as the ratio of total power loss
before and after the reconfiguration considering DGs of the system:
DPRloss
Prec:
loss
P0loss
The total power loss of the system is determined by the summation of losses in all line sections:
Ploss
Nbr
X
P2i Q 2i
Ri
V 2i
i1
VSIk1 jV k j4 4Pk1 X k Q k1 Rk 2
4Pk1 Rk Q k1 X k jV k j2
where Pi+1, Qi+1 are total real power and reactive power load fed
through node (k + 1), respectively.
If the VSI for each bus is higher, the stability of that relevant
node shall be better. In distribution network reconfiguration considering DGs, the voltage stability deviation index (DVSI) can be
defined as follows:
DVSI max
1 VSIi
8i 2; . . . Nbus
1
Vk
Vk+1
Ik
kth branch
Rk+jXk
Sending node
Receiving node
Pk+1 + jQ k+1
803
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
The proposed objective function (F) of the problem is formulated to minimize the total power loss and voltage stability
deviation index. The objective function can be described as
follows:
Constraints
Each proposed configuration in DNR considering DGs process,
the power flow analysis should be carried out to calculate the voltage stability index, power loss of system and current of each
branch. The constraints of objective function are as follows:
(1) The computed voltages and currents should be in their
premising range for the proposed configuration.
V min 6 V i 6 V max ;
0 6 Ii 6 Imax;i ;
I 1; 2; . . . Nbus
i 1; 2; . . . Nbr
6
7
(2) The radial nature of distribution network must be maintained and all loads must be served.
(3) Distributed generation capacity limits:
0 6 PDGi 6 PDGmax;i ;
i 1; 2; . . . NDG
1
s4
s1
s3
5
s13
s14
s8
s16
s9
10
s15
s11
12
s12
s2
11
s6
s7
6
s5
In the conventional CSA, the initial population is randomly created, which consists of a large number of infeasible individuals violating the radial constraint, particularly in medium/large
distribution networks. In the proposed ACSA, these infeasible individuals are reduced by using graph theory. A distribution network
can be represented with a graph that contains a set of branches B
and a set of nodes N. They are presented by connection matrix A,
which has one row for each branch and one column for each node.
In this matrix if any branch i is directed away from node j, element
14
s10
13
804
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
problem with simultaneous DG allocation, the first part of the solution vector is taken as the number of open branches in the distribution network, and the second part is the number of buses chosen for
DG installation and the third part is the sizes of DGs. Thus the solution vector for simultaneous reconfiguration and DG installation
considering their location and size is formed as follows:
h
i
i
i
X i Tie1 ; . . . ; TieNO ; Lo:DGi1 ; . . . ; Lo:DGim ; Size:DGi1 ; . . . ; Size:DGim
9
where Tie1, Tie2, . . . , TieNO are open branches in the fundamental
loops FL1 to FLNO formed corresponding to the tie lines; Lo.DG1, Lo.
DG2, . . . , Lo.DGm are the buses for DG installation; and Size.DG1,
Size.DG2, . . . , Size.DGm are sizes of DG units (MW) to be installed
at buses respectively. NO and m are the number of tie lines and
the number of DGs, respectively.
In the ACSA, each egg can be regarded as a solution which is
randomly generated in the initialization. Therefore, each nest i of
the population is randomly initialized as follows:
805
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
h
i
i
i
i
Tiei round Tielower;d1 rand Tieupper;d1 Tielower;d1
h
i
Lo:DGi round Loilower;d2 rand Loiupper;d2 Loilower;d2
h
i
i
i
i
Size:DGi Sizelower;d3 rand Sizeupper;d3 Sizelower;d3
11
12
new
new
X new
roundX new
d
d1 ; roundX d2 ; X d3
10
Except for the best nest, all the other nests are replaced based
on the quality of new cuckoo eggs which are generated by Lvy
flights from their position as follows:
X new
Xbest d a rand DX new
d
d
randx
jrandy j
1=b
rx b
Xbesti Gbesti
ry b
14
where randx and randy are two normally distributed stochastic variables with standard deviation rx b and ry b given by:
31=b
C1 b sinp2b5
rx b 4
ry b 1
b1
C1b
b 2
2
lim
Tied1
8
Tielower;d1
>
>
>
<
Tieupper;d1
>
>
>
:
Tied1
Lo:DGlim
d2
18
otherwise
8
2
>
>
>
<
Loupper;d2
>
>
>
:
Lo:DGd2
if Lo:DGd1 < 2
if Lod2 > Loupper;d2
19
otherwise
8
>
< Sizelower;d3
Sizeupper;d3
>
:
Size:DGd3
20
otherwise
13
DX new
The limits for each tie-line, location of each DG and power are
determined as follows:
Size:DGlim
d3
17
15
X new
Xbesti K DX new
i
i
where K is the updated coefficient determined based on the probability of a host bird to discover an alien egg in its nest:
K
16
21
if rand < Pa
0; otherwise
22
DX new
rand randp1 Xbesti randp2 Xbesti
i
23
806
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
new
new
X new
roundX new
d
d1 ; roundX d2 ; X d3
17
For the new solution, its lower and upper limits should be satisfied according to their limits by using Eqs. (18)(20).
Based on the new population of the nests, the radial topology
checking algorithm is run to check the nests. Then, the fitness values are calculated by the power flows using NewtonRaphson
method to find the best value of each nest Xbestd and the nest corresponding to the best fitness value is set to the best nest Gbest.
807
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
Table 1
Fundamental loops of the 33-bus system.
24
FL1
FL2
FL3
FL4
The 33-bus distribution system, which is a small-scale distribution networks, includes 37 branches, 32 sectionalizing switches
and 5 tie switches. The line and load data of this system are taken
from [29]. The total real and reactive power loads of the system are
3.72 MW and 2.3 MVAr, respectively. Fig. 7 shows the single line
diagram of this network. The parameters of ACSA algorithm used
in the simulation of network are number of nets Np = 30, probability of an alien egg to be discovered Pa = 0.2, number of iterations
Itermax = 2000.
Fundamental loops of the network are obtained by the finding
fundamental loop algorithms as given in Table 1. The performance
of the proposed method is presented in Table 2. From Table 2, it
can be seen clearly that in the initial case, power loss (kW) in the
system is 202.68, which is reduced to 139.98, 74.26, 58.79, 62.98,
63.69, and 53.21 using scenarios 2, 3, 4, 5, 6, and 7, respectively.
The percentage power loss reduction for scenario 27 is 30.93,
63.26, 71.0, 68.93, 68.58, and 73.75, respectively. It can be also
seen from Table 2 that, the minimum voltage magnitude of the system is improved remarkably in all the scenarios. In the base case,
the minimum voltage magnitude is improved from 0.9108 p.u. to
0.9413, 0.9778, 0.9802, 0.9826, 0.9786, and 0.9806 p.u. for using
case 2 to case 7. In addition, the VSI is also improved from
0.6978 to 0.7878, 0.9118, 0.9264, 0.9354, 0.9202, and 0.9318 by
23
Tie-line
FL5
23
Fundamental
loop
25
24
37
26
27
26
22
29 30
28
27
28
29
31
30
32
31
25
1
2
1
3
2
18
8
7
11
10
9
9
10
12
11
13
12
33
19 20
19
21
20
22
21
36
32
34
64 7
5
33
35
Fig. 7. IEEE 33-bus test system.
15 16
14
13
14
15
17
16
18
17
808
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
Table 2
Performance analysis of proposed method on the 33-bus system.
Scenario
Item
Proposed ACSA
FWA [19]
HSA [18]
Switches opened
Power loss (kW)
Minimum voltage (p.u.)
Minimum VSI
Switches opened
Power loss (kW)
% Loss reduction
Minimum voltage (p.u.)
Minimum VSI
7, 14, 9, 32, 28
139.98
30.93
0.9413
7, 14, 9, 32, 37
138.06
31.88
0.9342
Switches opened
Size of DG in MW (Bus number)
33, 34,
0.7798
1.1251
1.3496
74.26
63.26
0.9778
0.9118
33, 34,
0.5897
0.1895
1.0146
88.68
56.24
0.9680
33, 34,
0.1070
0.5724
1.0462
96.76
52.26
0.9670
Switches opened
Size of DG in MW (Bus number)
Switches opened
Size of DG in MW (Bus number)
Switches opened
Size of DG in MW (Bus number)
Simultaneous Reconfiguration, DG
installation and location of DG
(Scenario 7)
35, 36, 37
(14)
(24)
(30)
35, 36, 37
(14)
(18)
(32)
7, 14, 9, 32, 28
1.7536 (29)
0.5397 (12)
0.5045 (16)
58.79
71.00
0.9802
0.9264
7, 14, 9, 32, 28
0.5996 (32)
0.3141 (33)
0.1591 (18)
83.91
58.59
0.9612
7, 14, 9, 32, 37
0.2686 (32)
0.1611 (31)
0.6612 (30)
97.13
52.07
0.9479
33, 9, 8, 36, 27
0.7798 (14)
1.1251 (24)
1.3496 (30)
62.98
68.93
0.9826
0.9354
7, 34, 9, 32, 28
0.5897 (14)
0.1895 (18)
1.0146 (32)
68.28
66.31
0.9712
1
0.99
Voltage (p.u.)
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0.91
Case 1
Case 2
Case 3
Case 4
Case 5
Case 6
Case 7
10
35, 36, 37
(18)
(17)
(33)
15
20
25
Node No.
Fig. 8. Comparison of node voltages of 33-bus system.
30
33
809
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
1
0.95
VSI
0.9
0.85
Case 1
Case 2
Case 3
Case 4
Case 5
Case 6
Case 7
0.8
0.75
0.7
0
10
15
20
25
30
33
Node No.
Fig. 9. Comparison of VSI-nodes of 33-bus system.
1
0.9
Fitness value
0.8
0.7
0.6
0.5
0.4
0.3
200
400
600
800
1000
1200
1400
1600
1800
2000
Iterations
Fig. 10. Comparison of 33-bus system indices for scenarios in fitness function.
29
28
29
48
28
47
31
30
47
32
30
32
31
49
48
33
35
33
34
50
72
56
49
53
54
55
54
53
27
34
55
66
46
58
57
56
57
59
4
2
5
4
7
7
50
52
35
9 10
8
36
37
38
39
38
40
11
69
41
42
41
43
42
65
64
63
64
70
67
51
40
39
63
62
73
11 12
10
51
36 37
62
61
66
65
61
60
67
52
1
60
59
58
43
13 14
12
13
68
69
15 16
14 15 16
18 19
17 18 19
71
68
44
45
44
17
46
45
20
21 22
20
21
23
24 25
26
22 23 24 25 26
27
810
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
Table 3
Fundamental loops of the 69-bus system.
Fundamental
loop
Tie-line
FL1
FL2
FL3
FL4
FL5
as given in Table 3. This test system is also simulated for seven scenarios and the results are presented in Table 4. It is observed from
Table 4, base case power loss (in kW) in the system is 224.89 which
is reduced to 98.59, 72.44, 37.23, 41.13, 40.49, and 37.02 using scenarios 2, 3, 4, 5, 6, and 7, respectively. The percentage loss reduc-
Table 4
Performance analysis of proposed method on the 69-bus system.
Scenario
Item
Proposed ACSA
FWA [19]
HSA [18]
Switches opened
Power loss (kW)
Minimum voltage (p.u.)
Minimum VSI
Switches opened
Power loss (kW)
% Loss reduction
Minimum voltage (p.u.)
Minimum VSI
Switches opened
Size of DG in MW (Bus number)
0.1018 (65)
0.3690 (64)
1.3024 (63)
86.77
61.43
0.9677
69, 18,
1.0666
0.3525
0.4257
51.3
77.2
0.9619
69, 17,
1.0666
0.3525
0.4257
40.3
82.08
0.9736
Switches opened
Size of DG in MW (Bus number)
Switches opened
Size of DG in MW (Bus number)
Switches opened
Size of DG in MW (Bus number)
Switches opened
Size of DG in MW (Bus number)
13, 56, 61
(61)
(60)
(58)
13, 58, 61
(61)
(60)
(62)
811
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
1
0.99
Voltage (p.u.)
0.98
0.97
0.96
0.95
Case 1
Case 2
Case 3
Case 4
Case 5
Case 6
Case 7
0.94
0.93
0.92
0.91
10
20
30
40
50
60
69
Node No.
Fig. 12. Comparison of node voltages of 69-bus system.
1
0.95
VSI
0.9
0.85
Case 1
Case 2
Case 3
Case 4
Case 5
Case 6
Case 7
0.8
0.75
0.7
0
10
20
30
40
50
60
69
Node No.
Fig. 13. Comparison of VSI-nodes of 69-bus system.
0.9
Fitness value
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0
200
400
600
800
1000
1200
1400
1600
1800
2000
Iterations
Fig. 14. Comparison of 69-bus system indices for scenarios in fitness function.
812
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
s12
s11
s10
s18
s17
s9
s19
19
18
s3
s4
s5
s6
s7
s27
s20
38
s29 s30
29
s21
17
s119
s22
22
s39
s31
23
s41
s33
36
s34
43
s46
35
s123
34
s55
s56
56
s57
s89
89
s88
s66
67
s78
s79
78
s90
s48
s121
46
s49
49
s50
s51
51
50
s52
52
s53
53
54
s122
79
s85
s59
s68
61 s61 62
s97
s93
s70
s71
68
69
70
71
s80
s81
s82
s83
80
82 83
81
s87 s87
99
s128
s94
95
94
93
s69
s98
98
97
96
92
s60
60
s91 s92
91
90
s67
65 s65 66
s77
s45
45
48
59
s125
s96
s95
s62
s99
s47
47
s58
57 58
64
s44
44
37
55
63
27
26 s26
s118
s42 s43
42
41
s32
s54
s63 s64
s25
25
s132
s40
40
39
s0
s24
24
s124
31 32
33
s35
s36
30
s23
s120
9
s38
s28
s16
16
21
20
s37
28
s15
15
s8
s2
s1
s14
14
11
10
s13
13
12
s72
72
s126
s73
73
s74
74
s75
75
76 s76
77
s84
84
85
s127
86
88
87
s129
s130
s100 s101 s102 s103 s104 s105 s106 s107 s108 s109 s111 s112
100
s113
101
102
103
104 105
106
107
108
115 116
117
118
s131
113
111
Table 5
Fundamental loops of the 119-bus system.
Fundamental loop
Tie-line
FL1
FL2
FL3
FL4
FL5
FL6
FL7
FL8
FL9
FL10
FL11
FL12
FL13
FL14
FL15
3, 9, 10, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 37, 38, 39, 40, 41, 42, 43, 44, 45, 118
11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 119
3, 4, 5, 6, 7, 9, 10, 17, 18, 19, 20, 21, 22, 23, 120
29, 30, 31, 32, 33, 34, 37, 38, 39, 40, 41, 42, 46, 47, 48, 49, 50, 51, 52, 53, 121
29, 30, 31, 32, 33, 34, 46, 47, 48, 49, 50, 51, 52, 53, 54, 55, 56, 57, 58, 59, 60, 61, 122
29, 35, 36, 54, 55, 56, 57, 58, 59, 60, 61, 123
4, 5, 6, 7, 8, 27, 28, 37, 38, 39, 124
1, 3, 27, 28, 54, 55, 56, 57, 62, 63, 64, 88, 89, 90, 95, 125
65, 66, 67, 68, 69, 70, 71, 72, 88, 89, 90, 126
64, 65, 66, 67, 68, 69, 70, 71, 72, 73, 74, 77, 78, 85, 86, 87, 127
65, 66, 67, 68, 69, 70, 71, 72, 73, 74, 75, 76, 88, 89, 90, 95, 96, 97, 98, 128
62, 63, 77, 78, 79, 80, 81, 82, 99, 100, 101, 102, 103, 104, 105, 106, 107, 129
62, 63, 77, 78, 85, 99, 100, 101, 102, 103, 104, 130
100, 101, 102, 103, 104, 105, 106, 107, 108, 109, 113, 114, 115, 116, 117, 131
3, 9, 10, 17, 18, 19, 20, 21, 22, 23, 24, 27, 28, 29, 30, 31, 32, 33, 34, 132
and 15 tie switches as shown in Fig. 15. The total power loads
are 22709.7 kW and 17041.1 kVAr [31]. The parameters of ACSA
algorithm used in the simulation of network are number of nets
Np = 30, probability of an alien egg to be discovered Pa = 0.2.
Because the number of variables need to optimize in scenario 6
and scenario 7 are 18 and 21, respectively compared with 15, 6,
6, and 15 in scenarios 2, 3, 4 and 5, respectively. Thus, to ensure
the obtained solutions are minimum, the number of iterations
813
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
Table 6
Performance analysis of proposed method on the 119-bus system.
Scenario
Item
Proposed ACSA
Switches opened
Power loss (kW)
Minimum voltage (p.u.)
Minimum VSI
118, 119, 120, 121, 122, 123, 124, 125, 126, 127, 128, 129, 130,
131, 132
1273.45
0.8678
0.5676
Switches opened
Power loss (kW)
% Loss reduction
Minimum voltage (p.u.)
Minimum VSI
42, 25, 23, 121, 50, 58, 39, 95, 71, 74, 97, 129, 130, 109, 34
855.04
32.86
0.9298
0.7535
Switches opened
118, 119, 120, 121, 122, 123, 124, 125, 126, 127, 128, 129, 130,
131, 132
3.2664 (71)
3.1203 (109)
2.86267 (50)
648.10
49.11
0.9515
0.8199
Size of DG in MW (Bus
number)
Power loss (kW)
% Loss reduction
Minimum voltage (p.u.)
Minimum VSI
DG installation after reconfiguration (Scenario 4)
Switches opened
Size of DG in MW (Bus
number)
Power loss (kW)
% Loss reduction
Minimum voltage (p.u.)
Minimum VSI
Switches opened
Size of DG in MW (Bus
number)
Power loss (kW)
% Loss reduction
Minimum voltage (p.u.)
Minimum VSI
Switches opened
Size of DG in MW (Bus
number)
Power loss (kW)
% Loss reduction
Minimum voltage (p.u.)
Minimum VSI
Switches opened
Size of DG in MW (Bus
number)
Power loss (kW)
% Loss reduction
Minimum voltage (p.u.)
Minimum VSI
42, 25, 23, 121, 50, 58, 39, 95, 71, 74, 97, 129, 130, 109, 34
1.7145 (111)
1.7565 (96)
5 (65)
631.19
50.43
0.9526
0.8208
42, 25, 21, 121, 122, 58, 39, 125, 70, 127, 128, 129, 85, 131, 33
3.2664 (71)
3.1203 (109)
2.86267 (50)
613.79
51.80
0.9608
0.8523
42, 25, 23, 121, 50, 61, 39, 125, 126, 70, 75, 129, 130, 109, 34
2.9585 (75)
0.1924 (76)
1.3397 (77)
682.09
46.44
0.9298
0.7535
42, 25, 22, 121, 122, 58, 39, 125, 70, 127, 128, 81, 130, 131, 33
2.5331 (50)
3.6819 (109)
3.7043 (73)
586.24
53.96
0.9644
0.8700
Table 7
Comparison of simulation results for 119-node network in Scenario 2.
Methods
Open Switches
Delta P (kW)
Vmin (p.u.)
Initial
Proposed ACSA
ITS [31]
MTS [26]
CSA [4]
FWA [32]
119, 120, 121, 122, 123, 124, 125, 126, 127, 128, 129, 130, 131, 132, 133
42, 25, 23, 121, 50, 58, 39, 95, 71, 74, 97, 129, 130, 109, 34
42, 26, 23, 51, 122, 58, 39, 95, 71, 74, 97, 129, 130, 109, 34
42, 26, 23, 51, 122, 58, 39, 95, 71, 74, 97, 129, 130, 109, 34
42, 25, 23, 121, 50, 58, 39, 95, 71, 74, 97, 129, 130, 109, 34
42, 25, 23, 121, 50, 58, 39, 95, 71, 74, 97, 129, 130, 109, 34
1273.45
855.04
867.4
867.4
855.04
855.04
0.8678
0.9298
0.9323
0.9323
0.9298
0.9298
selected for scenario 6 and 7 are Itermax = 5000 and Itermax = 2000
for the rest of scenarios.
The fundamental loops of the network are obtained by the
finding fundamental loop algorithms as given in Table 5. Table 6
show the results obtained from proposed method for seven
scenarios. It can be seen from Table 6, base case power loss (in
kW) in the system is 1273.45 which is reduced to 855.04,
648.10, 631.19, 613.79, 682.09, and 586.24 using scenarios 2, 3,
4, 5, 6, and 7, respectively. The percentage loss reduction for
scenario 27 is 32.86, 49.11, 50.43, 51.80, 46.44, and 53.96,
814
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
Voltage (p.u.)
0.98
0.96
0.94
0.92
Case 1
Case 2
Case 3
Case 4
Case 5
Case 6
Case 7
0.9
0.88
0
20
40
60
80
100
118
Node No.
Fig. 16. Comparison of node voltages of 119-bus system.
1
0.95
0.9
VSI
0.85
0.8
0.75
Case 1
Case 2
Case 3
Case 4
Case 5
Case 6
Case 7
0.7
0.65
0.6
0.55
20
40
60
80
100
118
Node No.
Fig. 17. Comparison of VSI-nodes of 119-bus system.
1.8
Fitness Value
1.6
1.4
1.2
1
0.8
0.6
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Iteration
Fig. 18. Comparison of performance of ACSA in six scenarios for minimization of the 119-bus system.
T.T. Nguyen et al. / Electrical Power and Energy Systems 78 (2016) 801815
815
[8] Souza SSF, Romero R, Franco JF. Artificial immune networks Copt-aiNet and
Opt-aiNet applied to the reconfiguration problem of radial electrical
distribution systems. Electr Power Syst Res 2015;119:30412.
[9] Esmaeilian HR, Fadaeinedjad R. Distribution system efficiency improvement
using network reconfiguration and capacitor allocation. Int J Electr Power
Energy Syst 2015;64:45768.
[10] Hung DQ, Mithulananthan N, Bansal RC. An optimal investment planning
framework for multiple distributed generation units in industrial distribution
systems. Appl Energy 2014;124:6272.
[11] Doagou-Mojarrad H, Gharehpetian GB, Rastegar H, Olamaei J. Optimal
placement and sizing of DG (distributed generation) units in distribution
networks by novel hybrid evolutionary algorithm. Energy 2013;54:12938.
[12] Murty VVSN, Kumar A. Optimal placement of DG in radial distribution systems
based on new voltage stability index under load growth. Int J Electr Power
Energy Syst 2015;69:24656.
[13] Mohamed IA, Kowsalya M. Optimal size and siting of multiple distributed
generators in distribution system using bacterial foraging optimization.
Swarm Evol Comput 2014;15:5865.
[14] Ugranli F, Karatepe E. Multiple-distributed generation planning under load
uncertainty and different penetration levels. Int J Electr Power Energy Syst
2013;46(1):13244.
[15] Kayal P, Chanda CK. Placement of wind and solar based DGs in distribution
system for power loss minimization and voltage stability improvement. Int J
Electr Power Energy Syst 2013;53:795809.
[16] Ameli A, Shahab B, Farid K, Mahmood-Reza H. A multiobjective particle swarm
optimization for sizing and placement of DGs from DG Owners and
distribution companys viewpoints. IEEE Trans Power Deliv 2014;29
(4):183140.
[17] Tan S, Xu JX, Panda SK. Optimization of distribution network incorporating
distributed generators: an integrated approach. IEEE Trans Power Syst
2013;28(3):242132.
[18] Rao RS, Ravindra K, Satish K, Narasimham SVL. Power loss minimization in
distribution system using network reconfiguration in the presence of
distributed generation. IEEE Trans Power Syst 2013;28(1):19.
[19] Mohamed Imran A, Kowsalya M, Kothari DP. A novel integration technique for
optimal network reconfiguration and distributed generation placement in
power distribution networks. Int J Electr Power Energy Syst 2014;63:46172.
[20] Yang XS, Deb S. Cuckoo search via Lvy flights. In: 2009 world congress on
nature and biologically inspired computing, NABIC 2009 proceedings; 2009.
p. 2104.
[21] Balasubbareddy M, Sivanagaraju S, Suresh CV. Multi-objective optimization in
the presence of practical constraints using non-dominated sorting hybrid
cuckoo search algorithm. Eng Sci Technol Int J 2015;18(4):60315.
[22] Abd Elazim SM, Ali ES. Optimal power system stabilizers design via cuckoo
search algorithm. Int J Electr Power Energy Syst 2016;75:99107.
[23] Abdelaziz AY, Ali ES. Cuckoo search algorithm based load frequency controller
design for nonlinear interconnected power system. Int J Electr Power Energy
Syst 2015;73:63243.
[24] Dash P, Saikia LC, Sinha N. Comparison of performances of several FACTS
devices using Cuckoo search algorithm optimized 2DOF controllers in multiarea AGC. Int J Electr Power Energy Syst 2015;65:31624.
[25] Chakravorty M, Das D. Voltage stability analysis of radial distribution
networks. Int J Electr Power Energy Syst 2001;23(2):12935.
[26] Abdelaziz AY, Mohamed FM, Mekhamer SF, Badr MAL. Distribution system
reconfiguration using a modified Tabu search algorithm. Electr Power Syst Res
2010;80(8):94353.
[27] Gupta N, Swarnkar A, Niazi KR, Bansal RC. Multi-objective reconfiguration of
distribution systems using adaptive genetic algorithm in fuzzy framework. IET
Gener Transm Distrib 2010;4(12):1288.
[28] Dolatdar E, Soleymani S, Mozafari B. A new distribution network
reconfiguration approach using a tree model. World Acad Sci Eng Technol
2009;3(10).
[29] Baran ME, Wu FF. Network reconfiguration in distribution systems for loss
reduction and load balancing. IEEE Trans Power Deliv 1989;4(2):14017.
[30] Chiang H-D, Jean-Jumeau R. Optimal network reconfigurations in distribution
systems: Part 2: solution algorithms and numerical results. IEEE Trans Power
Deliv 1990;5(3):156874.
[31] Zhang D, Fu Z, Zhang L. An improved TS algorithm for loss-minimum
reconfiguration in large-scale distribution systems. Electr Power Syst Res
2007;77(56):68594.
[32] Mohamed Imran A, Kowsalya M. A new power system reconfiguration scheme
for power loss minimization and voltage profile enhancement using Fireworks
Algorithm. Int J Electr Power Energy Syst 2014;62:31222.