You are on page 1of 13

GUIDE

SPECIFICATIONS
WP Series Water-to-Water Reverse
Cycle Chillers & Low Temp Boilers
WP036-072 Reverse Cycle Chillers / Low Temperature Boilers
GENERAL

ELECTRICAL

Units shall be Underwriter Laboratories (UL) listed for


safety on all models. Each unit shall be run tested at the
factory. Each unit shall be pallet mounted and stretch
wrapped.

Controls and safety devices will be factory wired and


mounted within the unit. Controls shall include,
compressor contactor, 24V transformer, reversing valve
coil and solid state lockout controller (UPM) The UPM
controller shall include the following features: Anti-short
cycle time delay, random start, brown out/surge/power
interruption protection, 120 second low pressure switch
bypass timer, shutdown on high or low refrigerant
pressure safety switch inputs, shutdown for the optional
freezestat, 24 VAC alarm output for remote fault
indication, unit reset at thermostat or disconnect, ability
to defeat time delays for servicing and automatic
intelligent reset. The UPM shall automatically reset after
a safety shut down and restart the unit, if the cause of
the shut down no longer exists, after the anti-short cycle
and random start timers expire. Should a fault re-occur
within 60 minutes after reset, then a permanent lockout
will occur. A light emitting diode (LED) shall annunciate
the following alarms: high refrigerant pressure, low
refrigerant pressure and low water temperature (when
equipped with the optional low water temperature
sensor). The LED will display each fault condition as
soon as the fault occurs. If a permanent lockout occurs,
then the fault LED will display the type of fault until the
unit is reset.

The units shall be warranted by the manufacturer against


defects in materials and workmanship for a period of one
year on all parts, and 5 years on the compressor. The
units shall be manufactured in an ISO 9001:2000 certified
facility.
The units shall be designed to operate with entering fluid
temperatures between 20oF (-7oC) and 120oF (49oC) as
manufactured by FHP Manufacturing in Fort Lauderdale,
Florida. Refrigerant shall be R-22
CASING & CABINET
The cabinet shall be fabricated from heavy-gauge steel
finished with Galvalume plus, an aluminum-zinc alloy
with a clear acrylic coating for additional corrosion
protection. The interior shall be insulated with
(12.7mm) thick, multi density, coated, glass fiber. All
units shall allow sufficient service access to replace the
compressor without unit removal.
REFRIGERATION CIRCUITS
All units shall contain a sealed refrigerant circuit including
a hermetic scroll compressor, bidirectional thermal
expansion valve metering device, coaxial style fluid-torefrigerant heat exchangers, refrigerant reversing valve and
service ports. Compressor shall be high efficiency,
designed for heat pump duty with refrigerant R-22, and
mounted on rubber vibration isolators. Compressor motors
shall be equipped with overload protection. Refrigerant
reversing valves shall be pilot operated sliding piston type
with replaceable encapsulated magnetic coils energized
only during the chiller cycle. The coaxial water-torefrigerant heat exchanger shall be constructed of a
convoluted copper (optional cupronickel) inner tube and
steel outer tube with a designed refrigerant working
pressure of 450 PSIG (3100 kPa) and a designed water
side working pressure of no less than 400 PSIG (2750
kPa). Due to their susceptibility to fouling, brazed plate
heat exchangers are not acceptable. The fluid-torefrigerant heat exchangers shall be insulated to prevent
condensation at low fluid temperatures.

Safety devices include a low pressure cutout set a 20


PSIG (140 kPa) for loss of charge protection (freezestat
and/or high discharge gas temperature sensor is not
acceptable) and a high pressure cutout control set at
400 PSIG (2750 kPa). An optional energy management
relay that allows unit control by an external source shall
be factory installed. A terminal block with screw terminals
shall be provided for control wiring.
PIPING
Water piping connections shall be female pipe thread
with a single set of source and load connections flush
mounted to the unit cabinet.

WPSPECS.P65

REV: 3-05

GUIDE
SPECIFICATIONS
WP Series Water-to-Water Reverse
Cycle Chillers & Low Temp Boilers

WP120 - 420 Modular Reverse Cycle Chillers/Low Temperature Boilers


GENERAL

ELECTRICAL

Units shall be Underwriter Laboratories (UL) listed for safety


on all models. Each unit shall be run tested at the factory.
Each unit shall be pallet mounted and stretch wrapped.

Controls and safety devices will be factory wired and


mounted within the unit. Controls shall include compressor
contactors, 24V transformer, reversing valve coils and a
solid state lock-out control circuit (UPM). The UPM
controller shall include the following features: Anti-short
cycle time delay, random start, interstage delay, brown
out/surge/power interruption protection, 120 second low
pressure switch bypass timer, shutdown on high or low
refrigerant pressure safety switch inputs, shutdown for the
optional freezestat, 24 VAC alarm output for remote fault
indication, unit reset at thermostat or disconnect, ability
to defeat time delays for servicing, time delay between
stages and automatic intelligent reset. The UPM shall
automatically reset after a safety shut down and restart
the unit, if the cause of the shut down no longer exists,
after the anti-short cycle and random start timers expire.
Should a fault re-occur within 60 minutes after reset, then
a permanent lockout will occur. A light emitting diode (LED)
shall annunciate the following alarms for each refrigerant
circuit: high refrigerant pressure, low refrigerant pressure
and low water temperature (when equipped with the optional
low water temperature sensor). The LED will display each
fault condition as soon as the fault occurs. If a permanent
lockout occurs, then the fault LED will display the type of
fault until the unit is reset. Safety devices include a low
pressure cutout set at 20 PSIG (140 kPa) for loss of charge
protection (a freezestat used for loss of charge protection
is not acceptable) and a high pressure cutout control set
at 400 PSIG (2750 kPa). An optional energy management
relay to allow unit control by an external source shall be
factory installed.

The units shall be warranted by the manufacturer against


defects in materials and workmanship for a period of one
year on all parts, and 5 years on the compressor. The units
shall be manufactured in an ISO 9001:2000 certified facility.
The units shall be designed to operate with entering fluid
temperatures between 20oF (-7oC) and 120oF (49oC) as
manufactured by FHP Manufacturing in Fort Lauderdale,
Florida. Refrigerant shall be R-22.
CASING & CABINET
The cabinet shall be fabricated from heavy-gauge galvanized
steel and shall be supported by a full angle iron frame. The
interior shall be insulated with (12.7mm) thick, multi
density, coated, glass fiber. All units shall allow front service
access to replace the compressor and/or electrical
components without unit removal.
REFRIGERATION CIRCUITS
All units shall contain a sealed refrigerant circuit including
hermetic scroll compressor(s), bidirectional thermal
expansion valve metering device(s), coaxial style fluid-torefrigerant heat exchangers, refrigerant reversing valve(s) and
service ports. Compressor shall be high efficiency, designed
for heat pump duty with refrigerant R-22, and mounted on
rubber vibration isolators. Compressor motors shall be
equipped with overload protection. Refrigerant reversing
valves shall be pilot operated sliding piston type with
replaceable encapsulated magnetic coils energized only
during the chiller cycle. The coaxial water-to-refrigerant heat
exchanger shall be constructed of a convoluted copper
(optional cupronickel) inner tube and steel outer tube with a
designed refrigerant working pressure of 450 PSIG (3100
kPa) and a designed water side working pressure of no less
than 400 PSIG (2750 kPa). Due to their susceptibility to
fouling, brazed plate heat exchangers are not acceptable.
The fluid-to-refrigerant heat exchangers shall be insulated to
prevent condensation at low fluid temperatures.

PIPING
Water piping connections shall be female pipe thread
with a single set of source and load connections per
unit.

WPSPECS.P65

REV: 3-05

A
Height
24.25
24.25
24.25

B
Width
32.50
32.50
32.50

C
Depth
24.00
24.00
24.00
2.50
3.00
3.38

NOTES: All dimensions within +/- 0.125".


Specifications subject to change without notice.

WP036
WP060
WP072

MODEL
2.00
2.50
2.50

14.88
17.00
22.75

2.25
2.50
4.38

G
2.50
4.00
3.38

H
8.25
3.38
4.38

J
14.88
18.00
22.75

Water
Conn.
0.75 FPT
1.00 FPT
1.00 FPT

Cabinet Type:
CS-Condensing Section

WPSDGIP.P65

REV: 4-01

Condenser Material:
C-Copper
N-Cupro-Nickel

Water Connections:
F-Front

Return Air Location:


X-None

Nominal Capacity:
Voltage:
1-208/230-1-60
3-208/230-3-60
4-460-3-60
5-575-3-60

Supply Air Location:


X-None

Series:
WP-Water-to-Water

WP___-_ __ _-_ _ _

WP Series Reverse Cycle Chiller Nomenclature

2.25
3.38
2.50

Reverse Cycle Chillers

WP036-072 Series

Dimensions
E
F

FHP Manufacturing Co.


601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471
Fax: (800) 776-5529
http://www.fhp-mfg.com

A
Height
32.00
32.00
32.00
64.00
64.00
64.00

23.00
23.00
23.00
39.00
39.00
39.00

B
8.50
4.50
4.50
8.50
4.50
4.50

C
3.75
3.75
3.75
19.75
19.75
19.75

NOTES: All units are 46.00 in depth.


All dimensions within +/- 0.125".
Specifications subject to change without notice.

WP120
WP180
WP210
WP240
WP360
WP420

MODEL
10.50
10.50
10.50
10.50
10.50
10.50

28.50
28.50
28.50
44.50
44.50
44.50

10.50
10.50
10.50
10.50
10.50
10.50

G
9.25
9.25
9.25
25.25
25.25
25.25

H
9.00
5.00
5.00
9.00
5.00
5.00

Water
Conn.
1.25 FPT
1.50 FPT
1.50 FPT
2.00 FPT
2.00 FPT
2.00 FPT

Cabinet Type:
CS-Condensing Section

WPLDGIP.P65

REV: 4-01

Condenser Material:
C-Copper
N-Cupro-Nickel

Water Connections:
R-Rear

Return Air Location:


X-None

Nominal Capacity:
Voltage:
3-208/230-3-60
4-460-3-60
5-575-3-60

Supply Air Location:


X-None

Series:
WP-Water-to-Water

WP___-_ __ _-_ _ _

WP Series Reverse Cycle Chiller Nomenclature

Reverse Cycle Chillers

WP120-420 Series

Dimensions
E
F

FHP Manufacturing Co.


601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471
Fax: (800) 776-5529
http://www.fhp-mfg.com

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-1-60
208/230-3-60
460-3-60

-1
-3
-4

Compressor
RLA
18.9
12.2
6.2

LRA
96
75
40

WP036
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
23.6
15.3
7.8

Max.
Fuse
Size
40
25
15

Chilled Fluid Side (@ 55OF)


Flow (GPM)
P (FOH)
4
2.8
5
5.9
7
9.9
9
14.8
11
20.6

Cond. Fluid Side (@ 85OF)


Flow (GPM)
P (FOH)
4
2.7
5
5.6
7
9.3
9
14.0
11
19.4

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

250
270

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 7 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 7 GPM source fluid flow.

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
2.66
80O
2.56
40O
85O
2.45
90O
2.35
95O
2.24
75O
2.78
80O
2.68
42O
85O
2.57
90O
2.46
95O
2.35
75O
2.91
80O
2.80
44O
85O
2.68
90O
2.57
95O
2.46
75O
2.97
80O
2.86
45O
85O
2.75
90O
2.63
95O
2.51
75O
3.04
80O
2.92
46O
85O
2.81
90O
2.69
95O
2.57
75O
3.17
80O
3.05
48O
85O
2.93
90O
2.81
95O
2.69
75O
3.31
80O
3.18
50O
85O
3.06
90O
2.93
95O
2.81

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
31,965
2,251
30,717
2,330
29,456
2,403
28,184
2,469
26,906
2,529
33,410
2,277
32,120
2,360
30,817
2,438
29,505
2,509
28,187
2,574
34,899
2,300
33,565
2,389
32,219
2,471
30,864
2,548
29,504
2,617
35,669
2,311
34,312
2,402
32,943
2,487
31,566
2,566
30,167
2,639
36,450
2,322
35,054
2,416
33,662
2,503
32,262
2,584
30,858
2,659
38,032
2,342
36,603
2,440
35,148
2,533
33,701
2,619
32,250
2,699
39,663
2,361
38,183
2,464
36,693
2,561
35,181
2,653
33,682
2,738

EER
14.2
13.2
12.3
11.4
10.6
14.7
13.6
12.6
11.8
11.0
15.2
14.1
13.0
12.1
11.3
15.4
14.3
13.3
12.3
11.4
15.7
14.5
13.5
12.5
11.6
16.2
15.0
13.9
12.9
12.0
16.8
15.5
14.3
13.3
12.3

Heat
Rejection
(BtuH)
39,645
38,667
37,654
36,609
35,536
41,177
40,174
39,135
38,066
36,969
42,749
41,717
40,651
39,556
38,434
43,555
42,509
41,429
40,320
39,171
44,371
43,298
42,203
41,080
39,931
46,023
44,930
43,792
42,638
41,460
47,717
46,589
45,431
44,232
43,022

Heating
Capacity
(BtuH)
29,085
31,872
37,802
44,205
51,090
27,432
30,205
36,035
42,308
49,024
25,686
28,418
34,177
40,311
46,859
24,772
27,508
33,210
39,282
45,747
23,839
26,565
32,227
38,236
44,606

Power
Input
Watts
2,219
2,321
2,502
2,651
2,767
2,296
2,417
2,640
2,831
2,988
2,350
2,494
2,759
2,993
3,193
2,370
2,524
2,811
3,068
3,291
2,385
2,549
2,860
3,139
3,385

COP
3.8
4.0
4.4
4.9
5.4
3.5
3.7
4.0
4.4
4.8
3.2
3.3
3.6
3.9
4.3
3.1
3.2
3.5
3.8
4.1
2.9
3.1
3.3
3.6
3.9

Heat of
Absorb.
(BtuH)
21,513
23,953
29,266
35,158
41,649
19,599
21,958
27,027
32,649
38,829
17,667
19,910
24,765
30,098
35,963
16,685
18,897
23,618
28,813
34,519
15,703
17,866
22,470
27,526
33,056

Units are complete packages featuring 1 stage operation and


containing refrigeration compressor, reversing valve, expansion valve
metering device and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressor, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP036IP6.P65

Rev:4-01

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-1-60
208/230-3-60
460-3-60

-1
-3
-4

Compressor
RLA
25.1
17.7
8.1

LRA
169
123
49.5

WP060
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
31.4
22.1
10.1

Max.
Fuse
Size
50
40
15

Chilled Fluid Side (@ 55OF)


Flow (GPM)
P (FOH)
6
2.3
9
4.7
12
8.0
18
16.5
20
20.0

Cond. Fluid Side (@ 85OF)


Flow (GPM)
P (FOH)
6
2.2
9
4.5
12
7.5
18
15.6
20
18.8

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

310
330

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 12 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 12 GPM source fluid flow.

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
3.76
80O
3.70
40O
85O
3.63
90O
3.56
95O
3.49
75O
3.90
80O
3.84
42O
85O
3.77
90O
3.70
95O
3.62
75O
4.05
80O
3.98
44O
85O
3.91
90O
3.84
95O
3.76
75O
4.12
80O
4.05
45O
85O
3.98
90O
3.91
95O
3.82
75O
4.19
80O
4.13
46O
85O
4.05
90O
3.98
95O
3.90
75O
4.35
80O
4.28
48O
85O
4.20
90O
4.12
95O
4.04
75O
4.50
80O
4.43
50O
85O
4.35
90O
4.27
95O
4.18

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
45,168
3,177
44,416
3,370
43,612
3,578
42,746
3,804
41,831
4,047
46,849
3,180
46,075
3,373
45,249
3,580
44,369
3,802
43,425
4,045
48,577
3,181
47,774
3,376
46,927
3,581
46,025
3,802
45,067
4,041
49,449
3,184
48,643
3,376
47,784
3,581
46,864
3,804
45,895
4,042
50,339
3,185
49,521
3,377
48,652
3,582
47,721
3,803
46,741
4,040
52,148
3,188
51,301
3,381
50,410
3,585
49,465
3,803
48,455
4,040
53,992
3,193
53,130
3,383
52,216
3,586
51,242
3,805
50,219
4,038

EER
14.2
13.2
12.2
11.2
10.3
14.7
13.7
12.6
11.7
10.7
15.3
14.2
13.1
12.1
11.2
15.5
14.4
13.3
12.3
11.4
15.8
14.7
13.6
12.5
11.6
16.4
15.2
14.1
13.0
12.0
16.9
15.7
14.6
13.5
12.4

Heat
Rejection
(BtuH)
56,007
55,916
55,822
55,727
55,638
57,698
57,583
57,463
57,342
57,225
59,432
59,292
59,146
58,999
58,855
60,314
60,162
60,004
59,842
59,685
61,207
61,044
60,873
60,698
60,526
63,025
62,836
62,640
62,440
62,239
64,885
64,674
64,452
64,224
63,997

Heating
Capacity
(BtuH)
47,724
50,896
57,779
65,378
73,690
48,028
51,094
57,768
65,167
73,287
48,428
51,377
57,825
65,004
72,914
48,674
51,563
57,890
64,952
72,748
48,960
51,782
57,985
64,926
72,604

Power
Input
Watts
3,812
3,808
3,802
3,805
3,817
4,340
4,326
4,302
4,290
4,287
4,962
4,935
4,888
4,852
4,827
5,312
5,280
5,218
5,168
5,132
5,695
5,651
5,575
5,509
5,457

COP
3.7
3.9
4.5
5.0
5.7
3.2
3.5
3.9
4.5
5.0
2.9
3.1
3.5
3.9
4.4
2.7
2.9
3.3
3.7
4.2
2.5
2.7
3.0
3.5
3.9

Heat of
Absorb.
(BtuH)
34,718
37,904
44,806
52,395
60,665
33,220
36,332
43,089
50,529
58,659
31,498
34,539
41,147
48,448
56,442
30,551
33,546
40,086
47,319
55,239
29,529
32,500
38,962
46,129
53,984

Units are complete packages featuring 1 stage operation and


containing refrigeration compressor, reversing valve, expansion valve
metering device and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressor, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP060IP6.P65

Rev:4-01

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-1-60
208/230-3-60
460-3-60
575-3-60

-1
-3
-4
-5

Compressor
RLA
28.8
19.1
9.1
7.2

LRA
169
137
62
50

WP072
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
36.0
23.9
11.4
9.0

Max.
Fuse
Size
60
40
20
15

Chilled Fluid Side (@ 55OF)


Flow (GPM)
P (FOH)
7
2.7
11
5.6
14
9.3
17
12.9
21
19.3

Cond. Fluid Side (@ 85OF)


Flow (GPM)
P (FOH)
7
2.5
11
5.2
14
8.8
17
12.2
21
18.2

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

430
450

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 14 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 14 GPM source fluid flow.

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
4.55
80O
4.46
40O
85O
4.36
90O
4.26
95O
4.15
75O
4.71
80O
4.61
42O
85O
4.51
90O
4.41
95O
4.30
75O
4.87
80O
4.78
44O
85O
4.67
90O
4.56
95O
4.45
75O
4.96
80O
4.86
45O
85O
4.75
90O
4.64
95O
4.53
75O
5.04
80O
4.94
46O
85O
4.84
90O
4.72
95O
4.61
75O
5.21
80O
5.11
48O
85O
5.00
90O
4.89
95O
4.77
75O
5.39
80O
5.28
50O
85O
5.17
90O
5.06
95O
4.94

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
54,612
3,649
53,492
3,868
52,324
4,101
51,080
4,352
49,760
4,621
56,524
3,652
55,376
3,870
54,172
4,103
52,904
4,353
51,571
4,619
58,484
3,656
57,306
3,872
56,074
4,104
54,780
4,353
53,413
4,619
59,483
3,657
58,289
3,873
57,043
4,105
55,734
4,353
54,355
4,619
60,494
3,659
59,284
3,875
58,022
4,105
56,700
4,353
55,307
4,619
62,555
3,663
61,311
3,878
60,017
4,107
58,664
4,354
57,243
4,619
64,669
3,668
63,388
3,881
62,060
4,110
60,675
4,355
59,224
4,619

EER
15.0
13.8
12.8
11.7
10.8
15.5
14.3
13.2
12.2
11.2
16.0
14.8
13.7
12.6
11.6
16.3
15.0
13.9
12.8
11.8
16.5
15.3
14.1
13.0
12.0
17.1
15.8
14.6
13.5
12.4
17.6
16.3
15.1
13.9
12.8

Heat
Rejection
(BtuH)
67,063
66,690
66,315
65,927
65,526
68,985
68,580
68,171
67,755
67,331
70,957
70,518
70,077
69,631
69,175
71,962
71,505
71,047
70,585
70,115
72,980
72,505
72,030
71,552
71,066
75,055
74,542
74,031
73,520
73,002
77,183
76,631
76,083
75,536
74,985

Heating
Capacity
(BtuH)
56,626
60,280
68,118
76,728
86,182
56,285
59,877
67,555
75,958
85,156
55,849
59,394
66,941
75,162
84,136
55,587
59,114
66,606
74,749
83,620
55,294
58,807
66,253
74,324
83,098

Power
Input
Watts
4,359
4,354
4,352
4,357
4,367
4,932
4,920
4,907
4,903
4,909
5,588
5,571
5,547
5,537
5,537
5,954
5,933
5,903
5,890
5,888
6,341
6,317
6,283
6,266
6,264

COP
3.8
4.1
4.6
5.2
5.8
3.3
3.6
4.0
4.5
5.1
2.9
3.1
3.5
4.0
4.5
2.7
2.9
3.3
3.7
4.2
2.6
2.7
3.1
3.5
3.9

Heat of
Absorb.
(BtuH)
41,752
45,422
53,268
61,862
71,284
39,458
43,089
50,812
59,228
68,407
36,782
40,387
48,016
56,270
65,242
35,272
38,871
46,464
54,652
63,531
33,658
37,252
44,815
52,943
61,724

Units are complete packages featuring 1 stage operation and


containing refrigeration compressor, reversing valve, expansion valve
metering device and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressor, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP072IP6.P65

Rev:1-07

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-3-60
460-3-60
575-3-60

-3
-4
-5

Compressor
RLA
37.8
17.2
12.4

LRA
239
125
80

WP120
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
47.3
21.5
15.5

Max.
Fuse
Size
80
35
25

Chilled Water Side (@ 55OF)


Flow (GPM)
P (FOH)
12
2.5
18
5.2
24
8.7
30
13.0
36
18.1

Cond. Water Side (@ 85OF)


Flow (GPM)
P (FOH)
12
2.4
18
4.9
24
8.2
30
12.2
36
17.0

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

500
520

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 24 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 24 GPM source fluid flow.

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
8.80
80O
8.62
40O
85O
8.44
90O
8.24
95O
8.04
75O
9.12
80O
8.94
42O
85O
8.74
90O
8.54
95O
8.34
75O
9.45
80O
9.26
44O
85O
9.06
90O
8.85
95O
8.64
75O
9.62
80O
9.42
45O
85O
9.22
90O
9.01
95O
8.79
75O
9.79
80O
9.59
46O
85O
9.38
90O
9.17
95O
8.95
75O
10.13
80O
9.92
O
48
85O
9.71
90O
9.49
95O
9.27
75O
10.48
80O
10.27
O
50
85O
10.05
90O
9.82
95O
9.59

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
105,641
7,421
103,480
7,801
101,234
8,208
98,910
8,643
96,484
9,108
109,473
7,452
107,241
7,830
104,927
8,237
102,525
8,672
100,033
9,136
113,400
7,484
111,095
7,861
108,709
8,266
106,237
8,700
103,676
9,163
115,399
7,501
113,057
7,877
110,634
8,282
108,117
8,716
105,520
9,179
117,422
7,517
115,042
7,894
112,573
8,299
110,028
8,731
107,395
9,193
121,542
7,553
119,084
7,927
116,547
8,330
113,917
8,762
111,209
9,222
125,769
7,588
123,221
7,963
120,604
8,363
117,896
8,794
115,112
9,252

EER
14.2
13.3
12.3
11.4
10.6
14.7
13.7
12.7
11.8
10.9
15.2
14.1
13.2
12.2
11.3
15.4
14.4
13.4
12.4
11.5
15.6
14.6
13.6
12.6
11.7
16.1
15.0
14.0
13.0
12.1
16.6
15.5
14.4
13.4
12.4

Heat
Rejection
(BtuH)
130,960
130,095
129,240
128,398
127,561
134,898
133,959
133,030
132,113
131,205
138,935
137,918
136,914
135,921
134,940
140,991
139,935
138,891
137,856
136,837
143,072
141,976
140,889
139,818
138,760
147,311
146,132
144,967
143,812
142,674
151,659
150,389
149,139
147,901
146,681

Heating
Capacity
(BtuH)
108,518
115,727
131,227
148,212
166,727
108,057
115,067
130,118
146,583
164,507
107,625
114,442
129,052
145,004
162,348
107,417
114,142
128,533
144,232
161,290
107,216
113,847
128,024
143,473
160,245

Power
Input
Watts
8,485
8,543
8,665
8,796
8,947
9,460
9,517
9,629
9,750
9,891
10,560
10,615
10,720
10,830
10,958
11,164
11,214
11,315
11,421
11,541
11,800
11,850
11,945
12,044
12,159

COP
3.7
4.0
4.4
4.9
5.5
3.3
3.5
4.0
4.4
4.9
3.0
3.2
3.5
3.9
4.3
2.8
3.0
3.3
3.7
4.1
2.7
2.8
3.1
3.5
3.9

Heat of
Absorb.
(BtuH)
79,567
86,578
101,661
118,201
136,199
75,779
82,597
97,263
113,316
130,758
71,592
78,223
92,475
108,053
124,958
69,326
75,880
89,926
105,265
121,911
66,956
73,415
87,267
102,380
118,760

Units are complete packages featuring 1 stage operation and


containing refrigeration compressor, reversing valve, expansion valve
metering device and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressor, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP120IP6.P65

Rev:4-01

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-3-60
460-3-60
575-3-60

-3
-4
-5

Compressor
RLA
41.0
21.8
17.3

LRA
350
158
125

WP180
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
51.3
27.3
21.6

Max.
Fuse
Size
90
45
35

Chilled Fluid Side (@ 55OF)


Flow (GPM)
P (FOH)
24
5.2
30
7.7
36
10.8
42
14.2
48
18.1

Cond. Fluid Side (@ 85OF)


Flow (GPM)
P (FOH)
24
4.9
30
7.3
36
10.1
42
13.4
48
17.0

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

740
760

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 36 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 36 GPM source fluid flow.

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
10.61
80O
10.42
40O
85O
10.23
90O
10.04
95O
9.85
75O
10.98
80O
10.78
O
42
85O
10.58
90O
10.38
95O
10.18
75O
11.37
80O
11.15
44O
85O
10.94
90O
10.73
95O
10.52
75O
11.56
80O
11.34
45O
85O
11.13
90O
10.91
95O
10.69
75O
11.76
80O
11.54
46O
85O
11.32
90O
11.10
95O
10.87
75O
12.17
80O
11.94
48O
85O
11.71
90O
11.47
95O
11.24
75O
12.59
80O
12.35
O
50
85O
12.11
90O
11.86
95O
11.61

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
127,340
8,980
125,016
9,464
122,728
9,981
120,454 10,532
118,179 11,117
131,792
9,009
129,361
9,492
126,955 10,007
124,545 10,559
122,132 11,144
136,389
9,037
133,842
9,519
131,311 10,035
128,781 10,584
126,222 11,171
138,732
9,053
136,131
9,534
133,549 10,047
130,948 10,598
128,320 11,184
141,118
9,068
138,464
9,548
135,815 10,061
133,158 10,610
130,453 11,198
145,998
9,098
143,237
9,575
140,471 10,087
137,678 10,635
134,836 11,223
151,025
9,129
148,157
9,603
145,266 10,114
142,346 10,661
139,366 11,248

EER
14.2
13.2
12.3
11.4
10.6
14.6
13.6
12.7
11.8
11.0
15.1
14.1
13.1
12.2
11.3
15.3
14.3
13.3
12.4
11.5
15.6
14.5
13.5
12.6
11.6
16.0
15.0
13.9
12.9
12.0
16.5
15.4
14.4
13.4
12.4

Heat
Rejection
(BtuH)
157,978
157,308
156,784
156,389
156,111
162,530
161,746
161,099
160,572
160,156
167,224
166,322
165,550
164,895
164,338
169,621
168,662
167,831
167,108
166,481
172,058
171,040
170,145
169,358
168,660
177,041
175,907
174,888
173,966
173,128
182,174
180,924
179,776
178,722
177,743

Heating
Capacity
(BtuH)
136,373
144,542
162,647
183,247
206,495
137,648
145,261
162,273
181,807
204,017
139,379
146,365
162,147
180,482
201,526
140,378
147,024
162,139
179,825
200,239
141,446
147,733
162,147
179,150
198,898

Power
Input
Watts
10,384
10,449
10,571
10,683
10,791
11,580
11,654
11,788
11,900
11,999
12,926
13,014
13,169
13,295
13,395
13,659
13,758
13,927
14,063
14,168
14,436
14,544
14,734
14,882
14,996

COP
3.8
4.1
4.5
5.0
5.6
3.5
3.7
4.0
4.5
5.0
3.2
3.3
3.6
4.0
4.4
3.0
3.1
3.4
3.7
4.1
2.9
3.0
3.2
3.5
3.9

Heat of
Absorb.
(BtuH)
100,944
108,889
126,579
146,795
169,676
98,137
105,496
122,053
141,203
163,077
95,276
101,960
117,215
135,120
155,824
93,774
100,082
114,620
131,842
151,899
92,191
98,108
111,877
128,374
147,731

Units are complete packages featuring 1 stage operation and


containing refrigeration compressor, reversing valve, expansion valve
metering device and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressor, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP180IP6.P65

Rev:4-01

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-3-60
460-60-3
575-3-60

-3
-4
-5

Compressor
RLA
48.1
23.8
21.8

LRA
425
187
148

WP210
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
60.1
29.6
27.3

Max.
Fuse
Size
100
50
45

Chilled Fluid Side (@ 55OF)


Flow (GPM)
P (FOH)
24
5.2
30
7.7
36
10.8
42
14.2
48
18.1

Cond. Fluid Side (@ 85OF)


Flow (GPM)
P (FOH)
24
4.9
30
7.3
36
10.1
42
13.4
48
17.0

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

770
790

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 42 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 42 GPM source fluid flow

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
12.48
80O
12.21
40O
85O
11.92
90O
11.62
95O
11.30
75O
12.96
80O
12.68
O
42
85O
12.38
90O
12.07
95O
11.74
75O
13.45
80O
13.16
O
44
85O
12.85
90O
12.53
95O
12.19
75O
13.71
80O
13.41
45O
85O
13.09
90O
12.76
95O
12.42
75O
13.96
80O
13.66
46O
85O
13.34
90O
13.00
95O
12.65
75O
14.49
80O
14.17
48O
85O
13.83
90O
13.49
95O
13.13
75O
15.02
80O
14.69
50O
85O
14.35
90O
13.99
95O
13.62

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
149,760 11,216
146,509 11,862
143,050 12,541
139,414 13,251
135,602 13,996
155,519 11,227
152,138 11,873
148,556 12,553
144,801 13,266
140,866 14,015
161,449 11,237
157,933 11,882
154,222 12,563
150,334 13,278
146,281 14,031
164,477 11,241
160,882 11,888
157,113 12,567
153,162 13,283
149,037 14,039
167,548 11,246
163,882 11,892
160,035 12,573
156,018 13,290
151,841 14,045
173,828 11,255
170,016 11,899
166,019 12,581
161,867 13,299
157,550 14,057
180,288 11,264
176,314 11,908
172,169 12,589
167,876 13,307
163,425 14,066

EER
13.4
12.4
11.4
10.5
9.7
13.9
12.8
11.8
10.9
10.1
14.4
13.3
12.3
11.3
10.4
14.6
13.5
12.5
11.5
10.6
14.9
13.8
12.7
11.7
10.8
15.4
14.3
13.2
12.2
11.2
16.0
14.8
13.7
12.6
11.6

Heat
Rejection
(BtuH)
188,028
186,981
185,840
184,627
183,354
193,825
192,649
191,387
190,063
188,686
199,788
198,475
197,086
195,640
194,154
202,833
201,444
199,992
198,485
196,938
205,920
204,458
202,934
201,363
199,761
212,230
210,617
208,946
207,242
205,512
218,721
216,944
215,124
213,280
211,419

Heating
Capacity
(BtuH)
158,397
169,313
192,769
218,696
247,430
157,272
167,962
190,804
215,905
243,619
155,892
166,428
188,794
213,208
240,028
155,147
165,630
187,811
211,929
238,352
154,384
164,835
186,865
210,723
236,781

Power
Input
Watts
13,133
13,193
13,273
13,313
13,339
14,608
14,696
14,815
14,877
14,906
16,217
16,339
16,516
16,617
16,668
17,074
17,220
17,431
17,559
17,627
17,972
18,138
18,388
18,548
18,638

COP
3.5
3.8
4.3
4.8
5.4
3.2
3.3
3.8
4.3
4.8
2.8
3.0
3.4
3.8
4.2
2.7
2.8
3.2
3.5
4.0
2.5
2.7
3.0
3.3
3.7

Heat of
Absorb.
(BtuH)
113,586
124,299
147,482
173,272
201,918
107,429
117,820
140,255
165,144
192,761
100,559
110,678
132,440
156,510
183,158
96,891
106,876
128,337
152,019
178,208
93,065
102,949
124,126
147,438
173,186

Units are complete packages featuring 1 stage operation and


containing refrigeration compressor, reversing valve, expansion valve
metering device and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressor, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP210IP6.P65

Rev:4-01

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-3-60
460-3-60
575-3-60

-3
-4
-5

Compressor (Ea)
RLA
37.8
17.3
12.4

LRA
239
125
80

WP240
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
85.1
38.7
27.9

Max.
Fuse
Size
110
50
40

Chilled Fluid Side (@ 55OF)


Flow (GPM)
P (FOH)
24
4.3
36
9.0
48
15.1
60
22.6
72
31.3

Cond. Fluid Side (@ 85OF)


Flow (GPM)
P (FOH)
24
4.1
36
8.5
48
14.2
60
21.2
72
29.5

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

970
990

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 48 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 48 GPM source fluid flow.

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
17.61
80O
17.25
40O
85O
16.87
90O
16.48
95O
16.08
75O
18.24
80O
17.87
42O
85O
17.49
90O
17.09
95O
16.67
75O
18.90
80O
18.52
44O
85O
18.12
90O
17.71
95O
17.28
75O
19.23
80O
18.84
45O
85O
18.44
90O
18.02
95O
17.59
75O
19.57
80O
19.17
46O
85O
18.76
90O
18.34
95O
17.90
75O
20.26
80O
19.85
48O
85O
19.42
90O
18.99
95O
18.53
75O
20.96
80O
20.54
50O
85O
20.10
90O
19.65
95O
19.18

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
211,275 14,843
206,960 15,601
202,468 16,416
197,810 17,287
192,967 18,217
218,938 14,905
214,474 15,662
209,844 16,475
205,050 17,343
200,065 18,272
226,791 14,969
222,181 15,724
217,409 16,534
212,465 17,401
207,342 18,328
230,790 15,002
226,105 15,756
221,259 16,565
216,234 17,432
211,039 18,357
234,836 15,036
230,076 15,789
225,146 16,598
220,056 17,462
214,789 18,385
243,084 15,105
238,159 15,856
233,084 16,661
227,834 17,523
222,419 18,444
251,529 15,177
246,441 15,925
241,199 16,728
235,792 17,588
230,214 18,506

EER
14.2
13.3
12.3
11.4
10.6
14.7
13.7
12.7
11.8
10.9
15.2
14.1
13.1
12.2
11.3
15.4
14.4
13.4
12.4
11.5
15.6
14.6
13.6
12.6
11.7
16.1
15.0
14.0
13.0
12.1
16.6
15.5
14.4
13.4
12.4

Heat
Rejection
(BtuH)
261,917
260,190
258,480
256,792
255,123
269,792
267,914
266,057
264,225
262,410
277,866
275,833
273,824
271,839
269,876
281,978
279,865
277,779
275,713
273,674
286,140
283,947
281,777
279,636
277,520
294,623
292,260
289,930
287,624
285,349
303,313
300,778
298,275
295,801
293,357

Heating
Capacity
(BtuH)
217,035
231,453
262,454
296,422
333,451
216,113
230,135
260,236
293,163
329,013
215,248
228,884
258,103
290,006
324,693
214,834
228,282
257,067
288,464
322,577
214,432
227,692
256,048
286,944
320,486

Power
Input
Watts
16,970
17,089
17,331
17,593
17,896
18,920
19,033
19,259
19,502
19,782
21,124
21,231
21,440
21,662
21,919
22,328
22,430
22,630
22,841
23,085
23,602
23,702
23,891
24,090
24,319

COP
3.7
4.0
4.4
4.9
5.5
3.3
3.5
4.0
4.4
4.9
3.0
3.2
3.5
3.9
4.3
2.8
3.0
3.3
3.7
4.1
2.7
2.8
3.1
3.5
3.9

Heat of
Absorb.
(BtuH)
159,134
173,147
203,322
236,395
272,390
151,558
165,193
194,525
226,623
261,516
143,175
156,445
184,951
216,096
249,907
138,652
151,750
179,852
210,529
243,812
133,900
146,819
174,534
204,749
237,509

Units are complete packages featuring 2 stage operation and


containing refrigeration compressors, reversing valves, expansion valve
metering devices and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressors, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP240IP6.P65

Rev:4-01

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-3-60
460-3-60
575-3-60

-3
-4
-5

Compressor (Ea)
RLA
41.0
23.7
17.3

LRA
350
158
125

WP360
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
92.3
49.1
38.9

Max.
Fuse
Size
125
70
50

Chilled Fluid Side (@ 55OF)


Flow (GPM)
P (FOH)
54
11.1
60
13.4
72
18.6
84
24.6
96
31.2

Cond. Fluid Side (@ 85OF)


Flow (GPM)
P (FOH)
54
10.4
60
12.6
72
17.5
84
23.1
96
29.4

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

1490
1510

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 72 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 72 GPM source fluid flow.

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
21.22
80O
20.84
40O
85O
20.45
90O
20.08
95O
19.70
75O
21.97
80O
21.56
42O
85O
21.16
90O
20.76
95O
20.35
75O
22.73
80O
22.31
44O
85O
21.89
90O
21.46
95O
21.04
75O
23.12
80O
22.69
45O
85O
22.26
90O
21.82
95O
21.39
75O
23.52
80O
23.08
46O
85O
22.64
90O
22.19
95O
21.74
75O
24.33
80O
23.87
48O
85O
23.41
90O
22.95
95O
22.47
75O
25.17
80O
24.69
50O
85O
24.21
90O
23.72
95O
23.23

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
254,680 17,959
250,032 18,929
245,449 19,964
240,908 21,064
236,350 22,237
263,584 18,017
258,713 18,985
253,902 20,016
249,090 21,118
244,256 22,290
272,770 18,076
267,676 19,040
262,622 20,070
257,562 21,168
252,437 22,344
277,464 18,106
272,263 19,068
267,091 20,096
261,896 21,196
256,640 22,369
282,236 18,136
276,928 19,095
271,631 20,123
266,308 21,221
260,906 22,396
291,996 18,196
286,466 19,152
280,934 20,175
275,349 21,272
269,672 22,446
302,050 18,258
296,307 19,208
290,533 20,229
284,692 21,323
278,732 22,495

EER
14.2
13.2
12.3
11.4
10.6
14.6
13.6
12.7
11.8
11.0
15.1
14.1
13.1
12.2
11.3
15.3
14.3
13.3
12.4
11.5
15.6
14.5
13.5
12.5
11.6
16.0
15.0
13.9
12.9
12.0
16.5
15.4
14.4
13.4
12.4

Heat
Rejection
(BtuH)
315,956
314,616
313,566
312,779
312,221
325,060
323,489
322,195
321,145
320,311
334,445
332,641
331,100
329,789
328,675
339,242
337,324
335,659
334,215
332,963
344,115
342,081
340,290
338,714
337,320
354,081
351,812
349,773
347,930
346,256
364,347
361,844
359,553
357,445
355,486

Heating
Capacity
(BtuH)
272,747
289,084
325,293
366,491
412,986
275,298
290,523
324,546
363,614
408,032
278,758
292,732
324,294
360,963
403,053
280,759
294,049
324,278
359,649
400,475
282,893
295,469
324,295
358,298
397,793

Power
Input
Watts
20,768
20,899
21,142
21,369
21,583
23,162
23,311
23,575
23,801
23,999
25,851
26,031
26,338
26,589
26,789
27,321
27,516
27,854
28,125
28,337
28,872
29,091
29,467
29,766
29,994

COP
3.8
4.1
4.5
5.0
5.6
3.5
3.7
4.0
4.5
5.0
3.2
3.3
3.6
4.0
4.4
3.0
3.1
3.4
3.7
4.1
2.9
3.0
3.2
3.5
3.9

Heat of
Absorb.
(BtuH)
201,888
217,777
253,157
293,582
339,344
196,269
210,986
244,107
282,405
326,146
190,553
203,914
234,430
270,240
311,647
187,542
200,165
229,240
263,685
303,788
184,381
196,209
223,753
256,738
295,452

Units are complete packages featuring 2 stage operation and


containing refrigeration compressors, reversing valves, expansion valve
metering devices and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressors, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP360IP6.P65

Rev:4-01

WATER COOLED CHILLERS AND LOW TEMP BOILERS

SPECIFICATIONDATASHEET

FHP MANUFACTURING ENERGY WISE HVAC EQUIPMENT

ELECTRICAL SPECIFICATIONS
Electrical
Characteristics

Elect.
Symbol

208/230-3-60
460-3-60
575-3-60

-3
-4
-5

Compressor (Ea)
RLA
48.1
23.8
21.8

LRA
425
187
148

WP420
WP SERIES

FLUID FLOW & PRESSURE DROP


Min.
Circuit
Ampacity
108.2
53.3
49.1

Max.
Fuse
Size
150
70
70

Chilled Fluid Side (@ 55OF)


Flow (GPM)
P (FOH)
54
11.1
60
13.4
72
18.6
84
24.6
96
31.2

Cond. Fluid Side (@ 85OF)


Flow (GPM)
P (FOH)
54
10.4
60
12.6
72
17.5
84
23.1
96
29.4

UNIT WEIGHT
Unit Weight (lbs)
Shipping Weight (lbs)

1550
1570

CHILLER PERFORMANCE

HEATING PERFORMANCE

Based on 84 GPM chilled fluid & 10OF condenser fluid temp. rise.

Based on 10OF load temp. rise & 84 GPM source fluid flow.

Leaving Entering Total


Chilled Cond. Capacity
Fluid (F) Fluid (F) (Tons)
75O
24.96
80O
24.42
40O
85O
23.84
90O
23.24
95O
22.60
75O
25.92
80O
25.36
42O
85O
24.76
90O
24.13
95O
23.48
75O
26.91
80O
26.32
44O
85O
25.70
90O
25.05
95O
24.38
75O
27.41
80O
26.81
45O
85O
26.18
90O
25.53
95O
24.84
75O
27.92
80O
27.31
46O
85O
26.67
90O
26.00
95O
25.31
75O
28.97
80O
28.34
48O
85O
27.67
90O
26.98
95O
26.26
75O
30.05
80O
29.39
50O
85O
28.69
90O
27.98
95O
27.24

Leaving Entering
Load Source
Fluid (F) Fluid (F)
35O
40O
O
100
50O
60O
70O
35O
40O
O
110
50O
60O
70O
35O
40O
O
120
50O
60O
70O
35O
40O
O
125
50O
60O
70O
35O
40O
O
130
50O
60O
70O

Total
Power
Capacity
Input
(BtuH)
(Watts)
299,511 22,433
293,008 23,725
286,110 25,080
278,828 26,502
271,192 27,993
311,038 22,454
304,267 23,748
297,111 25,107
289,592 26,533
281,732 28,030
322,898 22,473
315,858 23,766
308,434 25,127
300,658 26,559
292,552 28,063
328,954 22,483
321,765 23,776
314,217 25,136
306,314 26,569
298,074 28,078
335,095 22,492
327,763 23,785
320,069 25,146
312,035 26,580
303,682 28,089
347,648 22,511
340,023 23,800
332,037 25,163
323,723 26,600
315,100 28,114
360,568 22,530
352,627 23,816
344,339 25,178
335,742 26,616
326,849 28,133

EER
13.4
12.3
11.4
10.5
9.7
13.9
12.8
11.8
10.9
10.1
14.4
13.3
12.3
11.3
10.4
14.6
13.5
12.5
11.5
10.6
14.9
13.8
12.7
11.7
10.8
15.4
14.3
13.2
12.2
11.2
16.0
14.8
13.7
12.6
11.6

Heat
Rejection
(BtuH)
376,053
373,959
371,683
369,254
366,705
387,651
385,294
382,775
380,123
377,371
399,576
396,946
394,168
391,277
388,304
405,665
402,889
399,981
396,966
393,875
411,840
408,917
405,869
402,727
399,521
424,456
421,229
417,892
414,481
411,025
437,438
433,888
430,247
426,555
422,838

Heating
Capacity
(BtuH)
316,794
338,625
385,537
437,388
494,860
314,542
335,924
381,607
431,811
487,235
311,785
332,856
377,588
426,412
480,053
310,292
331,259
375,621
423,859
476,704
308,767
329,667
373,727
421,443
473,561

Power
Input
Watts
26,266
26,388
26,546
26,627
26,677
29,219
29,392
29,630
29,755
29,813
32,434
32,679
33,032
33,236
33,337
34,151
34,440
34,862
35,118
35,254
35,943
36,278
36,778
37,098
37,277

COP
3.5
3.8
4.3
4.8
5.4
3.2
3.3
3.8
4.3
4.8
2.8
3.0
3.4
3.8
4.2
2.7
2.8
3.2
3.5
4.0
2.5
2.7
3.0
3.3
3.7

Heat of
Absorb.
(BtuH)
227,173
248,590
294,964
346,536
403,837
214,847
235,640
280,510
330,288
385,512
201,118
221,355
264,881
313,010
366,306
193,770
213,752
256,673
304,038
356,417
186,129
205,885
248,240
294,865
346,372

Units are complete packages featuring 2 stage operation and


containing refrigeration compressors, reversing valves, expansion valve
metering devices and water to refrigerant heat exchangers. Also
included are safety controls: Overload protection for compressors, high
and low refrigerant pressure switches and a lock-out control circuit.

FHP MANUFACTURING
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com

As a result of continuing research and development, specifications are subject to change without notice.

WP420IP6.P65

Rev:4-01

You might also like