You are on page 1of 5

Digital Setting Meter Relay

Description

Features
Model SM series are a Potentiometer setting meter relays with dual Hi & Lo setting.
Multi-turns Potentiometer setting
The setters are used multi-turns resistive potentiometers as preset buffers which setting
Dual Hi & Lo setting
able to be read directly in display for switch selection. The input functions of the units are of
Wide input parameters & ranges
wide varieties & ranges, including many parameters of industry process and power system
Output with adjustable time delayer
as DCV, ACV, DCA, ACA, DC rate, temerature, Frequency, Speed, Load cell as standard
4 digits up to 9999 counts
products. For wide application, with some external transducers, the series can be extended
to a wider field application as watt, var, power factor & etc.
The unit provides four digits display up to 9999 counts with find resolution & the displays are of high rate-super bringhtness LED,
0.56 size.
Dual control outputs compliant Hi & Lo setting of SPDT relay contacts of an on-off control type. The outputs also comply delaying function
adjusted 0-30 seconds standardly & longer requirement for 0-60 or 0-120 secs based on specified request. Dead band also an option
availably is selectively & alternatively to time delayer.
Special design in meter front of an open-door type, it keeps convenience in presetting & protects setting to avoid undersired misschange
in field application.

Specification
Accuracy

Stability
Input burden
Display
Setting

Response time
Input over capability

Frequency
Control output

Comm. mode voltage


Impulse voltage
Operation condition
Storage condition
Power supply

0.1% fs 2 counts for DC related input


0.25% fs 2 counts for AC related input
0.25% fs 0.5J for temperature related input (cjc. error included)
0.25% fs 1 counts for frequency related input
Temperatue < 100 pm per J, 5-50J
Long term stability < 0.15% draft per year
1 Megaohms for DC or AC voltage input sensing
500 mV drop for DC current input
0.5 VA for AC current sensing
4 digits maximum 9999 counts, 0.56super rate LED
(1) Hi & Lo set standard, Hi-Hi set optional
(2) Hi comparator setting < meter input output relay energied
(3) Lo comparator setting > meter input output relay energied
(4) multi-turns potentiometer for each setting
(5) switchable display range for S1, S2 & M (input measured)
Analog conversion < 1 sec of average integration typically
Analog to Digital conversion 2 sample rate per second
Voltage maximum for 100V rms or 2 x full input which ever great
current input
DC version 2 times continuous, 10 times 2 sec., 25 times 0.5 sec.
AC version 3 times continuous, 10 times 30 seconds, 25 times 2 seconds
40-400 Hz AC related meters
Specified range for frequency related meters
(1) on-off control type
(2) relay contact output of spdt type for each setting
(3) capacity AC250V / 2A, AC125V / 3A, DC24V / 3A
(4) time delayer adjustable 0-30 sec. typically, 0-60, 0-120 sec. for option
(5) dead band for option alternatively & availably to time delayer
(6) output indication : led lamp energied in front panel
2KV rms 50/60 Hz 1 minute
4KV 1.2 x 50 us common mode test
Temperature 0-50J, 20-90% RH non-condensed
Temperature -10~70J
Standard AC 110/220V 50 / 60HZ 15%, < 5VA
Option DC 12V / 24V / 48V / 125V, <6 Watts

Order information
Order form of AC Voltage

Order form of AC Current

SMV

SMA

SMV

SMA

Vn
Input range
ratio input
R = X/100-110-115-120V
direct input
0 - 100 m V
0-1
V
0 - 10 V
0 - 100 V
0 - 600 V
custom specified

Pn
Vn

Aux. power

An
Pn

R
1
2
3
4
5
Y

AC110 / 220V
DC12V
DC24V
DC48V
DC125V

S
1
2
3
4

Input range
ratio input
R = X / 5A or 1A
direct input
0 - 10 m A
0 - 100 m A
0-1
A
0 - 10 A
0 - 20 A
custom specified

Pn
An

Aux. power

Pn

AC110 / 220V
DC12V
DC24V
DC48V
DC125V

S
1
2
3
4

R
1
2
3
4
5
Y

Note: specified R = .....

Note: specified R = .....

Order form of DC Voltage

Order form of DC Current

SMDV

SMDA

SMDV

SMDA

DVn Pn
Input range
ratio input
R = X / VX
direct input
0 - 100 m V
0-1
V
0 - 10 V
0 - 100 V
0 - 600 V
custom specified

DVn

Aux. power

DAn Pn
Pn

D
1
2
3
4
5
Y

Note: specified D = .....

AC110 / 220V
DC12V
DC24V
DC48V
DC125V

S
1
2
3
4

Input range
ratio input
R = X amp. / Vx mV
direct input
0-1
mA
0 - 10 m A
0 - 100 m A
0-1
A
0 - 10 A
custom specified

DAn

Aux. power

Pn

AC110 / 220V
DC12V
DC24V
DC48V
DC125V

S
1
2
3
4

S
1
2
3
4
5
Y

Note: specified S = .....

Order information
Order form of DC Process Rate
SME

SME

Standard calibration zero - full input vs 0-100% ( 99.99% )

En

Pn

Input voltage range


0 - 10 m V
0 - 100 m V
0-1 V
0-5 V
1-5 V
0 - 10 V
2 - 10 V
custom specified

En
11
12
13
14
15
16
17
Y

Input current
0-1
m
0-5
m
0 - 10 m
0 - 20 m
4 - 20 m
0 - 50 m
10 - 50 m

range
A
A
A
A
A
A
A

En
1
2
3
4
5
6
7

Auxiliary power
AC 1 1 0 V / 2 2 0 V
DC12V
DC24V
DC48V
DC125V

Pn
S
1
2
3
4

En
1
2
3
Y

Auxiliary power
AC 1 1 0 V / 2 2 0 V
DC12V
DC24V
DC48V
DC125V

Pn
S
1
2
3
4

Order form of Load cell type


SMB

standard calibrator

SMB

99.99%=full span

Vn

En

SensitivitymV/per volt
0.5 m V
1
mV
1.5 m V
2
mV
3
mV
5
mV
Custom specified

Pn
Vn
1
2
3
4
5
6
Y

Exciting voltage
5
mA
10 m A
12 m A
Specified

External accessory of PB transmitter required. ( for signal conditioning )

Order form of Temperature


SMT

U
Tn

Sensor Input range


Thermocouple
J
0 - 700.0 C
K
0 - 1000.0 C
E
0 - 800.0 C
T
0 - 400.0 C
N
0 - 1000.0 C
R
300 - 1600 C
S
300 - 1700 C
B
500 - 1700 C
RTD
P T 1 0 0 0 - 400.0 C
customer specified

Pn
Tn
J
K
E
T
N
R
S
B

C
C
C
C
C
C
C
C

P C
Y

Input range
0
0
0
0
0
600
600
900

1000.0
2200
1400
750.0
2200
3000
3200
3200

0 - 750.0

Tn

Auxiliary power

Pn

F
F
F
F
F
F
F
F

J F
KF
EF
TF
NF
C F
SF
BF

AC 1 1 0 / 2 2 0 V
DC12V
DC24V
DC48V
DC125V

S
1
2
3
4

PF

Operation
Setting function
Function

Measured status

Output status

Lead indicator

Hi - set

The measured input > setting

Controlled output relay energied

S1 on

Lo - set

The measured input < setting

Controlled output relay energied

S2 on

Input

Signal conditioner

A - D conversion

Diaplay

Controlled output / relay contacts


Switch

Comparator

Hi (S1)
SPDT

S1

S2
Lo (S2)

Te r m i n a l c o n n e c t i o n
Model : SMA SMV SMDA SMDV
SME SMB SMT ( Thermocouple type )
Com.
+
1
2
3
4
5
6
Input

AC110V
AC220V
Aux. Power
8

10

11

12

S1
S2
NO NC
NO NC
Controlled output / relay contact
Note : 1. SMB input accepting signal from accessory
PB input.
2. DC power option for terminal 5 & 6.

Dimension
U type

O type

Model : SMT ( RTD type )


RTD input
1
A

2
B

3
b

NO

S1

AC110V
AC220V
Aux. Power
9

NC

10

11

NO

S2

12

NC

Controlled output / relay contact

SM Series
New Hybrid Asic Designed Digital-Setting Instruments
a ting Lo
gic-Based Tec
hnolo
g y & Design
pora
Logic-Based
echnolo
hnolog
Incor por

S2 indicator
(relay energied)

S1 indicator

analog sign
LO-SET

S2 dead
band

S2 time
S2
delayer potentiometer

HI-SET

S2 M S1
selector

S1
S1 time
potentiometer delayer

S1 dead
bank

Span

Zero

Features
1. Hybrid ASIC design-application
specified integrated circuit
2. Digital-setting meter relays specifically
designed for the utilities industries,
power system measurements and
process instrumentation applications
3. Multi-turns-potentiometer setting
4. Dual Hi & Lo setting
5. Wide input parameters & ranges
6. Output with adjustable time delayer
7. 4 digits up to 9999 counts

Specification
1. Accuracy :
0.1% fs 2 counts for DC related input
0.25% fs 2 counts for AC related input
0.25% fs 0.5J for temperature
related input (cjc. error included)
0.25% fs 1 count for frequency
related input
2. Stability :
Temperature < 100 ppm perJ, 5-50J
Long term stability < 0.15% draft per
year
3. Display :
4 digits maximum 9999 counts, 0.56
super rate LED

4. Input burden :
1 Megaohms for DC or AC voltage
input sensing
500mV drop for DC current input
0.5VA for AC current sensing
5. Setting :
(1)Hi & Lo set standard, Hi-Hi set optional
(2)Hi comparator setting < meter input
output relay energied
(3)Lo comparator setting > meter input
output relay energied
(4)multi-turns potentiometer for each
setting
(5)switchable display range for S1, S2 &
M (input measured)
6. Response time :
Analog conversion < 1 sec of average
integration typically
Analog to Digital conversion 2 sample
rate per second
7. Input over capability :
Voltage maximum for 100V rms or 2 x
full input which ever great
Current input
DC version 2 times continuous, 10 times
2 sec., 25 times 0.5 sec.
AC version 3 times continuous, 10 times
30 seconds, 25 times 2 seconds

8. Frequency :
40-400Hz AC related meters specified
range for frequency related meters
9. Control output :
(1)on-off control type
(2)relay contact output of spdt type
for each setting
(3)capacity AC 250V / 2A,
AC125V / 3A, DC24V / 3A
(4)time delayer adjustable 0-30 sec.
typically, 0-60, 0-120 sec. for option
(5)dead band for option alternatively
& availably to time delayer
(6)output indication : led lamp energied
in front panel
10. Comm. mode voltage :
2KV rms 50 / 60 Hz 1 minute
11. Impulse voltage:
4KV 1.2 x 50 us common mode test
12. Operation condition :
Temperature 0-55J, 20-99% RH
non-condensed
13. Storage condition :
Temperature -10~70J
14. Power supply :
Standard AC 110 / 220V 50 / 60Hz
15%, < 5 VA
Option DC 12V/24V/48V/125V,
< 6 watts