Option 1
(According to contract)
2MVR600
TOP TERMINAL VRLA
Nominal voltage
10 hour capacity to 1.80 Vpc
8 hour capacity to 1.75 Vpc
Float voltage
Accelerated charge voltage
Shelf life
Short circuit current
Internal resistance
at 25C
2 Volts
603.0 Ah
621.0 Ah
589.6 Ah
607.2 Ah
2.27 Vpc 1%
2.26 Vpc 1%
2.40 Vpc without current limit
1 year
6700 Amps
0.31 m
Mechanical Characteristics
SI Units
US Units
Length
386 mm
15.2 inches
Width
168 mm
6.6 inches
Height
232 mm
9.1 inches
Weight
41.5 kg
91.5 lbs
Terminal Torque
9.0 Nm
79.6 in.lbs
Uf, Vpc
1.60
1.65
1.70
1.75
1.80
1.85
5 min
2050.0
1880.0
1736.7
1573.3
1386.7
1183.3
Discharge performance at constant current discharge (A) for battery 2MVR600 at 20C
10 min 15 min 20 min 30 min 45 min
1h
2h
3h
4h
5h
8h
1440.0 1133.3 933.3 700.0 498.3 397.7 229.0 167.7 133.7 112.0
75.7
1386.7 1100.7 913.3 686.7 487.3 386.3 226.7 166.7 132.3 110.3
75.0
1296.7 1050.0 883.3 663.3 473.7 380.0 223.7 164.7 131.3 110.0
74.3
1228.0 1003.3 853.3 638.3 456.0 367.3 218.0 162.3 129.7 108.3
73.7
1103.3 930.0 793.3 596.0 435.3 352.0 213.0 158.3 126.3 106.3
72.3
972.0 833.3 700.0 528.0 398.3 326.7 201.0 150.0 120.0 101.7
68.7
10 h
62.7
62.0
61.7
61.0
60.3
57.7
20 h
34.3
33.7
33.3
33.0
32.3
31.3
Uf, Vpc
1.60
1.65
1.70
1.75
1.80
1.85
5 min
2111.5
1936.4
1788.8
1620.5
1428.3
1218.8
Discharge performance at constant current discharge (A) for battery 2MVR600 at 25C
10 min 15 min 20 min 30 min 45 min
1h
2h
3h
4h
5h
8h
1483.2 1167.3 961.3 721.0 513.3 409.6 235.9 172.7 137.7 115.4
77.9
1418.0 1133.7 940.7 707.3 502.0 397.9 233.5 171.7 136.3 113.6
77.3
1335.6 1081.5 909.8 683.2 487.9 391.4 230.4 169.6 135.3 113.3
76.6
1264.8 1033.4 878.9 657.5 469.7 378.4 224.5 167.2 133.6 111.6
75.9
1136.4 957.9 817.1 613.9 448.4 362.6 219.4 163.1 130.1 109.5
74.5
1001.2 858.3 721.0 543.8 410.3 336.5 207.0 154.5 123.6 104.7
70.7
10 h
64.5
63.9
63.5
62.8
62.1
59.4
20 h
35.4
34.7
34.3
34.0
33.3
32.3
Uf, Vpc
1.60
1.65
1.70
1.75
1.80
1.85
5 min
2955.6
2811.1
2644.4
2477.8
2211.1
1872.2
Discharge performance at constant power discharge (W per cell) for battery 2MVR600 at 20C
10 min 15 min 20 min 30 min 45 min
1h
2h
3h
4h
5h
8h
2138.9 1688.9 1400.0 1070.0 805.9 660.8 405.6 297.8 236.1 197.8 137.8
2055.6 1644.4 1377.8 1052.2 792.6 644.4 400.0 296.7 235.2 196.7 137.0
1988.9 1583.3 1338.9 1036.7 777.8 638.6 396.7 292.2 233.3 194.4 135.6
1888.9 1511.1 1277.8 1000.0 758.6 625.2 392.2 290.0 230.3 192.6 134.1
1688.9 1377.8 1183.7 940.8 726.8 610.3 382.2 282.2 225.9 188.9 131.9
1477.8 1215.6 1055.6 844.4 666.7 563.3 364.4 270.0 216.7 181.4 127.8
10 h
117.0
115.6
115.2
114.8
111.9
108.1
20 h
65.9
65.2
64.8
64.1
63.7
62.2
Uf, Vpc
1.60
1.65
1.70
1.75
1.80
1.85
5 min
3044.2
2895.4
2723.8
2552.1
2277.4
1928.4
Discharge performance at constant power discharge (W per cell) for battery 2MVR600 at 25C
10 min 15 min 20 min 30 min 45 min
1h
2h
3h
4h
5h
8h
2203.1 1739.6 1442.0 1102.1 830.1 680.6 417.7 306.7 243.2 203.7 141.9
2117.2 1693.8 1419.1 1083.8 816.3 663.8 412.0 305.6 242.3 202.6 141.1
2048.6 1630.8 1379.1 1067.8 801.1 657.7 408.6 301.0 240.3 200.3 139.6
1945.6 1556.4 1316.1 1030.0 781.3 644.0 404.0 298.7 237.2 198.3 138.1
1739.6 1419.1 1219.2 969.0 748.5 628.6 393.7 290.7 232.7 194.6 135.8
1522.1 1252.0 1087.2 869.8 686.7 580.2 375.4 278.1 223.2 186.9 131.6
10 h
120.5
119.0
118.7
118.2
115.2
111.4
20 h
67.9
67.2
66.7
66.0
65.6
64.1
www.nettaelektronik.com
EnvironmentallyCertified
CertificateofRegistration
PmiElektrikveElektronikSistemleriDisTicaretLtd.Sti.
H.RifatPasaMah.PerpaTicaretMerkeziABlokK:12No:1767Sisli,Istanbul,Turkey
ModernKerestecilerSanayiSitesi1.Cad.23.Sok.,No:12SarayKazan/Ankara,Turkey
TheabovelicenseehasbeenassessedandregisteredbyTQCSInternationalPtyLtdashavingthecapabilityto
controltheenvironmentalsystemsassociatedwithitsoperationsinaccordancewiththeconditionsofthe
LicenceAgreementatorfromtheaddressesshownabove,underanenvironmentalmanagementsystem
complyingwiththerequirementsof:
ISO14001:2004
Theregistrationcoversthedesign,manufacture,saleandserviceofpowersupplies,voltageregulatorsandother
electricalequipment.
IssueDate:11April2012
ExpiryDate:04April2015
LicenceNo:TK2846QCEC
OriginalCertification:11April2012
CraigJBates
President
TQCSInternational(Group)PtyLtd
LorraineWelsh
AccreditationManager
TQCSInternationalPtyLtd
Forandonbehalfofthe
TQCSICertificationApprovalPanel
Thiscertificateverifiestheoriginalcertificateissuedandisvalidaslongasitisdisplayedasanelectroniccopyatwww.tqcsi.comand
surveillanceauditsaresatisfactorilycompleted.
TQCSINTERNATIONALPTYLTD
www.tqcsi.com
www.jasanz.org/register
QualityCertified
CertificateofRegistration
PmiElektrikveElektronikSistemleriDisTicaretLtd.Sti.
H.RifatPasaMah.PerpaTicaretMerkeziABlokK:12No:1767Sisli,Istanbul,Turkey
ModernKerestecilerSanayiSitesi1.Cad.23.Sok.,No:12SarayKazan/Ankara,Turkey
TheabovelicenseehasbeenassessedandregisteredbyTQCSInternationalPtyLtdashavingthecapabilityto
controlthequalityofgoodsorservicesprovidedinaccordancewiththeconditionsoftheLicenceAgreementat
orfromtheaddressesshownabove,underaqualitymanagementsystemcomplyingwiththerequirementsof:
ISO9001:2008
Theregistrationcoversthedesign,manufacture,saleandserviceofpowersupplies,voltageregulatorsandother
electricalequipment.
Exclusions:None
IssueDate:11April2012
ExpiryDate:04April2015
LicenceNo:TK2846QCEC
OriginalCertification:11April2012
CraigJBates
President
TQCSInternational(Group)PtyLtd
LorraineWelsh
AccreditationManager
TQCSInternationalPtyLtd
Forandonbehalfofthe
TQCSICertificationApprovalPanel
Thiscertificateverifiestheoriginalcertificateissuedandisvalidaslongasitisdisplayedasanelectroniccopyatwww.tqcsi.comand
surveillanceauditsaresatisfactorilycompleted.
TQCSINTERNATIONALPTYLTD
www.tqcsi.com
www.jasanz.org/register
RDAT SERIES
BATTERY CHARGER /
DC RECTIFIER
DC CHARGER / RECTIFIER
DC CHARGER / RECTIFIER
STANDARD FEATURES
Adjustable Timer for Boost Charging
Adjustable Boost and Float Charge Voltages
Automatic Boost Charge Selection according to
boost / float current set value
Adjustable Rectifier Output Current and Battery
Charge Current
LCD Display for DC Load / Battery Voltage , DC Load
/ Battery Current , Input AC Voltage / Line Current /
Frequency
Event History for all Electrical values and failures
Automatic and Manuel Battery Test
Boost inhibit facility for interlock redundant
application
Output Filter Inductor and DC Longlife Capacitor
Electronic Over / Under Voltage, Over Current and
Short Circuit Protections
Isolated Output by Input Transformer and output
halleffect current module
OPTIONS
RS 485/ModBus, Profibus, TCP/IP or SMS/Mail Order
communication.
Silicon Dropper Module For Load Output
LVD Deep Discharge Battery Protection contactor.
Cabin options for Rectifier and Battery Group
Analogue Meterings for Output and Battery
Power Analyzer option for Input
DC CHARGER / RECTIFIER
Battery voltage
Boost voltage
Float voltage
AUTOMATIC BOOST
Time hour
0
Automatic boost charge can also be selected on menu. The automatic boost
menu
Battery
current has the options for selecting the boost
and float current based on battery capacity. Suitable float and boost currents of the battery are set before selecting the
automatic boost option. After the set-up, the automatic boost function will monitor the battery current and select boost or
float option by referring to the set values. If the charging current Charge
is higher
than the set boost current, the system will select
current
boost and if the charging current is lower than the set float current the system will select float option. In case of low battery
alarm, the automatic boost will select boost option until the battery
charging current reaches to the set float value.
Boost current
Float current
Time hour
0
6
8
Battery automatic boost/float charge technique
Boost voltage
Float voltage
Time hour
0
VOLTAGE (V)
Battery current
Boost
Float
Charge current
Amper (I)
Boost current
Battery
Float current
Time hour
0
6
8
Battery automatic boost/float charge technique
Output
Boost
Float
Amper (I)
Battery
Output
10
DC CHARGER / RECTIFIER
HIGH PROTECTION
FULLY CONTROLLED THRYSTOR RECTIFIER MODULE
COMPLETE ISOLATION
PMI DC Chargers are fully isolated since an isolation transformer is placed in between the input and output and because the
DC current is controlled by a DC current module. Therefore, the load is always safe even at high input voltage and congested
mains conditions. In addition, the failure risk is minimized as semi-conductors are used for the rectifier. Standard L-C filters at
the output maintain safe charging of the battery groups.
PROTECTIONS
DC RIPPLE < 1%
11
DC CHARGER / RECTIFIER
PARALLELING
The Charger has a modular design to provide service and maintenance
simplicity. The outputs of the Battery Chargers can be connected in
parallel. The parallel system can be active load sharing or hot-standby.
Besides this, parallel system can be placed in one unit industrial cabin
as seen from the picture on the right side or they can be placed in
different cabins based on the requirement.
12
DC CHARGER / RECTIFIER
13
DC CHARGER / RECTIFIER
REMOTE MONITORING
On both LCD panel and communication interface, all key parameters can be set and real time base
events and failures can be tracked. In parallel operation multiple rectifiers can be controlled by
the help of same communication interface. The communication is executed via RS 485/ModBus,
Profibus, TCP/IP or SMS/Mail Order.
14
DC CHARGER / RECTIFIER
PRODUCT PERFORMANCE
SOFT START FEATURE
DYNAMIC RESPONSE
MICROPROCESSOR CONTROL
15
DC CHARGER / RECTIFIER
Monophase Input
Threephase Input
For 3 phase input 6 Pulse Thyristor controlled AC/DC Rectifier with input isolation transformer
Optional 12 Pulse Thyristor controlled AC/DC Rectifier with input isolation transformer
110 VAC / 115VAC /208 VAC / 220 VAC / 190 VAC / 200 VAC /380 VAC / 400 VAC / 415 /
230 VAC / 240 VAC 15%
480 VAC 15%
50 / 60 Hz 5%
>0.8 Inductive (>0.9 with 12 Pulse Rectifier)
Galvanically isolated
<35% (standard); <10% (with 12 Pulse Rectifier)
Thermic-Magnetic Over Current Protection, Over Voltage Protection, Phase Sequence
Free Operation (3 Phase), Soft Start, MCB
12 VDC / 24 VDC / 48 VDC / 110 VDC / 220 VDC
24VDC output: 10VDC to 30VDC, 48VDC output: 48VDC to 60VDC, 110VDC output:
110VDC to 160VDC, 220VDC output: 220VDC to 300VDC
0-100% of Nominal Output Current
0-100% of Nominal Output Current
100% to 120% of Floating Output Voltage
2,4 lead acid battery 1,60 NiCd Battery (Might change based on battery brand)
2,23 lead acid battery 1,40 NiCd battery (Might change based on battery brand)
1% (Lower values available upon request)
Available upto 1000 Amp (12 Pulse over 400 Amp) (100 A was selected)
100% of nominal output current
<1% RMS AC of Output Voltage
2% of Output Voltage (100% load change)
Constant Current/ Constant Voltage
Short Circuit Protection, Over Voltage Protection, Reverse Voltage Protection,
Short Circuit, MCB or NH Fuse (based on current value)
L-C filters, Overcurrent Electronic protection, Over Voltage Protection and Thermic Fuse
0 99.9 hours adjustable
Forced fans with smart fan controlling system (Natural Cooling Optional)
2500VAC input/chassis and output/chassis
>80% (Higher values optional)
>90% (Higher values optional)
100,000 Hrs. (w/out battery group)
-10 / + 40 C (Higher Temperature Control, Optional)
IP20 (Standard); IP31 / IP42 / IP54 (Optional)
16
DC CHARGER / RECTIFIER
Enclosure Material
Cable Entry
Access to Batteries
Relative Humidity
Circuit Breakers
Silicon Dropper
Reset Button
Boost inhibit
DISPLAY PANEL
Front Panel Measured
Values
Front Panel Indicators
17
18
GROUP COMPANIES
www.pmienergy.com
PMI & OES GROUP COMPANIES reserves the right to make alterations on technical specifications.
Option 2
(corrected values)
EnvironmentallyCertified
CertificateofRegistration
PmiElektrikveElektronikSistemleriDisTicaretLtd.Sti.
H.RifatPasaMah.PerpaTicaretMerkeziABlokK:12No:1767Sisli,Istanbul,Turkey
ModernKerestecilerSanayiSitesi1.Cad.23.Sok.,No:12SarayKazan/Ankara,Turkey
TheabovelicenseehasbeenassessedandregisteredbyTQCSInternationalPtyLtdashavingthecapabilityto
controltheenvironmentalsystemsassociatedwithitsoperationsinaccordancewiththeconditionsofthe
LicenceAgreementatorfromtheaddressesshownabove,underanenvironmentalmanagementsystem
complyingwiththerequirementsof:
ISO14001:2004
Theregistrationcoversthedesign,manufacture,saleandserviceofpowersupplies,voltageregulatorsandother
electricalequipment.
IssueDate:11April2012
ExpiryDate:04April2015
LicenceNo:TK2846QCEC
OriginalCertification:11April2012
CraigJBates
President
TQCSInternational(Group)PtyLtd
LorraineWelsh
AccreditationManager
TQCSInternationalPtyLtd
Forandonbehalfofthe
TQCSICertificationApprovalPanel
Thiscertificateverifiestheoriginalcertificateissuedandisvalidaslongasitisdisplayedasanelectroniccopyatwww.tqcsi.comand
surveillanceauditsaresatisfactorilycompleted.
TQCSINTERNATIONALPTYLTD
www.tqcsi.com
www.jasanz.org/register
QualityCertified
CertificateofRegistration
PmiElektrikveElektronikSistemleriDisTicaretLtd.Sti.
H.RifatPasaMah.PerpaTicaretMerkeziABlokK:12No:1767Sisli,Istanbul,Turkey
ModernKerestecilerSanayiSitesi1.Cad.23.Sok.,No:12SarayKazan/Ankara,Turkey
TheabovelicenseehasbeenassessedandregisteredbyTQCSInternationalPtyLtdashavingthecapabilityto
controlthequalityofgoodsorservicesprovidedinaccordancewiththeconditionsoftheLicenceAgreementat
orfromtheaddressesshownabove,underaqualitymanagementsystemcomplyingwiththerequirementsof:
ISO9001:2008
Theregistrationcoversthedesign,manufacture,saleandserviceofpowersupplies,voltageregulatorsandother
electricalequipment.
Exclusions:None
IssueDate:11April2012
ExpiryDate:04April2015
LicenceNo:TK2846QCEC
OriginalCertification:11April2012
CraigJBates
President
TQCSInternational(Group)PtyLtd
LorraineWelsh
AccreditationManager
TQCSInternationalPtyLtd
Forandonbehalfofthe
TQCSICertificationApprovalPanel
Thiscertificateverifiestheoriginalcertificateissuedandisvalidaslongasitisdisplayedasanelectroniccopyatwww.tqcsi.comand
surveillanceauditsaresatisfactorilycompleted.
TQCSINTERNATIONALPTYLTD
www.tqcsi.com
www.jasanz.org/register
RDAT SERIES
BATTERY CHARGER /
DC RECTIFIER
DC CHARGER / RECTIFIER
DC CHARGER / RECTIFIER
STANDARD FEATURES
Adjustable Timer for Boost Charging
Adjustable Boost and Float Charge Voltages
Automatic Boost Charge Selection according to
boost / float current set value
Adjustable Rectifier Output Current and Battery
Charge Current
LCD Display for DC Load / Battery Voltage , DC Load
/ Battery Current , Input AC Voltage / Line Current /
Frequency
Event History for all Electrical values and failures
Automatic and Manuel Battery Test
Boost inhibit facility for interlock redundant
application
Output Filter Inductor and DC Longlife Capacitor
Electronic Over / Under Voltage, Over Current and
Short Circuit Protections
Isolated Output by Input Transformer and output
halleffect current module
OPTIONS
RS 485/ModBus, Profibus, TCP/IP or SMS/Mail Order
communication.
Silicon Dropper Module For Load Output
LVD Deep Discharge Battery Protection contactor.
Cabin options for Rectifier and Battery Group
Analogue Meterings for Output and Battery
Power Analyzer option for Input
DC CHARGER / RECTIFIER
Battery voltage
Boost voltage
Float voltage
AUTOMATIC BOOST
Time hour
0
Automatic boost charge can also be selected on menu. The automatic boost
menu
Battery
current has the options for selecting the boost
and float current based on battery capacity. Suitable float and boost currents of the battery are set before selecting the
automatic boost option. After the set-up, the automatic boost function will monitor the battery current and select boost or
float option by referring to the set values. If the charging current Charge
is higher
than the set boost current, the system will select
current
boost and if the charging current is lower than the set float current the system will select float option. In case of low battery
alarm, the automatic boost will select boost option until the battery
charging current reaches to the set float value.
Boost current
Float current
Time hour
0
6
8
Battery automatic boost/float charge technique
Boost voltage
Float voltage
Time hour
0
VOLTAGE (V)
Battery current
Boost
Float
Charge current
Amper (I)
Boost current
Battery
Float current
Time hour
0
6
8
Battery automatic boost/float charge technique
Output
Boost
Float
Amper (I)
Battery
Output
10
DC CHARGER / RECTIFIER
HIGH PROTECTION
FULLY CONTROLLED THRYSTOR RECTIFIER MODULE
COMPLETE ISOLATION
PMI DC Chargers are fully isolated since an isolation transformer is placed in between the input and output and because the
DC current is controlled by a DC current module. Therefore, the load is always safe even at high input voltage and congested
mains conditions. In addition, the failure risk is minimized as semi-conductors are used for the rectifier. Standard L-C filters at
the output maintain safe charging of the battery groups.
PROTECTIONS
DC RIPPLE < 1%
11
DC CHARGER / RECTIFIER
PARALLELING
The Charger has a modular design to provide service and maintenance
simplicity. The outputs of the Battery Chargers can be connected in
parallel. The parallel system can be active load sharing or hot-standby.
Besides this, parallel system can be placed in one unit industrial cabin
as seen from the picture on the right side or they can be placed in
different cabins based on the requirement.
12
DC CHARGER / RECTIFIER
13
DC CHARGER / RECTIFIER
REMOTE MONITORING
On both LCD panel and communication interface, all key parameters can be set and real time base
events and failures can be tracked. In parallel operation multiple rectifiers can be controlled by
the help of same communication interface. The communication is executed via RS 485/ModBus,
Profibus, TCP/IP or SMS/Mail Order.
14
DC CHARGER / RECTIFIER
PRODUCT PERFORMANCE
SOFT START FEATURE
DYNAMIC RESPONSE
MICROPROCESSOR CONTROL
15
DC CHARGER / RECTIFIER
Monophase Input
Threephase Input
For 3 phase input 6 Pulse Thyristor controlled AC/DC Rectifier with input isolation transformer
Optional 12 Pulse Thyristor controlled AC/DC Rectifier with input isolation transformer
110 VAC / 115VAC /208 VAC / 220 VAC / 190 VAC / 200 VAC /380 VAC / 400 VAC / 415 /
230 VAC / 240 VAC 15%
480 VAC 15%
50 / 60 Hz 5%
>0.8 Inductive (>0.9 with 12 Pulse Rectifier)
Galvanically isolated
<35% (standard); <10% (with 12 Pulse Rectifier)
Thermic-Magnetic Over Current Protection, Over Voltage Protection, Phase Sequence
Free Operation (3 Phase), Soft Start, MCB
12 VDC / 24 VDC / 48 VDC / 110 VDC / 220 VDC
24VDC output: 10VDC to 30VDC, 48VDC output: 48VDC to 60VDC, 110VDC output:
110VDC to 160VDC, 220VDC output: 220VDC to 300VDC
0-100% of Nominal Output Current
0-100% of Nominal Output Current
100% to 120% of Floating Output Voltage
2,4 lead acid battery 1,60 NiCd Battery (Might change based on battery brand)
2,23 lead acid battery 1,40 NiCd battery (Might change based on battery brand)
1% (Lower values available upon request)
Available upto 1000 Amp (12 Pulse over 400 Amp) (100 A was selected)
100% of nominal output current
<1% RMS AC of Output Voltage
2% of Output Voltage (100% load change)
Constant Current/ Constant Voltage
Short Circuit Protection, Over Voltage Protection, Reverse Voltage Protection,
Short Circuit, MCB or NH Fuse (based on current value)
L-C filters, Overcurrent Electronic protection, Over Voltage Protection and Thermic Fuse
0 99.9 hours adjustable
Forced fans with smart fan controlling system (Natural Cooling Optional)
2500VAC input/chassis and output/chassis
>80% (Higher values optional)
>90% (Higher values optional)
100,000 Hrs. (w/out battery group)
-10 / + 40 C (Higher Temperature Control, Optional)
IP20 (Standard); IP31 / IP42 / IP54 (Optional)
16
DC CHARGER / RECTIFIER
Enclosure Material
Cable Entry
Access to Batteries
Relative Humidity
Circuit Breakers
Silicon Dropper
Reset Button
Boost inhibit
DISPLAY PANEL
Front Panel Measured
Values
Front Panel Indicators
17
18
GROUP COMPANIES
www.pmienergy.com
PMI & OES GROUP COMPANIES reserves the right to make alterations on technical specifications.