Check the sensor wiring to the EXV board.

Check the board for a faulty channel.


Check for a faulty thermistor.
For thermistor descriptions, identifiers and connections, see
Thermistors on this page.
Condenser Subcooling Liquid Thermistor
th.18 Circuit A
th.19 Circuit B
Criteria for Trip Tested when the unit is On or Off. If the
temperature as measured by the sensor is outside of the range
of 40 F (40 C) to 240 F (115.6 C). This alarm is for units
with the heat reclaim option only.
Action to be Taken The unit will return to the air cooled
mode.
Reset Method Automatic, the alarm will reset once the reading is within the expected range.
Possible Causes If this condition is encountered, check the
following items:
Check the sensor wiring to the EMM HR.
Check for a faulty thermistor.
Confirm unit configuration.
th.21 Space Temperature Sensor Failure
Criteria for Trip This alarm criterion is checked whether the
unit is ON or OFF and if Space Temperature Reset has been
enabled. If the outdoor-air temperature as measured by the
thermistor is outside of the range 40 F (40 C) to 240 F
(115.6 C), the alarm will be triggered.
Action to be Taken Unit operates under normal control.
Temperature Reset based on Space Temperature is disabled.
Reset Method Automatic, once the thermistor reading is
within the expected range. The Space Temperature Reset will
resume once the alarm has cleared.
Possible Causes If this condition is encountered, check the
following items:
Check the sensor wiring to the energy management
module.
Check the board for a faulty channel.
Check for a faulty thermistor.
For thermistor descriptions, identifiers and connections, see
Thermistors below.

th.09 Leaving Condenser Reclaim Thermistor


Criteria for Trip Tested when the unit is On or Off. This
alarm is generated if the temperature measured by the sensor is
outside the range of 40 F (40 C) to 240 F (115.6 C). This
alarm is for units with the heat reclaim option only.
Action to be Taken None
Reset Method Automatic, the alarm will reset once the
thermistor reading is within the expected range.
Possible Causes If this condition is encountered, check the
following items:
Check the sensor wiring to the heat reclaim board.
Check for a faulty thermistor.
Check the board for a faulty channel.
Confirm unit configuration.
th.10 OAT Thermistor Failure
Criteria for Trip If the outdoor air temperature as measured
by the thermistor is outside of the range 40 F (40 C) to 240 F
(115.6 C).
Action to be Taken Unit shuts down under normal conditions or is not allowed to start. Temperature reset based on
outdoor air temperature will be disabled.
The OAT sensor controls the cooler heaters. If this sensor
fails, the cooler heaters will be energized when the machine
stages to 0.
Reset Method Automatic, the alarm will reset once the
thermistor reading is within the expected range and Temperature reset based on outdoor-air temperature will be enabled.
Possible Causes If this condition is encountered, check the
following items:
Check the sensor wiring to the main base board.
Check for a faulty thermistor.
For thermistor descriptions, identifiers and connections, see
Thermistors on this page.
th.11 Master/Slave Common Fluid Thermistor
Criteria for Trip This alarm criterion is checked whether the
unit is ON or OFF and has been configured for Dual Chiller
Control. The alarm will be triggered if the Dual Chiller
Common Fluid temperature as measured by the thermistor is
outside of the range 40 F (40 C) to 240 F (115.6 C).
Action to be Taken Dual Chiller Control disabled. Units
operate as a stand-alone machine.
Reset Method Automatic, once the thermistor reading is
within the expected range. The Dual Chiller algorithm will
resume once the alarm is cleared.
Possible Causes If this condition is encountered, check the
following items:
Check the sensor wiring to the main base board.
Check for a faulty thermistor.
For thermistor descriptions, identifiers and connections, see
Thermistors on this page.
Suction Gas Thermistor
th.12 Circuit A
th.13 Circuit B
th.14 Circuit C
Criteria for Trip This alarm criterion is checked whether the
unit is ON or OFF. If the suction gas temperature as measured
by the thermistor is outside of the range 40 F (40 C) to 240 F
(115.6 C), the alarm will be triggered.
Action to be Taken The affected circuit shuts down
normally.
Reset Method Automatic, once the thermistor reading is
within the expected range. The affected circuit will restart once
the alarm has cleared.
Possible Causes If this condition is encountered, check the
following items:

Sensors The electronic control uses up to six thermistors to sense temperatures and up to six transducers to sense
pressure for controlling chiller operation. These sensors are
outlined below.

Thermistors (Tables 45-46B) Thermistors that are


monitoring the chillers operation include: cooler entering water, cooler leaving water, dual chiller leaving water, compressor
suction gas temperature, and outside air thermistors. These
thermistors are 5 kat 77 F (25 C) and are identical in temperature versus resistance. The space temperature thermistor is
10 k at 77 F (25 C) and has a different temperature vs.
resistance.
COOLER LEAVING FLUID SENSOR On all sizes, this
thermistor is installed in a friction fit well in the leaving water
nozzle of the cooler. See Fig. 34 and 35.
COOLER ENTERING FLUID SENSOR On all sizes,
this thermistor is factory-installed in a friction fit well in the
entering water nozzle of the cooler.
DUAL CHILLER LWT On duplex chillers, 30RB315390, a factory-supplied, field-installed friction fit well and
thermistor are installed in the common supply water header of
the two modules.
COMPRESSOR RETURN GAS TEMPERATURE This
thermistor is factory-installed in a friction fit well located in the
71

2. Connect the other ends of the wires to terminals 7 and 8


on TB6 located in the unit control box.
Units on the CCN can be monitored from the space at the
sensor through the RJ11 connector, if desired. To wire the RJ11
connector into the CCN:
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black () conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of
the space temperature sensor.
4. Insert and secure the black () wire to terminal 2 of the
space temperature sensor.

common suction line for the circuit. There is one thermistor for
each circuit.
OUTDOOR AIR TEMPERATURE This sensor is factoryinstalled and is attached to the bottom of the condenser mounting rail.
REMOTE SPACE TEMPERATURE This sensor (part
no. 33ZCT55SPT) is a field-installed accessory mounted in the
indoor space and is used for water temperature reset. The
sensor should be installed as a wall-mounted thermostat would
be (in the conditioned space where it will not be subjected to
either a cooling or heating source or direct exposure to sunlight, and 4 to 5 ft above the floor).
Space temperature sensor wires are to be connected to
terminals in the unit main control box. See Fig. 36. The space
temperature sensor includes a terminal block (SEN) and a RJ11
female connector. The RJ11 connector is used access into
the Carrier Comfort Network (CCN) at the sensor.
To connect the space temperature sensor (see Fig. 36):
1. Using a 20 AWG twisted pair conductor cable rated for
the application, connect one wire of the twisted pair to
one SEN terminal and connect the other wire to the other
SEN terminal located under the cover of the space
temperature sensor.

IMPORTANT: The cable selected for the RJ11


connector wiring MUST be identical to the CCN
communication bus wire used for the entire network.
Refer to Table 12 for acceptable wiring.
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus.
NOTE: The energy management module (EMM) is required
for this accessory.

Table 45 Thermistor Identification


THERMISTOR ID
EWT
LWT
OAT
SGTA
SGTB
SGTC
DUAL
SPT

DESCRIPTION
Entering Water Thermistor
Leaving Water Thermistor
Outdoor Air Thermistor
Circuit A Suction Gas Thermistor
Circuit B Suction Gas Thermistor
Circuit C Suction Gas Thermistor
Dual Chiller LWT Thermistor
Space Temperature Thermistor

RESISTANCE AT 77 F (25 C)
5k
5k
5k
5k
5k
5k
5k
10k

O-RING

CONNECTION POINT
MBB-J6-CH2
MBB-J6-CH1
MBB-J6-CH4
EXV1-J3-A, THA
EXV1-J3-B, THB
EXV2-J3-A, THA
MBB-J6-CH3
EMM-J6-CH2

BRASS NUT 3/8 - 24 FOR


ASSEMBLY ON BRASS WELL

Fig. 34 5K Thermistor (P/N 30RB660036)

1/4-18 NPT

6" MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL

1.188 in.
2.315 in.

Fig. 35 Entering and Leaving Dual Water Thermistor Well (P/N 00PPG000008000A)

72

Table 46A 5K Thermistor Temperature (F) vs Resistance


TEMP
(F)
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

RESISTANCE
(Ohms)
98,010
94,707
91,522
88,449
85,486
82,627
79,871
77,212
74,648
72,175
69,790
67,490
65,272
63,133
61,070
59,081
57,162
55,311
53,526
51,804
50,143
48,541
46,996
45,505
44,066
42,679
41,339
40,047
38,800
37,596
36,435
35,313
34,231
33,185
32,176
31,202
30,260
29,351
28,473
27,624
26,804
26,011
25,245
24,505
23,789
23,096
22,427
21,779
21,153
20,547
19,960
19,393
18,843
18,311
17,796
17,297
16,814
16,346
15,892
15,453
15,027
14,614
14,214
13,826
13,449
13,084
12,730
12,387
12,053
11,730
11,416
11,112
10,816
10,529
10,250
9,979
9,717
9,461
9,213
8,973
8,739
8,511
8,291
8,076

TEMP
(F)
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142

RESISTANCE
(Ohms)
7,686
7,665
7,468
7,277
7,091
6,911
6,735
6,564
6,399
6,238
6,081
5,929
5,781
5,637
5,497
5,361
5,229
5,101
4,976
4,855
4,737
4,622
4,511
4,403
4,298
4,196
4,096
4,000
3,906
3,814
3,726
3,640
3,556
3,474
3,395
3,318
3,243
3,170
3,099
3,031
2,964
2,898
2,835
2,773
2,713
2,655
2,597
2,542
2,488
2,436
2,385
2,335
2,286
2,239
2,192
2,147
2,103
2,060
2,018
1,977
1,937
1,898
1,860
1,822
1,786
1,750
1,715
1,680
1,647
1,614
1,582
1,550
1,519
1,489
1,459
1,430
1,401
1,373
1,345
1,318
1,291
1,265
1,240
1,214

73

TEMP
(F)
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225

RESISTANCE
(Ohms)
1,190
1,165
1,141
1,118
1,095
1,072
1,050
1,029
1,007
986
965
945
925
906
887
868
850
832
815
798
782
765
750
734
719
705
690
677
663
650
638
626
614
602
591
581
570
561
551
542
533
524
516
508
501
494
487
480
473
467
461
456
450
445
439
434
429
424
419
415
410
405
401
396
391
386
382
377
372
367
361
356
350
344
338
332
325
318
311
304
297
289
282

Table 46B 5K Thermistor Temperature (C) vs Resistance/Voltage


TEMP
(C)
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14

TEMP
(C)
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61

RESISTANCE
(Ohms)
100,260
94,165
88,480
83,170
78,125
73,580
69,250
65,205
61,420
57,875
54,555
51,450
48,536
45,807
43,247
40,845
38,592
38,476
34,489
32,621
30,866
29,216
27,633
26,202
24,827
23,532
22,313
21,163
20,079
19,058
18,094
17,184
16,325
15,515
14,749
14,026
13,342
12,696
12,085
11,506
10,959
10,441
9,949
9,485
9,044
8,627
8,231

RESISTANCE
(Ohms)
7,855
7,499
7,161
6,840
6,536
6,246
5,971
5,710
5,461
5,225
5,000
4,786
4,583
4,389
4,204
4,028
3,861
3,701
3,549
3,404
3,266
3,134
3,008
2,888
2,773
2,663
2,559
2,459
2,363
2,272
2,184
2,101
2,021
1,944
1,871
1,801
1,734
1,670
1,609
1,550
1,493
1,439
1,387
1,337
1,290
1,244
1,200

TEMP
(C)
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107

RESISTANCE
(Ohms)
1,158
1,118
1,079
1,041
1,006
971
938
906
876
836
805
775
747
719
693
669
645
623
602
583
564
547
531
516
502
489
477
466
456
446
436
427
419
410
402
393
385
376
367
357
346
335
324
312
299
285

SENSOR

SEN

TB6

SEN

7
8

Fig. 36 Typical Remote Space Temperature Sensor Wiring


operate along with the EXVs. There must be a load on the
chiller of operate for an extended period of time. All circuit
safeties will be honored during the test. Service TestQUIC
allows for test of EXVs, condenser fans, pumps, low ambient
head pressure control speed control, crankcase and cooler heaters, and status points (alarm relays, running status and chiller
capacity). This mode allows for the testing of non-refrigeration
items. If there are no keys pressed for 5 minutes, the active test
mode will be disabled.
To enter the Manual Control mode, the Enable/Off/Remote
Contact switch must be in the OFF position. Move the LED to
the Service Test mode. Press ENTER to access TEST. Press
ENTER to access T.REQ. Press ENTER and the display
will show OFF. Press ENTER and OFF will flash. Enter the
password if required. Use either arrow key to change the

Service Test Main power and control circuit power

must be on for Service Test.


The Service Test function is used to verify proper operation
of various devices within the chiller, such as condenser fan(s),
compressors, minimum load valve solenoid (if installed),
cooler pump(s) and remote alarm relay. This is helpful during
the start-up procedure to determine if devices are installed
correctly. See Fig. 37-41 for 30RB wiring diagrams.
To use the Service Test mode, the Enable/Off/Remote Contact switch must be in the OFF position. Use the display keys to
move to the Service Test mode. The items are described in the
Service Test table. There are two sub-modes available. Service
TestT.REQ allows for manual control of the compressors
and minimum load control. In this mode the compressors will
operate only on command. The capacity control and head pressure control algorithms will be active. The condenser fans will
74

the Service Test mode. Press ENTER to access TEST. Use


the
key until the display reads QUIC. Press ENTER to
access Q.REQ. Press ENTER and the display will show OFF.
Press ENTER and OFF will flash. Enter the password if
required. Use either arrow key to change the QUIC value to
ON and press ENTER . Quick Test mode is now active. Follow the same instructions for the Manual Control mode to activate a component.

T.REQ value to ON and press ENTER . Manual Control


mode is now active. Press the arrow keys to move to the appropriate item. To activate an item locate the item, press ENTER
and the display will show OFF. Press ENTER and OFF will
flash. Use either arrow key to change the value to ON and
press ENTER . The item should be active. To turn the item
off, locate the item, press ENTER and the display will show
ON. The chiller must be enabled by turning the Enable/Off/
Remote Contact switch to Enable. Press ENTER and ON will
flash. Use either arrow key to change the value to OFF and
press ENTER . The item should be inactive.

Example Test the chilled water pump (see Table 47).


Power must be applied to the unit. Enable/Off/Remote
Contact switch must be in the OFF position.

To enter the Quick Test mode, the Enable/Off/Remote


Contact switch must be in the OFF position. Move the LED to
Table 47 Testing the Chilled Water Pump
MODE
(Red LED)

SUB-MODE

SERVICE TEST

KEYPAD
ENTRY

ITEM

VALUE
DESCRIPTION
(Units)

COMMENT

Service Test Mode

ENTER

TEST
QUIC

DISPLAY
EXPANSION

Manual Sequence
ENTER

Q.REQ
PASS WORD

Password may be required


0111

ENTER

ENTER

Each

ENTER

digit. If 0111 is not the password,

ENTER

will lock in the next

use the arrow keys to change the


ENTER

password digit and press

ENTER

ENTER

when correct.

ENTER

Q.REQ

Returns to the original field

ENTER

OFF

ENTER

OFF

OFF will flash

ON

The Enable/Off/Remote Contact


switch must be in the OFF
position.

ESCAPE

Q.REQ
EXV.A
EXV.B
PMP.1

Water Exchanger
Pump 1

ENTER

OFF

ENTER

OFF

OFF will flash

ON
ENTER

ON

Pump 1 will turn on.

ENTER

ON

ON will flash

OFF
OFF

ENTER

75

Pump 1 will turn off.

turn a compressor, circuit or the machine off if required. Any


other mode or sub-mode can be accessed, viewed, or changed
during the Manual Control mode only. The STAT item (Run
StatusVIEW) will display 0 as long as the Service mode is
enabled. The TEST sub-mode value must be changed back to
OFF before the chiller can be switched to Enable or Remote
contact for normal operation.
NOTE: There may be up to a one-minute delay before the
selected item is energized.

Test the condenser fans, cooler pump(s) and alarm relay by


changing the item values from OFF to ON. These discrete
outputs are then turned off if there is no keypad activity for
10 minutes. Test the compressor and minimum load valve solenoid (if installed) outputs in a similar manner. The minimum
load valve solenoids will be turned off if there is no keypad
activity for 10 minutes. Compressors will stay on until the
operator turns them off. The Service Test mode will remain
enabled for as long as there is one or more compressors
running. All safeties are monitored during this test and will

LEGEND FOR FIG. 37-41


ALM R
ALT R
CB
CL-HT
CWFS
DLSV
DPT
ECA
EMM
EXV
FIOP
FM
HOA
HOA-A
LCW
LLSV
LWT
MLV
MM
OAT
PDP
PMP
PMPI
RDY R
RRB
RUN R
SGT
SHD R
SPM
SPT
TB
TRAN
UPC

Alarm Relay
Alert Relay
Circuit Breaker
Cooler Heater
Chilled Water Flow Switch
Discharge Line Soleniod Valve
Discharge Pressure Transducer
Entering Condenser
Energy Management Module
Electronic Expansion Valve
Factory-Installed Option
Fan Motor
Hand/Off/Auto
Hand/Off/Auto, Auto Setting
Leaving Condenser Water
Liquid Line Soleniod Valve
Leaving Water Temperature
Minimum Load Valve
Low Ambient Temperature Head Pressure Control
Outdoor Air Temperature
Pumpdown Pressure
Pump, Chilled Water
Chilled Water Pump Interlock
Ready Relay
Reverse Rotation Board
Run Relay
Suction Gas Thermistor
Shutdown Relay
Scroll Protection Module
Suction Pressure Transducer
Terminal Block
Transformer
Unitary Protocol Controller

Terminal Block Connection


Marked Terminal
Unmarked Terminal
Unmarked Splice
Factory Wiring
Optional Wiring
Indicates common potential.
Does not represent wiring.
FIOP or Accessory
Wire Tag

76

?????????
???

?????????
???
???????
????
??????

???????
???????
??????

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

?
?

?
?

?
?
?

? ? ?? ? ?

??
???
? ? ? ? ? ? ? ?
??????????????????????

???
???
???

???????

???

????????????????????????
???????????????
?????????????????????????
????????????????????????????

??

???

???

?????

???

???

???????
?

???

??

???

?????

???

?
?

???

?
?

??? ???

???

?
?

???
?????

???

???

???

??? ??? ???

???

?????????
??????
?

???

???

???? ????
?

?
???

???

???

?
?

???

?
??

?????????
?????

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

?
?

??

???
?

????????????????
???????????????????????????

???
?
?
?

?
?

???

???

?
?
?

???
???
???

???
??????
??????
??? ???
??????
??? ???
????
????
??????????

??
?????

???

?
?

???

???

?
?

???

?
?

???
?

?
?

?????
?????

??

???? ???? ???? ????


???? ???? ???? ????

????
????

?
?

???

?????????????
???????????????????

???

???

?? ?? ?? ??

77

???
???

?? ?? ?? ??

Fig. 37 Control Schematic, 30RB060-080

??
???

???
????????????

?? ?? ??

???????

?????????

???

?????????????????

???

???

???

?????????????

???

?????????
?????????????

???

?????????

???
???
??????????????
??????
?????????

???
???

???

????????????

???

???

???

???????
??????
?????????

???
???

???

????????????
???

???

?
?

???????
??????
?????????

??????????????
??????
?????????

???

?
?

?????
????
?????

?
?

?
?

???
???

???
?

??

?
???

??
???

???

???

?
?
?
?
?
?
?
?

?
?
?
?
?
?
?
?
?
??

???

???
???

? ?? ???
????????

??
??

??????

??
?

??????????????

??
?

??????????

??
??

???

???

??
??

??

???
???

??
?

??

???

???

??

???

??
??

???

???

???

??

???

??

???

???

??

???

???

??

???

??

???????

??

??

???

???
?????
??????????????

??

??

??
?

???

???
?

?????

?????

???
?

???
??

??

???

? ?

???

??

???

?????????????
????

???

???

??? ?
??????
???
??

???

????????
???????
????????
???????

???
?

???

???

???

??

??

???

??????????????????????
????????????????????
??????????????????????
?????????????????
??????????????

??????????????????????
???????????
??????????????????????????????

???

???
?

??????????????
??????????

???

???

?
?

??
??????
??????????
?????????

??

???

???
???
?

???

???

???

???????????????
??????????

???

??

???

???
?

???

???

??

???

????
???????????

??

??

?????
????????????????????????????
?????????????????????????????????
?????????????????????????????

???
?

???

?????????
????????

??

???
??

??

???

?????

?
?

??
??????
??????????
?????????

???????
????????
???

???

???
??

???

??

???

?????

?????

???

??

????

???
?

???

???

???
??

???

????

???

?? ?????

??

???
?

????

???

??

???

??

???

???

???

???
??

???
???
??

???

??? ?
??????

??? ?? ???
?

??

?????

???
???
??

?????

???

?????

????
??
??
?????

??

?????

?????

??

????
??
???

???

?????

???

??
??
????
?????????????????????

???
?? ???

??

???
?????

???

??
?

???

???

???

??
?

???

???

??
?

???

??

????

???

??
?

????

?????

???

??

???

??
??

??

?
?

??
??

???

??

??

??
??

???
??
???

???

??
?

???

????

???

???

???

????

???
?

???

???
??

????

????

????

?
?

???

???

????

???
???

???

????

??
???

???????????????????????????

??
???

???

????

???
??

?????

???

?????

?????????????

????????????????????????????

???
?

???

??

?????

???
???
?

?????????????
??????????
??????????????

???

??????

???

???

???

???

????

???
?

?????

??

???

???

?????? ?????? ??????

???

???

? ?

?????

???
??????

??

?????????????
????

???

???

???

??????
?????????????

???

??

????

???
???
?

???
??

??????
???????

??
???
? ? ? ? ? ? ? ?
??????????????????????

??????????

a30-4619

?????????
???

?????????
???
???????
????
??????

???????
???????
??????

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

?
?

?
?
?

?
?

???

???

? ? ?? ? ?

???

??? ??? ???

??

???

????????????????????????
???????????????
?????????????????????????
????????????????????????????

???

???

???

?????

???

???

???????

???

??

?????

???

???

???

???

???? ????
?

?
?

???

???

?????????
?????

???

?
?

??? ???

???????
?

???
?????

???

???

???

???

?????????
??????

??
???
? ? ? ? ? ? ? ?
??????????????????????

???
???

??

???

??

????????????????
???????????????????????????

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

?
?
?

???

???

?
?
?

???
???
???

???
??????

?
?

?
????
??

???
???
???

?
?
?

?????
?
?
???
?
?????

????
????

???
??
???

???

???

???

???
??

???

???
?

??

??

???

???
???

??

???

???

???

???
???

?
?
?

?????

????

???
???

???

??
????
???????????

?
?

??????????????
??????????

?
?

?
?

???

???

??

???

??

???

??

?????????????
???????????????????

???
?? ??

???

???

???

???

???????????????????
??????????????????

??
?

??
?
?

???
???

??
???

???
???

?? ?? ?? ??

??
??
??
??

??
??

??
???

???

???
?

???

???

?????????????????
?????????????????

???

?????????????????
?????????????????
?????????????
?????????????????
?????????????????

???

???

?????????????????
?????????????????

???

?????????????????
?????????????????

???

?????????????????

???
???

????????
?????
??????
?????????

???
???

???

????????????

???

???

???

???

???
???

????????????

??
??
???

?? ?? ??

???

??????????????????
?????????????????

???????
??????
?????????

???

???

???

?
?

?????
????
?????

?
?

?
?

???????
??????
?????????
????????
?????
??????
?????????

???
???

???
?

??

?
???

?
?
?
?
?
?
?
?
?

?
?
?
?
?
?
?
?
?
??

???

???
???

? ?? ???
????????

???
?

??
??

??????

???

???
??

??????
??????

??
??

??????????????

???

???

??

??????????

???

???

???

??

???

??

???
????????????

???

?????

???
?

???
?

???

?????????

???

???

??
?

?????

??

?????????
????????

???

?? ?? ??

??

??

???

??

??

???

???
?????
??????????????

???

???

??

???

???
?? ??

???

??

???

???
???

??? ?
??????

???

??

??

?
?

??

???

??????

???

???

???

???

???

??

???

? ?
?

???

?? ?? ??

???

???

???

???
??

?? ?? ?? ??

???

??

???

??????????????????????
????????????????????
??????????????????????
?????????????????
??????????????

?????

???

?????????????
????

???

?????????????
????

???????????
?????????

?????????????
????

???

???

??

??

????????
???????
????????
???????

???????
???

???

??
??????
??????????
?????????

??????????????????????
???????????
??????????????????????????????

???

???
??

???

??

??

???

???????????????
??????????

?
?

??

???
???

??????

???

???

???????

??

??

???

??

?
?

??
??

?????

?
?

???
?

???

?????

???

?
?

?????????????
????

????????????????????

???

???
?

???????
????????
???

??

???
???
??

??

???

???

???
?

?
?

??

?
??? ?
??????

?????
?
?
??????????????????
?????????????????????
??
??????????????????????? ??????
??????????
????????????????????
?????????
?????????

???

???

????

??

???

???

???

?????

???

???
?

????

???

?????

??

???

???
??

????

???

???
?

???

?????

???

???

???

??

???
??

???
??

???

???

???
?? ?????

???

???
?????

???

???

???

???
??

???

???

???
???
??

?????

???

?????

?????

??

????
??
??

??

?????

???

??? ??
?

?????

???

?????

????
??
??

???
?? ???

???

?????

????

?
?

???????

??

??

?
?

??

???

???

??
????
?????????????????????

???

??
?

???

??

??
?

???
??
???

???

??

??
?

???

???

????

??
?

???
?

???

????

???

??
???

????

??
?

???????????????????????????

??

??
?

???

???

? ?

???

??
???

????

???

???

????

???
??

???

???

????

???
?

?????????????

?????????????
??????????
??????????????

????

???

????????????????????????????

???
?

???

????

???

???

???

?????

???
?

???

?????

???

??

?????

???

?????

??????

???

??????

???

??

?????? ?????? ??????

???

???

???

??????
?????????????

???

??

???? ???? ???? ????

????

???
???
?

???
??

??????
???????

??
???
? ? ? ? ? ? ? ?
??????????????????????

??????????

???? ???? ???? ????

??
?????

??????
??? ???
??????
??? ???
????
????
??????????

?? ?? ??

Fig. 38 Control Schematic, 30RB090-150


78

a30-4620

? ?? ? ??

???

???

???

?
?

???

???

???

???

???

???

???

???

?
?

???

???

?
?

??

?
?

???

???

???? ????

???

?
??

?????????
??????
?

?????????
?????
?
???

???

???

???

???

???

???

???

???

???

???

???

???
???
???
?

???

???

???

???

???

???

???

???

???

?
?

???

???

?
?
?

??

???

???

???

???

???

???

??

??

???
???????

???
??????

??

??????
??? ???
??????
??? ???
????
????
??????????

??
?????

????

???

???

?
????

???

???

???

???

???
??

???
?

??

???
??

???

???

???
?

?
?

???

?????

???
???
?

???

???

??

??

???

?????

?????

?????

???

???

???
??

???

???

????

??

???

???

??
???
???

?
?

???
???

????

???

???

??

??

???
???????

??

??????????????
??????????

?????
?????????????????
?????????????????????
???????????????????????
???????????????????
?????????

???????????????
??????????

?
?

??
???

???

?
?

???

??
?

???

?
?
?

??

???

?
?
?
?
?

??

??

??

??

??

??

??

??

??

??

??

???
???
???
???

?
???

???

?
???

?
?

???
???

?
?
?
?

???
???
???

?????????
???
???

???
???
???

???
???
???
???

???

??

??

??

??

??

??

??

??

??

??

??

??

?
?
?
?
?
?
?
?

?
?
?
?

?
?
?
?
?

???
???
???
???
???

?
?

???

???

???

?
???

?
?

???
???

?
?
?
?

?????????

???

??????????????
??????????
?????????????
?????????
?????????????
?????????
??????????????
??????????

???

??????????

???

??????????

???

???
???
????????
????? ???????
?????????

???
???

???

????????????

???

???

???

???????
??????
?????????

??
??

??
??
?????????????
???????????????????

?????

??
??

??
??

??
?

??
?
?

???

???

???

???

????

?? ?? ??

???

???

???

???

????

???

???

???

???

????

????

?? ?? ?? ??

???

???
?

??
??
?

???
???

???
????????????

???

???

??
???

?? ?? ?? ??

?????????
????????

???

???
?

???

??? ?
??????

???

???????
?????
????

???

???
??

???

???????
???

??
??

??
???

???

???

???????
??????
?????????

????????
????? ???????
?????????

???

?
?

?
?

?
?

???
???

???
?

?????
????
?????
??

?
???

???
???

?
?
?
?
?
?
?
?

?
?
?
?
?
?
?
?
?
??

???

???
???

? ?? ???
????????

???

??

??????

?????

????????????

???

??????????

???

???

???

???????
?????
????

?
?

???

???????????????????

?? ?? ?? ??

???

??

???

??

?????
???

??????

??

???

??

?????
???

???

???

???
?

??
??????
??????????
?????????

???
?????
??????????????

???

???
??

??????
??????

???

???

???

???

???

???

? ?

??????????????????????
????????????????????
??????????????????????
?????????????????
??????????????

???

???

????????
???????
????????
???????

???

?????

???

??????????????????????
???????????
??????????????????????????????

???

???
?

???

???

??????
???
??

???

???

???????

??

???

??

????
???????????

???

???
?

????

???

?
?

???

???????
????????
???

???

???

??

??

???

?????

???

???
?

??
???
? ? ? ? ? ? ? ?
??????????????????????

????

???

????????????????????

???
?

??
?

??
??????
??????????
?????????

? ?

??

???
???
??

???

???

????

???????

???

???

?
?

?????

????

???

???
?

???

?
??? ?
??????
???
??

??
?

?????
?

???

???

?????

?????

????
??
??

???
??

?
???

?
?

???

?? ?????

??

????
??
??

???

???

??
??
????
?????????????????????

???

???

???

??
?

??

?????

?????

??

???
??

??

???

?
?

??
??

???

??

???

????

???
???
??

???

????

??

???

???

?????????????
??????????
??????????????

???
??

???

????

???

???
?

???

??? ??
?

??

????

???

??
???

????

???

???????????????????????????

???
?? ???

???

????

??
???

???
??

????

????

???

????????????????????????????

?????

???
?

?????????????

?????

???

?????

???

???

???

???

?????

???
?

???
?

???

??????

???

??

?????? ?????? ??????

???

?????

??????

???

?????

????

??????
?????????????

???

???

?????

??????
???????

???

???
?

???
??

???

??

????

??????????

???

??

???
?

??
???
? ? ? ? ? ? ? ?
??????????????????????

???

???
???

????????????????
???????????????????????????

????????????????????????
???????????????
?????????????????????????
????????????????????????????

??? ???

???? ???? ???? ????

??? ??? ???

??????????????

???

???????
?
?

??

???

???? ???? ???? ????

???

??
?

???

?
?

???? ???? ???? ????

???

???

???
?????

???? ???? ???? ????

???

??
?

???

??
?

???

??
?

???

???

???????
?

??
?

???????
???????
??????

??
??

???????
????
??????

??
???
? ? ? ? ? ? ? ?
??????????????????????

????????? ?????????
???
???

?? ?? ?? ??

Fig. 39 Control Schematic, 30RB160-190


79

a30-4622

???

?????????
??????
?

???

???

???

??

??
????????????????????????
???????????????
?????????????????????????
????????????????????????????

???

???

???

???

???

???

???

???

?
?

???

???

???

???

???

???

?
?

???

???

?
????

???

??

???

???

???

???

???

?????

???
?

???

?
?

???

???

????
????

?????

??
??????????????
??????????

?
?

???

???

???
???
???

??

???

???

????

???

???

???

????

?????

??

??

???
???????

??
?

???
???

???

??
??

???

???

???

?????

???
?

????

?
?

???

?
???

???

???

???

???

????

????

????

?? ?? ??

???????
?????
????

?
?

???
???

???

???

???

???

???

???

?? ?? ?? ??

???

?
?
?
?
?
?

????

????

???

???

???

???

????

????

????

?? ?? ?? ??

???

??

???

??

??

???

???

???

???

???

???

?? ?? ?? ??

???

???

?????????????????

???

???

??

??

?????????????????

??

??

??

??

???
???
???

?
?

???

?
???

???

??

??

??

??

??

??

???

???
???
???

???

?
?

???

??

??

??

??

??

??

??

??

??

??

??

??

???

???
???
???
???
???
???

?
?

???
???
???

???????????
??????????????

???

??????? ?????????

?
?
?
?
?

?
?
?
?
?
?
?
?

?
?

???

??

??

??

??

??

???

??

??

??

??

??

??

???

????
???

???
???
???
???

???
???
????
????

???

???
???
?????
??????????????

???
??

??

???

???

?
?

??

???

?????

???

???

???

???

???

???????????
?????????
??????????????
??????????
??????????
??????????
??????????????
??????????
??????????
??????????
??????????????
??????????
??????????
??????????
??????????????
??????????
??????????
??????????
??????????
??????????
??????????
??????????

??
??
??
??
?

??

??
??

??
?

???

???? ???? ???? ????

???? ???? ???? ???? ????

??
?

??
??

???

?? ?? ??

?? ?? ?? ??

???
???

???

????????????
???

???

???

???????
??????
?????????

??

???

???

????????
?????
??????
?????????

???

???

???

???

??

???

?
?

???

???

???
???

?? ?? ?? ??

Fig. 40 Control Schematic, 30RB210-300

??
???

???
???

???

????????????

???

???

???????
??????
?????????

????????
?????
??????
?????????

???

?
?

?
?

?
?

80

???
???

? ?
???
???

???? ???? ????

?? ?? ?? ??

?????????????????
?????????????

???

???? ???? ???? ????

???

?????????????????
?????????????

???

???

???

???????
?????
????

???

?????????????????
?????????????

???

???

???

??

??????????????

?????????????????
?????????????

???

????????
???????
????????
???????

???

?? ?? ?? ??

???
???

?? ?? ??

??

?? ???????

??? ?
??????

???????
?????
????

???

???

?? ?? ??

?????????????????
?????????????

?????
????????????????????????????
?????????????????????????????????
?????????????????????????????

???

???
???

?
?

???

???????

?? ?? ??

??

????????????????????

??
??????
??????????
?????????

??????

???????????????????
??????????????????

???

??

??
??????
??????????
?????????

???????

??????

???

???

??
???
? ? ? ? ? ? ? ?
??????????????????????

??

??

???????????????????

???

???
???

??????

???

???

???????????????
??????????
?

?????????????
?????????????????

?
?

??
???
? ? ? ? ? ? ? ?
??????????????????????

??????????????????????
????????????????????
??????????????????????
?????????????????
??????????????

?????

???

???

?? ?? ??

?
?

? ?

?????

??????????
??????????
??????????
????????????
?????

????
???????????

?
???
?

???

??????

??

???

??

?????

???

???

?????

???
?

???????
????????
???

?????

???
?

???????
?????
????

????????????????????

???

??????
??????

??

?
?

??
?
???

???
??

?????

????

???
???
???
??

???
?

????

???

????

???

??? ?
??????

??

??

??
??????
??????????
?????????

?
?

??
???

???

??

???

???
???????

????
????

??

?????????

???

??
?

???
??

????

???

??

???
????

???? ???? ???? ????

???

???
?

???

??

?????

???
??

???

???????

??

???

???

???? ???? ???? ????

??

???
??

???
??

???

???????????

? ? ? ? ? ? ? ?
??????????????????????

???
?

???

???

???
??

???

????

???

???
??

?????

???
??

???

?????

???

??

?????

??

???

???

?? ?????

???

???

?????

???
?

??

??

?????

???

???

???

?????

?????

???
?

?
???

????
??
??
??

???

???
??

???

??

????
??
??

???
??

?
?

???

??
??
????
?????????????????????

???

?????

???

??
?

??

???

???

???

????

???

?????

?????????
????????

???
??

???

???

????

???
?????????????
??????????
??????????????

??????

???

?????? ?????? ??????

???
?

???

??

???
?

?
?

???

????
??????????
???????
???
????

????

???
?

???

??
???

????

??
???

???

???
??

???

???

???
???

???

???

???? ????

???

????

???
?

?????

???

?????????????
????????????????????????????

?????

???

???

???

???

????

???
?

???
?

???

??

????

???

???

?????

??

?????

??????
?????????????
???

??

???
???
???????

?
?

????

???

???????
?

??

??

???

??????

???

?????????????
???????????????????

???

???
?

???

??

??
?????

???
??

???

??????????

???

???

???
??????

??????
???????

???

???

??????
??? ???
??????
??? ???
????
????
??????????

???
?

???

???

???

?????

?? ? ??

???

???

???

???

??
???
? ? ? ? ? ? ? ?
??????????????????????

???
???

???

???

???

????????????????
???????????????????????????

???

???

???

???

???

???

???

???

???

???

???

???

???

?????????
?????
???

??

???

???? ????

???

??? ???

?
?

?
??? ??? ???

???????

???

???

???

???

???

??
?

??
?

???

??
?

???

???

??
?

???

??
?

???

?????

???

???
???

?
?

??
??

???

???
???
???????

??
??

???

??
??

???

???

??
??

???

???
???

??
???

???? ???? ???? ????

???

???? ???? ???? ????

???????
?

???? ???? ???? ????

???? ???? ???? ????

???

??
???
? ? ? ? ? ? ? ?
??????????????????????

?
?
?
?
?
?
?
?

???
?

?
???

??
?????
????
?????

?
?
?
?
?
?
?
?
?
??

???

???
???

? ?? ???
????????

???

? ?? ? ??

??????

??
??????
??? ??
?????? ??
??? ??????
???

???

??????????

???

?
???

???

??????????????

???????
???????
??????
???

???
????????????

???????
????
??????

a30-4622

???
?????????
??????????????

???

???

???

?????????
????????
?????
?????
??????
????????

???

??

?
?

???

??

??
?

????

???

???

???

????

????

???

??

???

??

???

??

???

??

????

??????

?????????????????????

??????

?????????????????????

????

??????

?????????????????????????????

?
?

????
?

???

????????????????????????????

??????

?????

????
?

??

???

???

???

????

??????????????
??????

???

?????

?????

?????

?????

?????

?????

?????

?????

?
?

??

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

???

??

??

??

??

?????

?????

?????

?????

?????

??

??

??

??

??

??

??

??

?????

??

?????

??

?????

??

??

?????

??

???

??

????
???

??????

??
??

?????

?????

????????

?
?

???

??
?

???
???

?????????????
????????????

???

??

???
???

???

??
?

??
?

??

??

???

???

???????

????????????
????????????
????????????
???

???

???

????

?????

???

????
??????

??
???

?????

???

???
???

???

???????

?????
??

??

???
???

???
???

?????
??

??

???

??

??

?????????
????????
???????
?????????????

???
?????

?????????
???????
???????
?????????????

???
???

???
??
????
????????

???
??

???

???????

?????
??

?????????
???????
???????????????

??

????????

???

?????????
???????
???????????????

???
???

?????
??

??

???
??

??

?????
??

??

???
???

???????
?????????
???????
?????????????

??

???

????????
?????????
???????
???????????????

???????
?????????
???????
?????????????

??

???
???

?????????
???????
?????????????

???

????????

??

???

?????

??????????????

??

??

???

???

?????? ??????????????

???

???????

?
??

????????
?????????
???????
???????????????

?????

???

???

????????
?????????
???????
???????????????
??

???

?????

??

???????
?????????
???????
?????????????

???
??

???
??

???
??

???
??

?????????????
?????????
????????
???????
???????????????

??????????

Fig. 41 Heat Reclaim Control Schematic


81

a30-4622

APPENDIX A LOCAL DISPLAY TABLES


MODE RUN STATUS
ITEM

EXPANSION

VIEW

AUTO VIEW OF RUN STATUS

EWT

Entering Fluid Temp

LWT

Leaving Fluid Temp

SETP

Active Setpoint

CTPT

Control Point

STAT

Unit Run Status

OCC
CTRL

Occupied
Status Unit Control Typ

CAP
CAP.S
LIM
STGE
ALRM

Percent Total Capacity


Capacity Indicator
Active Demand Limit Val
Current Stage
Alarm State

HC.ST

Heat Cool Status

RC.ST
TIME
MNTH

Reclaim Select Status


Time of Day
Month of Year

DATE
YEAR
R.CCN
CH.SS
HC.SL

Day of Month
Year of Century
CCN FOR PRODIALOG
CCN Chiller Start Stop
Heat Cool Select

C.OCC
RECL
SP.OC
D.LIM
CTRL

Chiller Occupied
Reclaim Select
Setpoint Occupied
Active Demand Limit Val
Control Point

EMGY
RUN
HRS.U
STR.U
HR.P1
HR.P2
HR.CD
HOUR
HR.A1
HR.A2
HR.A3
HR.A4
HR.B1
HR.B2
HR.B3
HR.B4
HR.C1
HR.C2
HR.C3
HR.C4
STRT
ST.A1
ST.A2
ST.A3
ST.A4
ST.B1
ST.B2
ST.B3
ST.B4
ST.C1
ST.C2
ST.C3
ST.C4

Emergency Stop
UNIT RUN HOUR AND START
Machine Operating Hours
Machine Starts
Water Pump 1 Run Hours
Water Pump 2 Run Hours
Heat Reclaim Pump Hours
COMPRESSOR RUN HOURS
Compressor A1 Run Hours
Compressor A2 Run Hours
Compressor A3 Run Hours
Compressor A4 Run Hours
Compressor B1 Run Hours
Compressor B2 Run Hours
Compressor B3 Run Hours
Compressor B4 Run Hours
Compressor C1 Run Hours
Compressor C2 Run Hours
Compressor C3 Run Hours
Compressor C4 Run Hours
COMPRESSOR STARTS
Compressor A1 Starts
Compressor A2 Starts
Compressor A3 Starts
Compressor A4 Starts
Compressor B1 Starts
Compressor B2 Starts
Compressor B3 Starts
Compressor B4 Starts
Compressor C1 Starts
Compressor C2 Starts
Compressor C3 Starts
Compressor C4 Starts

UNITS

XXXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)

XXX (%)
XX
XXX (%)
XX

XX.XX

XX
XX

STATEGEN

EWT

PAGE
NO.
3,33,
75
23

0-100

STATEGEN

LWT

23

0-100

GENUNIT

SP

0-100

GENUNIT

CTRL_PNT

23,44

0=Off
1=Running
2=Stopping
3=Delay
NO/YES
0=Local Off
1=Local On
2=CCN
3=Remote
0-100

GENUNIT

STATUS

32,33,
76

GENUNIT
GENUNIT

CHIL_OCC
ctr_type

32
32

GENUNIT

0-100

GENUNIT

0=Normal
1=Partial
2=Shutdown
0=Cooling
1=Heating
2=Standby
NO/YES
00.00-23.59
1=January
2=February
3=March
4-April
5=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December
1-31
00-99

GENUNIT

CAP_T
over_cap
DEM-LIM
cur_stag
ALM

GENUNIT

HEATCOOL

GENUNIT
N/A
N/A

reclaim_sel
TIME
moy

N/A
N/A

dom
yoc

RANGE

COMMENT

WRITE
STATUS

0-100

CCN TABLE

CCN POINT

ENBL/DSBL
0=Cool
1=Heat
2=Auto
NO/YES
NO/YES
NO/YES
0-100
0-100

forcible
forcible

GENUNIT
GENUNIT

CHIL_S_S
HC_SEL

forcible
forcible
forcible
forcible
forcible

GENUNIT
GENUNIT
GENUNIT
GENUNIT
GENUNIT

CHIL_OCC
RECL_SEL
SP_OCC
DEM_LIM
CTRL_PNT

ENBL/DSBL

forcible

GENUNIT

EMSTOP

XXXX (hours)
XXXX
XXXX (hours)
XXXX (hours)
XXXX (hours)

0-999000*
0-9999
0-999000*
0-999000*

forcible
forcible
forcible
forcible
forcible

STRTHOUR
FANHOURS
FANHOURS
FANHOURS

hr_mach
st_mach
hr_cpum1
hr_cpum2
hr_hpump

XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)

0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR

hr_cp_a1
hr_cp_a2
hr_cp_a3
hr_cp_a4
hr_cp_b1
hr_cp_b2
hr_cp_b3
hr_cp_b4
hr_cp_c1
hr_cp_c2
hr_cp_c3
hr_cp_c4

XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX

0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR
STRTHOUR

st_cp_a1
st_cp_a2
st_cp_a3
st_cp_a4
st_cp_b1
st_cp_b2
st_cp_b3
st_cp_b4
st_cp_c1
st_cp_c2
st_cp_c3
st_cp_c4

XXX (%)
XXX.X
(deg F/deg C)

82

22

23

68

32

49

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE RUN STATUS (cont)
ITEM
FAN
FR.A1
FR.A2
FR.A3
FR.A4
FR.A5
FR.A6
FR.B1
FR.B2
FR.B3
FR.B4
FR.B5
FR.B6
FR.C1
FR.C2
FR.C3
FR.C4
FR.C5
FR.C6
CP.UN
A1.UN
A2.UN
A3.UN
A4.UN
B1.UN
B2.UN
B3.UN
B4.UN
C1.UN
C2.UN
C3.UN
C4.UN
MAIN
CHRG
WATE
PMP.1
PMP.2
PMP.C
W.FIL
VERS

APPL
MARQ
NAVI
EXV1
EXV2
AUX1
AUX2
AUX3
AUX4
AUX5
CPA1
CPA2
CPA3
CPA4
CPB1
CPB2
CPB3
CPB4
CPC1
CPC2
CPC3
CPC4
EMM

EXPANSION
FAN RUN HOURS
Fan 1 Run Hours Cir A
Fan 2 Run Hours Cir A
Fan 3 Run Hours Cir A
Fan 4 Run Hours Cir A
Fan 5 Run Hours Cir A
Fan 6 Run Hours Cir A
Fan 1 Run Hours Cir B
Fan 2 Run Hours Cir B
Fan 3 Run Hours Cir B
Fan 4 Run Hours Cir B
Fan 5 Run Hours Cir B
Fan 6 Run Hours Cir B
Fan 1 Run Hours Cir C
Fan 2 Run Hours Cir C
Fan 3 Run Hours Cir C
Fan 4 Run Hours Cir C
Fan 5 Run Hours Cir C
Fan 6 Run Hours Cir C
COMPRESSOR DISABLE
Compressor A1 Disable
Compressor A2 Disable
Compressor A3 Disable
Compressor A4 Disable
Compressor B1 Disable
Compressor B2 Disable
Compressor B3 Disable
Compressor B4 Disable
Compressor C1 Disable
Compressor C2 Disable
Compressor C3 Disable
Compressor C4 Disable
PREDICTIVE MAINTENANCE
Refrigerant Charge
Water Loop Size
Pump 1 (days)
Pump 2 (days)
Cond Pump (days)
Water Filter (days)
SOFTWARE VERSION
NUMBER
CSA-XX-XXXXXXXXX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX
XXXXXX-XX-XX

UNITS
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)
XXXX (hours)

RANGE

COMMENT

WRITE
STATUS

CCN TABLE

CCN POINT

0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*
0-999000*

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS
FANHOURS

hr_fana1
hr_fana2
hr_fana3
hr_fana4
hr_fana5
hr_fana6
hr_fanb1
hr_fanb2
hr_fanb3
hr_fanb4
hr_fanb5
hr_fanb6
hr_fanc1
hr_fanc2
hr_fanc3
hr_fanc4
hr_fanc5
hr_fanc6

NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL
CP_UNABL

un_cp_a1
un_cp_a2
un_cp_a3
un_cp_a4
un_cp_b1
un_cp_b2
un_cp_b3
un_cp_b4
un_cp_c1
un_cp_c2
un_cp_c3
un_cp_c4

SERMAINT
SERMAINT
SERMAINT
SERMAINT
SERMAINT
SERMAINT

charge_m
wloop_m
cpump1_m
cpump2_m
hpump_m
wfilte_m

NO/YES
NO/YES
(days)
(days)
(days)
(days)
Press ENTER
and ESCAPE
simultaneously
to read version
information

*As data in all of these categories can exceed 9999 the following display strategy is used:
From 0-9999 display as 4 digits.
From 9999-99900 display xx.xK
From 99900-999000 display as xxxK.

83

PD5_APPL
STDU
Navigator
EXV_BRD1
EXV_BRD2
AUX_BRD1
AUX_BRD2
AUX_BRD3
AUX_BRD4
AUX_BRD5
SPM_CPA1
SPM_CPA2
SPM_CPA3
SPM_CPA4
SPM_CPB1
SPM_CPB2
SPM_CPB3
SPM_CPB4
SPM_CPC1
SPM_CPC2
SPM_CPC3
SPM_CPC4
EMM_NRCP

PAGE
NO.

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE SERVICE TEST
ITEM
TEST

T.REQ
CP.A1
CP.A2
CP.A3
CP.A4
HGB.A
CP.B1
CP.B2
CP.B3
CP.B4
HGB.B
CP.C1
CP.C2
CP.C3
CP.C4
HGB.C
QUIC
Q.REQ
EXV.A
EXV.B
EXV.C
FAN.A
FAN.B
FAN.C
SPD.A
SPD.B
SPD.C
FRV.A
FRP.A
FRV.B
FRP.B
FRV.C
FRP.C
RV.A
RV.B
BOIL
HR1.A
HR2.A
HR3.A
HR4.A
HR1.B
HR2.B
HR3.B
HR4.B
PMP.1
PMP.2
CND.P
CL.HT
CP.HT
CH.A1
CH.A2
CH.A3
CH.A4
CH.B1
CH.B2
CH.B3
CH.B4
CH.C1
CH.C2
CH.C3
CH.C4
HGB.A
HGB.B
HGB.C
Q.RDY
Q.RUN
SHUT
CATO
ALRM
ALRT
C.ALM

EXPANSION
COMPRESSORS
Manual Sequence
Compressor A1 Output
Compressor A2 Output
Compressor A3 Output
Compressor A4 Output
Hot Gas Bypass A Output
Compressor B1 Output
Compressor B2 Output
Compressor B3 Output
Compressor B4 Output
Hot Gas Bypass B Output
Compressor C1 Output
Compressor C2 Output
Compressor C3 Output
Compressor C4 Output
Hot Gas Bypass C Output
QUICK TEST MODE
Quick Test Mode
Circuit A EXV % Open
Circuit B EXV % Open
Circuit C EXV % Open
Circuit A Fan Stages
Circuit B Fan Stages
Circuit C Fan Stages
Circ A Varifan position
Circ B Varifan position
Circ C Varifan position
Free Cooling Valve A
Refrigerant Pump Out A
Free Cooling Valve B
Refrigerant Pump Out B
Free Cooling Valve C
Refrigerant Pump Out C
4 Way Valve Circuit A
4 Way Valve Circuit B
Boiler Command
Air Cond Enter Valve A
Air Cond Leaving Valv A
Water Cond Enter Valv A
Water Cond Leav Valve A
Air Cond Enter Valve B
Air Cond Leaving Valv B
Water Cond Enter Valv B
Water Cond Leav Valve B
Water Exchanger Pump 1
Water Exchanger Pump 2
Reclaim Condenser Pump
Cooler Heater Output
Condenser Heater Output
Compressor A1 Heater
Compressor A2 Heater
Compressor A3 Heater
Compressor A4 Heater
Compressor B1 Heater
Compressor B2 Heater
Compressor B3 Heater
Compressor B4 Heater
Compressor C1 Heater
Compressor C2 Heater
Compressor C3 Heater
Compressor C4 Heater
Hot Gas Bypass A Output
Hot Gas Bypass B Output
Hot Gas Bypass C Output
Chiller Ready Status
Chiller Running Status
Customer Shutdown Stat
Chiller Capacity 0-10v
Alarm Relay
Alert Relay
Critical Alarm Relay

UNITS

XXX (%)
XXX (%)
XXX (%)
X
X
X
XXX (%)
XXX (%)
XXX (%)

XX.X (vdc)

RANGE

COMMENT

WRITE
STATUS

OFF/ON*
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OFF/ON
0-100
0-100
0-100
0-6
0-6
0-6
0-100
0-100
0-100
OPEN/CLSE
OFF/ON
OPEN/CLSE
OFF/ON
OPEN/CLSE
OFF/ON
OPEN/CLSE
OPEN/CLSE
OFF/ON
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
0-100
OFF/ON
OFF/ON
OFF/ON

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.

EMM
EMM
EMM
Not supported.

CCN TABLE
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

CCN POINT
service_test
comp_serv_a_1
comp_serv_a_2
comp_serv_a_3
comp_serv_a_4
hgbp_serv_a
comp_serv_b_1
comp_serv_b_2
comp_serv_b_3
comp_serv_b_4
hgbp_serv_b
comp_serv_c_1
comp_serv_c_2
comp_serv_c_3
comp_serv_c_4
hgbp_serv_c
test_request
exv_qck_a
exv_qck_b
exv_qck_c
fan_qck_a
fan_qck_b
fan_qck_c
hd_qck_a
hd_qck_b
hd_qck_c
fr_qck_1a
fr_qck_2a
fr_qck_1b
fr_qck_2b
fr_qck_1c
fr_qck_2c
rv_qck_a
rv_qck_b
boiler_qck
hr_ea_qck_a
hr_la_qck_a
hr_ew_qck_a
hr_lw_qck_a
hr_ea_qck_b
hr_la_qck_b
hr_ew_qck_b
hr_lw_qck_b
cpump_qck1
cpump_qck2
cond_pump_qck
coo_heat_qck
cond_htr_qck
cp_ht_qck_a1
cp_ht_qck_a2
cp_ht_qck_a3
cp_ht_qck_a4
cp_ht_qck_b1
cp_ht_qck_b2
cp_ht_qck_b3
cp_ht_qck_b4
cp_ht_qck_c1
cp_ht_qck_c2
cp_ht_qck_c3
cp_ht_qck_c4

PAGE
NO.
51,74
51
51
51
51
51
51
51
51
51
51
51
51
51
75
50,51
50,51
50,51

ready_qck
running_qck
shutdown_qck
CAPT_010_qcK
alarm_qck
alert_qck
critical_qck

*Place the Enable/Off/Remote Contact switch to the Off position prior to configuring T.REQ to ON. Configure the desired item to ON, then
place the Enable/Off/Remote Contact switch to the Enable position.
Place the Enable/Off/Remote Contact switch to the Off position prior to configuring Q.REQ to ON. The switch should be in the Off position
to perform Quick Test.

84

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE TEMPERATURE
ITEM
UNIT

EXPANSION

EWT

ENT AND LEAVE UNIT TEMP


Water Exchanger Enter

LWT

Water Exchanger Leaving

OAT

Outside Air Temperature

CHWS

Lead/Lag Leaving Fluid

HEWT

Heat Reclaim Entering

HLWT

Heat Reclaim Leaving

SPT

Optional Space Temp

CIR.A
SCT.A

TEMPERATURES CIRCUIT A
Sat Cond Temp Circ A

SST.A

Sat Suction Temp Circ A

SGT.A

Suction Gas Temp Circ A

SUP.A
HRT.A

Superheat Temp Circ A


Sub Condenser Gas Tmp A

HRS.A
SCT.B

Sub Cooling Temp A


TEMPERATURES CIRCUIT B
Sat Cond Temp Circ B

SST.B

Sat Suction Temp Circ B

SGT.B

Suction Gas Temp Circ B

SUP.B
HRT.B

Superheat Temp Circ B


Sub Condenser Gas Tmp B

HRS.B
SCT.C

Sub Cooling Temp B


TEMPERATURES CIRCUIT C
Sat Cond Temp Circ C

SST.C

Sat Suction Temp Circ C

SGT.C

Suction Gas Temp Circ C

SUP.C

Superheat Temp Circ C

CIR.B

CIR.C

UNITS

RANGE

XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)

45-245 F
(43-118 C)
45-245 F
(43-118 C)
45-245 F
(43-118 C)
45-245 F
(43-118 C)

45-245 F
(43-118 C)

XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X (F/C)
XXX.X
(deg F/deg C)
XXX.X (F/C)

45-245 F
(43-118 C)
45-245 F
(43-118 C)
45-245 F
(43-118 C)

XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X (F/C)
XXX.X
(deg F/deg C)
XXX.X (F/C)

45-245 F
(43-118 C)
45-245 F
(43-118 C)
45-245 F
(43-118 C)

XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X (F/C)

45-245 F
(43-118 C)
45-245 F
(43-118 C)
45-245 F
(43-118 C)

COMMENT

WRITE
STATUS

CCN TABLE
STATEGEN

45-245 F
(43-118 C)

45-245 F
(43-118 C)

CCN POINT
EWT

PAGE
NO.
6,46

STATEGEN

LWT

6,46

GENUNIT

OAT

6,46

STATEGEN

CHWS TEMP

RECLAIM

HR_EWT

16,49

RECLAIM

HR_LWT

16,49

STATEGEN

SPACETMP

15

CIRCA_AN

SCT_A

CIRCA_AN

SST_A

CIRCA_AN

SUCT_T_A

CIRCA_AN
RECLAIM

SH_A
hr_subta

16

RECLAIM

hr_subca

16

CIRCB_AN

SCT_B

CIRCB_AN

SST_B

CIRCB_AN

SUCT_T_B

CIRCB_AN
RECLAIM

SH_B
hr_subtb

16

RECLAIM
CIRCC_AN
CIRCC_AN

hr_subcb

16

CIRCC_AN

SST_C

CIRCC_AN

SUCT_T_C

CIRCC_AN

SH_C

SCT_C

10

MODE PRESSURE
ITEM
PRC.A

EXPANSION

DP.A

PRESSURE CIRCUIT A
Discharge Pressure Cir A

SP.A

Suction Pressure Circ A

PD.A

Pumpdown Pressure Cir A

PRC.B
DP.B

PRESSURE CIRCUIT B
Discharge Pressure Cir B

SP.B

Suction Pressure Circ B

PD.B

Pumpdown Pressure Cir B

PRC.C
DP.C

PRESSURE CIRCUIT C
Discharge Pressure Cir C

SP.C

Suction Pressure Circ C

PD.C

Pumpdown Pressure Cir C

UNITS

RANGE

COMMENT

WRITE
STATUS

CCN TABLE

CCN POINT

PAGE
NO.

XXX.X
(psig/kPa)
XXX.X
(psig/kPa)
XXX.X
(psig/kPa)

CIRCA_AN

DP_A

6,48

CIRCA_AN

SP_A

RECLAIM

PD_P_A

16

XXX.X
(psig/kPa)
XXX.X
(psig/kPa)
XXX.X
(psig/kPa)

CIRCB_AN

DP_B

6,48

CIRCB_AN

SP_B

RECLAIM

PD_P_B

16

XXX.X
(psig/kPa)
XXX.X
(psig/kPa)
XXX.X
(psig/kPa)

CIRCC_AN

DP_C

14,48

CIRCC_AN

SP_C

14

RECLAIM

PD_P_C

85

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE SET POINTS
ITEM
COOL

EXPANSION

UNITS

CSP.1

COOLING SETPOINTS
Cooling Setpoint 1

CSP.2

Cooing Setpoint 2

XXXX.X
(deg F/deg C)

CSP.3

Ice Setpoint

XXXX.X
(deg F/deg C)

CRV1

Current No Reset Val

XX.X (mA)

CRV2

Current Full Reset Val

XX.X (mA)

CRT1

Delta T No Reset Temp

XXX.X (F/C)

CRT2

Delta T Full Reset Temp

XXX.X (F/C)

CRO1

OAT No Reset Temp

XXX.X
(deg F/deg C)

CRO2

OAT Full Reset Temp

XXX.X
(deg F/deg C)

CRS1

Space T No Reset Temp

XXX.X
(deg F/deg C)

CRS2

Space T Full Reset Temp

XXX.X
(deg F/deg C)

DGRC

Degrees Cool Reset

XX.X (F/C)

CAUT

Cool Changeover Setpt

CRMP

Cool Ramp Loading

XX.X
(deg F/deg C)
X.X

HEAT
HSP.1

HEATING SETPOINTS
Heating Setpoint 1

HSP.2

Heating Setpoint 2

HRV1
HRV2
HRT1
HRT2
HRO1

Current No Reset Val


Current Full Reset Val
Delta T No Reset Temp
Delta T Full Reset Temp
OAT No Reset Temp

HRO2

OAT Full Reset Temp

DGRH
HAUT

Degrees Heat Reset


Heat Changeover Setpt

HRMP
MISC
DLS1

Heat Ramp Loading


MISCELLANEOUS SETPOINTS
Switch Limit Setpoint 1
XXX (%)

DLS2

Switch Limit Setpoint 2

DLS3

Switch Limit Setpoint 3

XXX (%)

RSP

Heat Reclaim Setpoint

RDB

Reclaim Deadband

XXX.X
(deg F/deg C)
XX.X (F/C)

XXXX.X
(deg F/deg C)

XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XX.X (mA)
XX.X (mA)
XXX.X (F/C)
XXX.X (F/C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XX.X (F/C)
XX.X
(deg F/deg C)
X.X

XXX (%)

RANGE
20-70 F
(29-21 C),
Default = 44.0
20-70 F
(29-21 C),
Default = 44.0
20-70 F
(29-21 C),
Default = 44.0
0-20,
Default = 0
0-20,
Default = 0
0-125 F
(0-69.4 C),
Default = 0
0-125 F
(0-69.4 C),
Default = 0
0-125 F
(18-52 C),
Default = 14.0
0-25 F
(18-52 C),
Default = 14.0
0-125 F
(18-52 C),
Default = 14.0
0-125 F
(18-52 C),
Default = 14.0
30-30 F
(16.7-16.7 C),
Default = 0
Default = 75.0

COMMENT

Not supported.

0.2-2.0 F
(0.1-1.1 C),
Default = 1.0

WRITE
STATUS

CCN TABLE

CCN POINT

PAGE
NO.

forcible

SETPOINT

csp1

32,33,
44

forcible

SETPOINT

csp2

32,33

forcible

SETPOINT

ice_sp

32,33,
48

forcible

SETPOINT

v_cr_no

38

forcible

SETPOINT

v_cr_fu

38

forcible

SETPOINT

dt_cr_no

33

forcible

SETPOINT

dt_cr_fu

33

forcible

SETPOINT

oatcr_no

34

forcible

SETPOINT

oatcr_fu

34

forcible

SETPOINT

spacr_no

38

forcible

SETPOINT

spacr_fu

38

forcible

SETPOINT

cr_deg

33,34,
38

forcible

SETPOINT

cauto_sp

forcible

cramp_sp

17,23,
46

Default = 100

Not supported.

forcible

SETPOINT

HSP.1

Default = 100

Not supported.

forcible

SETPOINT

HSP.2

Default = 0
Default = 0
Default = 0
Default = 0
Default = 14.0

Not supported.
Not supported.
Not supported.
Not supported.
Not supported.

forcible
forcible
forcible
forcible
forcible

SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT

v_hr_no
v_hr_fu
dt_hr_no
dt_hr_fu
oathr_no

Default = 14.0

Not supported.

forcible

SETPOINT

oathr_fu

Default = 0
Default = 64

Not supported.
Not supported.

forcible
forcible

SETPOINT
SETPOINT

DGRH
hauto_sp

Default = 1.0

Not supported.

forcible

SETPOINT

hramp_sp

0-100,
Default = 100
0-100,
Default = 100
0-100,
Default = 100
Default = 122

forcible

SETPOINT

lim_sp1

41

forcible

SETPOINT

lim_sp2

41

forcible

SETPOINT

lim_sp3

forcible

SETPOINT

rsp

49

Default = 9.0

forcible

SETPOINT

hr_deadb

49

MODE INPUTS
ITEM
GEN.I
ONOF
LOCK
DLS1
DLS2
ICE.D
DUAL
ELEC
PUMP
OCCS
RECL
HC.SW
RLOC
C.FLO
DMND
RSET

EXPANSION
GENERAL INPUTS
On Off Switch
Cooler Interlock
Demand Limit Switch 1
Demand Limit Switch 2
Ice Done
Dual Setpoint Switch
Electrical Box Safety
Pump Run Feedback
Occupancy Override Swit
Heat Reclaim Switch
Heat Cool Switch Status
Remote Interlock Switch
Reclaim Cond Flow
4-20 mA Demand Signal
4-20 mA Reset/Setpoint

UNITS

RANGE

XXX.X (mA)
XXX.X (mA)

OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OFF/ON
OFF/ON
OPEN/CLSE
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OPEN/CLSE
OPEN/CLSE
4 to 20
4 to 20

86

COMMENT

WRITE
STATUS

CCN TABLE
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN

CCN POINT
ONOF
LOCK_1
LIM_SW1
LIM_SW2
ICE_SW
SETP_SW
ELEC_BOX
PUMP_DEF
OCC_OVSW
RECL_SW
HC_SW
REM-LOCK
CONDFLOW
LIM_ANAL
SP_RESET

PAGE
NO.
6
6,23
6
15
15,32
6
6
6
15
49
15
16
15
15

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE OUTPUTS
ITEM
CIR.A

CP.A1
CP.A2
CP.A3
CP.A4
HGB.A
HT.A1
HT.A2
HT.A3
HT.A4
FAN.A
SPD.A
EXV.A
FRP.A
FRVA
HR1.A
HR2.A
HR3.A
HR4.A
RV.A
CIR.B
CP.B1
CP.B2
CP.B3
CP.B4
HGB.B
HT.B1
HT.B2
HT.B3
HT.B4
FAN.B
SPD.B
EXV.B
FRP.B
FRVB
HR1.B
HR2.B
HR3.B
HR4.B
RV.B
CIR.C
CP.C1
CP.C2
CP.C3
CP.C4
HGB.C
HT.C1
HT.C2
HT.C3
HT.C4
FAN.C
SPD.C
EXV.C
FRP.C
FRVC
GEN.O
PMP.1
PMP.2
CND.P
CO.HT
CN.HT
REDY
RUN
SHUT
CATO
ALRM
ALRT
BOIL
C.ALM

EXPANSION
OUTPUTS CIRCUIT A
Compressor A1 Relay
Compressor A2 Relay
Compressor A3 Relay
Compressor A4 Relay
Hot Gas Bypass Circ A
Comp A1 Heater Relay
Comp A2 Heater Relay
Comp A3 Heater Relay
Comp A4 Heater Relay
Circuit A Fan Stages
Circ A Varifan Position
Circuit A EXV % Open
Refrigerant Pump Out A
Free Cooling Valve A
Air Cond Enter Valve A
Air Cond Leaving Valv A
Water Cond Enter Valv A
Water Cond Leav Valve A
4 Way Valve Circuit A
OUTPUTS CIRCUIT B
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Compressor B4 Relay
Hot Gas Bypass Circ B
Comp B1 Heater Relay
Comp B2 Heater Relay
Comp B3 Heater Relay
Comp B4 Heater Relay
Circuit B Fan Stages
Circ B Varifan Position
Circuit B EXV % Open
Refrigerant Pump Out B
Free Cooling Valve B
Air Cond Enter Valve B
Air Cond Leaving Valv B
Water Cond Enter Valv B
Water Cond Leav Valve B
4 Way Valve Circuit B
OUTPUTS CIRCUIT C
Compressor C1 Relay
Compressor C2 Relay
Compressor C3 Relay
Compressor C4 Relay
Hot Gas Bypass Circ C
Comp C1 Heater Relay
Comp C2 Heater Relay
Comp C3 Heater Relay
Comp C4 Heater Relay
Circuit C Fan Stages
Circ C Varifan Position
Circuit C EXV % Open
Refrigerant Pump Out C
Free Cooling Valve C
GENERAL OUTPUTS
Water Exchanger Pump 1
Water Exchanger Pump 2
Reclaim Condenser Pump
Cooler Heater Output
Condenser Heater Output
Chiller Ready Status
Chiller Running Status
Customer Shutdown Stat
Chiller Capacity 0-10 v
Alarm Relay
Alert Relay
Boiler Command
Critical Alarm Relay

UNITS
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
X
XXX (%)
XXX (%)
OFF/ON
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
X
XXX (%)
XXX (%)
OFF/ON
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
X
XXX (%)
XXX (%)
OFF/ON
OPEN/CLSE

RANGE

COMMENT

WRITE
STATUS

PAGE
NO.

CP_A1
CP_A2
CP_A3
CP_A4
HGBP_A
cp_a1_ht
cp_a2_ht
cp_a3_ht
cp_a4_ht
FAN_ST_A
hd_pos_a
EXV_A
FR_PMP_A
FR_VLV_A
hr_ca_a
hr_la_a
hr_en_a
hr_lw_a
RV_A

Not supported.

CIRCB_D
CIRCB_D
CIRCB_D
CIRCB_D
CIRCB_D
CIRCB_D
CIRCB_D
CIRCB_D
CIRCB_D
CIRCB_D
CIRCB_AN
CIRCB_AN
CIRCB_D
CIRCA_D
RECLAIM
RECLAIM
RECLAIM
RECLAIM
CIRCB_D

CP_B1
CP_B2
CP_B3
CP_B4
HGBP_B
CP_HT_B1
CP_HT_B2
CP_HT_B3
CP_HT_B4
FAN_ST_B
hd_pos_b
EXV_B
FR_PMP_B
FR_VLV_B
hr_ca_b
hr_la_b
hr_en_b
hr_lw_b
RV_B
CP_C1
CP_C2
CP_C3
CP_C4
HGBP_C
cp_c1_ht
cp_c2_ht
cp_c3_ht
cp_c4_ht
FAN_ST_C
hd_pos_c
EXV_C
FR_PMP_ C
FR_VLV_C

8
8
8
8
14
8
8
8
8

Not supported.
Not supported.

CIRCC_D
CIRCC_D
CIRCC_D
CIRCC_D
CIRCC_D
CIRCC_D
CIRCC_D
CIRCC_D
CIRCC_D
CIRCC_D
CIRCC_AN
CIRCC_AN
CIRCC_D
CIRCC_D
STATEGEN
STATEGEN
STATEGEN
STATEGEN
RECLAIM
RECLAIM
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN
STATEGEN

CPUMP_1
CPUMP_2
COND_PUMP
COOLHEAT
cond_htr
READY
RUNNING
SHUTDOWN
CAPT_010
ALARM
ALERT
BOILER
critical_qck

6
6
16
6
16
6
15
15
15
6
6

Not supported.
Not supported.

Not supported.

0-6
0-100
0-100
Not supported.
Not supported.

0-6
0-100
0-100

forcible
forcible
forcible
forcible
Not supported.
forcible

87

CCN POINT

CIRCA_D
CIRCA_D
CIRCA_D
CIRCA_D
CIRCA_D
CIRCA_D
CIRCA_D
CIRCA_D
CIRCA_D
CIRCA_D
CIRCA_AN
CIRCA_AN
CIRCA_D
CIRCA_D
RECLAIM
RECLAIM
RECLAIM
RECLAIM
CIRCA_D

0-6
0-100
0-100

OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
XX.X
OFF/ON
OFF/ON
OFF/ON
OFF/ON

CCN TABLE

8
8
8
8
6
8
8
8
8
11
8
16
16
16
16

8
8
8
8
6
8
8
8
8
11,12
8
16
16
16
16

14
10

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE CONFIGURATION
ITEM

EXPANSION

DISP
TEST
METR
LANG

DISPLAY CONFIGURATION
Test Display LEDs
Metric Display
Language Selection

UNIT
TYPE

UNIT CONFIGURATION
Unit Type

TONS

Unit Size

UNITS

RANGE
OFF/ON
US/METR
0=English
1=Espanol
2=Francais
3=Portugues
4=Translated
1=Air Cooled
2=Heat Pump

VAR.A Nb Fan on Varifan Cir A

56 to 300
(nominal size
refer to Table 1 for
unit modular
combinations)
0-6

VAR.B Nb Fan on Varifan Cir B

0-6

VAR.C Nb Fan on Varifan Cir C

0-6

HGBP

Hot Gas Bypass Control

60HZ
RECL
EHS
EMM
PAS.E

60 Hz Frequency
Heat Reclaim Select
Electrical Heater Stage
EMM Module Installed
Password Enable
Password Protection Must Be
Disabled to Change Password
Password
Free Cooling Select
Pro_Dialog User Display

PASS
FREE
PD4.D
BOIL
VLT.S
RPM.F
MCHX
SERV
FLUD

Boiler Command Select


VLT Fan Drive Select
VLT Fan Drive RPM
MCHX Exchanger Select
SERVICE CONFIGURATION
Cooler Fluid Type

MOP

EXV MOP Setpoint

HP.TH

High Pressure Threshold

SHP.A

Cir A Superheat Setp

SHP.B

Cir B Superheat Setp

SHP.C

Cir C Superheat Setp

HTR

Cooler Heater DT Setp

EWTO
AU.SM
BOTH
LLWT
LOSP

Entering Water Control


Auto Start When SM Lost
HSM Both Command Select
Brine Min. Fluid Temp.
Brine Freeze Setpoint

HD.PG
HD.DG
HD.IG
HR.MI
HR.MA
AVFA
AVFB
AVFC

Varifan Proportion Gain


Varifan Derivative Gain
Varifan Integral Gain
Reclaim Water Valve Min
Reclaim Water Valve Max
Attach Drive to Fan A
Attach Drive to Fan B
Attach Drive to Fan C

COMMENT

XXX (tons)

0=Unused
1=Startup Only
2=Close Ctrl
3=High Ambient
NO/YES
NO/YES
0-4
NO/YES
DSBL/ENBL
XXX

XXXX

1 to 0150
NO/YES
NO/YES
OFF/ON
NO/YES
0 to 1200
NO/YES
1=Water
2=Brine
3=Low Brine

Heat pump not


supported

1 is default for
med. temp.
brine units
(FLUD=2)
Not supported

Not supported.
Must be set to
NO
Not supported.
Not supported.
Not supported.

Low Brine is
not supported.

XX.X
40-60 F
(deg F/deg C)
(4.4-15.6 C)
XXX.X (psi/kPa) 500-640 psi
(3447 to
4412 kPa)
XX.X (F/C)
3-14 F
(1.7-7.8 C)
XX.X (F/C)
3-14 F
(1.7-7.8 C)
XX.X (F/C)
3-14 F
(1.7-7.8 C)
XX.X (F/C)
0.5-9 F
(0.3-5.0 C)

XX
XX.X
(deg F/deg C)
XX.X
XX.X
XX.X
XXX.X (%)
XXX.X (%)

NO/YES
NO/YES
NO/YES
20-38 F
4-50 F
(20-10 C)
10-10
10-10
10-10
NO/YES
NO/YES
NO/YES

Not supported.
Not supported.
Not supported.

88

WRITE
STATUS

DEFAULT

CCN
TABLE

CCN
POINT

OFF
US
0

N/A
display_test
DISPCONF DISPUNIT
DISPCONF LANGUAGE

FACTORY

unit_typ

FACTORY

unitsize

FACTORY

varfan_a

FACTORY

varfan_b

PAGE
NO.

66

0: No low ambient
temperature head
pressure control
1:low ambient
temperature head
pressure control
0: No low ambient
temperature head
pressure control
1: low ambient
temperature head
pressure control
0: No low ambient
temperature head
pressure control
1: low ambient
temperature head
pressure control
0

FACTORY

varfan_c

FACTORY

hgbp_sel

YES
NO
0
NO
ENBL

FACTORY
FACTORY
FACTORY
FACTORY
FACTORY

freq_60H
recl_opt
ehs_sel
emm_nrcp
pass_enb

0111
NO
NO

FACTORY
FACTORY
FACTORY

fac_pass
freecool
pd4_disp

OFF
NO
0
NO

FACTORY
FACTORY
FACTORY
FACTORY

boil_sel
Vh_sel
Vh_rpm
mchx_sel

SERVICE1

flui_typ

50

SERVICE1

mop_sp

17,
22-24
33,66,
67,69
67

609

SERVICE1

hp_th

23,48

9.0

SERVICE1

sh_sp_a

67,69

9.0

SERVICE1

sh_sp_b

67,69

9.0

SERVICE1

sh_sp_c

67,69

2.0
(Number of
degrees added to
brine freeze set
point to enable
cooler heater.)
NO
NO
NO

SERVICE1

heatersp

51

ewt_opt
auto_sm
both_sel
Mini_Lwt
lowestsp

33
68

34.0

SERVICE1
SERVICE1
USER
USER
SERVICE1

2.0
0.4
0.2
20
100
NO
NO
NO

SERVICE1
SERVICE1
SERVICE1
SERVICE1
SERVICE1
SERVICE3
SERVICE3
SERVICE3

hd_pg
hd_dg
hd_ig
min_3w
max_3w
set_drva
set_drvb
set_drvc

17,
20-23

49
65

23,24,
33,51,
66,69

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE CONFIGURATION (cont)
ITEM

EXPANSION

UNITS

OPTN
CCNA
CCNB
BAUD

UNIT OPTIONS 2 CONTROLS


CCN Address
CCN Bus Number
CCN Baud Rate

LOAD

Loading Sequence Select

LLCS

Lead/Lag Circuit Select

RL.S
DELY

Ramp Load Select


Minutes Off Time

ICE.M
PUMP

Ice Mode Enable


Cooler Pumps Sequence

ROT.P
PM.PS
P.SBY
P.LOC
LS.ST
LS.ND
LS.LT
OA.TH

Pump Rotation Delay


Periodic Pump Start
Stop Pump In Standby
Flow Checked if Pmp Off
Night Low Noise Start
Night Low Noise End
Low Noise Capacity Lim
Heat Mode OAT Threshold

FREE

Free Cooling OAT Limit

BO.TH

Boiler OAT Threshold

EHST

Elec Stag OAT Threshold

EHSB
E.DEF
EHSP
AUTO
RSET
CRST

Last Heat Elec Backup


Quick EHS in Defrost
Elec Heating Pulldown
XX (min)
Auto Changeover Select
RESET, COOL AND HEAT TEMP
Cooling Reset Type

HRST

Heating Reset Type

DMDC

Demand Limit Select

DMMX
DMZE
MSSL

mA for 100% Demand Lim


mA for 0% Demand Limit
Master/Slave Select

XX.X (mA)
XX.X (mA)

SLVA
LLBL

Slave Address
Lead/Lag Balance Select

XXX

LLBD

Lead/Lag Balance Delta

LLDY
LAGP

Lag Start Delay


Lag Unit Pump Select

LPUL

Lead Pulldown Time

XX (minutes)

XXX
XXX

XX (Minutes)

XXXX (hours)

XX.XX
XX.XX
XXX (%)
XX.X
(deg F/deg C)
XX.X
(deg F/deg C)
XX.X
(deg F/deg C)
XX.XX
(deg F/deg C)

RANGE

COMMENT

DEFAULT

CCN TABLE

CCN POINT

1-239
0-239
1=2400
2=4800
3=9600
4=19200
5=38400
0=Equal
1=Staged
0=Automatic
1=Cir A Leads
2=Cir B Leads
3=Cir C Leads
ENBL/DSBL
1 to 15

1
0
3

N/A
N/A
N/A

USER

lead_cir

20

USER

seq_typ

20,21

DSBL
1

USER
USER

ramp_sel
off_on_d

ENBL/DSBL
0=No Pump
1=1 Pump Only
2=2 Pumps Auto
3=PMP 1 Manual
4=PMP 2 Manual
24 to 3000
NO-YES
NO-YES
NO-YES
00.00-23.59
00-00-23.59
0-100

DSBL
0

USER
USER

ice_cnfg
pump_seq

17,23,
17,31,
68
32,33
31,44

48
NO
NO
YES
00.00
00.00
100
5F

USER
USER
USER
USER
USER
USER
USER
USER

pump_del
pump_per
pump_sby
pump_loc
nh_start
nh_end
nh_limit
heat_th

Not supported.

5-32 F
(15-0 C)
23 -70 F
(5-21 C)
NO-YES
NO-YES
NO-YES
0=No Reset
1=Out Air Temp
2=Delta T Temp
3=4-20 mA Input
4=Space Temp
0=No Reset
1=Out Air Temp
2=Delta T Temp
3=4-20 mA Input
0=None
1=Switch
2=4-20 mA Input

CCNA
CCNB
BAUD

PAGE
NO.

47
32
32

Not supported.

32.0

USER

free_oat

Not supported.

14

USER

boil_th

Not supported.

41

USER

ehs_th

Not supported.
Not supported.
Not supported.
Not supported.

NO
NO
0
NO

USER
USER
USER
USER

ehs_back
ehs_defr
ehs_pull
auto_sel

USER

cr_sel

USER

hr_sel

USER

lim_sel

41
41
41
46,66,
68

Not supported.

0=Disable
1=Master
2=Slave
1-236
ENBL/DSBL

0.0
0.0
0

USER
USER
MST_SLV

lim_mx
lim_ze
ms_sel

2
DSBL

MST_SLV
MST_SLV

slv_addr
ll_bal

XXX (hours)

40-400

168

MST_SLV

ll_bal_d

XX (minutes)

2-30
0=Off if Unit
stopped
1=On if Unit
stopped
0-60

10
0

MST_SLV
MST_SLV

lsrt_tim
lag_pump

MST_SLV

lead_pul

89

46
46

33,34,
38,46

17,45,
46
17,45,
46
17,45
17,20,
45
17,45

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE TIMECLOCK
ITEM
TIME

EXPANSION

UNITS

DATE
MNTH

TIME OF DAY
Hour and Minute
XX.XX
MONTH DATE DAY AND YEAR
Month of Year

DOM
DAY

Day of Month
Day of Week

XX

YEAR
SCH1
PER.1
PER.1OCC.1
PER.1UNO.1
PER.1MON.1
PER.1TUE.1
PER.1WED.1
PER.1THU.1
PER.1FRI.1
PER.1SAT.1
PER.1SUN.1
PER.1HOL.1
PER.2
PER.2OCC.2
PER.2UNO.2
PER.2MON.2
PER.2TUE.2
PER.2WED.2
PER.2THU.2
PER.2FRI.2
PER.2SAT.2
PER.2SUN.2
PER.2HOL.2
PER.3
PER.3OCC.3
PER.3UNO.3
PER.3MON.3
PER.3TUE.3
PER.3WED.3
PER.3THU.3
PER.3FRI.3
PER.3SAT.3
PER.3SUN.3
PER.3HOL.3
PER.4
PER.4OCC.4
PER.4UNO.4
PER.4MON.4
PER.4TUE.4
PER.4WED.4
PER.4THU.4
PER.4FRI.4
PER.4SAT.4
PER.4SUN.4
PER.4HOL.4
PER.5
PER.5OCC.5
PER.5UNO.5
PER.5MON.5
PER.5TUE.5
PER.5WED.5
PER.5THU.5
PER.5FRI.5
PER.5SAT.5
PER.5SUN.5
PER.5HOL.5
PER.6
PER.6OCC.6
PER.6UNO.6
PER.6MON.6
PER.6TUE.6
PER.6WED.6
PER.6THU.6
PER.6FRI.6
PER.6SAT.6
PER.6SUN.6
PER.6HOL.6

Year of Century
TIME SCHEDULE 1
Period 1 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 2 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 3 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 4 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 5 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 6 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select

XX

HH.MM

RANGE

COMMENT

WRITE
STATUS

CCN TABLE

CCN POINT

00.00-23.59

forcible*

N/A

HH.MM

1=January
2=February
3=March
4=April
5=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December
1-31
1=Monday
2=Tuesday
3=Wednesday
4=Thursday
5=Friday
6=Saturday
7=Sunday
00-99

forcible*

N/A

MNTH

forcible*
forcible*

N/A
N/A

DOM
DAY

forcible*

N/A

YEAR

PAGE
NO.

32,33
XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCCTOD1
UNOCTOD1
DOW1
DOW1
DOW1
DOW1
DOW1
DOW1
DOW1
DOW1

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S

OCCTOD4
UNOCTOD4
DOW4
DOW4
DOW4
DOW4
DOW4
DOW4
DOW4
DOW4

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S

OCCTOD5
UNOCTOD5
DOW5
DOW5
DOW5
DOW5
DOW5
DOW5
DOW5
DOW5

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S
OCC1P01S

OCCTOD6
UNOCTOD6
DOW6
DOW6
DOW6
DOW6
DOW6
DOW6
DOW6
DOW6

*Password protected.

90

OCCTOD2
UNOCTOD2
DOW2
DOW2
DOW2
DOW2
DOW2
DOW2
DOW2
DOW2
OCCTOD3
UNOCTOD3
DOW3
DOW3
DOW3
DOW3
DOW3
DOW3
DOW3
DOW3

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE TIMECLOCK (cont)
ITEM
SCH1

PER.7
PER.7OCC.7
PER.7UNO.7
PER.7MON.7
PER.7TUE.7
PER.7WED.7
PER.7THU.7
PER.7FRI.7
PER.7SAT.7
PER.7SUN.7
PER.7HOL.7
PER.8
PER.8OCC.8
PER.8UNO.8
PER.8MON.8
PER.8TUE.8
PER.8WED.8
PER.8THU.8
PER.8FRI.8
PER.8SAT.8
PER.8SUN.8
PER.8HOL.8
SCH2

PER.1
PER.1OCC.1
PER.1UNO.1
PER.1MON.1
PER.1TUE.1
PER.1WED.1
PER.1THU.1
PER.1FRI.1
PER.1SAT.1
PER.1SUN.1
PER.1HOL.1
PER.2
PER.2OCC.2
PER.2UNO.2
PER.2MON.2
PER.2TUE.2
PER.2WED.2
PER.2THU.2
PER.2FRI.2
PER.2SAT.2
PER.2SUN.2
PER.2HOL.2
PER.3
PER.3OCC.3
PER.3UNO.3
PER.3MON.3
PER.3TUE.3
PER.3WED.3
PER.3THU.3
PER.3FRI.3
PER.3SAT.3
PER.3SUN.3
PER.3HOL.3
PER.4
PER.4OCC.4
PER.4UNO.4
PER.4MON.4
PER.4TUE.4
PER.4WED.4
PER.4THU.4
PER.4FRI.4
PER.4SAT.4
PER.4SUN.4
PER.4HOL.4
PER.5
PER.5OCC.5
PER.5UNO.5
PER.5MON.5
PER.5TUE.5
PER.5WED.5
PER.5THU.5
PER.5FRI.5
PER.5SAT.5
PER.5SUN.5
PER.5HOL.5
PER.6
PER.6OCC.6
PER.6UNO.6
PER.6MON.6
PER.6TUE.6
PER.6WED.6
PER.6THU.6
PER.6FRI.6
PER.6SAT.6
PER.6SUN.6
PER.6HOL.6

EXPANSION
TIME SCHEDULE 1
Period 7 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 8 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
TIME SCHEDULE 2
Period 1 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 2 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 3 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 4 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 5 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 6 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select

UNITS

RANGE

COMMENT

WRITE
STATUS

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

XX.XX
XX.XX

CCN TABLE

CCN POINT

OCCTOD7
UNOCTOD7
DOW7
DOW7
DOW7
DOW7
DOW7
DOW7
DOW7
DOW7

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S
OCCP01S

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S

OCCTOD1
UNOCTOD1
DOW1
DOW1
DOW1
DOW1
DOW1
DOW1
DOW1
DOW1

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S

OCCTOD
UNOCTOD2
DOW2
DOW2
DOW2
DOW2
DOW2
DOW2
DOW2
DOW2

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S

OCCTOD
UNOCTOD3
DOW3
DOW3
DOW3
DOW3
DOW3
DOW3
DOW3
DOW3

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S

OCCTOD4
UNOCTOD4
DOW4
DOW4
DOW4
DOW4
DOW4
DOW4
DOW4
DOW4

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S

OCCTOD5
UNOCTOD5
DOW5
DOW5
DOW5
DOW5
DOW5
DOW5
DOW5
DOW5

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S
OCC2P02S

OCCTOD6
UNOCTOD6
DOW6
DOW6
DOW6
DOW6
DOW6
DOW6
DOW6
DOW6

PAGE
NO.

OCCTOD8
UNOCTOD8
DOW8
DOW8
DOW8
DOW8
DOW8
DOW8
DOW8
DOW8
32,33

91

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE TIMECLOCK (cont)
ITEM

PER.7
PER.7OCC.7
PER.7UNO.7
PER.7MON.7
PER.7TUE.7
PER.7WED.7
PER.7THU.7
PER.7FRI.7
PER.7SAT.7
PER.7SUN.7
PER.7HOL.7
PER.8
PER.8OCC.8
PER.8UNO.8
PER.8MON.8
PER.8TUE.8
PER.8WED.8
PER.8THU.8
PER.8FRI.8
PER.8SAT.8
PER.8SUN.8
PER.8HOL.8

EXPANSION

HOL.1
HOL.1MON.1

Period 7 Occ/Unocc Sel


Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
Period 8 Occ/Unocc Sel
Occupied Time
Unoccupied Time
Monday Select
Tuesday Select
Wednesday Select
Thursday Select
Friday Select
Saturday Select
Sunday Select
Holiday Select
HOLIDAYS CONFIGURATION
Holidays Config 1
Holiday Start Month

HOL.1DAY.1
HOL.1DUR.1
HOL.1HOL.2
HOL.1MON.2

Holiday Start Day


Holiday Duration in Day
Holidays Config 2
Holiday Start Month

HOL.2DAY.2

Holiday Start Day

HOL.2DUR.2

Holiday Duration in Day

HOL.9
HOL.9MON.9

Holidays Config 9
Holiday Start Month

HOL.9DAY.9

Holiday Start Day

HOL.9DUR.9

Holiday Duration in Days

HOLI

UNITS

Holiday Start Day

HOL.10DU.10

Holiday Duration in Days

COMMENT

WRITE
PAGE
CCN TABLE CCN POINT
STATUS
NO.

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

XX.XX
XX.XX

00.00-23.59
00.00-23.59
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES

forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

1=January
2=February
3=March
4=April
5=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December
1 to 31
1 to 99

forcible

HOLDY_01

HOL_MON

forcible
forcible

HOLDY_01
HOLDY_01

HOL_DAY
HOL_LEN

See
HOL.1MON.1
See
HOL.1DAY.1
See
HOL.1DUR.1

forcible

HOLDY_02

HOL_MON

forcible

HOLDY_02

HOL_DAY

forcible

HOLDY_02

HOL_LEN

See
HOL.1MON.1
See
HOL.1DAY.1
See
HOL.1DUR.1

forcible

HOLDY_09

HOL_MON

forcible

HOLDY_09

HOL_DAY

forcible

HOLDY_09

HOL_LEN

See
HOL.1MON.1
See
HOL.1DAY.1
See
HOL.1DUR.1

forcible

HOLDY_09

forcible

HOLDY_09

forcible

HOLDY_09

See
HOL.1MON.1
See
HOL.1DAY.1
See
HOL.1DUR.1

forcible

HOLDY_16

NO/YES
NO/YES
NO/YES
0-65,500
0-65,500
0-65,500

forcible*
forcible*
forcible*
forcible
forcible
forcible
forcible
forcible

XX
XX

HOL.10HO.10 Holidays Config 10


HOL.10MO.10 Holiday Start Month
HOL.10DA.10

RANGE

HOL.16HO.16 Holidays Config 16


HOL.16MO.16 Holiday Start Month
HOL.16DA.16

Holiday Start Day

HOL.16DU.16

Holiday Duration in Days

MCFG
AL.SV
CHRG
WATE
PMP.1
PMP.2
PMP.C
W.FIL
RS.SV

SERVICE MAINTENANCE CONFIG


Service Warning Select
Refrigerant Charge
Water Loop Size
Pump 1 (days)
XXXX (days)
Pump 2 (days)
XXXX (days)
Cond Pump (days)
XXXX (days)
Water Filter (days)
XXXX (days)
Servicing Alert Reset

OCC2P02S

OCCTOD7
UNOCTOD7
DOW7
DOW7
DOW7
DOW7
DOW7
DOW7
DOW7
DOW7
OCCTOD8
UNOCTOD8
DOW8
DOW8
DOW8
DOW8
DOW8
DOW8
DOW8
DOW8

forcible
forcible
70

0=Default
1=Refrigerant Charge
2=Water loop size
3=Not used
4=Pump 1
5=Pump 2
6=Reclaim Pump (not used)
7=Water filter
8=Reset all

*Default=NO.
Default=0.

92

MAINTCFG
MAINTCFG
MAINTCFG
MAINTCFG
MAINTCFG
MAINTCFG
MAINTCFG
SERMAINT

s_alert
charge_a
wloop_c
pump1_c
pump2_c
hpump_c
wfilte_c
s_reset

43
70

APPENDIX A LOCAL DISPLAY TABLES (cont)


MODE OPERATING MODES
ITEM
SLCT

EXPANSION

OPER

OPERATING TYPE CONTROL


Operating Control Type

SP.SE

Setpoint Select

HC.SE

Heat Cool Select

RL.SE

Reclaim Select

MODE

MODES CONTROLLING UNIT


Startup Delay in Effect
Second Setpoint in Use
Reset in Effect
Demand Limit Active
Ramp Loading Active
Cooler Heater Active
Water Pumps Rotation
Pump Periodic Start
Night Low Noise Active
System Manager Active
Mast Slave Ctrl Active
Auto Changeover Active
Free Cooling Active
Reclaim Active
Electric Heat Active
Heating Low EWT Lockout
Boiler Active
Ice Mode in Effect
Defrost Active on Cir A
Defrost Active on Cir B
Low Suction Circuit A
Low Suction Circuit B
Low Suction Circuit C
High DGT Circuit A
High DGT Circuit B
High DGT Circuit C
High Pres Override Cir A
High Pres Override Cir B
High Pres OVerride Cir C
Low Superheat Circuit A
Low Superheat Circuit B
Low Superheat Circuit C

MD01
MD02
MD03
MD04
MD05
MD06
MD07
MD08
MD09
MD10
MD11
MD12
MD13
MD14
MD15
MD16
MD17
MD18
MD19
MD20
MD21
MD22
MD23
MD24
MD25
MD26
MD27
MD28
MD29
MD30
MD31
MD32

UNITS

RANGE
0=Switch Ctrl
1=Time Sched
2=CCN Control
0=Setpoint Occ
1=Setpoint1
2=Setpoint2
3=4-20mA Setp
4=Dual Setp Sw
0=Cooling
1=Heating
2=Auto Chgover
3=Heat Cool Sw
0=No
1=Yes
2=Switch Ctrl
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON

COMMENT

WRITE
STATUS

CCN TABLE

CCN POINT

PAGE
NO.

Default = 0

forcible

N/A

N/A

32,46

Default = 0

forcible

N/A

N/A

32,33,
41

Default = 0
1-3 not
supported.

forcible

GENUNIT

HC_SEL

32,33

Default = 0
1 = CCN control

forcible

GENUNIT

RECL_SET

49

MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES
MODES

MODE_01
MODE_02
MODE_03
MODE_04
MODE_05
MODE_06
MODE_07
MODE_08
MODE_09
MODE_10
MODE_11
MODE_12
MODE_13
MODE_14
MODE_15
MODE_16
MODE_17
MODE_18
MODE_19
MODE_20
MODE_21
MODE_22
MODE_23
MODE_24
MODE_25
MODE_26
MODE_27
MODE_28
MODE_29
MODE_30
MODE_31
MODE_32

46
46
46
46
46
46
47
47
47
47
47
47
47
47
47
47
47
47
48
48
48
48
48
48
48
48
48
48
48
48
48
48

Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.

NOTE: See operating modes starting on page 46.

MODE ALARMS
ITEM
R.ALM
ALRM

H.ALM**

EXPANSION*

UNITS

RANGE

RESET ALL CURRENT ALRM


CURRENTLY ACTIVE ALARM
Current Alarm 1
Current Alarm 2
Current Alarm 3
Current Alarm 4
Current Alarm 5
ALARM HISTORY
Alarm History #1
Alarm History #2
Alarm History #29
Alarm History #30

*Expanded display will be actual alarm expansion.


Up to five current alarms will be displayed.
**History of thirty past alarms will be displayed.

93

COMMENT

WRITE
STATUS
forcible

CCN TABLE

CCN POINT

N/A

N/A

GENUNIT
GENUNIT
GENUNIT
GENUNIT
GENUNIT

alarm_1
alarm_2
alarm_3
alarm_4
alarm_5

ALRMHIST
ALRMHIST
ALRMHIST
ALRMHIST
ALRMHIST

alm_history_01
alm_history_02
alm_history_29
alm_history_30

PAGE
NO.
57
57
57
57
57
57
57

APPENDIX B CCN TABLES


STATUS DISPLAY TABLES
TABLE
CIRCA_AN

DISPLAY NAME

RANGE

UNITS
%
PSI
PSI
AMPS
AMPS
AMPS
AMPS
OHMS
OHMS
OHMS
OHMS
F
F
F
^F
%
%

POINT NAME

Percent Total Capacity


Discharge Pressure
Suction Pressure
Crank Heater Current Cp1
Crank Heater Current Cp2
Crank Heater Current Cp3
Crank Heater Current Cp4
Motor Thermistor Comp 1
Motor Thermistor Comp 2
Motor Thermistor Comp 3
Motor Thermistor Comp 4
Saturated Condensing Tmp
Saturated Suction Temp
Suction Gas Temperature
Suction Superheat Temp
EXV Position
Head Press Actuator Pos

0 - 100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnnn
nnnn
nnnn
nnnn
nnn.n
nnn.n
nnn.n
nnn.n
0 - 100
0 - 100

CAPA_T
DP_A
SP_A
cpa1_cur
cpa2_cur
cpa3_cur
cpa4_cur
cpa1_tmp
cpa2_tmp
cpa3_tmp
cpa4_tmp
SCT_A
SST_A
SUCT_T_A
SH_A
EXV_A
hd_pos_a

Compressor 1 Output
Compressor 2 Output
Compressor 3 Output
Compressor 4 Output
Compressor 1 Heater Out
Compressor 2 Heater Out
Compressor 3 Heater Out
Compressor 4 Heater Out
Hot Gas Bypass Output

On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off

CP_A1
CP_A2
CP_A3
CP_A4
cp_a1_ht
cp_a2_ht
cp_a3_ht
cp_a4_ht
HGBP_V_A

Fan Output DO # 1
Fan Output DO # 2
Fan Output DO # 3
Fan Output DO # 4
Fan Output DO # 5
Fan Output DO # 6
Fan Staging Number

On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-6

fan_a1
fan_a2
fan_a3
fan_a4
fan_a5
fan_a6
FAN_ST_A

4 Way Refrigerant Valve

On/Off

RV_A

Percent Total Capacity


Discharge Pressure
Suction Pressure
Crank Heater Current Cp1
Crank Heater Current Cp2
Crank Heater Current Cp3
Crank Heater Current Cp4
Motor Thermistor Comp 1
Motor Thermistor Comp 2
Motor Thermistor Comp 3
Motor Thermistor Comp 4
Saturated Condensing Tmp
Saturated Suction Temp
Suction Gas Temperature
Suction Superheat Temp
EXV Position
Head Press Actuator Pos

0 - 100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnnn
nnnn
nnnn
nnnn
nnn.n
nnn.n
nnn.n
nnn.n
0-100
0-100

Compressor 1 Output
Compressor 2 Output
Compressor 3 Output
Compressor 4 Output
Compressor 1 Heater Out
Compressor 2 Heater Out
Compressor 3 Heater Out
Compressor 4 Heater Out
Hot Gas Bypass Output

On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off

CP_B1
CP_B2
CP_B3
CP_B4
cp_b1_ht
cp_b2_ht
cp_b3_ht
cp_b4_ht
HGBP_V_B

Fan Output DO # 1
Fan Output DO # 2
Fan Output DO # 3
Fan Output DO # 4
Fan Output DO # 5
Fan Output DO # 6
Fan Staging Number

On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-6

fan_b1
fan_b2
fan_b3
fan_b4
fan_b5
fan_b6
FAN_ST_B

4 Way Refrigerant Valve

On/Off

RV_B

CIRCA_D

CIRCB_AN
%
PSI
PSI
AMPS
AMPS
AMPS
AMPS
OHMS
OHMS
OHMS
OHMS
F
F
F
^F
%
%

CAPB_T
DP_B
SP_B
cpb1_cur
cpb2_cur
cpb3_cur
cpb4_cur
cpb1_tmp
cpb2_tmp
cpb3_tmp
cpb4_tmp
SCT_B
SST_B
SUCT_T_B
SH_B
EXV_B
hd_pos_b

CIRCB_D

94

WRITE STATUS

APPENDIX B CCN TABLES (cont)


STATUS DISPLAY TABLES (cont)
TABLE
CIRCC_AN

DISPLAY NAME

RANGE

UNITS
%
PSI
PSI
AMPS
AMPS
AMPS
AMPS
OHMS
OHMS
OHMS
OHMS
F
F
F
^F
%
%

POINT NAME

Percent Total Capacity


Discharge Pressure
Suction Pressure
Crank Heater Current Cp1
Crank Heater Current Cp2
Crank Heater Current Cp3
Crank Heater Current Cp4
Motor Thermistor Comp 1
Motor Thermistor Comp 2
Motor Thermistor Comp 3
Motor Thermistor Comp 4
Saturated Condensing Tmp
Saturated Suction Temp
Suction Gas Temperature
Suction Superheat Temp
EXV Position
Head Press Actuator Pos

0-100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnnn
nnnn
nnnn
nnnn
nnn.n
nnn.n
nnn.n
nnn.n
0-100
0-100

CAPC_T
DP_C
SP_C
cpc1_cur
cpc2_cur
cpc3_cur
cpc4_cur
cpc1_tmp
cpc2_tmp
cpc3_tmp
cpc4_tmp
SCT_C
SST_C
SUCT_T_C
SH_C
EXV_C
hd_pos_c

Compressor 1 Output
Compressor 2 Output
Compressor 3 Output
Compressor 4 Output
Compressor 1 Heater Out
Compressor 2 Heater Out
Compressor 3 Heater Out
Compressor 4 Heater Out
Hot Gas Bypass Output

On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off

CP_C1
CP_C2
CP_C3
CP_C4
cp_c1_ht
cp_c2_ht
cp_c3_ht
cp_c4_ht
HGBP_V_C

Fan Output DO # 1
Fan Output DO # 2
Fan Output DO # 3
Fan Output DO # 4
Fan Output DO # 5
Fan Output DO # 6
Fan Staging Number
FAN Operating Hours
Circuit A Fan #1 Hours
Circuit A Fan #2 Hours
Circuit A Fan #3 Hours
Circuit A Fan #4 Hours
Circuit A Fan #5 Hours
Circuit A Fan #6 Hours
Circuit B Fan #1 Hours
Circuit B Fan #2 Hours
Circuit B Fan #3 Hours
Circuit B Fan #4 Hours
Circuit B Fan #5 Hours
Circuit B Fan #6 Hours
Circuit C Fan #1 Hours
Circuit C Fan #2 Hours
Circuit C Fan #3 Hours
Circuit C Fan #4 Hours
Circuit C Fan #5 Hours
Circuit C Fan #6 Hours
WATER PUMPS
Water Pump #1 Hours
Water Pump #2 Hours
Heat Reclaim Pump Hours
FREE COOLING PUMPS
Circuit A Pump Hours
Circuit B Pump Hours
Circuit C Pump Hours

On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-6

fan_c1
fan_c2
fan_c3
fan_c4
fan_c5
fan_c6
FAN_ST_C

CIRCC_D

FANHOURS

nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn

hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours

hr_fana1
hr_fana2
hr_fana3
hr_fana4
hr_fana5
hr_fana6
hr_fanb1
hr_fanb2
hr_fanb3
hr_fanb4
hr_fanb5
hr_fanb6
hr_fanc1
hr_fanc2
hr_fanc3
hr_fanc4
hr_fanc5
hr_fanc6

nnnnn
nnnnn
nnnnn

hours
hours
hours

hr_cpum1
hr_cpum2
hr_hpump

nnnnn
nnnnn
nnnnn

hours
hours
hours

hr_fcp_a
hr_fcp_b
hr_fcp_c

95

WRITE STATUS

APPENDIX B CCN TABLES (cont)


STATUS DISPLAY TABLES (cont)
TABLE
FREECOOL

DISPLAY NAME
GENERAL PARAMETER
Free Cooling Disable?
LWT-OAT Delta
Current Cooling Power
Estimated FreeCool Power
Next session allowed in
Cooling/FreeCool Timeout
Free Cool Conditions OK?
Free Cool Request ?
Valve Actuator Heaters ?
CIRCUIT A
Free Cooling Active
Fan Staging Number
3 Way Valve Position
3 Way Valve Status
Refrigerant Pump Out
Pump Inlet Pressure
Pump Outlet Pressure
Pump Differential Pressure
CIRCUIT B
Free Cooling Active
Fan Staging Number
3 Way Valve Position
3 Way Valve Status
Refrigerant Pump Out
Pump Inlet Pressure
Pump Outlet Pressure
Pump Differential Pressure

RANGE
Yes/No
nnn.n
nnn
nnn
nn
nn
Yes/No
Yes/No
On/Off
Yes/No
1-6
nnn
text*
On/Off
nnn
nnn
nnn
Yes/No
1-6
nnn
text*
On/Off
nnn
nnn
nnn

* Text reflects status of valve Closed, Closing, Opened, Opening, Stopped, or Failed.

96

UNITS

^F
KW
KW
min
min

%
PSI
PSI
PSI

%
PSI
PSI
PSI

POINT NAME
FC_SW
fc_delta
cool_pwr
fc_pwr
fc_next
fc_tmout
fc_ready
fc_reqst
FC_HTR
fc_on_a
FAN_ST_A
fc_vlv_a
FC_VLV_A
fc_pmp_a
fc_inp_a
fc_oup_a
fc_dp_a
fc_on_b
FAN_ST_B
fc_vlv_b
FC_VLV_B
fc_pmp_b
fc_inp_b
fc_oup_b
fc_dp_b

WRITE STATUS

APPENDIX B CCN TABLES (cont)


STATUS DISPLAY TABLES (cont)
TABLE
GENUNIT

DISPLAY NAME
GENERAL PARAMETER
Control Type
Run Status

CCN Chiller Start/Stop


Chiller Occupied?
Minutes Left for Start
Heat/Cool Status
Heat/Cool Select (0=Cool, 1=Heat,
2= Auto)
Heat Reclaim Select
Free Cooling Disable
Alarm State
Current Alarm 1
Current Alarm 2
Current Alarm 3
Current Alarm 4
Current Alarm 5
Percent Total Capacity
Active Demand Limit Val
Lag Capacity Limit Value
Current Setpoint
Setpoint Occupied
Setpoint Control

MODES

Control Point
Controlled Water Temp
External Temperature
Emergency Stop
OPERATING MODES
Startup Delay in Effect
Second Setpoint in Use
Reset in Effect
Demand Limit Active
Ramp Loading Active
Cooler Heater Active
Cooler Pumps Rotation
Pump Periodic Start
Night Low Noise Active
System Manager Active
Master Slave Active
Auto Changeover Active
Free Cooling Active
Reclaim Active
Electric Heat Active
Heating Low EWT Lockout
Boiler Active
Ice Mode in Effect
Defrost Active On Cir A
Defrost Active On Cir B
Low Suction Circuit A
Low Suction Circuit B
Low Suction Circuit C
High DGT Circuit A
High DGT Circuit B
High DGT Circuit C
High Pres Override Cir A
High Pres Override Cir B
High Pres Override Cir C
Low Superheat Circuit A
Low Superheat Circuit B
Low Superheat Circuit C

RANGE
Local
CCN
Remote
0 = Off
1 = Running
2 = Stopping
3 = Delay
4 = Tripout
5 = Ready
6 = Override
7 = Defrost
8 = Run Test
9 = Test
Enable/Disable
Yes/No
0-15
0 = Cool, 1 = Heat
2 = Stand-by
3 = Both
0 = Cool
1 = Heat
2 = Auto
Yes/No
Yes/No
0 Normal
1 Partial
2 Shutdown
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnn
nnn
nnn
nnn.n
Yes/No
Setpt 1
Setpt 2
Ice_sp
4-20mA
Auto
nnn.n
nnn.n
nnn.n
Enable/Disable
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No

97

UNITS

POINT NAME

WRITE STATUS

ctr_type
STATUS

min

%
%
%
F

F
F
F

CHIL_S_S
CHIL_OCC
min_left
HEATCOOL

forcible
forcible

HC_SEL

forcible

RECL_SEL
FC_DSBLE
ALM

forcible

alarm_1
alarm_2
alarm_3
alarm_4
alarm_5
CAP_T
DEM_LIM
LAG_LIM
SP
SP_OCC
sp_ctrl

CTRL_PNT
CTRL_WT
OAT
EMSTOP
Mode_01
Mode_02
Mode_03
Mode_04
Mode_05
Mode_06
Mode_07
Mode_08
Mode_09
Mode_10
Mode_11
Mode_12
Mode_13
Mode_14
Mode_15
Mode_16
Mode_17
Mode_18
Mode_19
Mode_20
Mode_21
Mode_22
Mode_23
Mode_24
Mode_25
Mode_26
Mode_27
Mode_28
Mode_29
Mode_30
Mode_31
Mode_32

forcible
forcible

forcible
forcible

APPENDIX B CCN TABLES (cont)


STATUS DISPLAY TABLES (cont)
TABLE
RECLAIM

STATEGEN

DISPLAY NAME
Heat Reclaim Select
Reclaim Condenser Pump
Reclaim Condenser Flow
Reclaim Condenser Heater
Reclaim Entering Fluid
Reclaim Leaving Fluid
Reclaim Fluid Setpoint
Reclaim Valve Position
HEAT RECLAIM CIRCUIT A
Reclaim Status Circuit A
Pumpdown Pressure Cir A
Sub Condenser Temp Cir A
Pumdown Saturated Tmp A
Subcooling Temperature A
Air Cond Entering Valv A
Water Cond Enter Valve A
Air Cond Leaving Valve A
Water Cond Leaving Val A
HEAT RECLAIM CIRCUIT B
Reclaim Status Circuit B
Pumpdown Pressure Cir B
Sub Condenser Temp Cir B
Pumdown Saturated Tmp B
Subcooling Temperature B
Air Cond Entering Valv B
Water Cond Enter Valve B
Air Cond Leaving Valve B
Water Cond Leaving Val B
UNIT DISCRETE IN
On/Off Remote Switch
Remote Heat/Cool Switch
Current Control
Remote Reclaim Switch
Free Cooling Disable Sw.
Remote Setpoint Switch
Limit Switch 1 Status
Limit Switch 2 Status
Occupied Override Switch
Ice Done Storage Switch
Interlock Status
Pump Run Status
Remote Interlock Status
Electrical Box Safety
UNIT DISCRETE OUT
Electrical Heat Stage
Boiler Command
Water Pump #1 Command
Water Pump #2 Command
Rotate Pumps Now
Reclaim Condenser Pump
Cooler Heater Command
Shutdown Indicator State
Alarm Relay Status
Alert Relay Status
Ready or Running Status
Running Status
Critical Alarm Status
UNIT ANALOG
Water Exchanger Entering
Water Exchanger Leaving
Optional Space Temp
CHWS Temperature
Reset /Setpoint 4-20mA In
Limit 4-20mA Signal
Chiller Capacity Signal

RANGE
Yes/no
On/Off
On/Off
On/Off
nnn.n
nnn.n
nnn.n
nnn.n
n
nnn.n
nnn.n
nnn.n
nnn.n
On/Off
On/Off
On/Off
On/Off
n
nnn.n
nnn.n
nnn.n
nnn.n
On/Off
On/Off
On/Off
On/Off

UNITS

F
F
F
%
psi
F
F
^F

psi
F
F
^F

POINT NAME
RECL_SEL
CONDPUMP
condflow
cond_htr
HR_EWT
HR_LWT
RSP
hr_v_pos

hrstat_b
PD_P_B
hr_subtb
hr_sat_b
hr_subcb
hr_ea_b
hr_ew_b
hr_la_b
hr_lw_b

RECL_SW
FC_SW
SETP_SW
LIM_SW1
LIM_SW2
OCC_OVSW
ICE_SW
LOCK_1
PUMP_DEF
REM_ LOCK
ELEC_BOX

0-4/Off
On/Off
On/Off
On/Off
Yes/No
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off

EHS_STEP
BOILER
CPUMP_1
CPUMP_2
ROT_PUMP
COND_PMP
COOLHEAT
SHUTDOWN
ALARMOUT
ALERT
READY
RUNNING
CRITICAL

98

forcible

hrstat_a
PD_P_A
hr_subta
hr_sat_a
hr_subca
hr_ea_a
hr_ew_a
hr_la_a
hr_lw_a

Open/Close
Open/Close
Off, On Cool, On
Heat, On Auto
Open/Close
Open/close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close

nnn.n
nnn.n
nnn.n
nnn.n
nn.n
nn.n
nn.n

WRITE STATUS

ONOFF_SW
HC_SW
on_ctrl

F
F
F
F
ma
ma
volts

EWT
LWT
SPACETMP
CHWSTEMP
SP_RESET
LIM_ANAL
CAPT_010

forcible
forcible
forcible
forcible

APPENDIX B CCN TABLES (cont)


STATUS DISPLAY TABLES (cont)
TABLE
STRTHOUR

DISPLAY NAME
Machine Operating Hours
Machine Starts Number
Compressor A1 Hours
Compressor A2 Hours
Compressor A3 Hours
Compressor A4 Hours
Compressor A1 Starts
Compressor A2 Starts
Compressor A3 Starts
Compressor A4 Starts
Compressor B1 Hours
Compressor B2 Hours
Compressor B3 Hours
Compressor B4 Hours
Compressor B1 Starts
Compressor B2 Starts
Compressor B3 Starts
Compressor B4 Starts
Compressor C1 Hours
Compressor C2 Hours
Compressor C3 Hours
Compressor C4 Hours
Compressor C1 Starts
Compressor C2 Starts
Compressor C4 Starts
Compressor C4 Starts
CYCLES
Starts Max During 1 Hour
Starts/hr From Last 24 h
Circuit A Defrost Number
Circuit B Defrost Number

RANGE
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn

UNITS
hours
hours
hours
hours
hours

hours
hours
hours
hours

hours
hours
hours
hours

nn
nn
nnnnn
nnnnn

POINT NAME
HR_MACH
st_mach
HR_CP_A1
HR_CP_A2
HR_CP_A3
HR_CP_A4
st_cp_a1
st_cp_a2
st_cp_a3
st_cp_a4
HR_CP_B1
HR_CP_B2
HR_CP_B3
HR_CP_B4
st_cp_b1
st_cp_b2
st_cp_b3
st_cp_b4
HR_CP_C1
HR_CP_C2
HR_CP_C3
HR_CP_C4
st_cp_c1
st_cp_c2
st_cp_c3
st_cp_c4

WRITE STATUS

st_cp_mx
st_cp_av
nb_def_a
nb_def_b

CONFIGURATION DISPLAY TABLES


TABLE
ALARMDEF/
ALARMS01

BRODEFS/
BRODCASTS

DISPLAY NAME
Alarm Routing Control
Alarm Equipment Priority
Comm Failure Retry Time
Realarm Time
Alarm System Name
Activate

OAT Broadcast
Bus #
Element #
DAYLIGHT SAVINGS SELECT
ENTERING
Month
Day of week* (1=Monday)
Week Number of Month
LEAVING
Month
Day of week* (1=Monday)
Week Number of Month

RANGE
0 or 1 for each position
0-7
1-240
1-255
8 chars
0=Unused
1=Broadcast time,
date, holiday flag
and OAT (as like
existing pro_dialog
control).
2=For Standalone
chiller. Daylight savings time & holiday
determination will
be done without
broadcasting
through the bus.

DEFAULT
00000000
4
10
30
PRO_RBRQ
2

UNITS

min
min

POINT NAME
ALRM_CNT
EQP_TYP
RETRY_TM
RE_ALARM
ALRM_NAM
Ccnbroad

0 to 239
0 to 239
Disable/Enable

0
0
Disable

Oatbusnm
Oatlocad
dayl_sel

1 to 12
1 to 7
1 to 5

3
7
5

Startmon
Startdow
Startwom

1 to 12
1 to 7
1 to 5

10
7
5

Stopmon
Stopdow
stopwom

*Day of week where daylight savings time will occur in the morning
(at 2:00 am). In the default setting, daylight savings time occurs on
Sunday (7) morning, 1 hour shall be added when entering and 1
hour subtracted when leaving.

Date once selected (from 1) shall occur in the week number


entered. 1: If day of week selected is 7 (Sunday) time change will
occur the first Sunday (week number 1) in the month. 5: If day of
week selected is 7 (Sunday) time change will occur the last
Sunday of the month (week number 4 or 5).

99

APPENDIX B CCN TABLES (cont)


CONFIGURATION DISPLAY TABLES (cont)
TABLE
!CtrlD /
PD5_RBRQ:

TABLE
DISPCONF

FACTORY

DISPLAY NAME
Device Name
Description

RANGE
8 chars
24 chars

Location
Software Part Number
Model Number
Serial Number
Reference Number

24 chars
16 chars
20 chars
12 chars
24 chars

DISPLAY NAME
Metric Display on STDU
Language Selection
0=English
1=Espanol
2=Francais
3=Portugues
4=English2
Unit Type

Pro_dialog Display Selec

Factory Password
High Static Fan Control
MCHX Exchanger Select
VLT Fan Drive Select
VLT Fan Drive RPM
Desuperheater Select
Dual Speed Fan Select

POINT NAME

UNITS

No
0

POINT NAME
DISPUNIT
LANGUAGE

unit_typ

PRO-DIALOG 5
30RB&30RQ

DEFAULT

1 (Cooling Only),
2 (not supported)
56 to 500
0 to 6
0 to 6
0 to 6
Yes/No
Yes/No
0 to 4
Yes/No
Yes/No
Yes/No
0-Hot gas bypass valve (not
used)
1=Used for Startup only
2=Close Control
3=High Ambient (if High
pressure mode is active,
close control shall be active)
No=Use ComfortLink
display as user interface
(factory installed)
Yes=Use Pro_dialog
synopsis as user interface
(not supported)
0 to 150
Not Supported
Yes/No
Not Supported
Not Supported
Not Supported
Not Supported

* Enter unit size. This item allows the controls to determine capacity
of each compressor and the total number of fans on each circuit
based on a compressor arrangement array (can be viewed in table
FACTORY2). It is not necessary to enter compressor capacity and
number of fans on each circuit. See the Unit Compressor Configuration table below as a reference.

UNITS

CSA-SR-20C460301

RANGE
Yes/No
0=English
1=Espanol
2=Francais
3=Portugues
4=English2

Unit Capacity*
NB Fans on Varifan Cir A
NB Fans on Varifan Cir B
NB Fans on Varifan Cir C
Air Cooled Reclaim Sel
Free Cooling Select
Electrical Heat Stages
Boiler Command Select
Power Frequence 60HZ Sel
Energy Management Module
Hot Gas Bypass Select

DEFAULT

Unit Dependent
0
0
0
No
No
0
No
Yes
No
0

tons

unitsize
varfan_a
varfan_b
varfan_c
recl_opt
free_opt
ehs_sel
boil_sel
freq_60H
emm_nrcp
hgbp_sel

No
(Must be set to No for
ComfortLink display)

pd4_disp

111
No
Unit Dependent
0
0
No
No

fac_pass
hsta_fan
mchx_sel
vlt_sel
vlt_rpm
desuper
dual_fan

Number of fans controlled directly by a variable speed fan actuator using 0 to 10 vdc signal. This will enable the controls to
determine the remaining discrete fan staging outputs from the
total fans on each circuit. Configure to 1 for low ambient head
pressure control.

UNIT COMPRESSOR CAPACITY (%) CONFIGURATION


30RB UNIT
SIZE
060
070
080
090
100
110
120
130
150
160
170
190
210
225
250
275
300

cap_a1
20
25
20
25
25
25
25
25
25
25
25
25
25
25
25
25
25

cap_a2
20
25
20
25
25
25
25
25
25
25
25
25
25
25
25
25
25

cap_a3
0
0
0
0
0
0
0
25
25
25
25
25
25
25
25
25
25

cap_a4
0
0
0
0
0
0
0
0
0
25
25
25
0
0
0
25
25

POINT NAME (FACTORY2 TABLE)


cap_b1
cap_b2
cap_b3
cap_b4
20
0
0
0
20
0
0
0
20
20
0
0
20
20
0
0
25
25
0
0
20
20
20
0
25
25
25
0
20
20
20
0
25
25
25
0
20
20
20
0
25
25
25
0
25
25
25
25
20
20
20
0
25
25
25
0
25
25
25
0
25
25
25
25
25
25
25
25

100

cap_c1
0
0
0
0
0
0
0
0
0
0
0
0
25
25
25
25
25

cap_c2
0
0
0
0
0
0
0
0
0
0
0
0
25
25
25
25
25

cap_c3
0
0
0
0
0
0
0
0
0
0
0
0
25
25
25
25
25

cap_c4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
25
0
25

APPENDIX B CCN TABLES (cont)


CONFIGURATION DISPLAY TABLES (cont)
TABLE
FACTORY2

DISPLAY NAME
Compressor A1 Capacity
Compressor A2 Capacity
Compressor A3 Capacity
Compressor A4 Capacity
Compressor B1 Capacity
Compressor B2 Capacity
Compressor B3 Capacity
Compressor B4 Capacity
Compressor C1 Capacity
Compressor C2 Capacity
Compressor C3 Capacity
Compressor C4 Capacity
Circuit A Total Fans NB
Circuit B Total Fans NB
Circuit C Total Fans NB
EXV A Maximum Steps Numb
EXV B Maximum Steps Numb
EXV C Maximum Steps Numb

RANGE
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 6
0 to 6
0 to 6
0/15000
0/15000
0/15000

NOTES:
1. Compressor capacity will be automatically be determined if unit
size entered in FACTORY1 table matches the values in the unit
compressor configuration table.

TABLE
HOLIDAY/
HOLDY01S to
HOLDY16S
MST_SLV

OCCDEFCS/
OCCPC01S and
OCCPC02S

DISPLAY NAME
Holiday Start Month
Start Day
Duration (days)
MASTER SLAVE CONTROL
Master/Slave Select
0=Disable
1=Master
2=Slave
Master Control Type
1=Local Control
2=Remote Control
3=CCN Control
Slave Address
Lag Start Timer
Lead/Lag Balance
Lead/Lag Balance Delta
Lag Unit Pump Control
0=Stop if Unit Stops
1=Run if Unit Stops
Lead Pulldown Time
Timed Override Hours
Period 1 DOW (MTWTFSSH)
Occupied From
Occupied To
Period 2 DOW (MTWTFSSH)
Occupied From
Occupied To
Period 3 DOW (MTWTFSSH)
Occupied From
Occupied To
Period 4 DOW (MTWTFSSH)
Occupied From
Occupied To
Period 5 DOW (MTWTFSSH)
Occupied From
Occupied To
Period 6 DOW (MTWTFSSH)
Occupied From
Occupied To
Period 7 DOW (MTWTFSSH)
Occupied From
Occupied To
Period 8 DOW (MTWTFSSH)
Occupied From
Occupied To

DEFAULT
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0=EXV not used
0
0

UNITS

POINT NAME
cap_a1
cap_a2
cap_a3
cap_a4
cap_b1
cap_b2
cap_b3
cap_b4
cap_c1
cap_c2
cap_c3
cap_c4
nb_fan_a
nb_fan_b
nb_fan_c
exva_max
exvb_max
exvc_max

2. Total number of fans includes fans controlled by a variable speed


fan. This value will be automatically populated if unit size entered
in FACTORY1 table matches the values in the unit compressor
configuration table.

0-12
0-31
0-99

RANGE
0
0
0

POINT NAME
HOL_MON
HOL_DAY
HOL_LEN

0=Disable
1=Master
2=Slave

ms_sel

1=Local Control
2=Remote Control
3=CCN Control

ms_ctrl

1 to 236
2 to 30
Yes/No
40 to 400
0=Stop if Unit Stops
1=Run if Unit Stops

2
10
No
168
0

0 to 60
0-4
0/1
00:00-24:00
00:00-24:00
0/1
00:00-24:00
00:00-24:00
0/1
00:00-24:00
00:00-24:00
0/1
00:00-24:00
00:00-24:00
0/1
00:00-24:00
00:00-24:00
0/1
00:00-24:00
00:00-24:00
0/1
00:00-24:00
00:00-24:00
0/1
00:00-24:00
00:00-24:00

0
0
11111111
00:00
24:00
11111111
00:00
00:00
00000000
00:00
00:00
00000000
00:00
00:00
00000000
00:00
00:00
00000000
00:00
00:00
00000000
00:00
00:00
00000000
00:00
00:00

101

DEFAULT

UNITS

min
hours

min

slv_addr
lstr_tim
ll_bal
ll_bal_d
lag_pump
lead_pul
OVR_EXT
DOW1
OCCTOD1
UNOCTOD1
DOW2
OCCTOD2
UNOCTOD2
DOW3
OCCTOD3
UNOCTOD3
DOW4
OCCTOD4
UNOCTOD4
DOW5
OCCTOD5
UNOCTOD5
DOW6
OCCTOD6
UNOCTOD6
DOW7
OCCTOD7
UNOCTOD7
DOW8
OCCTOD8
UNOCTOD8

APPENDIX B CCN TABLES (cont)


CONFIGURATION DISPLAY TABLES (cont)
TABLE
USER

DISPLAY NAME
Circuit Loading Sequence
0=Auto,1=A Lead
2=B Lead, 3 =C Lead
Staged Loading Sequence
Ramp Loading Select
Unit Off to On Delay
Cooler Pumps Sequence
0=No Pump
1=One Pump Only
2=Two Pumps Auto
3=Pump#1 Manual
4=Pump#2 Manual
Pump Auto Rotation Delay
Pump Sticking Protection
Stop Pump During Standby
Flow Checked if Pump Off
Auto Changeover Select
Cooling Reset Select
Heating Reset Select
1 =OAT,
0=None
2=Delta T,
3=4-20mA Control
4=Space Temp
Demand Limit Type Select
0=None
1=Switch Control
2=4-20mA Control
mA For 100% Demand Limit
mA For 0% Demand Limit
Heating OAT Threshold
Boiler OAT Threshold
Free Cooling
OAT Threshold
Full Load Timeout
Pre_Cooling Selected
HSM Both Commande Select
Elec Stage OAT Threshold
1 Elec Stage for backup
Electrical Pulldown Time
Quick EHS for Defrost
Night control
Start Hour
End Hour
Capacity Limit
Ice Mode Enable
Menu Description Select
Pass For All User Config

RANGE
0-3
0=Auto,
1=A Lead
2=B Lead,
3 =C Lead
No/Yes
No/Yes
1-15
0-4
0=No Pump
1=One Pump Only
2=Two Pumps Auto
3=Pump#1 Manual
4=Pump#2 Manual
24-3000
No/Yes
No/Yes
No/Yes
No/Yes
0-4
0-4
1 =OAT,
0=None
2=Delta T,
3=4-20mA Control
4=Space Temp
0-2
0=None
1=Switch Control
2=4-20mA Control
0-20
0-20
-4-32
5-59
-4-37.4
-4-37.4
5-60
No/Yes
No/Yes
23-70
No/Yes
0-60
No/Yes

DEFAULT

POINT NAME
lead_cir

No
No
1
0

seq_typ
ramp_sel
off_on_d
pump_seq

0
0
5
14
32
32.0
15
No
No
41
No
0
No

00:00-24:00
00:00-24:00
0-100
No/Yes
No/Yes
No/Yes

00:00
00:00
100
No
Yes
No

48
No
No
Yes
No
0
0

UNITS

Min

hours

pump_del
pump_per
pump_sby
pump_loc
auto_sel
cr_sel
hr_sel

lim_sel

ma
ma
F
F
F
F
min
F
min

lim_mx
lim_ze
heat_th
boil_th
free_oat
free_th
fc_tmout
pre_cool
both_sel
ehs_th
ehs_back
ehs_pull
ehs_defr
nh_start
nh_end
nh_cnfg
ice_cnfg
menu_des
all_pass

controls, then a 4 to 20 mA reset function shall be ignored. Configuration 3 (4-20mA Control) and 4 (Space Temperature) shall
require an Energy Management Module.
3. Configuration 2 (4-20mA Control) shall require an Energy Management Module. Configuration 1 Switch Demand limit provides
3 step demand limit if an Energy Management Module is present.
Otherwise, only one step is allowed.

NOTES:
1. Flow checked if pump off needed when a command is sent to the
primary pump to prevent cooler from freezing in winter conditions. Command will set the cooler flow switch to closed while the
controls stop the cooler pump. The controls may then generate
an alarm. If this decision is active, the cooler flow switch is not
checked when the cooler pump is stopped.
2. If cooling reset select set point has been selected the set point
based on 4 to 20 mA input signal through ComfortLink

102

APPENDIX B CCN TABLES (cont)


SETPOINT DISPLAY TABLES
TABLE
SETPOINT

DISPLAY NAME
COOLING
Cooling Setpoint 1
Cooling Setpoint 2
Cooling Ice Setpoinp
OAT No Reset Value
OAT Full Reset Value
Delta T No Reset Value
Delta T Full Reset Value
Current No Reset Value
Current Full Reset Value
Space T No Reset Value
Space T Full Reset Value
Cooling Reset Deg. Value
Cooling Ramp Loading
HEATING
Heating Setpoint 1
Heating Setpoint 2
OAT No Reset Value
OAT Full Reset Value
Delta T No Reset Value
Delta T Full Reset Value
Current No Reset Value
Current Full Reset Value
Heating Reset Deg. Value
Heating Ramp Loading
AUTO CHANGEOVER
Cool Changeover Setpt
Heat Changeover Setpt
MISCELLANEOUS
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
Reclaim Setpoint
Reclaim Deadband
Head Setpoint
Fan Max Speed

RANGE

DEFAULT

UNITS

POINT NAME

20.0-78.8
20.0-78.8
20.0-32.0
14-125
14-125
0-25
0-25
0-20
0-20
14-125
14-125
30-30
0.2-2.0

44.0
44.0
44.0
14.0
14.0
0.0
0.0
0.0
0.0
14.0
14.0
0.0
1.0

F
F
F
F
F
^F
^F
ma
ma
F
F
^F
^F

csp1
csp2
ice_sp
oatcr_no
oatcr_fu
dt_cr_no
dt_cr_fu
v_cr_no
v_cr_fu
spacr_no
spacr_fu
cr_deg
cramp_sp

68.0-122.0
68.0-122.0
14-125
14-125
0-25
0- 25
0-20
0-20
30-30
0.2-2.0

100.0
100.0
14.0
14.0
0.0
0.0
0.0
0.0
0.0
1.0

F
F
F
F
^F
^F
ma
ma
^F
^F

hsp1
hsp2
oathr_no
oathr_fu
dt_hr_no
dt_hr_fu
v_hr_no
v_hr_fu
hr_deg
hramp_sp

39-122
32-115

75.0
64.0

F
F

cauto_sp
hauto_sp

0-100
0-100
0-100
95.0-122.0
5-27
40.0-122.0
0-100

100
100
100
122.0
9.0
95.0
100

%
%
%
F
^F
F
%

lim_sp1
lim_sp2
lim_sp3
rsp
hr_deadb
head_stp
fan_smax

POINT NAME

WRITE STATUS

MAINTENANCE DISPLAY TABLES


TABLE
DEFROSTM

DISPLAY NAME
CIR A DEFROST CONTROL
Exchanger Frost Factor
Next Sequence Allowed in
Defrost Active?
Defrost Temperature
Defrost Duration
Fan Sequence Started
Override State
Mean SST Calculation
Delta: OAT - Mean SST
Reference Delta
Delta - Reference Delta
Frost Integrator Gain
Defrost Fan Start Cal A
Defrost Fan Offset Cal A
CIR B DEFROST CONTROL
Exchanger Frost Factor
Next Sequence Allowed in
Defrost Active?
Defrost Temperature
Defrost Duration
Fan Sequence Started?
Override State
Mean SST calculation
Delta: OAT - Mean SST
Reference Delta
Delta - Reference Delta
Frost Integrator Gain
Defrost Fan Start Cal B
Defrost Fan Offset Cal B

RANGE
0-100
nnn
True/False
nnn.n
nnn
n
nn
nnn.n
nnn.n
nnn.n
nnn.n
n.n
0.00
0.00
0-100
nnn
True/False
nnn.n
nnn
n
nn
nnn.n
nnn.n
nnn.n
nnn.n
n.n
0.00
0.00

UNITS
%
min
F
min
F
^F
^F
F
psi
psi
%
min
F
min
F
^F
^F
^F
psi
psi

NOTES: Tables for display only. Forcing shall not be supported on this maintenance screen.

103

frost_a
def_se_a
mode[19]
DEFRT_A
defr_dua
def_fa_a
over_d_a
sst_dm_a
delt_a
delt_r_a
delt_v_a
fr_int_a
def_ca_a
def_of_a
frost_b
def_se_b
mode[20]
DEFRT_B
defr_dub
def_fa_b
over_d_b
sst_dm_b
delt_b
delt_r_b
delt_v_b
fr_int_b
def_ca_b
def_of_b

APPENDIX B CCN TABLES (cont)


MAINTENANCE DISPLAY TABLES (cont)
TABLE
FANCTRL

LAST_POR

DISPLAY NAME
Cir A SCT Control Point
Cir A SCT Candidate
Cir A Fan Drive Power
Cir A Fan Drive Version
Cir B SCT Control Point
Cir B SCT Candidate
Cir B Fan Drive Power
Cir B Fan Drive Version
Cir C SCT Control Point
Cir C SCT Candidate
Cir C Fan Drive Power
Cir C Fan Drive Version
Power On 1: day-mon-year
Power On 1: hour-minute
PowerDown 1:day-mon-year
PowerDown 1:hour-minute
Power On 2: day-mon-year
Power On 2: hour-minute
PowerDown 2:day-mon-year
PowerDown 2:hour-minute
Power On 3: day-mon-year
Power On 3: hour-minute
PowerDown 3:day-mon-year
PowerDown 3:hour-minute
Power On 4: day-mon-year
Power On 4: hour-minute
PowerDown 4:day-mon-year
PowerDown 4:hour-minute
Power On 5: day-mon-year
Power On 5: hour-minute
PowerDown 5:day-mon-year
PowerDown 5:hour-minute

RANGE

UNITS

nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn

Average Ctrl Water Temp


Differential Water Temp
Water Delta T
Control Point
Reset Amount
Controlled Temp Error
Actual Capacity
Actual Capacity Limit
Current Z Multiplier Val
Load/Unload Factor
Active Stage Number
Active Capacity Override

nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn
nnn
n.n
nnn.n
nn
nn

F
F
^F
F
^F
^F
%
%

EXV Position Limit Cir A


SH Setpoint Circuit A
Cooler Exchange DT Cir A
Cooler Pinch Ctl Point A
EXV Override Circuit A
EXV Position Limit Cir B
SH Setpoint Circuit B
Cooler Exchange DT Cir B
Cooler Pinch Ctl Point B
EXV Override Circuit B
EXV Position Limit Cir C
SH Setpoint Circuit C
Cooler Exchange DT Cir C
Cooler Pinch Ctl Point C
EXV Override Circuit C

nnn.n
nn.n
nn.n
nn.n
nn
nnn.n
nn.n
nn.n
nn.n
nn
nnn.n
nn.n
nn.n
nn.n
nn

%
^F
^F
^F

EHS Ctrl Override


Requested Electric Stage
Electrical Pulldown?
Required Cooling Power
Free Cool Override Cir A
Free Cool Override Cir B

nn
nn
True/False

F
F
kW
F
F
kW
F
F
kW

POINT NAME
sct_sp_a
sct_fu_a
drva_pwr
drva_ver
sct_sp_b
sct_fu_b
drvb_pwr
drvb_ver
sct_sp_c
sct_fu_c
drvc_pwr
drvc_ver
date_on1
time_on1
date_of1
time_of1
date_on2
time_on2
date_of2
time_of2
date_on3
time_on3
date_of3
time_of3
date_on4
time_on4
date_of4
time_of4
date_on5
time_on5
date_of5
time_of5

LOADFACT

%
^F
^F
^F
%
^F
^F
^F

104

ctrl_avg
diff_wt
delta_t
CTRL_PNT
reset
tp_error
cap_t
cap_lim
zm
smz
cur_stag
over_cap
exvlim_a
sh_sp_a
pinch_a
pinch_spa
ov_exv_a
exvlim_b
sh_sp_b
pinch_b
pinch_spb
ov_exv_b
exvlim_c
sh_sp_c
pinch_c
pinch_spc
ov_exv_c
over_ehs
eh_stage
Ehspulld
req_pow
ov_fc_a
ov_fc_b

WRITE STATUS

APPENDIX B CCN TABLES (cont)


MAINTENANCE DISPLAY TABLES (cont)
TABLE
MSTSLAVE

DISPLAY NAME
MASTER/SLAVE CONTROL
Unit is Master or Slave
Master Control Type*
Master/Slave Ctrl Active
Lead Unit is the
Slave Chiller State
Slave Chiller Total Cap
Lag Start Delay**
Lead/Lag Hours Delta*
Lead/Lag Changeover?**
Lead Pulldown?
Master/Slave Error
Max Available Capacity?

RANGE
Disable/Master/Slave
Local/Remote/CCN
True/False
Master/Slave
0/1/2/3/4/5
0-100
1-30
nnnnn
Yes/No
Yes/No
nn
True/False

UNITS

POINT NAME

WRITE STATUS

mstslv
ms_ctrl
ms_activ
lead_sel
slv_stat
slv_capt
l_strt_d
ll_hr_d
ll_chang
ll_pull
ms_error
cap_max

%
min
hours

*Always CCN for the slave chiller.


Slave chiller chillstat value.
**This decision is consistent for Master chiller only. It shall be set by default to 0 for the slave chiller.
This item is true when chiller has loaded its total available capacity tonnage.

TABLE
OCCDEFCM/
OCC1PO1S
OCC2PO2S

TABLE
PR_LIMIT

DISPLAY NAME
Current Mode (1=occup.)
Current Occp Period #
Timed-Override in Effect
Timed-Override Duration
Current Occupied Time
Current Unoccupied Time
Next Occupied Day
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Prev Unoccupied Day
Prev Unoccupied Time

RANGE
0/1
1 to 8
Yes/No
0-4
00:00-23:59
00:00-23:59
Mon-Sun
00:00-23:59
Mon-Sun
00:00-23:59
Mon-Sun
00:00-23:59

UNITS

POINT NAME
MODE
PER_NO
OVERLAST
OVR_HRS
STRTTIME
ENDTIME
NXTOCDAY
NXTOCTIM
NXTUNDAY
NXTUNTIM
PRVUNDAY
PRVUNTIM

WRITE STATUS

DISPLAY NAME
Discharge A Temp Average
Discharge A Temp Rate
Discharge A Gas Limit
Suction A Temp Average
Discharge A Tp Average 2
Discharge A Temp Limit2
Discharge B Temp Average
Discharge B Temp Rate
Discharge B Gas Limit
Suction B Temp Average
Discharge C Temp Average
Discharge C Temp Rate
Discharge C Gas Limit
Suction C Temp Average

nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n

UNITS

POINT NAME
sdt_m_a
sdt_mr_a
sdtlim_a
sst_m_a
sdt_m2_a
sdtlim2a
sdt_m_b
sdt_mr_b
sdtlim_b
sst_m_b
sdt_m_c
sdt_mr_c
sdtlim_c
sst_m_c

WRITE STATUS

UNITS

nn

POINT NAME
S_RESET

WRITE STATUS
forcible

Normal/Low/Disable
Normal/Low/Disable

charge_m
wloop_m

0-1000/Alert/Disable
0-1000/Alert/Disable
0-1000/Alert/Disable
0-1000/Alert/Disable

cpump1_m
cpump2_m
hpump_m
wfilte_m

hours

RANGE
F
^F
F
F
^F
^F
F
^F
F
F
F
^F
F
F

NOTE: Table for display only. Used for Cooling and Heat Pump Compressor Envelope.

TABLE
SERMAINT

DISPLAY NAME
Reset Maintenance Alert
1 to 6: reset individually
7: reset all
OPERATION WARNINGS
1 Refrigerant Charge
2 Water Loop Size
GENERAL SERVICING DELAYS
3 Pump 1 (days)
4 Pump 2 (days)
5 Reclaim Pump (days)
6 Water Filter (days)

RANGE

105

APPENDIX B CCN TABLES (cont)


SERVICE DISPLAY TABLES
TABLE
CP_UNABL

DISPLAY NAME
Compressor A1 Disable
Compressor A2 Disable
Compressor A3 Disable
Compressor A4 Disable
Compressor B1 Disable
Compressor B2 Disable
Compressor B3 Disable
Compressor B4 Disable
Compressor C1 Disable
Compressor C2 Disable
Compressor C3 Disable
Compressor C4 Disable

RANGE
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes

DEFAULT
No
No
No
No
No
No
No
No
No
No
No
No

TABLE
SERVICE1

DISPLAY NAME
MAINTENANCE CONFIG
Servicing Alert
Refrigerant Charge Ctrl
Water Loop Control
CPump 1 Ctl Delay (days)
CPump 2 Ctl Delay (days)
HPump Ctrl Delay (days)
Water Filter Ctrl (days)

DISPLAY NAME
Cooler Fluid Type
Entering Fluid Control
Prop PID Gain Varifan
Int PID Gain Varifan
Deri PID Gain Varifan
EXV A Superheat Setpoint
EXV B Superheat Setpoint
EXV C Superheat Setpoint
EXV MOP Setpoint
High Pressure Threshold
Cooler Heater Delta Spt
Brine Freeze Setpoint
Minimum LWT Setpoint
Auto Start When SM Lost
Auto Z Multiplier Setpt
Maximum Z Multiplier
Recl Valve Min Position
Recl Valve Max Position
User Password
Service Password
SPM Board Configuration
Maximum Ducted Fan Speed

RANGE
Enable/Disable
Enable/Disable
Enable/Disable
0-1000
0-1000
0-1000
0-1000

POINT NAME

WRITE STATUS

un_cp_a1
un_cp_a2
un_cp_a3
un_cp_a4
un_cp_b1
un_cp_b2
un_cp_b3
un_cp_b4
un_cp_c1
un_cp_c2
un_cp_c3
un_cp_c4

NOTES:
1. Table used to disable compressors for maintenance purposes.
The capacity control will consider that these compressors (once
set to YES) are failed manually (no alarm will appear).

TABLE
MAINTCFG

UNITS

2. All data will be re-initialized to NO at Power on reset on units


using pro_dialog display. For ComfortLink display, data shall be
saved.

DEFAULT

UNITS

Disable
Disable
Disable
0
0
0
0

RANGE
1-3
Yes/No
20.0-20.0
5.0-5.0
20.0-20.0
2.5-54.0
2.5-54.0
2.5-54.0
30.8-50.0
500-640
1-6
20-34

DEFAULT
1
No
2.0
0.2
0.4
9.0
9.0
9.0
50.0
609
2
34
38
Enable/Disable
Disable
4-10
6
1.0-6.0
6.0
0-50
20
20-100
100
0-150
11
0-150
88
0 or 1 for each digit 00001010
0-100
100

POINT NAME

WRITE STATUS

s_alert
charge_c
wloop_c
cpump1_c
cpump2_c
hpump_c
wfilte_c

UNITS

^F
^F
^F
F
psi
^F
F
F

%
%
N/A
N/A
%

POINT NAME
flui_typ
ewt_opt
hd_pg
hd_ig
hd_dg
sh_sp_a
sh_sp_b
sh_sp_c
mop_sp
hp_th
heatersp
lowestsp
mini_lwt
auto_sm
zm_spt
hc_zm
min_3w
max_3w
use_pass
ser_pass
spm_conf
fan_max

WRITE STATUS

NOTE: This table shall be downloadable at any time. However, modified value shall not be used by tasks until the unit is in OFF state. This shall not
apply to the Varifan gains that shall be modified at any time and used immediately by the head pressure control tasks even if the unit is in operation.

106

APPENDIX B CCN TABLES (cont)


SERVICE DISPLAY TABLES (cont)
TABLE
UPDHRFAN

DISPLAY NAME
TABLE TO BE USED FOR
RUN TIMES & START
UPDATE IN CASE OF
CONTROL RETROFIT
FAN Operating Hours
Circuit A Fan #1 Hours
Circuit A Fan #2 Hours
Circuit A Fan #3 Hours
Circuit A Fan #4 Hours
Circuit A Fan #5 Hours
Circuit A Fan #6 Hours
Circuit B Fan #1 Hours
Circuit B Fan #2 Hours
Circuit B Fan #3 Hours
Circuit B Fan #4 Hours
Circuit B Fan #5 Hours
Circuit B Fan #6 Hours
Circuit C Fan #1 Hours
Circuit C Fan #2 Hours
Circuit C Fan #3 Hours
Circuit C Fan #4 Hours
Circuit C Fan #5 Hours
Circuit C Fan #6 Hours
WATER PUMP
WATER PUMP #1 Hours
WATER PUMP #2 Hours
Heat Reclaim Pump Hours
FREE COOLING PUMPS
Free Cool A Pump Hours
Free Cool B Pump Hours
Free Cool C Pump Hours

RANGE

UNITS

POINT NAME

nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn

hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours

hr_fana1
hr_fana2
hr_fana3
hr_fana4
hr_fana5
hr_fana6
hr_fanb1
hr_fanb2
hr_fanb3
hr_fanb4
hr_fanb5
hr_fanb6
hr_fanc1
hr_fanc2
hr_fanc3
hr_fanc4
hr_fanc5
hr_fanc6

nnnnn
nnnnn
nnnnn

hours
hours
hours

hr_cpum1
hr_cpum2
hr_hpump

nnnnn
nnnnn
nnnnn

hours
hours
hours

hr_fcp_a
hr_fcp_b
hr_fcp_c

WRITE STATUS

NOTE: This table shall be used for purposes of transplanting the devices on time in the event of a module hardware failure or software upgrade via
downloading. It shall be usable only if all items are still null. Afterwards, its access shall be denied.

TABLE
UPDTHOUR

DISPLAY NAME
TABLE TO BE USED FOR
RUN TIMES UPDATE IN
CASE OF CONTROL
RETROFIT
Machine Operating Hours
Machine Starts
Compressor A1 Hours
Compressor A2 Hours
Compressor A3 Hours
Compressor A4 Hours
Compressor A1 Starts
Compressor A2 Starts
Compressor A3 Starts
Compressor A4 Starts
Compressor B1 Hours
Compressor B2 Hours
Compressor B3 Hours
Compressor B4 Hours
Compressor B1 Starts
Compressor B2 Starts
Compressor B3 Starts
Compressor B4 Starts
Compressor C1 Hours
Compressor C2 Hours
Compressor C3 Hours
Compressor C4 Hours
Compressor C1 Starts
Compressor C2 Starts
Compressor C3 Starts
Compressor C4 Starts
Circuit A Defrost Number
Circuit B Defrost Number

RANGE

UNITS

nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn

hours
hours
hours
hours
hours

hours
hours
hours
hours

hours
hours
hours
hours

POINT NAME

WRITE STATUS

hr_mach
st_mach
hr_cp_a1
hr_cp_a2
hr_cp_a3
hr_cp_a4
st_cp_a1
st_cp_a2
st_cp_a3
st_cp_a4
hr_cp_b1
hr_cp_b2
hr_cp_b3
hr_cp_b4
st_cp_b1
st_cp_b2
st_cp_b3
st_cp_b4
hr_cp_c1
hr_cp_c2
hr_cp_c3
hr_cp_c4
st_cp_c1
st_cp_c2
st_cp_c3
st_cp_c4
nb_def_a
nb_def_b

NOTE: This table shall be used for purposes of transplanting the devices on time in the event of a module hardware failure or software upgrade via
downloading. It shall be usable only if all items are still null. Afterwards, its access shall be denied.

107

APPENDIX C CCN ALARM DESCRIPTION


ALARM CODE
th-01
th-02
th-03
th-04
th-08
th-09
th-10
th-11
th-12
th-13
th-14
th-18
th-19
th-21
Pr-01
Pr-02
Pr-03
Pr-04
Pr-05
Pr-06
Pr-07
Pr-08
Co-A1
Co-A2
Co-A3
Co-A4
Co-B1
Co-B2
Co-B3
Co-B4
Co-C1
Co-C2
Co-C3
Co-C4
Co-E1
Co-E2
Co-F1
Co-F2
Co-F3
Co-O1
Co-O2
Co-O3
Co-O4
Ct-01
Ct-02
Ct-03

ALARM TEXT DESCRIPTION AND CCN MESSAGE


Thermistor Failure
Water exchanger Entering Fluid Thermistor
Water exchanger Leaving Fluid Thermistor
Circuit A Defrost Thermistor
Circuit B Defrost Thermistor
Reclaim Condenser Entering Thermistor
Reclaim Condenser Leaving Thermistor
OAT Thermistor
MASTER/Slave Common Fluid Thermistor
Circuit A Suction Gas Thermistor
Circuit B Suction Gas Thermistor
Circuit C Suction Gas Thermistor
Circuit A Condenser Subcooling Liquid Thermistor
Circuit B Condenser Subcooling Liquid Thermistor
Space Temperature Thermistor
Pressure Transducer Failure
Circuit A Discharge Transducer
Circuit B Discharge Transducer
Circuit C Discharge Transducer
Circuit A Suction Transducer
Circuit B Suction Transducer
Circuit C Suction Transducer
Circuit A Reclaim Pumpdown Pressure Transducer
Circuit B Reclaim Pumpdown Pressure Transducer
Communication with Slave Board Failure
Loss of communication with Compressor Board A1
Loss of communication with Compressor Board A2
Loss of communication with Compressor Board A3
Loss of communication with Compressor Board A4
Loss of communication with Compressor Board B1
Loss of communication with Compressor Board B2
Loss of communication with Compressor Board B3
Loss of communication with Compressor Board B4
Loss of communication with Compressor Board C1
Loss of communication with Compressor Board C2
Loss of communication with Compressor Board C3
Loss of communication with Compressor Board C4
Loss of communication with EXV Board Number 1
Loss of communication with EXV Board Number 2
Loss of communication with Fan Board Number 1
Loss of communication with Fan Board Number 2
Loss of communication with Fan Board Number 3
Loss of communication with Free Cooling Board
Loss of communication with Electrical Heaters Board
Loss of communication with Energy Management NRCP2 Board
Loss of communication with Heat Reclaim Board
Circuit A Welded Contactor Failure
Circuit B Welded Contactor Failure
Circuit C Welded Contactor Failure

108

APPENDIX C CCN ALARM DESCRIPTION (cont)


ALARM CODE
FC-n0
FC-01
MC-nn
P-01
P-05
P-06
P-07
P-08
P-09
P-10
P-11
P-12
P-13
P-14
P-15
P-16
P-17
P-18
P-19
P-20
P-21
P-22
P-23
P-24
P-25
P-26
P-27
P-28
P-29
P-30
P-31
P-32
P-33
P-34
P-35
P-37
P-38
P-39
P-40
P-41
P-42
P-43
P-97

ALARM TEXT DESCRIPTION AND CCN MESSAGE


Process Failure
No factory configuration
Illegal factory configuration Number #1 to nn
Master chiller configuration error Number #1 to nn
Water Exchanger Freeze Protection
Circuit A Low Suction Temperature
Circuit B Low Suction Temperature
Circuit C Low Suction Temperature
Circuit A High Superheat
Circuit B High Superheat
Circuit C High Superheat
Circuit A Low Superheat
Circuit B Low Superheat
Circuit C Low Superheat
Cooler Interlock Failure
Condenser Flow Switch Failure
Compressor A1 Not Started or Pressure Increase not established
Compressor A2 Not Started or Pressure Increase not established
Compressor A3 Not Started or Pressure Increase not established
Compressor A4 Not Started or Pressure Increase not established
Compressor B1 Not Started or Pressure Increase not established
Compressor B2 Not Started or Pressure Increase not established
Compressor B3 Not Started or Pressure Increase not established
Compressor B4 Not Started or Pressure Increase not established
Compressor C1 Not Started or Pressure Increase not established
Compressor C2 Not Started or Pressure Increase not established
Compressor C3 Not Started or Pressure Increase not established
Compressor C4 Not Started or Pressure Increase not established
Electrical Box Thermostat or Power Reverse Phase Detection
Loss of communication with System Manager
Master/Slave communication Failure
Unit is in CCN emergency stop
Water pump #1 default
Water pump #2 default
Circuit A Reclaim Operation Failure
Circuit B Reclaim Operation Failure
Circuit A Repeated high discharge gas overrides
Circuit B Repeated high discharge gas overrides
Circuit C Repeated high discharge gas overrides
Circuit A Repeated low suction temp overrides
Circuit B Repeated low suction temp overrides
Circuit C Repeated low suction temp overrides
Low entering water temperature in heating
Water Exchanger Temperature Sensors Swapped

109

APPENDIX C CCN ALARM DESCRIPTION (cont)


ALARM CODE
Sr-nn
A1-01
A1-02
A1-03
A1-04
A1-05
A1-06
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A3-01
A3-02
A3-03
A3-04
A3-05
A3-06
A4-01
A4-02
A4-03
A4-04
A4-05
A4-06
B1-01
B1-02
B1-03
B1-04
B1-05
B1-06
B2-01
B2-02
B2-03
B2-04
B2-05
B2-06
B3-01
B3-02
B3-03
B3-04
B3-05
B3-06
B4-01
B4-02
B4-03
B4-04
B4-05
B4-06

ALARM TEXT DESCRIPTION AND CCN MESSAGE


Service Failure
Service maintenance alert Number # nn (see Table 44)
Compressor Failure
Compressor A1 Motor Temperature Too High
Compressor A1 Crankcase Heater Failure
Compressor A1 High Pressure Switch
Compressor A1 Motor Temperature Sensor PTC Out Of Range
Compressor A1 Power Reset
Compressor A1 Low Control Voltage Alert
Compressor A2 Motor Temperature Too High
Compressor A2 Crankcase Heater Failure
Compressor A2 High Pressure Switch
Compressor A2 Motor Temperature Sensor PTC Out Of Range
Compressor A2 Power Reset
Compressor A2 Low Control Voltage Alert
Compressor A3 Motor Temperature Too High
Compressor A3 Crankcase Heater Failure
Compressor A3 High Pressure Switch
Compressor A3 Motor Temperature Sensor PTC Out Of Range
Compressor A3 Power Reset
Compressor A3 Low Control Voltage Alert
Compressor A4 Motor Temperature Too High
Compressor A4 Crankcase Heater Failure
Compressor A4 High Pressure Switch
Compressor A4 Motor Temperature Sensor PTC Out Of Range
Compressor A4 Power Reset
Compressor A4 Low Control Voltage Alert
Compressor B1 Motor Temperature Too High
Compressor B1 Crankcase Heater Failure
Compressor B1 High Pressure Switch
Compressor B1 Motor Temperature Sensor PTC Out Of Range
Compressor B1 Power Reset
Compressor B1 Low Control Voltage Alert
Compressor B2 Motor Temperature Too High
Compressor B2 Crankcase Heater Failure
Compressor B2 High Pressure Switch
Compressor B2 Motor Temperature Sensor PTC Out Of Range
Compressor B2 Power Reset
Compressor B2 Low Control Voltage Alert
Compressor B3 Motor Temperature Too High
Compressor B3 Crankcase Heater Failure
Compressor B3 High Pressure Switch
Compressor B3 Motor Temperature Sensor PTC Out Of Range
Compressor B3 Power Reset
Compressor B3 Low Control Voltage Alert
Compressor B4 Motor Temperature Too High
Compressor B4 Crankcase Heater Failure
Compressor B4 High Pressure Switch
Compressor B4 Motor Temperature Sensor PTC Out Of Range
Compressor B4 Power Reset
Compressor B4 Low Control Voltage Alert

110

APPENDIX C CCN ALARM DESCRIPTION (cont)


ALARM CODE
C1-01
C1-02
C1-03
C1-04
C1-05
C1-06
C2-01
C2-02
C2-03
C2-04
C2-05
C2-06
C3-01
C3-02
C3-03
C3-04
C3-05
C3-06
C4-01
C4-02
C4-03
C4-04
C4-05
C4-06

ALARM TEXT DESCRIPTION AND CCN MESSAGE


Compressor Failure
Compressor C1 Motor Temperature Too High
Compressor C1 Crankcase Heater Failure
Compressor C1 High Pressure Switch
Compressor C1 Motor Temperature Sensor PTC Out Of Range
Compressor C1 Power Reset
Compressor C1 Low Control Voltage Alert
Compressor C2 Motor Temperature Too High
Compressor C2 Crankcase Heater Failure
Compressor C2 High Pressure Switch
Compressor C2 Motor Temperature Sensor PTC Out Of Range
Compressor C2 Power Reset
Compressor C2 Low Control Voltage Alert
Compressor C3 Motor Temperature Too High
Compressor C3 Crankcase Heater Failure
Compressor C3 High Pressure Switch
Compressor C3 Motor Temperature Sensor PTC Out Of Range
Compressor C3 Power Reset
Compressor C3 Low Control Voltage Alert
Compressor C4 Motor Temperature Too High
Compressor C4 Crankcase Heater Failure
Compressor C4 High Pressure Switch
Compressor C4 Motor Temperature Sensor PTC Out Of Range
Compressor C4 Power Reset
Compressor C4 Low Control Voltage Alert

111

APPENDIX D R-410A PRESSURE VS. TEMPERATURE CHART


PSIG
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112

F
37.7
34.7
32.0
29.4
26.9
24.5
22.2
20.0
17.9
15.8
13.8
11.9
10.1
8.3
6.5
4.5
3.2
1.6
0.0
1.5
3.0
4.5
5.9
7.3
8.6
10.0
11.3
12.6
13.8
15.1
16.3
17.5
18.7
19.8
21.0
22.1
23.2
24.3
25.4
26.4
27.4
28.5
29.5
30.5
31.2
32.2
33.2
34.1
35.1
35.5
36.9

C
38.7
37.1
35.6
34.1
32.7
31.4
30.1
28.9
27.7
26.6
25.4
24.4
23.4
22.4
21.4
20.3
19.6
18.7
17.8
16.9
16.1
15.3
14.5
13.7
13.0
12.2
11.5
10.8
10.1
9.4
8.7
8.1
7.4
6.8
6.1
5.5
4.9
4.3
3.7
3.1
2.6
1.9
1.4
0.8
0.4
0.1
0.7
1.2
1.7
1.9
2.7

PSIG
114
116
118
120
122
124
126
128
130
132
134
136
138
140
142
144
146
148
150
152
154
156
158
160
162
164
166
168
170
172
174
176
178
180
182
184
186
188
190
192
194
196
198
200
202
204
206
208
210
212
214

F
37.8
38.7
39.5
40.5
41.3
42.2
43.0
43.8
44.7
45.5
46.3
47.1
47.9
48.7
49.5
50.3
51.1
51.8
52.5
53.3
54.0
54.8
55.5
56.2
57.0
57.7
58.4
59.0
59.8
60.5
61.1
61.8
62.5
63.1
63.8
64.5
65.1
65.8
66.4
67.0
67.7
68.3
68.9
69.5
70.1
70.7
71.4
72.0
72.6
73.2
73.8

C
3.2
3.7
4.2
4.7
5.2
5.7
6.1
6.6
7.1
7.5
7.9
8.4
8.8
9.3
9.7
10.2
10.6
11.0
11.4
11.8
12.2
12.7
13.1
13.4
13.9
14.3
14.7
15.0
15.4
15.8
16.2
16.6
16.9
17.3
17.7
18.1
18.4
18.8
19.1
19.4
19.8
20.2
20.5
20.8
21.2
21.5
21.9
22.2
22.6
22.9
23.2

PSIG
216
218
220
222
224
226
228
230
232
234
236
238
240
242
244
246
248
250
252
254
256
258
260
262
264
266
268
270
272
274
276
278
280
282
284
286
288
290
292
294
296
298
300
302
304
306
308
310
312
314
316

F
74.3
74.9
75.5
76.1
76.7
77.2
77.8
78.4
78.9
79.5
80.0
80.6
81.1
81.6
82.2
82.7
83.3
83.8
84.3
84.8
85.4
85.9
86.4
86.9
87.4
87.9
88.4
88.9
89.4
89.9
90.4
90.9
91.4
91.9
92.4
92.8
93.3
93.8
94.3
94.8
95.2
95.7
96.2
96.6
97.1
97.5
98.0
98.4
98.9
99.3
99.7

C
23.5
23.8
24.2
24.5
24.8
25.1
25.4
25.8
26.1
26.4
26.7
27.0
27.3
27.6
27.9
28.2
28.5
28.8
29.1
29.3
29.7
29.9
30.2
30.5
30.8
31.1
31.3
31.6
31.9
32.2
32.4
32.7
33.0
33.3
33.6
33.8
34.1
34.3
34.6
34.9
35.1
35.4
35.7
35.9
36.2
36.4
36.7
36.9
37.2
37.4
37.6

PSIG
318
320
322
324
326
328
330
332
334
336
338
340
342
344
346
348
350
352
354
356
358
360
362
364
366
368
370
372
374
376
378
380
382
384
386
388
390
392
394
396
398
400
402
404
406
408
410
412
414
416
418

112

F
100.2
100.7
101.1
101.6
102.0
102.4
102.9
103.3
103.7
104.2
104.6
105.1
105.4
105.8
106.3
106.6
107.1
107.5
107.9
108.3
108.8
109.2
109.6
110.0
110.4
110.8
111.2
111.6
112.0
112.4
112.6
113.1
113.5
113.9
114.3
114.7
115.0
115.5
115.8
116.2
116.6
117.0
117.3
117.7
118.1
118.5
118.8
119.2
119.6
119.9
120.3

C
37.9
38.2
38.4
38.7
38.9
39.1
39.4
39.6
39.8
40.1
40.3
40.6
40.8
41.0
41.3
41.4
41.7
41.9
42.2
42.4
42.7
42.9
43.1
43.3
43.6
43.8
44.0
44.2
44.4
44.7
44.8
45.1
45.3
45.5
45.7
45.9
46.1
46.4
46.6
46.8
47.0
47.2
47.4
47.6
47.8
48.1
48.2
48.4
48.7
48.8
49.1

PSIG
420
422
424
426
428
430
432
434
436
438
440
442
444
446
448
450
452
454
456
458
460
462
464
466
468
470
472
474
476
478
480
482
484
486
488
490
492
494
496
498
500
502
504
506
508
510
512
514
516
518
520

F
120.7
121.0
121.4
121.7
122.1
122.5
122.8
123.2
123.5
123.9
124.2
124.6
124.9
125.3
125.6
126.0
126.3
126.6
127.0
127.3
127.7
128.0
128.3
128.7
129.0
129.3
129.7
130.0
130.3
130.7
131.0
131.3
131.6
132.0
132.3
132.6
132.9
133.3
133.6
133.9
134.0
134.5
134.8
135.2
135.5
135.8
136.1
136.4
136.7
137.0
137.3

C
49.3
49.4
49.7
49.8
50.1
50.3
50.4
50.7
50.8
51.1
51.2
51.4
51.6
51.8
52.0
52.2
52.4
52.6
52.8
52.9
53.2
53.3
53.5
53.7
53.9
54.1
54.3
54.4
54.6
54.8
55.0
55.2
55.3
55.6
55.7
55.9
56.1
56.3
56.4
56.6
56.7
56.9
57.1
57.3
57.5
57.7
57.8
58.0
58.2
58.3
58.5

PSIG
522
524
526
528
530
532
534
536
538
540
544
548
552
556
560
564
568
572
576
580
584
588
592
596
600
604
608
612
616
620
624
628
632
636
640
644
648
652
656
660
664
668
672
676
680
684
688
692
696

F
137.6
137.9
138.3
138.6
138.9
139.2
139.5
139.8
140.1
140.4
141.0
141.6
142.1
142.7
143.3
143.9
144.5
145.0
145.6
146.2
146.7
147.3
147.9
148.4
149.0
149.5
150.1
150.6
151.2
151.7
152.3
152.8
153.4
153.9
154.5
155.0
155.5
156.1
156.6
157.1
157.7
158.2
158.7
159.2
159.8
160.3
160.8
161.3
161.8

C
58.7
58.8
59.1
59.2
59.4
59.6
59.7
59.9
60.1
60.2
60.6
60.9
61.2
61.5
61.8
62.2
62.5
62.8
63.1
63.4
63.7
64.1
64.4
64.7
65.0
65.3
65.6
65.9
66.2
66.5
66.8
67.1
67.4
67.7
68.1
68.3
68.6
68.9
69.2
69.5
69.8
70.1
70.4
70.7
71.0
71.3
71.6
71.8
72.1

APPENDIX E MAINTENANCE SUMMARY AND LOG SHEETS


30RB Maintenance Interval Requirements
WEEKLY
Compressor
Condenser
Controls

Check Oil Level.


Check condenser coils for debris, clean as necessary.
Periodic clean water rinse, especially in coastal and industrial applications.
Review Alarm/Alert History.
MONTHLY

Cooler
Controls

Inspect water pumps.


Check accuracy of thermistors, replace if greater than 2 F (1.2 C) variance from calibrated thermometer.
Check accuracy of transducers, replace if greater than 5 psi (34.47 kPa) variance.
Check refrigerant charge level.

Refrigerant System

Check moisture indicating sight glass for possible refrigerant loss and presence of moisture.
Perform leak test.
QUARTERLY

Compressor
Controls
Condenser
Refrigerant System
Hydronic System

Check crankcase heater operation.


Check chilled water flow switch operation.
Check all condenser fans for proper operation.
Check all refrigerant joints and valves for refrigerant leaks, repair as necessary.
Inspect pump seal, if equipped with a hydronic pump package.
Lubricate pump motor as required.

Starter

Inspect all contactors.

Cooler

Check to be sure that the proper concentration of antifreeze is present in the chilled water loop, if applicable.
Verify that the chilled water loop is properly treated.

ANNUALLY

Check chilled water strainers, clean as necessary.


Check cooler heater operation, if equipped.
Condenser

Check condition of condenser fan blades and that they are securely fastened to the motor shaft.
Perform Service Test to confirm operation of all components.

Controls

Check all electrical connections, tighten as necessary.


Inspect all contactors and relays, replace as necessary.

Refrigerant System
Hydronic System

Check refrigerant filter driers for excessive pressure drop, replace as necessary.
Check pump heater operation if equipped.

NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.

113

APPENDIX E MAINTENANCE SUMMARY AND LOG SHEETS


30RB Weekly Maintenance Log
Plant ___________________________
Machine Model No. ________________

DATE

OIL LEVEL

CHECK
CONDENSER
COIL

CHECK
ALARMS /
FAULTS

OPERATOR
INITIALS

NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.

114

REMARKS

APPENDIX E MAINTENANCE SUMMARY AND LOG SHEETS


30RB Maintenance Log for Monthly, Quarterly, and Annual Checks
Month
Date
Operator
UNIT SECTION
Compressor

Cooler

Condenser

Controls

115
Starter

System

1
/

ACTION
Check Oil Level
Check Crankcase Heater Operation
Send Oil Sample Out for Analysis
Check Cooler Heater Operation
Check Chiller Water Loop
Check Chilled Water Strainers
Record Water Pressure Differential (PSI)
Inspect Water Pumps
Inspect and Clean All Coils
Check all Condesnoer Fans for Proper Operation
Check Condition of Consenser Fan Blades
General Cleaning and Tightening Connections
Check Chilled Water Flow Switch Operation
Perform Service Test
Confirm Accuracy of Pressure Transducers
Confirm Accuracy of Thermistors
General Tightening & Cleaning Connections
Inspect All Contactors
Check Refrigerant Charge Level
Verify Operation of EXVs and Record Position
Record System Super Heat
Check Moisture Sight Glass
Perform Leak Test
Check all Refrigerant Joints and Valves for Refrigerant Leaks
Check Filter Driers

2
/

UNIT
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
PSI
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
0-100%
deg. F
yes/no
yes/no
yes/no
yes/no

Annually
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements
are not covered under warranty.

3
/

4
/

5
/

6
/

7
/

ENTRY

8
/

9
/

10
/ /

11
/ /

12
/ /

APPENDIX E MAINTENANCE SUMMARY AND LOG SHEETS


30RB Seasonal Shutdown Log
Month
Date
Operator
UNIT SECTION
Cooler
Controls

1
/

2
/

3
/

ACTION
Isolate and Drain Cooler
Do Not Disconnect Control Power Unless Cooler is
Completely Drained

NOTES:
1. Equipment failures caused by lack of adherence to the Maintenance Interval Requirements
are not covered under warranty.
2. Refer to Installation Instructions for proper Winterization procedure.

4
/

5
/

6
/

7
/

ENTRY

8
/

9
/

10
/ /

11
/ /

12
/ /

116

APPENDIX F BACNET COMMUNICATIONS OPTION

7 8

2 34

10's

9 0

2 34

7 8

9 0

The following section is used to configure the UPC Open


controller which is used when the BACnet* communications
option is selected. The UPC Open controller is mounted in a
separate enclosure below the main control box.
TO ADDRESS THE UPC OPEN CONTROLLER The
user must give the UPC Open controller an address that is
unique on the BACnet network. Perform the following procedure to assign an address:
1. If the UPC Open controller is powered, pull the screw terminal connector from the controller's power terminals labeled Gnd and HOT. The controller reads the address
each time power is applied to it.
2. Using the rotary switches (see Fig. A and B), set the controller's address. Set the Tens (10's) switch to the tens digit of the address, and set the Ones (1's) switch to the ones
digit.
As an example in Fig. B, if the controllers address is 25,
point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.

1's

Fig. B Address Rotary Switches


BACNET DEVICE INSTANCE ADDRESS The UPC
Open controller also has a BACnet Device Instance address.
This Device Instance MUST be unique for the complete BACnet system in which the UPC Open controller is installed. The
Device Instance is auto generated by default and is derived by
adding the MAC address to the end of the Network Number.
The Network Number of a new UPC Open controller is 16101,
but it can be changed using i-Vu Tools or BACView device.
By default, a MAC address of 20 will result in a Device Instance of 16101 + 20 which would be a Device Instance of
1610120.

BT485
TERMINATOR

BACNET
CONNECTION
(BAS PORT)

POWER LED

Tx1 LED
Rx1 LED

Tx2 LED
Rx2 LED

23

45

01

8
67 9

EIA-485
JUMPERS

01

8
67 9

23

45

BACNET
BAUD RATE
DIP SWITCHES
ADDRESS
ROTARY
SWITCHES
RUN LED
ERROR LED

Fig. A UPC Open Controller

* Sponsored by ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers).

117

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


CONFIGURING THE BAS PORT FOR BACNET MS/
TP Use the same baud rate and communication settings for
all controllers on the network segment. The UPC Open controller is fixed at 8 data bits, No Parity, and 1 Stop bit for this
protocol's communications.
If the UPC Open controller has been wired for power, pull
the screw terminal connector from the controller's power terminals labeled Gnd and HOT. The controller reads the DIP
Switches and jumpers each time power is applied to it.
Set the BAS Port DIP switch DS3 to enable. Set the BAS
Port DIP switch DS4 to E1-485. Set the BMS Protocol DIP
switches DS8 through DS5 to MSTP. See Table A.

Fig. C DIP Switches

Table A SW3 Protocol Switch Settings


for MS/TP
DS8
Off

DS7
Off

DS6
Off

DS5
Off

DS4
On

Wire the controllers on an MS/TP network segment in a daisy-chain configuration. Wire specifications for the cable are
22 AWG (American Wire Gage) or 24 AWG, low-capacitance,
twisted, stranded, shielded copper wire. The maximum length
is 2000 ft.
Install a BT485 terminator on the first and last controller on
a network segment to add bias and prevent signal distortions
due to echoing. See Fig. A, D, and E.
To wire the UPC Open controller to the BAS network:
1. Pull the screw terminal connector from the controller's
BAS Port.
2. Check the communications wiring for shorts and
grounds.
3. Connect the communications wiring to the BAS ports
screw terminals labeled Net +, Net -, and Shield.
NOTE: Use the same polarity throughout the network
segment.
4. Insert the power screw terminal connector into the UPC
Open controller's power terminals if they are not currently connected.
5. Verify communication with the network by viewing a
module status report. To perform a module status report
using the BACview keypad/display unit, press and hold
the FN key then press the . Key.

DS3
Off

Verify that the EIA-485 jumpers below the CCN Port are set
to EIA-485 and 2W.
The example in Fig. C shows the BAS Port DIP Switches
set for 76.8k (Carrier default) and MS/TP.
Set the BAS Port DIP Switches DS2 and DS1 for the appropriate communications speed of the MS/TP network (9600,
19.2k, 38.4k, or 76.8k bps). See Fig. D and Table B.
Table B Baud Selection Table
BAUD RATE
9,600
19,200
38,400
76,800

DS2
Off
On
Off
On

DS1
Off
Off
On
On

WIRING THE UPC OPEN CONTROLLER TO THE MS/


TP NETWORK The UPC Open controller communicates
using BACnet on an MS/TP network segment communications
at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.

Fig. D Network Wiring

118

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)

Fig. E BT485 Terminator Installation

temperature rating specifications list two acceptable alternatives. The Halar specification has a higher temperature rating
and a tougher outer jacket than the SmokeGard specification,
and it is appropriate for use in applications where the user is
concerned about abrasion. The Halar jacket is also less likely to
crack in extremely low temperatures.
NOTE: Use the specified type of wire and cable for maximum
signal integrity.

To install a BT485 terminator, push the BT485 terminator


on to the BT485 connector located near the BACnet connector.
NOTE: The BT485 terminator has no polarity associated with
it.
To order a BT485 terminator, consult Commercial Products
i-Vu Open Control System Master Prices.
MS/TP WIRING RECOMMENDATIONS Recommendations are shown in Tables C and D. The wire jacket and UL

Table C MS/TP Wiring Recommendations


SPECIFICATION
Cable
Conductor
Insulation
Color Code
Twist Lay
Shielding
Jacket
DC Resistance
Capacitance
Characteristic Impedance
Weight
UL Temperature Rating
Voltage
Listing
AWG
CL2P
DC
FEP
NEC
O.D.
TC
UL

RECOMMMENDATION
Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable
22 or 24 AWG stranded copper (tin plated)
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Black/White
2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Aluminum/Mylar shield with 24 AWG TC drain wire
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
15.2 Ohms/1000 feet (50 Ohms/km) nominal
12.5 pF/ft (41 pF/meter) nominal conductor to conductor
100 Ohms nominal
12 lb/1000 feet (17.9 kg/km)
SmokeGard 167F (75C)
Halar -40 to 302F (-40 to 150C)
300 Vac, power limited
UL: NEC CL2P, or better

LEGEND
American Wire Gage
Class 2 Plenum Cable
Direct Current
Fluorinated Ethylene Polymer
National Electrical Code
Outside Diameter
Tinned Copper
Underwriters Laboratories

119

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


Table D Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS
Wire Type

RECOMMENDED VENDORS AND PART NUMBERS


Connect Air
Contractors
Belden RMCORP Wire and Cable
International

Description

22 AWG, single twisted shielded pair, low capacitance, CL2P,


TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.
MS/TP
Network (RS-485) 24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
Rnet
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
AWG
CL2P
CMP
FEP
TC

W221P-22227

25160PV

CLP0520LC

W241P-2000F

82841

25120-OR

W184C-2099BLB

6302UE

21450

CLP0442

LEGEND
American Wire Gage
Class 2 Plenum Cable
Communications Plenum Rated
Fluorinated Ethylene Polymer
Tinned Copper

number and CCN Bus number. The factory default settings for
CCN Element and CCN Bus number are 1 and 0 respectively.
If modifications to the default Element and Bus number are
required, both the ComfortLink and UPC Open configurations
must be changed.
The following configurations are used to set the CCN Address and Bus number in the ComfortLink control. These configurations can be changed using the scrolling marquee display
or accessory Navigator handheld device.
ConfigurationCCNCCN.A (CCN Address)
ConfigurationCCNCCN.B (CCN Bus Number)
The following configurations are used to set the CCN Address and Bus Number in the UPC Open controller. These configurations can be changed using the accessory BACview6 display.
Navigation: BACviewCCN
Home: Element Comm Stat
Element: 1
Bus: 0

LOCAL ACCESS TO THE UPC OPEN CONTROLLER The user can use a BACview6 handheld keypad display unit or the Virtual BACview software as a local user interface to an Open controller. These items let the user access the
controller network information. These are accessory items and
do not come with the UPC Open controller.
The BACview6 unit connects to the local access port on the
UPC Open controller. See Fig. F. The BACview software must
be running on a laptop computer that is connected to the local
access port on the UPC Open controller. The laptop will require an additional USB link cable for connection.
See the BACview Installation and User Guide for instructions on connecting and using the BACview6 device.
To order a BACview6 Handheld (BV6H), consult Commercial Products i-Vu Open Control System Master Prices.
CONFIGURING THE UPC OPEN CONTROLLER'S
PROPERTIES The UPC Open device and ComfortLink
control must be set to the same CCN Address (Element)

Fig. F BACview6 Device Connection

120

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


If the UPC Open is used with the chiller application of
Lead/Lag/Standby, all chillers and UPC Open's CCN element
numbers must be changed to a unique number in order to follow CCN specifications. In this application, there can only be a
maximum of 3 UPC Open controllers on a CCN bus.
For the CCN Alarm Acknowledger configuration, the UPC
Open defaults to CCN Acknowledger. If a Chiller Lead/Lag/
Standby application is being used, then the Carrier technician
must change the configuration to only one CCN Acknowledger
on the CCN bus.
For the CCN Time Broadcaster configuration, the UPC
Open defaults to CCN Time Broadcaster. If the Chiller Lead/
Lag/Standby application is used, then the Carrier technician
must change the configuration to only one CCN Time Broadcaster on the CCN bus.
TROUBLESHOOTING If there are problems wiring or
addressing the UPC Open controller, contact Carrier Technical
Support.
COMMUNICATION LEDS The LEDs indicate if the
controller is communicating with the devices on the network.

See Tables E and F. The LEDs should reflect communication


traffic based on the baud rate set. The higher the baud rate the
more solid the LEDs become. See Fig. A for location of LEDs
on UPC Open module.
REPLACING THE UPC OPEN BATTERY The UPC
Open controller's 10-year lithium CR2032 battery provides a
minimum of 10,000 hours of data retention during power
outages.
IMPORTANT: Power must be ON to the UPC Open when
replacing the battery, or the date, time, and trend data will
be lost.
Remove the battery from the controller, making note of the
battery's polarity. Insert the new battery, matching the battery's
polarity with the polarity indicated on the UPC Open
controller.
NETWORK POINTS LIST The points list for the controller is shown in Table G.

Table E LED Status Indicators


LED
Power
Rx
Tx
Run
Error

STATUS
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on
the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition
that caused the fault returns to normal.
Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.
Lights when the controller transmits data to the network segment; there is an Rx LED for Ports 1 and 2.
Lights based on controller status. See Table F.
Lights based on controller status. See Table F.

Table F Run and Error LEDs Controller and Network Status Indication
RUN LED
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
5 flashes per second
5 flashes per second
7 flashes per second
14 flashes per second

ERROR LED
Off
2 flashes, alternating with Run LED
3 flashes, then off
1 flash per second
On
On
Off
7 flashes per second, alternating with Run LED
14 flashes per second, alternating with Run LED

121

STATUS
Normal
Five minute auto-restart delay after system error
Controller has just been formatted
Controller is alone on the network
Exec halted after frequent system errors or control programs halted
Exec start-up aborted, Boot is running
Firmware transfer in progress, Boot is running
Ten second recovery period after brownout
Brownout

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


Table G Network Points List
READ/
WRITE
R
R
R
R
R
R

UNITS

Active Demand Limit Val


Air Cond Entering Valv A
Air Cond Entering Valv B
Air Cond Leaving Valve A
Air Cond Leaving Valve B
Alarm Relay Status

POINT
NAME
DEM_LIM
hr_ea_a
hr_ea_b
hr_la_a
hr_la_b
ALARMOUT

%
N/A
N/A
N/A
N/A
N/A

DEFAULT
VALUE
N/A
N/A
N/A
N/A
N/A
N/A

Alarm State

ALM

N/A

N/A

Alert Relay Status


Auto Changeover Active
Boiler Active
Boiler Command
CCN Chiller Start/Stop
Chiller Capacity Signal
Chiller Occupied?
CHWS Temperature - Prime Variable
Cir A Compressor 1 Heater Out
Cir A Compressor 1 Output
Cir A Compressor 2 Heater Out
Cir A Compressor 2 Output
Cir A Compressor 3 Heater Out
Cir A Compressor 3 Output
Cir A Compressor 4 Heater Out
Cir A Compressor 4 Output
Cir A Crank Heater Current Cp1
Cir A Crank Heater Current Cp2
Cir A Crank Heater Current Cp3
Cir A Crank Heater Current Cp4
Cir A Discharge Pressure
Cir A EXV Position
Cir A Fan Output DO # 1
Cir A Fan Output DO # 2
Cir A Fan Output DO # 3
Cir A Fan Output DO # 4
Cir A Fan Output DO # 5
Cir A Fan Output DO # 6
Cir A Fan Staging Number
Cir A Head Press Actuator Pos
Cir A Hot Gas Bypass Output
Cir A Motor Thermistor Comp 1
Cir A Motor Thermistor Comp 2
Cir A Motor Thermistor Comp 3
Cir A Motor Thermistor Comp 4
Cir A Percent Total Capacity
Cir A Saturated Condensing Tmp
Cir A Saturated Suction Temp
Cir A Suction Gas Temperature
Cir A Suction Pressure
Cir A Suction Superheat Temp
Cir B Compressor 1 Heater Out
Cir B Compressor 1 Output
Cir B Compressor 2 Heater Out
Cir B Compressor 2 Output
Cir B Compressor 3 Heater Out
Cir B Compressor 3 Output

ALERT
Mode_12
Mode_17
BOILER
CHIL_S_S
CAPT_010
CHIL_OCC
CHWSTEMP
cp_a1_ht
CP_A1
cp_a2_ht
CP_A2
cp_a3_ht
CP_A3
cp_a4_ht
CP_A4
cpa1_cur
cpa2_cur
cpa3_cur
cpa4_cur
DP_A
EXV_A
fan_a1
fan_a2
fan_a3
fan_a4
fan_a5
fan_a6
FAN_ST_A
hd_pos_a
HGBP_V_A
cpa1_tmp
cpa2_tmp
cpa3_tmp
cpa4_tmp
CAPA_T
SCT_A
SST_A
SUCT_T_A
SP_A
SH_A
cp_b1_ht
CP_B1
cp_b2_ht
CP_B2
cp_b3_ht
CP_B3

R
R
R
R
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

N/A
N/A
N/A
N/A
N/A
volts
N/A
F
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
amps
amps
amps
amps
psi
%
N/A
N/A
N/A
N/A
N/A
N/A
N/A
%
N/A
ohms
ohms
ohms
ohms
%
F
F
F
psi
^F
N/A
N/A
N/A
N/A
N/A
N/A

N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

POINT DESCRIPTION

CCN
CHWS
DGT
DO
EWT

LEGEND
Carrier Comfort Network
Chilled Water Setpoint
Discharge Gas Temperature
Discrete Output
Entering Water Temperature

EXV
OAT
R
W

Electronic Expansion Valve


Outdoor Air Temperature
Read
Write

122

RANGE
0-100
On/Off
On/Off
On/Off
On/Off
On/Off
0=Normal,
1=Partial,
2=Shutdown
On/Off
Yes/No
Yes/No
On/Off
Enable/Disable
nn.n
Yes/No
nnn.n
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
0-100
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-6
0-100
On/Off
nnnn
nnnn
nnnn
nnnn
0-100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off

BACNET
OBJECT ID
AV:1
BV:4
BV:5
BV:6
BV:7
BV:8

BACNET
OBJECT NAME
dem_lim_1
hr_ea_a_1
hr_ea_b_1
hr_la_a_1
hr_la_b_1
alarmout_1

AV:2

alm_1

BV:9
BV:10
BV:11
BV:12
BV:1500
AV:3
BV:1501
AV:1612
BV:13
BV:14
BV:15
BV:16
BV:17
BV:18
BV:19
BV:20
AV:4
AV:5
AV:6
AV:7
AV:1601
AV:8
BV:21
BV:22
BV:23
BV:24
BV:25
BV:26
AV:9
AV:10
BV:27
AV:11
AV:12
AV:13
AV:14
AV:15
AV:1602
AV:1603
AV:16
AV:1600
AV:17
BV:28
BV:29
BV:30
BV:31
BV:32
BV:33

alert_1
mode_12_1
mode_17_1
boiler_1
chil_s_s_1
capt_010_1
chil_occ_1
chwstemp_1
cp_a1_ht_1
cp_a1_1
cp_a2_ht_1
cp_a2_1
cp_a3_ht_1
cp_a3_1
cp_a4_ht_1
cp_a4_1
cpa1_cur_1
cpa2_cur_1
cpa3_cur_1
cpa4_cur_1
dp_a_1
exv_a_1
fan_a1_1
fan_a2_1
fan_a3_1
fan_a4_1
fan_a5_1
fan_a6_1
fan_st_a_1
hd_pos_a_1
hgbp_v_a_1
cpa1_tmp_1
cpa2_tmp_1
cpa3_tmp_1
cpa4_tmp_1
capa_t_1
sct_a_1
sst_a_1
suct_t_a_1
sp_a_1
sh_a_1
cp_b1_ht_1
cp_b1_1
cp_b2_ht_1
cp_b2_1
cp_b3_ht_1
cp_b3_1

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


Table G Network Points List (cont)
POINT DESCRIPTION
Cir B Compressor 4 Heater Out
Cir B Compressor 4 Output
Cir B Crank Heater Current Cp1
Cir B Crank Heater Current Cp2
Cir B Crank Heater Current Cp3
Cir B Crank Heater Current Cp4
Cir B Discharge Pressure
Cir B EXV Position
Cir B Fan Output DO # 1
Cir B Fan Output DO # 2
Cir B Fan Output DO # 3
Cir B Fan Output DO # 4
Cir B Fan Output DO # 5
Cir B Fan Output DO # 6
Cir B Fan Staging Number
Cir B Head Press Actuator Pos
Cir B Hot Gas Bypass Output
Cir B Motor Thermistor Comp 1
Cir B Motor Thermistor Comp 2
Cir B Motor Thermistor Comp 3
Cir B Motor Thermistor Comp 4
Cir B Percent Total Capacity
Cir B Saturated Condensing Tmp
Cir B Saturated Suction Temp
Cir B Suction Gas Temperature
Cir B Suction Pressure
Cir B Suction Superheat Temp
Cir C Compressor 1 Heater Out
Cir C Compressor 1 Output
Cir C Compressor 2 Heater Out
Cir C Compressor 2 Output
Cir C Compressor 3 Heater Out
Cir C Compressor 3 Output
Cir C Compressor 4 Heater Out
Cir C Compressor 4 Output
Cir C Crank Heater Current Cp1
Cir C Crank Heater Current Cp2
Cir C Crank Heater Current Cp3
Cir C Crank Heater Current Cp4
Cir C Discharge Pressure
Cir C EXV Position
Cir C Fan Output DO # 1
Cir C Fan Output DO # 2
Cir C Fan Output DO # 3
Cir C Fan Output DO # 4
Cir C Fan Output DO # 5
Cir C Fan Output DO # 6
Cir C Fan Staging Number
Cir C Head Press Actuator Pos
Cir C Hot Gas Bypass Output
Cir C Motor Thermistor Comp 1
Cir C Motor Thermistor Comp 2
Cir C Motor Thermistor Comp 3
Cir C Motor Thermistor Comp 4
CCN
CHWS
DGT
DO
EWT

POINT
NAME
cp_b4_ht
CP_B4
cpb1_cur
cpb2_cur
cpb3_cur
cpb4_cur
DP_B
EXV_B
fan_b1
fan_b2
fan_b3
fan_b4
fan_b5
fan_b6
FAN_ST_B
hd_pos_b
HGBP_V_B
cpb1_tmp
cpb2_tmp
cpb3_tmp
cpb4_tmp
CAPB_T
SCT_B
SST_B
UCT_T_B
SP_B
SH_B
cp_c1_ht
CP_C1
cp_c2_ht
CP_C2
cp_c3_ht
CP_C3
cp_c4_ht
CP_C4
cpc1_cur
cpc2_cur
cpc3_cur
cpc4_cur
DP_C
EXV_C
fan_c1
fan_c2
fan_c3
fan_c4
fan_c5
fan_c6
FAN_ST_C
hd_pos_c
HGBP_V_C
cpc1_tmp
cpc2_tmp
cpc3_tmp
cpc4_tmp

LEGEND
Carrier Comfort Network
Chilled Water Setpoint
Discharge Gas Temperature
Discrete Output
Entering Water Temperature

EXV
OAT
R
W

READ/
WRITE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UNITS
N/A
N/A
amps
amps
amps
amps
psi
%
N/A
N/A
N/A
N/A
N/A
N/A
N/A
%
N/A
ohms
ohms
ohms
ohms
%
F
F
F
psi
psi
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
amps
amps
amps
amps
psi
%
N/A
N/A
N/A
N/A
N/A
N/A
N/A
%
N/A
ohms
ohms
ohms
ohms

DEFAULT
VALUE
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

Electronic Expansion Valve


Outdoor Air Temperature
Read
Write

123

RANGE
On/Off
On/Off
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
0-100
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-6
0-100
On/Off
nnnn
nnnn
nnnn
nnnn
0-100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
0-100
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-6
0-100
On/Off
nnnn
nnnn
nnnn
nnnn

BACNET
OBJECT ID
BV:34
BV:35
AV:18
AV:19
AV:20
AV:21
AV:1605
AV:22
BV:36
BV:37
BV:38
BV:39
BV:40
BV:41
AV:23
AV:24
BV:42
AV:25
AV:26
AV:27
AV:28
AV:29
AV:30
AV:31
AV:32
AV:33
AV:34
BV:43
BV:44
BV:45
BV:46
BV:47
BV:48
BV:49
BV:50
AV:35
AV:36
AV:37
AV:38
AV:1609
AV:39
BV:51
BV:52
BV:53
BV:54
BV:55
BV:56
AV:40
AV:41
BV:57
AV:42
AV:43
AV:44
AV:45

BACNET
OBJECT NAME
cp_b4_ht_1
cp_b4_1
cpb1_cur_1
cpb2_cur_1
cpb3_cur_1
cpb4_cur_1
dp_b_1
exv_b_1
fan_b1_1
fan_b2_1
fan_b3_1
fan_b4_1
fan_b5_1
fan_b6_1
fan_st_b_1
hd_pos_b_1
hgbp_v_b_1
cpb1_tmp_1
cpb2_tmp_1
cpb3_tmp_1
cpb4_tmp_1
capb_t_1
sct_b_1
sst_b_1
suct_t_b_1
sp_b_1
sh_b_1
cp_c1_ht_1
cp_c1_1
cp_c2_ht_1
cp_c2_1
cp_c3_ht_1
cp_c3_1
cp_c4_ht_1
cp_c4_1
cpc1_cur_1
cpc2_cur_1
cpc3_cur_1
cpc4_cur_1
dp_c_1
exv_c_1
fan_c1_1
fan_c2_1
fan_c3_1
fan_c4_1
fan_c5_1
fan_c6_1
fan_st_c_1
hd_pos_c_1
hgbp_v_c_1
cpc1_tmp_1
cpc2_tmp_1
cpc3_tmp_1
cpc4_tmp_1

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


Table G Network Points List (cont)
READ/
WRITE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UNITS

Cir C Percent Total Capacity


Cir C Saturated Condensing Tmp
Cir C Saturated Suction Temp
Cir C Suction Gas Temperature
Cir C Suction Pressure
Cir C Suction Superheat Temp
Circuit A Fan #1 Hours
Circuit A Fan #2 Hours
Circuit A Fan #3 Hours
Circuit A Fan #4 Hours
Circuit A Fan #5 Hours
Circuit A Fan #6 Hours
Circuit B Fan #1 Hours
Circuit B Fan #2 Hours
Circuit B Fan #3 Hours
Circuit B Fan #4 Hours
Circuit B Fan #5 Hours
Circuit B Fan #6 Hours
Circuit C Fan #1 Hours
Circuit C Fan #2 Hours
Circuit C Fan #3 Hours
Circuit C Fan #4 Hours
Circuit C Fan #5 Hours
Circuit C Fan #6 Hours
Circuit Loading Sequence
Compressor A1 Hours
Compressor A1 Starts
Compressor A2 Hours
Compressor A2 Starts
Compressor A3 Hours
Compressor A3 Starts
Compressor A4 Hours
Compressor A4 Starts
Compressor B1 Hours
Compressor B1 Starts
Compressor B2 Hours
Compressor B2 Starts
Compressor B3 Hours
Compressor B3 Starts
Compressor B4 Hours
Compressor B4 Starts
Compressor C1 Hours
Compressor C1 Starts
Compressor C2 Hours
Compressor C2 Starts
Compressor C3 Hours
Compressor C3 Starts
Compressor C4 Hours
Compressor C4 Starts
Control Point
Controlled Water Temp

POINT
NAME
CAPC_T
SCT_C
SST_C
SUCT_T_C
SP_C
SH_C
hr_fana1
hr_fana2
hr_fana3
hr_fana4
hr_fana5
hr_fana6
hr_fanb1
hr_fanb2
hr_fanb3
hr_fanb4
hr_fanb5
hr_fanb6
hr_fanc1
hr_fanc2
hr_fanc3
hr_fanc4
hr_fanc5
hr_fanc6
lead_cir
HR_CP_A1
st_cp_a1
HR_CP_A2
st_cp_a2
HR_CP_A3
st_cp_a3
HR_CP_A4
st_cp_a4
HR_CP_B1
st_cp_b1
HR_CP_B2
st_cp_b2
HR_CP_B3
st_cp_b3
HR_CP_B4
st_cp_b4
HR_CP_C1
st_cp_c1
HR_CP_C2
st_cp_c2
HR_CP_C3
st_cp_c3
HR_CP_C4
st_cp_c4
CTRL_PNT
CTRL_WT

%
F
F
F
psi
^F
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
hours
N/A
F
F

DEFAULT
VALUE
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

Cooler Fluid Type

flui_typ

N/A

POINT DESCRIPTION

CCN
CHWS
DGT
DO
EWT

LEGEND
Carrier Comfort Network
Chilled Water Setpoint
Discharge Gas Temperature
Discrete Output
Entering Water Temperature

EXV
OAT
R
W

Electronic Expansion Valve


Outdoor Air Temperature
Read
Write

124

RANGE
0-100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
0-3
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnn.n
nnn.n
1=Water,
2=Brine
3=Low Brine

BACNET
OBJECT ID
AV:46
AV:47
AV:48
AV:49
AV:50
AV:51
AV:52
AV:53
AV:54
AV:55
AV:56
AV:57
AV:58
AV:59
AV:60
AV:61
AV:62
AV:63
AV:64
AV:65
AV:66
AV:67
AV:68
AV:69
AV:70
AV:71
AV:72
AV:73
AV:74
AV:75
AV:76
AV:77
AV:78
AV:79
AV:80
AV:81
AV:82
AV:83
AV:84
AV:85
AV:86
AV:87
AV:88
AV:89
AV:90
AV:91
AV:92
AV:93
AV:94
AV:96
AV:95

BACNET
OBJECT NAME
capc_t_1
sct_c_1
sst_c_1
suct_t_c_1
sp_c_1
sh_c_1
hr_fana1_1
hr_fana2_1
hr_fana3_1
hr_fana4_1
hr_fana5_1
hr_fana6_1
hr_fanb1_1
hr_fanb2_1
hr_fanb3_1
hr_fanb4_1
hr_fanb5_1
hr_fanb6_1
hr_fanc1_1
hr_fanc2_1
hr_fanc3_1
hr_fanc4_1
hr_fanc5_1
hr_fanc6_1
lead_cir_1
hr_cp_a1_1
st_cp_a1_1
hr_cp_a2_1
st_cp_a2_1
hr_cp_a3_1
st_cp_a3_1
hr_cp_a4_1
st_cp_a4_1
hr_cp_b1_1
st_cp_b1_1
hr_cp_b2_1
st_cp_b2_1
hr_cp_b3_1
st_cp_b3_1
hr_cp_b4_1
st_cp_b4_1
hr_cp_c1_1
st_cp_c1_1
hr_cp_c2_1
st_cp_c2_1
hr_cp_c3_1
st_cp_c3_1
hr_cp_c4_1
st_cp_c4_1
ctrl_pnt_1
ctrl_wt_1

AV:97

flui_typ_1

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


Table G Network Points List (cont)
READ/
WRITE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UNITS

Cooler Heater Active


Cooler Heater Command
Cooler Pumps Rotation
Cooler Pumps Sequence
Cooling Ice Setpoint
Cooling Ramp Loading
Cooling Reset Deg. Value
Cooling Setpoint 1
Cooling Setpoint 2
Critical Alarm Status
Current Full Reset Value
Current No Reset Value
Current Setpoint
Defrost Active On Cir A
Defrost Active On Cir B
Delta T Full Reset Value
Delta T No Reset Value
Demand Limit Active

POINT
NAME
Mode_06
COOLHEAT
Mode_07
pump_seq
ice_sp
cramp_sp
cr_deg
csp1
csp2
CRITICAL
v_cr_fu
v_cr_no
SP
Mode_19
Mode_20
dt_cr_fu
dt_cr_no
Mode_04

N/A
N/A
N/A
N/A
^F
^F
F
F
min
N/A
ma
ma
F
N/A
N/A
^F
^F
N/A

DEFAULT
VALUE
N/A
N/A
N/A
0
1
0
44
44
N/A
N/A
0
0
N/A
N/A
N/A
0
0
N/A

Demand Limit Type Select

lim_sel

R/W

N/A

Electric Heat Active


Electrical Box Safety
Electrical Heat Stage
Element Comm Status
Emergency Stop
Equipment Alarm
External Temperature
Flow Checked if Pump Off
Free Cooling Active
Free Cooling Disable Sw.
Free Cooling Disable?
Heat Reclaim Pump Hours
Heat Reclaim Select

Mode_15
ELEC_BOX
EHS_STEP

OAT
pump_loc
Mode_13
FC_SW
FC_DSBLE
hr_hpump
RECL_SEL

R
R
R
R
R/W
R
R
R/W
R
R
R
R
R

N/A
N/A
N/A
N/A
N/A
N/A
F
N/A
N/A
N/A
N/A
hours
N/A

N/A
N/A
N/A
N/A
N/A
N/A
N/A
Yes
N/A
N/A
N/A
N/A
N/A

Heat/Cool Select

HC_SEL

R/W

N/A

N/A

Heat/Cool Status

HEATCOOL

N/A

N/A

Heating Low EWT Lockout


High DGT Circuit A
High DGT Circuit B
High DGT Circuit C
High Pres Override Cir A
High Pres Override Cir B
High Pres Override Cir C
Ice Done Storage Switch
Ice Mode in Effect
Interlock Status
Lag Capacity Limit Value
Limit 4-20mA Signal
Limit Switch 1 Status
Limit Switch 2 Status
Local Schedule

Mode_16
Mode_24
Mode_25
Mode_26
Mode_27
Mode_28
Mode_29
ICE_SW
Mode_18
LOCK_1
LAG_LIM
LIM_ANAL
LIM_SW1
LIM_SW2

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
%
ma
N/A
N/A
N/A

N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

POINT DESCRIPTION

CCN
CHWS
DGT
DO
EWT

EMSTOP

LEGEND
Carrier Comfort Network
Chilled Water Setpoint
Discharge Gas Temperature
Discrete Output
Entering Water Temperature

EXV
OAT
R
W

Electronic Expansion Valve


Outdoor Air Temperature
Read
Write

125

RANGE
Yes/No
On/Off
Yes/No
0-4
0.2-2.0
-30 ->30
-20.0->78.8
-20.0->78.8
nn
On/Off
0-20
0-20
nnn.n
Yes/No
Yes/No
0-25
0-25
Yes/No
0=None,
1=Switch
control,
2=4-20mA
Control
0-4/Off
Yes/No
Open/Close
Enable/Disable
nnn.n
Yes/No
Yes/No
Yes/No
Yes/No
nnnnn
Yes/No
0=Cool,
1=Heat,
2=Auto
0=Cool,
1=Heat
2=Stand-by,
3=Both
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Open/Close
Yes/No
Open/Close
nnn
nn.n
Open/Close
Open/Close

BACNET
OBJECT ID
BV:58
BV:59
BV:60
AV:98
AV:99
AV:100
AV:101
AV:102
AV:103
BV:61
AV:104
AV:105
AV:3500
BV:62
BV:63
AV:106
AV:107
BV:64

BACNET
OBJECT NAME
mode_06_1
coolheat_1
mode_07_1
pump_seq_1
ice_sp_1
cramp_sp_1
cr_deg_1
csp1_1
csp2_1
critical_1
v_cr_fu_1
v_cr_no_1
chws_sp_1
mode_19_1
mode_20_1
dt_cr_fu_1
dt_cr_no_1
mode_04_1

AV:108

lim_sel_1

BV:67
BV:65
BV:66
BV:2999
BV:68
BV:146
AV:109
BV:69
BV:70
BV:72
BV:71
AV:112
BV:74

mode_15_1
elec_box_1
ehs_step_1
element_stat_1
emstop_1
element_alarm_1
oat_1
pump_loc_1
mode_13_1
fc_sw_1
fc_dsble_1
hr_hpump_1
recl_sel_1

AV:110

hc_sel_1

AV:111

heatcool_1

BV:73
BV:75
BV:76
BV:77
BV:78
BV:79
BV:80
BV:81
BV:82
BV:83
AV:113
AV:114
BV:84
BV:85
BV:2

mode_16_1
mode_24_1
mode_25_1
mode_26_1
mode_27_1
mode_28_1
mode_29_1
ice_sw_1
mode_18_1
lock_1_1
lag_lim_1
lim_anal_1
lim_sw1_1
lim_sw2_1
schedule_1

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


Table G Network Points List (cont)
READ/
WRITE
R
R
R
R/W
R/W
R
R

UNITS

Low Suction Circuit A


Low Suction Circuit B
Low Suction Circuit C
mA For 0% Demand Limit
mA For 100% Demand Limit
Machine Operating Hours
Machine Starts Number

POINT
NAME
Mode_21
Mode_22
Mode_23
lim_ze
lim_mx
HR_MACH
st_mach

N/A
N/A
N/A
mA
mA
hours
N/A

DEFAULT
VALUE
N/A
N/A
N/A
0
0
N/A
N/A

Master/Slave Select

ms_sel

R/W

N/A

Minutes Left for Start


Night Low Noise Active
OAT Full Reset Value
OAT No Reset Value
Occupied Override Switch
On/Off - Remote Switch
Optional Space Temp
Pass For All User Config
Percent Total Capacity
Pump Auto Rotation Delay
Pump Periodic Start
Pump Run Status
Pump Sticking Protection
Pumpdown Pressure Cir A
Pumpdown Pressure Cir B
Pumpdown Saturated Tmp A
Pumpdown Saturated Tmp B
Ramp Loading Active
Ramp Loading Select
Ready or Running Status
Reclaim Active
Reclaim Condenser Flow
Reclaim Condenser Heater
Reclaim Condenser Pump
Reclaim Condenser Pump
Reclaim Deadband
Reclaim Entering Fluid
Reclaim Leaving Fluid
Reclaim Setpoint
Reclaim Status Circuit A
Reclaim Status Circuit B
Reclaim Valve Position
Remote Heat/Cool Switch
Remote Interlock Status
Remote Reclaim Switch
Remote Setpoint Switch
Reset in Effect
Reset/Setpoint 4-20mA In
Rotate Pumps Now?

min_left
Mode_09
oatcr_fu
oatcr_no
OCC_OVSW
ONOFF_SW
SPACETMP
all_pass
CAP_T
pump_del
Mode_08
PUMP_DEF
pump_per
PD_P_A
PD_P_B
hr_sat_a
hr_sat_b
Mode_05
ramp_sel
READY
Mode_14
condflow
cond_htr
CONDPUMP
COND_PMP
hr_deadb
HR_EWT
HR_LWT
rsp
hrstat_a
hrstat_b
hr_v_pos
HC_SW
REM_LOCK
RECL_SW
SETP_SW
Mode_03
SP_RESET
ROT_PUMP

R
R
R
R
R
R
R
R/W
R
R
R
R
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R
R
R/W
R
R
R
R
R
R
R
R
R
R

min
N/A
F
F
N/A
N/A
F
N/A
%
hours
N/A
N/A
N/A
psi
psi
F
F
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
^F
F
F
F
N/A
N/A
%
N/A
N/A
N/A
N/A
N/A
ma
N/A

N/A
N/A
14
0
N/A
N/A
N/A
No
N/A
48
N/A
N/A
No
N/A
N/A
N/A
N/A
N/A
No
N/A
N/A
N/A
N/A
N/A
N/A
9.0
N/A
N/A
122
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

POINT DESCRIPTION

CCN
CHWS
DGT
DO
EWT

LEGEND
Carrier Comfort Network
Chilled Water Setpoint
Discharge Gas Temperature
Discrete Output
Entering Water Temperature

EXV
OAT
R
W

Electronic Expansion Valve


Outdoor Air Temperature
Read
Write

126

RANGE
Yes/No
Yes/No
Yes/No
0-20
0-20
nnnnn
nnnnn
0= Disable,
1=Master,
2=Slave
0-15
Yes/No
14-125
0-25
Open/Close
Open/Close
nnn.n
No/Yes
nnn
24-3000
Yes/No
Open/Close
No/Yes
nnn.n
nnn.n
n
n
Yes/No
No/Yes
On/Off
Yes/No
On/Off
On/Off
On/Off
On/Off
5-27
nnn.n
nnn.n
95-122
n
n
nnn.n
Open/Close
Open/Close
Open/Close
Open/Close
Yes/No
nn.n
Yes/No

BACNET
OBJECT ID
BV:86
BV:87
BV:88
AV:117
AV:118
AV:115
AV:116

BACNET
OBJECT NAME
mode_21_1
mode_22_1
mode_23_1
lim_ze_1
lim_mx_1
hr_mach_1
st_mach_1

AV:119

ms_sel_1

AV:120
BV:89
AV:121
AV:122
BV:90
BV:91
AV:123
BV:92
AV:1700
AV:124
BV:93
BV:94
BV:95
AV:125
AV:126
AV:127
AV:128
BV:96
BV:97
BV:98
BV:99
BV:100
BV:101
BV:102
BV:103
AV:129
AV:130
AV:131
AV:132
AV:133
AV:134
AV:135
BV:104
BV:105
BV:106
BV:107
BV:108
AV:136
BV:109

min_left_1
mode_09_1
oatcr_fu_1
oatcr_no_1
occ_ovsw_1
onoff_sw_1
spacetmp_1
all_pass_1
cap_t_1
pump_del_1
mode_08_1
pump_def_1
pump_per_1
pd_p_a_1
pd_p_b_1
hr_sat_a_1
hr_sat_b_1
mode_05_1
ramp_sel_1
ready_1
mode_14_1
condflow_1
cond_htr_1
condpump_1
cond_pmp_1
hr_deadb_1
hr_ewt_1
hr_lwt_1
rsp_1
hrstat_a_1
hrstat_b_1
hr_v_pos_1
hc_sw_1
rem_lock_1
recl_sw_1
setp_sw_1
mode_03_1
sp_reset_1
rot_pump_1

APPENDIX F BACNET COMMUNICATIONS OPTION (cont)


Table G Network Points List (cont)
POINT
NAME

POINT DESCRIPTION

UNITS

DEFAULT
VALUE

RANGE

BACNET
OBJECT ID

BACNET
OBJECT NAME

0=Off,
1=Running
2=Stopping,
3= Delay
4=Tripout,
5=Ready
6=Override,
7=Defrost
8=Run Test,
9=Test
On/Off
Yes/No
Yes/No

AV:137

status_1

BV:110
BV:111
BV:112

running_1
mode_02_1
sp_occ_1

Run Status

STATUS

N/A

N/A

Running Status
Second Setpoint in Use
Setpoint Occupied?

RUNNING
Mode_02
SP_OCC
SHUTDOWN
spacr_fu
spacr_no
seq_typ
st_cp_mx
st_cp_av
Mode_01
hr_subta
hr_subtb
hr_subca
hr_subcb
Mode_30
Mode_31
Mode_32
lim_sp1
lim_sp2
lim_sp3

R
R
R

N/A
N/A
N/A

N/A
N/A
N/A

N/A

N/A

On/Off

BV:113

shutdown_1

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

F
F
N/A
N/A
N/A
N/A
F
F
F
F
N/A
N/A
N/A
%
%
%
N/A
N/A
N/A
N/A
min
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
F
F
N/A
hours
N/A
hours

14
14
No
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
100
100
100
N/A
N/A
N/A
N/A
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

14-125
14-125
No/Yes
nnnnn
nnnnn
Yes/No
nnn.n
nnn.n
nnn.n
nnn.n
Yes/No
Yes/No
Yes/No
0-100
0-100
0-100

AV:138
AV:139
BV:114
AV:141
AV:140
BV:115
AV:142
AV:143
AV:144
AV:145
BV:116
BV:117
BV:118
AV:146
AV:147
AV:148
AV:9006
BV:3
BV:119
AV:80001
AV:149
AV:2901
AV:2902
AV:2903
AV:2904
AV:2905
BV:2911
BV:2912
BV:2913
BV:2914
BV:2915
BV:120
BV:121
BV:122
BV:123
AV:150
AV:151
BV:124
AV:152
BV:125
AV:153

spacr_fu_1
spacr_no_1
seq_typ_1
st_cp_mx_1
st_cp_av_1
mode_01_1
hr_subta_1
hr_subtb_1
hr_subca_1
hr_subcb_1
mode_30_1
mode_31_1
mode_32_1
lim_sp1_1
lim_sp2_1
lim_sp3_1
cool_demand_level_1
dem_lmt_act_1
mode_10_1
mstr_oa_temp_1
off_on_d_1
user_analog_1_1
user_analog_2_1
user_analog_3_1
user_analog_4_1
user_analog_5_1
user_binary_1_1
user_binary_2_1
user_binary_3_1
user_binary_4_1
user_binary_5_1
hr_ew_a_1
hr_ew_b_1
hr_lw_a_1
hr_lw_b_1
ewt_1
lwt_1
cpump_1_1
hr_cpum1_1
cpump_2_1
hr_cpum2_1

Shutdown Indicator State


Space T Full Reset Value
Space T No Reset Value
Staged Loading Sequence
Starts Max During 1 Hour
Starts/hr From Last 24 h
Startup Delay in Effect
Sub Condenser Temp Cir A
Sub Condenser Temp Cir B
Subcooling Temperature A
Subcooling Temperature B
Superheat Override Cir A
Superheat Override Cir B
Superheat Override Cir C
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
System Cooling Demand Level
System Demand Limiting
System Manager Active
System OAT Master
Unit Off to On Delay
User Defined Analog 1
User Defined Analog 2
User Defined Analog 3
User Defined Analog 4
User Defined Analog 5
User Defined Binary 1
User Defined Binary 2
User Defined Binary 3
User Defined Binary 4
User Defined Binary 5
Water Cond Enter Valve A
Water Cond Enter Valve B
Water Cond Leaving Val A
Water Cond Leaving Val B
Water Exchanger Entering Temp
Water Exchanger Leaving Temp
Water Pump #1 Command
Water Pump #1 Hours
Water Pump #2 Command
Water Pump #2 Hours
CCN
CHWS
DGT
DO
EWT

READ/
WRITE

Mode_10
/off_on_d

hr_ew_a
hr_ew_b
hr_lw_a
hr_lw_b
EWT
LWT
CPUMP_1
hr_cpum1
CPUMP_2
hr_cpum2

LEGEND
Carrier Comfort Network
Chilled Water Setpoint
Discharge Gas Temperature
Discrete Output
Entering Water Temperature

EXV
OAT
R
W

Electronic Expansion Valve


Outdoor Air Temperature
Read
Write

127

Yes/No
1-15

On/Off
On/Off
On/Off
On/Off
nnn.n
nnn.n
On/Off
nnnnn
On/Off
nnnnn

INDEX
Actual start-up 44
Alarms and alerts 57
Alarm codes 58-62
Alarm descriptions 63, 108-111
BACnet communications option 117-126
Boards
Board addresses 16
Capacity control 20
Capacity control overrides 22
Compressor stages and circuit cycling 21, 22
Compressor starts and run hours 20
CCN
ComfortLink CCN communication
wiring 16, 17
Interface 16
CCN alarm description 108-111
CCN control 33
CCN global schedule 32
CCN tables 94-107
Chilled water flow switch 53
Compressor protection 56
Compressors 56
Oil charge 56
Replacement 56
System burnout cleanup procedure 57
Condenser coils
Cleaning round tube plate fin coils 53
Cleaning MCHX coils 55
Condenser fans 55
Configuration point description conventions 3
Configuration set point limits 33
Control methods 32
CCN control 33
CCN global schedule 32
Switch control 32
Time schedule 32
Unit run status 33
Controls 5-43
Board addresses 16
Capacity control 20
Carrier Comfort Network interface 16
ComfortLink display menu structure 5
Configuring the master chiller 18
Configuring the slave chiller 19
Control methods 32
Control module communication 16
Cooler pump control 31
Demand limit 41
Dual chiller control 17
Electronic expansion valve (EXV) Board 8, 9
Emergency on/off switch 14
Enable-off-remote contact switch 14
Energy management module (EMM) 14, 15
Energy management module (EMM)
inputs and outputs 15
EXV1 board inputs and outputs 8
EXV2 inputs and outputs 10
Fan board 1 outputs 11
Fan board 2 outputs 12
Fan board 3 inputs and outputs 13
Fan boards 9
General 3-5
Heat reclaim 49
Local equipment network 16
Low ambient head pressure control 24
Machine control 32
Main Base Board 5
Main Base Board inputs and outputs 6
Minimum load control 17
Minutes off time 17
Navigator module 4, 5
Ramp loading 17
Remote alarm and alert relays 41
Reverse rotation board 14
Scroll protection module (SPM) 7, 8
Scroll protection module inputs and
outputs 8
Scrolling marquee display 3
Temperature reset 33

Cooler head bolts


Tightening 53-55
Cooler protection 51
Chilled water flow switch 53
Flow rate 53
Freeze protection 51
Loss of fluid flow protection 51
Low fluid temperature 51
Plug components 52
Tightening cooler head bolts 53-55
Tube plugging 51
Cooler pump control 31
Cooling set point selection 33
4 to 20 mA input 33
Configuration set point limits 33
Control methods and cooling set points
table 32
Dual switch 33
Ice mode 33
Set point 1 33
Set point 2 33
Set point occupancy 33
Crankcase heaters 56
Demand limit 41
2-step switch controlled 41
2-step switch controlled configuration
table 42
CCN loadshed controlled 41
Demand limit signal 41
Externally powered 41
Externally powered demand limit
configuration table 43
Electronic expansion valve 8, 49
Cutaway view of 50
Filter drier 51
Inspecting/opening 51
Installing motor 51
Liquid line service valve 51
Moisture liquid indicator 51
Troubleshooting procedure 50
Flow rate 53
Freeze protection 51
Head pressure control. See low ambient
head pressure control
Heat reclaim module 49
High-side protection 56
Local display tables 82-93
Loss of fluid flow protection 51
Low ambient head pressure control 24
Fan Staging 25
Operating instructions 24
Low fluid temperature 51
Machine control 32
Maintenance 57, 113-116
Minimum and maximum cooler flow rates
table (sizes 060-300) 45
Minimum and maximum cooler flow rates
table (sizes 315-390) 45
Minimum fluid loop volume 44
Modular unit combinations 3
Navigator display
Alarms mode 93
Configuration mode 88, 89
Inputs mode 86
Operating mode 93
Outputs mode 87
Password 3
Pressure mode 85
Run status mode 82, 83
Service test mode 84
Set points mode 86
Temperature mode 85
Time clock mode 90-92
Navigator module 4
Adjusting the backlight brightness 4
Adjusting the contrast 4

128

Start-up 44,45
Actual start-up 44
Operating limitations 44
Pre-start-up 43,44
System check 43
Start-up and operation. See Start-up Checklist
Start-up checklist CL-1 to Cl-9
Switch control 32
System check 43
Temperature limits
Standard units 44
Low ambient operation 44
Temperature reset 33
4 to 20mA temperature reset 38
4 to 20mA temperature reset configuration
table 40
Chilled water temperature control 35
Outdoor air temperature reset 35
Outdoor air temperature reset configuration
table 37
Space temperature reset 38
Space temperature reset configuration 39
Water temperature difference reset
configuration 36
Thermistors 71
Compressor return gas temperature 71
Cooler entering fluid sensor 71
Cooler leaving fluid sensor 71
Dual chiller LWT 71
Outdoor air temperature 72
Remote space temperature 72
Typical space temperature sensor
wiring 74
Time schedule 32
Troubleshooting 57-81
Sensors 71
Service test 74
Thermistors 71
Tube plugging 51

Operating limitations 44
Flow rate requirements 45
Minimum and maximum cooler flow rates
(sizes 060-300) 45
Minimum and maximum cooler flow rates
(sizes 315-390) 45
Minimum fluid loop volume 44
Password 4
Voltage 44
Plug components 52
Recommended maintenance schedule 57, 113-116
Refrigerant circuit 56
Refrigerant feed components
Electronic expansion valve 49
Relief devices 56
High-side protection 56
Low-side protection 56
Safety considerations 2, 3
Safety devices 56
Compressor protection 56
Crankcase heaters 56
Scrolling marquee display 3
Alarms mode 93
Configuration mode 88, 89
Display menu structure 5
Inputs mode 86
Operating mode 93
Outputs mode 87
Password 4
Pressure mode 85
Run status mode 82, 83
Service test mode 84
Set points mode 86
Temperature mode 85
Time clock mode 90-92
Service 49-57
Coil maintenance and cleaning 53-55
Compressors 56, 57
Condenser fans 55
Cooler protection 51
Electronic expansion valve (EXV) 49
MCHX (microchannel) 55
Refrigerant circuit 56
Relief devices 56
RTPF (round tube, plate fin) 53
Safety devices 56

129

Copyright 2011 Carrier Corporation


Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300068-01
Printed in U.S.A.
Form 30RB-4T
Pg 130 612
2-11
Replaces: 30RB-3T

START-UP CHECKLIST FOR 30RB LIQUID CHILLER


A. PROJECT INFORMATION
Job Name ______________________________________
Address ________________________________________
City __________________ State ________ Zip ________

Installing Contractor_______________________________
Sales Office _____________________________________
Start-Up Performed By ____________________________

Design Information
CAPACITY

EWT

LWT

FLUID TYPE

FLOW RATE

P.D.

AMBIENT

Cooler

Unit
Model ________________________________________
Serial _________________________________________

Cooler
Model ________________________________________
Serial _________________________________________

Compressors
A1)
Model ________________________________________
Serial _________________________________________
SPM Address __________________________________
A2)
Model ________________________________________
Serial _________________________________________
SPM Address __________________________________
A3)
Model ________________________________________
Serial _________________________________________
SPM Address __________________________________
A4)
Model ________________________________________
Serial _________________________________________
SPM Address __________________________________
B1)
Model ________________________________________
Serial _________________________________________
SPM Address __________________________________
B2)
Model ________________________________________
Serial _________________________________________
SPM Address __________________________________

B3)
Model _________________________________________
Serial _________________________________________
SPM Address ___________________________________
B4)
Model _________________________________________
Serial _________________________________________
SPM Address ___________________________________
C1)
Model _________________________________________
Serial _________________________________________
SPM Address ___________________________________
C2)
Model _________________________________________
Serial _________________________________________
SPM Address ___________________________________
C3)
Model _________________________________________
Serial _________________________________________
SPM Address ___________________________________
C4)
Model _________________________________________
Serial _________________________________________
SPM Address ___________________________________

Hydronic Package
P1)
Model
Serial
P2)
Model
Serial

_________________________________________
_________________________________________
_________________________________________
_________________________________________

B. PRELIMINARY EQUIPMENT CHECK (This section to be completed by installing contractor)


1. Is there any physical damage?

a. Will this prevent start-up?

Description _____________________________________________________________
_______________________________________________________________________
2. Unit is installed level as per the installation instructions.

3. Power supply agrees with the unit nameplate.

4. Correct control voltage ________vac. Check transformer primary on 208/230 v.

5. Electrical power wiring is installed properly.

6. Unit is properly grounded.

Yes
Yes

No
No

Yes
Yes
Yes
Yes
Yes

No
No
No
No
No

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300068-01
Printed in U.S.A.
Form 30RB-4T
Pg CL-1
612
2-11
Replaces: 30RB-3T

Electrical circuit protection has been sized and installed properly.


All terminals are tight.
All plug assemblies are tight.
All cables, thermistors and transducers have been inspected for cross wires.
All thermistors are fully inserted into wells.
Crankcase heaters energized for 24 hours before start-up.
All armatures more freely on contactors.

Yes
Yes
Yes
Yes
Yes
Yes
Yes

No
No
No
No
No
No
No

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

No
No
No
No
No
No
No
No

Chilled Water System Check


1.
2.
3.
4.
5.
6.
7.
8.

All chilled water valves are open.


All piping is connected properly.
All air has been purged from the system.
Chilled water pump is operating with the correct rotation.
Chilled water pump starter interlocked with chiller.
Chilled water flow switch operational.
Inlet piping to cooler includes a 20 mesh strainer.
Water loop volume greater than 3 gal/ton for air conditioning
or 6 gal/ton for process cooling and low ambient operation.
9. Proper loop freeze protection provided to ____ F (C).
Antifreeze type__________________ Concentration _____%.
(If antifreeze solution is not utilized on 30RB machines and the
minimum outdoor ambient is below 32 F (0 C)
then items 10 and 11 have to be completed to provide cooler
freeze protection to 20 F. Refer to Installation Instructions
for proper cooler winterization procedure.)
10. Outdoor piping wrapped with electric heater tape.
11. Cooler heaters installed and operational.
12. Is the unit equipped with low ambient head pressure control?
a. If yes, are wind baffles installed? (Required if chiller will run below 32 F
and be exposed to the wind.)
13. Are there any VFDs on the chilled water pumps?
a. Primary loop
b. Secondary loop

Yes

No

Yes
Yes
Yes
Yes

Yes
Yes

No
No
No
No

No
No

C. UNIT START-UP
All liquid line service valves located near EXVs are open.
Yes
No
All discharge service valves are open.
Yes
No
All suction service valves are open.
Yes
No
All compressor rack holddown bolts removed.
Yes
No
Leak check unit. Locate, repair and report any refrigerant leaks.
Yes
No
Voltage at terminal block is within unit nameplate range.
Yes
No
Check voltage imbalance: A-B______ A-C______B-C______
Average voltage = __________ (A-B + A-C + B-C)/3
Maximum deviation from average voltage = _______
Voltage imbalance = ______% (max. deviation / average voltage) X 100
Is voltage imbalance less than 2%.
Yes
No
(DO NOT start chiller if voltage imbalance is greater than 2%.
Contact local utility for assistance.)
8. Verify cooler flow rate
Yes
No
Pressure entering cooler
_____ psig (kpa)
Pressure leaving cooler
_____ psig (kpa)
Cooler pressure drop
_____ psig (kpa)
Psig x 2.31 ft./psi =
_____ ft of water
kPa x 0.334 m/psi =
_____ m of water
Cooler flow rate _____ gpm (l/s) (See Cooler Pressure Drop Curve provided in the 30RB Installation Instructions.)
9. Verify that isolation valves on factory-installed pump packages are properly
Yes
No
positioned and locked prior to start-up (slot in-line with piping on both sides of pump).
1.
2.
3.
4.
5.
6.
7.

CL-2

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE


CUT ALONG DOTTED LINE

7.
8.
9.
10.
11.
12.
13.

Start and operate machine. Complete the following:


1.
2.
3.
4.
5.

Complete component test (make sure EXVs are checked after liquid line service valves are opened).
Check refrigerant and oil charge. Record charge information below.
Record compressor and condenser fan motor current.
Record operating data.
Provide operating instructions to owners personnel. Instruction time _______ hours
Circuit A
Circuit B
Circuit C
Refrigerant Charge
__________
___________
___________
Additional charge required
__________
___________
___________

Oil Charge
Indicate level in sight glass of compressors A1, B1 and C1.
Additional oil charge required.
Circuit A ______
Circuit B ______
Circuit C ______

A1

B1

C1

A2

B2

C2

A3

B3

C3

A4

B4

C4

Record Software Versions


MODE RUN STATUS
SUB-MODE

VERS

ITEM
APPL
MARQ
EXV1
EXV2
AUX1
AUX2
AUX3

DISPLAY

ITEM EXPANSION
CSA-SR- __ __ __ __ __ __

(Press ENTER and ESCAPE simultaneously to obtain software versions)

CL-3

MODE CONFIGURATION
SUB-MODE
DISP

UNIT

SERV

OPTN

ITEM
TEST
METR
LANG
TYPE
TONS
VAR.A
VAR.B
VAR.C
HGBP
60HZ
RECL
EHS
EMM
PAS.E
PASS
FREE
PD4.D
BOIL
FLUD
MOP
HP.TH
SHP.A
SHP.B
SHP.C
HTR
EWTO
AU.SM
BOTH
LLWT
LOSP
HD.PG
HD.DG
HD.IG
HR.MI
HR.MA
AVFA
AVFB
AVFC
CCNA
CCNB
BAUD
LOAD
LLCS
RL.S
DELY
ICE.M
PUMP
ROT.P
PM.PS
P.SBY
P.LOC
LS.ST
LS.ND
LS.LT
OA.TH
FREE
BO.TH
EHST
EHSB
E.DEF
EHSP
AUTO

DISPLAY
OFF/ON
US-METR
x
x
xxx
x
x
x
x
NO/YES
NO/YES
x
NO/YES
DSBL/ENBL
xxxx
NO/YES
NO/YES
OFF/ON
x
xx.x
xxx.x
xx.x
xx.x
xx.x
xx.x
NO/YES
NO/YES
NO/YES
xx
xx.x
xx.x
xx.x
xx.x
xxx.x
xxx.x
NO/YES
NO/YES
NO/YES
xxx
xxx
x
x
x
ENBL/DSBL
xx
ENBL/DSBL
x
xxxx
NO/YES
NO/YES
NO/YES
xx.xx
xx.xx
xxx
xx.x
xx.x
xx.x
xx.xx
NO/YES
NO/YES
xx
NO/YES

ITEM EXPANSION
Test Display LEDs
Metric Display
Language
Unit Type
Unit Size
NB Fan on Varifan CIR A
NB Fan on Varifan CIR B
NB Fan on Varifan CIR C
Hot Gas Bypass Control
60 Hz Frequency
Heat Reclaim Select
Electric Heater Stage
EMM Module Installed
Password Enable
Password Protection Must be Disabled
Free Cooling Select
Pro_Dialog Users Display
Boiler Command Select
Cooler Fluid Type
EXV MOP Setpoint
High Pressure Threshold
Circuit A Superheat Setp
Circuit B Superheat Setp
Circuit C Superheat Setp
Cooler Heater DT Setp
Entering Water Control
Auto Start When SM Lost
HSM Both Command Select
Brine Min. Fluid Temp.
Brine Freeze Setpoint
Varifan Proportion Gain
Varifan Derivative Gain
Varifan Integral Gain
Reclaim Water Valve Min
Reclaim Water Valve Max
Attach Drive to Fan A
Attach Drive to Fan B
Attach Drive to Fan C
CCN Address
CCN Bus Number
CCN Baud Rate
Loading Sequence Select
Lead/Lag Circuit Select
Ramp Load Select
Minutes Time Off
Ice Mode Enable
Cooler Pumps Sequence
Pump Rotation Delay
Periodic Pump Start
Stop Pump in Standby
Flow Checked if Pump Off
Night Low Noise Start
Night Low Noise End
Low Noise Capacity Lim
Heat Mode OAT Threshold
Free Cooling OAT Limit
Boiler OAT Threshold
Elec Stag OAT Threshold
Last Heat Elec Backup
Quick EHS in Defrost
Elec Heat Pulldown
Auto Changeover Select

CL-4

ENTRY

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE


CUT ALONG DOTTED LINE

Record Configuration Information

MODE CONFIGURATION (cont)


SUB-MODE
RSET

ITEM
CRST
HRST
DMDC
DMMX
DMZE
MSSL
SLVA
LLBL
LLBD
LLDY
LAGP
LPUL

DISPLAY
x
x
x
xx.x
xx.x
x
xxx
ENBL/DSBL
xxx
xx
x
xx

ITEM EXPANSION
Cooling Reset Type
Heating Reset Type
Demand Limit Select
mA for 100% Demand Lim
mA for 0% Demand Limit
Master/Slave Select
Slave Address
Lead/Lag Balance Select
Lead/Lag Balance Delta
Lag Start Delay
Lag Unit Pump Select
Lead Pulldown Time

ENTRY

MODE SETPOINT
SUB-MODE
COOL

HEAT

MISC

ITEM
CSP.1
CSP.2
CSP.3
CRV1
CRV2
CRT1
CRT2
CRO1
CRO2
CRS1
CRS2
DGRC
CAUT
CRMP
HSP.1
HSP.2
HRV1
HRV2
HRT1
HRT2
HRO1
HRO2
DGRH
HAUT
HRMP
DLS1
DLS2
DLS3
RSP
RDB

DISPLAY
xxx.x
xxx.x
xxx.x
xx.x
xx.x
xxx.x
xxx.x
xxx.x
xxx.x
xxx.x
xxx.x
xx.x
xx.x
x.x
xxx.x
xxx.x
xx.x
xx.x
xxx.x
xxx.x
xxx.x
xxx.x
xx.x
xx.x
x.x
xxx
xxx
xxx
xxx.x
xx.x

ITEM EXPANSION
Cooling Setpoint 1
Cooling Setpoint 2
Ice Setpoint
Current No Reset Value
Current Full Reset Value
Delta T No Reset Temp
Delta T Full Reset Value
OAT No Reset Temp
OAT Full Reset Temp
Space T No Reset Temp
Space T Full Reset Temp
Degrees Cool Reset
Cool Changeover Setpt
Cool Ramp Loading
Heating Setpoint 1
Heating Setpoint 2
Current No Reset Val
Current Full Reset Val
Delta T No Reset Temp
Delta T Full Reset Temp
OAT No Reset Temp
OAT Full Reset Temp
Degrees Heat Reset
Heat Changeover Setpt
Heat Ramp Loading
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
Heat Reclaim Setpoint
Reclaim Deadband

ENTRY

N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

N/A
N/A

MODE OPERATING MODE


SUB-MODE
SLCT

ITEM
OPER
SP.SE
HC.SE
RL.SE

DISPLAY

ITEM EXPANSION
Operating Control Type
Setpoint Select
Heat Cool Select
Reclaim Select

x
x
x
x

CL-5

ENTRY

MODE SERVICE TEST


SUB-MODE
TEST*

QUIC

ITEM
T.REQ
CP.A1
CP.A2
CP.A3
CP.A4
HGB.A
CP.B1
CP.B2
CP.B3
CP.B4
HGB.B
CP.C1
CP.C2
CP.C3
CP.C4
HGB.C
Q.REQ
EXV.A
EXV.B
EXV.C
FAN.A
FAN.B
FAN.C
SPD.A
SPD.B
SPD.C
FRV.A
FRP.A
FRV.B
FRP.B
FRV.C
FRP.C
RV.A
RV.B
BOIL
HR1.A
HR2.A
HR3.A
HR4.A
HR1.B
HR2.B
HR3.B
HR4.B
PMP.1
PMP.2
CND.P
CL.HT
CP.HT

DISPLAY
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
xxx%
xxx%
xxx%
X
X
X
xxx%
xxx%
xxx%
OPEN/CLSE
OFF/ON
OPEN/CLSE
OFF/ON
OPEN/CLSE
OFF/ON
OPEN/CLSE
OPEN/CLSE
OFF/ON
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OPEN/CLSE
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON

ITEM EXPANSION
Manual Sequence
Compressor A1 Output
Compressor A2 Output
Compressor A3 Output
Compressor A4 Output
Hot Gas Bypass A Output
Compressor B1 Output
Compressor B2 Output
Compressor B3 Output
Compressor B4 Output
Hot Gas Bypass B Output
Compressor C1 Output
Compressor C2 Output
Compressor C3 Output
Compressor C4 Output
Hot Gas Bypass C Output
Quick Test Mode
Circuit A EXV % Open
Circuit B EXV % Open
Circuit C EXV % Open
Circuit A Fan Stages
Circuit B Fan Stages
Circuit C Fan Stages
Circ A Varifan Position
Circ B Varifan Position
Circ C Varifan Position
Free Cooling Valve A
Refrigerant Pump Out A
Free Cooling Valve B
Refrigerant Pump Out B
Free Cooling Valve C
Refrigerant Pump Out C
4 Way Valve Circuit A
4 Way Valve Circuit B
Boiler Command
Air Cond Enter Valve A
Air Cond Leaving Valve A
Water Cond Enter Valve A
Water Cond Leaving Valve A
Air Cond Enter Valve B
Air Cond Leaving Valve B
Water Cond Enter Valve B
Water Cond Leaving Valve B
Water Exchanger Pump 1
Water Exchanger Pump 2
Reclaim Condenser Pump
Cooler Heater Output
Condenser Heater Output

ENTRY

*Place the Enable/Off/Remote Contact switch to the Off position prior to configuring T.REQ to ON. Configure the desired item to ON, then
place the Enable/Off/Remote Contact switch to the Enable position.
Place the Enable/Off/Remote Contact switch to the Off position prior to configuring Q.REQ to ON. The switch should be in the Off position
to perform Quick Test.

CL-6

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE


CUT ALONG DOTTED LINE

Component Test Complete the following tests to make sure all peripheral components are
operational before the compressors are started.

MODE SERVICE TEST (cont)


SUB-MODE
QUIC(cont)

ITEM
CH.A1
CH.A2
CH.A3
CH.A4
CH.B1
CH.B2
CH.B3
CH.B4
CH.C1
CH.C2
CH.C3
CH.C4
HGB.A
HGB.B
HGB.C
Q.RDY
Q.RUN
SHUT
CATO
ALRM
ALRT
C.ALM

DISPLAY
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
xx.x
OFF/ON
OFF/ON
OFF/ON

ITEM EXPANSION
Compressor A1 Heater
Compressor A2 Heater
Compressor A3 Heater
Compressor A4 Heater
Compressor B1 Heater
Compressor B2 Heater
Compressor B3 Heater
Compressor B4 Heater
Compressor C1 Heater
Compressor C2 Heater
Compressor C3 Heater
Compressor C4 Heater
Hot Gas Bypass A Output
Hot Gas Bypass B Output
Hot Gas Bypass C Output
Chiller Ready Status
Chiller Running Status
Customer Shut Down Stat
Chiller Capacity 0-10v
Alarm Relay
Alert Relay
Critical Alarm Relay

ENTRY

*Place the Enable/Off/Remote Contact switch to the Off position prior to configuring T.REQ to ON. Configure the desired item to ON, then
place the Enable/Off/Remote Contact switch to the Enable position.
Place the Enable/Off/Remote Contact switch to the Off position prior to configuring Q.REQ to ON. The switch should be in the Off position
to perform Quick Test.

CL-7

Record the following information from the Run Status, Temperatures and Outputs Modes when machine is in a
stable operating condition. If cooling load is insufficient, these readings must be obtained by putting the chiller in
test mode (Service Test) and running each compressor.
TEMPERATURES
COOLER ENTERING FLUID
EWT _______________
COOLER LEAVING FLUID
LWT _______________
CONTROL POINT
CTPT _______________
CAPACITY
CAP _______________
OUTSIDE AIR TEMPERATURE
OAT _______________
LEAD/LAG LEAVING FLUID
CHWS_______________ (Dual Chiller Control Only)
OPTIONAL HEAT RECLAIM
ENTERING WATER TEMPERATURE
HEWT _______________
LEAVING WATER TEMPERATURE
HLWT _______________
Install a manifold gage set to obtain readings and verify these against pressure transducers.
CIRCUIT A
CIRCUIT B
CIRCUIT C
SCT.A __________
SCT.B __________
SCT.C___________
SST.A __________
SST.B __________
SST.C ___________
SGT.A __________
SGT.B __________
SGT.C ___________
SUP.A __________
SUP.B __________
SUP.C ___________
EXV.A__________
EXV.B __________
EXV.C ___________
NOTE: EXV A,B,C positions are found in the output mode.
COMPRESSOR MOTOR CURRENT
L1
L2
COMPRESSOR A1
______
______
COMPRESSOR A2
______
______
COMPRESSOR A3
______
______
COMPRESSOR A4
______
______
COMPRESSOR B1
______
______
COMPRESSOR B2
______
______
COMPRESSOR B3
______
______
COMPRESSOR B4
______
______
COMPRESSOR C1
______
______
COMPRESSOR C2
______
______
COMPRESSOR C3
______
______
COMPRESSOR C4
______
______

L3
______
______
______
______
______
______
______
______
______
______
______
______

CONDENSER FAN MOTOR CURRENT


L1
L2
FAN MOTOR 1
______
______
FAN MOTOR 2
______
______
FAN MOTOR 3
______
______
FAN MOTOR 4
______
______
FAN MOTOR 5
______
______
FAN MOTOR 6
______
______
FAN MOTOR 7
______
______
FAN MOTOR 8
______
______
FAN MOTOR 9
______
______

L3
______
______
______
______
______
______
______
______
______

FAN MOTOR 10
FAN MOTOR 11
FAN MOTOR 12
FAN MOTOR 13
FAN MOTOR 14
FAN MOTOR 15
FAN MOTOR 16
FAN MOTOR 17
FAN MOTOR 18

CL-8

L1
______
______
______
______
______
______
______
______
______

L2
______
______
______
______
______
______
______
______
______

L3
______
______
______
______
______
______
______
______
______

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE


CUT ALONG DOTTED LINE

Operating Data:

COMMENTS:
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
SIGNATURES:
Start-up
Technician _____________________________________

Date______________________________________________

Customer
Representative __________________________________

Date______________________________________________

CL-9

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300068-01
Printed in U.S.A.
Form 30RB-4T
Pg CL-10
612
2-11
Replaces: 30RB-3T

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE


CUT ALONG DOTTED LINE

Copyright 2011 Carrier Corporation