Product

Data

35D
Single Duct Units
for Variable Volume Systems

Nominal 200 to 4000 cfm

Features/Benefits
Flexible, high performance
units
The 35D single duct variable air volume (VAV) unit provides cooling
only or cooling with reheat to meet all
your application needs. It is designed
to allow maximum flexibility in configuration and control.
The 35D is offered in 11 sizes covering an air delivery range from 45
to 4000 cfm. The basic unit is a short,
high performance unit with a multiple blade damper that provides
reduced sound levels. Minimal leakage
and effective use of reheat airflow
combine to assure optimum utilization
of supplied airflow. The low height
of the unit ensures an easy fit in all
applications. (Size 18 is 1712 in. high;
all other 35D units are only 1212 in.
high.) The unit casing is 22-gage
galvanized steel, lined with 12-in. fiberglass. Both the casing and the optional foil liner meet the requirements
of UL-181 (Underwriters Laboratories) and NFPA-90A (National Fire
Protection Association).

Superior control offerings


Each 35D unit is supplied with the
new Carrier Linear Averaging Flow
probe as a standard feature. This
probe offers both flow averaging and
flow monitoring capability. When
combined with the flat oval inlets found
on larger 35D units, the flow probe
results in flow sensing capability superior to any competitive unit.
Control options include pressureindependent pneumatic, electronic,
and Carrier variable volume and temperature (VVT) and Product Integrated
Controls (PIC). Both VVT and
Copyright 1992 Carrier Corporation

Form 35D-1PD

PIC controls are communicating controls; the PIC units provide a control option compatible with the Carrier
Comfort Network (CCN).
Pneumatic control units utilize a
rack and pinion actuator, allowing
simple switch-over from normally
open to normally closed applications.
Electronic control units feature a
new factory-installed enclosure that
provides end access for field connections, simplifying installation and
increasing flexibility.

Designed for easy installation


Units have round inlets through size
10, and flat oval inlets for sizes 12
through 16. Size 18 has a rectangular
inlet. All round and oval inlets have
a raised collar bead to ensure tight
inlet duct connections. Units have a
rectangular slip and drive connection on the discharge for quick installation. Duct dimensions for 35 Series
units (size 16 and smaller) are the
same as for 45 Series fan-powered
boxes, for easy interchangeability.
The units can be specified with electric or hot water heat, foil-faced lining , multiple outlet assembly (octopus),
and sound attenuator.

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5,6
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-13
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16,17
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-39
Hot Water Coil Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electric Heater Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Box Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Sound Power Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Application NC Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39-41
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42,43

THE 35D DAMPER

SEAL

FORMED
BLADES

A unique feature of the 35D single duct unit is a specially designed multi-blade damper. The 35D damper utilizes large pivots for low friction adjustment and quiet
modulation of the duct air. Designed to allow tight sealing at shutoff, the damper provides an exceptionally short
airway length while offering excellent airstream control.

PIVOTS

CARRIERS LINEAR AVERAGING FLOW PROBE

Every 35D unit is equipped with a Linear Averaging Flow


Probe which provides an amplified differential pressure
that is proportional to the unit airflow. Output from this
probe is used to provide flow signal to both pneumatic
and electronic controls. Unit airflow (cfm) can be read
directly from the flow probe chart on the unit (also shown
below).

CARRIER LINEAR AVERAGING PROBE CHART

NOTE: The above flow signals (in. wg) should not be confused with the unit minimum inlet static pressures shown on page 33. These flow
signal readings are amplified differential pressure readings from the inlet probe used only for determining airflow (cfm) through the box.

Model number nomenclature

*PIC controls provide electronic control of the 35D unit as part of the Carrier Comfort Network (CCN).
Sizes 12, 14 and 16 have flat oval inlets that accommodate standard flex sizes. Size 18 has a 14-in.
high by 16-in. wide inlet collar.
**Both hot water coil and control hand are determined by looking in direction of airflow.
Electric heat units must have attenuator.
\For special package options, contact Savannah.
Units with electric heat do not require additional control transformers. Transformers are provided as
part of the electric heater.

Options
ELECTRIC HEATER OPTIONS

*For available capacities, see Electric Heater Data table, page 32.

35D UNITS WITH CONTROL AND HEAT OPTIONS

35DA UNIT WITH ANALOG ELECTRONIC CONTROL

Options (cont)
35D UNITS WITH CONTROL AND HEAT OPTIONS (cont)

35DA UNIT WITH ATTENUATOR AND ANALOG


ELECTRONIC CONTROLS
35DC UNIT WITH PIC
(PRODUCT INTEGRATED CONTROL)

HI

LO

35DP UNIT WITH PNEUMATIC CONTROL

35DV UNIT WITH VVT CONTROL

35DP UNIT WITH HOT WATER COIL AND


PNEUMATIC CONTROL

35DA UNIT WITH ELECTRIC HEAT, ATTENUATOR,


AND ANALOG ELECTRONIC CONTROLS

Physical data
UNIT AND COMPONENT WEIGHTS (LB)
35D UNIT SIZE
RATED CFM
BASE UNIT
(NO CONTROL)
BASE UNIT
WITH ATTENUATOR
BASE UNIT
WITH ATTENUATOR
AND ELECTRIC HEAT

HOT WATER COIL

ROW
1
2
3
4

CONTROLS
Pneumatic
Electronic*

04
200

05
350

06
500

07
650

08
800

09
1050

10
1300

12
1900

14
2500

16
3000

18
4000

14

14

14

16

16

18

18

20

22

24

28

23

23

23

27

27

30

30

36

39

42

50

46

46

46

55

55

62

62

76

87

99

119

6
9
11
14

6
9
11
14

6
9
11
14

7
10
13
16

7
10
13
16

8
12
15
18

8
12
15
18

9
13
17
21

10
14
19
23

11
16
21
25

12
18
24
31

10

10

10

10

10

10

10

10

10

10

10

*Includes Analog, PIC (Product Integrated Controls) and VVT (Variable Volume and Temperature) Controls.
NOTE: For units with electric heat, control weight should be added to weight shown above. For units with hot water
coil, coil weight and control weight should be added to base unit weight. For example, a size 12 unit with electronic
controls and a 3-row coil weighs 20 + 10 + 17 = 47 lbs.

Dimensions
35D BASIC DAMPER UNIT
NOMINAL
AIRFLOW
(Cfm)

INLET
SIZE
(in.)

200
350
500
650
800
1050
1300
1900
2500
3000

4 Round
5 Round
6 Round
7 Round
8 Round
9 Round
10 Round
12 Oval
14 Oval
16 Oval
16 W x 14 H
Rectangle

4000

DIMENSIONS (in.)
Plenum Plenum Discharge
Height Width (W) x (H)
(H)
(W)
1212
1212
1212
1212
1212
1212
1212
1212
1212
1212

1012
1012
1012
1212
1212
1412
1412
1812
2112
2412

1012
1012
1012
1212
1212
1412
1412
1812
2112
2412

1712

2112

2112 x 1712

x
x
x
x
x
x
x
x
x
x

1212
1212
1212
1212
1212
1212
1212
1212
1212
1212

NOTE: Right hand unit shown.

Dimensions (cont)
35D WITH ATTENUATOR
NOMINAL
AIRFLOW
(Cfm)

INLET
SIZE
(in.)

200
350
500
650
800
1050
1300
1900
2500
3000

4 Round
5 Round
6 Round
7 Round
8 Round
9 Round
10 Round
12 Oval
14 Oval
16 Oval
16 W x 14 H
Rectangle

4000

DIMENSIONS (in.)
Plenum
Plenum
Discharge
Height (H) Width (W) (W) x (H)
1212
1012
1012 x 1212
1212
1012
1012 x 1212
1212
1012
1012 x 1212
1212
1212
1212 x 1212
1
1
12 2
12 2
1212 x 1212
1212
1412
1412 x 1212
1212
1412
1412 x 1212
1212
1812
1812 x 1212
1
1
12 2
21 2
2112 x 1212
1212
2412
2412 x 1212

NOTE: Right hand unit shown.

1712

2112

2112 x 1712

35DP (PNEUMATIC) CONTROL DIMENSIONS

35DA (ANALOG ELECTRONIC) AND 35DC (PIC) CONTROL DIMENSIONS

35DV (VVT) CONTROL DIMENSIONS

Dimensions (cont)
35D UNIT WITH HOT WATER HEAT
DIMENSIONS (in.)
NOMINAL AIRFLOW
(Cfm)

INLET SIZE
(in.)

Plenum Height (H)

Plenum Width (W)

200
350
500
650
800
1050
1300
1900
2500
3000
4000

4 Round
5 Round
6 Round
7 Round
8 Round
9 Round
10 Round
12 Oval
14 Oval
16 Oval
16 W x 14 H Rectangle

1212
1212
1212
1212
1212
1212
1212
1212
1212
1212
1712

1012
1012
1012
1212
1212
1412
1412
1812
2112
2412
2112

Discharge (W) x (H)


1

NOTE: Right hand control and coil shown.

10

1012
1012
1012
1212
1212
1412
1412
1812
2112
2412
2112

x
x
x
x
x
x
x
x
x
x
x

1212
1212
1212
1212
1212
1212
1212
1212
1212
1212
1712

18

Overall Length
Rows
2
3
4

18

18

19.5

HOT WATER COIL DIMENSIONS

ROWS

CIRCUITS

1
2
3
4

1
2
3
4

A
6
6
6
712

CONN.*
1 2
5 8
3 4
7 8

DIMENSIONS (IN.)
D
E
G
H
516
1516
5
3
516
516
5
2716
1516
1516
5
3
612 2716 158
158

*OD Male solder connection.


NOTE: Dimensions I is stubout available for connection.

I
3
1716
2
2

J
N/A
1-916
3
212

SIZE
04-06
07, 08
09, 10
12
14
16
18

W
1012
1212
1412
1812
2112
2412
2112

B
1212
1212
1212
1212
1212
1212
1712

11

Dimensions (cont)
35D WITH ELECTRIC HEAT
NOMINAL
AIRFLOW
(Cfm)

INLET
SIZE
(in.)

200
350
500
650
800
1050
1300
1900
2500
3000

4 Round
5 Round
6 Round
7 Round
8 Round
9 Round
10 Round
12 Oval
14 Oval
16 Oval
16 W x 14 H
Rectangle

4000

DIMENSIONS (in.)
Plenum
Plenum
Discharge
Height (H) Width (W) (W) x (H)
1212
1012
1012 x 1212
1212
1012
1012 x 1212
1212
1012
1012 x 1212
1212
1212
1212 x 1212
1
1
12 2
12 2
1212 x 1212
1212
1412
1412 x 1212
1212
1412
1412 x 1212
1212
1812
1812 x 1212
1
1
12 2
21 2
2112 x 1212
1212
2412
2412 x 1212

NOTE: Right hand unit shown.

12

1712

2112

2112 x 1712

Accessory dimensions
OCTOPUS ATTENUATOR

UNIT
SIZE*
04
05
06
07
08
09
10
12

DIMENSIONS (in.)
H
1212
1212
1212
1212
1212
1212
1212
1212

W
1012
1012
1012
1212
1212
1412
1412
1812

L
12
12
12
24
24
36
36
36

OUTLET DIAM (in.)


6
8
No. of Outlets
3
2
3
2
3
2
5
5
5
5
7
7
7
7
8
8

NOTES:
1. Octopus available for base unit with hot water reheat coil or base
unit with attenuator. Octopus is NOT available for units with electric heat.
2. Octopus is 22-gage galvanized steel and includes manual balancing dampers with locking screw.

*Octopus is not available for sizes 14, 16 and 18.

13

Selection procedure
To determine unit sizing for a particular job, use the Carrier
Terminals Program available from your local Carrier representative, or follow the example shown below.
Selection example 35D with 35BD boot diffusers
IMPORTANT: The following is a selection example.
Do NOT use any data included within this example
when making your unit selection. Use the performance data found on pages 18 through 40 to
make your selection.
I Establish design parameters.
Control Zone Size . . . . . . . . . . . . . Conference Room,
20 ft x 24 ft
Sensible Cooling Load . . . . . . . . . . . . . . . 28.0 MBtuh
Supply Air Temperature . . . . . . . . . . . . . . . . . . . . 50 F
Design Room Temperature . . . . . . . . . . . . . . . . . 75 F
II Determine design supply air quantity.
Supply Air Quantity (Cfm)
= Sensible Cooling Load (MBtuh) x 1000
1.10 x (Room Temp Supply Air Temp)
28.0 x 1000
=
1.10 x (75 50)
= 1018 Cfm
III From the table below, select a 35D unit with a
maximum capacity (cfm) equal to or greater than
the space design airflow.
UNIT SIZE
04
05
06
07
08
09
10
12
14
16
18

MAXIMUM AIRFLOW (CFM)


200
350
500
650
800
1050
1300
1900
2500
3000
4000

A size 09 unit will provide the necessary air quantity.


IV Determine the air outlet arrangements available with selected 35D unit.
Using the table shown on page 13 for the accessory
octopus attenuator, find that seven 8-in. outlets are available for use with size 09. Five 8-in. outlets will be used
to distribute the air to the conditioned space.

14

V Determine the air delivery per outlet.


35D Unit Design Cfm
(Step II)
Air Delivery (Cfm) =
No. of Air Outlets (Step IV)
1018
= 203
5
VI Determine that selected 35D system meets sound
level requirements.
Refer to Performance Data (pages 35-39) and Application Data (pages 16 and 17).
VII Locate the boot-diffusers and 35D unit in the
space.
Consider the ceiling system, air supply duct arrangement, and lighting fixture location. Determine minimum and maximum air throw of selected boot-diffuser.
(See Boot-Diffuser Product Data).
With five 8-in. outlet collars: Cfm =

Enter the Boot-Diffuser Optimum Air Throw table with


an AH Type, 2-way, 4-ft boot between 200 to 250
cfm and find:
Minimum Throw from Centerline = 4.0 ft
Maximum Throw from Centerline = 12.5 ft.
Locate boot-diffusers so that distance between room
boundaries and diffusers falls within the minimum/
maximum throw area (within the limitations of the ceiling system).
Flexible duct should be of relatively equal lengths.
Return air and dummy units can be introduced to achieve
desired ceiling effect.
For the selection example, an acceptable layout is
shown.

VIII Establish design parameters for optional reheat


coil (hot water or electric).
Heating Load . . . . . . . . . . . . . . . . . . . . . . 12.0 MBtuh
Entering Water Temperature . . . . . . . . . . . . . . . 180 F
Heating at 45% Design Cfm . . . . . . . . . . . . 458 Cfm
Design Room Temperature (From Step I) . . . . . 75 F
IX Determine total heating capacity required.
Air Temperature Rise (F)
Heating Load (MBtuh) x 1000
=
1.10 x Cfm
=

12,000
1.10 x 458

= 24 F
Leaving Coil Temperature (F)
= Rise Room Temperature
= 44 +75
= 99 F
Total Heating Capacity
Cfm x 1.10 x (Leaving Coil Temp
Supply Air Temp)
=
1000
458 x 1.10 x (99 50)
1000
= 24.7 MBtuh
X Select optional reheat coil (hot water or
electric).
A. Hot Water Coil
Correct the heating capacity as required for entering water temperature. If unit is operating at conditions other than rating conditions of 180 F entering water temperature (EWT) and 50 F entering
air temperature (EAT), subtract the EAT from the
EWT and enter the Correction Factors table (page
17) at this value. For this example, using EWT of
180 F and EAT of 50 F, enter capacity corrections
table at 130 F to find correction factor of 1.04.
Adjust heating capacity as follows:
Required Heating Capacity
Total Heating Capacity (MBtuh)
=
Capacity Correction Factor
=

Enter Hot Water Coil Performance tables for selected unit size and heating mode cfm, and find a
coil that will deliver the required MBtuh for the heating load.
Referring to the table on page 22, find by interpolation that for a 35D size 09 unit operating at 500
heating cfm, a 2-row coil at 1 gpm delivers 26.8
MBtuh.
Obtain coil static pressure drop at full design cfm
from Performance Data and insert in inlet static
pressure calculation (Step XI).
B. Electric Heating Coil
Determine heating coil kW requirements
Required Heating Capacity
(MBtuh)
Required kW =
3.414
=

24.7
3.414

= 7.24 kW
Refer to Electric Heater Data table and select coil
with kW equal to or greater than required kW. Establish coil voltage, phase, and number of steps.
Obtain coil static pressure drop from Performance
Data and insert in inlet static pressure calculation
(Step XI).
XI Determine the required inlet static pressure.
Using the performance tables and industry data, obtain the minimum inlet duct pressures for each component:
35D unit (size 09) . . . . . . . . . . . . . . . . . . 0.23
Octopus (8-in. connection) . . . . . . . . . . . 0.05
Reheat coil (2-row, hot water) . . . . . . . . 0.33
Flex duct (6 in. x 10 ft) . . . . . . . . . . . . . . 0.10
Boot-Diffuser (35BD, AH, 2-way,
5 ft, 250 cfm)
(Assuming 4 boot diffusers/box) . . . . . 0.12
Total
0.83

in.
in.
in.
in.

wg
wg
wg
wg

in. wg
in. wg

Approximately 0.9 in. wg static pressure is required to


deliver design airflow.

24.7
1.04

= 23.8 MBtuh

15

Application data
Several factors should be considered when selecting single
duct units. These include:

Airflow range
Carrier single duct units include a linear averaging flow probe
in the unit inlet to allow pressure-independent control of
airflow on the basis of a control signal. The flow range is
limited by the sensitivity of the controller employed; the inlet duct conditions; and the size of the selected unit.
In most cases, inlet duct minimum airflow of less than
350 fpm should be avoided to prevent erratic control. A
minimum flow less than 350 fpm results in pressure signals
less than 0.01 in. wg, which cannot be resolved reliably by
most control systems.
Maximum inlet flow limits are typically restricted to less
than 2500 fpm by duct pressure loss limitations, although
acoustical limits may also limit selection above this range.
The 35D units will operate well up to 3000 fpm inlet velocity, but with increased pressure drop through the supply
duct and high noise levels.

System pressure
Control of duct pressures is the most effective means of ensuring low noise levels, accurate flow control, and minimum
energy use. The use of various fan tracking techniques can
ensure optimum system efficiency and operation. Response
times of the fan tracking system should be adjustable in order to prevent system oscillations between the pressure
independent controllers and the fan system.
Minimum inlet static pressure shown in the Box Flow Data
table on page 33 is the pressure required by a given size
box at a specified airflow with the unit damper wide open.
This pressure was measured by tests conducted in accordance with ARI (Air Conditioning and Refrigeration
Institute) Standard 880-89, using 3 ft of discharge duct of
the same size as the unit plenum. The pressure shown is
for the unit only or for unit plus hot water coil or electric
heat coil. To determine the total static pressure loss in the
distribution system, the minimum inlet static pressure must
be added to the duct pressure drop (both upstream and downstream of the 35D unit) and the outlet pressure drop.

Acoustics
The primary determinant in the acoustics of a terminal is
the inlet, or duct, static pressure. While velocity (flow rate)
is also a factor, significant reductions in sound can be realized by reducing duct pressures in the branch duct supplying the unit.
Lined duct downstream of the unit is very effective in
reducing discharge noise levels. Where no duct lining is employed between the unit and the room diffusers, a noisy
system is possible. Reducing inlet pressure drop will help,
provided the techniques used to reduce local duct pressure
levels do not increase noise levels in the duct which will be
carried into the space.

16

Radiated sound is seldom a problem with single duct terminals. Flexible duct at the inlet, however, can transmit
airborne sound levels into the plenum space, where they
add to the radiated sound component.
Acoustic performance data Acoustic performance
data shown for 35 Series is based on tests conducted in accordance with ARI Standard 880-89. Data is presented as
sound power for the units indicated. When the attenuator,
octopus, or electric reheat version is ordered, a long unit
will be shipped. The added length of this unit reduces sound
power in a similar manner as the equivalent amount of lined
duct. If the attenuator option is used, additional attenuation
is achieved equivalent to 3 ft of lined duct, producing an
effective 3 NC (Noise Criteria) reduction in room sound levels in most cases.
Application sound levels are provided as NC levels. These
are determined by applying factors provided in ARI
Standard 885-90, as indicated below. Lined duct, ceiling
effect, and room attenuation are typical for many office
spaces. These assumptions, for discharge (airborne) sound,
also include a typical end reflection effect. Alternate effects
can be examined by using the Carrier Air Terminals program (available from Carrier ATF, Savannah) or ARI
Standard 885-90.
The use of multiple outlet plenum will result in reduced
sound levels due to power division. The supplied application data assumes that the sound power levels are split
based on a fixed cfm maximum per split, as indicated. This
assumes, however, that split flows are not directed to the
same conditioned space. When two split flows are supplied
to the same space, the effect of power splits is often negated, depending on the location of the supply outlets and
the observer.
The addition of electric or hot water heat has little effect
on sound power levels, either discharge or radiated. There
is, however, an effect on the pressure assumptions. Sound
data presented for the units is based on unit pressure drop
vs sound generated. If there is little downstream pressure
(0.3 in. wg or less), the inlet static pressure (duct pressure)
is used to enter the sound level tables; if, however, there is
significant discharge pressure drop, then the pressure drop
across the unit is less than the inlet duct pressure and should
be accounted for when determining discharge sound. For
example, if a 35D size 10 unit with a 4-row coil is selected
at 975 cfm, the unit pressure drop (from the Box Flow Data
table) is 0.63 in. wg. If the duct pressure is 1.5 in. wg, then
the sound is a function of only 0.87 in. wg pressure drop
(1.5 0.63). For radiated sound, use the 1.5 in. wg inlet
pressure (the coil is downstream and not included in
radiated analysis).

If both the diffuser and the terminal are selected at the


same delivered sound power level, the discharge (airborne)
sound levels should be combined, by octave band, with the
sound power generated by the selected diffuser when predicting sound levels in the space. In many cases, diffusers
generate higher frequency sound than the terminal, and the
two power levels combine without raising the room NC level.
Each application of unit and diffuser must be examined individually to verify that the net NC does not increase. (Equal
sound power levels, when added, increase the sound level
by 3 db.)
The application data assumes no significant inlet duct
breakout. If considerable flexible duct is used at the inlet,
sound power levels will be higher. Refer to ARI Standard
885-90 for guidance on this effect. A special table is also
provided in the Carrier Air Terminals program.

CORRECTION FACTORS FOR HOT WATER COIL


PERFORMANCE*

NOTE: The following table gives hot water coil correction


factors for performance at other than the rating conditions
of 180 F entering water temperature (EWT) and 55 F entering air temperature (EAT).
EWT-EAT (F)
CORRECTION
FACTOR
EWT-EAT (F)
CORRECTION
FACTOR

40

45

50

55

60

65

70

75

80

.31

.35

.39

.43

.47

.51

.55

.59

.63

85

90

95

100

105

110

115

120

.67

.71

.75

.79

.83

.88

.92

.96

EWT-EAT (F) 125 130 135 140 145 150 155 160
CORRECTION 1.00 1.04 1.08 1.13 1.17 1.21 1.25 1.29
FACTOR
*To determine corrected performance, multiply the standard capacity rating (MBtuh) by the correction factor. For example, for a 35D size 10
unit with a 2-row coil operating at 100 cfm, the standard rating is 42.7
MBtuh. If the unit is running at 75 F primary air and a 125 F water temperature, subtract the EAT from the EWT:
125 F 75 F = 50 F.
Enter the Correction Factors table at 50 F and find a correction factor
of 0.39. Multiply the standard rating of 42.7 MBtuh for this unit by the
correction factor:
42.7 MBtuh = 42,700 Btuh
Corrected capacity = (0.39) (42,700) = 16,653 Btuh.
The corrected LAT (leaving air temperature) and LWT (leaving water
temperature) can be calculated from the following relationships:
LWT = EWT

Capacity (Btuh)
Gpm x 500

LAT = EAT +

Capacity (Btuh)
1.08 x cfm

17

Performance data
HOT WATER COIL PERFORMANCE
UNIT 35D SIZE 04-06

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
1 Row
2 Row

45

0.01

0.01

110

0.01

0.01

175

0.01

0.03

240

0.02

0.05

305

0.04

0.07

370

0.05

0.10

435

0.07

0.13

500

0.09

0.17

WATER FLOW
Water PD
Rate
(ft)
(gpm)
1 Row
2 Row
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.3
1.0
3.0
6.7
2.0
4.0
11.2
3.3
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.3
1.0
3.0
6.7
2.0
4.0
11.3
3.3
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.3
1.0
3.0
6.7
2.0
4.0
11.3
3.3
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.3
1.0
3.0
6.8
2.0
4.0
11.3
3.3
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.3
1.0
3.0
6.8
2.0
4.0
11.3
3.3
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.3
1.0
3.0
6.8
2.0
4.0
11.3
3.3
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.3
1.0
3.0
6.8
2.0
4.0
11.3
3.3
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.3
1.0
3.0
6.8
2.0
4.0
11.3
3.3

LAT
(F)
1 Row
144.2
148.6
151.0
151.9
152.3
112.4
118.1
121.5
122.8
123.5
98.0
103.6
107.0
108.3
109.0
89.7
94.9
98.2
99.5
100.2
84.3
89.1
92.3
93.5
94.2
81.1
85.8
89.0
90.3
91.0
78.6
83.2
86.4
87.7
88.4
76.5
81.1
84.3
85.5
86.3

2 Row
157.6
162.1
164.4
165.3
165.7
132.0
141.0
146.2
148.1
149.2
116.9
127.6
134.3
136.9
138.3
106.9
118.1
125.7
128.7
130.3
99.7
111.1
119.1
122.3
124.1
94.4
105.5
113.8
117.2
119.1
90.2
101.1
109.4
112.9
114.9
86.8
97.4
105.7
109.3
111.3

PERFORMANCE
LWT
(F)
1 Row
2 Row
162.7
160.1
170.9
169.6
175.3
174.7
176.9
176.4
177.6
177.3
152.7
143.4
165.0
159.6
172.1
169.2
174.6
172.6
175.9
174.4
147.5
133.2
161.6
152.6
170.2
165.0
173.3
169.7
174.9
172.1
144.0
126.2
159.3
147.3
168.8
161.7
172.3
167.3
174.1
170.2
141.4
121.1
157.5
143.1
167.7
158.9
171.5
165.2
173.5
168.6
138.3
117.1
155.4
139.6
166.4
156.5
170.6
163.4
172.8
167.2
135.7
113.9
153.5
136.7
165.2
154.4
169.8
161.9
172.2
165.9
133.5
111.3
151.9
134.2
164.2
152.6
169.0
160.5
171.6
164.8

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

18

Capacity
(MBtuh)
1 Row
2 Row
4.3
5.0
4.6
5.2
4.7
5.3
4.7
5.4
4.7
5.4
6.8
9.2
7.5
10.2
7.9
10.8
8.1
11.1
8.1
11.2
8.1
11.7
9.2
13.7
9.8
15.0
10.1
15.5
10.2
15.7
9.0
13.4
10.3
16.4
11.2
18.3
11.5
19.1
11.7
19.5
9.7
14.7
11.2
18.5
12.3
21.1
12.7
22.2
12.9
22.8
10.4
15.7
12.3
20.2
13.6
23.5
14.1
24.9
14.4
25.6
11.1
16.5
13.3
21.7
14.8
25.6
15.4
27.2
15.7
28.1
11.6
17.2
14.1
22.9
15.8
27.4
16.5
29.3
16.9
30.4

HOT WATER COIL PERFORMANCE


UNIT 35D SIZE 04-06

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
3 Row
4 Row

45

0.01

0.01

110

0.02

0.02

175

0.04

0.05

240

0.07

0.09

305

0.1

0.14

370

0.15

0.19

435

0.19

0.26

500

0.25

0.33

WATER FLOW
Water PD
Rate
(ft)
(gpm)
3 Row
4 Row
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.6
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.6
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.6
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.6
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.6
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.6
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.6
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.6
1.0

LAT
(F)
3 Row
168.4
172.2
174.0
174.6
174.9
144.4
155.0
160.8
162.7
163.8
127.5
141.3
149.7
152.8
154.4
115.7
130.8
140.8
144.7
146.7
107.2
122.6
133.5
137.9
140.3
100.7
116.0
127.5
132.3
134.9
95.7
110.6
122.4
127.4
130.2
91.7
106.1
118.0
123.2
126.1

4 Row
173.6
176.4
177.6
178.0
178.1
152.2
163.2
168.6
170.4
171.2
134.5
150.2
159.2
162.3
163.9
121.6
139.3
150.7
154.9
157.1
112.1
130.4
143.4
148.4
151.1
104.9
123.2
137.0
142.7
145.8
99.3
117.1
131.5
137.6
141.0
94.8
112.1
126.7
133.1
136.7

PERFORMANCE
LWT
(F)
3 Row
4 Row
158.0
156.9
168.6
168.2
174.2
174.0
176.1
176.0
177.1
177.0
137.5
133.8
156.2
154.3
167.4
166.5
171.5
170.9
173.5
173.1
125.2
119.9
147.4
144.0
162.1
160.3
167.7
166.5
170.6
169.7
117.1
111.0
140.7
136.3
157.8
155.2
164.5
162.7
168.1
166.8
111.3
104.8
135.5
130.3
154.1
150.9
161.8
159.5
165.9
164.2
106.9
100.3
131.3
125.5
151.0
147.2
159.4
156.6
164.0
161.9
103.5
96.8
127.8
121.6
148.3
144.0
157.3
154.1
162.3
159.8
100.8
94.1
124.8
118.4
146.0
141.3
155.5
151.9
160.8
157.9

Capacity
(MBtuh)
3 Row
4 Row
5.5
5.8
5.7
5.9
5.8
6.0
5.8
6.0
5.8
6.0
10.6
11.5
11.9
12.9
12.6
13.5
12.8
13.7
12.9
13.8
13.7
15.0
16.3
18.0
17.9
19.7
18.5
20.3
18.8
20.6
15.7
17.3
19.7
21.9
22.2
24.8
23.2
25.9
23.8
26.5
17.2
18.8
22.3
24.9
25.9
29.1
27.3
30.8
28.1
31.7
18.3
19.9
24.4
27.2
29.0
32.8
30.9
35.0
31.9
36.3
19.1
20.8
26.1
29.2
31.7
36.0
34.0
38.8
35.3
40.4
19.8
21.5
27.6
30.8
34.0
38.7
36.8
42.2
38.4
44.1

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

19

Performance data (cont)


HOT WATER COIL PERFORMANCE (cont)
UNIT 35D SIZE 07, 08

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
1 Row
2 Row

100

0.01

0.01

200

0.01

0.02

300

0.03

0.05

400

0.04

0.08

500

0.06

0.12

600

0.09

0.17

700

0.12

0.22

800

0.15

0.28

WATER FLOW
Water PD
Rate
(ft)
(gpm)
1 Row
2 Row
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.5
1.0
3.0
7.1
2.1
4.0
11.9
3.5
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.5
1.0
3.0
7.1
2.1
4.0
11.9
3.5
0.5
0.3
0.0
1.0
1.0
0.3
2.0
3.5
1.0
3.0
7.1
2.1
4.0
11.9
3.5
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.5
1.0
3.0
7.1
2.1
4.0
11.9
3.5
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.5
1.1
3.0
7.1
2.1
4.0
11.9
3.5
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.5
1.1
3.0
7.1
2.1
4.0
11.9
3.5
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.5
1.1
3.0
7.2
2.1
4.0
11.9
3.5
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.5
1.1
3.0
7.2
2.1
4.0
11.9
3.5

LAT
(F)
1 Row
120.9
126.9
130.4
131.7
132.4
98.3
104.3
108.1
109.5
110.3
87.8
93.2
96.8
98.2
98.9
81.9
87.0
90.4
91.8
92.5
78.3
83.3
86.7
88.1
88.9
75.6
80.5
83.9
85.3
86.0
73.6
78.2
81.6
83.0
83.8
71.9
76.4
79.7
81.1
81.9

2 Row
139.2
147.6
152.3
153.9
154.8
116.3
127.8
134.9
137.6
139.1
103.4
115.4
123.7
127.0
128.8
95.0
106.9
115.7
119.3
121.2
89.2
100.7
109.5
113.3
115.4
84.8
95.8
104.7
108.5
110.7
81.5
91.9
100.7
104.6
106.8
78.8
88.8
97.4
101.3
103.5

PERFORMANCE
LWT
(F)
1 Row
2 Row
151.5
143.6
164.5
160.0
171.9
169.5
174.5
172.9
175.8
174.6
142.6
127.0
158.7
148.6
168.5
162.7
172.2
168.1
174.0
170.9
137.6
117.3
155.2
140.8
166.5
157.7
170.7
164.5
172.9
168.1
133.6
110.9
152.4
135.1
164.7
153.8
169.4
161.5
171.9
165.7
129.7
106.2
149.5
130.7
162.9
150.5
168.1
159.0
170.9
163.7
126.5
102.7
147.0
127.1
161.3
147.8
166.9
156.9
169.9
161.9
123.8
99.9
144.9
124.1
159.9
145.5
165.9
155.0
169.1
160.4
121.6
97.6
143.0
121.6
158.7
143.4
165.0
153.4
168.4
159.0

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

20

Capacity
(MBtuh)
1 Row
2 Row
7.1
9.1
7.8
10.0
8.2
10.5
8.3
10.7
8.4
10.8
9.4
13.3
10.7
15.7
11.5
17.3
11.8
17.9
11.9
18.2
10.6
15.7
12.4
19.6
13.5
22.3
14.0
23.3
14.2
23.9
11.6
17.3
13.8
22.4
15.3
26.2
15.9
27.8
16.2
28.6
12.6
18.5
15.3
24.7
17.1
29.5
17.9
31.5
18.3
32.6
13.4
19.3
16.5
26.5
18.7
32.2
19.6
34.7
20.1
36.1
14.0
20.0
17.6
27.9
20.1
34.5
21.2
37.5
21.7
39.2
14.6
20.6
18.5
29.2
21.4
36.6
22.6
40.0
23.2
41.9

HOT WATER COIL PERFORMANCE


UNIT 35D SIZE 07,08

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
3 Row
4 Row

100

0.01

0.01

200

0.04

0.05

300

0.07

0.1

400

0.12

0.16

500

0.18

0.24

600

0.25

0.33

700

0.33

0.43

800

0.41

0.55

WATER FLOW
Water PD
Rate
(ft)
(gpm)
3 Row
4 Row
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.7
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.7
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.7
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.7
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.0
0.6
4.0
1.7
1.0
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.5
0.3
3.0
1.1
0.6
4.0
1.7
1.0
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.1
0.6
4.0
1.7
1.1
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.1
0.6
4.0
1.7
1.1

LAT
(F)
3 Row
151.7
161.0
165.6
167.2
168.0
126.5
141.3
150.2
153.4
155.1
111.1
127.4
138.5
142.8
145.1
101.1
117.3
129.5.
134.4
137.1
94.1
109.7
122.3
127.7
130.6
88.9
103.8
116.4
122.1
125.2
85.0
99.0
111.6
117.3
120.6
81.8
95.1
107.5
113.3
116.7

4 Row
159.1
168.2
172.3
173.5
174.1
133.1
150.0
159.5
162.8
164.4
116.2
135.4
148.3
153.0
155.5
105.0
124.4
138.9
144.8
147.9
97.2
115.9
131.2
137.7
141.3
91.5
109.2
124.8
131.8
135.7
87.1
103.8
119.4
126.6
130.7
83.7
99.4
114.7
122.1
126.4

PERFORMANCE
LWT
(F)
3 Row
4 Row
138.2
135.0
157.1
155.5
168.1
167.3
171.9
171.5
173.9
173.6
118.2
112.5
142.7
139.0
159.4
157.4
165.8
164.5
169.2
168.2
107.2
100.7
133.1
127.9
153.0
149.8
161.0
158.8
165.4
163.7
100.3
93.5
126.2
120.0
147.8
143.7
157.1
154.1
162.3
159.9
95.5
88.8
120.9
114.2
143.7
138.8
153.8
150.2
159.6
156.7
92.0
85.4
116.8
109.7
140.2
134.8
151.0
146.8
157.2
153.9
89.4
82.9
113.4
106.2
137.2
131.3
148.6
143.9
155.2
151.4
87.2
81.0
110.6
103.3
134.7
128.4
146.4
141.4
153.4
149.2

Capacity
(MBtuh)
3 Row
4 Row
10.4
11.3
11.4
12.2
12.0
12.7
12.1
12.8
12.2
12.9
15.4
16.9
18.6
20.5
20.6
22.6
21.3
23.3
21.6
23.6
18.2
19.8
23.5
26.1
27.1
30.2
28.4
31.8
29.2
32.6
19.9
21.6
26.9
30.0
32.2
36.3
34.3
38.8
35.5
40.1
21.1
22.8
29.6
32.9
36.3
41.2
39.2
44.7
40.9
46.6
22.0
23.6
31.6
35.1
39.8
45.2
43.5
49.7
45.5
52.3
22.7
24.3
33.3
36.9
42.8
48.7
47.1
54.1
49.6
57.2
23.2
24.8
34.7
38.4
45.4
51.6
50.4
58.0
53.3
61.7

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

21

Performance data (cont)


HOT WATER COIL PERFORMANCE (cont)
UNIT 35D SIZE 09, 10

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
1 Row
2 Row

250

0.01

0.03

400

0.03

0.06

550

0.06

0.11

700

0.09

0.17

850

0.13

0.24

1000

0.17

0.32

1150

0.22

0.41

1300

0.27

0.51

WATER FLOW
Water PD
Rate
(ft)
(gpm)
1 Row
2 Row
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.7
1.1
3.0
7.5
2.2
4.0
12.5
3.7
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.7
1.1
3.0
7.5
2.2
4.0
12.5
3.7
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.7
1.1
3.0
7.5
2.2
4.0
12.5
3.7
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.7
1.1
3.0
7.3
2.2
4.0
12.6
3.7
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.7
1.1
3.0
7.5
2.2
4.0
12.6
3.7
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.7
1.1
3.0
7.5
2.2
4.0
12.6
3.7
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.7
1.1
3.0
7.6
2.3
4.0
12.6
3.7
0.5
0.3
0.0
1.0
1.1
0.3
2.0
3.7
1.1
3.0
7.6
2.3
4.0
12.6
3.7

LAT
(F)
1 Row
95.1
101.4
105.4
107.0
107.8
83.5
89.0
92.6
94.0
94.8
78.3
83.5
87.2
88.7
89.5
74.8
79.8
83.4
84.9
85.7
72.2
77.0
80.6
82.0
82.9
70.3
74.9
78.3
79.8
80.6
68.8
73.1
76.5
77.9
78.8
67.5
71.7
75.0
76.4
77.2

2 Row
111.8
124.2
132.2
135.2
136.8
97.2
109.8
118.9
122.6
124.6
88.6
100.6
110.0
114.0
116.2
82.9
94.2
103.5
107.6
109.9
78.9
89.4
98.5
102.6
105.0
75.9
85.7
94.5
98.6
101.0
73.6
82.7
91.3
95.3
97.7
71.8
80.3
88.5
92.5
94.9

PERFORMANCE
LWT
(F)
1 Row
2 Row
136.7
118.7
154.9
142.6
166.4
159.2
170.6
165.6
172.9
169.0
130.7
107.1
150.6
132.6
163.7
152.4
168.8
160.5
171.4
165.0
124.7
100.2
146.1
125.8
160.9
147.3
166.7
156.6
169.8
161.8
120.2
95.5
142.5
120.8
158.5
143.3
164.9
153.5
168.4
159.2
116.7
92.1
139.6
116.8
156.5
140.1
163.4
150.8
167.2
157.0
113.9
89.5
137.1
113.7
154.8
137.3
162.2
148.6
166.2
155.1
111.5
87.5
135.0
111.1
153.3
134.9
161.0
146.6
165.2
153.5
109.5
85.8
133.1
108.9
152.0
132.9
160.0
144.9
164.4
152.0

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

22

Capacity
(MBtuh)
1 Row
2 Row
10.8
15.3
12.5
18.7
13.6
20.8
14.0
21.7
14.3
22.1
12.3
18.2
14.7
23.7
16.3
27.6
16.9
29.2
17.2
30.1
13.8
20.0
17.0
27.1
19.1
32.7
20.2
35.0
20.5
36.4
14.9
21.1
18.7
29.6
21.5
36.7
22.6
39.8
23.2
41.5
15.8
22.0
20.2
31.6
23.5
40.0
24.8
43.7
25.6
45.9
16.5
22.6
21.4
33.2
25.2
42.7
26.8
47.1
27.7
49.7
17.1
32.1
22.5
34.5
26.7
45.1
28.5
50.1
29.5
53.1
17.6
23.6
23.4
35.6
28.1
47.1
30.1
52.7
21.2
56.1

HOT WATER COIL PERFORMANCE


UNIT 35D SIZE 09, 10

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
3 Row
4 Row

250

0.04

0.05

400

0.09

0.12

550

0.17

0.22

700

0.25

0.33

850

0.36

0.47

1000

0.48

0.63

1150

0.61

0.81

1300

0.76

1.0

WATER FLOW
Water PD
Rate
(ft)
(gpm)
3 Row
4 Row
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.1
0.7
4.0
1.8
1.1
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.1
0.7
4.0
1.8
1.1
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.1
0.7
4.0
1.8
1.1
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.1
0.7
4.0
1.8
1.1
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.1
0.7
4.0
1.8
1.1
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.5
0.3
3.0
1.1
0.7
4.0
1.8
1.1
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.6
0.3
3.0
1.1
0.7
4.0
1.8
1.1
0.5
0.0
0.0
1.0
0.1
0.0
2.0
0.6
0.3
3.0
1.1
0.7
4.0
1.8
1.1

LAT
(F)
3 Row
120.8
137.1
147.2
151.0
152.9
103.4
120.5
132.9
137.9
140.6
93.1
109.4
122.6
128.3
131.4
86.4
101.5
114.8
120.8
124.2
81.7
95.6
108.7
114.8
118.3
78.2
91.1
103.7
109.8
113.5
75.5
87.4
99.6
105.7
109.4
73.4
84.5
96.2
102.2
105.9

4 Row
126.7
145.6
156.7
160.6
162.5
107.3
127.7
142.5
148.2
151.2
95.9
115.3
131.4
138.2
142.0
88.5
106.4
122.8
130.2
134.4
83.3
99.7
115.9
123.6
128.0
79.5
94.6
110.2
118.0
122.7
76.6
90.5
105.6
113.3
118.1
74.3
87.2
101.6
109.3
114.1

PERFORMANCE
LWT
(F)
3 Row
4 Row
108.9
102.6
135.7
131.1
155.1
152.5
162.7
161.0
166.8
165.5
96.4
89.7
123.4
117.2
146.3
142.2
156.1
153.2
161.5
159.2
89.5
82.9
115.4
108.4
139.8
134.6
151.0
147.0
157.3
154.2
85.1
78.8
109.7
102.3
134.8
128.8
146.9
142.1
153.9
150.0
82.0
76.0
105.4
97.9
130.7
124.1
143.4
138.0
150.9
146.5
79.7
74.0
102.1
94.5
127.4
120.3
140.5
134.6
148.4
143.5
77.9
72.5
99.4
91.8
124.6
117.2
138.0
131.7
146.2
140.8
76.6
71.4
97.2
89.7
122.1
114.5
135.8
129.2
144.3
138.5

Capacity
(MBtuh)
3 Row
4 Row
17.8
19.4
22.2
24.5
24.9
27.5
25.9
28.5
26.4
29.0
20.9
22.6
28.3
31.4
33.7
37.8
35.8
40.3
37.0
41.6
22.6
24.3
32.3
35.8
40.2
45.4
43.5
49.5
45.4
51.7
23.7
25.3
35.1
38.8
45.2
51.2
49.7
56.8
52.3
60.0
24.5
26.0
37.3
41.1
49.3
55.9
54.9
62.9
58.1
67.1
25.1
26.5
39.0
42.7
52.6
59.7
59.2
68.1
63.2
73.1
25.5
26.9
40.3
44.1
55.4
62.8
63.0
72.5
67.6
78.3
25.9
27.2
41.4
45.2
57.9
65.5
66.3
76.3
71.4
82.9

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

23

Performance data (cont)


HOT WATER COIL PERFORMANCE (cont)
UNIT 35D SIZE 12

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
1 Row
2 Row

325

0.02

0.03

550

0.04

0.07

775

0.07

0.13

1000

0.11

0.21

1225

0.16

0.30

1450

0.21

0.40

1675

0.27

0.52

1900

0.34

0.65

WATER FLOW
Water PD
Rate
(ft)
(gpm)
1 Row
2 Row
0.5
0.3
0.1
1.0
1.2
0.3
2.0
4.0
1.2
3.0
8.2
2.4
4.0
13.7
4.0
0.5
0.4
0.1
1.0
1.2
0.4
2.0
4.0
1.2
3.0
8.2
2.5
4.0
13.8
4.0
0.5
0.4
0.1
1.0
1.2
0.4
2.0
4.1
1.2
3.0
8.3
2.5
4.0
13.8
4.1
0.5
0.4
0.1
1.0
1.2
0.4
2.0
4.1
1.2
3.0
8.3
2.5
4.0
13.8
4.1
0.5
0.4
0.1
1.0
1.2
0.4
2.0
4.1
1.2
3.0
8.3
2.5
4.0
13.8
4.1
0.5
0.4
0.1
1.0
1.2
0.4
2.0
4.1
1.2
3.0
8.3
2.5
4.0
13.9
4.1
0.5
0.4
0.1
1.0
1.2
0.4
2.0
4.1
1.2
3.0
8.3
2.5
4.0
13.9
4.1
0.5
0.4
0.1
1.0
1.2
0.4
2.0
4.1
1.2
3.0
8.3
2.5
4.0
13.9
4.1

LAT
(F)
1 Row
92.8
99.8
104.3
106.0
106.9
80.6
86.6
90.7
92.3
93.2
75.3
80.9
85.0
86.6
87.6
71.9
77.1
81.1
82.8
83.7
69.5
74.4
78.2
79.9
80.8
67.7
72.3
76.0
77.6
78.6
66.3
70.7
74.2
75.8
76.7
65.2
69.3
72.8
74.3
75.2

2 Row
107.4
121.2
130.3
133.8
135.7
91.4
104.9
115.2
119.4
121.7
82.9
95.2
105.5
110.0
112.6
77.6
88.7
98.7
103.3
106.0
74.0
84.1
93.7
98.2
100.9
71.4
80.6
89.7
94.2
96.9
69.4
77.9
86.6
90.9
93.6
67.9
75.7
84.0
88.2
90.8

PERFORMANCE
LWT
(F)
1 Row
2 Row
127.0
106.5
148.6
133.5
162.7
153.6
168.1
161.6
170.9
165.8
119.1
93.5
142.4
120.7
158.8
144.3
165.2
154.5
168.7
160.2
112.1
86.6
136.6
112.7
154.9
137.7
162.3
149.3
166.4
155.9
107.1
82.3
132.2
107.1
151.8
132.8
160.0
145.2
164.5
152.5
103.4
79.3
128.7
102.9
149.3
128.8
158.0
141.9
162.9
149.6
100.4
77.1
125.8
99.7
147.1
125.6
156.4
139.1
161.6
147.2
98.0
75.5
123.3
97.1
145.2
122.9
154.9
136.7
160.3
145.1
96.0
74.1
121.2
95.0
143.5
120.6
153.6
134.6
159.3
143.3

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

24

Capacity
(MBtuh)
1 Row
2 Row
13.3
18.4
15.7
23.2
17.3
26.4
17.9
27.7
18.2
28.3
15.2
21.6
18.8
29.6
21.2
35.7
22.2
38.3
22.7
39.6
17.0
23.3
21.7
33.7
25.1
42.3
26.5
46.1
27.3
48.2
18.2
24.4
23.9
36.5
28.2
47.3
30.0
52.2
31.0
55.1
19.2
25.2
25.7
38.5
30.8
51.2
32.9
57.2
34.2
60.7
19.9
25.7
27.1
40.1
32.9
54.4
35.5
61.4
36.9
65.6
20.5
26.1
28.4
41.4
34.8
57.1
37.7
65.0
39.3
69.8
21.0
26.5
29.4
42.5
36.5
59.4
39.7
68.1
41.5
73.4

HOT WATER COIL PERFORMANCE


UNIT 35D SIZE 12

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
3 Row
4 Row

325

0.04

0.06

550

0.11

0.14

775

0.2

0.26

1000

0.31

0.41

1225

0.44

0.58

1450

0.6

0.79

1675

0.77

1.02

1900

0.96

1.27

WATER FLOW
Water PD
Rate
(ft)
(gpm)
3 Row
4 Row
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.6
0.3
3.0
1.2
0.7
4.0
2.0
1.2
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.6
0.3
3.0
1.2
0.7
4.0
2.0
1.2
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.6
0.4
3.0
1.2
0.7
4.0
2.0
1.2
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.6
0.4
3.0
1.2
0.7
4.0
2.0
1.2
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.6
0.4
3.0
1.2
0.7
4.0
2.0
1.2
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.6
0.4
3.0
1.2
0.7
4.0
2.0
1.2
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.6
0.4
3.0
1.2
0.8
4.0
2.0
1.2
0.5
0.0
0.0
1.0
0.1
0.1
2.0
0.6
0.4
3.0
1.2
0.8
4.0
2.0
1.2

LAT
(F)
3 Row
114.9
133.3
145.1
149.4
151.7
95.9
114.0
128.2
134.1
137.3
85.9
102.1
116.7
123.3
127.0
79.7
94.2
108.4
115.2
119.1
75.6
88.6
102.2
108.9
112.9
72.7
84.4
97.2
103.9
107.9
70.5
81.1
93.2
99.7
103.8
68.8
78.5
90.0
96.3
100.3

4 Row
119.7
141.2
154.5
159.1
161.4
98.5
120.0
137.2
144.1
147.8
87.5
106.7
124.6
132.6
137.1
80.9
97.8
115.2
123.7
128.6
76.5
91.4
108.0
116.6
121.8
73.4
86.7
102.4
110.9
116.1
71.0
83.1
97.8
106.1
111.3
69.2
80.2
94.0
102.1
107.3

PERFORMANCE
LWT
(F)
3 Row
4 Row
95.8
89.2
125.0
119.5
148.4
145.1
157.9
155.7
163.0
161.3
82.9
76.6
110.0
102.8
136.5
131.2
148.7
144.7
155.6
152.4
76.7
71.1
101.1
93.5
128.3
121.8
141.9
136.7
149.9
145.6
73.1
68.1
95.2
87.7
122.3
115.0
136.7
130.5
145.4
140.2
70.7
66.2
91.1
83.6
117.6
109.8
132.4
125.7
141.7
135.8
69.1
64.9
87.9
80.7
113.9
105.8
129.0
121.7
138.6
132.2
67.8
63.9
85.5
78.5
110.8
102.6
126.0
118.4
135.9
129.0
66.9
63.2
83.5
76.8
108.3
99.9
123.5
115.6
133.6
126.4

Capacity
(MBtuh)
3 Row
4 Row
21.0
22.7
27.5
30.3
31.6
34.9
33.1
36.5
33.9
37.3
24.3
25.8
35.0
38.6
43.5
48.8
47.0
52.9
48.9
55.1
25.8
27.2
39.5
43.2
51.7
58.2
57.1
65.0
60.2
68.7
26.7
28.0
42.4
46.2
57.7
65.0
65.0
74.2
69.2
79.5
27.3
28.5
44.5
48.2
62.4
70.2
71.3
81.5
76.7
88.3
27.7
28.8
46.0
49.6
66.1
74.2
76.5
87.5
82.9
95.7
28.0
29.0
47.2
50.7
69.2
77.4
80.9
92.4
88.2
101.9
28.3
29.2
48.2
51.6
71.7
80.1
84.7
96.7
92.9
107.3

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

25

Performance data (cont)


HOT WATER COIL PERFORMANCE (cont)
UNIT 35D SIZE 14

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
1 Row
2 Row

400

0.02

0.03

700

0.04

0.09

1000

0.08

0.16

1300

0.13

0.26

1600

0.19

0.37

1900

0.26

0.50

2200

0.34

0.65

2500

0.43

0.81

WATER FLOW
Water PD
Rate
(ft)
(gpm)
1 Row
2 Row
0.5
0.4
0.1
1.0
1.3
0.4
2.0
4.3
1.3
3.0
8.8
2.6
4.0
14.7
4.3
0.5
0.4
0.1
1.0
1.3
0.4
2.0
4.3
1.3
3.0
8.8
2.6
4.0
14.7
4.3
0.5
0.4
0.1
1.0
1.3
0.4
2.0
4.3
1.3
3.0
8.9
2.6
4.0
14.7
4.3
0.5
0.4
0.1
1.0
1.3
0.4
2.0
4.4
1.3
3.0
8.9
2.7
4.0
14.8
4.4
0.5
0.4
0.1
1.0
1.3
0.4
2.0
4.4
1.3
3.0
8.9
2.7
4.0
14.8
4.4
0.5
0.4
0.1
1.0
1.3
0.4
2.0
4.4
1.3
3.0
8.9
2.7
4.0
14.8
4.4
0.5
0.4
0.1
1.0
1.3
0.4
2.0
4.4
1.3
3.0
8.9
2.7
4.0
14.8
4.4
0.5
0.4
0.1
1.0
1.3
0.4
2.0
4.4
1.3
3.0
8.9
2.7
4.0
14.9
4.4

LAT
(F)
1 Row
89.9
97.3
102.1
104.0
105.0
78.0
84.3
88.7
90.4
91.4
72.8
78.6
82.9
84.7
85.7
69.6
74.9
79.0
80.8
81.8
67.4
72.2
76.2
78.0
79.0
65.8
70.3
74.1
75.8
76.8
64.6
68.7
72.4
74.0
75.0
63.6
67.5
71.0
72.6
73.5

2 Row
102.8
117.6
127.6
131.5
133.6
86.6
100.2
111.3
116.0
118.6
78.5
90.6
101.3
106.2
109.0
73.8
84.4
94.6
99.5
102.3
70.6
80.0
89.6
94.4
97.2
68.4
76.8
85.8
90.4
93.3
66.7
74.3
82.8
87.3
90.0
65.4
72.4
80.4
84.6
87.3

PERFORMANCE
LWT
(F)
1 Row
2 Row
119.7
97.5
143.5
125.9
159.6
148.6
165.9
158.0
169.2
163.0
110.4
84.5
135.8
111.6
154.6
137.5
162.1
149.3
166.2
156.0
103.0
78.3
129.1
103.2
149.9
129.9
158.6
143.1
163.4
150.8
98.0
74.5
124.2
97.6
146.3
124.4
155.9
138.4
161.2
146.8
94.3
72.1
120.4
93.5
143.3
120.2
153.5
134.6
159.3
143.5
91.4
70.3
117.3
90.5
140.8
116.8
151.6
131.5
157.7
140.8
89.2
69.0
114.7
88.1
138.7
113.9
149.9
128.9
156.3
138.4
87.3
68.0
112.5
86.1
136.8
111.6
148.3
126.6
155.0
136.4

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

26

Capacity
(MBtuh)
1 Row
2 Row
15.1
20.6
18.3
27.0
20.4
31.4
21.2
33.1
21.6
34.0
17.4
23.9
22.1
34.2
25.4
42.6
26.8
46.1
27.5
48.1
19.3
25.4
25.4
38.4
30.1
50.1
32.0
55.3
33.1
58.4
20.5
26.4
27.9
41.2
33.7
55.6
36.2
62.4
37.6
66.4
21.4
27.0
29.8
43.2
36.7
59.8
39.7
68.1
41.4
73.0
22.1
27.4
31.4
44.8
39.2
63.2
42.7
72.7
44.6
78.5
22.7
27.8
32.7
46.0
41.3
66.1
45.2
76.7
47.5
83.2
23.2
28.0
33.8
46.9
43.2
68.5
47.5
80.1
50.0
87.3

HOT WATER COIL PERFORMANCE


UNIT 35D SIZE 14

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
3 Row
4 Row

400

0.05

0.06

700

0.13

0.17

1000

0.24

0.31

1300

0.38

0.5

1600

0.54

0.72

1900

0.74

0.97

2200

0.96

1.26

2500

1.2

1.59

WATER FLOW
Water PD
Rate
(ft)
(gpm)
3 Row
4 Row
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.6
0.4
3.0
1.3
0.8
4.0
2.1
1.3
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.6
0.4
3.0
1.3
0.8
4.0
2.1
1.3
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.6
0.4
3.0
1.3
0.8
4.0
2.1
1.3
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.3
0.8
4.0
2.2
1.3
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.3
0.8
4.0
2.2
1.3
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.3
0.8
4.0
2.2
1.3
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.3
0.8
4.0
2.2
1.3
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.3
0.8
4.0
2.2
1.3

LAT
(F)
3 Row
109.0
128.7
142.0
147.0
149.5
89.8
107.9
123.4
130.0
133.6
80.6
96.1
111.3
118.4
122.5
75.2
88.6
102.9
110.1
114.4
71.6
83.4
96.7
103.8
108.1
69.2
79.5
92.0
98.8
103.1
67.3
76.6
88.2
94.8
99.0
65.9
74.3
85.1
91.5
95.6

4 Row
112.8
136.0
151.3
156.7
159.4
91.6
112.9
131.7
139.6
143.9
81.6
99.6
118.2
127.1
132.2
75.8
91.1
108.6
117.7
123.2
72.1
85.3
101.5
110.5
116.1
69.5
81.1
96.1
104.8
110.3
67.6
77.9
91.8
100.1
105.6
66.1
75.4
88.3
96.3
101.6

PERFORMANCE
LWT
(F)
3 Row
4 Row
86.7
80.1
116.3
110.0
142.4
138.4
153.5
150.7
159.6
157.4
74.7
69.3
100.0
92.5
128.3
122.0
142.2
137.4
150.3
146.4
69.6
65.1
91.2
83.7
119.2
111.8
134.3
128.1
143.5
138.3
66.8
62.9
85.7
78.6
112.7
104.7
128.4
121.3
138.3
132.1
65.1
61.6
82.0
75.2
107.9
99.6
123.8
116.1
134.1
127.2
63.9
60.8
79.3
72.9
104.1
95.7
120.1
111.9
130.6
123.2
63.0
60.2
77.2
71.1
101.1
92.6
117.0
108.5
127.7
119.9
62.3
59.7
75.6
69.8
98.6
90.2
114.3
105.7
125.2
117.1

Capacity
(MBtuh)
3 Row
4 Row
23.3
25.0
31.8
35.0
37.6
41.6
39.7
43.9
40.8
45.1
26.3
27.7
40.0
43.8
51.7
58.0
56.7
64.0
59.4
67.2
27.6
28.7
44.4
48.1
60.8
68.2
68.5
77.9
72.9
83.4
28.3
29.3
47.1
50.7
67.3
75.3
77.4
88.1
83.4
95.7
28.7
29.6
49.0
52.4
72.1
80.4
84.3
95.9
91.8
105.5
29.0
29.8
50.4
53.6
75.9
84.3
89.9
102.1
98.7
113.5
29.3
30.0
51.4
54.4
78.9
87.4
94.6
107.2
104.6
120.2
29.4
30.1
52.2
55.1
81.4
89.8
98.5
111.4
109.6
125.8

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

27

Performance data (cont)


HOT WATER COIL PERFORMANCE (cont)
UNIT 35D SIZE 16

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
1 Row
2 Row

550

0.02

0.04

900

0.06

0.11

1250

0.10

0.19

1600

0.15

0.29

1950

0.22

0.42

2300

0.29

0.56

2650

0.38

0.72

3000

0.47

0.89

WATER FLOW
Water PD
Rate
(ft)
(gpm)
1 Row
2 Row
0.5
0.4
0.1
1.0
1.4
0.4
2.0
4.6
1.4
3.0
9.4
2.8
4.0
15.6
4.6
0.5
0.4
0.1
1.0
1.4
0.4
2.0
4.6
1.4
3.0
9.4
2.8
4.0
15.7
4.6
0.5
0.4
0.1
1.0
1.4
0.4
2.0
4.6
1.4
3.0
9.4
2.8
4.0
15.7
4.6
0.5
0.4
0.1
1.0
1.4
0.4
2.0
4.7
1.4
3.0
9.5
2.8
4.0
15.7
4.7
0.5
0.4
0.1
1.0
1.4
0.4
2.0
4.7
1.4
3.0
9.5
2.8
4.0
15.8
4.7
0.5
0.4
0.1
1.0
1.4
0.4
2.0
4.7
1.4
3.0
9.5
2.9
4.0
15.8
4.7
0.5
0.4
0.1
1.0
1.4
0.4
2.0
4.7
1.4
3.0
9.5
2.9
4.0
15.8
4.7
0.5
0.4
0.1
1.0
1.4
0.4
2.0
4.7
1.4
3.0
9.5
2.9
4.0
15.8
4.7

LAT
(F)
1 Row
84.2
91.5
96.5
98.5
99.6
75.1
81.5
86.2
88.1
89.1
70.7
76.5
81.0
82.9
84.0
67.9
73.2
77.5
79.4
80.4
66.0
70.8
74.9
76.8
77.8
64.6
69.0
72.9
74.7
75.7
63.5
67.6
71.3
73.1
74.1
62.6
66.5
70.0
71.7
72.7

2 Row
94.4
109.7
121.0
125.6
128.0
81.6
95.0
106.6
111.7
114.6
75.0
86.5
97.6
102.8
105.8
71.0
81.1
91.4
96.5
99.6
68.4
77.3
86.9
91.8
94.8
66.5
74.4
83.4
88.1
91.1
65.1
72.2
80.6
85.1
88.0
63.9
70.5
78.3
82.7
85.5

PERFORMANCE
LWT
(F)
1 Row
2 Row
110.7
86.4
136.6
115.0
155.3
140.8
162.8
152.1
166.8
158.3
101.7
76.7
128.5
102.3
149.7
129.9
158.6
143.3
163.4
151.1
95.1
71.9
122.0
94.8
144.9
122.5
154.9
137.0
160.4
145.7
90.5
69.1
117.2
89.9
141.1
117.1
151.9
132.2
158.0
141.5
87.2
67.2
113.4
86.3
138.1
112.9
149.5
128.3
156.0
138.1
84.7
65.8
110.3
83.6
135.5
109.6
147.4
125.2
154.2
135.2
82.7
64.8
107.8
81.5
133.2
106.8
145.5
122.5
152.7
132.8
81.0
64.0
105.6
79.8
131.3
104.5
143.9
120.2
151.3
130.6

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

28

Capacity
(MBtuh)
1 Row
2 Row
17.3
23.4
21.7
32.5
24.7
39.2
25.8
41.9
26.5
43.4
19.6
25.8
25.8
38.8
30.3
50.1
32.2
55.1
33.2
57.9
21.2
27.0
29.0
42.6
35.1
57.5
37.7
64.5
39.1
68.6
22.4
27.7
31.4
45.1
38.9
62.9
42.1
71.8
44.0
77.0
23.2
28.2
33.3
46.9
41.9
67.1
45.8
77.5
48.0
83.9
23.8
28.5
34.8
48.2
44.5
70.4
49.0
82.3
51.5
89.6
24.3
28.8
36.1
49.3
46.8
73.2
51.7
86.3
54.6
94.5
24.8
29.0
37.2
50.1
48.7
75.5
54.1
89.7
57.3
98.7

HOT WATER COIL PERFORMANCE


UNIT 35D SIZE 16

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
3 Row
4 Row

550

0.07

0.09

900

0.16

0.21

1250

0.28

0.37

1600

0.43

0.57

1950

0.61

0.81

2300

0.82

1.09

2650

1.06

1.4

3000

1.32

1.74

WATER FLOW
Water PD
Rate
(ft)
(gpm)
3 Row
4 Row
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.4
0.8
4.0
2.3
1.4
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.4
0.8
4.0
2.3
1.4
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.4
0.8
4.0
2.3
1.4
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.4
0.9
4.0
2.3
1.4
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.4
0.9
4.0
2.3
1.4
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.4
0.9
4.0
2.3
1.4
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.4
0.9
4.0
2.3
1.4
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.7
0.4
3.0
1.4
0.9
4.0
2.3
1.4

LAT
(F)
3 Row
98.7
119.0
134.4
140.5
143.7
83.8
101.1
117.4
124.7
128.8
76.4
90.9
106.3
114.0
118.4
72.0
84.3
98.6
106.2
110.8
69.1
79.8
93.0
100.3
104.8
67.0
76.5
88.6
95.6
100.1
65.5
73.9
85.1
91.8
96.2
64.3
71.9
82.3
88.7
92.9

4 Row
101.1
125.0
143.4
150.3
153.9
84.9
104.9
124.8
133.8
138.8
77.0
93.5
112.3
121.9
127.5
72.4
86.2
103.5
113.0
118.9
69.4
81.2
97.0
106.2
112.1
67.2
77.6
92.0
100.8
106.6
65.6
74.9
88.1
96.4
102.1
64.4
72.7
84.9
92.8
98.3

PERFORMANCE
LWT
(F)
3 Row
4 Row
76.3
70.5
104.0
96.8
132.8
127.5
146.1
142.3
153.7
150.6
68.2
63.9
90.4
82.9
119.4
112.2
134.8
129.0
144.1
139.3
64.7
61.2
83.1
76.1
110.7
102.7
126.9
119.8
137.2
131.1
62.8
59.9
78.6
72.1
104.6
96.2
121.1
113.2
131.8
124.8
61.5
59.0
75.5
69.5
100.1
91.6
116.5
108.1
127.5
119.9
60.7
58.5
73.3
67.7
96.6
88.1
112.8
104.1
124.0
115.9
60.1
58.1
71.6
66.4
93.7
85.4
109.7
100.9
121.1
112.6
59.7
57.8
70.3
65.3
91.4
83.2
107.2
98.3
118.5
109.8

Capacity
(MBtuh)
3 Row
4 Row
25.9
27.4
38.0
41.6
47.2
52.5
50.8
56.6
52.7
58.7
28.0
29.0
44.8
48.5
60.6
67.8
67.7
76.6
71.7
81.4
28.8
29.7
48.5
51.9
69.3
77.3
79.6
90.3
85.6
97.9
29.3
30.0
50.7
53.9
75.4
83.8
88.4
100.2
96.3
110.3
29.6
30.2
52.2
55.2
79.9
88.4
95.3
107.8
104.9
120.2
29.8
30.4
53.4
56.1
83.4
91.9
100.8
113.8
112.0
128.2
30.0
30.5
54.2
56.8
86.3
94.6
105.4
118.6
117.9
134.8
30.2
30.6
54.9
57.3
88.6
96.8
109.2
122.6
123.0
140.3

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

29

Performance data (cont)


HOT WATER COIL PERFORMANCE (cont)
UNIT 35D SIZE 18

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
1 Row
2 Row

500

0.01

0.03

1000

0.05

0.09

1500

0.10

0.18

2000

0.16

0.30

2500

0.24

0.45

3000

0.33

0.62

3500

0.43

0.82

4000

0.55

1.04

WATER FLOW
Water PD
Rate
(ft)
(gpm)
1 Row
2 Row
0.5
0.5
0.1
1.0
1.6
0.5
2.0
5.3
1.6
3.0
10.7
3.2
4.0
17.8
5.2
0.5
0.5
0.1
1.0
1.6
0.5
2.0
5.3
1.6
3.0
10.8
3.2
4.0
17.9
5.3
0.5
0.5
0.1
1.0
1.6
0.5
2.0
5.3
1.6
3.0
10.8
3.2
4.0
18.0
5.3
0.5
0.5
0.1
1.0
1.6
0.5
2.0
5.4
1.6
3.0
10.9
3.3
4.0
18.1
5.4
0.5
0.5
0.1
1.0
1.6
0.5
2.0
5.4
1.6
3.0
10.9
3.3
4.0
18.1
5.4
0.5
0.5
0.1
1.0
1.6
0.5
2.0
5.4
1.6
3.0
10.9
3.3
4.0
18.1
5.4
0.5
0.5
0.1
1.0
1.6
0.5
2.0
5.4
1.7
3.0
11.0
3.3
4.0
18.2
5.4
0.5
0.5
0.1
1.0
1.7
0.5
2.0
5.4
1.7
3.0
11.0
3.3
4.0
18.2
5.4

LAT
(F)
1 Row
89.2
98.1
104.0
106.2
107.5
74.9
81.8
87.0
89.1
90.3
69.5
75.5
80.5
82.6
83.8
66.4
71.8
76.4
78.5
79.7
64.5
69.2
73.6
75.6
76.7
63.1
67.4
71.5
73.4
74.5
62.0
66.0
69.8
71.7
72.8
61.2
64.9
68.5
70.3
71.3

2 Row
99.5
116.3
128.1
132.7
135.1
80.3
94.5
107.1
112.8
115.9
72.6
84.1
95.8
101.6
104.9
68.5
78.1
88.7
94.2
97.6
65.9
74.1
83.8
89.0
92.3
64.2
71.3
80.1
85.1
88.2
62.9
69.2
77.3
82.0
85.0
62.0
67.6
75.1
79.5
82.4

PERFORMANCE
LWT
(F)
1 Row
2 Row
106.1
84.0
133.5
113.8
153.6
140.5
161.6
152.0
165.8
158.4
94.2
70.5
122.1
94.8
145.5
123.7
155.4
138.4
160.9
147.1
86.1
65.7
113.4
85.7
138.7
113.8
150.2
129.7
156.7
139.6
81.3
63.2
107.5
80.4
133.8
107.2
146.2
123.5
153.4
134.0
77.9
61.8
103.1
76.9
129.9
102.4
143.0
118.8
150.7
129.7
75.5
60.8
99.7
74.4
126.7
98.7
140.3
115.0
148.4
126.2
73.7
60.1
97.0
72.5
124.0
95.7
138.0
112.0
146.4
123.2
72.2
59.6
94.8
71.0
121.7
93.4
136.0
109.4
144.7
120.8

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

30

Capacity
(MBtuh)
1 Row
2 Row
18.5
24.0
23.3
33.1
26.4
39.5
27.7
41.9
28.3
43.2
21.5
27.4
28.9
42.6
34.5
56.3
36.8
62.4
38.1
65.8
23.5
28.6
33.3
47.2
41.3
66.2
44.7
75.4
46.7
80.9
24.7
29.2
36.2
49.8
46.2
72.8
50.7
84.8
53.3
92.0
25.5
29.6
38.4
51.6
50.1
77.6
55.6
91.8
58.7
0.7
26.1
29.8
40.1
52.8
53.3
81.3
59.6
97.4
63.2
0.7
26.6
30.0
41.5
53.8
56.0
84.3
63.0
0.0
67.1
0.5
26.9
30.1
42.6
54.5
58.3
86.6
66.0
0.9
70.6
0.5

HOT WATER COIL PERFORMANCE


UNIT 35D SIZE 18

Rate
(cfm)

AIRFLOW
Air PD*
(in. wg)
3 Row
4 Row

500

0.04

0.05

1000

0.13

0.17

1500

0.27

0.36

2000

0.45

0.59

2500

0.66

0.88

3000

0.92

1.21

3500

1.21

1.59

4000

1.53

2.02

WATER FLOW
Water PD
Rate
(ft)
(gpm)
3 Row
4 Row
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.8
0.5
3.0
1.6
0.9
4.0
2.6
1.6
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.8
0.5
3.0
1.6
1.0
4.0
2.6
1.6
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.8
0.5
3.0
1.6
1.0
4.0
2.6
1.6
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.8
0.5
3.0
1.6
1.0
4.0
2.7
1.6
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.8
0.5
3.0
1.6
1.0
4.0
2.7
1.6
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.8
0.5
3.0
1.6
1.0
4.0
2.7
1.6
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.8
0.5
3.0
1.6
1.0
4.0
2.7
1.6
0.5
0.0
0.0
1.0
0.2
0.1
2.0
0.8
0.5
3.0
1.7
1.0
4.0
2.7
1.6

LAT
(F)
3 Row
104.1
126.3
141.9
147.7
150.7
82.0
99.9
117.5
125.5
130.0
73.5
87.5
103.6
112.0
116.9
69.0
80.4
94.7
102.8
107.8
66.3
75.8
88.6
96.2
101.2
64.4
72.6
84.1
91.3
96.0
63.1
70.3
80.7
87.4
91.9
62.1
68.5
78.0
84.3
88.6

4 Row
106.6
132.7
150.8
157.1
160.2
82.7
103.2
124.5
134.3
139.8
73.8
89.3
108.8
119.2
125.5
69.2
81.6
98.6
108.7
115.2
66.4
76.6
91.6
101.1
107.5
64.5
73.2
86.5
95.4
101.5
63.2
70.7
82.7
90.9
96.8
62.2
68.9
79.7
87.4
92.9

PERFORMANCE
LWT
(F)
3 Row
4 Row
74.0
68.5
103.0
96.1
133.1
128.2
146.6
143.2
154.2
151.6
63.4
60.1
83.0
76.0
112.5
104.9
129.2
122.9
139.5
134.2
60.3
58.0
74.8
68.7
101.2
92.9
118.5
110.7
129.8
122.9
58.9
57.1
70.4
65.2
94.2
85.8
111.2
102.6
122.9
115.0
58.1
56.7
67.7
63.2
89.3
81.8
105.8
96.9
117.7
109.2
57.6
56.4
65.9
61.9
85.7
77.8
101.7
92.7
113.5
104.6
57.2
56.2
64.6
60.9
83.0
75.4
98.4
89.4
110.2
101.0
57.0
56.0
63.7
60.3
80.8
73.5
95.7
86.8
107.4
98.1

Capacity
(MBtuh)
3 Row
4 Row
26.5
27.9
38.5
42.0
46.9
51.8
50.1
55.1
51.7
56.8
29.1
30.0
48.5
52.0
67.5
75.1
76.2
85.7
81.0
91.5
29.9
30.5
52.6
55.6
78.8
87.1
92.3
104.0
100.3
114.1
30.3
30.7
54.8
57.4
85.8
94.2
103.3
116.1
114.1
130.0
30.5
30.8
56.1
58.4
90.7
98.9
111.3
124.6
124.6
141.7
30.6
30.9
57.0
59.1
94.3
102.2
117.5
130.9
132.9
150.7
30.7
31.0
57.7
59.5
97.0
104.6
122.4
135.9
139.7
157.9
30.8
31.0
58.2
59.9
99.2
106.5
126.4
139.8
145.3
163.8

*Coil only
LEGEND
LAT Leaving Air Temperature
LWT Leaving Water Temperature
PD Pressure Drop
NOTES:
1. All data is based on 180 F entering water temperature and 55 F entering air temperature at an altitude of 0 ft
above sea level.
2. See Correction Factors for Hot Water Coil Performance table, page 17, for other conditions, or use Carrier Air
Terminals computer program, available from your Carrier representative.

31

Performance data (cont)


ELECTRIC HEATER DATA

35D
UNIT SIZE

MAX AIRFLOW
(CFM)

04
05
06
07
08
09
10
12
14
16
18

200
350
500
650
800
1050
1300
1900
2500
3000
4000

HEATING
MIN AIRFLOW
(CFM)
120

75 Cfm/kW

MINIMUM kW
Single Phase
Three Phase
Voltage
208/240
277
208/240
480
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

1.0
1.0

1.0

1.0

1.0

1.0

NOTES:
1. Minimum airflow (cfm) shown is for electric heat; unit must also meet minimum cfm for cooling, as
shown in 35D Box Flow Data table, page 26.
2. Minimum kW per step is 0.5.
3. Box kW must be selected between minimum and maximum and can be achieved 1, 2, or 3 steps in
increments of 0.1 kW.
EXAMPLE: A size 10 box single phase at 277 kW with 7.5 kW with 3 steps of 2.5 kW/step has a
minimum heating cfm of 563 cfm which exceeds the cooling minimum of 227 cfm.(7.5 kW x 75
cfm/kW =563)
4. Pneumatic control units are energized in steps (stages) by pneumatic electric (PE) switches preset
by the factory and shown in table below.

Control
Type
DA
RA

PE SWITCH SETTINGS (PSI)


Steps (Stages)
1
2
6.0
4.5
10.0
11.5

3
3.0
13.0

LEGEND
DA Direct Acting
RA Reverse Acting
5. Electric heat units equipped with airflow switch require a minimum of 0.05 in. wg static pressure at
discharge end of box.

32

120

MAXIMUM kW
Single Phase
Three Phase
Voltage
208/240
277
208/240
480
2.0
2.0
3.5
3.5
5.0
5.0
6.0
6.0
7.5
7.5
10.0
10.0

12.0
12.0

16.5
18.0

24.0

28.0

36.0

35D BOX FLOW DATA

UNIT
SIZE

04
(0.083 sq ft)
05
(0.130 sq ft)
06
(0.186 sq ft)
07
(0.253 sq ft)
08
(0.331 sq ft)
09
(0.419 sq ft)
10
(0.518 sq ft)
12
(0.731 sq ft)
14
(0.943 sq ft)
16
(1.156 sq ft)
18
(1.550 sq ft)

BOX
CFM
50
100
150
200
100
175
225
350
125
250
375
500
200
325
475
600
200
400
600
800
250
525
750
1050
325
650
975
1300
475
950
1425
1900
625
1250
1875
2500
750
1500
2250
3000
1000
2000
3000
4000

MINIMUM AIRFLOW
(CFM)*
Cooling Only or
Cooling with
Cooling with
Electric Heat
Hot Water Heat
37
or
0
58
or
0
82
or
0
112
or
0
147
or
0
186
or
0
230
or
0
324
or
0
418
or
0
513
or
0
693
or
0

75
cfm/
kW

MINIMUM INLET STATIC PRESSURE (in. wg)


(UNIT AND HEAT PRESSURE DROP)
Hot Water Coil

Unit
Only

1-Row

2-Row

3-Row

4-Row

Electric
Heat

0.03
0.10
0.23
0.40
0.03
0.10
0.17
0.42
0.01
0.04
0.10
0.17
0.02
0.05
0.11
0.18
0.01
0.04
0.08
0.15
0.00
0.02
0.04
0.07
0.00
0.01
0.02
0.04
0.00
0.02
0.04
0.07
0.01
0.02
0.05
0.10
0.01
0.03
0.06
0.11
0.01
0.03
0.07
0.13

0.03
0.10
0.23
0.40
0.03
0.10
0.17
0.42
0.01
0.04
0.10
0.17
0.02
0.05
0.11
0.18
0.01
0.04
0.09
0.16
0.01
0.05
0.10
0.20
0.02
0.08
0.17
0.30
0.02
0.09
0.21
0.37
0.03
0.12
0.26
0.47
0.03
0.13
0.30
0.54
0.03
0.14
0.31
0.55

0.03
0.10
0.23
0.40
0.03
0.10
0.17
0.42
0.01
0.04
0.10
0.17
0.02
0.05
0.11
0.18
0.02
0.07
0.17
0.30
0.02
0.09
0.19
0.37
0.04
0.14
0.32
0.57
0.04
0.18
0.40
0.71
0.06
0.22
0.50
0.90
0.06
0.26
0.58
1.03
0.06
0.25
0.56
1.00

0.03
0.10
0.23
0.40
0.03
0.10
0.17
0.42
0.02
0.07
0.15
0.27
0.03
0.07
0.16
0.25
0.03
0.11
0.25
0.45
0.03
0.14
0.28
0.56
0.05
0.21
0.48
0.85
0.07
0.26
0.59
1.06
0.08
0.34
0.76
1.35
0.09
0.37
0.83
1.47
0.10
0.38
0.86
1.53

0.03
0.10
0.23
0.40
0.03
0.10
0.17
0.42
0.01
0.09
0.20
0.35
0.04
0.10
0.21
0.33
0.04
0.15
0.33
0.59
0.04
0.18
0.37
0.73
0.07
0.28
0.63
1.12
0.09
0.35
0.78
1.39
0.11
0.44
1.00
1.78
0.12
0.49
1.10
1.95
0.13
0.51
1.15
2.04

0.03
0.10
0.23
0.40
0.03
0.10
0.17
0.42
0.01
0.04
0.10
0.17
0.02
0.05
0.11
0.18
0.01
0.04
0.08
0.15
0.01
0.06
0.12
0.23
0.00
0.01
0.02
0.04
0.00
0.02
0.04
0.07
0.01
0.02
0.05
0.10
0.01
0.03
0.06
0.11
0.01
0.03
0.07
0.13

*Minimum airflow for cooling or cooling with hot water heat is the minimum flow rate controllable by the unit
volume controller; shutoff or zero is also acceptable. For Carrier CCN controls, see specific Application Data for
required minimum cfm.
Minimum inlet static pressure is the pressure drop for unit only (with wide open damper) or for unit with hot
water coil or electric heat; for example, a size 10 unit at 975 cfm has a minimum pressure drop of 0.02 in. wg;
with a 3-row coil, the unit and coil pressure drop is 0.48 in. wg. Data is based on tests conducted in accordance
with ARI Standard 880-89.
NOTES:
1. Where electric heat is added to the 35D unit, minimum cfm must be at least 75 cfm per installed kW of power.
Thus, a 4.3 kW heater on a size 10 unit requires a minimum cfm of 4.3 x 75, or 322.5 cfm.
2. Electric heat units equipped with airflow switch require a minimum of 0.05 in. wg static pressure at discharge
end of box.

33

Performance data (cont)


SOUND POWER LEVEL (dB)* (cont)
UNIT 35D SIZE 04
DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

50
100
150
200

2
38
52
60
66

3
43
56
63
69

4
45
54
59
63

1.0
5
43
52
57
61

6
41
47
50
52

7
39
44
47
49

2
39
53
61
67

3
44
57
64
69

4
47
56
61
65

2.0
5
45
54
59
63

6
44
49
53
55

Octave
7
43
48
51
53

Band
2
40
54
62
67

3
45
57
65
70

4
49
58
63
67

3.0
5
48
57
62
65

6
47
52
56
58

7
46
51
54
56

2
40
54
62
68

3
45
58
65
71

4
50
58
65
69

5
49
58
63
67

6
48
54
57
59

7
48
53
56
58

5
34
42
47
50

6
31
37
40
43

7
30
35
38
40

5
59
65
68
72

6
57
60
62
65

7
55
59
60
63

5
41
47
50
55

6
35
40
42
46

7
32
36
38
41

5
63
68
72
74

6
60
64
66
67

7
58
61
63
64

5
43
49
53
56

6
35
41
44
47

7
30
36
39
42

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

50
100
150
200

2
33
47
56
62

3
32
45
52
57

4
30
41
47
52

1.0
5
24
32
37
40

6
19
25
29
31

7
15
20
23
25

2
32
47
55
61

3
34
46
53
59

4
33
44
50
55

2.0
5
28
36
41
44

6
24
30
33
36

Octave
7
21
26
29
31

Band
2
31
46
54
60

3
35
47
55
60

4
36
47
53
58

3.0
5
32
40
44
48

6
28
34
38
40

7
27
32
35
37

2
31
45
54
60

3
36
48
55
61

4
38
48
55
59

UNIT 35D SIZE 05


DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

100
175
225
350

2
47
58
64
73

3
55
64
68
75

4
55
61
63
68

1.0
5
53
59
61
66

6
49
52
54
57

7
47
50
51
54

2
48
59
65
74

3
56
65
69
76

4
57
63
66
70

2.0
5
55
61
63
68

6
51
55
56
59

Octave
7
49
53
54
57

Band
2
49
61
66
75

3
58
66
70
77

4
60
66
68
73

3.0
5
58
64
66
71

6
55
58
60
63

7
53
56
58
60

2
50
61
67
76

3
58
67
71
78

4
61
67
70
75

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

100
175
225
350

2
41
53
59
68

3
43
52
56
63

4
40
48
51
57

1.0
5
31
37
40
45

6
24
29
31
35

7
19
23
25
28

2
41
53
58
68

3
44
53
57
64

4
43
51
54
60

2.0
5
34
40
43
48

6
28
33
35
39

Octave
7
23
27
29
33

Band
2
41
53
58
67

3
46
55
59
66

4
47
54
58
63

3.0
5
39
45
47
52

6
32
37
39
43

7
29
33
35
38

2
40
52
58
67

3
47
56
60
67

4
49
56
60
66

UNIT 35D SIZE 06


DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

125
250
375
500

2
46
61
69
75

3
56
66
71
75

4
57
62
65
68

1.0
5
54
60
63
66

6
50
54
55
57

7
48
51
53
54

2
48
62
71
77

3
59
68
73
77

4
60
65
69
71

2.0
5
57
63
67
69

6
54
57
59
61

Octave
7
52
55
57
58

Band
2
49
64
73
79

3
61
70
75
79

4
63
69
72
74

3.0
5
61
66
70
72

6
58
61
63
65

7
56
59
61
62

2
50
65
74
80

3
62
71
76
80

4
65
71
74
76

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

125
250
375
500

2
40
56
64
71

3
43
53
59
63

4
40
48
53
56

1.0
5
30
37
41
44

6
23
29
32
35

7
17
23
26
28

2
40
55
64
71

3
45
55
61
65

4
45
52
57
60

2.0
5
35
42
46
49

6
27
34
37
40

Octave
7
22
28
31
33

Band
2
40
55
64
71

3
48
58
63
68

4
49
57
61
65

3.0
5
40
47
51
53

6
32
38
42
44

7
27
33
36
39

*Sound power in dB re 10-12 Watts.


NOTE: All sound performance data is based on reverberant room sound data collected in accordance with ARI (Air Conditioning
and Refrigeration Institute) Standard 880-89.

34

2
40
55
64
71

3
49
59
65
69

4
52
59
64
67

SOUND POWER LEVEL (dB)* (cont)


UNIT 35D SIZE 07
DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

200
325
475
650

2
51
62
70
77

3
60
65
69
72

4
59
62
64
65

1.0
5
57
60
62
64

6
53
54
55
56

7
50
52
53
54

2
53
64
72
79

3
62
68
72
75

4
63
65
67
69

2.0
5
60
64
66
68

6
57
59
60
61

Octave
7
54
56
57
58

Band
2
56
66
75
81

3
65
70
74
78

4
67
69
71
73

3.0
5
64
67
70
72

6
62
63
64
65

7
59
60
61
62

2
57
68
76
83

3
67
72
76
79

4
69
72
74
75

5
66
69
72
74

6
64
66
67
68

7
61
63
64
65

5
46
50
53
56

6
37
41
45
47

7
31
36
39
42

5
66
69
71
72

6
66
67
67
68

7
62
64
64
65

5
44
50
53
56

6
35
41
45
47

7
28
35
39
41

5
66
69
71
73

6
65
67
67
68

7
61
63
64
65

5
45
51
53
56

6
36
43
46
48

7
30
37
40
43

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

200
325
475
650

2
45
56
64
72

3
46
52
57
61

4
43
47
50
53

1.0
5
32
37
40
43

6
25
29
32
35

7
19
23
26
29

2
45
56
65
72

3
49
55
60
64

4
48
52
55
58

2.0
5
38
42
45
48

6
29
34
37
40

Octave
7
24
28
31
34

Band
2
46
56
65
72

3
52
58
63
67

4
53
57
60
63

3.0
5
43
47
50
53

6
34
39
42
45

7
28
33
36
39

2
46
57
65
72

3
53
59
64
68

4
56
60
63
66

UNIT 35D SIZE 08


DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

200
400
600
800

2
46
62
71
77

3
57
62
66
68

4
58
60
61
62

1.0
5
55
58
60
61

6
53
54
54
55

7
50
51
52
53

2
49
64
74
80

3
60
66
69
71

4
62
64
65
66

2.0
5
60
62
64
65

6
58
59
59
60

Octave
7
55
56
57
57

Band
2
52
67
76
83

3
64
69
72
75

4
66
68
70
70

3.0
5
64
67
68
69

6
63
64
64
65

7
60
61
61
62

2
53
69
78
85

3
66
71
75
77

4
69
71
72
73

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

200
400
600
800

2
39
55
65
71

3
42
50
54
57

4
39
44
47
49

1.0
5
30
35
39
41

6
22
28
32
34

7
17
23
27
30

2
40
56
65
72

3
45
53
57
60

4
45
50
53
55

2.0
5
35
41
44
47

6
27
33
37
39

Octave
7
21
28
32
34

Band
2
41
57
66
73

3
49
56
61
64

4
51
56
58
60

3.0
5
41
47
50
52

6
32
38
42
44

7
26
32
36
39

2
41
57
66
73

3
51
58
63
66

4
54
59
62
64

UNIT 35D SIZE 09


DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

250
525
750
1050

2
50
65
73
80

3
55
62
66
69

4
57
60
61
63

1.0
5
55
59
60
62

6
52
54
55
56

7
49
51
52
53

2
52
68
75
83

3
59
66
69
72

4
61
64
66
67

2.0
5
59
63
64
66

6
57
59
60
60

Octave
7
54
56
57
58

Band
2
55
70
78
85

3
62
69
72
76

4
66
68
70
71

3.0
5
63
67
68
70

6
62
64
65
65

7
58
60
61
62

2
56
72
80
87

3
64
71
74
78

4
68
71
72
73

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

250
525
750
1050

2
41
57
65
73

3
41
50
54
58

4
40
45
47
50

1.0
5
31
37
40
42

6
24
30
33
36

7
18
25
28
31

2
42
58
66
74

3
45
53
57
61

4
45
50
53
55

2.0
5
36
42
45
48

6
29
35
38
41

Octave
7
22
29
33
36

Band
2
43
59
67
75

3
48
57
61
65

4
50
56
58
61

3.0
5
41
47
50
53

6
33
40
43
46

7
27
34
37
40

2
43
60
68
75

3
50
59
63
67

4
54
59
62
64

*Sound power in dB re 10-12 Watts.


NOTE: All sound performance data is based on reverberant room sound data collected in accordance with ARI (Air Conditioning
and Refrigeration Institute) Standard 880-89.

35

Performance data (cont)


SOUND POWER LEVEL (dB)* (cont)
UNIT 35D SIZE 10
DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

325
650
775
1300

2
54
68
72
82

3
56
63
65
70

4
58
61
62
64

1.0
5
55
59
60
63

6
53
55
55
57

7
49
52
52
54

2
56
71
74
85

3
60
67
68
74

4
62
65
66
68

2.0
5
60
63
64
67

6
57
59
60
61

Octave
7
54
56
57
58

Band
2
59
73
77
87

3
63
70
72
77

4
66
69
70
72

3.0
5
64
67
68
71

6
62
64
65
66

7
58
61
61
63

2
60
74
78
89

3
65
72
74
79

4
68
71
72
74

5
66
70
71
73

6
65
67
67
69

7
61
63
64
65

5
46
51
53
57

6
38
44
45
49

7
31
38
39
44

5
66
71
73
75

6
65
68
70
71

7
61
64
66
67

5
47
52
56
58

6
40
45
48
51

7
34
40
43
46

5
67
72
75
77

6
66
70
72
73

7
61
65
68
69

5
49
54
58
60

6
42
47
51
53

7
36
42
46
48

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

325
650
775
1300

2
44
59
63
75

3
43
51
53
59

4
41
46
47
51

1.0
5
32
38
39
43

6
26
32
33
37

7
20
26
27
32

2
45
61
64
76

3
46
54
56
63

4
46
51
52
56

2.0
5
37
43
44
49

6
30
36
38
42

Octave
7
24
30
32
37

Band
2
46
62
65
77

3
49
57
60
66

4
51
56
58
61

3.0
5
43
48
50
54

6
35
41
42
47

7
29
35
37
41

2
47
62
66
77

3
51
59
61
68

4
54
59
61
64

UNIT 35D SIZE 12


DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

1.0

2.0

CFM

475
950
1425
1900

3.0

Octave Band
2
58
71
79
84

3
57
65
70
73

4
59
63
65
67

5
56
61
63
65

6
54
57
58
59

7
49
53
55
56

2
61
73
81
86

3
60
68
73
77

4
63
67
69
71

5
60
65
67
69

6
58
61
63
64

7
54
57
59
60

2
63
76
83
88

3
63
72
76
80

4
66
70
73
74

5
64
69
71
73

6
63
65
67
68

7
58
62
63
65

2
64
77
84
90

3
65
73
78
82

4
68
72
75
76

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

475
950
1425
1900

2
47
61
70
76

3
44
53
58
62

4
42
47
51
53

1.0
5
34
40
43
45

6
28
34
37
39

7
21
28
31
34

2
48
63
71
77

3
47
56
61
65

4
47
52
55
58

2.0
5
39
45
48
50

6
33
38
41
44

Octave
7
26
32
36
39

Band
2
50
64
72
78

3
50
59
64
68

4
51
57
60
62

3.0
5
44
49
53
55

6
37
43
46
48

7
31
37
41
43

2
51
65
73
79

3
51
60
66
69

4
54
60
63
65

UNIT 35D SIZE 14


DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

625
1250
1875
2500

2
61
73
80
84

3
58
68
73
77

4
60
65
68
70

1.0
5
57
62
65
67

6
55
58
61
62

7
50
54
57
58

2
63
75
81
86

3
62
71
76
80

4
64
68
71
73

2.0
5
61
66
69
71

6
59
63
65
66

Octave
7
55
59
61
63

Band
2
65
77
83
88

3
65
74
79
83

4
67
72
75
77

3.0
5
65
70
73
75

6
63
67
69
71

7
59
63
65
67

2
66
78
85
90

3
66
75
81
85

4
69
74
77
79

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

625
1250
1875
2500

2
53
67
75
81

3
47
56
62
65

4
44
50
53
55

1.0
5
36
42
45
48

6
30
36
39
41

7
24
30
34
36

2
54
68
77
83

3
50
59
65
68

4
49
54
58
60

2.0
5
41
47
50
52

6
35
40
44
46

Octave
7
29
35
38
41

Band
2
55
70
78
84

3
53
62
68
71

4
54
59
62
65

3.0
5
46
52
55
57

6
39
45
48
50

7
33
39
43
46

*Sound power in dB re 10-12 Watts.


NOTE: All sound performance data is based on reverberant room sound data collected in accordance with ARI (Air Conditioning
and Refrigeration Institute) Standard 880-89.

36

2
56
71
79
85

3
55
64
69
73

4
56
62
65
67

SOUND POWER LEVEL (dB)* (cont)


UNIT 35D SIZE 16
DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

750
1500
2250
3000

2
61
72
78
83

3
59
69
75
79

4
62
67
70
72

1.0
5
58
63
67
69

6
56
60
63
65

7
51
56
59
61

2
63
73
80
84

3
62
72
78
82

4
65
70
73
76

2.0
5
62
67
70
73

6
60
65
67
69

Octave
7
55
60
63
65

Band
2
64
75
82
86

3
65
75
81
85

4
68
73
77
79

3.0
5
66
71
74
76

6
64
69
71
73

7
59
64
67
69

2
65
76
83
87

3
67
77
83
87

4
70
75
78
81

5
68
73
76
79

6
67
71
74
75

7
62
67
69
71

5
47
53
56
58

6
41
46
49
51

7
35
41
45
47

5
70
75
79
81

6
69
73
75
77

7
64
69
71
73

5
50
55
58
61

6
43
48
51
54

7
38
44
47
50

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

750
1500
2250
3000

2
48
61
68
74

3
45
55
61
65

4
44
50
53
56

1.0
5
36
42
45
47

6
30
36
39
41

7
23
29
33
35

2
49
63
70
76

3
48
58
64
68

4
48
54
57
60

2.0
5
40
46
49
52

6
34
40
43
45

Octave
7
28
34
37
40

Band
2
51
64
72
78

3
51
61
66
71

4
52
58
61
64

3.0
5
45
50
54
56

6
39
44
47
49

7
33
39
42
45

2
52
66
73
79

3
52
62
68
72

4
54
60
64
66

UNIT 35D SIZE 18


DISCHARGE SOUND
Inlet Pressure (in. wg)
0.5

CFM

1000
2000
3000
4000

2
65
76
83
87

3
63
73
79
83

4
64
69
72
75

1.0
5
60
66
69
71

6
58
62
65
66

7
53
58
61
62

2
67
78
84
89

3
66
76
82
86

4
67
72
76
78

2.0
5
64
69
73
75

6
62
66
69
71

Octave
7
57
62
65
67

Band
2
69
80
86
91

3
69
79
85
89

4
70
76
79
81

3.0
5
68
73
76
79

6
66
70
73
75

7
61
66
69
71

2
70
81
87
92

3
71
81
87
91

4
72
78
81
83

RADIATED SOUND
Inlet Pressure (in. wg)
0.5

CFM

1000
2000
3000
4000

2
53
66
74
79

3
50
60
65
70

4
46
52
56
59

1.0
5
38
44
47
59

6
33
38
41
43

7
26
32
35
38

2
55
68
76
81

3
52
62
68
72

4
50
56
60
63

2.0
5
43
48
52
54

6
37
42
45
47

Octave
7
30
36
40
42

Band
2
57
70
78
83

3
55
65
71
75

4
54
60
64
67

3.0
5
47
53
56
58

6
41
46
49
51

7
35
41
45
47

2
58
71
79
84

3
56
66
72
76

4
56
63
66
69

*Sound power in dB re 10-12 Watts.


NOTE: All sound performance data is based on reverberant room sound data collected in accordance with ARI (Air Conditioning
and Refrigeration Institute) Standard 880-89.

37

Performance data (cont)


APPLICATION NC* LEVELS
UNIT
35D
SIZE

04

05

06

07

08

09

10

12

14

16

18

CFM
50
100
150
200
100
175
225
350
125
250
375
500
200
325
475
650
200
400
600
800
250
525
750
1050
325
650
775
1300
475
950
1425
1900
625
1250
1875
2500
750
1500
2250
3000
1000
2000
3000
4000

MINIMUM
INLET
STATIC
PRESSURE
(in. wg)
0.03
0.10
0.23
0.40
0.03
0.10
0.17
0.42
0.01
0.04
0.10
0.17
0.02
0.05
0.11
0.21
0.01
0.04
0.08
0.15
0.00
0.01
0.01
0.03
0.00
0.01
0.02
0.04
0.01
0.02
0.04
0.07
0.01
0.02
0.06
0.10
0.01
0.03
0.06
0.11
0.01
0.03
0.07
0.13

MINIMUM
INLET
TOTAL
PRESSURE
(in. wg)
0.05
0.19
0.43
0.76
0.07
0.22
0.36
0.86
0.04
0.15
0.34
0.61
0.06
0.15
0.32
0.60
0.03
0.12
0.27
0.48
0.02
0.09
0.19
0.38
0.02
0.09
0.13
0.37
0.03
0.10
0.23
0.41
0.03
0.10
0.22
0.39
0.02
0.09
0.21
0.37
0.03
0.10
0.22
0.40

INLET STATIC PRESSURE (in. wg)


0.5

1.0

2.0

Discharge

Radiated

Discharge

Radiated

Discharge

Radiated

Discharge

Radiated

,20
,20
,20
25.5
,20
20.0
24.5
29.0
,20
22.0
25.0
27.5
,20
,20
23.0
25.0
,20
,20
,20
25.0
,20
,20
20.0
28.0
,20
,20
,20
29.0
,20
,20
24.5
29.0
,20
,20
24.5
28.0
,20
,20
22.5
25.5
,20
21.5
26.0
29.5

,20
,20
,20
22.0
,20
,20
20.0
29.5
,20
,20
24.5
32.5
,20
,20
24.5
33.5
,20
,20
25.0
33.5
,20
,20
25.5
35.5
,20
,20
23.0
37.5
,20
20.5
31.5
39.0
,20
28.0
38.5
46.0
,20
20.0
29.5
36.5
,20
26.5
36.5
43.5

,20
,20
20.5
26.5
,20
21.5
26.0
30.5
,20
24.5
27.5
30.0
,20
21.5
26.5
29.0
,20
,20
22.0
28.5
,20
,20
23.5
31.0
,20
,20
21.5
32.0
,20
,20
27.0
32.0
,20
20.0
26.5
30.5
,20
20.5
25.5
29.0
,20
25.0
29.5
33.0

,20
,20
,20
24.5
,20
20.0
23.5
30.5
,20
22.0
27.0
32.5
,20
21.5
25.0
34.0
,20
,20
25.5
34.0
,20
,20
27.0
36.5
,20
20.5
24.5
39.0
,20
22.5
33.0
40.5
,20
29.5
40.5
48.0
,20
23.5
32.0
39.0
,20
29.0
39.0
46.0

,20
,20
21.5
27.5
,20
23.0
28.0
32.5
,20
27.0
30.0
32.5
22.5
25.0
29.5
32.0
22.0
23.5
25.5
32.0
22.5
22.0
26.5
34.5
,20
23.0
24.5
35.0
20.0
22.5
30.0
35.0
,20
24.0
29.0
33.5
,20
24.0
29.0
32.5
21.0
28.5
33.0
36.5

,20
,20
22.5
27.5
,20
24.0
27.5
34.0
,20
26.5
31.5
35.0
22.0
27.0
30.5
34.5
20.5
25.5
28.5
35.0
,20
25.5
28.5
37.5
20.5
26.0
27.5
40.0
20.5
27.0
35.0
42.5
23.0
31.5
42.0
50.0
21.0
28.0
34.5
41.5
24.0
31.5
41.5
48.5

,20
,20
22.0
28.0
,20
24.0
29.0
33.5
,20
28.5
31.5
33.5
24.5
27.0
31.5
33.5
25.0
26.0
27.5
34.0
25.0
24.5
28.5
36.5
22.0
25.0
26.5
37.0
22.5
24.5
31.5
36.5
21.0
26.0
30.5
35.0
21.0
26.0
31.5
34.5
23.5
30.5
35.0
38.5

,20
,20
24.5
29.5
,20
26.0
30.0
36.5
21.0
29.5
34.5
38.0
25.5
30.0
34.0
37.0
24.0
29.0
32.0
35.5
23.0
29.0
32.0
38.5
23.5
29.5
31.0
41.0
23.5
20.0
36.0
43.5
26.0
32.5
43.0
51.0
23.5
30.5
36.0
43.0
26.5
33.0
43.0
50.0

*Noise criteria
NOTE: The NC values are based on ARI (Air Conditioning and Refrigeration Institute) Standard 885-90 application assumptions including:
Discharge Sound 5 ft of 1-in. lined duct with the dimensions of the units discharge opening; end reflection
assuming a 10-in. duct diameter termination; 200 cfm power division (200 cfm per diffuser at each occupant
location); and 5 ft of 8-in. diam flexible duct.
Radiated Sound Typical mineral tile ceiling, with light fixtures and return penetrations.
Room Effect A 3000 cu ft room, with the observer 10 ft from the sound source.

38

3.0

NOISE CRITERIA APPLICATION DATA

(References are to ARI Standard 885-90)


1. Plenum/ceiling cavity effect based on Type 2 Mineral Fiber Tile
(Ref: Table B-12).
2. Space (room) effect calculated on use of 3000 cu ft room and
10 ft between terminal and individual.
3. Duct attenuation and branch power division estimated from 5 ft
long lined discharge duct, of A and B cross section, where A and
B are width and height of discharge of unit (Ref: Table B-7) and
from 300 cfm/outlet (Ref: Table B-1).
4. End reflection based on 12-in. mean duct width (Ref: Table
B-11).

5. Environmental factor included in calulation (Ref: Appendix A).


6. Attenuation from 5 ft of 8-in. diam flex duct is included. Regeneration at outlet is not included.
These assumptions result in a room effect as follows:
OCTAVE BAND:
ROOM EFFECT (db)

2
6

3
7

4
8

5
9

6
10

7
11

Controls
The 35D single duct unit is offered with a wide variety of
factory-mounted controls which regulate the volume of air
delivery from the unit and respond to cooling and heating
load requirements of the conditioned space. Stand-alone
controls will fulfill the thermal requirements of a given control space. These devices are available in both pneumatic
and electronic arrangements.
Carrier VVT and PIC are communicating controls which
are integrated with the building system. The PIC controls
are compatible with the CCN.
The control offerings are identified as follows:
35DA Analog Electronic
35DC PIC Direct Digital Electronic

35DP Pneumatic
35DV VVT Electronic
Each control approach offers a variety of operating functions; combinations of control functions are identified by a
control package number. The tables on page 41 list the
basic function arrangements for each of the basic control
offerings.
Because of the variety of functions available, circuit diagrams, operating sequences, and function descriptions are
contained in separate Application Data publications. Refer
to the specific control publication for details.

39

Controls (cont)
35D CONTROL SEQUENCE IDENTIFICATION
35DA ANALOG CONTROLS (HOFFMAN)
1100 Cooling Only, Direct Acting
1101 Cooling Only, Damper Override
1102 Cooling Only, With Cooling Offset
1103 Cooling/Heating With Auto Changeover
1104 Cooling With 3-Stage Electric Heat
1105 Cooling With On/Off Hot Water Heat
1106 Cooling With 3-Stage Electric Heat and Offset
1107 Cooling With On/Off Hot Water Heat and Offset
1108 Cooling With 3-Stage Electric Heat and Dual Minimum Cfm
1109 Cooling With On/Off Hot Water Heat and Dual Minimum Cfm
1110 Cooling With 3-Stage Electric Heat, Dual Minimum Cfm and Offset
1111 Cooling With On/Off Hot Water Heat, Dual Minimum Cfm and Offset
1112 Cooling With 3-Stage Electric Heat, Offset and Damper Override
1113 Cooling With On/Off Hot Water Heat, Offset and Damper Override
1114 Cooling With 3-Stage Electric Heat and Damper Override
1115 Cooling With On/Off Hot Water Heat and Damper Override
1116 Cooling With 3-Stage Electric Heat, Dual Minimum Cfm and Damper Override
1117 Cooling With On/Off Hot Water Heat, Dual Minimum Cfm and Damper Override
1118 Cooling With Time Proportioning Hot Water Heat
1119 Cooling With Time Proportioning Hot Water Heat and Offset
1120 Cooling With Time Proportioning Hot Water Heat and Dual Minimum Cfm
1121 Cooling With Time Proportioning Hot Water Heat, Dual Minimum Cfm and Offset
1122 Cooling With Time Proportioning Hot Water Heat and Damper Override
1123 Cooling With 6 to 9 vdc Output Hot Water Heat
1124 Cooling With 6 to 9 vdc Output Hot Water Heat and Offset
1125 Cooling With 6 to 9 vdc Output Hot Water Heat and Dual Minimum Cfm
1126 Cooling With 6 to 9 vdc Output Hot Water Heat, Dual Minimum Cfm and Offset
1127 Cooling With 6 to 9 vdc Output Hot Water, Dual Minimum Cfm, Offset and Damper Override
35DC PIC (PRODUCT INTEGRATED CONTROLS) FOR USE ON CCN (CARRIER COMFORT NETWORK)
4100, 4110* Cooling Only
4101, 4111* Cooling With 3-Stage Electric Heat
4102, 4112* Cooling With On/Off Hot Water Heat
4103, 4113* Cooling With Proportional Hot Water Heat
4110 Cooling Only
4111 Cooling With 3-Stage Electric Heat
4112 Cooling With On/Off Hot Water Heat
4113 Cooling With Proportional Hot Water Heat
35DP PNEUMATIC CONTROLS (KREUTER)
6100 DA, NC VAV Pressure Dependent Cooling With Sequenced Heat
6101 RA, NO VAV Pressure Dependent Cooling With Sequenced Heat
6102 DA, NO VAV Pressure Independent Cooling With Sequenced Heat
6103 DA, NC VAV Pressure Independent Cooling With Sequenced Heat
6104 RA, NC VAV Pressure Independent Cooling With Sequenced Heat
6105 RA, NO VAV Pressure Independent Cooling With Sequenced Heat
6106 Constant Volume Cooling Only, NO Damper
6107 Constant Volume Cooling Only, NC Damper
35DV VVT (VARIABLE VOLUME AND TEMPERATURE) CONTROLS
8100 VAV Pressure Dependent Cooling Only
8101 VAV Pressure Dependent Cooling With 2-Stage Electric Reheat
8102 VAV Pressure Dependent Cooling With On/Off Hot Water Reheat
8103 VAV Pressure Independent Cooling Only: 0.5 in. wg Transducer
8104 VAV Pressure Independent Cooling With 2-Stage Electric Heat; 0.5 in. wg Transducer
8105 VAV Pressure Independent Cooling With On/Off Hot Water Heat; 0.5 in. wg Transducer
8106 VAV Pressure Independent Cooling Only: 2.0 in. wg Transducer
8107 VAV Pressure Independent Cooling With 2-Stage Electric Heat; 2.0 in. wg Transducer
8108 VAV Pressure Independent Cooling With On/Off Hot Water Heat; 2.0 in. wg Transducer
8109 VAV Pressure Dependent Unit Control Zone (Monitor)
8110 Bypass Controller With 2.0 in. wg Transducer
*Sequences 4110 4113 include set point adjustment capability on space temperature sensor.

LEGEND
DA
NC
NO
RA
VAV

40

Direct Acting
Normally Closed
Normally Open
Reverse Acting
Variable Air Volume

35DC PIC (PRODUCT INTEGRATED CONTROL)

35DA ANALOG ELECTRONIC CONTROL

35DV VVT ELECTRONIC CONTROL

35DP PNEUMATIC CONTROL

41

Guide specifications
Single Duct VAV Terminal Unit
HVAC Guide Specifications
Size Range: 200 to 4000 Nominal Cfm
Carrier Model Number:
35DA (Analog Electronic Control)
35DC (Product Integrated Controls [PIC])
35DN (No Control)
35DP (Pneumatic Control)
35DV (Variable Volume and Temperature Control [VVT])
Part 1 General
1.01 SYSTEM DESCRIPTION
Variable air volume control box for installation in a
ceiling that permits access to the unit. Manufacturer
shall supply unit(s) of the design, number, size and
performance as shown on equipment drawings and
schedules. Unit(s) are for use in conjunction with air
distribution manifolds, distribution ductwork and ceiling mounted diffusers.
1.02 QUALITY ASSURANCE
A. Insulation shall meet NFPA-90A requirements for
flame spread and smoke generation and UL-181 requirements for anti-erosion, corrosion and fungus
properties.
B. Hot water coils, when specified, shall be tested for
leakage at 250 psig with the coil submerged in water.
C. Electric heating coils, when specified shall be UL or
ETL listed and designed to comply with UL Standard
1096.
D. Sound power levels shall be ARI certified in accordance with the requirements of ARI-880-89.
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturers
recommendations.
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, externally powered, variable air
volume control terminal. Unit shall be complete with
a damper assembly, flow sensor, externally mounted
volume controller, collars for duct connection and all
required features. Control box shall be clearly marked
with an identification label that lists such information
as nominal cfm, maximum and minimum factoryset airflow limits, coil type and coil hand, where
applicable.
B. Unit Cabinet:
1. Constructed of 22-gage galvanized steel with round,
rectangular or flat oval inlet collar and rectangular
discharge with slip and drive connection.
2. Insulated with 12-in. thick, 1.5-lb. equivalent density mat-faced insulation.

42

C. Damper Assembly:
The damper assembly shall be composed of multiple
16-gage damper blades located in a 16-gage damper
frame, utilizing steel damper linkages and mounted
on nylon self lubricating blade bearings. Dampers shall
have an open cell foam damper seal affixed to the
blade, providing a maximum of 2% of the maximum
rated capacity with dampers closed with an inlet pressure of 3 in. wg. Damper assembly will consist of
either 4 or 6 blades with a 90 degree travel, and shall
provide uniform air delivery over the entire face of
the unit at all flows.
D. Controls:
Units shall have pressure-independent pneumatic, electronic, or communicating controls, as specified, capable of maintaining required airflow setpoints 6 5%
of the units capacity at any inlet pressure up to 6 in.
wg. The controllers shall be capable of resetting between factory or field-set maximum and minimum
(.350 fpm inlet duct velocity) set points to satisfy the
room thermostat demand.
The unit shall be equipped with a double ended amplified linear averaging flow probe located horizontally across the inlet. The probe shall have capped
ports at the end opposite to the controller connection for flow verification in the field against provided
flow/pressure charts. The sensor will provide a differential pressure signal amplified to equal 3 times the
velocity pressure with an accuracy of 6 10% throughout the range of 350 to 2600 fpm inlet duct velocity.
E. Accessories:
1. Hot Water Heating Coil:
Coil shall be mounted in a galvanized steel casing
and factory mounted on the base unit as shown
on the equipment drawings. Coils shall have:
a. Aluminum fins (10 ft/in.) bonded to the
12-in. OD copper tubes by mechanical
expansion.
b. Up to 4 rows as shown on equipment drawings or designed on the equipment schedule.
There shall be one circuit/row.
c. Right or left-hand fittings with sweat connection sizes as indicated on equipment
drawings.
2. Electric Heating Coil:
Heater shall be horizontally mounted slip-in unit,
mounted into a galvanized steel plenum formed as
an integral part of a 36-in. long damper unit, lined
with 12-in. thick, 1.5-lb. equivalent dual density of
mat-faced insulation, and shall be factory installed
on the right or left side as required.
Units with heaters installed shall be identified on
the equipment drawings. Heaters shall be:
a. Designed for the capacity, electrical characteristics and steps of control as shown on the
equipment schedule.

b.

Open coil construction with 80% nickel, 20%


chronium wire supported in free-floating
ceramic bushings. Coil frame shall be constructed of corrosion resistant steel.
c. Factory wired and include all limit switches.
3. Octopus Attenuator
Octopus attenuator shall be 36 in. long and factory installed on the non-attenuated base unit that
is not equipped with electric heat. Refer to equipment schedule for effected units. The octopus shall
be:
a. Equipped with 6-in. or 8-in. diameter collars
in the quantity and configuration specified on
the equipment drawings. Each collar shall include a locking butterfly balancing damper.

b.

Insulated with 12-in thick, 1.5-lb. equivalent


dual density or mat-faced insulation.
4. Sound Attenuator:
An attenuated unit is available either as an integral unit (36 in. long) or as an add-on option. When
electric heat is required, the attenuator will be used.
5. Foil-Faced Insulation Lining
Factory installed foil-faced lining shall be a tripleply laminate made with fiberglass scrim, aluminized polyester face and aluminum foil backing,
bonded to 12-in. insulation, and shall be UL listed.
All edges of the insulation shall be fully enclosed.

43

Carrier Corporation Syracuse, New York 13221

5-92

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3
Tab 6a

Page 44

Catalog No. 523-518

Printed in U.S.A.

201

Form 35D-1PD
Replaces: New