Presenters
Frankie Victor, EngL, BCQ
Jun H. Kim, BASc, EIT
GHL CONSULTANTS LTD
Building Codes and Fire Science
ToknowandunderstandtheCode.
Toknowandunderstandthefiresciencebehindthe
Code.
ToassistincorrectapplicationoftheCode.
Todevelopnewsolutionsbasedonfirescienceto
enablecreativesafebuildings.
Tounderstandtheneedsoftheclientandofthe
AuthoritiesandFirstResponders.
GHLs Role
7Engineers,4withMastersdegreesinfirescience
1Architect
4CertifiedProfessionals(CPs)
2formerBuildingOfficials
4BuildingCodeQualified(BCQ)
GHL Team
CPCommittee(DavidGraham)
APEGBCBuildingCodeCommittee(JohnBuscemi)
BCBuildingCodeAppealBoard(FrankieVictor)
CityofVancouverBuildingBylawAppealBoard
(TeddyLai)
BCBuildingCodeInterpretationCommittee(TeddyLai)
Codecompliancenorisk.
Codecompliance=risksat
acceptablelevel.
Failurewilloccur:
Limitittoanacceptablelevel.
Buildingsaresubjecttorisks:
Maximumtraveldistance
Exitsatfullcapacity
Minimumceilingheight(2100mm)
Minimumaccesstoexitwidth(1100mmcorridors)
6m deadendsinpubliccorridors
TheBuildingCodesbuildinghas:
Highhazardindustrial 5m=25m
Sprinkler* +15m= 45m
Servicespace +20m =50m
Openairstoragegarage +30m =60m
Perimeterexits60mapart unlimitedtraveldistance
Publiccorridor** traveldistancex2
Mallcorridor +75m =105m(50%ofoccupants)
Base=unsprinklered floorarea,30mtraveldistance
Geometry dimensionalandspatialfeaturesofthespace.
Demographics characteristicsofoccupants;mobility.
Psychology potentialoccupantbehaviourinfires.
Tenability visibility,breathability,toxicity,heat.
ThefollowingpresentationfocusesprimarilyonGeometry,
whichcanbeexpressedintermsoftime.
Elements of Evacuation
10
Traveldistancetranslatestotimetowalkacrosstheroom.
Allelsebeingequal,increasingtraveldistancesimply
increasestimetoevacuate.
11
12
Exitcapacity(width)translatestotimetopassthrougha
corridor,doorordownastair.
13
1828mm
914mm
1828mm
914mm
14
4 x 914mm = 3656mm
2 x 1828mm = 3656mm
Increasingnumberofexitswithoutincreasedaggregate
widthhasnoimpact.
15
Occupantloaddeterminesqueuingtime.
Higheroccupantload/longerqueue/increasedtime.
16
Sameexitcapacity.Samenumberofexits.
Higheroccupantload=increasedtimetoegress.
1.2m2/person
120 persons
1.2m2/person
180 persons
17
Sameexitcapacity.Sameoccupantload.
Smallerfloorarea=shortertraveldistance.
Equaltimetoegress.
10m x 10m
60 persons
15m x 15m
60 persons
18
TheBuildingCodesfactorsforexitcapacityareasimplified
methodofdeterminingtimetopassthroughacorridor,
doorordownastair.
19
4 x 914mm = 3656mm
2 x 1828mm = 3656mm
Effective width
= 4 x (914mm-300mm)
= 3536mm
Effective width
= 2 x (1828mm-300mm)
= 3596mm
Reducedtotaleffectivewidth=increasedtimetoegress.
20
Vestibulesatexits(interconnectedfloorspace).
Useofentryforticketcollecting,security,displays.
Retailantitheftequipment.
Turnstiles.
Etc.
21
Relationshipbetweenceilingheight,orvolumeofspace,
andtimetoegressiscodifiedinSentence3.4.2.5.(1):
22
Ceilingheighttranslatestotimebeforesmokedescends
toheadlevel.
23
24
Demographics
Occupantswithlocomotivedisabilityareconsideredinthe
averageoccupanttravelspeed.
25
Psychology
Truepanicismostlya
mythperstudiesand
expertopinion.
R.F.Fahy,G.Proulx.Panic
andhumanbehaviourin
fire. (2009)
Notnecessaryto
considerinmosttimed
egressanalyses.
Humanbehaviouris
predictable.and
unpredictable.
26
Behaviouruponalerttoahazarddependson
occupancy:
Nightclub unfamiliar,dark,crowded,impaired,
noisy.
Home/work familiar,senseofownership,
protectiveofothers.
School familiar,additionalpreparedness,
leadership.
Weather,gender,commitmenttoatask,aloneor
inagroup,focalpoint/leader.
Humanbehaviourcanbepredictedtoadegree:
27
Notnecessarytotryandpredictbehaviourpriorto
movementprovidedcomparisonisofthesame:
People
Space
Conditions
Psychologyisindependentoftimedegressanalysis.
28
Whatispanic?Anoverwhelmingfear,withorwithout
cause,thatproducesanirrationalresponseandmay
spreadthroughagroup.
Whendopeoplepanic? Whentheycanseenoway
outofasituation.
Whendoesitmatter? Whenitcausesactionwithout
assessmentofsafety
Whatdopeoplemeanwhentheysaypanic?
Whatdobuildingofficialsmeanwhentheysaypanic?
Realpanicinanemergencyisrare;expertsconsidereditamythsince
about1970butthemoviesandnewschannelslikeit.
Psychology - Panic
29
MarginofSafety
EvacuationTime
Premovement
Response
Recognition
Alarm
Movement
AvailableSafeEgressTime(ASET)
Detection
30
AvailableSafeEgressTime(ASET)
MarginofSafety
MovementTime
Detection/Alarm
Alertstagecanbeadjustedbydetection
(smokedetectoractivatessoonerthansprinkler)
RequiredSafeEgressTime(RSET)
31
UpperLayerHeight
Visibility
Heatflux/Temperature
Toxicity
Tenability
32
Tenability
ZoneModel:Upperlayerheight
Simplerspaces
CFDModel:Tenabilityparameters
3Dcomplexspaces
Twotypesofcomputermodelsareused
togaugetenability:
33
Whereastraightcomparisonto
BuildingCodescenariosdoesnttell
thewholestory:
Dontmeetcumulativeexit
capacityinaninterconnectedfloor
space.
Usingopenstairforegress.
Convergingegressroutes.
Tenability
34
Elements of Evacuation
Geometry dimensionalandspatialfeaturesofthespace.
Psychology potentialoccupantbehaviourinfires.
Tenability visibility,breathability,toxicity,heat.
Demographics characteristicsofoccupants;mobility.
35
Hand Calculation
Firstoccupanttoreachdoor(t1)+timetoqueueatdoor(t2)
OR
Lastoccupanttoreachdoor(t3)
Timetocommencemovementisnotconsidered;
assumedtobethesameforBuildingCodeandactualscenarios.
Timetoegressisthetimeforeither:
36
Hand Calculation
TravelDistance
Exits
Occupant Load
Assumption
BuildingCodeScenario
AlternativeSolution
45m
60m
2x914mmdoor
2x914mmdoor
2x914 6.1=300
2x914 6.1=300
Nearest person
5m fromexit
Furthestpersons
45m fromexit
Nearest person
5m fromexit
Furthestperson
60m fromexit
Example:ComparingBuildingCodeandalternativesolution
37
Hand Calculation
Building CodeScenario
5
t 1*
t2
t3
t
1.1
300
0.914 0.3
45
AlternativeSolution
4.5
1.32
1.1
5
185
41
1.1
4.5
300
0.914 0.3
1.32
60
1.1
185
55
189.5s
189.5s
*assumed5mfornearestoccupanttoanexit.Thismayvarydependingonfloorlayout.
Queuing(t2)isthelimitingfactor,hence15mextratravel
distancedoesnotcontributetoaddedevacuationtime.
38
1.
2.
3.
4.
5.
EgressviaOpenStair.
CumulativeExiting(interconnectedfloorspace).
EgressfromTwoStoreyDwellingUnit.
ConvergingEgress(Departmentstoretraveldistance).
Parkade70m TravelDistance.
Project Examples
39
Singleexitandopenegressstair.
40
Sentence3.4.2.1.(1) atleasttwoexitsrequired
Buildingdividedintotwostoreysuiteseachserved
byoneexitfromupperstorey.
Traveldistanceandexitcapacitymetbyexitstair.
Openstairprovidedsecondegressroute.
Timedegress,smokemodeltoconfirmtenability.
Additionalfeaturesincludedsmokedetectionfor
earlyalert.
41
42
Sentence3.4.3.2.(6) Exitstairsserving
interconnectedfloorspacebasedoncumulative
occupantload.
Cumulativeexitingnotmet.
Usedconveniencestairleadingtoexiton1st storey
asameansofegress.
Timedegress,smokemodeltoconfirmtenability.
Additionalfeaturesincludedsmokedetectionand
smokeexhausttokeepopenstairtenable.
43
44
Sentence3.3.4.4.(2) describesegressdoorsinmulti
leveldwellingunitsatboththeupperandlower
storeys.
Egressdoorwasnotprovidedattheupperstorey
Timedegressconfirmedincreasedegressof3seconds.
Concernwastenabilityatroutefromupperstorey.
Smokemodelconfirmedtenableconditions.
Draftstopwasnecessary.
Additionalfeaturesincludedsmokealarmsforearly
alert,emergencylightinglinkedtosmokealarm.
Firealarmannunciation bothstoreysatlower.
45
Back-of-house Corridor
Mall Corridor
46
Clause3.4.2.5.(1)(d) 50%ofoccupantsexitviamall
corridorwithtraveldistanceof105m.
Rearcorridorconvergedwithmallcorridor.
Usedmallcorridorasameansofegressfor100%of
occupants.
Timedegress,smokemodeltoconfirmtenability.
Additionalfeaturesincludepassivesmokeventingto
maintaintenability.
Codecompliantsolution=tunneloutofthebuilding.
Arepeoplewilling?
47
48
Sentence3.4.2.5.(1) prescribes45mtraveldistance.
Increasedtraveldistancefromcentreareas.
Increasedtotalexitwidth(extradoors).
Lowoccupantloadeliminatedqueuingatexits.
Timedegress.
Additionalfeaturesincludeexitsignage,increasedlight
levels.
Scenario
1.CodeMinimumusing
fulldoorcapacity
2. ProposedScenario
Numberof
Occupants
perExit
(persons)
Maximum
Travel
Distance
(m)
Timeto
Evacuate
(sec)
149
45
219
54
70
110
49
Occupancy
BC
IBC
NFPA101
Assembly
45m
76m
76m
Care
45m
76m
61m
Business/service
45m
90m
91m
Residential
45m
76m
61m
Retail
45m
76m
76m
25/45/45m
23/76/120m
30/122/unlimited
Industrial F1/F2/F3
50
BuildingCodelimits traveldistance,ceilingheight,
exitcapacity defineaspace,createascenario.
ReallifescenariosarecomparedtoBuildingCode
scenario.
Humanbehaviourispredictable/unpredictable.
Canreducedetection/alertstagebysmokedetection
(operateearlierthansprinklers).
Canbuytimebyincreasingceilingheightorexit
capacity.
Summary
51
Questions?