Professional Documents
Culture Documents
The total
number of 380 KV transmission lines is 161 line. A set of contingencies related to
these lines was built, this set of contingencies have 302 contingencies. After running
this contingency set on the Turkish Power System, the following contingencies were
insecure:
67
68
133
161
162
163
164
165
166
167
168
170
171
172
173
174
175
177
179
185
187
188
189
191
193
194
195
196
197
198
213
273
286
288
291
292
301
-4.85*
-9.98*
-81.02*
-77.94*
-77.94*
-77.94*
-77.94*
-77.94*
-77.94*
-77.19*
-77.94*
-71.25*
-79.01*
-71.24*
-77.19*
-78.65*
-77.94*
-77.94*
-77.94*
-78.71*
-78.03*
-79.71*
-78.03*
-79.49*
-79.51*
-79.49*
-78.03*
-79.49*
-79.71*
-79.49*
-78.03*
-78.03*
-77.94*
-77.94*
-64.81*
-81.02*
-77.94*
59.46
57.37
25.86
59.98
59.99
59.98
59.98
59.99
59.98
59.97
59.98
52.72
53.73
52.53
59.97
51.93
59.98
59.98
59.98
52.87
59.82
59.84
59.82
59.83
59.84
59.83
59.82
59.83
59.84
59.83
59.82
59.82
53.79
53.79
53.04
25.86
53.79
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
Insecure
4ZETES 380.
4OSMANCA 380.
4KONYA_KAPI 380.
4SEYDISEHIR 380.
4OYMAPINAR 380.
4SEYDISEHIR 380.
4VARSAK 380.
4OYMAPINAR 380.
4VARSAK 380.
4AKSA380 380.
4VARSAK 380.
4DEN_AFY_RE 380.
4DENIZLI 380.
4DEN_AFY_RE 380.
4AKSA380 380.
4DENIZLI 380.
4SEYDISEHIR 380.
4SEYDISEHIR 380.
4SEYDISEHIR 380.
4DENIZLI 380.
4KAYABASI 380.
4ALTINKAYA 380.
4KAYABASI 380.
4CARSAMBA 380.
4HUGURLU 380.
4CARSAMBA 380.
4KAYABASI 380.
4CARSAMBA 380.
4ALTINKAYA 380.
4CARSAMBA 380.
4KAYABASI 380.
4KAYABASI 380.
4URGUP_SKM 380.
4URGUP_SKM 380.
4KONYA_4 380.
4KONYA_KAPI 380.
4URGUP_SKM 380.
232610 231110
231110 232610
420511 422010
510010 510210
510210 510010
510010 510110
510110 510010
510210 510110
510110 510210
514310 510110
510110 514310
520111 520010
520110 520111
520111 520110
514310 520110
520110 514310
510010 420910
510010 420510
510010 520010
520110 330310
612710 610410
610410 612710
612710 612310
620610 620210
620910 620610
620610 620910
612710 620610
620610 612710
610410 620610
620610 610410
612710 810510
612710 410510
410311 810710
410311 810610
420510 420511
420511 420510
410311 410312
tripping the line they will be isolated from the network, causing the instability. These
two generators are the second biggest generators in the Turkish Grid.
Generator angle (degrees)
840
830
666
660
492
490
318
320
144
150
-30
-20
0.000
0.166
0.332
0.497
0.663
0.829
0.000
0.166
0.332
0.497
0.663
0.829
Time (sec)
Time (sec)
51
32000
38
25400
25
18800
13
12200
-0
5600
-13
0.00
0.02
0.04
0.06
0.08
0.10
-1000
0.000
0.528
Time (sec)
1.057
1.585
2.113
2.642
Time (sec)
Figure 2: System Response for Contingencies 133, and 292 for different TSAT setting
shown in Figure 3, right side. From Figure 3, it can be seen that this fault is causing
the three generators connected to bus (510210 4OYMAPINAR 380) to run out of
synchronism, these generators are:
51068GEN_4OYMAPINAR
51069GEN_4OYMAPINAR
51070GEN_4OYMAPINAR
Generator angle (degrees)
51
3900
38
3100
25
2300
13
1500
-0
700
-13
0.000
0.021
0.042
0.064
0.085
Time (sec)
0.106
-100
0.000
0.087
0.173
0.260
0.347
0.433
Time (sec)
Figure 3: System Response for Contingencies 161, 162, 163, 164, 165, and 166
51
80
38
56
25
32
13
-0
-16
-13
0.00
0.02
0.04
0.06
0.08
0.10
-40
0.00
1.00
2.00
Time (sec)
3.00
4.00
5.00
Time (sec)
Figure 4: System Response for Contingencies 167 for different TSAT setting
Generator angle (degrees)
51
12000
38
9400
25
6800
13
4200
-0
1600
-13
0.00
0.02
0.04
0.06
0.08
0.10
Time (sec)
-1000
0.000
0.207
0.415
0.622
0.830
1.037
Time (sec)
Figure 5: System Response for Contingencies 168 for different TSAT setting
73
80
56
58
38
36
21
14
-8
-14
0.000
0.037
0.073
0.110
0.147
0.183
-30
0.00
1.00
2.00
Time (sec)
3.00
4.00
5.00
Time (sec)
Figure 6: System Response for Contingencies 170, 171, and 172 for different TSAT setting,
left insecure, right secure
51
110
38
84
25
58
13
32
-0
-13
0.00
0.02
0.04
0.06
Time (sec)
0.08
0.10
-20
0.000
0.041
0.082
0.122
0.163
0.204
Time (sec)
Figure 7: System Response for Contingencies 173, and 174 for TSAT Max Generator Speed
Deviation as 0.1 p.u
80
110
48
76
16
42
-16
-48
-26
-80
0.00
1.00
2.00
3.00
4.00
-60
5.00
0.00
1.00
2.00
Time (sec)
3.00
4.00
5.00
Time (sec)
Figure 8: System Response for Contingencies 173, and 174 for TSAT Max Generator Speed
Deviation as 1 p.u
50200
37400
24600
11800
-1000
0.00
1.00
2.00
3.00
4.00
5.00
Time (sec)
Figure 9: System Response for Contingencies 175 for TSAT Max Generator Speed Deviation
as 1 p.u
3660
2720
1780
840
-100
0.000
0.099
0.198
0.297
0.397
0.496
Time (sec)
Figure 10: System Response for Contingencies 177 for TSAT Max Generator Speed Deviation
as 1 p.u
Generator angle (degrees)
4600
3660
2720
1780
840
-100
0.000
0.099
0.198
0.297
0.397
0.496
Time (sec)
Figure 11: System Response for Contingencies 179 for TSAT Max Generator Speed Deviation
as 1 p.u
Contingency 185:
This fault is happening in a tie line connecting Area 52 and Area 33. For the normal
settings of TSAT related to Max Generator Speed Deviation settings as 0.1 p.u, the
system response was insecure, and terminated at early stage for both contingencies
as shown in Figure 12, left side. But if this setting was increased to 1 p.u, then the
system response was secure, as shown in Figure 12, right side!
110
110
84
76
58
42
32
-26
-20
0.000
0.041
0.082
0.122
0.163
0.204
-60
0.00
1.00
2.00
Time (sec)
3.00
4.00
5.00
Time (sec)
Figure 12: System Response for Contingencies 185 for different TSAT Max Generator Speed
Deviation setting
Contingencies 187, 188, 189, 191, 193, 194, 195, 196, 197, 198, 213,
and 273:
For all these contingencies the simulation terminated directly at the time when the
fault applied to the system, and TSAT indicated all these contingencies as insecure.
For investigating the system response after the fault applied, the simulation is
forced to be advanced by increasing the Max Generator Speed Deviation up to 1 p.u
instead of 0.1 p.u, the results are shown in Figures 13, 14, 15, 16, 17, and 18,
respectively. For all the mentioned contingencies, 4 generators were causing the
instability, these generators are:
62031GEN_4HUGURLU
62031GEN_4HUGURLU
62032GEN_4HUGURLU
62032GEN_4HUGURLU
Generator angle (degrees)
510
73000
404
58200
298
43400
192
28600
86
13800
-20
0.00
1.00
2.00
3.00
Time (sec)
4.00
5.00
-1000
0.00
1.00
2.00
3.00
4.00
5.00
Time (sec)
Figure 13: System Response for Contingencies 187, and 188 for TSAT Max Generator Speed
Deviation as 1 p.u
510
920
404
732
298
544
192
356
86
168
-20
0.00
1.00
2.00
3.00
4.00
5.00
-20
0.000
0.037
0.073
Time (sec)
0.110
0.147
0.183
Time (sec)
Figure 14: System Response for Contingencies 189, and 191 for TSAT Max Generator Speed
Deviation as 1 p.u
Generator angle (degrees)
920
920
732
732
544
544
356
356
168
168
-20
0.000
0.037
0.073
0.110
0.147
0.183
-20
0.000
0.037
0.073
Time (sec)
0.110
0.147
0.183
Time (sec)
Figure 15: System Response for Contingencies 193, and 194 for TSAT Max Generator Speed
Deviation as 1 p.u
Generator angle (degrees)
520
74000
412
59000
304
44000
196
29000
88
14000
-20
0.00
1.00
2.00
3.00
Time (sec)
4.00
5.00
-1000
0.00
1.00
2.00
3.00
4.00
5.00
Time (sec)
Figure 16: System Response for Contingencies 195, and 196 for TSAT Max Generator Speed
Deviation as 1 p.u
72000
73000
57400
58200
42800
43400
28200
28600
13600
13800
-1000
0.00
1.00
2.00
3.00
4.00
5.00
-1000
0.00
1.00
2.00
Time (sec)
3.00
4.00
5.00
Time (sec)
Figure 17: System Response for Contingencies 197, and 198 for TSAT Max Generator Speed
Deviation as 1 p.u
Generator angle (degrees)
510
510
404
404
298
298
192
192
86
86
-20
0.00
1.00
2.00
3.00
4.00
5.00
-20
Time (sec)
0.00
1.00
2.00
3.00
4.00
5.00
Time (sec)
Figure 18: System Response for Contingencies 213, and 273 for TSAT Max Generator Speed
Deviation as 1 p.u
90
90
54
54
18
18
-18
-18
-54
-54
-90
0.00
1.00
2.00
3.00
4.00
5.00
-90
0.00
1.00
2.00
Time (sec)
3.00
4.00
5.00
Time (sec)
Figure 19: System Response for Contingencies 286, and 288 for TSAT Max Generator Speed
Deviation as 1 p.u
Generator angle (degrees)
90
90
66
54
42
18
18
-18
-6
-54
-30
0.00
1.00
2.00
3.00
Time (sec)
4.00
5.00
-90
0.00
1.00
2.00
3.00
4.00
5.00
Time (sec)
Figure 20: System Response for Contingencies 291, and 301 for TSAT Max Generator Speed
Deviation as 1 p.u
Conclusion
From the previous results, it can be said that for all the 380 KV transmission lines,
only three contingencies can be considered as critical, and it needs more
investigations and studies on them. These contingencies are as follows:
133 -81.02*
25.86 Insecure 4KONYA_KAPI 380.
420511 422010
168 -77.94*
59.98 Insecure 4VARSAK 380.
510110 514310
292 -81.02*
25.86 Insecure 4KONYA_KAPI 380.
420511 420510
Another thing to be noticed is that for any contingency that is terminated at early
stage from its simulation, it needs more investigations on it. For TSAT simulation
program, the Max Generator Speed Deviation setting should be increased beyond its
default value of 0.1 p.u to check the security of each of these contingencies that are
terminating in early stage of the simulation.