You are on page 1of 56

CHAPTER-1

INTRODUCTION
1.1.INTRODUCTION

TO WIND ENER

The wind is a free, clean, and inexhaustible energy source. It has served
mankind well for many centuries by propelling ships and driving wind turbines to
grind grain and pump water. Interest in wind power lagged, however, when cheap and
plentiful petroleum products became available after World War II. The high capital
costs and the uncertainty of the wind placed wind power at an economic disadvantage.
Then in 1973, the Arab nations placed an embargo on petroleum. The days of cheap
and plentiful petroleum were drawing to an end. People began to realize that the
worlds oil supplies would not last forever and that remaining supplies should be
conserved for the petrochemical industry. The use of oil as a boiler fuel, for example,
would have to be eliminated. Other energy sources besides oil and natural gas must be
developed.
The two energy sources besides petroleum which have been assumed able to
supply the long term energy needs of the United States are coal and nuclear energy.
Many people think there is enough coal for several centuries at present rates of
consumption, and likewise for nuclear energy after the breeder reactor is fully
developed. These are proven resources in the sense that the technology is highly
developed, and large coal and nuclear powered electrical generating plants are in
operation and are delivering substantial blocks of energy to the consumer.
Unfortunately, both coal and nuclear present serious environmental problems.
Coal requires large scale mining operations, leaving land that is difficult or
impossible to restore to usefulness in many cases. The combustion of coal may upset
the planets heat balance. The production of carbon dioxide and sulfur dioxide may
affect the atmosphere and the ability of the planet to produce food for its people. Coal
is also a valuable petrochemical feedstock and many consider the burning of it as a
boiler fuel to be foolish.
Nuclear energy has several advantages over coal in that no carbon dioxide or
sulfur dioxide are produced, mining operations are smaller scale, and it has no other
major use besides supplying heat. The major difficulty is the problem of waste
disposal, which, because of the fears of many, will probably never have a truly
satisfying solution.

Because of these problems, wind power and other forms of solar power are
being strongly encouraged. Wind power may become a major source of energy in
spite of slightly higher costs than coal or nuclear power because of the basically noneconomic or political problems of coal and nuclear power. This is not to say that wind
power will always be more expensive than coal or nuclear power, because
considerable progress is being made in making wind power less expensive. But even
without a clear cost advantage, wind power may become truly important in the world
energy picture.

1.2.WIND TURBINES
A wind turbine is a rotating machine which converts the kinetic energy in
wind into mechanical energy. If the mechanical energy is then converted to electricity,
the machine is called a wind generator, wind turbine, wind power unit (WPU), wind
energy converter (WEC), or aero generator. Wind turbines can be separated into two
types based by the axis in which the turbine rotates. Turbines that rotate around a
horizontal axis are more common. Vertical-axis turbines are less frequently used.

1.2.1.HORIZONTAL AXIS WIND TURBINES


The Federal Wind Energy Program had its beginning in 1972 when a joint
Solar Energy Panel of the National Science Foundation (NSF) and the National
Aeronautics and Space Administration (NASA) recommended that wind energy be
developed to broaden the Nations energy options for new energy sources.[9]
Horizontal-axis wind turbines (HAWT) have the main rotor shaft and
electrical generator at the top of a tower, and must be pointed into the wind. Most
have a gearbox, which turns the slow rotation of the blades into a quicker rotation that
is more suitable to drive an electrical generator. Since a tower produces turbulence
behind it, the turbine is usually pointed upwind of the tower. Turbine blades are made
stiff to prevent the blades from being pushed into the tower by high winds.

Additionally, the blades are placed a considerable distance in front of the tower and
are sometimes tilted up a small amount.

Horizontal axis wind turbine

Downwind machines have been built, despite the problem of turbulence,


because they don't need an additional mechanism for keeping them in line with the
wind, and because in high winds the 3 blades can be allowed to bend which reduces
their swept area and thus their wind resistance. Since cyclic (that is repetitive)
turbulence may lead to fatigue failures most HAWTs are upwind machines.
HAWT ADVANTAGES

Variable blade pitch, which gives the turbine blades the optimum angle of attack.
Allowing the angle of attack to be remotely adjusted gives greater control, so the
turbine collects the maximum amount of wind energy for the time of day and season.
The tall tower base allows access to stronger wind in sites with wind shear. In some
wind shear sites, every ten meters up, the wind speed can increase by 20% and the
power output by 34%.
High efficiency, since the blades always move perpendicularly to the wind, receiving
power through the whole rotation. In contrast, all vertical axis wind turbines, and most
proposed airborne wind turbine designs, involve various types of reciprocating

actions, requiring airfoil surfaces to backtrack against the wind for part of the cycle.
Backtracking against the wind leads to inherently lower efficiency.

HAWT DISADVANTAGES

The tall towers and blades up to 90 meters long are difficult to transport.

Transportation can now cost 20% of equipment costs.


Tall HAWTs are difficult to install, needing very tall and expensive cranes and
skilled operators.
Massive tower construction is required to support the heavy blades, gearbox, and
generator
Reflections from tall HAWTs may affect side lobes of radar installations creating
signal clutter, although filtering can suppress it.
Downwind variants suffer from fatigue and structural failure caused by turbulence
when a blade passes through the tower's wind shadow (for this reason, the majority of
HAWTs use an upwind design, with the rotor facing the wind in front of the tower).
HAWTs require an additional yaw control mechanism to turn the blades toward the
wind.

1.2.2.VERTICAL AXIS WIND TURBINES


Vertical-axis wind turbines (or VAWTs) have the main rotor shaft arranged
vertically. Key advantages of this arrangement are that the turbine does not need to be
pointed into the wind to be effective. This is an advantage on sites where the wind
direction is highly variable. VAWTs can utilize winds from varying directions. With a
vertical axis, the generator and gearbox can be placed near the ground, so the tower
doesn't need to support it, and it is more accessible for maintenance. Drawbacks are
that some designs produce pulsating torque. Drag may be created when the blade
rotates into the wind.

VAWT ADVANTAGES
A massive tower structure is less frequently used, as VAWTs are more frequently
mounted with the lower bearing mounted near the ground.
Designs without yaw mechanisms are possible with fixed pitch rotor designs.
A VAWT can be located nearer the ground, making it easier to maintain the moving
parts.
VAWTs have lower wind startup speeds than HAWTs. Typically, they start creating
electricity at 6 M.P.H. (10 km/h).
VAWTs may have a lower noise signature.
VAWT DISADVANTAGES
Most VAWTs produce energy at only 50% of the efficiency of HAWTs in large part
because of the additional drag that they have as their blades rotate into the wind.

While VAWTs' parts are located on the ground, they are also located under the
weight of the structure above it, which can make changing out parts nearly impossible
without dismantling the structure if not designed properly.
Having rotors located close to the ground where wind speeds are lower due to wind
shear, VAWTs may not produce as much energy at a given site as a HAWT with the
same footprint or height.
Because VAWTs are not commonly deployed due mainly to the serious
disadvantages mentioned above, they appear novel to those not familiar with the wind
industry. This has often made them the subject of wild claims and investment scams
over the last 50 years.

1.3.CONTROL OF WIND TURBINES


1.3.1.POWER CONTROL
A wind turbine is designed to produce a maximum of power at wide spectrum of wind
speeds. The wind turbines have three modes of operation:
Below rated wind speed operation
Around rated wind speed operation
Above rated wind speed operation
If the rated wind speed is exceeded the power has to be limited. There are various
ways to achieve this.

1.3.2.STALL CONTROL
Stalling works by increasing the angle at which the relative
wind strikes the blades (angle of attack), and it reduces the induced
drag (drag associated with lift). Stalling is simple because it can be
made to happen passively (it increases automatically when the
winds speed up), but it increases the cross-section of the blade face7

on to the wind, and thus the ordinary drag. A fully stalled turbine
blade, when stopped, has the flat side of the blade facing directly
into the wind.
A fixed-speed HAWT inherently increases its angle of attack at
higher wind speed as the blades speed up. A natural strategy, then,
is to allow the blade to stall when the wind speed increases. This
technique was successfully used on many early HAWTs. However, on
some of these blade sets, it was observed that the degree of blade
pitch tended to increase audible noise levels.

1.3.3.PITCH CONTROL
Furling works by decreasing the angle of attack, which
reduces the induced drag from the lift of the rotor, as well as the
cross-section. One major problem in designing wind turbines is
getting the blades to stall or furl quickly enough should a gust of
wind cause sudden acceleration. A fully furled turbine blade, when
stopped, has the edge of the blade facing into the wind.
Standard modern turbines all pitch the blades in high winds.
Since pitching requires acting against the torque on the blade, it
requires some form of pitch angle control. Many turbines use
hydraulic systems. These systems are usually spring loaded, so that
if hydraulic power fails, the blades automatically furl. Other turbines
use an electric servomotor for every rotor blade. They have a small
battery-reserve in case of an electric-grid breakdown. Small wind
turbines (under 50 kW) with variable-pitching generally use systems
operated by centrifugal force, either by flyweights or geometric
design, and employ no electric or hydraulic controls.
1.3.4.OTHER CONTROLS
Yawing
8

Modern large wind turbines are typically actively controlled to


face the wind direction measured by a wind vane situated on the
back of the nacelle. By minimizing the yaw angle (the misalignment
between wind and turbine pointing direction), the power output is
maximized and non-symmetrical loads minimized. However, since
the wind direction varies quickly the turbine will not strictly follow
the direction and will have a small yaw angle on average. The power
output losses can simplified be approximated to fall with cos3(yaw
angle).
Electrical braking
Braking of a small wind turbine can also be done by dumping
energy from the generator into a resistor bank, converting the
kinetic energy of the turbine rotation into heat. This method is
useful if the kinetic load on the generator is suddenly reduced or is
too small to keep the turbine speed within its allowed limit.
Cyclically braking causes the blades to slow down, which
increases the stalling effect, reducing the efficiency of the blades.
This way, the turbine's rotation can be kept at a safe speed in faster
winds while maintaining (nominal) power output. This method is
usually not applied on large grid-connected wind turbines.
Mechanical braking
A mechanical drum brake or disk brake is used to hold the turbine at
rest for maintenance. Such
brakes

are

usually

applied

only

after

blade

furling

and

electromagnetic braking have reduced the turbine speed, as the


mechanical brakes would wear quickly if used to stop the turbine
from full speed. There can also be a stick brake.
9

1.4.GENERATORS
A generator is a device which converts mechanical energy into
electrical energy. Wind generators have traditionally been wind
turbines, i.e. a propeller attached to an electric generator attached
to appropriate electronics to attach it to the electrical grid.
Generators can be classified broadly into two categories:
a) Synchronous Generators
b) Asynchronous Generators
The basis of this categorization is the speed at which the generators
are run. Synchronous generators are run at synchronous speed
(1500 rpm for a 4 pole machine at 50Hz frequency) while
asynchronous generators run at a speed more than the synchronous
speed.

1.4.1.SYNCHRONOUS GENERATOR
Synchronous generators are doubly fed machines which
generate electricity by the principle when the magnetic field around
a conductor changes, a current is induced in the conductor.
Typically, a rotating magnet called the rotor turns within a stationary
set of conductors wound in coils on an iron core, called the stator.
The field cuts across conductors, generating an electrical current, as
the mechanical input causes the rotor to turn.

1.4.2.ASYNCHRONOUS GENERATOR
Asynchronous generators or Induction generators are singly
excited a.c. machine. Its stator winding is directly connected to the

10

ac source whereas its rotor winding receives its energy from stator
by means of induction. Balanced currents produce constant
amplitude rotating mmf wave. The stator produced mmf and rotor
produced mmf wave, both rotate in the air gap in the same direction
at synchronous speed. These two mmf s combine to give the
resultant air-gap flux density wave of constant amplitude and
rotating at synchronous speed. This flux induces currents in the
rotor and an electromagnetic torque is produced which rotates the
rotor.
Asynchronous generators are mostly used as wind turbines as they
can be operated at variable speed unlike synchronous generator.
Two kinds of asynchronous generators are used namely
a) Squirrel cage induction generator (SCIG)
b) Doubly fed induction generator (DFIG)

1.4.3.SQUIRREL CAGE INDUCTION GENERATOR


A squirrel cage rotor is the rotating part. In overall shape it is a cylinder
mounted on a shaft. Internally it contains longitudinal conductive bars (usually made
of aluminum or copper) set into grooves and connected together at both ends by
shorting rings forming a cage-like shape. The core of the rotor is built of a stack of
iron laminations. The field windings in the stator of an induction motor set up a
rotating magnetic field around the rotor. The relative motion between this field and
the rotation of the rotor induces electric current in the conductive bars. In turn these
currents lengthwise in the conductors react with the magnetic field of the motor to
produce force acting at a tangent to the rotor, resulting in torque to turn the shaft. In
effect the rotor is carried around with the magnetic field but at a slightly slower rate of
rotation. The difference in speed is called slip and increases with load.

1.4.4.DOUBLY FED INDUCTION GENERATOR

11

DFIG is Double Fed Induction Generator, a generating principle widely


used in wind turbines. It is based on an induction generator with a
multiphase wound rotor and a multiphase slip ring assembly with
brushes for access to the rotor windings.

1.5.PRINCIPLE OF A DOUBLE FED INDUCTION GENERATOR


CONNECTED TO A WIND TURBINE
The principle of the DFIG is that rotor windings are connected
to the grid via slip rings and back to- back voltage source converter
that controls both the rotor and the grid currents. Thus rotor
frequency can freely differ from the grid frequency (50 or 60 Hz).
By controlling the rotor currents by the converter it is possible
to adjust the active and reactive power fed to the grid from the
stator independently of the generators turning speed. The control
principle used is either the two-axis current vector control or direct
torque control (DTC). DTC has turned out to have better stability
than current vector control especially when high reactive currents
are required from the generator

12

The doubly-fed generator rotors are typically wound with from 2 to 3 times
the number of turns of the stator. This means that the rotor voltages will be higher and
currents respectively lower. Thus in the typical 30 % operational speed range
around the synchronous speed the rated current of the converter is accordingly lower
leading to a low cost of the converter.

CHAPTER-2
INTRODUCTION TO WIND-DIESEL H
13

2.1.INTRODUCTION
A Wind Diesel Hybrid System (WDHS) is any autonomous electricity
generating system using Wind Turbine Generators(s) (WTG)with Diesel Generator(s)
(DG) to obtain a maximum contribution by the intermittent wind resource to the total
produced power, while providing continuous high quality electric power [1]. The
main goal with these systems is to reduce fuel consumption and in this way to reduce
system operating costs and environmental impact. If the WDHS is capable of shutting
down the Diesel Generators during periods of high wind availability, the WDHS is
classified as high wind penetration. High penetration (HP) WDHS have three
operation modes: Diesel Only (DO), Wind Diesel (WD) and Wind Only (WO)
In DO mode the Diesel Generators supply the active and reactive power
demanded by the consumer load (WTGs are disconnected). In WD mode, in addition
to DG(s), WTG(s) also supply active power. In WO mode the Diesel Generators are
14

not running, only the wind turbines are supplying active power, so that no fuel is
consumed in this mode. Several papers have been published on the subject of WDHS
dynamic simulation.
In the interaction between one DG and a constant/ variable speed WTG is
studied. In a no-storage WDHS is simulated against several perturbations, among
them the connection of a WTG to the DG isolated grid (DO to WD transition). In a
previous work [5] a HP-WDHS with a BESS is simulated in WO mode, but the
battery is modeled by a simple constant voltage source. In [6] the modeled HP-WDHS
has a DG with a locked-disengaged simplified clutch model and it is simulated the
mandatory transition from WO to WD when the active power generated is less than
consumed.
During this type of WO to WD transition the power system is without control
until the DE is added to the system. In the present article the WO mode is also
simulated, but a more elaborated model for a Ni-Cd battery is used and the main
battery variables: current, voltage and state of charge are presented during the
simulation. Additionally, in the present article a more realistic clutch model is also
used to transition from WO to WD, but in this case the transition simulated is
controlled and it is done in order to substitute a supplying BESS by the DE.
The different isolated hybrid power systems considered in the paper are multiwind/single diesel, and single wind/multi- diesel. Multi-wind/single diesel systems
attenuate the effect of power fluctuations produced by the turbulence of the wind. In
fact, it is estimated that the variability of the power should decrease by the square root
of the number of wind turbines[1]. Thus the need for short-term storage would
decrease when the wind generation capacity is made up of more than one machine.
Single wind/ multi-diesel systems allow a variety of possible operation and control
strategies.
Typically the most efficient diesel generators are allowed to run at their rated
output. Load fluctuations are supplied by one of the less efficient diesel generators,
which are allowed to cycle up and down. Diesel grid of Block Island, USA [1] is such
type of an example. First the system state equations are derived from real and reactive
15

power balance equations of the system. A voltage deviation signal is used by


STATCOM controller to eliminate the reactive power mismatch in the system. Also
the voltage deviation signal is used by excitation system of the synchronous generator
to eliminate the voltage deviation.

2.2.OVERVIEW OF WIND DIESEL HYBRID SYSTEM


Given the significant economic (and environmental) incentives to add wind
energy to remote diesel generator systems. the technical aspects must also be
addressed. The peak demand loads of remote communities in Canada typically nm
from 45 kW to 6.7 MW .The installed capacity in the generation plant. typically
comprising three to five diesel generation. is usually large enough (approximately
twice the peak dernand) to allow for future demand load growth, and to accommodate
at least one machine king out of service. in moa modem installations, the sizes of the
diesel generator are staggered such that the appropriately sized generator(s) can be
engaged to most efficiently meet the demand load at that the. Diesel engine
manufacturers advise a minimum operating load of approximately 20 to 40 per cent in
order to maintain high fuel efficiency and to avoid excessive fouling and Wear.

[ FIGURE 1: GENERAL WIND DIESEL SYSTEM]


16

Wind is a random and highly variable source of energy. The scales of wind
variation range

term to long term short seasonal to hourly fluctuation. down to

short-term fluctuation in the order of minutes to seconds due to local turbulence

(gusts). Long-term wind trends cm be for- from weather patterns and disperse
monitoring stations.
Demand loads also exhibit short-term and long-term frequency trends. but
unlike the wind they are relatively easy to predict (both in frequency and amplitude)
since they follow the community's habits. With the knowledge of the demand pattern
throughout the &y, the load can be anti cipateci, and the appropriate diesel generation
capacity can be brought on line to provide a disable and optimally efficient supply.
With a significant mount of wind energy in the power mix, it is the short-term
fluctuation of the wind that is the greatest impediment to wind-diesel integration.
Diesel generators respond rapidly to load variations in order to keep the system's
frequency and voltage within an acceptable range. This makes them well suited for
operation with wind energy while the wind power penetration remains low.
With higher levels of penetration. additional controls will be needed to
maintain the stability and power quality of the system. A general wind-diesel system
is shown in Figure 1 The initial diesel system comprises the diesel generators
supplying the village load. With the addition of the wind turbines, a dump load will
most likely be needed to absorb the excess energy whenever the generated wind
power exceeds the darned. A clutch may be added between the engines and the
generators of some, or ail, of the diesel generator sets to allow the synchronous
generators to operate as synchronous condensers when it is desirable to nin
exclusively from wind power. In this system the synchronous generators regulate the
grid voltage and provide

2.3.THE ISOLATED POWER SYSTEM (WIND -DIESEL HYBRID


SYSTAM ARCHITECTURE)

17

The high penetration WDHS of Fig. 2 comprises one DG and one WTG. The
DG consists of a Diesel Engine (DE), a Synchronous Machine (SM), and a friction
clutch. The SM generates the voltage waveform of the isolated grid and its automatic
voltage regulator controls the system voltage to be within the prescribed levels during
the three modes of operation. For this reason the SM must be always running close to
its rated speed. The DE provides mechanical power to the SM and its speed governor
(speed regulator+ actuator) controls the DE speed. In this article the DE speed control
is isochronous, so the diesel speed governor will command the necessary fuelling rate
to make the DE run at constant speed.
The DE is needed to supply active power and regulate the system frequency in
the DO and WD modes. The clutch has three states: engaged, locked and disengaged .
If the clutch is disengaged, the frictional surfaces are not in contact and no torque is
transferred from the DE to the SM, so that if CT is closed the operation mode is WO.
In WO mode since the DE and SM axes are independent, the DE must not be running
in order to save fuel, but in this paper it will run at slow speed as it is explained later
on. With the clutch engaged, the frictional surfaces slip past one another and kinetic
friction torque is transferred to the SM. Finally, if the clutch is locked, the frictional
surfaces are locked together without slipping and static friction torque is transferred to
the SM. With the clutch locked the DE and SM turn at the same speed and the WDHS
is in the DO/WD mode if the WTG circuit breaker CT is opened/closed respectively.
Several real HP-WDHS include a clutch to transition from WO to WD modes and
vice versa
The WTG consists of a Wind Turbine (WT) driving an Induction Generator
(IG) directly connected to the autonomous grid conforming a constant speed stallcontrolled WTG (no pitch control). The WTG produced active power PT depends
among other factors on the cube of the wind speed and since the WT used has no pitch
control, there is no way to control the WTG active power, so it behaves as an
uncontrolled source of active power. The IG consumes reactive power so a capacitor
bank has been added to compensate the power factor. The Dump Load (DL) consists
of a set of semiconductor power switches and a binary bank of resistors. By
closing/opening these power switches, the dl consumed active power can be
controlled behaving as a controlled sink of active power. the battery based energy
18

storage system (bess) consists of a battery bank and a power converter that interfaces
the battery bank to the autonomous grid. the bess can store or retrieve power as
needed, so it behaves as a controlled sink/source of active power.
The system frequency is regulated by maintaining an instantaneous balance of
the active power consumed and produced. in do and wd modes the de speed governor
modulates the de active power in order to accomplish this balance, so the de behaves
as a controlled source of active power. in wo mode the clutch is disengaged and the
active power consumed by the load (pl) is produced only by the wtg (pt).
Since pt (also called wind power) and pl are uncontrolled the DL + BESS must
perform the instantaneous balance of the active power. being pd the power consumed
by the dl, ps the power consumed/supplied by the BESS, j the SM inertia and x the
SM shaft speed, the power equation of the SM in wo mode if no losses are taking into
account is

19

[ Fig. 2. Layout of the isolated WDHS ]

Where PT is considered positive if produced and PL, PD and PS are


considered positive if consumed. In Eq. (1) the SM shaft speed x is in rad/s ant it is
related with the system frequency (frequency of the voltage waveform) f by x = 2pf/p,
with p the number of pole pairs of SM. Eq. (2) shows that to obtain a synchronous
shaft speed constant (dx/dt = 0), the DL + BESS combination must consume power
when PT exceeds PL and the BESS must generate power when PT is less than PL

The situation where the BESS supplies power is temporary, so that if this
situation persists the control system of the WDHS must order to start the DE and
when the speed difference between DE and SM is small enough engaged the clutch,
changing to the WD mode. With the clutch locked the DE will supply the necessary
20

active power PDE to keep the system frequency at rated value. Finally to obtain Eq.
(1) in WD mode, PDE (positive when produced)must be added to the left side of (1)
and J must be the sum of the DE + SM inertia

21

CHAPTER-3

3.1.OPERATING STATES OF WIND DIESEL HYBRID


SYSTEM
There are three devices subject to the direct control of the wind-diesel
controller: the rotary converter AC machine, the rotary converter DC machine, and the
secondary load controller (which actually consists of multiple distributed load

controllers). Each of these devices has several different control modes associated with
THE
CONTROL MECHANISM OF WIND-DIE
it. For example, the AC machine can be controlled to achieve any of the following:

22

Match voltage with the AC bus (prior to synchronization)


Share reactive power with the diesel generators
Deliver a specified amount of reactive power to the grid
Regulate AC bus voltage
The power flow management algorithm determines the appropriate control
mode for each of these three devices depending on the operating state of the power
system.
The Wales wind-diesel hybrid power system involves multiple diesels and
multiple wind turbines. In addition there is a power converter consisting of two
separate rotating machines and a secondary load that is divided into local dump
load and remote dump load. Because each of these components may or voltage
source inverter, the frequency is typically set by a crystal oscillator and does not vary.
However, a similar situation exists in that any power imbalance then typically shows
up as an increase or decrease in voltage on the AC and/or DC side of the inverter. The
problem then becomes one of voltage control rather than frequency control.
To develop a power flow management algorithm flexible enough to handle all
possible operating states, one must identify a minimum set of key state variables that
provide sufficient information to determine the appropriate control mode for each
device.
Our top level state variable is the diesel status, because it has the biggest
impact on how voltage and frequency is regulated. Diesel ON refers to the state
where one or more diesel generators is connected to the bus and loaded (i.e. not in
load or unload ramp). Conversely, Diesel OFF refers to the state in which all diesel
generators are either disconnected from the bus or connected but not fully loaded. The
other state is Diesel Wind state where both the diesel and wind turbine gives the
required load demand.

3.1.1.DIESEL ON STATE

23

The stand-alone diesel generator is designed to regulate the voltage and


frequency on an isolated power bus. In a multiple diesel configuration equipped with
automatic load sharing controls, the diesels collectively regulate frequency and share
both the real and reactive power load in proportion to their respective ratings. Diesel
gensets do an excellent job of frequency and voltage control provided that the real and
reactive power load on them remains within their rated capacity and they are not
subject to large reverse power transients. In the Diesel ON state, we allow the diesel
generator(s) to perform the i intended function of frequency and voltage control, and
we control the rotary converter and/or secondary loads to maintain the diesel loading
in a comfortable range. In summary, in Diesel ON state,
The diesel generator(s) assume both frequency and voltage control
Power flow to the secondary loads and/or energy storage is controlled to maintain
diesel loading within a comfortable range
The rotary converter ac machine is used to assist the diesel generators in meeting the
var load, as necessary.

3.1.2.DIESEL OFF STATE


In the Diesel OFF state, the only synchronous machine left on the system is
the AC machine of the rotary converter. The rotational speed of the rotary converter
will establish the grid frequency. As with the diesel generator, the voltage regulator on
the rotary converter AC machine controls the field current so as to maintain the
desired AC bus voltage. Frequency is controlled by modulating power flow to the
secondary load or battery, depending on factors to be discussed below.
Is there instantaneous excess wind power?

In the case where there is excess wind power, secondary (or dump) load
may be used to provide frequency control. As long as there is excess wind
power, this works fine, but suppose the wind suddenly drops, resulting in a
power deficit. As wind power drops, secondary load will be rapidly removed
in an attempt to maintain grid frequency. Once it has all been removed, the
ability to control frequency is lost. The system must switch immediately to
frequency control by the DC machine.
24

Is the battery full?

This question refers to whether the present level of current into the battery can
be sustained. It is actually several questions rolled into one. With a yes

answer to any one of them, the battery is considered full.


Is the battery at a high state of charge (i.e., actually full)?

3.2.WIND-DIESEL ELECTRICAL NETWORK

A wind-diesel electrical network in its simplest form comprises a single


electrical bus, or node, to which all the generators and loads are connected A more
complex wind diesel electrical network comprises a grid of several buses
interconnected by impedance transmission lines or transformers.
For the purposes of this study the village and dump loads have been represented as
passive components. Thus, the loads can be incorporated into one algebraic mode1 to
represent the entire electrical network. The algebraic network equations can be solved
directly, thus an iterative solution to the network voltages and currents. commonly
found in other wind-diesel models, is avoided.
3.2.1.VILLAGE LOAD
In classical power system analysis, the demand load is represented by a
constant, passive impedance, hence the village load power is

The impedance of the village load, ZL , is assumed constant with respect to voltage
and frequency, thus PL - V' and QL a v2, and both PL and QL are independent of
frequency. This assumption is often on the pessimistic side.
3.2.2.DUMP LOAD
25

At low levels of instantaneous wind power penetration wind turbine is seen as


a negative load. At this level the diesel generator maintains the network frequency
under fluctuating wind power and demand load. As the instantaneous wind power
penetration increases, the diesel generator loading will be reduced dom to its
minimum loading. Ideally, beyond this point the dump load, controlled by the dump
load controller. begins to dump excess power from the system to maintain the system
frequency and minimum diesel loading. Hence, the dump load must be variable and
able to absorb the maximum potential surplus power.
The dump load consists of eight three phase resistors connected in series with
GTO switches. The resistors values follow an 8 bit binary progression so that the
power consumed by the DL, provided that the voltage in the isolated grid is nominal,
can be expressed in the form:

Equation (5) means that the power can be varied discretely from 0 to 255.
PSTEP, where PSTEP is the power corresponding to the least significant bit and IJ is
1 when the associated GTO is turned on and 0 when the GTO is turned off. For
this article PSTEP = 1.4 Kw and then PD-NOM = 357 kW, which is a 30% greater than
PT-NOM, so that the WDHS can be controlled in WO mode even in the case of no
consumer load and BESS fully charged/failure.

3.3.THE CONTROL SYSTEM


Our proposal to control the DL and BESS in the presented power system is by
means of a Distributed Control System (DCS). A DCS comprises several CPU based
electronic control units (also called nodes) physically distributed and linked by a
communication network (also called communication bus). As it can be seen in Fig. ,
the presented DCS consists of three nodes: a SM and DE shaft speeds measurement
sensor node NW and two actuators nodes: the DL converter ND and the BESS
converter NS. The type of control that the sensor node NW applies depends on the
operation mode. As commented in the previous section, in WD mode the DE performs
26

the isochronous speed control, so NW calculates a PD frequency regulator whose


input is the frequency error (difference between the current frequency and the power
system nominal frequency 50/60 Hz) and whose output is the reference power PREF
needed to be absorbed (PREF > 0) by the DL + BESS combination or to be supplied
(PREF < 0) by the BESS to balance the active power of the system. In WO mode,
there is no DE controlling the system frequency, so to calculate PREF, the sensor node
NW applies a PID regulator to the frequency error to control the power system
frequency. The integral part of the PID eliminates the steady state frequency error,
performing an isochronous speed control. The node NW also calculates the power
sharing between DL and BESS when PREF > 0 by computing the reference power to
be dumped by DL PD-REF and the reference power to be stored/retrieved PS-REF by
BESS, so that:

(3) is simplified to PREF = PD-REF if battery is fully charged/failure and (4)


means that the DL can only consume power up to its rated power (PD-NOM) and
BESS can consume/supply power up to its rated power (PS-NOM). On the other
hand, the nodes of a DCS exchange information between them through message
passing. In order to coordinate DL and BESS actuators when PREF > 0, the sensor
node NW shall communicate with the message shown in Fig. 1 the current reference
powers PS-REF and PD-REF through the network to the actuator nodes ND and NS.
This message is periodic and guarantees that both actuators receive its reference
power at the same time.

3.4.FREQUENCY AND VOLTAGE CONTROL


A fundamental requirement of a wind-diesel system is that the addition of
wind power to the autonomous diesel generator system should not degrade the power
quality (frequency and voltage performance) of the system from that of the diesel
generator(s) operating alone. This is based on the prernise that the system was
27

originally an autonomous diesel generator system, and that the power quality of the
diesel generator(s) is satisfactory.
The diesel generator of the existing system will have been specified to meet
the requirements of the village load. In a HPNSWD system, the addition of wind
power to the system can greatly increase the active and reactive power fluctuations in
the system. This increased variability may require that the frequency and voltage
control systems of the diesel generator(s) be augmented In addition, to maximize
diesel fuel savings, the HPNSWD system must be able to operate solely from wind
power with the diesel engine(s) shut down. This mode of operation requires a
frequency control system independent of the diesel engine..
3.4.1.VOLTAGE CONTROL
The voltage of the network is most effectively regulated by controlling the
reactive power in the system. The AVR of the diesel generator regulates the network
voltage by controlling the amount of reactive power produced (or absorbed) by the
diesel's synchronous generator. The synchronous generator remains operational at all
times. When the diesel engine is off the synchronous generator functions as a
synchronous condenser.
A village load normally consists of many small loads. Therefore the
synchronous generator typically sees relatively small reactive and active power
fluctuations. The wind turbine, on the other hand, is an electric machine with a
capacity comparable to, if not larger than, the capacity of the synchronous generator.
The induction generator of the wind turbine also requires a large amount of reactive
power for excitation. The start-up and shutdown of the wind turbine cause sudden
changes in the reactive and active power in the system. In addition, both the reactive
and active power of the turbine can fluctuate widely in turbulent wind conditions.
These rapid power fluctuations can cause voltage variations that are detrimental to the
operation of voltage sensitive loads and/or result in objectionable disturbances to
lighting levels.
3.4.2.VOLTAGE REGULATION

28

Analogously, regulating the AC voltage of the power system is a problem of


maintaining an equilibrium between the source and sinks of reactive power (VARs) in
the system. The induction generators of the wind turbines, transformers in the
distribution system, and induction motors in the consumer load are all reactive power
sinks. Power factor correction capacitors on the wind turbines or the distribution
system are sources of reactive power. Synchronous generators, both on the diesel
gensets and on the rotary converter, can either be sources or sinks, but generally they
are supplying the reactive power demanded by the sinks.
Unlike the case of real power, where an imbalance can be absorbed by the
system as a change in stored kinetic energy, there is no storage mechanism for
reactive energy, which only actually exists as a mathematical construct. The
reactive power supplied by the sources is inherently equal to the reactive power
absorbed by the sinks. This is expressed in Equation 2, in which the reactive power
flows for each component are expressed as functions of voltage.

Where Q = reactive power (KVAR)


AC bus voltage
If the reactive power sources are unable to deliver the reactive power
demanded by the sinks, the bus voltage will fall such that the equilibrium is
maintained. With reactive power, the issue is not so much ensuring that equilibrium is
maintained (which is automatic), but that the equilibrium occurs at the desired voltage
level. On a synchronous machine, the function of the voltage regulator is actually to
control the generator excitation such that the generator delivers the reactive power
demanded by the load at the desired voltage.
3.4.3.FREQUENCY CONTROL
The frequency of an autonomous power system remains constant as long as
the power supplied and the power demanded remains balanced. A power imbalance
will accelerate or decelerate the rotational velocities of the system, causing the system

29

frequency to increase or decrease, respectively. The diesel generator regulates the


system frequency by controlling the amount of power developed by the diesel engine.
The AOC 15/50 wind turbine used in this study is a fixed pitch, constant
speed, passive yaw turbine. Therefore there is no control mechanism to regrate the
power output of the wind turbine. The odd method to maintain a constant frequency in
the system is to absorb the surplus power produced by the wind turbine. The diesel
engine is capable of being back-driving to absorbing some excess power (up to 30%
of rated power for short periods). But the unidirectional coupling between the engine
and the synchronous generator prevents the diesel engine from being used in this way.
In addition, the significant capacity of the wind turbine. Relative to the diesel
generator and the sluggish response of the diesel's speed governor make back-driving
the diesel an undesirable method for dynamic frequency control. A more desirable
approach is to use a fast acting programmable dump load to absorb any surplus wind
power in the system, thus the power balance and a constant system frequency. The
controller which controls the dump load and redacts the frequency under conditions of
surplus wind power is referred to here as the dump load controller.
As stated in Chapter 2, a WDHS system has three distinct modes of operation
which are determined by the relative levels of the wind power and the demand
(village) load. Refining the list from Chapter 1, these three operational modes are:
1. The instantaneous demand load minus the instantaneous wind power is greater than
the diesel's minimum loading level (wind power seen as a negative load). The diesel
generator regulates the system frequency.
2. The instantaneous demand load minus the instantaneous wind power is less than the
diesel minimum loading level. The diesel engine continues to operate. The diesel
generator and the dump load controller work in parallel to regulate the system
frequency and to maintain a minimum load on the diesel.
3. The wind power exceeds the demand load and the wind conditions are sufficient to
allow the diesel engine to be safely shut-down. The dump load is now solely
responsible for regulating the system frequency.
30

The power quality must be maintained within each mode, as well as during the
transfer between consecutive modes. This requires that the dump load controller be
stable when operating with the turbine alone, with the diesel generator and the wind
turbine operating in parallel, and with the diesel alone. The latter scenario is not a
requirement if the dump load is automatically disabled in the diesel only
configuration.
3.4.4.CONTROL SYSTEM FOR FREQUENCY CONTROL

Another way to see Eq. (1) is by means of the rightmost adder and block of the
diagram of Fig3. In this gure the frequency regulator receives as input the frequency
error (difference between the current frequency and the power system frequency
50/60 Hz) and outputs the reference power P REF to the ESS and DL actuator blocks.
Under normal conditions the ESS node takes up to its nominal power of the P REF
power as its reference power P S-REF and the DL takes the difference P REF-PS-NOM if
positive or zero in other case as its reference power PD-REF .
The previous positive limit PS-NOM c a n b e decreased depending on the storage
charge level of the ESS. It can reach 0 if the storage is fully charged and then the DL
will have to dump the whole PREF power (PD-REF = PREF).With this variable ESS
positive power limit (PPL), the power sharing of Fig.3 guarantees t h a t t h e D L
w i l l d u m p j u s t t h e e x c e s s w i n d p o w e r t h a t E S S c a n n o t s t o r e . To
make this

power sharing possible, both actuators must be coordinated and this

coordination implies that the DL and ESS controllers must know the current P REF with
the same precision and in the same instants.

31

[ F i g . 3 Block diagram for frequency control ]

Our proposal to coordinate both DL and ESS actuators in WO mode is by


means of a d i s t r i b u t e d c o n t r o l s ys t e m ( D C S ) . A D C S i s c o m p o s e d
by several CPU based electronic control units (also called
n o d e s ) p h y s i c a l l y d i s t r i b u t e d a n d l i n k e d b y a communication
network (also called communication bus). As it can be seen in Fig. 5, the DCS
dened for the frequency control in WO mode consists of three nodes: a SM shaft
speed measurement sensor (shown in F i g . 2 ) node which also
i n c l u d e s t h e f r e q u e n c y regulator block of Fig. 2 and two actuators nodes: the
DL controller and the ESS controller embedded in DL and ESS converters,
respectively, and also shown in Fig. 2.
The nodes of a DCS exchange information between them through messages.
The sensor node NW shall communicate with a periodic message the current reference
power PREF through the network to the actuator nodes ND and NS. This broadcasted
message guarantees that both actuators receive the very same P REF data at the same
instants.

32

[ Fig. 4. Active power sharing between ESS and DL actuators]

In the DCS of Fig. 5 there is another node NGC, this is the WDHS general
controller, which by transmitting and receiving messages, supervises all the nodes of
the DCS, sets the mode of operation of the WDHS, modies parameters of the
regulator block to improve the dynamics of the hybrid system, etc. This proposed
DCS has other advantages against a centralized control. Because it has two actuators,
exibility can be improved by simple failure messages from the actuator nodes or
from NGC. Using these type of messages three control actuations could be performed:
both actuators as it has been explained, dump load actuator alone (P S=0) (same
actuation as if the ESS is full and has the limitation of PT PL >0) and storage system
actuator alone (PD=0) (with the limitation / PT - PL / < PS-NOM ) what gives a more
exible structure in case of failure of any actuator. With PPL messages from NS, the
power sharing between ESS and DL actuators showed in Fig. 3can be accommodated
according to this new positive limit.

33

[ Fig. 5. frequency control in WO mode]

3.7.FREQUENCY REGULATION
The entire power system, including all its generators, distribution wiring, and
even motors present in the village load, can be thought of as one big
electromechanical entity, as shown in Figure 3. Power flows into this system as power
from the wind transferred to the wind turbine rotor, mechanical power developed in
the diesel engines as a result of combustion, and electric power drawn from the
battery.
Power flows out of the system to consumer resistive loads, to consumer
mechanical loads, to secondary loads, and as various mechanical and electrical losses.
At any given moment, if more power is flowing into the system than out of it, the
difference will be stored as an increase in kinetic energy of the rotating machines
within the system, both generators and motors that happen to be on-line at that time.
The effect of any power imbalance in the system is expressed in Equation 1.
34

where = active power (kW)


K.E. = kinetic energy of system
J = moment of inertia of rotating machine
w= angular velocity of rotating machine
This increase in kinetic energy is manifested as an increase in rotational speed
of the synchronous machines in the system and thus an increase in electrical
frequency. The task of frequency regulation is essentially a problem of maintaining an
instantaneous balance of the real power flowing into and out of the system

35

CHAPTER-4

SIMULATION SCHEMAT
36

4.1.SIMULATION
The Matlab-Simulink [11] model of the WDHS of Fig. 2 is shown in Fig. 6.
Some of the components described next such as the IG, the SM and its voltage
regulator, the consumer load, etc. are blocks which belong to the SimPowerSystems
library for Simulink.
The SM has a rated power (PSM-NOM) of 300 kVA. An IEEE type 1 Voltage
regulator plus an exciter regulates the voltage in the SM terminals. The mechanical
parts of the DE and the SM and the friction clutch are modeled by using blocks of the
SimDriveLine library . The model inside the corresponding block of Fig. 6 includes
the inertia constants of the SM (HSM = 1s) and DE (HDE = 0.75 s) and the friction
clutch. The DE mechanical torque TD and the SM electric torque TS both in per unit
values (pu) are the inputs of the block. The shaft speeds of the DE and SM , both in
pu, are the outputs of the block.
The clutch state is set by the binary input signal CLUTCH, which controls the
clutch pressure actuator. When CLUTCH signal is high (clutch engaged/locked), the
pressure actuator is ordered to apply force normal to the surfaces. When CLUTCH
signal is low (clutch disengaged), the pressure actuator is ordered to relieve the force
normal to the surfaces. The actuator dynamics is modeled as a simple first order
system with 0.04 s time constant whose input is CLUTCH and whose output is the
normalized clutch pressure. The mechanical parts and Friction Clutch Block in Fig. 6
detailed schematic can be seen in[13]
The DE along with its actuator and speed regulator are included in the Diesel
Engine block of Fig. 6 and their modeling is justified in[14]. This block has the
current DE speed (pu) as input and outputs the mechanical torque (pu) to take the DE
speed to its speed reference. The DE has been simulated by means of a gain, relating
fuelling rate to torque (lower/upper torque limits are 0/1.1 pu) and a dead time. The
actuator has been simulated by a second order system and the speed regulator by a
PID control.

37

The constant speed stall-controlled WTG [15]

consists of an Induction

Generator (IG) of 275 kW (WTG rated power PTNOM = 275 kW) directly connected to
the autonomous grid and the Wind Turbine (WT) block. This WT block contains the
wind turbine characteristic which defines the mechanical torque applied to the IG as a
function of the wind speed and the IG shaft speed. This WTG has no pitch control, so
there is no way to control the power it produces.
The dump load [15] consists of eight three phase resistors connected in series
with GTO switches. The resistors values follow an 8 bit binary progression so that the
power consumed by the DL, provided that the voltage in the isolated grid is nominal,
can be expressed in the form:

It (eq-5) means that the power can be varied discretely from 0 to 255.P STEP, where
PSTEP is the power corresponding to the least significant bit and IJ is 1 when the
associated GTO is turned on and 0 when the GTO is turned off. For this article
PSTEP = 1.4 Kw and then PD-NOM = 357 kW, which is a 30% greater than P T-NOM, so that
the WDHS can be controlled in WO mode even in the case of no consumer load and
BESS fully charged/failure [5].
The BESS is based on a Ni-Cd battery bank, a LC filter, an IGBT three-phase
bidirectional Current Controlled Inverter (CCI) of rated power P S-MOM = 150 kW and a
150 kVA elevating transformer.
The elevating transformer isolates the three phase power inverter and the
battery bank from the autonomous grid. Its rated line to line voltage in the
grid/inverter sides are 480/120 VAC.
A detailed description of the CCI block can be seen in bellow. The CCI
receives its active power reference PS-REF from the power sharing block. PS-REF can be
established for inverter mode operation (the CCI supplies power to the isolated grid
and discharges the battery), or rectifier mode operation (the CCI absorbs power from

38

the isolated grid and charges the battery). Although the CCI can control the reactive
power it consumes/produces its reactive reference power is set to 0.
The 240 V Ni-Cd battery [15] model consists of a DC voltage source function
of the state of charge (SOC), based on the discharge characteristic of the battery, and
an internal resistance of assumed constant value. The energy stored in the battery is
93.75 kWh, which is obtained from a storage energy need of 15 min for the 150 kW
CCI rated power and a Ni-Cd battery operating between 35% and 75% of its rated
capacity (150 kW_15 min/(0.4_60 min/h) = 93.75 kWh) . This 93.75 kWh
corresponds to a capacity C of 390.625 Ah (93.75 kWh/240 V = 390.625 Ah). The NiCd battery is tolerant to a current ripple of rms value up to 0.2 C with the only effect
of an increased water usage. Connecting the battery directly to the DC side of the
power converter would excess this ripple size, so a LC filter has been used for
smoothing the battery current.
The described short term BESS helps to cover the load during short term load
peaks or wind power deficits, minimizing the number of the DG start/stop cycles
needed. This start/stop cycles minimization reduces the fuel consumption and DG
wearing and the Sizing made in [6] is done according to these benefits. Also short
term BESS improves the frequency stability and the continuity of supply of the
isolated power system as it is shown in the simulation section. In addition to previous
mentioned benefits, long term energy storage allows to match a variable and
uncontrolled renewable energy production to a generally variable and hardly
predictable load demand. Long term storage allows storing excess renewable energy
to meet the load during days of higher than average load or lower than average
renewable energy availability. In the sizing of long term energy storage in order to
obtain the most cost efficiency configuration in an isolated power system is
addressed.
The WD/WO block of Fig. 6 sets the operation mode selected by the WDHS
DCS. Its output is 1 for WD mode and 0 for WO mode. If WD/WO_ = 1 or
CLUTCH = 1 the speed reference to the DE is 1 pu as the DE is needed to keep the
system frequency at rated value. In WO mode (WD/WO* = 0 and CLUTCH = 0) the
DE speed reference is 0.3 pu, so that the DE is kept running instead of being stopped
39

to simplify the simulation of the DE cranking system. When a DE is started the


cranking system is switched on until the DE reaches the firing speed, where the DE
internal combustion process starts, and then, the DE cranking system is switched off
and the DE speed controller is activated with a speed reference of 1 pu. For this article
the time the cranking system is switched on is supposed to be 0.5 s, and the firing
speed is 0.3 pu, which are standard values for a DE. So if the WDHS is in WO mode
and the WD/WO* changes from 0 to 1, the diesel speed reference is not changed to 1
pu until the 0.5 s delay of Fig. 6 elapses, to take into account that the DE is already
running at 0.3 pu firing speed.
The NW node of Fig. 2 is simulated by the Active Power Regulator (APR) and
the Power Sharing block of Fig. 6. The APR, whose schematic is shown in Fig. 7, has
the SM and DE shaft speeds and the binary WD/WO_ signal as inputs. Based on these
signals the APR calculates the adequate PREF directed toward the Power Sharing
block and orders to engage/disengage the clutch, by means of the CLUTCH signal.
The CLUTCH order is the output of the RS flip-flop of Fig. 7, which outputs 1 for
DO/WD modes and 0 for WO mode. The conditions to set it when its value is 0
(WO to WD transition) are that there must be a transition to WD mode order and the
DE-SM slip is less than 2 *10^-3 pu. This 2 *10^-3pu slip accuracy is available in many
commercial auto synchronizers. The calculation of PREF by using a PD control in
WD mode or a PID control in WO mode is also shown in Fig. 7. The CLUTCH signal
selects the proportional and derivative gains of the controls for WD mode (blocks in
grey color) when set and these gains for WO mode, besides of adding the integral part
when reset. When CLUTCH is set the integral part is removed and its output last
value is reduced to 0 by ramping down with a 150 kW/s slope. The gains for WD
mode are calculated to position the dominant pole pair of the WDHS liberalized
model to be a double pole in order to increase speed response and minimize the
over/under shooting. The WD derivative part is disabled during a 0.02 s interval after
the clutch is engaged to avoid high output from this part during the engagement
process. The values of the gains for WO mode, the WO derivative filter and the 2.5
ms sample time come from . This 2.5 ms sample time sets the 400 Hz transmission
frequency for the PREF Message of Fig. 2.

40

The BESS/DL sharing defined in (3) and (4) is performed within the Power
Sharing Block of Fig. 6, according to the following equation:

that means that the DL does not actuate unless the positive PREF needed is greater than
the BESS rated power PS-NOM, guaranteeing that the DL only will dump just the wind
power excess that the BESS cannot store. So when P REF > PS-NOM, this block assigns to
the DL the minimum integer number XD-REF which verifies XD-REF - PSTEP > PREF
PS-NOM and after this, PS-REF is defined as PS-REF = PREF XD-REF.PSTEP. With these
calculations (3) and (5) are always satisfied and the value of P S-REF is accommodated to
take into account the discrete nature of the DL used in this simulation.

41

[Fig .6. Matlab-Simulink model of the isolated WDHS ].

42

[ Fig.7. APR Simulink schematic ]

43

4.2.SIMULATION RESULTS

Time in sec
[ Fig. 8. System frequency per unit and diesel engine speed per unit.]

In the graphs presented below the system frequency/SM speed and the DE
speed are plotted in pu value in Figs. 8 and 9. The rms voltage in pu value is shown in
Fig. 10. The active powers for the WTG, SM, BESS and consumer load are plotted in
kW in Fig. 7. The DL does not actuate during the presented test as the positive P REF
calculated in APR block during the test is in the [0,PS-NOM] range, so that the DL
reference and consumed powers PD-REF and PD are cero during the test and therefore PD
is not plotted. Fig. 11 shows the active powers as being positive when produced and
negative when consumed, so that the sum of active powers in Fig. 11 is null whenever
the power system is in equilibrium.

44

At the starting point in t = 0, the WDHS is in WO mode (WD/ WO_ = 0), so


the DE speed is 0.3 pu (Fig. 8) as it has been explained, the clutch is disengaged
(CLUTCH = 0), the input torque to the SM is zero and the WO PID regulator controls
system frequency. The active powers (Fig. 11) in the load and BESS are -50 and -42
kW (consumed) respectively. The wind speed is 8 m/s and the active power produced
by the WTG is 92 kW, being the system in equilibrium. The battery initial SOC is
50%.

Time in sec
[Fig. 9 Closer view of system frequency and diesel engine speed in per units.]

45

4.2.1.FREQUENCY REGULATION IN WO MODE


Starting at the initial state, a positive step of 100 kW in the load is applied in t
= 0.2 s. by closing the three phase breaker 3PB shown in Fig. 3, so that the total load
(175 kW) is greater than the WTG produced power. Fig. 11 shows the load step, how
the BESS changes from consuming -42 kW to supplying 58 kW and a transient in the
WTG active power with minimum and maximum during oscillations of 78 and 192
kW respectively. During the transient the minimum frequency pu is 0.9985 (Fig. 9)
and the RMS voltage pu minimum and maximum are 0.9921 and 1.0038 respectively
(Fig. 10). In the steady state reached at t = 1.727 s, the WTG produced active power
stays at the same initial value (92 kW) as the wind speed has not changed and the
BESS supplies the active power deficit to the consumer load.

Time in sec
[ Fig. 10. RMS voltage per unit.]
46

4.2.2.WO TO WD MODE TRANSITION


As this situation with the BESS producing power can not be permanent, in t =
2.2s. the WD/WO block in Fig. 5 changes to 1, ordering to the DE to reach rated
speed and to engage the clutch when conditions are met. The WD/WO_ signal is
delayed 0.5 s, so in t = 2.7 s the speed reference to the diesel speed controller changes
from 0.3 to 1 pu and since this instant the DE begins to accelerate. As it can be seen in
Fig. 8 the DE speed increases and when the DE-SM slip is less than 0.002 pu at t =
4.11 s, the CLUTCH output from the APR block changes to 1. With CLUTCH = 1 the
Friction Clutch Block changes from disengaged to engaged state, so the DE starts to
transfer torque to the SM and the APR changes the WO PID regulator to the WD PD
regulator, changing the proportional and derivative constants, the derivative filter and
ramping down the WO integral part with the 150 kW/s slope. The described sequence
of events is presented in Fig. 8, where it is plotted the DE speed and the SM
speed/system frequency until the clutch locks at t = 4.12 s and since this point the
system frequency response.
In Fig. 11 it is shown that the fpu over/undershoots with values of 1.0029 and
0.9995 respectively and reaches the steady state at t = 6.777 s. The VRMS pu
response in Fig. 10 has a 1.0114 and 0.9879 maximum and minimum peaks
respectively during the transient after the clutch engages. The WTG active power in
Fig. 11 presents a minimum and maximum during oscillations of 65 and 122 kW
respectively, but its value at steady state is 92 kW as the wind speed has not changed.
Also Fig. 11 shows that the consumer load active power overshoots due to the system
voltage variations as the consumer load is purely resistive. The SM runs with zero
input power until the clutch engaging instant so the active power supplied by the SM
is around 0 in that interval.
After the clutch locked instant the DE and SM runs behaving as if they were
forming one axis, with the DE transferring the necessary torque to the SM to take the
system frequency to 1 pu and the SM active power shows in that interval over/under
shooting with values of 75 and 56 kW respectively. Also in Fig. 11 the active power
produced/ consumed by the BESS shows an over/undershooting of 61/-9 kW
respectively. In the steady state the DE + SM is supplying the 58 kW that the BESS
47

was supplying previous to the WO to WD mode change order and the active power of
the BESS is 0 kW.

Time in secs
[ Fig. 11. WTG, BEES, SM (DG) and load active powers ]
Fig. 12 shows the Ni-Cd battery voltage (normalized to its 240 V rated
voltage), current (also normalized to its rated current 150 kW/240 V = 625 A) and
state of charge (SOC) in pu. The battery current is considered positive when
discharging and negative when charging. The battery current in Fig. 11 looks like a
scaled version of the BESS active power in Fig. 12. This is so because of the small
48

variations in the battery voltage during the simulation. Initially Ni-Cd battery absorbs
charging current of -0.265 pu storing the wind power excess. After the positive 100
kW load step in t = 0.2 s, Ni-Cd battery start to supply discharging current with a
maximum of +0.4784 pu, until steady state is reached in t = 1.727 s where discharging
current is +0.395 pu. Once the DE is engaged, the BESS does not have to supply
power to the system, so after the transient due to the engagement process, with current
peaks of +0.417 pu and _0.057 pu respectively, steady state is

Time in secs
[ Fig. 12. Normalized battery current, voltage and SOC. ]
reached in t = 6.777 s with 0 pu current. The battery SOC initially set at 50%, hardly
changes because of the relatively great battery capacity and the short simulation time.
The battery voltage is initially 1.05 pu. After the load step increasing, minimum
voltage is 1.02 pu. During DE engagement process minimum and maximum voltage
49

peaks are 1.022 pu and 1.041 pu respectively. These data agree with the employed
battery model, since SOC variations are negligible, voltage will vary little and will
follow the current variations due to the internal resistance.

CHAPTER-5

FUTURE SCOPE
50

5.FUTURE SCOPE
From this project we concluded that it can give reliable power supply but due to
the diesel generation system it is quite expensive because of the amount of fuel input
to the diesel engine. In future if we add

solar generation system with wind diesel

system then we can reduce the cost of generation. The solar energy generation system
will also give the power along with the wind and diesel system. So the number of
diesel engine need to start will be less. During the day time the solar system work
quite effectively to contribute the power. We can also add biomass energy generation
system along with wind diesel hybrid system to save the fuel cost and to get reliability
of power supply. Using the nonconventional energy generation system is eco friendly
too. we can also consider some of the other new hybrid systems are
1. Solar Diesel system
2. Wind-Solar system

51

CHAPTER-6

CONCLUSION
52

CONCLUSION
A comparative analysis of different storage technologies currently in use was
effectuated according to several criteria such as cost, energy density, specific power,
contributing to reducing fuel consumption and GHG emissions, the lifetime and
efficiency of each technology. This analysis was served to determine the performance
index of each storage technology based on the nature of the project application. The
determination of the performance index of each technology represents, despite its
subjectivity resulting from the use of the decision matrix, a solution where we have
some difficulty to choose a technology and where the constraint of time does not
achieve a detailed modeling of the studied systems. This method showed that the
CAES answers to the choice criteria with a performance index approximately 82 %.
Other systems are also more or less effective but at the cost, simplicity, adaptability to
the WDHS, the contribution to reducing fuel consumption and GHG emissions and
duration of life that there is some difference. For these reasons, CAES technology was
adopted to associate with the wind-diesel hybrid system.

53

CHAPTER-7

REFERENCE
54

14.REFERENCE
[1] Adelaar & Ass., Communitech & Ass., Community Specific Energy Supply in the
Yukon and Northwest Territories, Gov. of Canada, Dep. of Indian & Northern Aff.,
Contract N. 81-117, (1981).
[2] Sebastian R., Castro M., Sancristobal E., Yeves F., Peire, J., Quesada, J.,
Approaching hybrid winddiesel systems and controller area network, IECON02, Vol.
3, Pages. 2300-2305, Issue: 5-8 Nov. 2002.
[3] J.G. McGowan, J.F. Manwella and S.R. Connors, "Wind/diesel energy systems:
Review of design options and recent developments", Solar Energy, Volume 41, Issue
6, Pages 561-575, 1988.
[4] J. Kaldellis et al, Autonomous energy systems for remote islands based on
renewable energy sources, in Proceedings of EWEC 99, Nice 1999.
[5] J.F. Maisson Wind Power Development in Sub-Arctic Conditions with Severe
Rime Icing Presented at the Circumpolar Climate Change Summit and Exposition,
Whitehorse, Yukon, 2001
[6] B. Reeves Kotzebue Electric Association Wind Projects , Proceedings of
NREL/AWEA 2002 Wind- Diesel Workshop, Anchorage, Alaska, USA, 2002
[7] P. Ebert P and J. Zimmermann, Successful high wind penetration into a medium
sized diesel grid without energy storage using variable speed wind turbine
technology, in Proceedings of EWEC 99, Nice 1999.
[8] Lawrenz W. CAN system engineering. Springer; 1997.

55

[9] The MathWorks, Inc. Simulink (built upon Matlab).


[10] The MathWorks, Inc. SimPowerSystems. Simulink (built upon Matlab) block
library online documentation.
[11] Sebastin R, Pea Alzola R. Effective active power control of a high penetration
wind diesel system with a NiCd battery energy storage. Renew Energy
[12] Tremblay O, Dessaint L-A, Dekkiche A-I. A generic battery model for the
dynamic simulation of hybrid electric vehicles. Vehicle power and propulsion
conference. VPPC 2007. IEEE; 912 September 2007. p. 2849.
[13] Kaldellis JK, Zafirakis D, Kondili E. Optimum sizing of photovoltaic-energy
storage systems for autonomous small islands. Int J Electr Power Energy Syst
2010;32(1):2436.
[14] Yeager KE, Willis JR. Modelling of emergency diesel generators in an 800
Megawatt nuclear power plant. IEEE Trans Energy Convers 1994;8(3).
[15] Gagnon R, Saulnier B, Sybille G, Giroux P. Modelling of a generic high
penetration no-storage wind-diesel system using matlab/power system blockset.
Global windpower conference, Paris, France; April 2002.

56

You might also like