Ing. Jos de la Luz vila Contreras, Calle Paraguay N 1103-1, Col.

5
de Diciembre
Tel. 322 10 89 117, Puerto Vallarta, Jal. C.P. 48350,
E-mail: javilaco@outlook.com
Puerto Vallarta, Jalisco. Aug. 26, 2013

Visual inspection report of the Condo 502, located at Condominios Punta


Esmeralda, in Cerrada Madreperlas 102, Conchas Chinas, Puerto
Vallarta, Jalisco.

Attending to Mrs. Marilyn Newman request, from Prudential Realty, a


visual inspection of the conditions of habitability and operation of the existing
facilities in the indicated property was performed.
Scopes
The inspection provides review and current operation of installations:
electrical, hydraulics, sanitary, paint, drainage, appliances. Through inspection
it identifies potential failures and defects in the refereed items, also provides
solution recommendations.
The inspection is not a structural revision nor is unrelated to the
specifications and control quality during construction, as well as any hidden
defects arising from this. By the nature of the inspection, no plans or
documentation of the project were reviewed.
Review and features
The building of the Condo 502 displays good general state and the facilities
are in good conditions of operability. The safety requirements are met in
access, stairs also elevator.
The condominium distribution consists of: Two bedrooms, the main with
Jacuzzi, two bathrooms, equipped kitchen, Living Dining room, Balcony and
Laundry room.

The operation of the facilities also appliances was proved; hydraulic, sanitary,
electricity, air conditioning, as their operability and physical conditions as well,
being stated that the facilities are in conditions of operability; nevertheless
some smaller defects are observed, which are below described. These can be
corrected with maintenance.
Next, a description of the zones reviewed by areas, identifying the following
minor defects:
1. Kitchen
1.1.The wall behind the sink is damaged; there are some holes that
require finishing and painting.
1.2.The structure of the kitchen cabinets are plywood, while only the doors
are hardwood, for this reason there are some plywood parts damaged
by moisture.
1.3.Some old patches of humidity can be observed in the ceiling. It
requires new painting.
2. Laundry room
2.1.Some old patches of humidity can be observed in the ceiling. It
requires new painting.
2.2.There is an electric outlet uncovered.
3. 1st Bedroom
3.1.In the edges of walls beside the windows, there are some old moisture
stains where bad repairing in windows could be the cause.
3.2.The same defect is observed in the ceiling of bathroom one and wall,
where the same cause was explained for maintenance personnel. It
requires new painting too.
3.3.The air conditioning mini split does not work properly. It is old and
inefficient. It is recommended changing it.
3.4.The Jacuzzis window is dirty; there is rust that requires deep cleaning.
3.5.The outside window tiles are broken. It requires replacing.
3.6.The window iron rail painting is deteriorated. It requires cleaning and
new painting.

3.7.Wall tapestry is damaged by moisture beside the windows. It is


recommended replacing it.
4. 2nd bedroom
4.1.The outside window tiles are broken. It requires replacing.
5. Balcony
5.1.The window iron rail painting is deteriorated. It requires cleaning and
new painting.
6. Living room
6.1.The air conditioning mini split does not work properly. It is old and
inefficient. It is recommended changing it.
7. Recommendations
7.1.It is recommended to repairing or replacing the plywood cabinets
by hardwood cabinets in kitchen.
7.2.Repairing and painting walls behind the sink in kitchen.
7.3.Maintenance to the air conditioning condensers, also replacing
the minisplits.
7.4.Painting the ceiling in general.
7.5.Replacing the wall tapestry in damaged areas or by painting.
7.6.Replacing the broken window exterior tiles
7.7.Cleaning the rust in the window beside the Jacuzzi also sealed
with polyurethane.
.

Looking forward to meeting your expectations, I am to your disposition


should you need further information.

Attentively

Ing. Jos de la Luz Avila Contreras


Professional Certificate 3562980

PHOTOGRAFIC ANNEX

Safety instructions beside the elevator 20-05Main entrance to Caracoles Condos

Safe conditions are met in access

20-05-

20-05Evacuation
signaling
in the
corridor
Safe conditions
are met
in elevator

20-0520-05-

Water faucets in
damaged
20-05-2013 - 10

bathrooms

in

general

are

In the ceiling of the master bathroom, there are


some
old
moisture
stains
20-05-2013 - 07
The metallic pieces on the top of the waste
disposer are oxidized. Must be cleaned and over
coating to protect them from corrosion, or

The fan loose caused the crack around the basis in


the
ceiling
terrace

In the master bathroom, old patches of moisture


on the wall from the floor above during pipes
repairing
20-05-2013 -

Detachment of the coating in the terrace ceiling

The same problem of moisture stains is in


bedroom 2, repairs in potable water fittings in
the above floor could be the cause
20-05-2013 - 12

may be a faulty repair


20-05-2013 - 08

Above: the mini split condenser; bottom: the


central system of air conditioning condenser; both
need maintenance

20-05-

Pass valves below the washbasin 2 for water are


used
20-05-2013

Moisture stains are observed


bathroom ceiling 20-05-2013 - 13

in

master

Lamp without basis in master bedroom


2013 - 23

Hole in the bedroom 3 ceiling


2013 - 24

23-03-

20-05-

Master bedroom has mini split and central


system
air
conditioned
as
well

The sliding doors and windows are jammed, also


clouded the living right door. It is necessary to
change the slices and maintenance.

The central air conditioning system does not


work properly in bedrooms 2 and 3

Ceiling fans are old, noisy and inefficient


2013 19, 20

20-05-

A floor drain covered with adhesive tape, was


found in the laundry room, which may indicate
problems of bad smells or intrusion of insects. It
must be inspected by a plumber to identify the

The exhaust fan in bathroom one does not work


20-05-2013 - 26

The refrigerator lamps are fused


2013 - 25

23-03-