Professional Documents
Culture Documents
3, AUGUST 2005
1465
I. INTRODUCTION
1466
an ac-to-dc converter fed from the synchronous machine terminals or auxiliary power. The static exciter type is used as power
stage in this study. It is represented by a scaling gain which is
incorporated here into the controller gains.
C. Prime Mover Model
(7)
(8)
The well-known two-axis model in per unit is used to represent the synchronous machine. The stator dynamics and the
subtransient dynamics from two of the three damper-windings
is then represented
are neglected. Generator ,
in its local - reference frame by a fourth order model consisting of the field voltage, one damper winding, the rotor and
the power angle dynamics [8]
(1)
(2)
(3)
,
, and
are the mechanical torque, steam presand
are
sure, and steam valve position respectively.
the re-heater main inlet volumes and steam chest time constants,
is the fraction of total power generated by
respectively.
the high pressure (HP) section.
D. The Network Model
generators through
The network interconnecting the
buses is represented by two sets of algebraic equations [8]. The
first one describes the power equation at a generator terminal
bus and the second set is for a bus without generation
(4)
Equation (1) stands for the slower damper dynamics while the
field dynamics are described by (2). The rotor and the power
angle dynamics are presented by (3) and (4), respectively. Since
stator dynamics are neglected, the latter are simply described by
the following two algebraic equations:
(9.a)
(5)
(9.b)
(6)
,
,
,
,
, and
represent the current, the terminal voltage, the damper-winding flux linkage, and the field
flux voltage in the (local) - reference frame, respectively.
,
,
, and
are the direct- and quadrature-axis synchronous and transient reactances, respectively.
and
are the generator open-circuit time constants.
and
stand for the field voltage and the mechanical torque to the shaft
, and are provided by the exciter and prime mover respectively.
is the rotor speed and the power angle expressed in the absolute reference frame.
B. Exciter Model
The main exciter may be either a dc generator or an inverted
ac generator driven off the main shaft, or a static device such as
and
are the active and reactive powers of loads at bus
. Parameter
is the
entry of the network bus
is expressed in
admittance matrix. The bus voltage
the absolute reference frame. The relation
is valid at the generator terminal bus. Fig. 2
gives the relationship between the absolute frame
and
position and variables.
machine local reference frame
1467
become time-varying parameters. Dividing both active and reactive powers by the square of the load terminal voltage leads
to the following expression:
(13)
Fig. 2.
(11)
is the constant load impedance. Several results in the literature on load modeling have pointed out that the dominant behavior of large power systems loads can be accurately described
by static and dynamic aggregate models [9][11]. Without loss
of generality, let us consider the KarissonHill model [9] to represent dynamic loads
(12.a)
(12.b)
(14.b)
Parameter
is the
entry of the admittance matrix,
and
including all instantaneous impedances
on the
diagonal.
is a time-varying parameter since it depends on
.
Remark 1: The idea behind the loads unified description is
that both the constant impedance and the dynamic loads can be
and
which
represented by the two quantities
can be constant or time-varying depending on the nature of the
is
load. Equation (14) with time-varying parameter
a result of combining (9) and (12). Recall also that the two-axis
model which describes the synchronous generator, the network
model and the loads dynamical model (hence the loads unified
description) are valid under the assumption that fast stator (and
network) dynamics are neglected.
Equations (1)(14) are therefore the equivalent of the traditional multimachine power systems model. This model is not
appropriate for the design of a model-based controller since it
and
) with other signals (curcombines state variables (
rents and voltages). Next, a more suitable multimachine power
system model is derived from the so-called traditional multimachine model.
F. Power System Model for the Design of Decentralized and
Hierarchical Multivariable Control
(12.c)
and
The static load case is obtained by setting
, with
for the constant
impedance case.
and
are referred to as recovery active
and reactive powers respectively [9] (or the constant power comand
, in the dynamic load case,
ponents [8]). Note that
1468
(17)
(15.b)
(16)
The expressions of the parameters appearing in the model are
given in the Appendix .
and
denote the angle (
)
), respectively.
and speed difference (
Remark 2: Since generators terminal voltages can experience abrupt variations (or discontinuities) particularly during
short-circuits, they can not be used a priori as state variables.
The two-axis model assumption which neglects the fast dynamics makes this possible however. Model ((15)(17)) is valid
,
) and
therefore only after the discontinuity (i.e., for
the instant of the discontinuity. Generators terminal
not at
voltages when used as state variables are usually referred to as
pseudo-state variables.
The proposed model is in a form suitable for the application
of modern model-based control methods. Decentralized power
system voltage and rotor speed regulator design becomes more
tractable since each generator terminal voltage and rotor speed
are simply expressed in terms of state variables. (Recall that the
). Also, since nonlinear perturvoltage expression is
bation terms from other generators on generator - represented
by
,
and
are (explicitly) available, a decentralized
controller guaranteeing global stability of multimachine power
,
, and
system is possible. In [12], the perturbation terms (
) are dominated by the local controllers linear terms. The
controllers fixed gains are computed from a global stability condition. Although very good transient and stability performance
may be obtained, this technique remains conservative even if additional tuning conditions based on LMI optimization are used
to reduce this conservativeness [13].
This paper proposes an alternative solution which is less conservative and is based on cancellation of inter generators interactions. The basic idea is to explicitly cancel perturbation terms
on the terminal voltage and rotor speed dynamics using suitably
computed nonlinear terms provided by control inputs (excitation and servo-valve input). Since the perturbations to be cancelled depend on remote generators state variables, remote measurement is needed to implement the solution. Such a control
strategy is called wide-area control. The controller structure and
robustness as well as the transportation delay compensation are
challenging problems that need to be dealt with in this context.
Wide-area control benefits and the technology required for
its implementation, namely phasor measurement unit are amply
reported in recent power systems control literature. The contribution of this paper is to use model-based nonlinear control
technique to systematically derive the controller expression and
specify the remote signals to be measured. The main advantage
of our solution is that it can be used in conjunction with any
1469
Fig. 3.
where
,
,
, and
are the steady-state values of the
excitation, valve-input, mechanical power, and steam chest, re,
,
, and
can be
spectively. The expressions of
derived in a straightforward manner but are omitted here for sake
of simplicity. The sequel gives the step-by-step procedure to derive the multivariable wide-area control laws for each generator.
B. Wide-Area Controller Equations
Each control input (
or
) is decomposed into a local
or
which depends only on locally measurable
term (
or
which depends on
variables) and a global term (
remote signals). That is
(27)
(28)
Recall that our objective is to compute
and
in order
to cancel interaction terms in the voltage and rotor speed dynamics. We adopt the input-output linearization approach for
the design. The method consists of first finding the dynamics of
each variable to be controlled by differentiating it until one input
appears explicitly. Secondly, the inputs expressions are selected
in order to cancel terms which depend on remote signals. To this
end, let us now introduce the variable , which represents the
terminal voltage deviation
(29)
Differentiating
gives
(21)
(22)
(23)
(30)
(24)
From this equation, we choose the global control law for generator as
(25)
(26)
if
otherwise
(31)
1470
(32)
Note that these dynamics depend exclusively on locally measurable signals
and . Also,
depends on all generators
variables hence its wide-area characteristic. A linear controller
such as the conventional AVR-PSS or a nonlinear one [4] can
be used at this level to stabilize local dynamics (32).
, we introduce the rotor speed deviFor the synthesis of
ation
Fig. 4. Example of local controller with global signals from the central
controller.
(33)
Differentiating twice
(i.e., until the control input appears
explicitly) leads to the following dynamics:
(34)
Again,
in (34)
(35)
The remaining dynamics depend only on local variables and are
of the form
(36)
Linear controllers such as the conventional Speed Governor or
a nonlinear counterpart can be used to stabilize local dynamics
(36). Fig. 4 shows an example of interaction between wideand
) and local AVRarea controller output signals (
PSS/Speed Governor standard regulators.
and
deRemark 3: Note that global control laws
,
and
respectively. An append on derivatives of
proximation of the differentiation operation (which filters out
very high frequencies) is very often appropriate. To this end, we
used the following transfer function:
(37)
Remark 4: When a complete ninth-order nonlinear model is
used to represent the synchronous machine and turbine, controls
(31) and (35) will only provide additional damping instead of
exact cancellation. Furthermore, since all practical limitations
on excitation and valve input have not been taken into account
during the design, a scaling gain and saturation are added to
the central controller outputs to give
(38a)
(38b)
1471
TABLE I
LOST SIGNAL EFFECT ON CCT (IN CYCLE)
TABLE II
DELAY EFFECTS ON CCT
1472
TABLE III
SYNCHRONOUS MACHINE PARAMETERS
TABLE IV
TRANSFORMERS, LINES, AND LOADS PARAMETERS
In the next two sections, our solution is tested in a more realistic context. Delays both in the incoming and outgoing communication channels (between generators and the central controller) are now taken into account. A power system with nonlinear loads namely an induction motor and a voltage dependent
load are considered.
Fig. 8. G2 terminal voltage after a 6-cycle short-circuit hierarchical (solid line)
versus conventional (dash line).
Fig. 12.
Fig. 13.
Fig. 14.
Fig. 15.
1473
Fig. 16. G2 rotor oscillations after a 6-cycle short-circuit conFig. 1 (solid line),
conFig. 2 (dashed line), conFig. 3 (dot-dash line).
Fig. 17. G2 terminal voltage after a 4-cycle short-circuit 0 ms delay (solid line)
400 ms delay (dashed line).
time-varying delay one. The constant delay value being the maximum value over the range of variation of the delays. The case
of nonuniform delays (i.e., different delay for each generator) is
out of the scope of this paper and left for further investigation.
D. Aggregate Dynamic Loads Case
A 20 000 MW induction machine supplying 0.9 p.u. of
mechanical power and a voltage dependent nonlinear load
of 10 000 MW and 3000 MVAR are included in load Chr3
1474
Fig. 18. G2 rotor speed after a 4-cycle short-circuit 0 ms delay (solid line) 400
ms delay (dashed line).
Fig. 20. G2 voltage profile in a power system with nonlinear loads hierarchical
(solid line) versus conventional (dashed line).
TABLE V
NONLINEAR LOADS PARAMETERS
Fig. 21. Resistor part of load Chr3 instantaneous impedance after a short
circuit at B3.
Fig. 19. G2 speed profile in a power system with nonlinear loads hierarchical
(solid line) versus conventional (dashed line).
connected to bus B3. The characteristics of the loads are summarized in the appendix section (Table V). Only Chr3 which is
the most significant load is involved in the adaptation process.
The main objective during the test is to assess the proposed
control strategy performance in a realistic power system with
nonlinear and dynamic loads.
Figs. 19 and 20 compare the hierarchical structure performance to the one of the local controller for a three-phase shortcircuit at the dynamic loads bus B3. Once again, the transient
appears in
. The contingency induces a large variation of
the load impedance. These dynamics could considerably affect
the wide-area controller performance if its parameters were left
constant (i.e., without the adaptation process). Updating the parameters helps preserve the model-based hierarchical structure
performance in a realistic power system.
V. CONCLUSION
A wide-area signals-based hierarchical control structure is
proposed to improve power systems stability. Our solution is a
two-level voltage and rotor speed regulator. It consists namely
of local controllers damping local oscillations and a centralized
controller decoupling the subsystems interactions to maximize
the local controllers performance. We propose a multivariable
design approach where wide-area control laws are systematically derived from a reformulation of the multimachine model.
1475
1476
ACKNOWLEDGMENT
The authors are grateful to I. Kamwa and R. Grondin from the
Hydro-Quebec Research Institute for their helpful comments
and invaluable insight. The authors would like to thank the Editor for the unreserved help and patience, the Associate Editor
for giving them the opportunity to improve this paper to its
present quality, and the anonymous reviewers for their constructive comments.
REFERENCES
[1] S. Chen and O. P. Malik, Power system stabilizer design using synthesis, IEEE Trans. Energy Convers., vol. 10, pp. 175181, Mar. 1995.
[2] M. Klein, L. X. Le, G. J. Rogers, S. Farrokhpay, and N. J. Balu, H
damping controller design in large power systems, IEEE Trans. Power
Syst., vol. 10, no. 1, pp. 158166, Feb. 1995.
1477
Louis-A. Dessaint (M88-SM91) received the B.Ing., M.Sc.A., and Ph.D. degrees from the cole Polytechnique de Montral, Montreal, QC, Canada, in
1978, 1980 and 1985, respectively, all in electrical engineering.
He was a research Assistant with the Hydro-Qubec Research Institute
(IREQ) from 1980 to 1985, where he worked on the simulation and control
of a wind energy conversion system. He is currently a Professor of Electrical
Engineering at the cole de Technologie Suprieure, Montral, QC, Canada.
From 1992 to 2001, he was the Director of the Groupe de Recherche en
lectronique de Puissance et Commande Industrielle (GREPCI), a research
group on power electronics and digital control. Since 2002, he has held the
Transnergie Chair on Power Systems Simulation and Control. He is an author
of the MathWorks SimPowerSystems simulation software.
Dr. Dessaint received the Oustanding Engineer Award from the
IEEE-Canada in 1997.
Ouassima Akhrif (M93) received the Diplme dIngnieur dtat degree from
the cole Mohammadia, Rabat, Morocco, in 1984 and the M.Sc.A. and Ph.D.
degrees from the University of Maryland, College Park, in 1987 and 1989, respectively, all in electrical engineering.
During 19891990, she was a Visiting Assistant Professor in the Systems
Engineering Department, Case Western Reserve University, Cleveland, OH. In
1992, she joined the cole de Technologie Suprieure, Montral, PQ, Canada,
where she is currently a Professor in the Electrical Engineering Department.
Her research interests are nonlinear geometric control, nonlinear adaptive control, and their applications in electric drives, power systems, and flight control
systems.