RXYQ-P9

VRVIII heat pump,


small footprint combination

RXYQ44-46-48P9

High sensible mode: allows the VRV system to work with


increased sensible capacity in cooling mode, resulting
in higher efficiency and improved comfort
Easy installation thanks to automatic refrigerant
charging and automatic testing
Easy compliance with F-gas regulation thanks to
automated refrigerant containment check
Flexible combination of outdoor units: small footprint combination,
high COP combination or any other combination of your choice
Compact size leaves maximum floorspace
High external static pressure (up to 78.4Pa) allows indoor installation
Night quiet mode in two steps: step 1: 50 dBA, step 2: 45 dBA
Wide piping flexibility: maximum piping length:
165m, total piping length: 1,000m
All indoor units can be individually controlled
Phased installation possible
Wide outdoor unit range: from 5 to 54HP via 1 single refrigerant circuit
Wide range of indoor units: 15 different models in a total of 76 variations

182

Heating & Cooling


Outdoor system
Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
HeightxWidthxDepth
Dimensions
Unit
Weight
Unit
Sound power level Cooling
Nom.
Sound pressure
Cooling
Nom.
level
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage
Outdoor system
System

mm
kg
dBA
dBA

mm
mm
m
m
Hz / V

*8
8
22.4
25.0
5.22
5.56
4.29
4.5
17

54

57

*10
10
28.0
31.5
7.42
7.70
3.77
4.09
21
1,680x930x765
240

187

HP
kW
kW
kW
kW

dBA
dBA

*22
RXYQ10P9
RXYQ12P9
22
61.50
69.00
16.99
17.08
3.62
4.04
47
83

62

*24
RXYQ12P9

*26
RXYQ8P9

*28
RXYQ10P9

24
67.00
75.00
19.20
18.89
3.49
3.97
52

26
71.40
81.50
20.94
20.69
3.41
3.94
56

28
77.00
88.00
23.62
22.98
3.26
3.83
60

324
83

60

63

12.7

15.9
28.6

*30
*32
RXYQ12P9
RXYQ14P9
RXYQ18P9
30
32
82.50
89.00
94.00
102.00
25.78
28.62
24.67
26.63
3.20
3.11
3.81
3.83

*34
RXYQ16P9

*36
RXYQ18P9

34
94.00
107.00
30.42
28.23
3.09
3.79

36
98.00
113.00
32.45
30.62
3.02
3.69

64
85

63

*18
18
49.0
56.5
16.2
15.30
3.02
3.69
39

64

86
65

66

-5.0~43.0
-20.0~15.0
R-410A

mm
mm
m
m
Hz / V

dBA
dBA

*16
16
45.0
50.0
14.2
12.90
3.17
3.88
34
1,680x1,240x765
316

80

-5.0~43.0
-20.0~15.0
R-410A
12.7
22.2
28.6
1,000
50 (outdoor unit in highest position) (optional: 90)
3N~ / 50 / 400

CDB
CWB

HP
kW
kW
kW
kW

*14
14
40.0
45.0
12.4
11.30
3.23
3.98
30

58

9.52
19.1

20
55.90
62.50
14.71
14.95
3.80
4.18
43

*12
12
33.5
37.5
9.62
9.44
3.48
3.97
26

78

15.9

*20
RXYQ8P9

Outdoor unit module 1


Outdoor unit module 2
Outdoor unit module 3

Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Sound pressure
Cooling
Nom.
level
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage

*5
5
14.0
16.0
3.52
4.00
3.98
4.00
10
1,680x635x765
159
72

CDB
CWB

Outdoor unit module 1


Outdoor unit module 2

Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Sound pressure
Cooling
Nom.
level
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage
Outdoor system
System

HP
kW
kW
kW
kW

15.9

19.1

28.6

34.9

41.3

1,000
50 (outdoor unit in highest position) (optional: 90)
3N~ / 50 / 400
*38
RXYQ8P9

*40
RXYQ10P9
RXYQ12P9

*42
RXYQ12P9

*44
RXYQ8P9

*46
RXYQ10P9

38
105.00
119.00
30.61
30.13
3.43
3.95

40
111.00
126.00
33.23
32.39
3.34
3.89

42
116.00
132.00
35.37
34.20
3.28
3.86

44
120.00
138.00
36.92
35.94
3.25
3.84

RXYQ18P9
46
126.00
145.00
39.75
38.26
3.17
3.79
64

*48
*50
RXYQ12P9
RXYQ14P9
RXYQ18P9
48
132.00
151.00
42.04
39.95
3.14
3.78

50
138.00
158.00
44.81
41.91
3.08
3.77

*52
RXYQ16P9

*54
RXYQ18P9

52
143.00
163.00
46.58
43.47
3.07
3.75

54
147.00
170.00
48.68
45.95
3.02
3.70

86

87

88

66

67

68

CDB
CWB

-5.0~43.0
-20.0~15.0
R-410A
19.1
41.3
1,000
50 (outdoor unit in highest position) (optional: 90)
3N~ / 50 / 400

mm
mm
m
m
Hz / V

183

VRVIII heat pump, with connection to stylish


indoor units

RXYRQ-P

RXYRQ8-12P

Including connection to

NE

Innovative VRV technology combined with stylish and silent indoor units
Wide range of indoor units: combine VRV indoor units
and stylish indoor units as Daikin Emura and Nexura
Up to 39 indoor units can be connected to a 18HP unit
Integrate temperature control, fresh air provision, Biddle air curtains
and the production of hot water in one total solution system
High external static pressure (up to 78.4Pa) allows indoor installation
Night quiet mode in two steps: step 1: 50 dBA, step 2: 45 dBA
All indoor units can be individually controlled
Phased installation possible

nnection to

Including co

Nexura

Daikin Emura

More info

rmation in

the Resid
ential Cha
p

ter

More

This product picture is preliminary

inform

FXSQ-P
VRV indoor unit
FTXG-J

FVXS-F

BPMKS967B3

FTXS-G
BPMKS967B2

FTXG-J
FXFQ-P9
VRV indoor unit

FVXG-K
BPMKS967B2

184

atio

te
Chap
ential
id
s
e
eR
n in th

CONNECTABLE INDOOR UNITS


Daikin Emura - Wall mounted unit
Wall mounted unit
Nexura - Floor standing unit
Floors tanding unit
Flexi type unit
Slim concealed ceiling unit
Concealed ceiling unit
4-way blow ceiling mounted cassette (600x600)
Round flow cassette
Ceiling suspended cassette
All VRV indoor units in all available classes

20 class

25 class

35 class

42 class

50 class

60 class

71 class

FTXS20J
-

FTXG25JW/S
FTXS25J
FVXG25K
FVXS25F
FLXS25B
FDXS25E
FDBQ25B
FFQ25BV
-

FTXG35JW/S
FTXS35J
FVXG35K
FVXS35F
FLXS35B
FDXS35E
FBQ35C
FFQ35BV
FCQ35C8
FHQ35B

FTXS42J
-

FTXG50JW/S
FTXS50J
FVXG50K
FVXS50F
FLXS50B
FDXS50C
FBQ50C
FFQ50BV
FCQ50C8
FHQ50B

FTXS60G
FLXS60B
FDXS60C
FBQ60C
FFQ60BV
FCQ60C8
FHQ60B

FTXS71G
-

Heating & Cooling


Outdoor units
Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Sound pressure
Cooling
Nom.
level
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping
System Actual
length
Level difference OU - IU
Power supply
Phase / Frequency / Voltage

HP
kW
kW
kW
kW

dBA
dBA

RXYRQ10P
10
28.0
31.5
7.42
7.70
3.77
4.09
21

mm
mm
m

RXYRQ12P
12
33.5
37.5
9.62
9.44
3.48
3.97
26

RXYRQ14P
14
40.0
45.0
12.4
11.30
3.23
3.98
30
80

78
57

58

60

9.52
19.1

RXYRQ18P
18
49.0
56.5
16.2
15.30
3.02
3.69
39
83
63

12.7
22.2

15.9
28.6

135

m
Hz / V

40 (outdoor unit in highest position)


3N~ / 50 / 400

BPMKS967B2
kW
mm
kg

RXYRQ16P
16
45.0
50.0
14.2
12.90
3.17
3.88
34

-5.0~43.0
-20.0~15.0
R-410A

CDB
CWB

Branch Provider
Max. n of indoor units to be connected
Max. indoor unit connectable capacity
Dimensions
Height x Width x Depth
Weight

RXYRQ8P
8
22.4
25.0
5.22
5.56
4.29
4.50
17

BPMKS967B3
!
)"*$%+")$'$&"1$'$&"1(

1#" $%&"1$'$&"1(
1*)$,$ -#$,$!.)
&".

*
!"#$%&'($)&*$++,&*"-#./-&0($+/1/-.()&2.#.

185

VRVIII-S heat pump


Single phase

RXYSQ-P8V1

RXYSQ4-5-6P8V1

Cost effective, low energy consumption heating system


Lower CO2 emmisions compared to traditional heating systems
Small capacities: 4, 5 & 6HP
Slim design for flexible installation
Wide range of indoor units: either connect VRV or
stylish indoor units: Daikin Emura, Nexura
Up to 9 indoor units connectable
All indoor units can be individually controlled
Night quiet mode in three steps: step 1: 47 dBA,
step 2: 44 dBA , step 3 / 41 dBA
Easy installation thanks to automatic refrigerant
charging and automatic testing
Possibility to limit power consumption

Heating & Cooling


Outdoor units
Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
HeightxWidthxDepth
Dimensions
Unit
Weight
Unit
Sound power level Cooling
Nom.
Sound pressure
Cooling
Nom.
level
Heating
Nom.
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage

HP
kW
kW
kW
kW

RXYSQ4P8V1
4
11.2
12.5
2.81
2.74

RXYSQ5P8V1
5
14.0
16.0
3.51
3.86
3.99

4.56
8
mm
kg
dBA
dBA
dBA
CDB
CWB

4.15
10
1,345x900x320
120
67
51
53
-5.0~46.0
-20~15.5
R-410A
9.52

66
50
52

mm
mm
m
m
Hz / V

15.9

RXYSQ6P8V1
6
15.5
18.0
4.53
4.57
3.42
3.94
13

69
53
55

19.1
300
50 (outdoor unit in highest position)
1N~ / 50 / 220-240

!"#$%&'($)&*$++,&*"-#./-&0($+/1/-.()&2.#.

186

VRVIII-S heat pump


Three phase

RXYSQ-P8Y1

RXYSQ4-5-6P8Y1

Cost effective, low energy consumption heating system


Lower CO2 emmisions compared to traditional heating systems
Small capacities: 4, 5 & 6HP
Slim design for flexible installation
Wide range of indoor units: either connect VRV or
stylish indoor units: Daikin Emura, Nexura...
Up to 9 indoor units connectable
All indoor units can be individually controlled
Night quiet mode in three steps: step 1: 47 dBA,
step 2: 44 dBA , step 3 / 41 dBA
Easy installation thanks to automatic refrigerant
charging and automatic testing
Possibility to limit power consumption

Heating & Cooling


Outdoor units
Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
HeightxWidthxDepth
Dimensions
Unit
Weight
Unit
Sound power level Cooling
Nom.
Sound pressure
Cooling
Nom.
level
Heating
Nom.
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping
System Actual
length
Level difference OU - IU
Power supply
Phase / Frequency / Voltage

HP
kW
kW
kW
kW

RXYSQ4P8Y1
4
11.2
12.5
2.89
2.82

RXYSQ5P8Y1
5
14.0
16.0
3.61
3.97
3.88

4.43
8
mm
kg
dBA
dBA
dBA
CDB
CWB

4.03
10
1,345x900x320
120
67
51
53
-5.0~46.0
-20~15.5
R-410A
9.52

66
50
52

mm
mm
m

15.9

RXYSQ6P8Y1
6
15.5
18.0
4.66
4.70
3.33
3.83
13

69
53
55

19.1
300

m
Hz / V

50 (outdoor unit in highest position)


3N~ / 50 / 380-415

!"#$%&'($)&*$++,&*"-#./-&0($+/1/-.()&2.#.

187

VRVIII heat recovery high COP combination

REYHQ-P

REYHQ24P

Top energy efficiency in Daikin heat recovery range, thanks to the


redesigned 8HP modular unit and newly developed 12HP high COP
modular unit
4.40
+ 11%

4.30

COP

4.20

High COP range


Small footprint range

4.10
3.90
3.80
3.70
3.60

16

20

22

24

Wide range of indoor units: 15 different models in a total of 76 variations


Continuous heating (resulting in a higher integrated heating capacity)
High sensible mode, allows the VRV system to work with
increased sensible capacity in cooling mode resulting
in higher efficiency and improved comfort
Easy installation thanks to automatic refrigerant
charging operation, automatic test operation
Increased piping flexibility: maximum piping length:
165m, increased total piping length: 1,000m
The ability to control each conditioned zone keeps VRVIII
system running costs to an absolute minimum
Only those areas calling for air conditioning need to be cooled or heated
and the system can be shut down completely in unoccupied rooms
Quick cool/heat change over
Improved refrigerant containment check
2 steps in night quiet mode (step 1: 50 dBA / step 2: 45 dBA)
Possibility to extend the operation range in cooling down to -20C

Heat recovery
Outdoor system
System

REYHQ16P
Outdoor unit module 1
Outdoor unit module 2

Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Sound pressure level Cooling
Nom.
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage
Outdoor unit module
HeightxWidthxDepth
Dimensions
Unit
Weight
Unit
Refrigerant
Type
Power supply
Phase / Frequency / Voltage

REYHQ20P

REYHQ22P
REMQ10P8
REMHQ12P8
22
61.5
69.0
16.0
16.3
3.84
4.24
47

REMQ8P9
HP
kW
kW
kW
kW

REMQ8P9
16
45.0
50.0
10.5
11.5
4.29

20
56.0
62.5
13.9
14.3
4.04
4.36

dBA
dBA
CDB
CWB
mm
mm
m
m
Hz / V

34
82
62

43
85
64
-5~43
-20~15
R-410A

12.7

Hz / V

24
67.0
75.0
17.2
17.2
3.89
4.37
52
87
66

15.9
28.6

34.9

1.000
50 (outdoor unit in highest position) (optional: 90)
3N~ / 50 / 380-415
REMQ8P9

mm
kg

REYHQ24P
REMHQ12P8

REMHQ12P8
1,680x930x765

204
3~ / 50 / 380-415

175

331
R-410A
3~ / 50 / 380-415

REMQ10P8
1,680x1,240x765
254
3~ / 50 / 380-415

VRVIII heat recovery


small footprint combination

REYQ-P8/P9

REYQ46-48P8

Increased EER/COP thanks to the redesigned 8 and


12HP stand alone units and 8HP modular unit
Wide outdoor unit range: from 8 to 48HP via one single refrigerant circuit
Up to 64 connectable indoor units
Continuous heating (resulting in a higher integrated heating capacity)
High sensible mode, allows the VRV system to work with
increased sensible capacity in cooling mode resulting
in higher efficiency and improved comfort
Easy installation thanks to automatic refrigerant
charging operation, automatic test operation
Increased piping flexibility: maximum piping length:
165m, increased total piping length: 1,000m
The ability to control each conditioned zone keeps the
VRVIII system running costs to an absolute minimum
Only those areas calling for air conditioning need to be cooled or heated
and the system can be shut down completely in unoccupied rooms
Quick cool/heat change over
Improved refrigerant containment check
2 steps in night quiet mode: step 1: 50 dBA / step 2: 45 dBA
Possibility to extend the operation range in cooling down to -20C

REYQ-P8/P9
Stand alone units

REYQ8P9
REYQ10P8
REYQ12P9
REYQ14P8
REYQ16P8

?5@A9<B$AC:6D

?5@A9<B$AC:6D

"$

"%

"&

$#

$$

$%

$&

$!

456$7889:;<=9>
1
1
1

1
456$7889:;<=9>

1
1

1
1
1

'#

'$

'%

'&

REYQ8P9
REYQ10P8
REYQ12P9
REYQ14P8
REYQ16P8
REMQ8P9
REMQ10P8
REMQ12P8
REMQ14P8
REMQ16P8

"!

REMQ8P9
REMQ10P8
REMQ12P8
REMQ14P8
REMQ16P8

REYQ-P8/P9
Stand alone units

"#

'!

%#

%$

%%

%&

%!

456$7889:;<=9>

1
1
1

1
1

1
1
1

176

Heat recovery
Outdoor system
Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Operation range Cooling
Field set. /
min.~ max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Discharge gas
OD
Oil equalizing
OD
Total piping
System Actual
length
Level difference OU - IU
Power supply
Phase / Frequency / Voltage
Outdoor system
System

REYQ10P8
10
28.0
31.5
7.09
7.38
3.95
4.27
21

9.52

mm
mm
mm
mm
m

19.1
15.9

dBA
CDB

19.10
1,000
50 (outdoor unit in highest position) (optional: 90)
3~ / 50 / 380-415

Heating
Type

20
REMQ8P9
REMQ10P8
REMQ12P8
18
20
50.4
55.9
56.5
62.5
12.7
14.9
13.4
15.2
3.97
3.75
4.20
4.12
39
43
81

Field set. /
min.~ max.
Min.~Max.

22
24
REMQ10P8
REMQ12P8
REMQ12P8
22
24
61.5
67.0
69.0
75.0
17.0
19.2
17.1
18.9
3.62
3.49
4.04
3.97
47
52

26
REMQ10P8

28
30
32
REMQ12P8
REMQ14P8
REMQ16P8
REMQ16P8
28
30
32
78.5
85.0
90.0
87.5
95.0
100
23.8
26.6
28.4
22.3
24.2
25.8
3.30
3.20
3.17
3.92
3.93
3.88
60
64

26
73.0
81.5
21.6
20.6
3.38
3.96
56
83

-20 / -5 ~ 43
-20 ~ 15
R-410A
15.9

19.1

28.6

34.9

22.2

28.6
19.1
1,000

m
Hz / V

50 (outdoor unit in highest position) (optional: 90)


3~ / 50 / 380-415
34
REMQ8P9
REMQ10P8

36
REMQ8P9

38
REMQ10P8
REMQ12P8

40
REMQ12P8

34
95.4
107
26.9
26.3
3.55
4.06

36
101
113
29.1
28.1
3.48
4.02

38
107
119
31.2
30.0
3.43
3.97

40
112
125
33.4
31.8
3.35
3.93

42
REMQ10P8

44
46
REMQ12P8
REMQ14P8
REMQ16P8

48
REMQ16P8

REMQ16P8
HP
kW
kW
kW
kW

42
118
132
35.8
33.5
3.30
3.94

44
124
138
38.0
35.2
3.26
3.92

46P
130
145
40.8
37.1
3.19
3.94

48
135
150
42.6
38.7
3.17
3.88

64
dBA
CDB

84

85
-20 / -5 ~ 43
-20 ~ 15
R-410A
19.1

CWB
mm
mm
mm
mm
m

34.9

41.3
28.6

34.9
19.1
1,000

m
Hz / V

50 (outdoor unit in highest position) (optional: 90)


3~ / 50 / 380-415
REMQ8P9Y1B

HeightxWidthxDepth

22.2
-

CWB
mm
mm
mm
mm
m

REYQ16P8
16
45.0
50.0
14.1
12.8
3.19
3.91
34
84

12.7
28.6

22.2

m
Hz / V

HP
kW
kW
kW
kW

REYQ14P8
14
40.0
45.0
11.4
11.0
3.51
4.09
30
83

-20 ~ 15
R-410A

CWB

Outdoor unit module 1


Outdoor unit module 2
Outdoor unit module 3

Outdoor unit module


Dimensions
Unit
Weight
Unit
Operation range Cooling

REYQ12P9
12
33.5
37.5
8.72
8.84
3.84
4.24
26
80
-20 / -5 ~ 43

78

18

Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Operation range Cooling
Field set. /
min.~ max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Discharge gas
OD
Oil equalizing
OD
Total piping
System Actual
length
Level difference OU - IU
Power supply
Phase / Frequency / Voltage

Refrigerant

REYQ8P9
8
22.4
25.0
5.20
5.71
4.31
4.38
17

dBA
CDB

Outdoor unit module 1


Outdoor unit module 2

Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Operation range Cooling
Field set. /
min.~ max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Discharge gas
OD
Oil equalizing
OD
Total piping
System Actual
length
Level difference OU - IU
Power supply
Phase / Frequency / Voltage
Outdoor system
System

HP
kW
kW
kW
kW

mm
kg
CDB

REMQ10P8Y1B
1,680x930x765

204

REMQ12P8Y1B
254
-20 / -5~43

CWB

-20~15
R-410A

177

REMQ14P8Y1B
REMQ16P8Y1B
1,680x1,240x765
334

RXHQ-P

VRVIII heating only

RXHQ44-46-48P

Cost effective, low energy consumption heating system


Lower CO2 emmisions compared to traditional heating systems
Easy installation thanks to automatic refrigerant
charging and automatic testing
Easy compliance with F-gas regulation thanks to
automated refrigerant containment check
Flexible combination of outdoor units
Compact size leaves maximum floorspace
High external static pressure (up to 78.4Pa) allows indoor installation
Night quiet mode in two steps: step 1: 50 dBA, step 2: 45 dBA
Wide piping flexibility: maximum piping length:
165m, total piping length: 1,000m
All indoor units can be individually controlled
Phased installation possible
Wide outdoor unit range: from 5 to 54HP via 1 single refrigerant circuit
Wide range of indoor units: 15 different models in a total of 76 variations

178

Heating only
Outdoor system
Capacity range
Heating capacity Nom.
Power input - 50Hz Heating
Nom.
COP
Maximum number of connectable indoor units
HeightxWidthxDepth
Dimensions
Unit
Weight
Unit
Operation range Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage
Outdoor system
System

HP
kW
kW

mm
kg
CWB
mm
mm
m
m
Hz / V

HP
kW
kW

HP
kW
kW

*14
14
45.0
11.30
3.98
30

240

*16
16
50.0
12.90
3.88
34
1,680x1,240x765
316

*18
18
56.5
15.30
3.69
39
324

-20.0~15.0
R-410A
19.1

22.2

12.7
28.6

12.7

15.9
28.6

1,000
50 (outdoor unit in highest position) (optional: 90)
3N~ / 50 / 400
*22
RXHQ10P
RXHQ12P
22
69.00
17.08
4.04
47

20
62.50
14.95
4.18
43

*24
RXHQ12P

*26
RXHQ8P

*28
RXHQ10P

24
75.00
18.89
3.97
52

26
81.50
20.69
3.94
56

28
88.00
22.98
3.83
60
-20.0~15.0
R-410A

*30
*32
RXHQ12P
RXHQ14P
RXHQ18P
30
32
94.00
102.00
24.67
26.63
3.81
3.83

*34
RXHQ16P

*36
RXHQ18P

34
107.00
28.23
3.79

36
113.00
30.62
3.69

64

15.9

mm
mm
m
m
Hz / V

Outdoor unit module 1


Outdoor unit module 2
Outdoor unit module 3

Capacity range
Heating capacity Nom.
Power input - 50Hz Heating
Nom.
COP
Maximum number of connectable indoor units
Operation range Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage

*12
12
37.5
9.44
3.97
26

CWB

Outdoor system
System

*10
10
31.5
7.70
4.09
21
1,680x930x765

187

*20
RXHQ8P

Outdoor unit module 1


Outdoor unit module 2

Capacity range
Heating capacity Nom.
Power input - 50Hz Heating
Nom.
COP
Maximum number of connectable indoor units
Operation range Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage

*8
8
25.0
5.56
4.5
17

19.1

28.6

34.9

41.3

1,000
50 (outdoor unit in highest position) (optional: 90)
3N~ / 50 / 400
*38
RXHQ8P

*40
RXHQ10P
RXHQ12P

*42
RXHQ12P

*44
RXHQ8P

*46
RXHQ10P

38
119.00
30.13
3.95

40
126.00
32.39
3.89

42
132.00
34.20
3.86

44
138.00
35.94
3.84

RXHQ18P
46
145.00
38.26
3.79

*48
*50
RXHQ12P
RXHQ14P
RXHQ18P
48
151.00
39.95
3.78

50
158.00
41.91
3.77

*52
RXHQ16P

*54
RXHQ18P

52
163.00
43.47
3.75

54
170.00
45.95
3.70

64
CWB

-20.0~15.0
R-410A
19.1
41.3
1,000
50 (outdoor unit in highest position) (optional: 90)
3N~ / 50 / 400

mm
mm
m
m
Hz / V

*Note: grey cells contain preliminary data

179

VRVIII heat pump, optimised for heating

RTSYQ-P

RTSYQ14-16P

First system in the industry developed for heating operation in low


ambient conditions, making it suitable for single source heating
Extended operation range for heating down to -25CWB

HEATING
50
40
30
20

VRV III-C
+15.5 CWB

VRV III
+15.5 CWB

10
0
-5
-10
-15
-20 CWB

-20
-25 CWB

-25

High COP values at low ambients due to the use of two stage
compression technology (COP values of 3.0 and more at -10C)
Improved comfort levels because of shorter defrost time
Shorter heat up time compared to standard VRVIII heat pump
Easy installation thanks to automatic refrigerant
charging operation, automatic test operation
Connectable to all VRV indoor units, ventilation and Control systems.

Heating & Cooling


Outdoor system
System

Capacity range
Cooling capacity
Heating capacity

Outdoor unit module 1


Outdoor unit module 2
Function unit
Nom.
Nom.

Power input - 50Hz Cooling


Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Sound pressure level Cooling
Max./Nom.
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Oil equalizing
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage

RTSYQ10P
RTSQ10P

RTSYQ14P
RTSQ14P
-

10
28.0 (1)
31.5 (2)
28.0 (3)
7.90
7.70
3.54 (1)
4.09 (2)
21

14
40.0 (1)
45.0 (2)
40.0 (3)
12.6
11.3
3.17 (1)
3.98 (2)
30

62/60

63/61

RTSYQ16P
RTSQ16P

RTSYQ20P
RTSQ8P
RTSQ12P

16
45.0 (1)
50.0 (2)
45.0 (3)
14.9
12.9
3.02 (1)
3.88 (2)
34

20
56.0 (1)
63.0 (2)
56.0 (3)
15.4
15.3
3.64 (1)
4.12 (2)
43

BTSQ20P
HP
kW
kW
kW
kW

dBA
dBA
CDB
CWB
mm
mm
mm
m
m
Hz / V

65/63
-5~46
-25~15.5
R-410A
12.7
28.6

9.52
22.2

15.9
28.6
19.1

500
50 (outdoor unit in highest position)
3~ / 50 / 380-415

(1) Cooling: Indoor temp. 27CDB, 19CWB / outdoor temp. 35CDB / equivalent piping length: 7.5m / level difference: 0m / function unit length: 6m / combined indoor unit: FXFQ50P x 5 units
(2) Heating: Indoor temp. 20CDB / outdoor temp. 7CDB,6CWB / equivalent piping length: 7.5m / level difference: 0m / function unit length: 6m / combined indoor unit: FXFQ50P x 5 units
(3) Heating: Indoor temp. 20CDB / outdoor temp. -10CWB / equivalent piping length: 7.5m / level difference 0m / function unit length: 6m / combined indoor unit: FXFQ50P x 5 units

Outdoor unit module


HeightxWidthxDepth
Dimensions
Unit
Weight
Unit
Refrigerant
Type
Power supply
Phase / Frequency / Voltage

RTSQ8P
mm
kg

RTSQ10P
1,680x930x765

205

RTSQ12P
257

RTSQ14P
RTSQ16P
1,680x1,240x765
338
344

R-410A
3~ / 50 / 380-415

Hz / V

180

BTSQ20P
1,570x460x765
110

VRVIII heat pump,


high COP combination

RXYHQ-P9

RXYHQ20-22P9

Top energy efficiency in Daikin heat pump range, thanks


to specially developed 12HP high COP unit
High sensible mode: allows the VRV system to work with
increased sensible capacity in cooling mode, resulting
in higher efficiency and improved comfort
Easy installation thanks to automatic refrigerant
charging and automatic testing
Easy compliance with F-gas regulation thanks to
automated refrigerant containment check
Flexible combination of outdoor units: small footprint combination,
high COP combination or any other combination of your choice
High external static pressure (up to 78.4Pa) allows indoor installation
Night quiet mode in two steps: step 1: 50 dBA, step 2: 45 dBA
Wide piping flexibility: maximum piping length:
165m, total piping length: 1,000m
All indoor units can be individually controlled
Phased installation possible
Wide outdoor unit range: from 5 to 54HP via 1 single refrigerant circuit
Wide range of indoor units: 15 different models in a total of 76 variations

Heating & Cooling


Outdoor system
System

Outdoor unit module 1


Outdoor unit module 2
Outdoor unit module 3

Capacity range
Cooling capacity Nom.
Heating capacity Nom.
Power input - 50Hz Cooling
Nom.
Heating
Nom.
EER
COP
Maximum number of connectable indoor units
Sound power level Cooling
Nom.
Sound pressure
Cooling
Nom.
level
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Piping
Liquid
OD
connections
Gas
OD
Total piping length System Actual
Level difference OU - IU
Power supply
Phase / Frequency / Voltage
Outdoor unit module
HeightxWidthxDepth
Dimensions
Unit
Weight
Unit
Sound power level Cooling
Nom.
Sound pressure level Cooling
Nom.
Operation range Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Power supply
Phase / Frequency / Voltage

HP
kW
kW
kW
kW

dBA
dBA

*12
*16
*18
RXYHQ12P9W1B
RXYQ8P9W1B
RXYQ8P9W1B RXYQ10P9W1B
12
16
18
33.5
45.00
49.00
37.50
50.00
56.50
8.61
10.49
12.25
8.58
11.11
13.23
3.89
4.29
4.00
4.37
4.50
4.27
26
34
39
80
82
60

*20

*22
RXYQ10P9W1B
RXYHQ12P9W1B
20
55.90
62.50
13.80
14.14
4.05
4.42
43

22
61.50
69.00
16.02
16.27
3.84
4.24
47

61

*28
*30
RXYQ8P9W1B
RXYQ8P9W1B
RXYQ10P9W1B
RXYQ8P9W1B
RXYQ10P9W1B
24
26
28
30
67.00
71.40
77.00
82.50
75.00
81.50
88.00
94.00
15.62
17.46
18.69
20.83
16.67
18.78
19.82
21.81
4.29
4.09
4.12
3.96
4.50
4.34
4.44
4.31
52
56
60
83

*32

*34
*36
RXYQ10P9W1B RXYHQ12P9W1B
RXYHQ12P9W1B
RXYHQ12P9W1B
32
34
36
89.00
94.00
98.00
102.00
107.00
113.00
22.31
24.42
25.19
23.18
24.94
25.86
3.99
3.85
3.89
4.40
4.29
4.37
64
85

63

64

65

-5.0~43.0
-20.0~15.0
R-410A
12.7

15.9

19.1

28.6

34.9

41.3

1,000
50 (outdoor unit in highest position) (optional: 90)
3N~ / 50 / 400
RXYQ8P9

mm
kg
dBA
dBA
CDB
CWB

*26

62

CDB
CWB
mm
mm
m
m
Hz / V

*24

RXYQ10P9
1,680x930x765

187

240
78

57

58
-5.0~43.0
-20.0~15.0
R-410A
3N~ / 50 / 400

Hz / V

RXYHQ12P9
1,680x1,240x765
281
80
60

*Note: grey cells contain preliminary data

181