TSHK 670...672: Fan-coil room-temperature controller, heating-cooling sequence
For flexible individual-room control in residential and business premises. For quasi-continuous
temperature control of air-conditioning systems (fan-coil). Gradual change-over from heating to cooling
via a sequence characteristic. For 2-point pulsed operation. Suitable for thermal drives, ventilators or
cooling equipment in air-conditioning systems.
Housing 127 75 mm of pure-white (RAL 9010), flame-retardant thermoplastic (fire class as per
UL94 HB). Black baseplate with NTC sensor, electronic evaluation unit and switching relay. Setpoint
adjuster with scale and rear mechanical min./max. limitation of the setting range. Suitable for mounting
onto walls or recessed junction boxes. Cable inlet at rear. Separate terminal compartment with screw
terminals (for wire of max. 2,5 mm2).
Type
Operating mode
Number of
switches
Power
Weight
kg
1
2
230 V~
230 V~
230 V~
0,18
0,18
0,18
T
Y01938
E (control factor)
1
TSHK 670
TSHK 671
TSHK 672
1 LED
A09161
A09162
A09163
Power supply 1)
Switch rating
Ventilator
10%, 50...60 Hz
10(4) A, 230 V~
6 (3) A, 230 V~
Setting range
P-band Xp
Sequence dead zone
Hysteresis1)
Shortest switching period
5...30 C
23K
2 K 0,7
approx. 0,1...0,5 K
approx. 19 min (E = 0,5)
0,5
0
Xp
Wiring diagram
Dimension drawing
Fitting instructions
see table
M09206
MV 505680
Xs
Xp
E=0,25
E=0,50
E=0,75
B09204
Accessories
0362239 001* Intermediate cover plate in pure white; fits various recessed junction boxes
*)
1)
The device is electronically made to pulse. The control factor initially falls to nought at the heating output as the temperature rises. After a
dead zone, the control factor rises at the cooling output. The pulsing causes a small temperature deviation of 0,1...0,5 K, depending on
the time constant of the room.
Operation
The room temperature is measured using an internal NTC temperature sensor and then compared
with the setpoint. An electric switching relay is operated in relation to the temperature deviation. When
the setpoint has been reached, the switch moves to the mid-position (OFF). The controllers operating
points are determined by the setpoint, the dead zone and the proportional band.
Sauter Components
7121165003 02
21.165/2 TSHK
Wiring diagrams
TSHK 670
TSHK 670
T
30
25
N
20
15
10
5
B09201
N
L
A09161
TSHK 671
TSHK 671
T
ON
30
C
N
25
OFF
20
15
10
N
L
B09202
A09162
TSHK 672
TSHK 672
T
T
ON
ON
30
C
N
25
5
I
OFF
4
II
3
III
20
15
10
5
B09203
Sauter Components
A09163
7121165003 02
TSHK
21.165/3
Dimension drawing
28,6
75
127
M09206
Accessories
135,5
11,5
83
362239
M09152
Sauter Components
Printed in Switzerland
Right of amendment reserved
N.B.: A comma between cardinal
numbers denotes a decimal point
Fr. Sauter AG, CH-4016 Basle
7121165003 02