You are on page 1of 4

<<Contents>> <<Index>>

Terminal Boards (for FIO)

General
Specications
GS 33K50H50-50E

[Release 5]

GENERAL

This document describes the specications of terminal boards used for FIOs of CENTUM VP systems.

STANDARD SPECIFICATIONS
Model
AEA3D

AEA4D

Description
For 2-wire Transmitter
(for single or dual redundant
modules)

For analog signals


(for single or dual redundant
modules)

AET4D

For thermocouple
(for single or dual redundant
modules)

AED5D

For digital signals


(for single or dual redundant
modules)

For eldbus
(for single or dual redundant
modules)
For resistance temperature
AER4D
detectors
For resistance temperature
MRT(*2)
detectors

AEF9D

Points

Terminals

8 pts x 4

M4 screws

8 pts x 2

M4 screws

16 pts x 2

16 pts x 2

M4 screws

Modules
Connected
AAI135
AAI835
AAP135
AAI135
AAI835
AAP135
AAI141
AAV141
AAV142
AAV144
AAB841
AAI841
AAV542
AAV544
AAI143
AAI543

Connection
Weight
Cable
KS1

1.8 kg

KS1

1.5 kg

Insulation resistance: 100


M or greater at 500 V DC

M4 screws

AAT145

M4 screws

ADV151
AKB331
ADV551
ADV161 (*1)
AKB337
ADV561 (*1)

1.5 kg

4 ports x 4 M4 screws

ALF111

AKB336

1.8 kg

16 pts

M4 screws

AAR145

AKB335

1.5 kg

16 pts x 2

M4 screws

AAR145

KS8

1.8 kg

32 pts x 1

Specications

KS1

1.8 kg

Withstanding voltage: 500


V AC for 1 minute

Insulation resistance: 100


M or greater at 500 V DC

AEC4D

For digital signals


(for single or dual redundant
modules)

16 pts x 2

M4 screws

ADV141
ADV142
ADR541

AKB332
AKB333
AKB334

1.8 kg

Withstanding voltage:
Between commons;
1500 V AC for 1 minute,
common minus side
every 8-channel
Between signal and case;
2300 V AC for 1 minute

Note: Be sure to leave the connector caps on connectors that are not used, in order to protect the connector pins and prevent
dust from accumulating on them.
*1:
Two sets of AED5D or AKB337 are required for one set of ADV161 or ADV561.
*2:
For details on the MRT, see GS 33K55R40-50E.

Yokogawa Electric Corporation


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33K50H50-50E
Copyright Aug. 2011 (YK)
2nd Edition Apr. 1, 2013 (YK)

<<Contents>> <<Index>>

EXTERNAL DIMENSIONS
Terminal Boards
AEA3D
(85)
18.4

66.6
34.6

Unit: mm

482.6
8.75
21.3

465.1
440

57.15
132.5

37.7

Hole for 19-inch rack mounting


(4 M5 screw holes)
F01E.ai

AEA4D, AET4D
(85)
18.4

66.6
34.6

Unit: mm

482.6
8.75

465.1

21.3

440

88.1

37.7

Hole for 19-inch rack mounting


(2 M5 screw holes)
F02E.ai

AED5D
(85)
18.4

66.6
34.6

Unit: mm

482.6
8.75

465.1

21.3

440

88.1

37.7

Hole for 19-inch rack mounting


(2 M5 screw holes)
F03E.ai

All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation

GS 33K50H50-50E Aug. 19, 2011-00

<<Contents>> <<Index>>
AEC4D
(85)
18.4

66.6
34.6

Unit: mm

482.6
8.75

465.1

21.3

440

57.15
132.5

37.7

Hole for 19-inch rack mounting


(4 M5 screw holes)
F04E.ai

AER4D
(85)
18.4

66.6
34.6

Unit: mm

482.6
8.75

465.1

21.3

440

88.1

37.7

Hole for 19-inch rack mounting


(2 M5 screw holes)
F05E.ai

AEF9D
(85)
18.4

66.6
34.6

Unit: mm

482.6
8.75

465.1

21.3

440

57.15
132.5

37.7

Hole for 19-inch rack mounting


(4 M5 screw holes)
F06E.ai

All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation

GS 33K50H50-50E Aug. 19, 2011-00

<<Contents>> <<Index>>

MODELS AND SUFFIX CODES


Terminal Board for Analog
(single and dual-redundant)

Model

AEA3D
-0
5

Sufx
Codes

6
E
F

Description
Terminal Board for Analog
(single and dual-redundant, 8channel)
Always 0
Basic type with no explosion
protection
With ISA Standard G3 option and no
explosion protection
Basic type with explosion protection
With ISA Standard G3 option and
explosion protection

Terminal Board for Analog


(single and dual-redundant)

Model

AEA4D
-0
5

Sufx
Codes

6
E
F

Description
Terminal Board for Analog
(single and dual-redundant, 16channel)
Always 0
Basic type with no explosion
protection
With ISA Standard G3 option and no
explosion protection
Basic type with explosion protection
With ISA Standard G3 option and
explosion protection

Terminal Board for Thermocouple


(single and dual-redundant)

Model

AET4D
-0
5

Sufx
Codes

6
E
F

Description
Terminal Board for Thermocouple
(single and dual-redundant, 16channel)
Always 0
Basic type with no explosion
protection
With ISA Standard G3 option and no
explosion protection
Basic type with explosion protection
With ISA Standard G3 option and
explosion protection

Terminal Board for Digital (single and dualredundant)

Model

AED5D
-0
5

Sufx
Codes

6
E
F

Description
Terminal Board for Digital
(single and dual-redundant, 32channel)
Always 0
Basic type with no explosion
protection
With ISA Standard G3 option and no
explosion protection
Basic type with explosion protection
With ISA Standard G3 option and
explosion protection

Note: When the AED5D is used in voltage output mode,


it does not conform to Non-Incendive standard.
All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation
Subject to change without notice.

Terminal Board for Digital


(single and dual-redundant)
Model

AEC4D
-5
-6
-7
5

Sufx
Codes

6
E
F

*1:

Description
Terminal Board for Digital (single and
dual-redundant, 16-channel)
For 100 V - 120 V AC input
For 220 V - 240 V AC input
For Relay output
Basic type with no explosion
protection
With ISA Standard G3 option and no
explosion protection
Basic type with explosion protection
(*1)
With ISA Standard G3 option and
explosion protection (*1)

These sufx codes cannot be specied with


AEC4D-6.

Terminal Board for Resistance Temperature


Detectors (single and dual-redundant)

Model

AER4D
-0
5

Sufx
Codes

6
E
F

Description
Terminal Board for resistance
temperaure detectors
(single and dual-redundant, 16channel)
Always 0
Basic type with no explosion
protection
With ISA Standard G3 option and no
explosion protection
Basic type with explosion protection
With ISA Standard G3 option and
explosion protection

Terminal Board for Fieldbus


(single and dual-redundant)
Model

AEF9D
-0
5

Sufx
Codes

6
E
F

Description
Terminal Board for Fieldbus
(single and dual-redundant)
Always 0
Basic type with no explosion
protection
With ISA Standard G3 option and no
explosion protection
Basic type with explosion protection
With ISA Standard G3 option and
explosion protection

ORDERING INFORMATION

Specify model and sufx codes.


For selecting the right products for explosion protection,
please refer to TI 33Q01J30-01E without fail.

TRADEMARK

CENTUM is a registered trademark of Yokogawa


Electric Corporation.
Other company names and product names in this
document are registered trademarks or trademarks of
their respective holders.
GS 33K50H50-50E

Apr. 1, 2013-00

You might also like