Professional Documents
Culture Documents
I. INTRODUCTION
It is estimated that conventional reserves of fossil fuels will
be significantly depleted in the next few decades [1], and to
satisfy carbon reduction targets [2] a considerable quantity of
renewable energy (e.g. wind, solar radiation, tidal and wave
energy) will have to be integrated into our existing power
systems. Unlike a traditional and centralized system whose
generation profile is roughly predictable and known in
(2)
is
where:
the damping torque. In the former,
is the synchronizing
torque coefficient whilst
is the change in rotor angle
and
=
. In the latter,
is the damping torque
is the deviation from the nominal rotor
coefficient while
.
angular speed
have to be positive
Kundur [6] suggested that both and
to maintain the stability of the generator, otherwise aperiodic
rotor angle drift (lack of synchronizing torque) or oscillatory
instability (lack of damping torque) may occur. The overview
of the generator model and its associated control based on
equation (1) and (2) is given in Figure 2. The process of this
control scheme can be described as following:
x Measure the rotor angular speed
and calculate the
speed deviation
from the nominal value
.
x Determine the desired value for the change in mechanical
( ) and evaluate the mechanical torque .
torque
x Derive the mechanical power
by multiplying the
with the rotor angular speed
.
mechanical torque
x Feed
output.
(1)
(3)
(4)
(7)
(8)
(9)
Load
Disturbances
Generation
Disturbances
Fault
Disturbances
Single phase-to-ground
transmission line
fault
the
3 phase-to-ground voltages (
on
VII. CONCLUSION
The utilization of a BESS in an isolated power system would
create benefits and drawbacks as summarized in Table 3.
Table 3. Impact of BESS for Each Type of Disturbance
Disturbance
Type
Load
Increase
9
9
x
9
Generation
loss
9
9
x
9
Figure 15. Voltage at Load Side when Single Phase Fault Occurs
Fault
Occurrence
Figure 16. Current at Load Side when Single Phase Fault Occurs
Impact of BESS
9
9
x
x
Figure 17. Rotor Angle of Generator 1 when Single Phase Fault Occurs
Figure 18. Rotor Angle of Generator 2 when Single Phase Fault Occurs