Professional Documents
Culture Documents
Installation/
Operation Manual
C572M (7/98)
CONTENTS
Section
Page
LIST OF ILLUSTRATIONS
Figure
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Page
Front View of CM9760-ALM ............................................................... 7
Front Panel Removal ......................................................................... 7
DIP Switch Location ........................................................................... 8
DIP Switch 1 Functions ...................................................................... 8
DIP Switch 2 Functions ...................................................................... 9
Rear View of CM9760-ALM .............................................................. 10
Alarm Input Headers ......................................................................... 11
Relay Output Connector ................................................................... 12
DB-9 Pin-outs ................................................................................... 13
RJ-45 Pin-outs .................................................................................. 14
RJ-45 Connector Pin-out Geometry ................................................. 14
Power Input Fuse Replacement ....................................................... 15
CM9760-ALM Rack-Mount Installation ............................................. 16
Daisy-Chain Configuration ................................................................ 17
Supervised Alarm Input Wiring ......................................................... 19
Unsupervised Alarm Input Wiring ..................................................... 20
TTL/CMOS External Alarm Wiring .................................................... 21
Alarm Unit Block Diagram ................................................................. 22
Communication Loss Operation ....................................................... 25
CM9760-ALM Dimension Diagram ................................................... 27
LIST OF TABLES
Table
A
Page
Command Set ................................................................................... 24
REVISION HISTORY
Manual #
Date
Comments
C572M
4/98
Original version.
C572M
7/98
1.0 GENERAL
1.1 IMPORTANT SAFEGUARDS AND WARNINGS
Please thoroughly familiarize yourself with the information in this manual
prior to installation and
operation.
Prior to installation and use of this product, the following WARNINGS should be
observed.
1.
2.
Unless the unit is specifically marked as a NEMA Type 3, 3R, 3S, 4, 4X,6, or
6P enclosure, it is designed for Indoor use only and it must not be installed
where exposed to rain and moisture.
3.
4.
After replacement/repair of this units electrical components, conduct a resistance measurement between line and exposed parts to verify the exposed
parts have not been connected to line circuitry.
CAUTION:
RISK OF
ELECTRIC SHOCK.
DO NOT OPEN.
CAUTION:
TO REDUCE THE RISK OF ELECTRICAL SHOCK,
DO NOT REMOVE COVER. NO USERSERVICEABLE PARTS INSIDE. REFER SERVICING
TO QUALIFIED SERVICE PERSONNEL.
Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
2.0 DESCRIPTION
The CM9760-ALM is another ancillary product belonging to the CM9760 family
of large matrix switching configurations. The ALM unit utilizes an RS-232/422
communication interface with the CM9760 system controller and replaces the
CM9750-AL1, CM9750-AL1-X, CM9750-AL2 and the CM9750-AL2-X. The unit
can be remotely placed with respect to the controller, from where it can communicate back to the central system when an alarm occurs.
Some of the more important features of the alarm unit are as follows:
Up to four units can be chained together giving a total of 256 alarms, accessed and supported from a single sercom port on the CM9760-CC1.
Alarm inputs, in groups of 16, can be wired either normally open or normally
closed.
The unit is backward compatible with the CM9750 system unit (version 5.4
and later).
Provisions are made for detecting communication loss for cascaded units.
2.1 MODELS
CM9760-ALM
2.2 CERTIFICATIONS
The products identified below have been tested and certified for agency compliance as noted.
Model
CM9760-ALM
CE
X
NEMA Type 1
IP 30
PORT 0 = CONNECTORS
UNDER UART 0s INFLUENCE
(REFER TO BLOCK DIAGRAM, FIGURE 18)
PORT 1 = CONNECTORS
UNDER UART 1s INFLUENCE
(REFER TO BLOCK DIAGRAM,
FIGURE 18)
PORT 0 (P1/P2)
P1=DB-9, RS-232 CONNECTOR
P2=RJ-45 IN CONNECTOR
(ACTIVE PORT DETERMINED
BY SETTING OF S7)
ADDRESS
SELECT
BY
GROUP
2400
4800
9600
19200
OFF
ON
OFF
ON
1 - 64
GROUP I
GROUP II 65 - 128
GROUP III 129 -192
GROUP IV 193 - 256
OFF
OFF
ON
ON
OFF
ON
OFF
ON
2400
4800
9600
19200
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON=LOOKS FOR
COMMUNICATION LOSS
3.1.2 LEDs
The green POWER LED located on the left front panel of the unit comes ON at
power up.
The red ALARM LED located on the right side of the front panel of the unit is lit for
any valid alarm condition and flashes ON and OFF at about 1/4 second intervals
until the alarm is no longer active. The ALARM LED follows ALARM OUT relay
activation.
The four 16-input groupings of input alarm connectors in the form of screwtype connectors labelled I, II, III and IV
2.
3.
3.
4.
A power-on LED (functionally a mirror of the one existing on the front panel)
located just to the left of the input power terminals and above the RS-232
connector
5.
The grouped input power functions consisting of the input power terminals, a
fuse, and an ON/OFF switch
SEE FIGURE 7
10
For example, refer to the left-most dual-header position referenced in Figure 6 and
represented by Figure 7, which shows alarm inputs 1-16. Of these alarm inputs, 1-8
are wired using the top 16 screw terminal positions. Alarm inputs on these headers
physically alternate with their associated GND connection for a total of eight available ALM/GND connections in the top header: that is, pin 1 is alarm input 1 and
pin 2 is the GND connection associated with alarm input 1; pin 3 is alarm input 2
and pin 4 is alarm input 2s associated GND connection, and so on. The same
explanation applies to the lower header except alarm inputs 9-16 are accommodated, starting with alarm input 9 which is associated with physical pin 17 on the
header (see Section 4.4, ALARM WIRING).
In a similar manner, the remaining dual-header (upper/lower) combinations accommodate the three remaining alarm input groups: that is, inputs 17-32 are handled by
header two; inputs 33-48 by header three and inputs 49-64 by header four. The
wiring of alarms is covered in Section 4.4, ALARM WIRING.
11
12
13
RJ-45 COMMUNICATION
CONNECTORS
IN INPUT FROM CM9760-CC1
OUT USED FOR CABLING
SUBSEQUENT UNITS
BROWN
BROWN
STRAIGHT CABLE
OR
PARALLEL
BROWN
FLIPPED CABLE
OR
REVERSE CABLE
TO IDENTIFY A CABLE
TYPE, PHYSICALLY
ORIENT THE RJ-45
CABLE AS DEPICTED
IN THE ILLUSTRATIONS.
ORIENT THE CONNECTORS
SIDE BY SIDE. TAB
SIDE DOWN. USE
THE COLOR RUN
OF THE WIRES TO
DETERMINE CABLE
TYPE AND USE THE
CABLE TYPE
APPROPRIATE TO
THE SITUATION.
14
15
4.0 INSTALLATION
Physical installation of the alarm unit is relatively simple, although various configurations are possible.
16
4.3 DAISY-CHAINING
Daisy-chain configurations may be invoked whether alarm units are situated locally, remotely or as a combination of the two. In any case, no more than four alarm
units can be chained together. To accomplish this, the first unit is connected from its
IN connector to the CC1 and connected to the second unit through its OUT connector. Subsequent units are chained together in the same way.
Figure 14 depicts the connection of four cascaded units. Note that the remarks
made in the previous section regarding RS-422 wiring run distances are applicable
here when considering cables distance runs between daisy-chained units.
IN OUT
UNIT 1
CM9760-ALM
IN OUT
UNIT 2
CM9760-ALM
IN OUT
UNIT 3
CM9760-ALM
IN
UNIT 4
CM9760-ALM
17
Your alarm input wiring must reflect DIP switch 2 slide switch position settings
or vice versa.
2.
In supervised mode, alarm inputs must be defined in the system setup file.
3.
Integrating supervised and unsupervised wiring modes within the same group
is not allowed and furthermore, in non-supervised mode, you cannot have
alarms wired for both normally open and normally closed operation in the
same alarm group.
4.
If wiring a group of inputs specified as supervised, no unwired inputs are allowed as this would result in a constant alarm condition. Any unused alarm
position should have a 10K resistor wired across its input and associated GND
connection (refer to the table in Figure 7, and to Figure 15).
5.
18
SWITCH SETTINGS
DO NOT
CARE ABOUT
THESE
SWITCH
POSITIONS
WHEN IN
SUPERVISED
MODE
ON
S1/S2
GROUP
1-16
S2 S2
S3/S4
GROUP
17-32
S3 S4
S5/S6
GROUP
33-48
S5 S6
OFF
S7/S8
GROUP
49-64 NOT USED
S7 S8
DIP SWITCH 2
19
SWITCH SETTINGS
INDIVIDUAL ALARM WIRING CONDITIONS
IN UNSUPERVISED
MODE, SWITCH
POSITIONS AS
SHOWN CONFIGURE
INPUT FOR
NORMALLY CLOSED
POSITION
ON
S1/S2
GROUP
1-16
S2 S2
DIP SWITCH 2
S3/S4
GROUP
17-32
S3 S4
S5/S6
GROUP
33-48
S5 S6
OFF
S7/S8
GROUP
49-64 NOT USED
S7 S8
SWITCH SETTINGS
IN UNSUPERVISED
MODE, SWITCH
POSITIONS AS
SHOWN CONFIGURE
INPUT FOR
NORMALLY OPEN
POSITION
ON
S1/S2
GROUP
1-16
S2 S2
S3/S4
GROUP
17-32
S3 S4
S5/S6
GROUP
33-48
S5 S6
OFF
S7/S8
GROUP
49-64 NOT USED
S7 S8
20
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
21
ANALOG
SWITCH
RJ-45 OUT
22
Handles the input and output processing of messages to and from the unit
and the CC1 as well as handling the communications between itself and other
ALM units in cascaded configurations.
2.
3.
23
DIRECTION
CC1 to ALM unit
CC1 to ALM unit
CC1 to ALM unit
ALM unit to CC1
CC1 to ALM unit
As previously mentioned, ARM table information from the CC1 is transferred to all
alarm units and their respective database tables on initial power up of the system.
The CC1 automatically sends ARM table information (Send Arm Table command)
to the alarm units. If, during normal operation, an alarm unit is turned off, then
turned back on or a new unit is added, for example, to a cascaded configuration
and turned on, then the alarm unit itself will issue an ARM request (Arm Table
Request command) from the CC1 when it is powered on.
The ARM table database is an integral part of the software operation of the ALM unit.
Essentially, the ARM table contains the programmed sum of all the pre-defined conditions that affect the operational relationship between the operator and user of the
system and the wired alarm inputs to the ALM unit. As a practical matter, though, the
contents and use of the ARM table by the software is transparent to the user. We
mention it here because one of the commands within the command set available to
any operator; namely, an Arm/Disarm Alarm Input command, which can be sent
by an operator to an alarm unit affects the ARM table. Upon receipt of this command,
the ALM unit in question acknowledges the command and updates its respective
ARM table database for the affected group of alarms.
The relay commands (Send Set Relay Off and Send Set Relay On) are not acted
upon by the alarm unit. Instead, they are acknowledged by the ALM unit and then
essentially thrown away. Relays are programmed to be a relay follow of alarm activation. When any valid alarm is sensed on any alarm unit, the relay on that alarm unit
becomes active and will not go inactive until all alarms on that unit go away. In
addition, the alarm LED will actively follow the alarm relay and, in an alarm condition, will flash ON and OFF in 1/4-second intervals until the alarm relay deactivates.
24
ACK
ACK
LOSS MODE
ENABLED
LOSS MODE
ENABLED
NORMAL OPERATION
;;
COMMUNICATION
FAILURE BETWEEN
UNITS B AND C
ALARM 128
REPORTED
(COMMUNICATION
LOSS WITHIN UNIT C)
;;
ACK
LOSS MODE
ENABLED
LOSS MODE
ENABLED
A
1-64
B
65-128
C IS DISCONNECTED
25
Define communication modes and run appropriate communication cables, paying attention to cable distance runs.
2.
3.
Wire the external alarms according to your site plan. Pay close attention to the
following:
4.
26
a.
b.
Be sure to wire unused alarm inputs for any group configured as unsupervised and normally closed with a shorting wire between the unused
alarm input and its associated ground connection.
Configure your DIP switches for each alarm unit. For cascaded units, remember to set the communication failure slide switch for detecting communication
loss downstream, if desired. Also be sure to set the termination bit for the last
unit in either a chain of units or, in the case of only one alarm unit, consider it
the last unit and activate its termination bit slide switch.
6.0 SPECIFICATIONS
Electrical
Input Voltage:
Power:
30 vA
Data Ports
Input:
Output:
Indicators:
Fusing:
Relay Out:
General
Dimensions:
Operating
Temperature:
32 to 122F (0 to 50C)
Weight:
7 lb (3.17 kg)
Rating:
NEMA 1
Mechanical
Connectors:
Power:
RS-422:
RS-232:
Relay Out:
8.15
(20.70)
19.00 (48.26)
1.75
(4.45)
PWR
ALARM
CM9760-ALM
Alarm Interface Unit
S Y S T E M 9760
Made in USA
17.40 (44.20)
27
If a warranty repair is required, the Dealer must contact Pelco at (800) 289-9100 or
(559) 292-1981 to obtain a Repair Authorization number (RA), and provide the following
information:
1. Model and serial number
2. Date of shipment, P.O. number, Sales Order number, or Pelco invoice number
3. Details of the defect or problem
If there is a dispute regarding the warranty of a product which does not fall under the
warranty conditions stated above, please include a written explanation with the product
when returned.
Method of return shipment shall be the same or equal to the method by which the item was
received by Pelco.
RETURNS
In order to expedite parts returned to the factory for repair or credit, please call the factory at
(800) 289-9100 or (559) 292-1981 to obtain an authorization number (CA number if returned
for credit, and RA number if returned for repair).
All merchandise returned for credit may be subject to a 20% restocking and refurbishing
charge.
Goods returned for repair or credit should be clearly identied with the assigned CA or RA
number and freight should be prepaid. Ship to the appropriate address below.
If you are located within the continental U.S., Alaska, Hawaii or Puerto Rico, send goods to:
Service Department
Pelco
3500 Pelco Way
Clovis, CA 93612-5699
If you are located outside the continental U.S., Alaska, Hawaii or Puerto Rico and are
instructed to return goods to the USA, you may do one of the following:
If the goods are to be sent by a COURIER SERVICE, send the goods to:
Pelco
3500 Pelco Way
Clovis, CA 93612-5699 USA
If the goods are to be sent by a FREIGHT FORWARDER, send the goods to:
Pelco c/o Expeditors
473 Eccles Avenue
South San Francisco, CA 94080 USA
Phone: 650-737-1700
Fax: 650-737-0933
The materials used in the manufacture of this document and its components are compliant to the requirements of Directive 2002/95/EC.
This equipment contains electrical or electronic components that must be recycled properly to comply with Directive 2002/96/EC of the European Union
regarding the disposal of waste electrical and electronic equipment (WEEE). Contact your local dealer for procedures for recycling this equipment.
Pelco, the Pelco logo, Camclosure, Esprit, Genex, Legacy, and Spectra are registered trademarks of Pelco.
Endura and ExSite are trademarks of Pelco.
DLP is a registered trademark of Texas Instruments, Inc.