You are on page 1of 6

Design of Air-Insulated Outdoor Substations

Standards Stresses Variables affecting switchgear


■ Electrical stresses, e.g. rated current,
1 short-circuit current, adequate creepage
installation
Air-insulated outdoor substations of open distances and clearances
design must not be touched. Therefore,
■ Mechanical stresses (normal stressing), Switchgear design is significantly influ-
air-insulated switchgear (AIS) is always set
e.g. weight, static and dynamic loads, enced by:
up in the form of a fenced-in electrical op-
ice, wind ■ Minimum clearances (depending on
erating area, to which only authorized per-
2 sons have access. ■ Mechanical stresses (exceptional rated voltages) between various active
stresses), e.g. weight and constant parts and between active parts and
Relevant IEC 60060 specifications apply to loads in simultaneous combination with earth
outdoor switchgear equipment. Insulation maximum switching forces or short-
coordination, including minimum phase- ■ Arrangement of conductors
circuit forces, etc.
to-phase and phase-to-ground clearances, ■ Rated and short-circuit currents
■ Special stresses, e.g. caused by instal-
3 is effected in accordance with IEC 60071.
lation altitudes of more than 1000 m
■ Clarity for operating staff
Outdoor switchgear is directly exposed to ■ Availability during maintenance work,
above sea level, or earthquakes
the effects of the environment such as the redundancy
weather. Therefore it has to be designed ■ Availability of land and topography
based on not only electrical but also envi- ■ Type and arrangement of the busbar
ronmental specifications. disconnectors
4
Currently there is no international standard The design of a substation determines its
covering the setup of air-insulated outdoor accessibility, availability and clarity. The
substations of open design. Siemens de- design must therefore be coordinated in
signs AIS in accordance with DIN/VDE close cooperation with the customer. The
standards, in line with national standards following basic principles apply:
5 or customer specifications. Accessibility and availability increase with
The German standard DIN VDE 0101 (erec- the number of busbars. At the same time,
tion of power installations with rated volt- however, clarity decreases. Installations
ages above 1 kV) demonstrates typically involving single busbars require minimum
the protective measures and stresses that investment, but they offer only limited flex-
6 have to be taken into consideration for air- ibility for operation management and main-
insulated switchgear. tenance. Designs involving 1 1/2 and 2 cir-
cuit-breaker arrangements assure a high
redundancy, but they also entail the high-
Protective measures est costs. Systems with auxiliary or bypass
Protective measures against direct contact, busbars have proved to be economical.
7 i. e. protection in the form of covering, The circuit-breaker of the coupling feeder
obstruction or clearance and appropriately for the auxiliary bus allows uninterrupted
positioned protective devices and mini- replacement of each feeder circuit-breaker.
ker mum heights. For busbars and feeder lines, mostly wire
Protective measures against indirect touch- conductors and aluminum are used. Multi-
8 ing by means of relevant grounding meas- ple conductors are required where currents
ures in accordance with DIN VDE 0141. are high. Owing to the additional short-
Protective measures during work on circuit forces between the subconductors
equipment, i.e. during installation must (pinch effect), however, multiple conduc-
be planned such that the specifications tors cause higher mechanical stressing at
of DIN EN 50110 (VDE 0105) (e.g. 5 safety the tension points. When wire conductors,
9 rules) are complied with particularly multiple conductors, are used
higher short-circuit currents cause a rise
■ Protective measures during operation, not only in the aforementioned pinch ef-
e.g. use of switchgear interlock equip- fect but in further force maxima in the
ment event of swinging and dropping of the con-
■ Protective measures against voltage ductor bundle (cable pull). This in turn re-
10 surges and lightning strike sults in higher mechanical stresses on the
■ Protective measures against fire, water switchgear components. These effects can
and, if applicable, noise insulation. be calculated in an FEM (Finite Element
Method) simulation (Fig. 4).

2/4 Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition
Design of Air-Insulated Outdoor Substations

When rated and short-circuit currents are Preferred designs


high, aluminum tubes are increasingly used
to replace wire conductors for busbars 1
and feeder lines. They can handle rated The multitude of conceivable designs in-
currents up to 8000 A and short-circuit clude certain preferred versions, which are
currents up to 80 kA without difficulty. dependent on the type and arrangement of
Not only the availability of land, but also the busbar disconnectors:
the lie of the land, the accessibility and lo- 2
cation of incoming and outgoing overhead H arrangement
lines together with the number of trans- The H arrangement (Fig. 5) is preferrably
formers and voltage levels considerably used in applications for feeding industrial
influence the switchgear design as well. consumers. Two overhead lines are con-
A one or two-line arrangement, and possi- nected with two transformers and inter-
bly a U arrangement, may be the proper linked by a single-bus coupler. Thus each 3
solution. Each outdoor switchgear installa- feeder of the switchgear can be main-
tion, especially for step-up substations in tained without disturbance of the other
connection with power stations and large feeders. This arrangement assures a high
transformer substations in the extra-high- availability.
voltage transmission system, is therefore
unique, depending on the local conditions. 4
HV/MV transformer substations of the dis- Special layouts for single busbars up to
tribution system, with repeatedly used 145 kV with withdrawable circuit-break-
equipment and a scheme of one incoming er and modular switchbay arrangement
and one outgoing line as well as two trans- Further to the H arrangement that is built
formers together with medium-voltage in many variants, there are also designs 5
switchgear and auxiliary equipment, are with withdrawable circuit-breakers and
more subject to a standardized design modular switchbays for this voltage range.
from the individual power supply compa-
nies. For detailed information see the following
pages:
6
– Q8 – Q8
Vertical displacement in m

–0.6
7
–0.8 – Q0 – Q0

–1.0 M – Q1 – Q1 M

– T5 – T5
–1.2 8
– T1 – T1
–1.4
– T1 – T1
M M
–1.6
– Q1 M – Q10 – Q11 M – Q1
9
–1.8
– Q0 – Q0
Horizontal
–2.0 displacement in m
– F1 – F1
–2.2
–1.4 –1.0 –0.6 –0.2 0 0.2 0.6 1.0 1.4 10
= T1 = T1

Fig. 4: FEM calculation of deflection of wire conductors in the event of short circuit Fig. 5: Module plan view

Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition 2/5
Design of Air-Insulated Outdoor Substations

Withdrawable circuit-breaker without disconnectors). The isolating dis- tance. An electromechanical motive unit
tance is reached with the moving of the ensures the uninterrupted constant moving
General
1 circuit-breaker along the rails, similar to the motion to both end positions. The circuit-
For 123/145 kV substations with single well-known withdrawable-unit design tech- breaker can only be operated if one of the
busbar system a suitable alternative is the nique of medium-voltage switchgear. In end positions has been reached. Move-
withdrawable circuit-breaker. In this kind of disconnected position busbar, circuit-break- ment with switched-on circuit-breaker is
switchgear busbar- and outgoing discon- er and outgoing circuit are separated from impossible. Incorrect movement, which
nector become inapplicable (switchgear each other by a good visible isolating dis- would be equivalent to operating a discon-
2 nector under load, is interlocked. In the
6300 event of possible malfunction of the posi-
2500 2500
tion switch, or of interruptions to travel
17001700
between disconnected position and operat-
ing position, the operation of the circuit-
3 breaker is stopped.
7600 The space required for the switchgear is
2247 reduced considerably. Due to the arrange-
ment of the instrument transformers on
-Q11 -T1/ 1050
-Q12 -Q9 -T5 -Q0 the common steel frame a reduction in the
-Q11-Q12 =T1 -F1 -Q0 -T1 required space up to about 45% in compar-
4 2530 3000 2530 3100 625 7000 625 3100 ison to the conventional switchgear sec-
7000 6400 7000 2500 4500 14450 tion is achieved.
21450
Description
A common steel frame forms the base for
all components necessary for reliable oper-
5 ation. The withdrawable circuit-breaker
contains:
■ Circuit-breaker type 3AP1F
■ Electromechanical motive unit
■ Measuring transformer for protection
6 and measuring purposes
■ Local control cubicle
All systems are preassembled as far as
possible. Therefore the withdrawable CB
can be installed quite easily and efficiently
7 on site.
The advantages at a glance
■ Complete system and therefore lower
Fig. 6a: H arrangement with withdrawable circuit-breaker, plan view and sections costs for coordination and adaptation.
■ A reduction in required space by about
8 45% compared with conventional
switchbays
■ Clear wiring and cabling arrangement
■ Clear circuit state
■ Use as an indoor switchbay is also pos-
9 sible.

Technical data

10 Nominal voltage [kV] 123 kV (145 kV)


Nominal current [A] 1250 A (2000 A)
Nominal short [kA] 31.5 kA, 1s,
time current (40 kA, 3s)
Auxiliary supply/ 230/400 V AC
motive unit [V]
Control voltage [V] 220 V DC

Fig. 6b: H arrangement with withdrawable circuit-breaker, ISO view Fig. 7: Technical data

2/6 Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition
Design of Air-Insulated Outdoor Substations

Modular switchbay Description The advantages at a glance


General A common steel frame forms the base for ■ Complete system and therefore lower
As an alternative to conventional substa-
all components necessary for a reliable op- costs for coordination and adaptation. 1
eration. The modul contains: ■ Thanks to the integrated control cubicle,
tions an air-insulated modular switchbay
can often be used for common layouts. ■ Circuit-breaker type 3AP1F upgrading of the control room is
In this case the functions of several HV ■ Motor-operated disconnecting device scarecely necessary.
devices are combined with each other. ■ Current transformer for protection and ■ A modular switchbay can be inserted
This makes it possible to offer a standard- measuring purposes very quickly in case of total breakdown 2
ized module. ■ Local control cubicle
or for temporary use during reconstruc-
Appropriate conventional air-insulated tion.
All systems are preassembled as far as
switchbays consist of separately mounted ■ A reduction in required space by about
possible. Therefore the module can be in-
HV devices (for example circuit-breaker, stalled quite easily and efficiently on site. 50% compared with conventional
disconnector, earthing switches, transform- switchbays is achieved by virtue of the
ers), which are connected to each other by compact and tested design of the mod- 3
conductors/tubes. Every device needs its ule (Fig. 8).
own foundations, steel structures, earthing ■ The application as an indoor switchbay is
connections, primary and secondary termi- possible.
nals (secondary cable routes etc.).
4
Technical data
3000
2000 2000
Nominal voltage 123 kV (145 kV)
Nominal current 1250 A (2000 A)
5
8000 Nominal short 31.5 kA, 1s,
current (40 kA, 3s)
Auxiliary supply 230/400 V AC
Control voltage 220 V DC 6
-Q8 -Q0-Q1 -T1 -Q10/-Q11 -T1 -Q1 -Q0 -F1 =T1
-T5
Fig. 9: Technical data
3000 4500 4500 3000 4000

7500 11500
7

8000
8
9500

19000 3000
A 9
A

9500
8000 10

7500 11500
19000

Fig. 8: Plan view and side view of H arrangement with modular switchbays

Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition 2/7
Design of Air-Insulated Outdoor Substations

In-line longitudinal layout, with rotary


disconnectors, preferable up to 170 kV Dimensions in mm
Section A-A
1 The busbar disconnectors are lined up one R1 S1 T1 T2 S2 R2 2500
behind the other and parallel to the longitu-
dinal axis of the busbar. It is preferable to 8000
have either wire-type or tubular busbars
located at the top of the feeder conductors. 20500 8400 19400
2 Where tubular busbars are used, gantries 48300
are required for the outgoing overhead
lines only. The system design requires only Top view
two conductor levels and is therefore clear.
If, in the case of duplicate busbars, the 6500
second busbar is arranged in U form rela- End bay
9000
3 tive to the first busbar, it is possible to ar- 4500 A
range feeders going out on both sides of
the busbar without a third conductor level
(Fig. 10). Normal 9000
bay
A
4
Fig. 10: Substation with rotary disconnector, in-line design
Central tower layout with rotary
disconnectors, normally only for 245 kV Dimensions in mm
5 3000
The busbar disconnectors are arranged
side by side and parallel to the longitudinal
axis of the feeder. Wire-type busbars locat- 12500
ed at the top are commonly used; tubular
busbars are also conceivable. This arrange- 9000
6 ment enables the conductors to be easliy
jumpered over the circuit-breakers and the 7000 18000 17000 17000
bay width to be made smaller than that of
in-line designs. With three conductor levels
the system is relatively clear, but the cost
of the gantries is high (Fig. 11).
7
16000

8
Fig.11: Central tower design

Diagonal layout with pantograph


disconnectors, preferable up to 245 kV Section Dimensions in mm
9 The pantograph disconnectors are placed Bus system Bypass bus
diagonally to the axis of the busbars and
feeder. This results in a very clear, space- 13300
saving arrangement. Wire and tubular con-
ductors are customary. The busbars can
be located above or below the feeder con- 10000 8000 28000 48000 10000
10 ductors (Fig. 12). 10400

Top view

5000
18000 4000
4000
5000

Fig. 12: Busbar area with pantograph disconnector of diagonal design, rated voltage 420 kV

2/8 Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition
Design of Air-Insulated Outdoor Substations

1 1/2 circuit-breaker layout,


preferable up to 245 kV
Planning principles
The 1 1/2 circuit-breaker arrangement as- 1
sures high supply reliability; however, ex- For air-insulated outdoor substations of
penditure for equipment is high as well. open design, the following planning princi-
ples must be taken into account:
The busbar disconnectors are of the panto-
graph, rotary and vertical-break type. Verti- ■ High reliability
cal-break disconnectors are preferred for – Reliable mastering of normal and 2
the feeders. The busbars located at the top exceptional stresses
can be of wire or tubular type. Of advan- – Protection against surges and light-
tage are the equipment connections, which ning strikes
are very short and enable (even in the case – Protection against surges directly
of multiple conductors) high short-circuit on the equipment concerned (e.g.
currents to be mastered. Two arrange- transformer, HV cable)
3
ments are customary:
■ Good clarity and accessibility
■ External busbar, feeders in line with
– Clear conductor routing with few
three conductor levels conductor levels
■ Internal busbar, feeders in H arrange-
– Free accessibility to all areas (no 4
ment with two conductor levels (Fig. 13). equipment located at inaccessible
depth)
– Adequate protective clearances for
Dimensions in mm installation, maintenance and transpor-
4000 tation work
– Adequately dimensioned transport 5
routes
17500
■ Positive incorporation into surroundings
– As few overhead conductors as
possible
8500 48000 29000 – Tubular instead of wire-type busbars 6
– Unobtrusive steel structures
– Minimal noise and disturbance level
■ EMC grounding system
for modern control and protection
18000 7
■ Fire precautions and environmental
protection
– Adherence to fire protection speci-
fications and use of flame-retardant
Fig.13 : 1 1/2 Circuit-breaker design and nonflammable materials 8
– Use of environmentally compatible
technology and products

For further information please contact:


Fax: ++ 49 - 9131- 73 18 58 9
e-mail: Gerda.Friedel@erls04.siemens.de

10

Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition 2/9

You might also like