Professional Documents
Culture Documents
I. INTRODUCTION
However, with a better understanding of the nature and characteristics of HIF and the advancements in simulation software,
the trend has shifted more towards simulation studies. The HIF
models used for simulation studies are discussed in Section II.
Researchers, from both academia and utilities, have proposed
different methods comprising of single or multiple algorithms
to detect HIFs in a distribution system. Majority of the studies
in this area were reported in 1980s and 1990s, but the simulation and detection methods are still being developed and
refined. An extensive literature survey of HIF can be found in
[3]. The HIF detection methods can be broadly classified into
frequency domain algorithms, time domain algorithms, hybrid
algorithms, and expert systems. Statistical techniques using
sequence components and their harmonics [4], third harmonics
[5], second-fourth-sixth harmonics [6], and high frequency
components (210 kHZ) [7] are some of the methods based
on the frequency domain. Other frequency domain algorithms
include the use of burst noise signal [8], improvements over the
use of third harmonic based algorithms [9], [10] and a combination of current magnitude with the magnitude and phase of its
harmonics [11]. Time domain algorithms include proportional
relaying [12], ratio ground relay [13], randomness algorithm
[14], use of current flicker [15], fractal techniques [16], and
signal superposition [17]. Frequency and time domain hybrid
methods such as discrete wavelet transform [18][24] have
also been proposed by researchers. Because of the randomness of HIFs, expert methods using combinations of multiple
algorithms [25][28], multiple tools [29][31], Kalman filter
[32], [33] as well as training based methods such as decision
tree [34], artificial neural networks [35][38], and neuro-fuzzy
method [39] based on genetic algorithm [40] are proposed.
Another expert method [41] uses neural networks with features
extracted using mathematical morphology for the detection of
HIF.
These prior studies and proposed algorithms have helped reveal many hidden properties of the HIF, but they are not capable of detecting all HIFs. These studies also do not report
the detection delay except for [16] and [27], where the detection delays are reported as 4 s and approximately 1 min, respectively. This paper proposes a superior method that tracks the
shape of the voltage waveforms to detect an HIF with excellent
reliability and speed, using a tool based on mathematical morphology (MM). No training or learning is required.
MM is a nonlinear time domain signal processing tool that
transforms the shape of signals [42], [43]. The transformation
is based on set theory and integral geometry, and was originally
GAUTAM AND BRAHMA: DETECTION OF HIGH IMPEDANCE FAULT IN POWER DISTRIBUTION SYSTEMS
developed by Matheron [44] and Serra [45]. Dilation and Erosion are two elementary transformations in MM. All other transformations are derived from these two. The transformation is
carried out by a signal processing function called Structuring
Element. The structuring element is defined based on the type
of application and plays a pivotal role in MM operations. The
real-time applications and the performance of the MM operators
have been reported by Gautam and Brahma [46][48]. References [46] and [47] discuss the effect of the structuring element
on the real-time performance of MM. They also demonstrate the
capabilities of MM operators in detecting and extracting transients from voltage and current waveforms that result from different power system disturbances.
Drawing from the observations made in [46][48], this paper
describes how MM operators can be applied to efficiently
detect HIFs, and to distinguish them from other distribution
system events that tend to produce disturbances in current
and voltage waveforms. The proposed method is tested on the
IEEE 13-node and IEEE 34-node test feeders simulated using
PSCAD/EMTDC. Matlab is used to implement the method.
The paper is divided into six sections. Section I presents literature review and an overview of this paper. Section II describes
the selection of test systems, formation of the HIF model, and
selection of waveforms for HIF detection. Section III briefly illustrates the proposed MM operations to detect and distinguish
an HIF, and documents some results that help capture the distinguishing signature of HIFs. Based on these characteristics,
Section IV illustrates the formulation and implementation of a
detection and classification methodology. Section V describes
the simulation results using this methodology. Finally, conclusions are drawn in Section VI.
1227
II. MODELING
A. Choice and Modeling of Test System
This paper uses standard test systems to demonstrate the
performance of the proposed detection method. IEEE PSRC
Working Group D15 [1] suggests that HIF studies be performed
at voltage levels of 15 kV and below. Therefore, the IEEE
13-node 4.16-kV test feeder [49] shown in Fig. 1 was selected
and modeled using PSCAD/EMTDC. The substation bus was
modeled by an equivalent Thevenin source with an equivalent
impedance of
pu. Distribution lines were modeled
using a coupled-wire model with lumped parameters. Voltage
regulator was modeled by three 1-phase 2-winding transformers
with on-load tap changer. To further verify the robustness of
the proposed concept, the paper also reports the performance of
the method using another standard test systemIEEE 34-node
test feeder [49] shown in Fig. 2. The two systems selected for
testing the proposed detection method have diverse properties.
The 13-node feeder is short and heavily loaded, whereas the
34-node feeder is long and lightly loaded. Although the latter
is a 24.9-kV system, which is rated at higher voltage than that
suggested by the PSRC Working Group, it was chosen for the
current study to test the proposed method on systems with
different sizes and properties.
B. Model of HIF
The HIF detection methods can be broadly classified into two
groups based on the data used for developing the method; one
that uses data obtained from staged faults, and the other that
uses data generated by simulations. Detection methods developed using results from staged faults tend to be more system
(network) specific, and may not be applicable to other systems
(networks). Moreover, staged faults require special gears and
manpower, and naturally involve a risk of service disconnection.
The methods developed using simulation results on the other
hand can be tested extensively, and hence are more adaptable to
various systems (networks) with none or few modifications. A
wide variety of events/situations can be studied by simulation
based methods. Hence, the simulation based method is chosen
for the study reported in this paper. However, the waveforms
resulting from simulation are shown to resemble well with the
waveforms from staged HIFs reported in literature, thus illustrating the validity of the simulation model.
HIFs are almost always accompanied by arcing, which makes
the fault current unpredictable and random. Depending upon the
type of surface involved in the fault path, the fault resistance
may change due to the heat produced by the arc, changing the
magnitude of the fault current randomly. Thus, HIF is a random
phenomenon, and results in a wide variation in the shape of
1228
GAUTAM AND BRAHMA: DETECTION OF HIGH IMPEDANCE FAULT IN POWER DISTRIBUTION SYSTEMS
1229
(1)
Similarly, (2) defines the erosion of a signal
Fig. 5. V-I characteristics during HIF.
by
(2)
In these equations,
is the signal to be transformed, defined in domain
, and
is the structuring element, defined in domain
, and
and are integers such that
.
Based on these two elementary transformations, opening and
closing are defined by (3) and (4):
(3)
(4)
examine this, Fig. 6(b) shows the current drawn from the substation during the same HIF. As suspected, this current hardly
shows any traces of the irregularities of the actual HIF current.
The strength of MM based tools lies in the fact that they can
detect and distinguish between very small (seemingly insignificant) changes to a wave-shape. Fig. 4(a) shows the voltage
waveform across the HIF. A zoomed view shows there is a slight
distortion in the waveform. This slight distortion is obviously
also reflected at the substation, as seen in Fig. 6(a). It is possible
that the current waveform at the substation would also contains
a slight disturbance, but the extent of such distortion may vary
for different pre-fault conditions. In contrast, the distortion in
the voltage waveform does not depend on the pre-fault currents,
and is more likely to provide a more consistent signature when
processed by MM. Due to the unique property of MM based
tools to detect very small distortions, and the better likelihood
of the voltage waveforms providing a more consistent signature
when processed by such tools, the voltage waveform is chosen
for processing. The results documented in Sections III and IV
further confirm the validity of this choice.
1230
Fig. 7. Phase A voltage waveform and the CODO output for High Impedance
Fault.
Fig. 8. Phase A voltage waveform and the CODO output for Capacitor
Switching.
Fig. 9. Phase A voltage waveform and the CODO output for Load Switching.
GAUTAM AND BRAHMA: DETECTION OF HIGH IMPEDANCE FAULT IN POWER DISTRIBUTION SYSTEMS
1231
AND
This section describes a method to detect an HIF, and distinguish it from other disturbances discussed in Section III. The
first step in this process is the detection of disturbance. Based
on the analysis of the CODO output for the three different disturbances in Section III, a disturbance is detected if a spike is
present in the output of the CODO operation. A threshold value
is set and the CODO output is tracked for each phase-voltage
to detect the disturbance. For the application proposed in this
paper, the threshold value was set at 115% of the maximum
value of the CODO output during the healthy condition. As
mentioned in Section III, the CODO output is close to zero
during healthy condition; the 15% margin is simply a buffer.
This threshold value translates to approximately 0.0053 pu for
the examples shown in Figs. 79.
The next step is to distinguish an HIF from other disturbances. As mentioned in Section III, the comparison of the
CODO output for different disturbances in Figs. 79 shows that
an HIF generates a series of non-uniformly distributed spikes
over an extended time-period, whereas a capacitor switching
and a load switching generate either a single spike or multiple
consecutive spikes over a short time period never longer than
one eighth of a cycle. The difference in the signatures is so
clear, there is no need for any learning based pattern recognition method. A rule-based method is therefore adopted. This
method, and an algorithm to implement it are described now.
In addition to the threshold value defined previously in this
section to detect a disturbance, the algorithm requires two other
parameterswait-time
and reset-time
for the classification of HIF. Wait-time
is implemented to avoid the
initial multiple consecutive spikes that are sometimes generated
by capacitor switching. To make sure such spikes are no longer
present in the CODO output, a conservative choice of a quarter
cycle is made for the wait-time. For the chosen sampling rate of
64 sample per cycle, the wait-time translates to 16 samples, and
equals to 4.17 ms in a 60-Hz system.
Once the wait time is over, the method prepares to detect another spike in the CODO output. If such a spike is detected, it
is certainly due to an HIF. The detection time for this second
spike, or the detection delay, depends upon the amount of transients present in the voltage waveform. A slower change in the
effective impedance of HIF implies less transients in voltage
waveform and thus, a larger separation of spikes, and a larger
detection delay. Similarly, a faster change implies more transients and thus, a smaller separation of spikes, and a smaller
detection delay. Therefore, it is necessary to wait for some time
to allow even the most sparsely separated spike to be detected.
This time is defined as the reset time
. If no spike is encountered during the reset time, the algorithm determines the
detected disturbance was not an HIF, and resets itself. However,
Fig. 10. Flowchart for the proposed detection and classification method.
if a spike is detected between the end of the wait time and end of
the reset time, the HIF flag is made high. At the end of the reset
time, if the HIF flag is high, a trip or alarm signal is generated,
otherwise the algorithm resets and starts afresh. Based on the
simulation studies, a conservative choice of 1 s is made for the
value of the reset time . This means any HIF will be detected
and classified within 1 s.
The algorithm that captures this logic is shown in Fig. 10.
As can be seen from this flowchart, at the very beginning of
the process, a pickup signal from an overcurrent relay is included. If the relay picks up, it means there is a conventional
fault, and the whole algorithm is simply suspended by resetting
all flags and timers. Thus, the proposed detection and classification method is integrated with a digital overcurrent relay, and
simply suspends operation for all faults detected by the overcurrent relay. The rest of the algorithm is self-explanatory, as it
basically implements the detection and classification logic described in the previous paragraphs. The threshold value Th is
taken as described previously in this section. DF stands for Disturbance Flag.
V. SIMULATION RESULTS
A total of 15 HIF cases were simulated at different locations, on different phases and at different time-instants in the
IEEE 13-node test feeder. The HIF locations were chosen at
nodes as well as at intermediate points. Intermediate points were
chosen in the branches with distributed loads. The locations
were chosen to include 1-phase, 2-phase, and 3-phase branches;
and both unbroken (denoted as type-1) and broken (denoted
1232
TABLE I
SIMULATION RESULT FOR IEEE 13-NODE TEST FEEDER
TABLE II
SIMULATION RESULT FOR IEEE 34-NODE TEST FEEDER
of HIFs. The detection delay in this case varies from less than
10 ms for the fastest detection to 66 ms for the slowest one. As
mentioned in Section II-A, the 34-node feeder is lightly loaded.
This means the method is not affected by loading conditions.
To test the reliability and robustness of the method even further,
a study was performed with both test systems operating at half
load. The performance of the method was similar to that observed with full load. This underscores the rationale described
in Section II-C in choosing the voltage waveform for this study,
making the method robust against pre-fault (load) conditions.
These results show that the algorithm is robust, since it successfully works on two standard distribution systems with very different properties, simulated with varying load conditions. The
100% success rate of detection and classification for both systems indicates the proposed method exhibits excellent reliability
and security.
VI. CONCLUSION
This paper summarizes the use of MM to detect high
impedance faults which are otherwise undetected by the overcurrent protection scheme in a power distribution system. An
MM based tool is proposed, implemented and tested to develop
a method that can be integrated as a separate module with a
digital overcurrent relay. The detection method uses voltage
waveforms sampled at the substation. The proposed method is
designed to operate in parallel and assist the existing protection
scheme to detect an HIF. This method is fast, with a detection
delay of 1 s. The method is shown to exhibit reliability, as all
the HIF cases simulated were detected, even for fault currents
GAUTAM AND BRAHMA: DETECTION OF HIGH IMPEDANCE FAULT IN POWER DISTRIBUTION SYSTEMS
1233
1234