You are on page 1of 5

LPE

Insulated
Armored &
Unarmored
Cables:

1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)
UN-ARMOURED CABLE

Crosssectional
area
(Sq MM)
1cX4
1cX 6
1cX10
1cX16
1cX25
1cX 35
1cX50
1cX70
1cX 95
1cX120
1cX150
1cX185
1cX240
1cX300
1cX400
1cX 500
1cX 630
1cX800
1cX1000

Overall
Diameter
(mm)
8
9
10
11
12
13
15
16
18
20
22
24
27
30
33
36
40
47
51

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air

48
47
45
48
45
45
60
59
57
62
62
61
80
78
77
81
80
83
104
102
106
99
90
115
130
115
145
117
110
135
155
140
175
138
125
170
185
165
215
168
155
210
225
200
270
204
185
255
265
235
330
230
210
300
300
265
380
265
230
342
335
300
430
295
260
385
380
335
495
340
300
450
435
385
590
390
335
519
490
430
670
450
380
605
550
480
780
500
430
700
610
530
900
555
485
809
680
590
1020
625
530
935
740
630
1140
690
570
1065
780
660
1250

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
0.376
0.564
0.940
1.504
2.350
3.290
4.700
6.580
8.930
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

Copper
0.572
0.858
1.430
2.288
3.575
5.005
7.150
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00

1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)
ARMOURED CABLE

Crosssectional
area
(Sq MM)
1cX4
1cX 6
1cX10
1cX16
1cX25
1cX 35
1cX50
1cX70
1cX 95
1cX120
1cX150
1cX185
1cX240
1cX300
1cX400
1cX 500
1cX 630

Overall
Diameter
(mm)
10
11
12
13
14
15
17
19
22
24
25
28
30
33
38
41
46

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air

48
47
45
45
45
40
60
59
57
59
62
53
80
78
77
76
80
73
104
102
106
99
90
115
130
115
145
117
110
140
155
140
175
138
125
170
185
165
215
168
155
210
225
200
270
204
185
255
265
235
330
230
210
300
300
265
380
265
230
342
335
300
430
295
260
385
380
335
495
340
300
450
435
385
590
390
335
519
490
430
670
450
380
605
550
480
780
500
430
700
610
530
900
555
485
809
680
590
1020

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
0.376
0.56
0.94
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

Copper
0.572
0.858
1.43
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1cX800
1cX1000

51
56

625
690

530
570

935
1065

740
780

630
660

1140
1250

75.20
94.00

114.40
143.00

1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)


UN-ARMOURED CABLE

Crosssectional
area
(Sq MM)
2cX4
2cX 6
2cX10
2cX16
2cX25
2cX35
2cX50
2cX70
2cX95
2cX120
2cX150
2cX185
2cX240
2cX300
2cX400
2cX500
2cX630

Overall
Diameter
(mm)
13
14
17
17
19
20
22
25
28
31
33
37
41
44
48
54
62

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air
34
28
30
44
37
39
43
37
40
55
47
50
57
48
53
74
61
67
78
61
70
94
78
85
95
80
99
120
100
125
116
94
117
145
120
155
140
110
140
170
145
190
170
140
176
210
175
235
200
165
221
250
210
290
225
185
258
285
240
330
255
210
294
315
270
375
285
235
339
355
300
435
325
270
402
410
350
510
370
305
461
460
390
590
435
350
542
520
440
670
481
405
624
580
480
750
537
470
723
680
575
875

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

Copper
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)


ARMOURED CABLE

Crosssectional
area
(Sq MM)
2cX4
2cX 6
2cX10
2cX16
2cX25
2cX35
2cX50
2cX70
2cX95
2cX120
2cX150
2cX185
2cX240
2cX300
2cX400
2cX500
2cX630

Overall
Diameter
(mm)
15
16
18
19
21
23
25
28
31
34
37
40
45
49
52
60
66

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air
34
28
30
44
37
39
43
37
40
55
47
50
57
48
53
74
61
67
78
61
70
94
78
85
95
80
99
120
100
125
116
94
117
145
120
155
140
110
140
170
145
190
170
140
176
210
175
235
200
165
221
250
210
290
225
185
258
285
240
330
255
210
294
315
270
375
285
235
339
355
300
435
325
270
402
410
350
510
370
305
461
460
390
590
0.33
435
350
542
520
440
0.34
481
405
624
580
480
0.36
537
470
723
680
575

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
670
750
875

1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)


UN-ARMOURED CABLE

Crosssectional
area
(Sq MM)

Copper
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.1
13.59
17.16
21.45
26.46
34.32
42.90
37.60
47.00
59.22

Crosssectional
area
(Sq MM)
3cX 4
3cX 6
3cX 10
3cX 16
3cX 25
3cX 35
3cX 50
3cX 70
3cX 95
3cX 120
3cX 150
3cX 185
3cX 240
3cX 300
3cX 400
3cX 500
3cX 630

Overall
Diameter
(mm)
14
16
18
18
21
22
25
30
32
35
39
43
49
53
59
66
73

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air
34
28
30
44
37
39
43
37
40
55
47
50
57
48
53
74
61
67
78
61
70
94
78
85
95
80
99
120
100
125
116
94
117
145
120
155
140
110
140
170
145
190
170
140
176
210
175
235
200
165
221
250
210
290
225
185
258
285
240
330
255
210
294
315
270
375
285
235
339
355
300
435
325
270
402
410
350
510
370
305
461
460
390
590
435
350
542
520
440
670
481
405
624
580
480
750
537
470
723
680
575
875

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

Copper
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Three CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I)
ARMOURED CABLE

Crosssectional
area
(Sq MM)
3cX 4
3cX 6
3cX 10
3cX 16
3cX 25
3cX 35
3cX 50
3cX 70
3cX 95
3cX 120
3cX 150
3cX 185
3cX 240
3cX 300
3cX 400
3cX 500
3cX 630

Overall
Diameter
(mm)
18
19
20
20
23
25
29
32
35
39
43
48
53
58
65
72
81

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air
34
28
30
44
37
39
43
37
40
55
47
50
57
48
53
74
61
67
78
61
70
94
78
85
95
80
99
120
100
125
116
94
117
145
120
155
140
110
140
170
145
190
170
140
176
210
175
235
200
165
221
250
210
290
225
185
258
285
240
330
255
210
294
315
270
375
285
235
339
355
300
435
325
270
402
410
350
510
370
305
460
460
390
590
435
350
542
520
440
670
481
405
624
580
480
750
537
470
723
680
575
875

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

Copper
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)


UN-ARMOURED CABLE

Crosssectional
area (Sq
MM)
3.5X25
3.5X35

Overall
Diameter
(mm)
22
24

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air
95
80
99
120
100
125
116
94
117
145
120
155

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
2.35
3.29

Copper
3.58
5.01

3.5X50
3.5X70
3.5X95
3.5X120
3.5X150
3.5X185
3.5X240
3.5X300
3.5X400
3.5X500
3.5X630

27
31
34
38
43
46
52
57
65
73
82

140
170
200
225
255
285
325
370
435
481
537

110
140
165
185
210
235
270
305
350
405
470

140
176
221
258
294
339
402
461
542
624
723

170
210
250
285
315
355
410
460
520
580
680

145
175
210
240
270
300
350
390
440
480
575

190
235
290
330
375
435
510
590
670
750
875

4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Three & Half CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)
ARMOURED CABLE

Crosssectional
area (Sq
MM)
3.5X25
3.5X35
3.5X50
3.5X70
3.5X95
3.5X120
3.5X150
3.5X185
3.5X240
3.5X300
3.5X400
3.5X500
3.5X630

Overall
Diameter
(mm)
25
27
30
35
38
42
46
51
56
60
71
79
88

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air
95
80
99
120
100
125
116
94
117
145
120
155
140
110
140
170
145
190
170
140
176
210
175
235
200
165
221
250
210
290
225
185
258
285
240
330
255
210
294
315
270
375
285
235
339
355
300
435
325
270
402
410
350
510
370
305
461
460
390
590
435
350
542
520
440
670
481
405
624
580
480
750
537
470
723
680
575
875

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

Copper
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)
UN-ARMOURED CABLE

Crosssectional
area (Sq
MM)
4cX4
4cX 6
4cX 10
4cX16
4cX 25
4cX35
4cX 50
4cX70
4cX 95
4cX 120
4cX 150
4cX 185
4cX 240
4cX 300
4cX 400
4cX 500
4cX 630

Overall
Diameter
(mm)
17
18
20
20
24
26
29
34
37
41
45
50
56
63
70
79
88

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air
34
28
30
44
37
39
43
37
40
55
47
50
57
48
53
74
61
67
78
61
70
94
78
85
95
80
99
120
100
125
116
94
117
145
120
155
140
110
140
170
145
190
170
140
176
210
175
235
200
165
221
250
210
290
225
185
258
285
240
330
255
210
294
315
270
375
285
235
339
355
300
435
325
270
402
410
350
510
370
305
461
460
390
590
435
350
542
520
440
670
481
405
624
580
480
750
537
470
723
680
575
875

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

Copper
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)
ARMOURED CABLE

Crosssectional
area (Sq
MM)
4cX4
4cX 6
4cX 10
4cX16
4cX 25
4cX35
4cX 50
4cX70
4cX 95
4cX 120
4cX 150
4cX 185
4cX 240
4cX 300
4cX 400
4cX 500
4cX 630

Overall
Diameter
(mm)
18
19
21
22
26
28
32
37
40
44
49
54
65
68
76
86
94

Normal Current Rating in Amps


Aluminums Conductor
Copper Conductor
Ground
Duct
Air
Ground
Duct
Air
34
28
30
44
37
39
43
37
40
55
47
50
57
48
53
74
61
67
78
61
70
94
78
85
95
80
99
120
100
125
116
94
117
145
120
155
140
110
140
170
145
190
170
140
176
210
175
235
200
165
221
250
210
290
225
185
258
285
240
330
255
210
294
315
270
375
285
235
339
355
300
435
325
270
402
410
350
510
370
305
460
460
390
590
435
350
542
520
440
670
481
405
624
580
480
750
537
470
723
680
575
875

Short Circuit Current


Rating for 1Sec.duration
in K. Amps
Aluminums
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

Copper
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

You might also like