You are on page 1of 7

COMPLEX LOOP DESCRIPTION

FC0155_CC / FI0155_CC / FC5323_CC /


FY0155A_CC / FY0155B_CC /
HY0155_CC / LC0196_CC
PV-8100 CDHydro NAPHTHA SPLITTER
INTERNAL REFLUX FLOW

Page 1 of 7
NOTICE
Confidential Bechtel Corporation 2001. This item contains confidential information
proprietary to Bechtel Corporation that is not to be used, disclosed, or reproduced in any
format by any non-Bechtel party without Bechtel's prior permission. Not withstanding
the above, EQUIVA Services LLC has the right to use the information contained in this
document pursuant to Contract 24583 between Bechtel Corporation and EQUIVA
Services LLC.

COMPLEX LOOP
JOB NO.: 24583-300
000

01/06/03

Issued As Config

FT

TP

EK

RN

00B

01/03/02

Issued for Design

FT

TP

EK

RN

Issued For Approval

FT

TP

EK

RN

BY

CKD EGS

00A

11/02/01

NO.

DATE

REVISION

APE

SCALE: NONE
NUMBER ASSIGNED
AND TRACING
RECORD ENTERED

J3-JD-00031

A-57X-0001

DATE

000

2 of 7

COMPLEX LOOP DESCRIPTION


LSG PROJECT NORCO REFINING

A: LOOP DIAGRAM
E-8108

HH
H
LC
0196_CC

PV-8104
REFLUX DRUM

LN
0196_CC

SP
X2
FC
0155_CC

FY
0155A_CC

See Note 2.

CV = X2 * (1 + (CP / ) * T), See Note 1.

CV
TI
0205_CC

X2

FN
0155_CC

FY
0155B_CC

X1

HY
0155_CC

Z VALUE
(SET BY OPERATOR)

CV
X

FO

SP

FI
0155_CC

PV-8100
CDHYDRO
NAPHTHA
SPLITTER

P-8102/8103

FC
5323_CC

INTERNAL REFLUX

OSBL AREAS

H
FN
5323_CC

TI
0157_CC

Z
FC

(X Z)

E-7233A/B

TO NAPHTHA
SPLITTER FEED
DRUM

NOTE 1:
T IS THE DIFFERENCE BETWEEN TI0157_CC AND TI0205_CC,
BUT FOR PRACTICAL PURPOSES IT IS ASSUMED TO BE A CONSTANT.
NOTE 2:
CALCULATORS (FY0155A/B_CC) ON P&ID E-57A-0063 REPRESENT THE FUNCTIONS INSIDE THE DOTTED
LINE.

300-J3-JD-00031

TO LCN
PRODUCT

3 of 7

COMPLEX LOOP DESCRIPTION


LSG PROJECT NORCO REFINING

B:

PROCESS CONTRL FUNCTIONAL DESCRIPTION


LOOP:

Reference:

FC0155_CC/FI0155_CC/FY0155A_CC/FY0155B_CC/FC5323_CC/
HY0155_CC/ LC0196_CC
PV-8100 CDHydro NAPHTHA SPLITTER
Internal Reflux Flow Control
P&ID Drawing No. E-57A-0063
E-57A-0067 /E-57A-0171
E-53A-0354 / E-53A-0264 (OSBL)

The purpose of this complex loop is to control the light gasoline product sidedraw and reflux flow to
achieve a constant internal reflux rate in the catalyst beds. The operator is given the flexibility to set the
desired internal reflux Z at subtractor, FY0155B_CC via HY0155_CC by resetting the setpoint.
The required controls and calculations are given in the following section, Section C, in detail.

300-J3-JD-00031

4 of 7

COMPLEX LOOP DESCRIPTION


LSG PROJECT NORCO REFINING

C:

INSTRUMENTATION FUNCTIONAL DESCRIPTION


LOOP:

FC0155_CC/FI0155_CC/FY0155A_CC/FY0155B_CC/FC5323_CC/
HY0155_CC/LC0196_CC
PV-8100 CDHydro NAPHTHA SPLITTER
Internal Reflux Flow Control

The following discussion provides additional information required for point configuration.
LC0196_CC
LC0196_CC is a standard PID controller with the following exceptions:
1) PVTRACK is set to NOTRACK.
2) CTLEQN is set to EqC.
FC0155_CC
FC0155_CC is a standard PID controller normally set in CAS mode receiving its setpoint input from
LC0196_CC.
FI0155_CC
FI0155_CC is a standard RegPv slot with DataAcq algorithm, which displays the calculated internal
reflux, the CV of FY0155A_CC.
FY0155A_CC
FY0155A_CC performs a calculating function, i.e., the internal reflux of the CDHydro column. A
regulatory control block, MulDiv, is used to keep the integrity of the complex control loop. Detailed
calculation is discussed below:
The internal reflux is calculated based on the enthalpy balance as follows,
FY0155A_CC.CV = FN0155_CC.PV * [1 + (Cp / ) * T)]
Where,
FY0155A_CC.CV = Internal reflux mass flow rate in pasteurization section
FN0155_CC.PV = External reflux mass flow rate
Cp = Heat capacity
= Latent heat of vaporization
T = Temperature difference between side draw, TI0157_CC.PV, and external reflux, TI0205_CC.PV.

300-J3-JD-00031

5 of 7

COMPLEX LOOP DESCRIPTION


LSG PROJECT NORCO REFINING

The value of the ratio (Cp / ) based on the CDTECH computer simulated back calculation may be
approximated by a constant, i. e., 0.0039.
From the same simulation, it was found that the percent variation in T due to changes in side draw and
external reflux temperature is generally small. Based on the result of the simulation, it gives,
T = 228 130 = 98 Deg F
With these simplifications, the above equation can be reduced to the following,
FY0155A_CC.CV = (FN0155_CC.PV) * [1 + 0.0039 * 98] = (FN0155_CC.PV) * (1.3822)
Using Eq. A, RegCtl MulDiv Algorithm, we have
CV = K * (K1 * X1 + B1) * (K2 * X2 + B2) + B
Where,
K = 1.0,
K1 = 0.0,
K2 = 1.0,

B = 0.0,
B1 = 1.3822,
B2 = 0.0.

This final equation will be used to configure the DCS block. However, it is reminded that if during
start-up or normal operation experience indicates otherwise, the approximated constant, 1.3822, should
be adjusted accordingly.
FY0155B_CC
FY0155B_CC is a subtractor. For the same justification, a SUMMER regulatory control block is used.
This DCS block calculates the internal reflux rate below the side draw tray by the following equation,
FY0155B_CC.CV = X2 X1 = Set point to FC5323_CC.
Where,
X2 = FY0155A_CC.CV = (FN0155_CC.PV) * (1.3822)
X1 = Operator Manual Set Value from HY0155_CC, but must be greater than ZMIN.
FC5323_CC
FC5323_CC is a standard PID controller normally set in CAS mode receiving its setpoint from
FY0155B_CC.
HY0155_CC

300-J3-JD-00031

6 of 7

COMPLEX LOOP DESCRIPTION


LSG PROJECT NORCO REFINING

HY0155_CC is a standard PID controller set in Auto mode. The operator uses the setpoint parameter of
this controller to adjust the required Z value. The range of the Packed Bed Wetting rate is LIMITED
between 25.6 MBBL/D and 46.9 MBBL/D. The normal rating is being set at 42.7 MBBL/D

300-J3-JD-00031

7 of 7

COMPLEX LOOP DESCRIPTION


LSG PROJECT NORCO REFINING

D:

LOGIC SLOT DIAGRAM

This complex loop does not require Logic Slot Diagram.