1.0 INSTRUCTION
The cold chamber electronic controller printed circuit

board (AE-CC-01) is designed for automatic control of


room temperature and coolant solenoid valve control.
AE-CC-01 PCB is a feature packed microprocessor based
control unit suitable to perform fan motor run, to open
and close refrigerant solenoid valve and to turn ON and
OFF defrosting element.
AE-CC-01 PCB is designed for maximum reliability with
100% solid state circuitry and isolated relay contact
for outside use.
AE-CC-01 PCB is incorporated with two (2) temperature
controller, run hour meter, cooling and defrosting
timer.
An alpha-numeric display (5-digit 7-segment) is visible
through window in front of enclosure. During normal
condition it displays room temperature.
System alarm conditions are signaled at the panel
visually (by alarm LED) and alpha-numeric display. When
an alarm condition is present, the display will emit an
alpha-numeric code. This code can then be interpreted
using a menu affixed in front of the door to determine
the error.
Pad buttons and LED Indicators with its different
functions are provided for programming, monitoring of
room temperature, surface temperature of cooling coil,
fan running hours, start/stop of fan motor.
Lamp test function is provided to check dead LED and 7segment display. Press the button and it will light up
all LEDs and the 7-segment display.

IMPORTANT

Completely read and understand this manual before using


the AE-CC-01 PCB.
- AE-CC-01 controller shall be supplied separately in
each room.

-Master and Slave for Cooling and Defrosting Time


One AE-CC-01 controller can set the Cooling and
Defrosting time for all different kinds of rooms i.e.
Meat room, Vegetable room, Fish room. Or each cooling and
defrosting time of each room can be set by their own
AE-CC-01 controller. This function is called MASTER and
SLAVE (see programming section for more details). For
example, there are 3 rooms (Meat, Fish and Vegetable
room)
the controller AE-CC-01 of Meat room has been chosen
to
be the Master. This means that Fish and Vegetable rooms
have to be the Slave. The cooling and defrosting time of
the Master has to be followed by the Slaves.

-Cold Room and Freezing Room (Pt2-1 or PT2-0)


It is available to monitor both temperature of the room
and the surface temperature on evaporator coil. In the
case of Cold Room (defrosting heater element is not
provided like Vegetable Room and / or temperature sensor
on surface evaporator coil is not installed), by setting
PT2-0 (see programming section for more detail), signal
of PT2-0 sensor can be canceled.

2.0

PHOTO OF REF-AT-01 CONTROLLER

Fig. 1 FRONT DETAIL

LED

DESCRIPTION
No.
1
2
3
4
5
6
7
8
9

Name / Description
FAN RUN INDICATOR
SOLENOID VALVE OPEN INDICATOR
DEFROST INDICATOR
ALARM INDICATOR
ROOM TEMPERATURE INDICATOR
COOLING COIL SURFACE TEMP. INDICATOR
FAN RUN HOUR INDICATOR
FAN START BUTTON ON INDICATOR
MANUAL DEFROST BUTTON ON INDICATOR

Color
GREEN
GREEN
GREEN
RED
YELLOW
YELLOW
YELLOW
GREEN
GREEN

BUTTON DESCRIPTION
SYMBOL
A
B
C
D
E

Name / Description
FAN START / STOP
UP BUTTON / LAMP TEST
MANUAL DEFROSTING BUTTON /
DOWN BUTTON
DISPLAY CHANGE / ALARM RESET
BUTTON
PARAMETER SETTING BUTTON

Remark
DUAL
FUNCTION
DUAL
FUNCTION
-

ALPHA-NUMERIC DISPLAY
THE ALPHA-NUMERIC DISPLAY (7-SEGMENT) DISPLAYS ROOM TEMPERATURE, RUNNING
HOURS, SURFACE TEMPERATURE ON COOLING COIL BY PRESSING THE DISPLAY
BUTTON. AN ERROR CODE SHALL BE DISPLAYED UNDER RELEVANT CONDITIONS.

Fig. 1 FRONT DETAIL

3.0 PAD BUTTONS AND LED INDICATOR

3.1

LED

INDICATOR
1. FAN RUN LED Illuminates when fan motor runs
2. SOLENOID VALVE LED Illuminates when solenoid valve opens.
3. DEFROST LED- Illuminates during defrosting time and power is
supplied to defrosting element under cooling coil.
4. ALARM LED- Illuminates with error code on the alpha-numeric
display when any alarm conditions meet.
5. TEMP. 1 LED- Illuminates when Room Temperature is indicated
on the alpha-numeric display.
6. TEMP. 2 LED- Illuminates when Surface Temperature on the
cooling coil is indicated on the alpha-numeric display.
7. HOUR LED- Illuminates when Fan motor running time (hour) is
indicated on the alpha-numeric display.
For example: display value is room temperature

Room Temperature:
-20OC

Pressing Pad Button D changes the displayed value


3.2

PAD BUTTONS
1. START/STOP BUTON By pressing this button, the Fan turns ON

and OFF
2. UP BUTTON / LAMP TEST- Increases the value of input number,
also for lamp testing. Perform lamp test by pressing it off
and on, check for dead LED of 7-segment, if dead LED were
found, replace with new Button and Display PCB
3. DOWN BUTTON / MANUAL DEFROST- Decreases the value of the
input number, also for Manual Defrosting.
Manual Defrost: Press the button to manually start or stop
manually the defrosting.
4. DISPLAY BUTTON- Changes the displayed value on Alphanumeric display. The 3 LEDs on the left side of the Alphanumeric display indicate if the displayed value is room
temperature, surface temperature on cooling coil or fan
running time.
This figure shows alpha-numeric display indicates fan
running hour because the LED Hour illuminates.

5. SET BUTTON- Initiates setting for all parameters and saves


changed value.
3.3

ALPHA-NUMERIC DISPLAY (5-DIGIT, 7-SEGMENT)


When under Fan Motor Stop Condition, pressing Set Button S
will show Ct xx (Cooling time). To search the setting, just
press Up Button and Down Button, the display on Alphanumeric display changes.
When alarm occurs, the Alpha-Numeric Display shows error
code.

4.0 OPERATION

4.1

INITIAL START UP
1. Disconnect power supply to the controller. Check the
external connection (especially, motor power line
and
PT100
sensors). After that, go to the next step.
2. Supply the power again. Then all LEDs and 7-segment will
light up for 5 seconds. Check if it all light up.
*As soon as there is power supply, the cooling / defrosting
timer starts, therefore if you want to restart the cooling
time, disconnect the controllers power supply for at least 10
seconds then supply the power again.
3. Press the Fan Start Button on front of controller.
*During startup, the room temperature is higher than the high
temperature alarm on the setting, so expect an alarm will
occur. This alarm should be neglected as everything is working
normally. Then check whether the room temperature is
decreasing.
4. The individual room temperature is indicated on 7-segment
of each controller.
5. Confirm if each parameter has been set exactly based on the
quick reference guide affixed outside of the door.
*If there is an abnormal status, the alarm will turn ON. It
either go to Auto Reset or it can be Manually Reset. If it
goes to Auto Reset, the Fan remains ON, if it goes to Manual
Reset, the Fan turns OFF.
5. If everything is working normally, check the refrigerators
compressor, it should be running.
*If the Compressor STOPS, the solenoid valve should be OFF
and the Fan should be ON.
7. While in Cooling Time,
*If the Room Temperature is above the set temperature, both
Solenoid Salve and Fan should be ON. But if the Room
temperature is below the set temperature, the Solenoid Valve
should be OFF and the FAN should be ON.
*While in Cooling Time, it is possible to manually defrost by
manually pushing the Defrost button, Heater turns ON, Solenoid

Valve and Fan turn OFF. Also while in Manual Defrost, the
cooling timer is still running.
8. After Cooling Time, Defrosting Time comes next,
*During Defrosting Time if the Temperature on the surface of
cooling pins is below Set Temperature, the Heater should be ON
and the Solenoid Valve and Fan should be OFF. But if it is
above Set Temperature, All the Heater, Fan and Solenoid valve
should be OFF.
9. After the Defrosting Time, the cycle will go back to the
Fan Start ON and repeat the cycle.
Figure 4.2

Figure
4.3

5.0 INPUT / OUTPUT DESCRIPTION

5.1

INPUT DESCRIPTION
5.1.1 Analog Input
A. Room Temperature: (No.1 PT100 Ohm)
Room Temperature via PT100 ohm sensor in the room.
B. Surface Temperature on Evaporator Coil: (No.2 PT100 Ohm)
Temperature above evaporator coil.
5.1.2 Digital Input
Table 5.1.2
INPUT NUMBERS
IN 1
IN 2
IN 3

5.2

NORMAL
OPEN
CLOSE
CLOSE

ERROR CODE
N/A
N/A
Err - 03

REMARKS
REMOTE START/STOP FOR FAN
SOL. V/V OPEN/CLOSE
FAN RUN FEED BACK SIGNAL

OUTPUT DESCRIPTION
5.2.1 FAN RUN SIGNAL
Transistor Output 2: Out 2 shall be energized during fan motor
run. These ports shall be normally connected with fan
magnetic contactor.
5.2.2 DEFROSTING SIGNAL
Transistor Output 1: Out 1 shall be energized during electric
heater run. These ports shall be normally connected with
electric defrosting heater magnetic contactor.
5.2.3 SOLENOID OPEN/CLOSE SIGNAL
Relay Output 2: Relay Out 2 shall be connected to solenoid
valve and energized during compressor run and / or stand-by
condition.
5.2.4 ALARM SIGNAL
Relay Output 1: Relay Out 1 shall be energized when alarm
occurred. The alarm condition has to be transferred to
external alarm device (Normal Close Dry Contact).

6.0 PROGRAMMING (This section provided


for supervisor or authorized person)

Table 6.0 MODE DESCRIPTION FOR SETTING


DISPLAY
EnSt_x
RUN
T
E
M
P
2
T
E
M
P
1

HOUR
Pt2
Su
df
St
hi
Su
dF
St
Lo
hi
nt
dt
Ct
rt

DESCRIPTION
CONFIRMATION WHAT ERRORS OCCURRED
MASTER CONTROLLER
SLAVE CONTROLLER
DISPLAY RUNNING HOUR
COLD ROOM
FREEZING ROOM
CORRECTION FOR DISPLAY TEMPERATURE
DIFF. TEMP.FOR DEFROSTING
SET TEMP. FOR DEFROSTING
SET HIGH TEMP. ON THE EVAP. COIL
CORRECTION FOR DISPLAY TEMPERATURE
DIFF. TEMP. FOR SOL. V/V OPEN/CLOSE
SET POINT FOR ROOM TEMP.

UNIT

SET VALUE

HOUR

1
0
0
1
IF REQUIRED

SET POINT FOR HIGH TEMP. IN THE ROOM

C
- oC
o
C
o
C
o
C
+ oC
o
C
o
C
o
C

MANUAL DEFROSTING TIME


DEFROSTING TIME
THIS MENU IS TO BE USED FOR
COOLING TIME
MASTER CONTROLLER ONLY
TIMER FOR HIGH TEMP ALARM REPOSE

MIN
MIN
HOUR
MIN

10
20
11

SET POINT FOR LOW TEMP. IN THE ROOM (COLD RM ONLY)

10~10
20~30
80
IF REQUIRED

2
SEE BELOW
-1
50

AS PER ACTUAL
CONDITION

TYPICAL SET VALUE FOR ROOM TEMPERATURE (REFERENCE ONLY)

DESIGN
ACTUAL

MEAT ROOM
-18 oC

FISH ROOM
-18 oC

VEG. ROOM
4 oC

The controller utilizes a memory device called an EEPROM. This


memory, once programmed, will store the desired program information
permanently, even if power is removed, yet it will allow adapt the
controller to the system requirement.

6.1

MASTER OR SLAVE SETTING


This setting is set from factory, it is not necessary to
change the setting on the former panel. But it must be measured
according to the content
6.1.1 Master (In case of using the timer separately)
Set-up the controllers as follows:
1. Press S button
2. Press Down Button twice.

3. nSt-0 or nSt-1 is shown on 7-segment


*If nSt-1 is shown, press D Button and go to step 5.
*If nSt-0 is shown, press S Button and then 0 will
flick.
4. Press Up button then nSt-1 will appear, then press
S button to save the setting.
Result: MASTER = nSt-1, SLAVE = nSt-0
*Follow step 1-5 to set other controller.
5. Turn the power OFF. After 10 seconds, turn ON the power
once more and the controller will operate normally.
*After finishing the above procedure, Cooling and Defrosting
Time are operated in each room separately.

6.1.2 Slave (In case of using a common timer)


1. First, determine which controller will be used as
MASTER. The MASTER CONTROLLER must be set as same as
parameters mentioned above.
2. Connect jumper wire the same as the following figure
below among controllers:
Fig. 6.1.2 Typical Wiring between Master and Slave

3. Set-up for SLAVE CONTROLLER

3.1 Press S button


3.2 Press Down Button twice.
3.3 nSt-0 or nSt-1 is shown on 7-segment
*If nSt-0 is shown, press D Button then exit menu.
*If nSt-1 is shown, press S Button and then 1 will
flick.
3.4 Press Up button then nSt-0 will appear, then press
S button to save the setting. Repeat step 3.1-3.4 to the
designated SLAVE CONTROLLER.
*Cooling / Defrosting time of Slave Controller shall follow
MASTER CONTROLLER
6.2 Set-up for Cold Room or Freezing Room (PT2-1 or PT2-0)
It is possible to monitor both room temperature and surface
temperature on evaporator coil.
In case of cold room (defrosting heater element is not
provided like vegetable room and temperature sensor on
surface evaporator coil is not installed), by setting PT2-0
signal of PT2 sensor will be cancelled and operating logic
shall follow Flow Chart for Cold Room (See Fig. 4.2)
*First, determine the controller to be used for cold room or
freezing room.
6.2.1 Freezing Room (PT2-1)
Set-up for Freezing Room
1. Press S button
2. Press Down Button four times.
3. Pt-0 or Pt-1 is shown on 7-segment
*If Pt2-1 is shown, press D Button then exit menu.
*If Pt2-0 is shown, press S Button and then 0 will
flick.
4. Press S button
5. Press Up button then Pt2-1 appears, then press
S button to save the setting. Repeat the above steps to

other designated Freezing Room.


6.2.2 Cold Room (PT2-0)
Set-up for Cold Room
1. Press S button
2. Press Down Button four times.
3. Pt-0 or Pt-1 is shown on 7-segment
*If Pt2-1 is shown, press D Button then exit menu.
*If Pt2-0 is shown, press S Button and then 0 will
flick.
4. Press S button
5. Press Up button then Pt2-1 appears, then press
S button to save the setting. Repeat the above step to other
designated Cold Room.
*Pt2-0 means to neglect PT sensor connected on PT-2 input port
6.3 Programming for another value
If you need to change another value, you can accomplish in the
same way as the above and refer to Table 6.0

FLOW CHART FOR PROGRAMMING


STOP

Fan start/stop button

SET

Initiate Setting

UP or DOWN

Search Mode

SET

UP or DOWN

Press to set the value

SET

6.4 Identifying ERROR messages


D

Press this button to exit

AE-CC-01 CONTROLLER has a function to store alarm messages.


You may find the meaning of every alarm occurred in menu
E-xx. Total of 20 alarm messages are stored in controller.
To identify alarm messages:
1. Press S button
2. Press Down Button
3. E-1xx is shown on 7-segment, E is flicking
4. Press S button
5. 01-xx appears on 7-segment
*This is the latest error code
For example: If you see error message 01-21, the latest
alarm is PT-2 or high temperature alarm on evaporator coil.
To identify different kinds of error, see error code Table 7.0
To go to the next message:
6. Press Down Button
7. 02-xx appears on 7-segment

To scroll more error messages, press Down Button


repeatedly.

1st: 01-xx (The latest error code)


2nd: 02-xx
3rd: 03-xx
|
|
|
20th: 20-xx (The last error code)

7.0 TROUBLESHOOTING

Table 7.0 ERROR CODE DESCRIPTION


ERROR
CODE
Err - 00
Err 03

DESCRIPTION

CORRECTIVE ACTION

EEPROM ERROR
FAN RUN FEED BACK FAULT

Err 11
Err 12

NO.1 PT 100 SENSOR LOOP FAULT


HIGH TEMPERATURE IN CHAMBER (AUTO
RESET)
LOW TEMPERATURE IN CHAMBER (AUTO
RESET) COLD ROOM ONLY
NO.2 PT 100 SENSOR FAIL OR HIGH
TEMP. ALARM

Replace a new controller


Check control power and
contactor of fan motor
Check No.1 sensor and connection
The room temperature is higher
than set temperature
The room temperature is lower
than set temperature
Check No.1 sensor and connection

Err 13
Err 21

The AE-CC-01 Controller has been tested for two (2) years in
our company with actual conditions and it didnt encounter any
malfunction.
It is guaranteed that there will be no problems.
However, if you found any problems with the controller, please
check the following:
-Alarm with error code displaying:
Most errors are caused by mixed-internal wiring or connection
between local instruments and controller Input port.
Therefore, if alarm error code happens, please check external
wiring and connection according to table 7.0. If it does not
work, consult HI AIR KOREA.
-Controller does not work:
Check power supply and correct according to drawing
-Strange display on 7-segment LED
Perform lamp test by pressing it off and on, check for dead
LED of 7-segment, if dead LEDs were found, replace with new
Button and Display PCB (S/N:DS-PT-2-V1-A1).
-Fan and/or solenoid valve dont work under normal condition
INPU
T
IN 1

NORMA
L
OPEN

ABNORMA
L
CLOSE

IN 2

CLOSE

OPEN

TROUBLE
Fan doesnt work. Check Input No.1 whether OPEN or
CLOSED with common
Sol. v/v doesnt work. Check Input No.2 whether
OPEN or CLOSED under compressor stand-by condition